Vista-15P Control Panel. Agenda. Basic Panel Features Mechanics of Programming Programming Locations *56 Zone Programming *79 Output Device Mapping *80 Defining Output Functions Security Codes – Authority Levels & Special Features. Features. 32 zones maximum (any configuration) - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Vista-15P Control Panel

Vista-15P

Control Panel

Page 2: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Agenda

• Basic Panel Features• Mechanics of Programming• Programming Locations• *56 Zone Programming• *79 Output Device Mapping• *80 Defining Output Functions• Security Codes – Authority Levels & Special Features

Page 3: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Features

• 32 zones maximum (any configuration)– 6 wired zones standard

– 22 max wired expansion (4219/4229)

– 26 max wireless (5800 series)

• 8 Keyfob zones (do not count in 32 max)– but will use up points on the receiver.

• 8 Programmable outputs (4204/4229/X10)• 2 on-board voltage triggers• 15P rev3+ = 2 Symphony (AUI) Consoles

Page 4: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Features• 10 zone lists

– ZL3 = chime by zone

– ZL4 = cross zones

– ZL5 = night stay zones

– ZL9&10 = zones to send to pager

• Pager support (up to 2)• Fully downloadable• 50 event log (view via keypad or downloader)

Page 5: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Features• Unvacated auto stay • Cross zoning• Night arming• Carbon monoxide zone type• Dynamic zone type• Scheduling• Vent Zone• Automatic Periodic Test Command• SIA compliant

Page 6: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

ANSI/SIA CP-01-2000

A FALSE ALARM REDUCTION standard, calls for manufacturer’s to default control panels as follows:

•60 second exit delay•30 second entry delay plus 30 second dialer delay•Auto Stay arming enabled•Cancel verify option is enabled (displays on keypad)•Swinger suppression defaulted to 1 report per zone per armed period

Page 7: Vista-15P Control Panel

Vista-15P Mechanics of Programming

Page 8: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Mechanics of Programming

• Entering Program Mode - Use one of the following methods to enter Programming Mode:

1. Press both the [*] and [#] keys at the same time, within 50 seconds after power is applied to the Control.

2. After power-up, enter the Installer Code (4112) + 800

(If *98 was used to exit previously, method 1 above must be used to enter the program mode again)

Note: When connecting a console to a defaulted panel, the console must be set to address 16. This will be covered later.

Page 9: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Defaulting

• To default the panel you will enter:– [ * ] + 9 + 7– Upon entering programming for the first time, it is recommended

that you default the panel.• To set the panel for first time communication with Compass

Downloading Software you will enter:– [ * ] + 9 + 6

• CSID = FFFFFFFF• Primary Subscriber Account Number = FFFF

Note: If your downloader requires a call back phone number, refer to field *94 in your programming form.

Page 10: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Mechanics of Programming

* 20 Installer Code [4112]

Enter 4 digits, 0 – 9

To change the Installer’s Code you would enter Programming mode, then press *20, then the new code.

To view what is in field 20 you would enter #20, the panel will display the location contents one digit at a time.

Page 11: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Mechanics of Programming

• Exiting Program Mode:

*98 prevents re-entry into the Programming modes using the Installer Code.

*99 allows re-entry into the Programming modes using Installer Code (4112) + 800

Note: If *98 is used to exit programming mode, the system must be powered down, AC and Battery, then press * & # simultaneously within 50 seconds of power up to re-enter programming.

Page 12: Vista-15P Control Panel

Vista-15P

Programming Locations

Page 13: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Entry/Exit Programming

*34 Exit Delay

*35 Entry Delay #1

*36 Entry Delay #2

[ 60 ]

00 - 96 = 0-96 Sec. 97 = 120 Sec.

[ 30 ]

00 - 96 = 0-96 Sec. 97 = 120 Sec. 98 = 180 Sec. 99 = 240 Sec.

[ 30 ]

Same entry choices as *35

Page 14: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Communication Programming

*43 Primary Account Number

*44 Second Account Number

4 or 10 Digits [ FFFF ]

4 or 10 Digits [ FFFF ]

Enter up to 20 digits…

Enter up to 20 digits

*41 Primary Phone Number

*42 Second Phone Number

Page 15: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Communication Programming

*48 Report Format [ 7,7 ]

0 = 3+1, 4+1 Ademco L/S Stand. 6 = 4+2 Ademco Express1 = 3+1, 4+1 Radionics Stand. 7 = 4-digit Ademco Contact ID2 = 4+2 Ademco L/S Stand. 8 = 3+1, 4+1 Ademco L/S Stand.3 = 4+2 Radionics Stand. 9 = 3+1, 4+1 Radionics Expanded5 = 10-Digit Ademco Contact ID

Prim. Sec.

Note: for 10 digit Contact ID you must enter all 10 digits for the account number and 4 digit Contact ID you must enter all 4 digits for the account number.

Page 16: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

This is a Menu Mode command, not a data field, for programming IP/GSM options.

Backup Communications

*29 Menu Mode for IP/GSM Enable (rev 7+)

Enable IP/GSM?0= NO 1=YES

Enable INT IP/GSM?0 = no, not using either IP or GSM1 = yes, Using IP and/or GSM module[*] to continue

1=PROG 2=DIAG0=QUIT

Programming/Diagnostics Select1 = Prog (program the IP/GSM options)2 = Diag (enter diagnostic mode) Do not select if using an external comm device0 = Quit; returns to data field programming mode

*29 Long Range Radio Output [ 0 ] 0 = No1 = Yes

Page 17: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Internal Device Programming Prompts[ ] = scroll the options of a particular prompt∗[#] = accept the entry and move to the next prompt[A] = backspace or shift-[A] for escape[B] = scroll to next prompt or shift-[B] scroll to previous prompt[C] = answer No or shift-[C] answer Yes to prompt[D] = shift key

*29 Menu Mode Keypad Functions

Page 18: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Backup Communications

*54 Dynamic Signaling Delay

*55 Dynamic Signaling Priority

0 = No delay (Both signals sent)1-15 = delay times in 15 sec. increments1 = 15 Sec. 2 = 30 Sec. Etc.Note: if *55 is set to “0”, use min. 30 sec to avoid redundant IP report.

[ 0 ]

0 = Primary Dialer first1 = IP/GSM module first

[ 0 ]

Page 19: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

System Setup

*84 Auto Stay Arm

*85 Cross Zone Timer

*93 Reports in Armed Period Per Zone

[1] 0 = No, 1 = Yes

[0] 0 = 15 sec.

(see program sheet for complete list of options)

(Assign cross zones on zone list 4, with *81 Menu mode)

If enabled, the system will automatically change AWAY mode to STAY mode if the entry/exit door is not opened and closed within the exit delay time after the user arms in AWAY mode from a wired keypad.

[1] 0 = Unlimited Reports 1 = 1 report per 2 = 2 reports per

Page 20: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Pager Information

*160 Pager 1 Phone No.

….

….Enter up to 20 digits

Enter up to 16 digits

*161 Pager 1 Characters

The character could be composed of: • PIN number• Subscriber account number• * (enter # + 11 to send *)• # (enter # + 12 to send #)• Pause (enter # + 13 to allow a 2-second pause)

7-digit status code: XXX-YYYY

XXX = 3-digit event code:911 = Alarm811 = Trouble101 = Opening (disarm)102 = Closing (arm AWAY

YYYY = 4-digit user or zone numberThe first digit indicates the partition, followed by the 3-digit user or zone number. 0 = system, 1 = part 1

2 = part 2, 3 = part 3

Page 21: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Pager Options

*162 Pager 1 Reporting Options

0 = no report sent 1 = open/closes all users 4 = All alarms and troubles12 = Alarms/troubles for zones entered in zone list 913 = Alarms/troubles for zones entered in zone list 9 and open/close for all users

Pager 2 is set up the same way in Locations *163 -*165

[ 0 ]

Page 22: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Pager Options

*172 Pager Delay Option for Alarms [3]

0 = none1 = 1 minute2 = 2 minutes3 = 3 minutes

This delay is for ALL pagers in the system.

Page 23: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Configurable Zone Type Programming

See programming sheet for complete List of options. 1 2 3 4 5 6 7 8 9 10

*182 Configurable Zone Type 90

Enter the desired 3-digit Contact ID report codes for alarms and troubles occurring on zones assigned to this zone type.

90 Alarm ID XXXTrouble ID:XXX

*183 Zone Type 90 Report Codes

See programming sheet for complete List of options. 1 2 3 4 5 6 7 8 9 10

*184 Configurable Zone Type 91

Enter the desired 3-digit Contact ID report codes for alarms and troubles occurring on zones assigned to this zone type.

91 Alarm ID XXXTrouble ID:XXX

*185 Zone Type 91 Report Codes

Page 24: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Advanced User Interface Programming

*189 Symphony (AUI) enable

0 = disabled1 = enabled

[1] [1]AUI 1 AUI 2

Note: an external power supply may be required when using AUI consoles.

Page 25: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Keypad Options

*190 Keypad 2 Address 17

*191 – *196 Are Identical for addresses 18 – 23 respectively.

Enable Sound

[0] [0]

0 = keypad disabled1 = keypad enabled

0 = no suppression1 = suppress arm/disarm and E/E beeps2 = suppress chime beeps only3 = suppress arm/disarm, E/E, and chime beeps

NOTE: Options for keypad address 16 are set by the factory and cannot be changed. Each keypad must be assigned a unique address.

Page 26: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Keypad Options

*197 Exit Time Display Interval

*199 ECP Fail Display

[0]0 = no display1-5 = seconds between display refresh

[0]0 = 3-digit display (“1” + device address)1 = 2-digit fixed-display as “91”

Page 27: Vista-15P Control Panel

Vista-15P

ECP Addressing

Page 28: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Table of Device Addresses

All devices attached to ECP (keypad) terminals must be addressed.Depending on the device and its function the address is determined by the following:

Address Keypad Message †† Device

00 100/91 RF Receiver

01 N/A AUI 1

02 N/A AUI 2

03 103/91 Long Range Radio

04 104/91 4286 Voice Module

07

08

107/91

108/91

Zone Expanders (4219/4229)

Module 1 zones 09-16

Module 2 zones 17-24

Page 29: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Table of Device Addresses

Address Keypad Message†† Device

12

13

112/91

113/91

Relay Modules (4204)

Module 1

Module 2

16 – 23 N/A

Keypads

Keypad 1 – 8

28 N/A 5800TM module

†† Addressable devices are identified by “1” plus the device address when reporting. Enter a report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199, mentioned earlier, for ECP Fail Display options.

Page 30: Vista-15P Control Panel

Vista-15P Zone Programming*56 Menu Mode

Page 31: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming Mode

SET TO CONFIRM?0= NO 1=YES 0

Confirm?

Zn ZT RC In: L10 00 10 RF 1

Enter Zone Number01-99 = zone number00 = quit

[*] to continueNot all numbers Available.

Enter Zn Num.(00 = Quit) 10

Summary Screen[*] to continue

IN: L = Wireless, RF = SupervisionIN: AD = Expansion, AW = Aux wiredHW: RT = Hard Wire, EL = loop type

Zn ZT RC In: AD10 00 10 AW: 07

Zn ZT RC HW: RT02 00 10 EL 1

Or

Or

0 = no1= yes

Page 32: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming Mode

10 Zone TypePerimeter 03

Zone Type (ZT)00 = Not Used01 = Entry/Exit #102 = Entry/Exit #203 = Perimeter04 = Interior Follower05 = Day/Night06 = 24-Hr Silent07 = 24-Hr Audible08 = 24-Hr Aux09 = Fire10 = Interior w/Delay

12 = Monitor Zone14 = Carbon Monoxide16 = Fire w/Verify20 = Arm-Stay*21 = Arm-Away*22 = Disarm*23 = No Alarm Response24 = Silent Burglary77 = Keyswitch81 = AAV Mon. Zone90-91 = Configurable

* 5800 button-type transmitters only.

Page 33: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming Mode

02 Hardwire TypeEOL 0

Report Code (RC)01-09, 10 for 0, 11 for B, 12 for C, 13 for D, 14 for E, 15 for F. 00 to DisableExamples: 01 00 = report code 10 13 15 = report code DF

10 Report Code1st 01 2nd 00 10

Hardwire Type0=EOL; 1=NC; 2=NO; This prompt appears only for zone numbers 02-06. [*] to continue

Page 34: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming Mode

02 Response Time 1

Response Time (RT)

10 Input S/N: LA XXX-XXXX 1

Input Device type (In)2 = AW (Aux wired zone)3 = RF (supervised RF transmitter)4 = UR (unsupervised RF transmitter)5 = Button type RF transmitter (unsupervised)

0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds[*] to continueOnly for zones 02-06, zone 02 shown

10 Input TypeRF Trans 3

Serial number Entry and Loop Number EntryUsed only when enrolling wireless transmitters.a. Transmit two open/close sequences.b. Manually enter the 7-digit serial number.c. Press key [C] to copy the serial number previously

enrolled.[*] to continue

Page 35: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming ModeLoop Number Change10 Input S/N: L

A 022- 4064 ?

Enroll SummaryIf the serial/loop number combination is not a duplicate in the system, a display showing the serial number and loop number entry will appear.[*] to continue

Enter the loop number.To delete enter 0 in the loop number.[*] to continue

10 Input S/N: LA 022-4064 1

10 XMIT TO CONFIRMPRESS * TO SKIP

ConfirmNote: This prompt will only appear if the firstprompt after entering *56 was answered “YES”[*] to continue

Page 36: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*56 Zone Programming Mode

Not Confirmed[*] to continueIf the serial number transmitted does not match the serial number entered this prompt will appear.

Entd A022-4063Rcvd A022-4064

Zn ZT RC In: L10 03 10 RF 1

Summary Screen[*] to continue

Page 37: Vista-15P Control Panel

Vista-15P

Output Programming

Page 38: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Output Device Option

*177 Device Duration 1,2

(used in *80 menu mode-Device Actions 5/6)

[0] [0]

1 2

0 = 15 secs1 = 30 secs2 = 45 secs3 = 60 secs4 = 90 secs5 = 2 min6 = 2-1/2 min7 = 3 min

8 = 4 min 9 = 5 min# = 10 = 6 min# + 11 = 7 min# +12 = 8 min# + 13 = 10 min# + 14 = 12 min# + 15 = 15 min

Page 39: Vista-15P Control Panel

Vista-15P Output Device Mapping*79 Menu Mode

Page 40: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

*79 Mode is used to identify available outputs that the panel can use.

These outputs are actually programmed to activate and release in

*80 defining output functions.

Page 41: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

ENTER OUTPUT NO.00 = QUIT xx

Device Output Number01 – 08, 17, 18 relays/X-10;00 = Quit[*] to continue

XX OUTPUT TYPEDELETE 0

Output Type This prompt appears if selecting outputs 01 – 08.0 = delete1 = relay on 4204/4229 module2 = Powerline / X-10[*] to continue

If X-10 is selected, we will use “A” promptIf relay is selected, we will use “B” prompt

This is the reference relay number as used in the system. Relays and X-10 devices are numbered 01 – 08. The on-board triggers are numbered 17 and 18.

Page 42: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

XX UNIT No. yy

Unit NumberIf X-10 is selected, a prompt for the unit number appears.01-16 = predefined unit number[*] to continue

“A”

Page 43: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

01 Module Addr07, 08, 12, 13 00

Module Address07, 08, 12, 13 = predefined address[*] to continue

“B”

Module Address

Address Module

07 1st 4229 (with zones 09-16)

08 2nd 4229 (with zones 17-24)

12 1st 4204

13 2nd 4204

Page 44: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

XX Rly Position1-4 1

Relay Position1 – 4 = relay position[*] to continueThis is the physical relay position with respect to the relay module upon which it is located.

The system then returns to the Output Number prompt for programming the next device.

Enter Output No00 = QUIT 01

Page 45: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*79 Menu Mode

17 OUT NORM LOW0= NO 1=YES 0

Output Normally Low0=no (standard default)1=yes[*] to continue

This prompt appears only for triggers 17 & 18.Selecting 0 (no) sets the output level normally high(open).Selecting 1 (yes) set the output level normally low(ground).Output trigger 17 (100mA max.) can be used for resetting 4-wire smoke detectors (up to 2 smokes) by connecting it to the negative power terminal of the smoke detector.

Page 46: Vista-15P Control Panel

Vista-15P Defining Output Functions*80 Menu Mode

Page 47: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

In *80, we program relays or X-10 devices, previously defined in *79 output device mapping, to activate and deactivate.

The Vista-15P allows 24 output functions to be programmed. Each output function determines only one action.

For example: To turn a relay on and off requires two output functions.

Page 48: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

Output Funct. #(00 = Quit) 01

Output Function No.01 – 24 output function numberEnter the output function number to be defined(or 00 to exit).[*] to continue

01 A E Trig?00 0 0 ZL=1

Summary ScreenA = Output Action; E = Triggering event;P = Partition; Trig = Trigger type[*] to continue

Note: A question mark in the summary screen indicates that the device number shown has not been mapped. Use *79 Menu mode to map the device.

Page 49: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

Activated By0 = delete (delete the output function and any previous programming; see prompt below1 = zone list (go to “A” prompt)2 = zone type (go to “B” prompt)3 = zone number (go to “C” prompt)[*] to continue

Delete?0 = NO, 1 = YES Press 1 to delete this output definition.

01 Activated by:Delete 0

Page 50: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

01 Zn List

1

Zone List1 – 8 zone list[*] to continue

“A”

Enter EventAlarm 1

0 = restore; 1 = alarm;2 = fault; 3 = trouble

NOTE: For alarm, fault, and trouble an event on ANYZone in the list activates the output, but ALL zones inthe list must be restored before the output is restored.Press [*] to continue to the “Output Action” prompt.

*80 Menu Mode

01 Activated by:Zone List 1

Page 51: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

01 Enter Zn typePerimeter 03

Zone TypeEnter the desired zone type:There are a wide variety of zone types and system operations available.Press [*] to continue to the “Output Action” prompt.

“B”

01 Activated by:Zone Type 2

Page 52: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

“C”

01 Enter Zn No. 12

Zone NumberEnter the zone number desiredPress [*] to continue.

01 Enter EventRestore 0

Enter the zone event that will activate this output.0 = restore; 1 = alarm/fault/trouble

Press [*] to continue to the “Output Action prompt

01 Activated by:Zone Number 3

Page 53: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

*80 Menu Mode

01 Output ActionClose for 2 sec

Output Action 0 – 60 = off 4 = Change Device State1 = Close for 2 seconds 5 = Duration 1 (see data field *177)2 = Close and Stay Closed 6 = Duration 2 (see data field *177)3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)

Enter Output No.R02 02

Output Number 01 – 08 = as defined in *7917 – 18 = on-board triggersEnter the device output number (as defined in *79) you want associated with this output function. Press [*] to continue

02 A E TRIGR02 1 1 ZL=1

Summary ScreenPress [*] to continue

Page 54: Vista-15P Control Panel

Vista-15P

Test Report Setup

Page 55: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Automatic Periodic Test Report

The system can be set to automatically send test reports (automatically enables report code in field *64; Contact ID code 602) at specified intervals.

The frequency of the report can be set in Scheduling mode (event 11) or by the following key commands:

Installer code + [#] + 0 + 0 = test report sent every 24 hoursInstaller code + [#] + 0 + 1 = test report sent once per weekInstaller code + [#] + 0 + 2 = test report sent every 28 days

Each mode sets schedule 08, to the stated repeat option; the first test report is sent 12 hours after command.

To ensure that test reports are sent at the times expected, set the Real-Time Clock to the proper time before entering the test report schedule command.

Page 56: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Setting the Real Time Clock

Enter [4-digit Installer or Master code] + # + 63

•Press the [*] key to change the Date/Time settings. The blinking cursor appears on the first digit of the hour.•Enter the time (hour, then minute). After each entry the cursor moves to the right.•Press any odd-digit for PM, or any even-digit for AM.•Enter the 2-digit year, 2-digit month, and the 2-digit day in sequence. The day of the week is automatically calculated and displayed based on the date entered.•Press the [#] key to move the cursor to the left to make any changes that may be needed.•When entry is complete press the [*] key until the cursor is at the far right position.•To accept all of the clock information, press the [*] key again.

TIME/DATE SAT12:00AM 01/01/00

TIME/DATE SAT12:00A 2000/01/01

Page 57: Vista-15P Control Panel

Vista-15P

Security Codes

Page 58: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Security Codes

Vista-15P supports up to 33 user codes which can be assigned one of 5 authority levels.

Page 59: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Security Codes

Level User No. Functions

Installer 01 Perform all security functions except can disarm only if used to arm; can enter program mode; cannot change installer code (default-4112)

System

Master

02 Only one system master code per system; can perform all security functions, add/delete users in either partition, change master code, view event log, set system clock, program keypad macro, program scheduled events, activate output devices (triggers/relays) (default-1234)

Authority Levels (Authority Levels can be assigned to users 03 – 33 only; users 1 and 2 cannot be changed.)

Page 60: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Security Codes

Level User No. Functions

0-User 03-33 Perform security functions (arm, disarm,etc) only; cannot add/delete users, view event log, set system clock or program scheduled events.

1-Arm only 03-33 Arm system only

2- Guest 03-33 Can disarm the system only if it was used to arm the system

3-Duress 03-33 Performs security functions, but also silently sends a duress message to the central station; reports as zone 92

Authority Levels (authority levels can be assigned to users 03 – 33 only; users 1 and 2 cannot be changed.)

Page 61: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Security Codes

Adding a User Code: Master code + [8] + 2-digit user no. + user’s codeDeleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no] + value

Attributes: Values

1 = Authority Level 0 – 3 (see Authority Level table)2 = Access Group 0 – 8 (0= not assigned to a group)4 = RF Zone No. Assigns user number to button type

zone for arm/disarm5 = Open/Close paging 1 for yes; 0 for no

Page 62: Vista-15P Control Panel

Honeywell Proprietary

Honeywell.com

Review

• What is the maximum number of zones?• Do the keyfob zones count in the above number?• How many programmable outputs do the panels offer?• Do all ECP devices (keypads, expanders, etc.) need to have a

unique address?• Can we program a relay to throw in *79 output device mapping?