    TECHNICAL DATA

    April 17, 2009

    rELEAsE pLACEmENT

    opEN sTruCTurEs

    The Viking Catin, 210 N Indtial pak Dive, Hating mI 49058

    Telehne: 269-945-9501 Technical sevice 877-384-5464 Fax: 269-818-1680 Eail: [email protected]

    Design 207g

    Revised page replaces page 207g-l, dated April 18, 2003

    (Reformatted.

    Form No. F_042999

    CAuTIoN

    THEsE DEsIGN proCEDurEs ArE proVIDED oNLY For THE GENErAL GuIDANCE oF sYsTEm DEsIGNErs. THEY

    CoNTAIN BroAD ouTLINEs oF THE TYpEs oF CoNsIDErATIoNs WHICH ENTEr INTo THE DEsIGN oF sYsTEms. BECAusE

    oF THE mANY DIFFErENT TYpEs oF EQuIpmENT AND AppLICATIoNs ENCouNTErED IN prACTICE, No GENErAL sYsTEm

    DEsIGN CAN BE proVIDED WHICH WILL sATIsFY ALL oF THE VArYING NEEDs. THErEForE, rELIANCE musT BE puT

    IN THE EXpErTIsE oF A sYsTEm DEsIGNEr WHo sHouLD BE ENCourAGED To usE ALL AVAILABLE INFormATIoN

    From THE oWNEr, INsurANCE AuTHorITIEs AND LoCAL GoVErNmENTAL uNITs. VIKING DoEs NoT WArrANT

    or GuArANTEE THAT FoLLoWING THEsE proCEDurEs WILL rEsuLT IN sATIsFACTorY sYsTEm DEsIGN For ANY

    pArTICuLAr proJECT.

    A. LoCATIoN oF VIKING moDEL C THErmosTATIC rELEAsEs IN opEN sTruCTurEs or ouTsIDE.

    1. First determine the atmosphere the Model C Release is used for.

    Model C-1 is used for general purposes, non-corrosive atmospheres and is more sensitive to response of heat.

    Model C-2 release shall be used for corrosive or seawater air atmospheres and as indicated by spacing information is

    less sensitive to heat.See technical data pages for Model C-1 and C-2 Thermostatic Release devices for specific details of product.

    B. GENErAL proCEDurE

    1a. f semi-enclosed building, determinef semi-enclosed building, determineetermine

    Location of grating floors.

    All information required under inside spacing.

    1b. f individual or groups of equipment, determine

    Size and shape.

    2. Note characteristics of and location of special features

    Monitors and skylights note size and depth.

    Decks size and height.

    Heat producing equipment note direction of normal heat output.

    Probable sources of fire.

    3. Select the release spacing chart for the type of situation.

    4. f a large semi-enclosed building is involved, follow the rules for inside spacing when placing the interior releases.5. n covering individual pieces or groups of equipment initially, lay out the releases so they will be as close as possible to the

    probable source of fire. Then fill out coverage using the appropriate chart. Try to put releases so they are in the path of fire

    spread and/or downwind from fire.

    6. When covering a number of individual pieces of equipment in an area, check to see if releases protect more than one piece

    of equipment. Area coverage may be more desirable.

    7. Release hoods should be used for protection of the release from weather or physical damage such as under grating floors

    or where release may be subject to accumulation of dirt. Hoods have little or no value as heat collectors.

    8. t may be desirable to place 160 F (71 C) fixed temperature release at preferred locations where the fire may originate o

    be confined for a short time. n particular, fixed temperature release may be located under tanks and under inside equipment

    Also, fixed temperature release may be located inside small rooms.

    9. Review the layout to see that it is reasonable. The maximums stated are conservative, but due to variance in natural weathe

    conditions, maximum and minimum spacing is recommended to be used.

    a.

    b.

    c.

    a.

    b.

    a.

    a.

    b.

    c.

    d.

  • 7/28/2019 Vikin 1

    2/6

    TECHNICAL DATA

    April 17, 2009

    rELEAsE pLACEmENT

    opEN sTruCTurEs

    The Viking Catin, 210 N Indtial pak Dive, Hating mI 49058

    Telehne: 269-945-9501 Technical sevice 877-384-5464 Fax: 269-818-1680 Eail: [email protected]

    Design 207h

    Fige 1

    maxi acing f Viking mdel C Thetatic releae facty etting 0.025 (0.63 ) f

    mdel C-1 0.018 (0.46 ) f mdel C-2 f vetical tank lcated tide in en tcte.

    maxi TankDiaete

    C

    maxi Ht.f Tank

    D

    maxi Ht.Abve Gnd

    E

    maxi Ditance fC f Tank t releae

    F

    mini Ht. freleae Abve Tank

    G

    Nbe freleae

    reqied

    ft () ft () ft () ft () ft () C-1 C-2

    5 1.5 20 6.1 24 7.3 0 0 1 .30 1 1

    8 2.4 20 6.1 24 7.3 7 2.1 1 .30 2 2

    12 3.7 20 6.1 24 7.3 9.5 2.9 1 .30 3 3

    20 6.1 20 6.1 24 7.3 14. 4.3 1 .30 4 4

    28 8.5 20 6.1 24 7.3 17 5.2 1 .30 5 6

    35 10.7 20 6.1 24 7.3 20 6.1 1 .30 6 7

    41 12.5 20 6.1 24 7.3 23 7.0 1 .30 7 8

    48 14.6 20 6.1 24 7.3 26 7.9 1 .30 8 10

    55 16.8 20 6.1 24 7.3 29 8.8 1 .30 9 11

    62 18.9 20 6.1 24 7.3 32 9.8 1 .30 10 12

    When tank height exceeds 20 ft, (6.1 m) add additional rings around the tank at a maximum of 20 ft. (6.1 m) for Model C-1 or 16 ft (4.9

    m) for Model C-2 vertical intervals. Stagger the releases. When multiple rings or releases are used, the top ring should be 1 ft (.30 m

    minimum above top of tank. The other release rings should be spaced equally between bottom of tank and top ring. On tanks over 30

    ft (9.1 m) and to 60 ft (18.3 m) in diameter, locate a release over top or center. Over 60 ft (18.3 m), use three releases in a triangula

    pattern. If possible, space releases around tank so they can see each other. Use a 160 F (71 C) xed temperature release unde

    the center of a small elevated tank or pilot heads on 10 ft (3.0 m) centers for a larger elevated tanks. For high risks, use releases

    under tanks.

  • 7/28/2019 Vikin 1

    3/6

    TECHNICAL DATA

    April 17, 2009

    rELEAsE pLACEmENT

    opEN sTruCTurEs

    The Viking Catin, 210 N Indtial pak Dive, Hating mI 49058

    Telehne: 269-945-9501 Technical sevice 877-384-5464 Fax: 269-818-1680 Eail: [email protected]

    Design 207

    Fige 2

    Locate releases 1 ft (.30 m) minimum above

    top of tank or equipment. Equipment should

    fall substantially inside the area outlined. f

    height exceeds the maximum, add additional

    rings of releases around the equipment at a

    maximum of 20 ft. (6.10 m) for Model C-1

    or 16 ft. (4.9 m) for Model C-2 vertical in-

    tervals. Stagger lower releases in alternate

    location. When multiple rings or releases are

    used, the top ring should be 1 ft. (.30 m)

    minimum above equipment top, and the

    other rings should be spaced equally be-

    tween top ring and the equipment bottom.

    t may be desirable to place a 160 F (71 C)

    fixed temperature release under the center

    of elevated tanks or equipment. Use one re-

    lease in each 10 ft x 10 ft (3 m x 3 m) square.

    For high risks, use releases under tanks.

    maxi acing f Viking mdel C Thetatic releae facty etting 0.025 (0.63 ) f mdel C-1 0.018 (0.46 )

    f mdel C-2. F all individal hizntal tank all g f eqient, lan view ae hwn.

  • 7/28/2019 Vikin 1

    4/6

    TECHNICAL DATA

    April 17, 2009

    rELEAsE pLACEmENT

    opEN sTruCTurEs

    The Viking Catin, 210 N Indtial pak Dive, Hating mI 49058

    Telehne: 269-945-9501 Technical sevice 877-384-5464 Fax: 269-818-1680 Eail: [email protected]

    Design 207j

    maxi acing f Viking mdel C Thetatic releae facty etting 0.025 (0.63 ) f mdel C-1

    0.018 (0.46 ) f mdel C-2 lid f, n wall.

    Fige 3

    LEVEL rooF, sHED or pEAK rooF - Whee sle de nt exceed 1 in 8.

    sHED rooF - rf pitch 1 in 8 geate.

    pEAK rooF - rf pitch 1 in 8 geate.

  • 7/28/2019 Vikin 1

    5/6

  • 7/28/2019 Vikin 1

    6/6

    TECHNICAL DATA

    April 17, 2009

    rELEAsE pLACEmENT

    opEN sTruCTurEs

    The Viking Catin, 210 N Indtial pak Dive, Hating mI 49058

    Telehne: 269-945-9501 Technical sevice 877-384-5464 Fax: 269-818-1680 Eail: [email protected]

    Design 207l

    maxi acing f Viking mdel C-2 Thetatic releae facty 0.018 (0.46 ) f mdel C-2

    f lage aea td ei-encled bilding.

    NOTES

    1. Locate releases close to underside of solid floor or roof.

    2. f maximum allowable, A and B dimensions, place interior

    release outside of exterior line of releases, then interior

    releases are not needed.

    3. Where multiple floors are involved, treat each floor as

    a separate building. f height between floors exceeds

    the maximum, add additional releases below in such a

    manner that vertical distance between releases does not

    exceed maximum height between floors.

    4. Where top of building is open or grating, locate releases 1 ft

    (.30 m) minimum above top of grating. Locate releasesbelow intermediate grating floors.

    5. Locate releases 1 ft (.30 m) minimum above top of equip-

    ment.

    6. f height of equipment exceeds the maximum, add ad-

    ditional releases directly above lower releases at a maxi-

    mum of 16 ft (4.8 m); vertical intervals. Space releases

    equally between the top row and the equipment bottom.

    Fige 5: releae placeent f mdel C-2 Thetatic releae

    CnditinLage Than A max. B max. H max. J max. L max. m max.

    max.

    HeightBetween

    Fl

    t T

    max.Height

    t peak

    see

    Nte

    ft () ft () ft () ft () ft () ft () ft () ft () ft ()

    Building without WallsWith Roof or Solid Floors

    34x34 10.4x10.4 nside Spacing 20 6.1 20 6.1 7 2.1 7 2.1 24 7.3 30 9.1 1, 2, 3

    Building with Walls Down to 10 ftor Less From Grade - Solid Roof

    34x34 10.4x10.480% nside

    Spacing20 6.1 20 6.1 7 2.1 7 2.1 24 7.3 30 9.1 1, 2, 3

    Buildings with Walls ExtendingDown to More Than 10 ft AboveGrade with Roof or Solid Floors

    34x34 10.4x10.475% nside

    Spacing20 6.1 20 6.1 7 2.1 7 2.1 24 7.3 30 9.1 1, 2, 3

    Buildings with Full Wallsor with Walls Extending Down to10 ft or Less Above Grade withno Roof or with Grating Floors

    50x50 15.2x15.2 20 6.1 20 6.1 20 6.1 20 6.1 8 2.4 8 2.4 24 7.3 -- -- 3, 4

    Buildings with Walls ExtendingDown to More Than 10 ft Above

    Grade with No Roof or withGrating Floors

    40x40 12.2x12.2 16 4.8 16 4.8 16 4.8 16 4.8 7 2.1 7 2.1 24 7.3 -- -- 3, 4

    Buildings with No Wallsand Grating Floors

    18x18 5.5 x 5.5 16 4.8 16 4.8 16 4.8 16 4.8 1 .30 1 .30 19 5.8 -- -- 3, 4

    Large Equipment or Groupsof Equipment in the Open

    20x20 6.1 x 6.1 16 4.8 16 4.8 16 4.8 16 4.8 0 0 0 0 19 5.8 -- -- 3, 4