HART XL

Why Hart XL Aspirating Smoke Detection?

Earliest detection to enable business continuity

Extra time is required for safe evacuation

Unnecessary suppression release must be avoided

Smoke is difficult to detect

Environmentally challenging areas

Aesthetics & concealed detection are important

Maintenance access is limited

Earliest Detection to Enable Business

Continuity

Critical processes that cannot incur any business

disruption

­ Telecommunications facilities

­ Computer rooms

­ Banking operations

­ Production facilities

­ Internet Service Providers

Hart XL provides the earliest possible

warning - buying time

TIME

INT

EN

SIT

Y

1st StageIncipient

2nd StageVisible smoke

3rd StageFlames

Final StageHeat

Alarm 1PRE-ALARM 1 PRE-ALARM 2 Alarm 2

Extra Time is Required for Controlled

Evacuation

Environments where rapid exit can be impeded

­ Underground Stations

­ Theatres

­ Public buildings

­ Airports

Unnecessary Suppression Release Must

be Avoided

Early warning gives time to investigate to avoid

unnecessary suppression release

­ Telecommunication facilities

­ EDP facilities

­ Computer rooms

­ Electrical sub-stations

Smoke is Difficult to Detect

Environments with high ceilings, high air flows or

vast open areas provide

unique characteristics

­ Clean rooms

­ Warehouses

­ Aircraft hangers

­ Computer rooms

­ Atria

Warehouse and Atrium Protection

Hart XL

detector

Area open

to main

atrium

Horizontal

and vertical

sampling

pipes

Hart XL

detector

S M O K E

Stratified

smoke layer

Environmentally Challenging Areas

Aggressive environments with high levels of

pollution or extreme temperature conditions can be

protected reliably with acceptable maintenance

levels

­ Cold Stores

­ Production areas

­ Paper mills

­ Underground tunnels

­ Mines

Aesthetics are Important &

Replacement Impossible

Interiors that must not be spoilt by unsightly conventional

detectors Hart XL can be installed unobtrusively

­ Cathedrals

­ Stately Homes

­ Museums

­ Art Galleries

Maintenance Access is Limited

Hart XL can be located at an accessible location

while the sampling pipework makes

its way to the restricted area

­ Warehouses

­ Production machinery

­ Prisons

­ Restricted areas

­ EMC Controlled areas

­ Hospitals

HART XL

Technical Features

Detector Enclosure

Display Module

Self Contained Power Supply

LaserNet (Direct & Network)

SNIFF Version 3

Hart XL Range

Modular System

Detector

Display

Power Supply

Detector

Fan

Detector

Inlet

Outlet

Termination

Board

Features

Laser Particle Counter

User Selectable Sensitivity Range(s)

Digital Communications

4 Levels of Alarm

Monitors Air Flow

Modular in Design

Features (Cont.)

Historical Smoke & Event Log

Autosetup Function

Alarm Level Selection

Multiple Status Indications

Programmable Delays

Day/Night Setting

Network Capabilities

Specification

IP31

Weight 3.4 kg (7.5 lbs.)

Polycarbonate Light Grey

Dimensions - 320 by 228 by 108 mm

Input Voltage 18 - 30 V DC

Input Current 315 mA (With Display 445 mA)

Operating Temperature - 0 to 52°

Humidity - 10 to 95% Non Condensing

Standard Detector ApplicationsSensitivity R anges R ecom m ended Applica tions Sm oking

1

% /Ft % /m

0.30 - 0 .076 1.0 - 0.25 U nderground E lectric Yes

0.24 - 0 .048 0.8 - 0.16 R ailways, Sem i D irty

0 .18 - 0 .024 0.6 - 0.08 M anufacturing A reas

0.16 - 0 .016 0.55 - 0 .055

0.15 - 0 .015 0.50 - 0 .05

0.13 - 0 .013 0.45 - 0 .045

0.12 - 0 .012 0.4 - 0.04 M anufacturing A reas Yes

0.10 - 0 .010 0.35 - 0 .035

0.09 - 0 .009 0.3 - 0.03

0.076 - 0 .0076 0.25 - 0 .025

0.06 - 0 .006 0.2 - 0.02 O ffice A reas, M useum s, N o

0.045 - 0 .0030 0.15 - 0 .01 C lean M anufacturing A re as

0.03 - 0 .0015 0.1 - 0.005 Low G rade C lean R oom N o

0.015 - 0 .00076 0.05 - 0 .0025

Ultra Detector Applications

Sensitivity R anges R ecom m ended App lica tions

% /Ft % /m

0.030 - 0 .0076 0.10 - 0 .025 Low G rade C lean R oom

0.024 - 0 .0048 0.08 - 0 .016

0.018 - 0 .0024 0.06 - 0 .008

0.016 - 0 .0016 0.055 - 0 .0055

0.015 - 0 .0015 0.050 - 0 .005 H igh G rade C lean R oom

0.013 - 0 .0013 0.045 - 0 .0045

0.012 - 0 .0012 0.04 - 0 .004

0.010 - 0 .0010 0.035 - 0 .0035

0.009 - 0 .0009 0.03 - 0 .003

0.0076 - 0 .00076 0.025 - 0 .0025 U ltra G rade C lean R oom

0.006 - 0 .0006 0.02 - 0 .002

0.0045 - 0 .00030 0.015 - 0 .001

0.0038 - 0 .00022 0.0125 - 0 .00075

0.0030 - 0 .00015 0.01 - 0 .0005

Servicing & Maintenance

Easy and quick to service and maintain

Reduced downtime

Lower servicing cost

Lower spares holding

Reduced cost of ownership

Display Module

• Status Normal Indication

• Time and Date

• Cursor Menu Control

• Password Access for Further

Information

Hart XL Display Control Unit

• Large LCD Display

• Clear Information

• Three Colour Status LED

Alarm condition

Ten bar graph scale

Location identifier

Fault type identified

through password

access

Hart XL Display Control Unit

Features

Local or Remote Mount Option

Mono Back Lit Graphical LCD

Displays Real Time Information

5 Control Keys

Audible Sounder Indication

Status LED Indication

Specifications

Weight 0.5 kg (1.1 lbs.)

Polycarbonate Light Grey

Dimensions - 122 by 145 by 38 mm

RS485 Communications - 1 km (max)

Input Voltage 18 - 30 V DC

Input Current 130 mA (Back lit on)

Operating Temperature - 0 to 52°

Humidity - 10 to 95% Non Condensing

Self Contained Power Supply

Features

1 amp Power Supply

90 to 260 V AC Input

28.75 Volt @ 1 amp Output

Space for 2 off 12volt 2.0 Ah Batteries

Blends in with Enclosure Design

Ease of Installation

Specification

Weight 3.1 kg (7 lbs.) - Without Batteries

Polycarbonate Light Grey

Dimensions - 320 by 112 by 108 mm

Input Voltage 90 to 260 V AC

Operating Temperature - 0 to 52°

Humidity - 10 to 95% Non Condensing

LaserNet Software

Direct or Network Mode Option

Windows Compatible (95,98, 2000 & NT)

Used to Configure Detector

Used to Commission System

Used to Monitor System

Password Protected Entry

View Event & Smoke History

Direct connection to PC for Programming

and Downloading using LaserNet Software.

No programmers or interfaces are required

Programming and Diagnostics

Programming

Options

­ Fixed or automatically set

sensitivity

­ Programmable relays

­ Latching or non latching

alarms

­ Two or Four levels of

Alarm

­ Delay timers

­ Day/Night option

Diagnostics &

Monitoring

­ Download history & event

log

­ Full fault analysis

­ Dial in & dial out via

modem monitoring

(Network)

­ Intelligent interface

module (IIM) common

alarm & fault relay

outputs

LaserNet Features

SNIFF Software

System Design Software

Windows Compatible (95,98, 2000 & NT)

Sample Calculation & Optimisation Tool

Flexible Design Criteria

Isometric Design Layout Feature

Design Reports (Including Parts Lists)

Allows 100 sample points over 40 Segments

New Updated SNIFF System Design Software

Windows compatible

Easy operation and clear displays

Isometric drawings from several angles

New Updated SNIFF System Design Software

Benefits

­ High quality print out with isometric

drawings & calculations

­ Optimised sample hole sizing

­ Compatible with current PC operating