vesda laserplus accreditation training - fire security deigmatolipsia hart xl.pdf · hart xl...
TRANSCRIPT
Why Hart XL Aspirating Smoke Detection?
Earliest detection to enable business continuity
Extra time is required for safe evacuation
Unnecessary suppression release must be avoided
Smoke is difficult to detect
Environmentally challenging areas
Aesthetics & concealed detection are important
Maintenance access is limited
Earliest Detection to Enable Business
Continuity
Critical processes that cannot incur any business
disruption
Telecommunications facilities
Computer rooms
Banking operations
Production facilities
Internet Service Providers
Hart XL provides the earliest possible
warning - buying time
TIME
INT
EN
SIT
Y
1st StageIncipient
2nd StageVisible smoke
3rd StageFlames
Final StageHeat
Alarm 1PRE-ALARM 1 PRE-ALARM 2 Alarm 2
Extra Time is Required for Controlled
Evacuation
Environments where rapid exit can be impeded
Underground Stations
Theatres
Public buildings
Airports
Unnecessary Suppression Release Must
be Avoided
Early warning gives time to investigate to avoid
unnecessary suppression release
Telecommunication facilities
EDP facilities
Computer rooms
Electrical sub-stations
Smoke is Difficult to Detect
Environments with high ceilings, high air flows or
vast open areas provide
unique characteristics
Clean rooms
Warehouses
Aircraft hangers
Computer rooms
Atria
Warehouse and Atrium Protection
Hart XL
detector
Area open
to main
atrium
Horizontal
and vertical
sampling
pipes
Hart XL
detector
S M O K E
Stratified
smoke layer
Environmentally Challenging Areas
Aggressive environments with high levels of
pollution or extreme temperature conditions can be
protected reliably with acceptable maintenance
levels
Cold Stores
Production areas
Paper mills
Underground tunnels
Mines
Aesthetics are Important &
Replacement Impossible
Interiors that must not be spoilt by unsightly conventional
detectors Hart XL can be installed unobtrusively
Cathedrals
Stately Homes
Museums
Art Galleries
Maintenance Access is Limited
Hart XL can be located at an accessible location
while the sampling pipework makes
its way to the restricted area
Warehouses
Production machinery
Prisons
Restricted areas
EMC Controlled areas
Hospitals
Detector Enclosure
Display Module
Self Contained Power Supply
LaserNet (Direct & Network)
SNIFF Version 3
Hart XL Range
Features
Laser Particle Counter
User Selectable Sensitivity Range(s)
Digital Communications
4 Levels of Alarm
Monitors Air Flow
Modular in Design
Features (Cont.)
Historical Smoke & Event Log
Autosetup Function
Alarm Level Selection
Multiple Status Indications
Programmable Delays
Day/Night Setting
Network Capabilities
Specification
IP31
Weight 3.4 kg (7.5 lbs.)
Polycarbonate Light Grey
Dimensions - 320 by 228 by 108 mm
Input Voltage 18 - 30 V DC
Input Current 315 mA (With Display 445 mA)
Operating Temperature - 0 to 52°
Humidity - 10 to 95% Non Condensing
Standard Detector ApplicationsSensitivity R anges R ecom m ended Applica tions Sm oking
1
% /Ft % /m
0.30 - 0 .076 1.0 - 0.25 U nderground E lectric Yes
0.24 - 0 .048 0.8 - 0.16 R ailways, Sem i D irty
0 .18 - 0 .024 0.6 - 0.08 M anufacturing A reas
0.16 - 0 .016 0.55 - 0 .055
0.15 - 0 .015 0.50 - 0 .05
0.13 - 0 .013 0.45 - 0 .045
0.12 - 0 .012 0.4 - 0.04 M anufacturing A reas Yes
0.10 - 0 .010 0.35 - 0 .035
0.09 - 0 .009 0.3 - 0.03
0.076 - 0 .0076 0.25 - 0 .025
0.06 - 0 .006 0.2 - 0.02 O ffice A reas, M useum s, N o
0.045 - 0 .0030 0.15 - 0 .01 C lean M anufacturing A re as
0.03 - 0 .0015 0.1 - 0.005 Low G rade C lean R oom N o
0.015 - 0 .00076 0.05 - 0 .0025
Ultra Detector Applications
Sensitivity R anges R ecom m ended App lica tions
% /Ft % /m
0.030 - 0 .0076 0.10 - 0 .025 Low G rade C lean R oom
0.024 - 0 .0048 0.08 - 0 .016
0.018 - 0 .0024 0.06 - 0 .008
0.016 - 0 .0016 0.055 - 0 .0055
0.015 - 0 .0015 0.050 - 0 .005 H igh G rade C lean R oom
0.013 - 0 .0013 0.045 - 0 .0045
0.012 - 0 .0012 0.04 - 0 .004
0.010 - 0 .0010 0.035 - 0 .0035
0.009 - 0 .0009 0.03 - 0 .003
0.0076 - 0 .00076 0.025 - 0 .0025 U ltra G rade C lean R oom
0.006 - 0 .0006 0.02 - 0 .002
0.0045 - 0 .00030 0.015 - 0 .001
0.0038 - 0 .00022 0.0125 - 0 .00075
0.0030 - 0 .00015 0.01 - 0 .0005
Servicing & Maintenance
Easy and quick to service and maintain
Reduced downtime
Lower servicing cost
Lower spares holding
Reduced cost of ownership
• Status Normal Indication
• Time and Date
• Cursor Menu Control
• Password Access for Further
Information
Hart XL Display Control Unit
• Large LCD Display
• Clear Information
• Three Colour Status LED
Alarm condition
Ten bar graph scale
Location identifier
Fault type identified
through password
access
Hart XL Display Control Unit
Features
Local or Remote Mount Option
Mono Back Lit Graphical LCD
Displays Real Time Information
5 Control Keys
Audible Sounder Indication
Status LED Indication
Specifications
Weight 0.5 kg (1.1 lbs.)
Polycarbonate Light Grey
Dimensions - 122 by 145 by 38 mm
RS485 Communications - 1 km (max)
Input Voltage 18 - 30 V DC
Input Current 130 mA (Back lit on)
Operating Temperature - 0 to 52°
Humidity - 10 to 95% Non Condensing
Features
1 amp Power Supply
90 to 260 V AC Input
28.75 Volt @ 1 amp Output
Space for 2 off 12volt 2.0 Ah Batteries
Blends in with Enclosure Design
Ease of Installation
Specification
Weight 3.1 kg (7 lbs.) - Without Batteries
Polycarbonate Light Grey
Dimensions - 320 by 112 by 108 mm
Input Voltage 90 to 260 V AC
Operating Temperature - 0 to 52°
Humidity - 10 to 95% Non Condensing
LaserNet Software
Direct or Network Mode Option
Windows Compatible (95,98, 2000 & NT)
Used to Configure Detector
Used to Commission System
Used to Monitor System
Password Protected Entry
View Event & Smoke History
Direct connection to PC for Programming
and Downloading using LaserNet Software.
No programmers or interfaces are required
Programming and Diagnostics
Programming
Options
Fixed or automatically set
sensitivity
Programmable relays
Latching or non latching
alarms
Two or Four levels of
Alarm
Delay timers
Day/Night option
Diagnostics &
Monitoring
Download history & event
log
Full fault analysis
Dial in & dial out via
modem monitoring
(Network)
Intelligent interface
module (IIM) common
alarm & fault relay
outputs
LaserNet Features
SNIFF Software
System Design Software
Windows Compatible (95,98, 2000 & NT)
Sample Calculation & Optimisation Tool
Flexible Design Criteria
Isometric Design Layout Feature
Design Reports (Including Parts Lists)
Allows 100 sample points over 40 Segments
New Updated SNIFF System Design Software
Windows compatible
Easy operation and clear displays
Isometric drawings from several angles