Revised July 11, 2014. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Cooling Fresh Air Clean AirHeating
Vertical Stack Water Source Heat Pump
Submittal DataEnglish Language, IP Units
Submittal data
Unit designation
Job name
Architect
Engineer
Contractor
Electrical dataPower supply
Volts Phase Hz
Minimum circuit ampacity
Maximum overcurrent protection
Performance dataCooling capacity
BTU/hr
EER
Heating capacity
BTU/hr
COP
Ambient air temperature
°F
Entering water temperature (cooling)
°F
Entering air temperature (cooling)
°F
Water flow (cooling)
GPM
Entering water temperature (heating)
°F
Entering air temperature (heating)
°F
Water flow (heating)
GPM
Airflow
CFM
Fan speed or motor/RPM/turns
Operating weight
lb.
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: ii
Table of contents *Page number
Unit features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions and data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mechanical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cutsheets
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 1 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Standard unit features
Summary of all features, some features may not be specific to every project.
1. Cabinetnn 20-gauge galvanized steel construction.nn Two sizes available.
n Small: 18" x 18" x 88" for sizes 09-18 n Large: 24" x 24" x 88" for sizes 24-36
nn 1/2" thick, 2 lb. density matt-faced fiberglass insulation.nn Pre-configured riser knockouts: left, right and rear.nn Pre-configured supply air knockouts: left, right, rear, front and top.
2. Stainless steel drain pannn Factory installed P-trap.nn Externally insulated using closed cell foam.nn Positively sloped in two directions to ensure proper drainage and maximize protection against microbial growth.
3. Removable blower/motor assemblynn 208-230V/60/1 permanent split capacitor type motor.nn Easily removable assembly with motor quick connect.
4. Chassisnn Seven available sizes named for their nominal capacities
n 09: 9,000 BTU/hr n 12: 12,000 BTU/hr n 15: 15,000 BTU/hr n 18: 18,000 BTU/hr n 24: 24,000 BTU/hr n 30: 30,000 BTU/hr n 36: 36,000 BTU/hr
nn Exceeds ASHRAE 90.1 efficiency requirements using environmentally friendly R-410A refrigerant. nn Front service ports for refrigerant system maintenance.nn TXV metering device.nn Appliance wheels, drop down service legs and electrical quick connects for system maintenance.nn Insulated water/refrigeration piping for low temperature applications.nn Sound attenuation package including dual compressor isolation.
5. Compressornn Rotary type or scroll type, dependent upon size.nn 208-230V/60/1 compressor voltage.nn Wrapped in an insulation blanket for noise attenuation.
6. Air coilnn Multi-louvered, lanced 0.0045" thick aluminum fins.nn Rifled 3/8" O.D. copper tube construction with 0.012" tube wall thickness.nn Hydrophilic coating.
7. Filternn Washable nylon type.
8. Controlsnn Standard unit mounted microprocessor control with system troubleshooting codes and dip switches.nn 24V, 50VA transformer with resettable fuse.nn Low and high pressure switches.nn Air side and water side freeze protection sensors.nn Electronic condensate overflow protection.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 2 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
1. Cabinetnn Contact the factory for other cabinet heights./nn 1/2" thick foil-faced fiberglass or closed cell insulationnn 277V/60/1 permanent split capacitor blower motor available.nn 208-230V/60/1 and 277V/60/1 high static permanent split capacitor blower motors available.nn 208-230V/60/1 EC blower motors available.nn Sight/sound baffle available when there are multiple opposing supply air discharge openings.
2. Chassisnn 277V/60/1 compressor voltage available.
3. Hose kitsnn 1/2" or 3/4" stainless steel flexible hoses.nn 2-way on/off normally closed zone valve.nn Y-srainer with P/T ports.nn Autoflow valve with P/T ports.
4. Return air panelnn 18-gauge construction with 16-gauge and 14-gauge options.nn Removable perimeter bypass (Allen lock), hinged perimeter bypass (key lock or Allen lock) and removable louvered (Allen lock).nn Ivory epoxy powder coating is standard. Additional colors can be selected from the Zehnder Rittling color chart. Please furnish a color chip for custom color.nn Contact the factory for ADA options.
Optional unit features
5. Discharge grille(s)nn Single deflection, double deflection or double deflection with opposed blade damper.nn Aluminum construction.nn Color matched to return air panel.
6. Risersnn Diameters from 3/4" to 2-1/2" with 3" swaged connections.nn 104" to 115" standard lengths.nn Type L or M copper.nn Uninsulated or insulated with 1/2" or 3/4" closed cell foam.nn Contact the factory for:
n Type K copper n 3" diameter n Lengths up to 118"
7. Controlsnn Optional disconnect switch.nn Optional BACnet or LonWorks interface.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 3 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
General data
Size 09 12 15 18 24 30 36
Cooling capacity (BTU/hr) 9200 12000 16500 18500 22500 30000 34000
Heating capacity (BTU/hr) 12500 16000 21500 23500 29500 37000 41000
Compressor (1 each) Rotary Rotary Rotary Rotary Rotary Rotary Scroll
Factory refrigerant charge R-410A (oz) 27.5 31.7 45.8 47.0 52.9 64.6 60.0
Fan data
Speeds 2 2 2 2 2 2 2
Blower wheel size (D x W) (in.) standard/high static
7.1 x 6.7 7.1 x 6.7 7.1 x 6.7 7.1 x 6.7 9.2 x 10.0 9.2 x 10.0 9.2 x 10.0
Air flow (CFM @ 0.0" of static pressure) 360 420 540 630 820 1080 1220
Water/condensate side data
Flow rate (GPM) 2.6 3.6 4.9 5.3 6.6 8.7 9.4
Water connection size (female NPT, in.) 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Water side pressure drop (psi) 4.5 6.2 5.8 6.5 5.0 7.3 7.8
Condensate connection size (in.) 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Air coil data
Total face area (ft.) 1.48 1.48 1.81 1.81 1.72 1.72 1.72
Tube size (in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Fin spacing (FPI) 14 14 14 14 12 12 12
Number of rows 2 3 4 4 3 4 4
Cabinet data
Depth (in.) 18 18 18 18 24 24 24
Height (in.) 88 88 88 88 88 88 88
Width (in.) 18 18 18 18 24 24 24
Filter standards - washable filter (in.)14-1/4 x 18-1/2
14-1/4 x 18-1/2
14-1/4 x 22-1/2
14-1/4 x 22-1/2
19 x 28-3/4
19 x 28-3/4
19 x 28-3/4
Cabinet weight (lb.) 120 120 120 120 170 170 170
Chassis weight (lb.) 99 105 119 122 187 198 225
Notes: n Capacities based on a water loop application at AHRI/ASHRAE/ISO 13256-1 specifications.
n Cooling capacity based upon 80.6 °F DB, 66.2 °F WB entering air temperature.
n Heating capacity based upon 68 °F DB, 59 °F WB entering air temperature.
n All ratings based upon air flow at high speed and operation at lower voltage (208V) of dual voltage ratings.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 4 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Unit typeVHN = Vertical Stack Water Source Heat Pump complete
ModelM = MasterS = SlaveA = Stand Alone
Nominal capacity09 = 9,000 BTU/Hr12 = 12,000 BTU/Hr15 = 15,000 BTU/Hr18 = 18,000 BTU/Hr24 = 24,000 BTU/Hr30 = 30,000 BTU/Hr36 = 36,000 BTU/Hr
VoltageA = 208-230V/60/1B = 277V/60/1
Blower/motor optionsA = Standard/PSCB = High static/PSCC = Standard/ECMD = High static/ECM
OptionsX = None (standard)S = With sight and sound baffle
ControlsS = Microprocessor controlsC = Microprocessor and customer supplied DDC controlsL = Microprocessor and Lon Network CommunicationB = Microprocessor and BACnet network communicationN = Microprocessor and N2 network communication
Power terminationX = No disconnect1 = Disconnect switch
Supply air/risersNA = None/back DA = Front, right/back TA = Front, left, right/backNB = None/right DB = Front, left/back TB = Front, top, right/backNC = None/left DC = Left, right/back TC = Front, top, left/backSA = Front/back DD = Front, top/back TD = Top, left, right/backSB = Right/back DE = Front, left/right TE = Front, back, left/rightSC = Left/back DF = Back, left/right TF = Front, back, top/rightSD = Top/back DG = Front, back/right TG = Front, top, left/rightSE = Left/right DH = Left, top/back TH = Top, back, left/rightSF = Front/right DJ = Back, right/left TJ = Front, back,right/leftSG = Back/right DK = Front, right/left TK = Front, back, top/leftSH = Top/right DL = Front, back/left TL = Front, top, right/leftSJ = Right/left DM = Right, top/back TM = Top, back, right/leftSK = Back/left DN = Front, top/leftSL = Front/left DO = Back, top/leftSM = Top/left DP = Right, top/left
DQ = front, top/rightDR = Back, top/rightDS = Left, top/right
1, 2, 3 4 5, 6 7 8 9 10 11 12, 13 14 15 16 17 18 19 20 21 22 23 24, 25
VHN M 09 A A X S X DB 1 D A X A 1 1 A A – AA
Special option codesAA = Standard
Placeholder
Revision levelA = Rev. 1
Supply air sizeX = NoneA = 10" x 8" (09-18)B = 12" x 10" (09, 12, 24-36)C = 14" x 12" (15, 18)D = 16" x 14" (24-36)
Cabinet1 = 88"3 = Custom
Air filter1 = Washable2 = 1" throwaway
Hose kit (3')X = NoneA = 1/2"B = 3/4"
Y strainerX = NoneA = 1/2" Y strainer (09, 12)
Zone valveX = NoneA = 1/2" 24VAC zone valve (09, 12)B = 3/4" 24VAC zone valve (15-36)
Flow regulatorX = NoneA = 1/2", 1.5 GPM (09, 12)B = 1/2", 2.0 GPM (09, 12)C = 1/2", 2.5 GPM (09, 12)D = 1/2", 3.0 GPM (09, 12)E = 3/4", 2.0 GPM (15, 18)F = 3/4", 2.5 GPM (15, 18)G = 3/4", 3.0 GPM (15-24)H = 3/4", 3.5 GPM (24, 30)I = 3/4", 4.0 GPM (24, 30)J = 3/4", 5.0 GPM (24-36)K = 3/4", 6.0 GPM (24-36)L = 3/4", 7.0 GPM (30, 36)M = 3/4", 8.0 GPM (30, 36)N = 3/4", 9.0 GPM (36)O = 3/4", 10.5 GPM (36)
Heat exchanger1 = Copper coax with air coil
Nomenclature: VS series, complete unit
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 5 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Unit typeVHC = Vertical Stack Water Source Heat Pump cabinetry
ModelM = MasterS = SlaveA = Stand Alone
Nominal capacity09 = 9,000 BTU/Hr12 = 12,000 BTU/Hr15 = 15,000 BTU/Hr18 = 18,000 BTU/Hr24 = 24,000 BTU/Hr30 = 30,000 BTU/Hr36 = 36,000 BTU/Hr
VoltageA = 208-230V/60/1B = 277V/60/1
Blower/motor optionsA = Standard/PSCB = High static/PSCC = Standard/ECMD = High static/ECM
OptionsX = None (standard)S = With sight and sound baffle
ControlsS = Microprocessor controlsC = Microprocessor and customer supplied DDC controlsL = Microprocessor and Lon Network CommunicationB = Microprocessor and BACnet network communicationN = Microprocessor and N2 network communication
Power terminationX = No disconnect1 = Disconnect switch
Supply air/risersNA = None/back DA = Front, right/back TA = Front, left, right/backNB = None/right DB = Front, left/back TB = Front, top, right/backNC = None/left DC = Left, right/back TC = Front, top, left/backSA = Front/back DD = Front, top/back TD = Top, left, right/backSB = Right/back DE = Front, left/right TE = Front, back, left/rightSC = Left/back DF = Back, left/right TF = Front, back, top/rightSD = Top/back DG = Front, back/right TG = Front, top, left/rightSE = Left/right DH = Left, top/back TH = Top, back, left/rightSF = Front/right DJ = Back, right/left TJ = Front, back,right/leftSG = Back/right DK = Front, right/left TK = Front, back, top/leftSH = Top/right DL = Front, back/left TL = Front, top, right/leftSJ = Right/left DM = Right, top/back TM = Top, back, right/leftSK = Back/left DN = Front, top/leftSL = Front/left DO = Back, top/leftSM = Top/left DP = Right, top/left
DQ = front, top/rightDR = Back, top/rightDS = Left, top/right
1, 2, 3 4 5, 6 7 8 9 10 11 12, 13 14 15 16 17 18
VHC M 09 A A X S X DB 1 A A – AA
Special option codesAA = Standard
Placeholder
Revision levelA = Rev. 1
Supply air sizeX = NoneA = 10" x 8" (09-18)B = 12" x 10" (09, 12, 24-36)C = 14" x 12" (15, 18)D = 16" x 14" (24-36)
Cabinet1 = 88"3 = Custom
Nomenclature: VS series, cabinetry
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 6 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Nomenclature: VS series, chassis
Unit typeVHCH = Vertical Stack Water Source Heat Pump chassis
Nominal capacity09 = 9,000 BTU/Hr12 = 12,000 BTU/Hr15 = 15,000 BTU/Hr18 = 18,000 BTU/Hr24 = 24,000 BTU/Hr30 = 30,000 BTU/Hr36 = 36,000 BTU/Hr
VoltageA = 208-230V/60/1B = 277V/60/1
Heat exhanger1 = Copper coax with air coil
Flow regulatorX = NoneA = 1/2", 1.5 GPM (1, 2)B = 1/2", 2.0 GPM (1, 2)C = 1/2", 2.5 GPM (1, 2)D = 1/2", 3.0 GPM (1, 2)E = 3/4", 2.0 GPM (3, 4)F = 3/4", 2.5 GPM (3, 4)G = 3/4", 3.0 GPM (3, 4, 5)H = 3/4", 3.5 GPM (5, 6)I = 3/4", 4.0 GPM (5, 6)J = 3/4", 5.0 GPM (5, 6, 7)K = 3/4", 6.0 GPM (5, 6, 7)L = 3/4", 7.0 GPM (6, 7)M = 3/4", 8.0 GPM (6, 7)N = 3/4", 9.0 GPM (7)O = 3/4", 10.5 GPM (7)
1, 2, 3, 4 5, 6 7 8 9 10 11 12 13 14 15 16, 17
VHCH 09 A 1 D A X A 1 A – AA
Special option codesAA = Standard
Placeholder
Revision levelA = Rev. 1
Air filter1 = Washable2 = 1" throwaway
Hose kit (3')X = NoneA = 1/2"B = 3/4"
Y strainerX = NoneA = 1/2" Y strainer (09, 12)B = 3/4" Y straner (15-36)
Zone valveX = NoneA = 1/2" 24VAC zone valve (09, 12)B = 3/4" 24VAC zone valve (15-36)
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 7 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
AHRI approved standard ratings
All ratings based on AHRI/ASHRAE/ISO 13256-1 specifications
Water loop heat pump
Size Total cooling at 86 °F Total heating at 68 °F
Capacity (BTU/hr)
EER (BTU/W)
Capacity (BTU/hr)
COP
09 9200 13.5 12500 4.7
12 12000 13.0 16000 4.6
15 16500 13.0 21500 4.5
18 18500 13.0 23500 4.5
24 22500 13.0 29500 4.7
30 30000 12.7 37000 4.5
36 34000 13.0 41000 4.5
Ground water heat pump
Size Total cooling at 59 °F Total heating at 50 °F
Capacity (BTU/hr)
EER (BTU/W)
Capacity (BTU/hr)
COP
09 11200 21.0 10500 4.1
12 14800 21.0 13500 4.0
15 19500 20.0 18500 3.9
18 20500 19.5 19500 3.9
24 26800 20.0 24500 4.2
30 35000 19.0 32000 4.0
36 38000 19.0 35000 4.0
Ground loop heat pump
Size
Total cooling at 77 °F Total heating at 32 °F
Capacity (BTU/hr)
EER (BTU/W)
Capacity (BTU/hr)
COP
09 9700 15.6 8100 3.4
12 13200 15.5 10000 3.3
15 18000 15.0 15000 3.2
18 19000 14.8 16800 3.2
24 24000 15.0 19000 3.3
30 32000 14.5 25000 3.3
36 36000 15.0 27000 3.2
Notesnn Cooling capacity based upon 80.6°F DB, 66.2°F WB entering air temperaturenn Heating capacity based upon 68°F DB, 59°F WB entering air temperaturenn All ratings based upon air flow at high speed and operation at lower voltage (208V) of dual voltage ratings
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 8 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Electrical data
Standard PSC motors
SizeVoltage
codeRated voltage
(V/Hz/Ph)Voltage
min./max.Compressor Power
(W)FLA
Total unit FLA
Min. circuit Amps
Max. fuse/HACR sizeRLA LRA
09A 208-230/60/1 197/254 4.7 20.0 37 0.44 5.1 6.3 15
B 277/60/1 250/293 3.3 18.8 40 0.40 3.7 4.5 15
12A 208-230/60/1 197/254 6.3 27.0 46 0.44 6.7 8.3 15
B 277/60/1 250/293 4.6 20.0 50 0.40 5.0 6.2 15
15A 208-230/60/1 197/254 9.9 42.0 87 1.30 11.2 13.7 25
B 277/60/1 250/293 7.1 43.0 100 1.30 8.4 10.2 20
18A 208-230/60/1 197/254 9.9 42.0 111 1.30 11.2 13.7 25
B 277/60/1 250/293 9.0 54.0 125 1.30 10.3 12.6 20
24A 208-230/60/1 197/254 10.8 46.0 304 2.10 12.9 15.6 25
B 277/60/1 250/293 9.0 54.0 300 1.70 10.7 13.0 25
30A 208-230/60/1 197/254 13.1 65.9 368 2.10 15.2 18.5 30
B 277/60/1 250/293 12.2 72.0 340 1.70 13.0 17.0 30
36A 208-230/60/1 197/254 18.6 79.0 442 2.10 20.7 25.4 40
B 277/60/1 250/293 13.5 72.0 360 1.70 15.2 18.6 40
Notes:nn Maximum circuit ampacity (MCA) =
1.25 x (FLA motor 1 + FLA motor 2 + FLA electric heat)nn Maximum overcurrent protection (MOP) =
(2.25 x FLA motor 1) + FLA motor 2 + FLA electric heatnn If the calculated MOP is within 10% of the next smaller available
fuse size, that fuse size shall be used. If not, the next larger fuse size above the calulated MOP must be used.nn If the selected MOP is smaller than the MCA, the selected MOP
must be increased to the next larger available fuse size above the MCA.nn If the MOP is less than 15, it shall be rounded up to 15 amps. This
is the minimum fuse or circuit breaker permitted by code.
nn EC motor nameplate amperage indicates the motor hardware peak amperage while the motor full load amperage (FLA) is limited by the motor’s factory programmed operating range, programmed specifically for each unit size. The programmed operating range is generally only a portion of the motor hardware full potential resulting in the motor FLA being lower than the nameplate FLA. Motor FLA will be reflected on the Fan Coil serial tag and should be used when sizing building electrical requirements.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 9 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Standard EC motors
SizeVoltage
codeRated voltage
(V/Hz/Ph)Voltage
min./max.Compressor
FLATotal unit
FLAMin. circuit
AmpsMax. fuse/HACR sizeRLA LRA
09A 208-230/60/1 197/254 4.7 20.0 2.9/2.6 7.6/7.3 8.8/8.5 15
B 277/60/1 250/293 3.3 18.8 2.5 5.8 6.6 15
12A 208-230/60/1 197/254 6.3 27.0 2.9/2.6 9.2/8.9 10.8/10.5 20
B 277/60/1 250/293 4.6 20.0 2.5 7.1 8.3 15
15A 208-230/60/1 197/254 9.9 42.0 2.9/2.6 12.8/12.5 15.3/15.0 25
B 277/60/1 250/293 7.1 43.0 2.5 9.6 11.4 20
18A 208-230/60/1 197/254 9.9 42.0 2.9/2.6 12.8/12.5 15.3/15.0 25
B 277/60/1 250/293 9.0 54.0 2.5 11.5 13.8 25
24A 208-230/60/1 197/254 10.8 46.0 2.9/2.6 13.7/13.4 16.4/16.1 25
B 277/60/1 250/293 10.9 60.0 2.5 13.4 16.1 25
30A 208-230/60/1 197/254 13.1 65.9 2.9/2.6 16.0/15.7 19.3/19.0 30
B 277/60/1 250/293 12.2 72.0 2.5 14.7 17.8 30
36A 208-230/60/1 197/254 18.6 79.0 2.9/2.6 21.5/21.2 26.2/25.9 50
B 277/60/1 250/293 16.0 87.0 2.5 18.5 22.5 40
Electrical data
Notes:nn Maximum circuit ampacity (MCA) =
1.25 x (FLA motor 1 + FLA motor 2 + FLA electric heat)nn Maximum overcurrent protection (MOP) =
(2.25 x FLA motor 1) + FLA motor 2 + FLA electric heatnn If the calculated MOP is within 10% of the next smaller available
fuse size, that fuse size shall be used. If not, the next larger fuse size above the calulated MOP must be used.nn If the selected MOP is smaller than the MCA, the selected MOP
must be increased to the next larger available fuse size above the MCA.nn If the MOP is less than 15, it shall be rounded up to 15 amps. This
is the minimum fuse or circuit breaker permitted by code.
nn EC motor nameplate amperage indicates the motor hardware peak amperage while the motor full load amperage (FLA) is limited by the motor’s factory programmed operating range, programmed specifically for each unit size. The programmed operating range is generally only a portion of the motor hardware full potential resulting in the motor FLA being lower than the nameplate FLA. Motor FLA will be reflected on the Fan Coil serial tag and should be used when sizing building electrical requirements.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 10 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Electrical data
High static PSC motors
SizeVoltage
codeRated voltage
(V/Hz/Ph)Voltage
min./max.Compressor Power
(W)FLA
Total unit FLA
Min. circuit Amps
Max. fuse/HACR sizeRLA LRA
09A 208-230/60/1 197/254 4.7 20.0 79 1.3 6.0 7.2 15
B 277/60/1 250/293 3.3 18.8 80 1.3 4.6 5.4 15
12A 208-230/60/1 197/254 6.3 27.0 102 1.3 7.6 9.2 15
B 277/60/1 250/293 4.6 20.0 120 1.3 5.9 7.1 15
15A 208-230/60/1 197/254 9.9 42.0 155 3.2 13.1 15.6 25
B 277/60/1 250/293 7.1 43.0 170 2.9 10.0 11.8 20
18A 208-230/60/1 197/254 9.9 42.0 199 3.2 13.1 15.6 25
B 277/60/1 250/293 9.0 54.0 210 2.9 11.9 14.2 25
24A 208-230/60/1 197/254 10.8 46.0 450 3.4 14.2 16.9 30
B 277/60/1 250/293 10.9 60.0 450 2.9 13.8 16.5 25
30A 208-230/60/1 197/254 13.1 65.9 560 3.4 16.5 19.8 30
B 277/60/1 250/293 12.2 72.0 560 2.9 15.1 18.2 30
36A 208-230/60/1 197/254 18.6 79.0 650 3.4 22.0 26.7 50
B 277/60/1 250/293 16.0 87.0 650 2.9 18.9 22.9 40
Notes:nn Maximum circuit ampacity (MCA) =
1.25 x (FLA motor 1 + FLA motor 2 + FLA electric heat)nn Maximum overcurrent protection (MOP) =
(2.25 x FLA motor 1) + FLA motor 2 + FLA electric heatnn If the calculated MOP is within 10% of the next smaller available
fuse size, that fuse size shall be used. If not, the next larger fuse size above the calulated MOP must be used.nn If the selected MOP is smaller than the MCA, the selected MOP
must be increased to the next larger available fuse size above the MCA.nn If the MOP is less than 15, it shall be rounded up to 15 amps. This
is the minimum fuse or circuit breaker permitted by code.
nn EC motor nameplate amperage indicates the motor hardware peak amperage while the motor full load amperage (FLA) is limited by the motor’s factory programmed operating range, programmed specifically for each unit size. The programmed operating range is generally only a portion of the motor hardware full potential resulting in the motor FLA being lower than the nameplate FLA. Motor FLA will be reflected on the Fan Coil serial tag and should be used when sizing building electrical requirements.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 11 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Electrical data
High static EC motors
SizeVoltage
codeRated voltage
(V/Hz/Ph)Voltage
min./max.Compressor
FLATotal unit
FLAMin. circuit
AmpsMax. fuse/HACR sizeRLA LRA
09A 208-230/60/1 197/254 4.7 20.0 2.9/2.6 7.6/7.3 8.8/8.5 15
B 277/60/1 250/293 3.3 18.8 2.5 5.8 6.6 15
12A 208-230/60/1 197/254 6.3 27.0 2.9/2.6 9.2/8.9 10.8/10.5 20
B 277/60/1 250/293 4.6 20.0 2.5 7.1 8.3 15
15A 208-230/60/1 197/254 9.9 42.0 8.1/7.3 18.0/17.2 20.5/19.7 30
B 277/60/1 250/293 7.1 43.0 5.5 12.6 14.4 20
18A 208-230/60/1 197/254 9.9 42.0 8.1/7.3 18.0/17.2 20.5/19.7 30
B 277/60/1 250/293 9.0 54.0 5.5 14.5 16.8 25
24A 208-230/60/1 197/254 10.8 46.0 8.1/7.3 18.9/18.1 21.6/20.8 30
B 277/60/1 250/293 10.9 60.0 5.5 16.4 19.1 30
30A 208-230/60/1 197/254 13.1 65.9 8.1/7.3 21.2/20.4 24.5/23.7 40
B 277/60/1 250/293 12.2 72.0 5.5 17.7 20.8 30
36A 208-230/60/1 197/254 18.6 79.0 8.1/7.3 26.7/25.9 31.4/30.6 50
B 277/60/1 250/293 16.0 87.0 5.5 21.5 25.5 40
Notes:nn Maximum circuit ampacity (MCA) =
1.25 x (FLA motor 1 + FLA motor 2 + FLA electric heat)nn Maximum overcurrent protection (MOP) =
(2.25 x FLA motor 1) + FLA motor 2 + FLA electric heatnn If the calculated MOP is within 10% of the next smaller available
fuse size, that fuse size shall be used. If not, the next larger fuse size above the calulated MOP must be used.nn If the selected MOP is smaller than the MCA, the selected MOP
must be increased to the next larger available fuse size above the MCA.nn If the MOP is less than 15, it shall be rounded up to 15 amps. This
is the minimum fuse or circuit breaker permitted by code.
nn EC motor nameplate amperage indicates the motor hardware peak amperage while the motor full load amperage (FLA) is limited by the motor’s factory programmed operating range, programmed specifically for each unit size. The programmed operating range is generally only a portion of the motor hardware full potential resulting in the motor FLA being lower than the nameplate FLA. Motor FLA will be reflected on the Fan Coil serial tag and should be used when sizing building electrical requirements.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 12 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Octave band sound power level
SizeUnit test
operation mode
With single supply double deflection grille with standard perimeter bypass Allen lock, removable
125 250 500 1000 2000 4000 8000
09
Fan only: low speed 52.3 50.5 46.0 41.1 33.6 32.1 31.0
Fan only: high speed 52.9 51.0 47.4 41.5 33.9 32.8 31.1
Cooling: low speed 53.5 51.5 47.6 41.7 34.4 32.9 31.1
Cooling: high speed 56.5 54.3 50.1 44.3 37.9 36.3 31.8
Heating: low speed 53.9 51.0 48.4 42.4 34.9 33.2 33.1
Heating: high speed 56.2 53.8 50.2 44.2 37.5 36.3 32.8
12
Fan only: low speed 54.8 52.3 40.1 43.3 37.5 36.5 32.7
Fan only: high speed 54.4 52.1 37.6 43.4 36.9 38.6 32.2
Cooling: low speed 56.0 53.3 49.6 43.9 38.3 36.6 32.8
Cooling: high speed 58.0 55.4 41.7 46.2 40.9 39.2 34.2
Heating: low speed 60.9 54.2 49.9 44.2 37.6 36.4 33.8
Heating: high speed 60.7 56.2 51.7 45.8 39.6 38.6 34.4
15
Fan only: low speed 58.9 57.8 54.0 51.5 45.0 43.7 38.4
Fan only: high speed 59.2 59.1 54.3 52.6 45.2 44.7 41.3
Cooling: low speed 60.1 58.8 55.6 52.1 45.8 44.5 38.6
Cooling: high speed 62.8 62.4 58.2 55.4 49.1 48.1 41.8
Heating: low speed 61.3 59.3 56.4 52.3 45.4 44.1 39.1
Heating: high speed 63.8 62.3 58.1 55.2 48.4 47.7 41.7
18
Fan only: low speed 62.0 60.9 55.9 54.9 48.3 47.4 42.1
Fan only: high speed 61.6 60.9 55.4 53.6 47.8 47.0 44.2
Cooling: low speed 63.3 61.9 57.4 55.5 49.1 48.2 42.3
Cooling: high speed 65.1 64.1 59.4 57.5 51.3 50.5 44.8
Heating: low speed 63.8 61.9 57.9 55.1 48.3 47.1 42.0
Heating: high speed 65.1 63.9 59.4 57.5 50.3 49.2 43.7
24
Fan only: low speed 60.7 58.6 54.1 48.3 42.3 38.4 35.7
Fan only: high speed 59.6 58.7 54.8 49.2 43.1 39.2 36.9
Cooling: low speed 61.9 59.6 55.7 48.9 43.1 39.2 35.9
Cooling: high speed 63.1 62.0 58.9 52.0 47.1 43.0 37.5
Heating: low speed 63.7 60.8 57.9 51.1 44.8 40.5 38.4
Heating: high speed 65.7 63.2 59.4 52.3 48.7 44.1 39.6
30
Fan only: low speed 67.4 63.7 58.8 54.3 49.9 45.7 41.3
Fan only: high speed 65.2 64.2 58.7 55.8 50.4 46.9 44.0
Cooling: low speed 68.6 64.8 60.2 54.8 50.7 46.6 41.5
Cooling: high speed 68.8 67.4 63.0 58.5 54.2 50.3 44.5
Heating: low speed 69.7 65.7 61.2 56.1 51.9 47.8 41.9
Heating: high speed 68.7 67.7 63.2 58.6 54.4 50.3 44.8
36
Fan only: low speed 70.2 68.0 62.1 59.1 56.6 50.1 45.1
Fan only: high speed 70.3 68.1 63.2 65.3 56.6 50.3 46.8
Cooling: low speed 71.4 68.6 62.1 59.4 56.7 50.4 45.2
Cooling: high speed 71.5 69.8 64.0 65.4 56.2 52.1 47.0
Heating: low speed 69.9 68.3 63.0 60.1 58.5 51.3 45.8
Heating: high speed 70.5 69.6 64.0 60.9 58.8 53.0 47.7
Notesnn All are sound power level in dB referenced to one picoWattnn Data is based on sound measurements made in a reverberant room on representative units from each cabinet size in accordance with AHRI Standard 350-86
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 13 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
R
RC
C
Y1
AL
G
O
Y2
Note 3
Typical 24VAC2-Stage stat
4
L1
Com2 modbus address
8
J1
123
OR
AN
GE
240
V
Brown
Black
BlueYellow
White
Red
Yellow
O
W
AL
G
Y2
Y1
C
R
Note 2
Note 2ES
NSB
JP1
JP2
P3
COM
NC2
COM
NC1
NO2
NO1R
R
COM 2
COM
COM 1
Note 4Optional
Disconnect Switch
G
208-230V/60HZ/1PHPower Supply
Unit
L1L2
T2 T1CC
BlueBlack
78
5
63
41
27
85
63
12
OrangeOrangeRedRedBlackBlack
CO1
RV
LP
HP
FP1T
FP2T
LWT
DAT
T
T
Black
Black
Com2 modbus address7654321
Com2 modbus address
Com2/com1RV=Cooling OFF/ONTstat=Comm/24VACFP1=GLYCOL / WATERTest/Normal
SW1 Off/On
Power
LD 1
CCG
CC CC
P6
HP
LPR
Vco
12
34
56
78
8
LWT
DA
TFP
1FP
2
12
34
65
7
White
Orange
BLA
CK
CO
M
Blue
Orange
Yellow
Note 1
LD 4
LD 3
LD 2
H
MotorBlower
PSC
MLL2
GrnYel
Gry
Cap
Transformer
24V
R
P5
C
BR2
BR1
P4
P2
P1
S C
Compressor
R
Zone valve
+(A)
- (B)
+(NETA)- (NETB)
24VAC+-
Fieldinstalled
wiring
Connect tonetwork
L2
Note 5
ACCESSORYRELAY 1
ACCESSORYRELAY 2
Brown
Black
WhiteBlack
YellowYellow
White
Black
Black
See blowerspeed wiring chart for wire
colors
RE
D 2
08V
Blue Capacitor
CAP
OptionalBACnet or
Lonworks card
See Note 6
Blower speed wiringUnit Size
Orange Brown Blue Red
09 Low High
12 Low High
15 Low High
18 Low High
24 Low High
30 Low High
36 Low High
Factory low voltage wiring
Factory high voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
Internal PCB connection
Quick connect terminal
Screw terminal
CC Compressor contactor
BR1 Fan enable relay
BR2 Fan speed relay
HP High pressure switch
LP Low pressure switch
FP1 Freeze protection water side
FP2 Freeze protection air side
CO Condensate overflow
RV Reversing valve
DAT Discharge air temperature
LWT Leaving water temperature
Relay coil
Capacitor
High pressure switch
Low pressure switch
Temperature thermistor
Condensate switch
Relay contacts
Legend
Wiring diagram, 208-230V standard and high static
Notes1. Used for optional communicating thermostat.2. Cut JP1 or JP2 for dry contact output on accessory relay 1 and 2.3. If a single stage thermostat is used place a jumper wire between Y1
and Y2 at P1 terminal.
4. If disconnect option is not installed connect line power to the L1 and L2 lugs on the compressor contactor.
5. Accessory relays 24VAC max. Activated by compressor output.6. All 208-230V units are factory wired for 208V operation. If supplier
voltage is 230V, installer must rewire transformer.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 14 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Wiring diagram, 208-230V EC motor
R
RC
C
Y1
AL
G
O
Y2
Note 3
Typical 24VAC2-Stage stat
4L1
Com2 modbus address
8
J1
123
OR
AN
GE
240
V
Brown
Black
BlueYellow
White
Red
Yellow
O
W
AL
G
Y2
Y1
C
R
Note 2
Note 2ES
NSB
JP1
JP2
P3
COM
NC2
COM
NC1
NO2
NO1RR
COM 2
COM
COM 1
Note 4Optional
Disconnect Switch
G
208-230V /60HZ/1PHPower Supply
Unit
L1L2
T2 T1CC
BlueBlack
78
5
63
41
27
85
63
12
OrangeOrangeRedRedBlackBlack
CO1
RV
LP
HP
FP1T
FP2T
LWT
DAT
T
T
Black
Black
Com2 modbus address7654321
Com2 modbus address
Com2/com1RV=Cooling OFF/ONTstat=Comm/24VACFP1=GLYCOL / WATERTest/Normal
SW1 Off/On
Power
LD 1
CCG
CC CC
P6
HP
LPR
Vco
12
34
56
78
8
LWT
DA
TFP
1FP
2
12
34
65
7
SEE MOTOR CHART
Orange
BLA
CK
CO
M
Blue
SEE MOTOR CHART
Yellow
Note 1
LD 4
LD 3
LD 2
MotorBlower
ECMGrn
Transformer
24V
R
P5
C
BR2
BR1
P4
P2
P1
S C
Compressor
R
Zone valve
+(A)
- (B)
+(NETA)- (NETB)
24VAC+-
Fieldinstalled
wiring
Connect tonetwork
L2
Note 5
ACCESSORYRELAY 1
ACCESSORYRELAY 2
Brown
Black
WhiteBlack
YellowYellow
White
Black
Black
TWO 24VACDISCRETESPEEDS
RE
D 2
08V
Blue Capacitor
CAP
OptionalBACnet or
Lonworks card
See Note 6
MOTORHARNESS
SE
E M
OTO
R C
HA
RT
SE
E M
OTO
R C
HA
RT
SEE MOTOR CHART
Factory low voltage wiring
Factory high voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
Internal PCB connection
Quick connect terminal
Screw terminal
CC Compressor contactor
BR1 Fan enable relay
BR2 Fan speed relay
HP High pressure switch
LP Low pressure switch
FP1 Freeze protection water side
FP2 Freeze protection air side
CO Condensate overflow
RV Reversing valve
DAT Discharge air temperature
LWT Leaving water temperature
Relay coil
Capacitor
High pressure switch
Low pressure switch
Temperature thermistor
Condensate switch
Relay contacts
Legend
Notes1. Used for optional communicating thermostat.2. Cut JP1 or JP2 for dry contact output on accessory relay 1 and 2.3. If a single stage thermostat is used place a jumper wire between Y1
and Y2 at P1 terminal.
4. If disconnect option is not installed connect line power to the L1 and L2 lugs on the compressor contactor.
5. Accessory relays 24VAC max. Activated by compressor output.6. All 208-230V units are factory wired for 208V operation. If supplier
voltage is 230V, installer must rewire transformer.
Wire colors Discrete speeds Power leads
1st spd 2nd spd Comm L1 L23/4 HP Red Blue Brown Black White1/4 HP Purple White Blue Black Red
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 15 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
R
RC
C
Y1
AL
G
O
Y2
Note 3
Typical 24VAC2-Stage stat
4
L1
Com2 modbus address8
J1
123
BrownBlack
BlueYellowWhiteRed
Yellow
O
W
AL
G
Y2
Y1
C
R
Note 2
Note 2ES
NSB
JP1
JP2
P3
COM
NC2
COM
NC1
NO2
NO1RR
COM 2
COM
COM 1
Note 4Optional
Disconnect Switch
G
277V/60HZ/1PHPower Supply
Unit
L1L2
T2 T1CC
BlueBlack
78
5
63
41
27
85
63
12
OrangeOrangeRedRedBlackBlack
CO1
RV
LP
HP
FP1T
FP2T
LWT
DAT
T
T
Black
Black
Com2 modbus address7654321
Com2 modbus addressCom2/com1RV=Cooling OFF/ONTstat=Comm/24VACFP1=15°F/32°FTest/Normal
SW1 Off/On
Power
LD 1
CCG
CC CC
P6
HP
LPR
Vco
12
34
56
78
8
LWT
DA
TFP
1FP
2
12
34
65
7
White
Orange
BLAC
K C
OM
Blue
Orange
Yellow
Note 1
LD 4
LD 3
LD 2
H
MotorBlower
PSC
MLL2
GrnYel
Gry
Cap
Transformer
24V
CR
R
P5
C
BR2
BR1
P4
P2
P1
S C
Compressor
R
Zone valve
+(A)
- (B)
+(NETA)- (NETB)
24VAC+-
Fieldinstalled
wiring
Connect tonetwork
L2
Note 5
ACCESSORYRELAY 1
ACCESSORYRELAY 2
Brown
Black
WhiteBlack
YellowYellow
White
Black
Black
See blowerspeed wiring chart for wire
colors
BRO
WN
277
V
Blue Capacitor
OptionalBACnet or
Lonworks card
See Note 6
Blower speed wiringUnit Size
Orange Brown Black Blue Red
09 Low High
12 Low High
15 Low High
18 Low High
24 Low High
30 Low High
36 Low High
Wiring diagram, 277V standard and high static
Factory low voltage wiring
Factory high voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
Internal PCB connection
Quick connect terminal
Screw terminal
CC Compressor contactor
BR1 Fan enable relay
BR2 Fan speed relay
HP High pressure switch
LP Low pressure switch
FP1 Freeze protection water side
FP2 Freeze protection air side
CO Condensate overflow
RV Reversing valve
DAT Discharge air temperature
LWT Leaving water temperature
Relay coil
Capacitor
High pressure switch
Low pressure switch
Temperature thermistor
Condensate switch
Relay contacts
Legend
Notes1. Used for optional communicating thermostat.2. Cut JP1 or JP2 for dry contact output on accessory relay 1 and 2.3. If a single stage thermostat is used place a jumper wire between Y1
and Y2 at P1 terminal.
4. If disconnect option is not installed connect line power to the L1 and L2 lugs on the compressor contactor.
5. Accessory relays 24VAC max. Activated by compressor output.6. All 208-230V units are factory wired for 208V operation. If supplier
voltage is 230V, installer must rewire transformer.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 16 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Wiring diagram, 277V EC motor
R
RC
C
Y1
AL
G
O
Y2
Note 3
Typical 24VAC2-Stage stat
4
L1
Com2 modbus address
8
J1
123
Brown
Black
BlueYellow
White
Red
Yellow
O
W
AL
G
Y2
Y1
C
R
Note 2
Note 2ES
NSB
JP1
JP2
P3
COM
NC2
COM
NC1
NO2
NO1RR
COM 2
COM
COM 1
Note 4Optional
Disconnect Switch
G
277V /60HZ/1PHPower Supply
Unit
L1L2
T2 T1CC
BlueBlack
78
5
63
41
27
85
63
12
OrangeOrangeRedRedBlackBlack
CO1
RV
LP
HP
FP1T
FP2T
LWT
DAT
T
T
Black
Black
Com2 modbus address7654321
Com2 modbus address
Com2/com1RV=Cooling OFF/ONTstat=Comm/24VACFP1=GLYCOL / WATERTest/Normal
SW1 Off/On
Power
LD 1
CCG
CC CC
P6
HP
LPR
Vco
12
34
56
78
8
LWT
DA
TFP
1FP
2
12
34
65
7
SEE MOTOR CHART
Orange
BLA
CK
CO
M
Blue
SEE MOTOR CHART
Yellow
Note 1
LD 4
LD 3
LD 2
MotorBlower
ECMGrn
Transformer
24V
R
P5
C
BR2
BR1
P4
P2
P1
S C
Compressor
R
Zone valve
+(A)
- (B)
+(NETA)- (NETB)
24VAC+-
Fieldinstalled
wiring
Connect tonetwork
L2
Note 5
ACCESSORYRELAY 1
ACCESSORYRELAY 2
Brown
Black
WhiteBlack
YellowYellow
White
Black
Black
TWO 24VACDISCRETESPEEDS
BR
OW
N 2
77V
Blue Capacitor
OptionalBACnet or
Lonworks card
MOTORHARNESS
SE
E M
OTO
R C
HA
RT
SE
E M
OTO
R C
HA
RT
SEE MOTOR CHART
Factory low voltage wiring
Factory high voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
Internal PCB connection
Quick connect terminal
Screw terminal
CC Compressor contactor
BR1 Fan enable relay
BR2 Fan speed relay
HP High pressure switch
LP Low pressure switch
FP1 Freeze protection water side
FP2 Freeze protection air side
CO Condensate overflow
RV Reversing valve
DAT Discharge air temperature
LWT Leaving water temperature
Relay coil
Capacitor
High pressure switch
Low pressure switch
Temperature thermistor
Condensate switch
Relay contacts
Legend
Notes1. Used for optional communicating thermostat.2. Cut JP1 or JP2 for dry contact output on accessory relay 1 and 2.3. If a single stage thermostat is used place a jumper wire between Y1
and Y2 at P1 terminal.
4. If disconnect option is not installed connect line power to the L1 and L2 lugs on the compressor contactor.
5. Accessory relays 24VAC max. Activated by compressor output.6. All 208-230V units are factory wired for 208V operation. If supplier
voltage is 230V, installer must rewire transformer.
Wire colors Discrete speeds Power leads
1st spd 2nd spd Comm L1 L23/4 HP Red Blue Brown Black White1/4 HP Purple White Blue Black Red
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 17 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Dimensions and data: stand alone unit (VHNA)
* Supply grille rough-in dimensions
Top view
88"
3"
104"
-
115
"
Risers
65-5
/16"
2-1/4"
GF
DE
Swage
Return
Supply
Condensate drain
A
A
2-1/2"
Front view
Filter
Optional 24V thermostat location
Return air opening
Optional disconnect switch location
Hose kits
Motor/blower assembly
Control box
Knockout dimensions typical for all
Chassis
Factory-installed P-trap
Air coil drain pan
Control box access panel
Optional auto flow regulator location
(return side)Optional water valve location(supply side)
Condensate drain pan
Right view
Air coil
Optional duct connection
C B
1" 3"
N
3-1/4"
2-3/8"
HI
J
K
MH
L
2-1/8"
2-5/16"
2-11/16"
1-5/8"
57-1
/8"
39-1
/2"
2-7/
8"
Unit dimensions: 88" height
Dimension Models 09-18 Models 24-36
A 18" 24-1/4"
B 8" 10"
C 12" 14"
D 10" 12"
E 14" 16"
F 54-11/16" 55-1/2"
G 5-9/16" 5-5/8"
H 2-1/16" 4-1/8"
I 4-1/16" 6-1/8"
J 1-15/16" 4-1/16"
K 3-5/16" 6-1/16"
L 1-1/4" 1-7/16"
M 3-1/4" 3-7/16"
N 4-3/4" 8-13/16"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 18 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Dimensions and data: master (VHNM)
* Supply grille rough-in dimensions
Top view
88"
3"
104"
-
115
"
Risers
65-5
/16"
2-1/4"
GF
DE
Swage
Return
Supply
Condensate drain
A
A
2-1/2"
Front view
Filter
Optional 24V thermostat location
Return air opening
Optional disconnect switch location
Hose kits
Motor/blower assembly
Control box
Knockout dimensions typical for all
Chassis
Factory-installed P-trap
Air coil drain pan
Control box access panel
Optional auto flow regulator location
(return side)Optional water valve location(supply side)
Condensate drain pan
Right view
Air coil
Optional duct connection
C B
1" 3"
N
3-1/4"
2-3/8"
HI
J
K
MH
L
3"
2-1/8"
2-5/16"
2-11/16"
1-5/8"
57-1
/8"
39-1
/2"
2-7/
8"
Unit dimensions: 88" height
Dimension Models 09-18 Models 24-36
A 18" 24-1/4"
B 8" 10"
C 12" 14"
D 10" 12"
E 14" 16"
F 54-11/16" 55-1/2"
G 5-9/16" 5-5/8"
H 2-1/16" 4-1/8"
I 4-1/16" 6-1/8"
J 1-15/16" 4-1/16"
K 3-5/16" 6-1/16"
L 1-1/4" 1-7/16"
M 3-1/4" 3-7/16"
N 4-3/4" 8-13/16"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 19 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Dimensions and data: slave (VHNS)
* Supply grille rough-in dimensions
Top view
88"
65-5
/16"
2-1/4"
GF
DE
A
A
Front view
Filter
Optional 24V thermostat location
Return air opening
Optional disconnect switch location
Hose kits
Motor/blower assembly
Control box
Knockout dimensions typical for all
Chassis
Factory-installed P-trap
Air coil drain pan
Control box access panel
Optional auto flow regulator location
(return side)Optional water valve location(supply side)
Condensate drain pan
Right view
Air coil
Optional duct connection
C B
1" 3"
N
3-1/4"
2-3/8"
HI
J
K
MH
L
2-1/8"
2-5/16"
2-11/16"
1-5/8"
57-1
/8"
39-1
/2"
2-7/
8"
Unit dimensions: 88" height
Dimension Models 09-18 Models 24-36
A 18" 24-1/4"
B 8" 10"
C 12" 14"
D 10" 12"
E 14" 16"
F 54-11/16" 55-1/2"
G 5-9/16" 5-5/8"
H 2-1/16" 4-1/8"
I 4-1/16" 6-1/8"
J 1-15/16" 4-1/16"
K 3-5/16" 6-1/16"
L 1-1/4" 1-7/16"
M 3-1/4" 3-7/16"
N 4-3/4" 8-13/16"
Note: Riser knockouts are 2-1/2" center to center
SupplyCondensateReturnSupply
CondensateReturn
SlaveMaster
Reference only: Field piping to master by others. Ensure master and slave are connected supply-to-supply and return-to-return
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 20 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Dimensions and data: chassis
B
C
A
B
C
A
B
C
A
Unit size A B C
09-1216-1/32"
37"16-3/32"
15-18 44"
24-36 22-1/32" 46" 23"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 21 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
2"
9"
44-21/32"
43-5/16"
11-17/32"
4-3/8"
2-27/32"
Right side view
Sizes 24-36
Sizes 09-18
Knockout location for risers
Back of cabinet
5"
6-3/8"6-3/8"
9"
2-27/32"
Rear view (back)
2"
4-3/8"
9"
2-27/32"
11-17/32"
44-21/32"
43-5/16"
Left side view
Knockout location for condensate drain
Front of cabinet
5-1/4"
9-1/2"9-1/2"
12"
3-1/2"
Rear view (back)
2-1/2"
6"
12"
3-1/2"
11-17/32"
39-1/2"
48-1/2"
Left side view
Knockout location for condensate drain
Front of cabinet
3-1/2"
2-1/2"
12"
39-1/2"
48-1/2"
6"
3-1/2"
Right side view
Knockout location for risers
Back of cabinet
3-1/2"
11-17/32"
Riser slot arrangements
Note:nn Right and left are determined by facing front of cabinet
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 22 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
GeneralFurnish and install Vertical Stack Water Source Heat Pumps where indicated on the plans and in the specifications, with required mounting components and accessories. All units shall be capable of meeting or exceeding the scheduled capacities for cooling, heating and air delivery. Units shall be ETL certified for the United States and Canada in compliance with UL/ANSI Standard 1995 and CSA C22.2 No. 236-05, and be certified as complying with ANSI/ARI/ASHRAE/ISO Standard 13256-1. ConstructionAll unit cabinet panels shall be fabricated of 20-gauge galvanized steel panels. All cabinet panels shall be insulated with ½" thick 2 lb density matt-faced fiberglass [½" thick foil faced fiberglass with scrim and taped edges to prevent any fibers from reaching the airstream] [½" thick elastomeric closed cell foam insulation]. Insulation shall conform to NFPA 90A for fire, smoke and melting, and comply with a 25/50 Flame Spread and Smoke Developed Index per ASTM E-84 or UL 723. Additionally, insulation shall comply with Antimicrobial Performance Rating of 0, no observed growth, per ASTM G-21.
All unit panels shall have knockouts for supply air openings and riser slots to facilitate the field conversion of riser location and supply air grille location.
nn Option: Supply air opening knockouts shall be factory sealed and left in place during shipping and staging at the job site.
The removable perimeter bypass with Allen lock [hinged perimeter bypass with Allen lock] [hinged perimeter bypass with key lock] [removable perimeter bypass with Allen lock] [removable louvered with Allen lock] front access panel shall be fabricated of not less than 18-gauge [16-gauge] [14-gauge] cold rolled steel.
The front panel mounts within a frame that is flush with the wall. A front panel that protrudes from the wall is not acceptable.
nn Option: Provide an architectural grade double deflection [single deflection] [double deflection opposed blade damper] aluminum discharge grille.
Mechanical specifications Models VHNA, VHNM and VHNS
Painted finishAll front return panels, mounting frames and supply air grilles shall be finished with a standard ivory epoxy powder coat paint. Optional colors can be selected from the Zehnder Rittling Color Chart. Liquid coat paint shall not be acceptable. Custom colors are also available with the submission of a color chip for color match.
nn Option: For units with multiple outlets, include a sheet metal baffle, insulated on 2 sides, inside the discharge plenum to break the sight lines between the two discharge outlets and to attenuate room noise that could be transmitted through the openings.
PowerUnits shall not exceed scheduled power consumption.
Fan and motorUnit fan shall be dynamically balanced, forward curved, DWDI centrifugal type constructed of galvanized steel for corrosion resistance. Motors shall be 208-230V/60Hz/1Ph [277V/60Hz/1Ph] permanent split-capacitor [electronically commutated high-efficiency, programmable brushless DC], totally enclosed, tap wound for 2-speed, permanently lubricated sleeve bearing, type with automatic reset integral thermal overload protection and resiliently mounted. High static motors are available for ducted applications. Shaded pole motors are not acceptable. Single speed motors are not acceptable. Prior to shipping, all motors shall be assembled, factory tested and installed in the unit
The fan/motor assembly shall be constructed of 18-gauge galvannealed steel and installed in a z-channel mounting frame for ease of sliding fan/motor deck in and out through the front panel. Each fan/motor assembly shall be fastened by no more than 2 screws. The motor shall have a quick connect to allow service and removal without the need for tools.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 23 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
ChassisThe chassis consists of a compressor, complete refrigeration and water piping circuits, copper coaxial heat exchanger and incorporates a coated hydrophilic aluminum air coil for enhanced condensate drainage. A rotary or scroll compressor utilizes R-410A refrigerant. All units are equipped with two drop down service legs to support the chassis when testing or servicing is required. All units feature wheels on the bottom of the chassis that allow for easy installation and removal during installation or servicing. Front facing refrigerant test ports are accessible without removing the chassis.
Drain panPrimary condensate drain pans shall be single wall, 20-gauge stainless steel for superior corrosion resistance. Drain pans shall be of one piece construction and be positively sloped in 2 directions for condensate removal. An easily removable rubber p-trap shall be furnished, factory piped to the condensate drain riser, held in place by 2 compression clamps. A condensate level sensor is provided to eliminate power to unit if drain pan becomes clogged.
The primary drain pan shall be externally insulated with elastomeric closed cell foam insulation. The insulation shall carry no more than a 25/50 Flame Spread and Smoke Developed Rating per ASTM E-84 and UL 723 and an Antimicrobial Performance Rating of 0, no observed growth, per ASTM G-21. Internally sprayed insulation will not be acceptable.
CoilsThe air coil shall optimize rows to meet the specified capacity. Coils shall have 3/8" OD seamless copper tubes and shall be mechanically expanded to provide an efficient, permanent bond between the tube and aluminum fin. Minimum copper tube thickness shall be 0.012".
Fins shall have high efficiency aluminum surface optimized for heat transfer, air pressure drop and carryover. Minimum fin thickness shall be 0.0045". Lanced fins shall not be acceptable.
All coils shall be tested at 500 PSIG with helium and rated for a maximum 600 PSIG working pressure.
Coil casing shall be fabricated from galvanized steel [stainless steel].
FiltersAll units shall be furnished with a washable nylon type filter [1" nominal glass fiber throwaway] filter. Filters are held in place by four (4) filter clips and shall be tight fitting to prevent air bypass.
ElectricalUnits shall be furnished with single point power connection. All electrical terminations to be made in terminal strip. The factory mounted terminal wiring strip consists of a multiple position screw terminal block to facilitate wiring terminations for the electric control valve and thermostat. The control box shall contain a 50VA transformer, 24V secondary voltage with 2A low voltage circuit breaker, 2-pole compressor contactor and microprocessor controller.
The reversing valve, fan motor and unit safety controls wiring shall be connected to the microprocessor for unit operation and monitoring. The units shall be name-plated for use with time delay fuses or HACR circuit breakers.
The unit controls shall be 24V and provide heating or cooling as required by the remote thermostat. The microprocessor can accept either a standard 24V digital, non-programmable thermostat [digital, programmable thermostat] [digitally communicating thermostat with IR remote control operation] designed to control up to two independently energized fan speeds. Thermostat will be provided with wiring harness complete with quick connect and pre-wired to terminal blocks.
nn Option: Provide a service disconnect switch to isolate power from the unit during maintenance.
Primary internal wiring and testing shall be conducted at the factory. All units shall be shipped with wiring diagrams.
Mechanical specifications Models VHNA, VHNM and VHNS
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 24 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Hose kitsnn Option: Provide a standard factory assembled and mounted ½” [3/4”] 2-way, on/off, 24V normally closed zone valve. Control valve shall be wired to terminal blocks through quick connect to allow service and replacement of valves. Maximum entering water temperature on the control valve shall be 200°F, and maximum operating pressure shall be 300 PSIG. nn Option: Piping packages shall include stainless steel braided hoses to allow for thermal expansion within the unit cabinet. The hose shall be EPDM inner lined and Kevlar® reinforced, with stainless steel FNPT swivels and/or fittings. The hoses shall be rated for a maximum 450 PSIG working pressure at 250°F, and shall conform to NFPA 90A and carry no more than a 25/50 Flame Spread and Smoke Developed Rating, per ASTM E-84 and UL 723.nn Option: Provide a y-strainer with pressure-temperature ports (P/T) on supply line.nn Option: Provide a fixed flow control device with pressure-temperature ports (P/T) on return line.
Piping packages shall be completely factory assembled including interconnecting pipe and factory tested for leaks.
RisersFurnish chilled and hot water supply and return risers mounted to the unit. Risers shall be Type-M seamless copper tube and include 3" deep swaged connections at the top for connection to the unit above. Slip couplings are not acceptable.
nn Option: Provide Type-L copper risers that meet or exceed the requirements stated above.
Risers shall be insulated with ½" closed cell foam insulation covering the entire riser. Insulation shall conform to NFPA 90A and carry no more than a 25/50 Flame Spread and Smoke Developed Rating, per ASTM E-84 and UL 723.
nn Option: Provide ¾" closed cell foam insulation that meets or exceeds the requirements stated above.nn Option: Risers to be provided without insulation.
Condensate drain risers shall be Type-M seamless copper tube and meet the requirements stated above.
nn Option: Risers shall be factory fabricated, bundled, and tagged separate from the heat pump units, allowing for shipment and installation of risers prior to the heat pumps.
Units shall be manufactured in accordance with ISO 9001:2008 standards established and maintained by Zehnder Rittling.
Mechanical specifications Models VHNA, VHNM and VHNS
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 25 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Standard 24VAC sequence of operation
Random start delayWhen the unit is first powered “on” the control microprocessor will generate a random number to determine the start delay of the compressor operation (3-5 minutes). This delay is used to prevent multiple units from cycling “on” at the same time. The purpose is to prevent a large power load on the building electrical system after a power outage. After the number, or delay time, is generated the microprocessor will use it to determine the minimum amount of time delay before the compressor is cycled “on” after a demand is received from the thermostat.
Anti-short cycling delayAfter the random start delay is generated the microprocessor will use it to determine the minimum amount of delay before the compressor is cycled “on” after a demand is received from the thermostat. This allows the refrigerant system to equalize in pressure and prevents short-cycling of the compressor.
Minimum compressor runtimeThe minimum compressor runtime of each cycle, heating or cooling, is sixty seconds. Once the compressor is energized it will not de-energize until the minimum runtime is satisfied, even if the thermostat input is removed. Cooling 1st stage (Y1, O)When the microprocessor receives (Y1, O) at the 24VAC thermostat input connection, the unit will proceed with the cooling 1st stage sequence. The microprocessor must receive these signals for two continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/de-energize after five seconds. The microprocessor will then verify that the anti-short cycling delay has been satisfied. Once the anti-short cycling delay has been satisfied the compressor will cycle “on.” The blower will cycle “on” in low speed fifteen seconds after the compressor is cycled “on.”
Cooling 2nd stage (Y1, Y2, O)When the microprocessor receives (Y1, Y2, O) at the 24VAC thermostat input connection, the unit will proceed with the cooling 2nd stage sequence. The microprocessor must receive these signals for two continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid
the reversing valve will energize/de-energize after five seconds. The microprocessor will then verify that the anti-short cycling delay has been satisfied. Once the anti-short cycling delay has been satisfied the compressor will cycle “on.” The blower will cycle “on” in high speed 15 seconds after the compressor is cycled “on.”
Heating 1st stage (Y1)When the microprocessor receives (Y1) at the 24VAC thermostat input connection, the unit will proceed with the cooling 1st stage sequence. The microprocessor must receive these signals for two continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/de-energize after five seconds. The microprocessor will then verify that the anti-short cycling delay has been satisfied. Once the anti-short cycling delay has been satisfied the compressor will cycle “on.” The blower will cycle “on” in low speed fifteen seconds after the compressor is cycled “on.”
Heating 2nd stage (Y1, Y2)When the microprocessor receives (Y1, Y2) at the 24VAC thermostat input connection the unit will proceed with the heating 2nd stage sequence. The microprocessor must receive these signals for two continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/de-energize after five seconds. The microprocessor will then verify that the anti-short cycling delay has been satisfied. Once the anti-short cycling delay has been satisfied the compressor will cycle “on.” The blower will cycle “on” in high speed fifteen seconds after the compressor is cycled “on.”
Fan only mode (G)The fan only mode can only be used with a 24VAC thermostat and will energize the low speed blower when a (G) input has been received at the 24VAC thermostat input connection. When the input is removed the blower will de-energize immediately.
Honeywell 24 volt thermostats Non-Programmable and programmable thermostats use a control algorithm that uses both time and temperature difference from the setting to determine when to turn on stage 1 fan speed low and stage 2 fan speed hi. This logic therefore controls the room temperature to plus or minus 1 degree from set point.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 26 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Microprocessor control system
Microprocessor control systemUnits shall have a microprocessor control system. Units utilizing electro-mechanical control shall not be acceptable. The control system microprocessor board shall be specifically designed to protect against building electrical system noise contamination including high voltage spikes and brown-out situations, EMI, and RFI interference. The control system shall interface with a heat pump type thermostat or a digitally communicating thermostat.
Featuresnn Rapid system refrigerant pressure equalization to prevent hard compressor startsnn Anti-short cycle time delay on compressor operationnn Random start on power up modenn Low/high voltage protectionnn Unit shutdown on high or low refrigerant pressuresnn Unit shutdown on low water/air temperaturenn Condensate overflow electronic protection for unit drain pannn Option to reset unit at thermostat or disconnectnn If a fault occurs 3 times sequentially without thermostat meeting temperature, then lockout requiring manual reset will occurnn Time delay override for servicingnn Light emitting diodes (LED’s) on circuit board to indicate high or low pressure, high or low voltage, low water/air temperature, condensate overflow, control voltage status, temperature sensor failurenn The low-pressure switch shall not be monitored for the first 60 seconds after a compressor start command to prevent nuisance safety tripsnn 24V output to cycle a motorized water valve or other device with compressor contactor.nn Water coil low temperature sensing (dip switch selectable for water or anti-freeze)
nn Two stage control of cooling and heating modesnn Removable thermostat connectornn Two dry contact accessory relays that can be cycled with the compressor or the fannn Ability to work with heat pump thermostats using O or B reversing valve controlnn Emergency shutdown contactsnn Relay to operate an external dampernn Ability to automatically change fan speed from multistage thermostatnn 24V relay to start system pumpnn 50VA control transformer - shall have load side short circuit and overload protection via a built in circuit breaker
Digital communicating thermostatThe microprocessor control system shall communicate with thermostat to display (at the thermostat) the unit status, fault status, and specific fault condition. The digital communicating thermostat shall have an infrared remote control unit for operation of the temperature set point.
RS-485 communication portThe microprocessor shall have an RS-485 serial communication port that will allow connection of a PC. This port will allow read and write access to the microprocessor with proprietary software for maintenance and servicing functions. The RS-485 serial communication port shall also allow connections of BACnet and LonWorks application cards for connection to BAS systems.
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 27 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
SpecificationsHardware characteristic
nn Power supply: 24V AC/DC, 50/60 Hz
nn Power: <3W
nn Dimensions: 4-1/8" L x 2-3/4" W x 25/32" H (105 mm x 70 mm x 20 mm)
nn MODBUS side baud rate: 4800 (non-adjustable)
nn BACnet/MSTP side baud rate: option 4800, 9600, 19200 (configuration software can adjust)
nn Toggle switch: used to configure BACnet/MSTP ad-dress, 1-254 available. 0 and 255 is invalid. Facing the numbers 1-8, up is 1, down is 0. Cannot have dupli-cate address in one RS485 bus.
nn Red LED shows BACnet side communication n LED off: no communication n LED on: receive data n LED flashing: send data
nn Green LED shows MODBUS side communication n LED off: no communication n LED on: receive data n LED flashing: send data
nn Yellow LED shows running lights, normal for each 2 seconds out of a cycle
J1
123
P3 on microprocessor
COM 2
COM
+(A)
- (B)
+(NETA)- (NETB)
24VAC+-
Connect tonetwork
BACnet card
To 24V control transformer
BACnet control board
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 28 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
LonWorks control board
SpecificationsHardware characteristic
nn Power supply: 24V AC/DC, 50/60Hz
nn Power: <3W
nn Dimensions: 4-1/8" L x 2-3/4" W x 1" H (105 mm x 70 mm x 25 mm)
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 29 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Non-programmable digital thermostat
Features n Large, clear backlit display n Precise comfort control +/- 1° of your set temperature
n Heat 40°F to 90°F temperature range
n Cool 50°F to 99°F temperature range n Temperature control range stops n Soft-key, simplified controls n Easy change battery door - flips out without disassembling thermostat
n Automatic / manual selectable changeover n Built-in compressor protection: Minimum-off timer protects compressor from restarting too early after a shutdown
n Premier white®
Specifications n Temperature ranges:
� Heat: 40° to 90°F (4.5° to 32°C) � Cool: 50° to 99°F (10° to 37°C)
n Operating ambient temperature: � 32°F to 120°F (0°C to 48.9°C)
n Shipping temperature: � -20°F to 120°F (-28.9°C to 48.9°C)
n Operating relative humidity: � 5% to 90% (non-condensing)
Thermostat descriptionTerminal designation Description
Powering methods n Battery only n 20 to 30 Vac
System types
n 1 heat/1 cool conventional n 1 heat/1 cool heat pump (no aux. heat) n Heat only- 2-wire systems, 3-wire zone
valves and normally open zone valves n Heat only with fan n Cool only n 2 heat/1 cool heat pump (with aux. heat) n 2 heat/2 cool conventional n 2 heat/1 cool conventional n 1 heat/2 cool conventional n 2 heat/2 cool heat pump (no aux. heat) n 3 heat/2 cool heat pump (with aux. heat)
Changeover Manual or auto changeover selectable
System setting Heat-off-cool-auto-EM. heat
Fan setting Auto-on
Fan speeds Low, high
Electrical ratings
Terminal Voltage (50/60 Hz) Running current
W heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux/E) heating 20-30 Vac 0.02-1.0 A
Y cooling 20-30 Vac 0.02-1.0 A
Y2 cooling 20-30 Vac 0.02-1.0 A
G fan 20-30 Vac 0.02-0.5 A
O/B changeover 20-30 Vac 0.02-0.5 A
L output 20-30 Vac 0.02-0.5 A
Terminal designation Description
Rc 24VAC power from cooling transformer
R 24VAC power from heating transformer
O/B Changeover valve
Y Compressor contactor
Y2 Compressor contactor (stage 2)
G Fan relay
Aux/E Auxiliary/emergency heat relay
L Sends output when set to Em. heat
C 24VAC common
Note 1: Common wire is optional when thermostat is used with batteries
Dimensions in inches (mm)
Special functionComfort settingnn The thermostat will prioritize comfort over economy depending on
heat pump performance, load conditions and whether the thermostat is calling for the heat pump. Raising the temperature just a few degrees will often activate the auxiliary heat.
Economy settingnn The thermostat will attempt to reach the temperature setting without
activiating the auxiliary heat. The thermostat will wait to activate the auxiliary heat depending on heat pump performance, load conditions and how many degrees the temperature setting is changed.
Thermostat
5-13/16 (147)
3-9/16 (91)
1-1/2 (38)
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 30 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Programmable digital thermostat
Features n Selectable to 5-1-1 (weekdays, Saturday, Sunday) or 5-2 (weekdays, weekend)
n Large, clear backlit display, easy to read in various lighting conditions
n Available in large screen or standard display n Precise comfort control +/- 1°F, maintains consistent comfort to the highest level of accuracy
n Simplified programming and operation n Easy change battery door, flip out door allows for easy battery replacement without removing or disassembling the thermostat
n Adaptive Intelligent Recovery™ ensures programmed temperature is reached by programmed time
n Temperature range stops, prevents user from setting the temperature too high or too low
n Built in compressor protection: Minimum-off timer protects compressor from restarting too early after shutdown
n Premier white
Specifications n Temperature ranges:
� Heat: 40° to 90°F (4.5° to 32°C) � Cool: 50° to 99°F (10° to 37°C)
n Operating ambient temperature: � 32°F to 120°F (0°C to 48.9°C)
n Shipping temperature: � -20°F to 120°F (-28.9°C to 48.9°C)
n Operating relative humidity: � 5% to 90% (non-condensing)
Thermostat descriptionTerminal designation Description
Powering methods n Battery only n 20 to 30 Vac
System types
n 1 heat/1 cool conventional n 1 heat/1 cool heat pump (no aux. heat) n Heat only- 2-wire systems, 3-wire zone
valves and normally open zone valves n Heat only with fan n Cool only n 2 heat/1 cool heat pump (with aux. heat) n 2 heat/2 cool conventional n 2 heat/1 cool conventional n 1 heat/2 cool conventional n 2 heat/2 cool heat pump (no aux. heat) n 3 heat/2 cool heat pump (with aux. heat)
Changeover Manual or auto changeover selectable
System setting Heat-off-cool-auto-EM. heat
Fan setting Auto-on
Fan speeds Low, high
Electrical ratings
Terminal Voltage (50/60 Hz) Running current
W heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux/E) heating 20-30 Vac 0.02-1.0 A
Y cooling 20-30 Vac 0.02-1.0 A
Y2 cooling 20-30 Vac 0.02-1.0 A
G fan 20-30 Vac 0.02-0.5 A
O/B changeover 20-30 Vac 0.02-0.5 A
L output 20-30 Vac 0.02-0.5 A
Terminal designation Description
Rc 24VAC power from cooling transformer
R 24VAC power from heating transformer
O/B Changeover valve
Y Compressor contactor
Y2 Compressor contactor (stage 2)
G Fan relay
Aux/E Auxiliary/emergency heat relay
L Sends output when set to Em. heat
C 24VAC common
Note 1: Common wire is optional when thermostat is used with batteries
Dimensions in inches (mm)
Special functionAuto changeovernn When set to auto, the thermostat automatically selects heating or
cooling depending on the indoor temperature. The thermostat will automatically adjust heat and cool settings to maintain a 3-degree separation (fixed). nn Note: If you select Auto Changeover Only, the system setting on the
thermostat will stay locked in the auto position, preventing the user from changing it to Em heat, heat cool or off.
Adaptive Intelligent Recovery™nn Allows the thermostat to "learn" how long the furnace and air
conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
Compressor protectionnn Forces the compressor to wait a few minutes before restarting, to
prevent damage. During the wait time, the message 'Cool on' or 'Heat on' (heat pumps only) will flash on the display.
5-13/16 (147)1-1/2 (38)
Thermostat and wallplate
3-9/16 (91)
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 31 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Communicating thermostat
Electrical shock can cause personal injury or death. When installing or servicing system, always turn off main power to system. There may be more than one disconnect switch.
WARNING
Wiring harness provided with communicating thermostat
Plug P2Connection port to communicating thermostat
Plug P2Emergency shutdown, night setback and auxiliary contacts
Plug P124 volt thermostat terminal block (for use with standard 24V thermostats)
PCB inside electrical box of cabinetDip switch positions for proper communicating thermostat operation Dip Switch Position
Description
1 On
2Varies, depends on system temperatures
3 Off
4 On
5 On
6 Off
7 Off
8 Off
Temperature adjustment
Failure code display area
On/off power button
Fan: high/low
On/off power button
Sleep mode
Temperature adjustment
Mode: heat, cool or fan
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 32 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Digital communicating thermostat operating instructions
Featuresnn Precise comfort control (+/- 1 °F); maintains consistent comfort to the highest level of accuracy.nn Convert Celsius to Fahrenheitnn Set time and daynn Set or change timed power on and off setting in heating, cooling and fan only modesnn Set fan speed to low or highnn Change mode setting switches between the cooling, heating, auto or fan only modesnn Temperature inquiry allows you to check system temperatures at any timenn Communicating thermostat battery is dead
n If the battery is dead or not installed, the thermostat screen will not display the time but will still retain its set point. The thermostat will still function in heating or cooling mode.
nn Remote control for temperature setting, fan speed, on/off, mode and sleep.
Failure codesWhen the system fails, the corresponding failure code is displayed in the failure display area (lower right hand corner of the thermostat display). If no failure code(s) are present the area on the thermostat display will be blank:1. Refrigerant hi-pressure failure (lockout after 3 times)2. Refrigerant low pressure failure (lockout after 3 times)3. Not used4. Freeze protection water side (FP1) temperature
failure (lockout after 3 times)5. Freeze protection air side (FP2) temperature failure
(lockout after 3 times)6. Emergency shutdown input (ES) failure
(reset automatically)7. Night setback (NSB) failure (reset automatically)8. Communication failure (reset automatically)9. Condensate overflow switch (CO1) failure
(lockout after 3 times)10. Not used 11. Line voltage (OUV) over-voltage failure
(lockout after 3 times)12. Not used13. Low water temperature (LWT) sensor failure
(reset automatically)14. Discharge air temperature (DAT) sensor failure (reset
automatically)15. Freeze protection water side (FP1) sensor failure
(reset automatically)16. Freeze protection (FP2) sensor failure
(reset automatically)
Set system parametersTemp. area
Time area
d0Low voltage lockout lower limit (16-30V); 16V as default. Use temperature “-” or “+” to change setting, use humidify “+” or “-” to scroll up to d1.
d1Low voltage lockout upper limit (16-30V); 28V as default. Use temperature “-” or “+” to change setting, use humidify “+” or “-” to scroll up to d2.
d2Freeze protection air side (FP2) lockout temperature 35 ºF (2 °C) as default. Use temperature “-” or “+” to change setting, use humidify “+” or “-” to scroll up to d3.
d3
Auxiliary relay 1 (Plug P2 on PCB) parameter - C means relay 1 starts up along with the compressor, 9 means relay starts up along with the fan. Use temperature “-” or “+” to change setting, use humidify “+” or “-” to scroll up to d4.
d4Auxiliary relay 2 (Plug P2 on PCB) parameter - C means relay 2 starts up along with the compressor, 9 means relay 2 starts up along with the fan.
Note: Consult factory before changing settings.
Product specificationsMounting Typical 2-screw mounting
Changeover deadband 2 °F (1 °C)
Color Beige
Power method24VAC power from control board, 3VDC lithium battery back up (CR2032)
Connection type 4-pin plug
Switch positions (fan) Low and high
Switch positions (system) Cooling, heating, ventilation, off
Switch type Manual or auto
Accuracy ± 1 °F (0.5 °C)
Dimensions 4-3/4" W x 3-3/8" H x 3/4" D
Setting temperature range 55-90 °F (10-30 °C)
Electrical ratings 2W, 100mA
Frequency 50/60 Hz
Sensor element Thermistor
Operating humidity range <95%
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 33 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Contactor, 208-230V/277V/24V
Wiring
Main circuit rated capacityRated voltage
(Vac)Full load
current (A)Locked rotor
current (A)Resistance load
current (A)
240/277 40 200 50
480 40 160 50
600 40 120 50
Coil parametersRated
voltage (Vac)
50/60Hz
Coil resistance (W) ± 10%
Pull-in voltage
(Vac)
Free voltage
(Vac)
Rated power consumption
(reference value) (VA)
24 11 18 max. 6-15 6.5
LifeLife expectancy Number of requests Operating frequency
Mechanical life 500,000 3600/hour
Electrical life 200,000 360/hour
Locked rotor current test
10,000 180/hour
Other related parameters
1-5/8"
2-5/16" 1-5/8"
2"Ø7/32"
3-5/16"
2"
T1
A1
L1
A2
T2
L2
nn Mechanical parameter: riveting coil terminals installed should be able to withstand the strength 110N pulling force 5s.
nn Electrical data n Insulation resistance: 100M W min. n Voltage requirements: withstanding voltage 2200Vac/min., 5mA max.
n Contact voltage coils, withstanding voltage for the coil 2500Vac/min., 5mA max.
nn Usage n Applicable temperature: -40 to ~65 °C n Recommended screw tightening torque 2.5Nm
nn Safety certificates n UL508 file number 227250 n CSA file number 221260 n CE file number EN60947-4-1:2001
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 34 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
208/230/277V, 30A
Features n One-piece nickel-plated brass strap for superior corrosion-resistance
n Cam control and spring actuator for positive “makes and breaks” with a minimum of arcing
n Heavy-duty bumpers for quiet, smooth operation
n Oversized silver-alloy contacts for long life and better heat dissipation
n Heavy-duty, brass alloy, one-piece contact arm virtually eliminates contact bounce
n Auto-ground clip assures positive ground n Glass-reinforced nylon back body for durability & strength n Side and external screw-pressure-plate back wire with #14 – #10 AWG copper or copper-clad wire
n Grounding terminal is standard with screw-pressure-plate back wire
Dimensions
1.437"
3.281"
2.375"
1.073"
2.196"
3rd party compliance n UL Listed, File Number E140597, Standard UL20, General Use Snap
Switches n Federal Specification WS896 n cULus Listed, File Number LR17446, Standard CSA-C22.2 No. 111,
General Use Snap Switches n Conforms to NEMA WD-1 and WD-6
PerformanceElectrical
Dielectric withstand voltage 1500V minimum
Maximum working voltage 277VAC
Overload minimum 4.8 times rated current for 100 cycles
Temperature rise 30 °C maximum at rated current
Maximum continuous current 277VAC
Endurance50,000 cycles min., resistive, inductive, tungsten filament lamp load (fed spec)
Mechanical
Terminal accommodations #14 AWG – #10 AWG
Environmental
Flammability UL94 V2
Operating temperature Max. continuous +115 °C, min. -40 °C
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 35 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Transformer, 208V/240V/24V, 50A
nn 208V/240V primary input 50/60 Hz rated
nn 24VAC secondary output 50VA
nn 2.08 amp maximum
nn Class 2 energy limiting (inherent design)
nn Core: 0.875" x 1.25" EI66x32
nn Date code to be stamped on side of part
nn Rating input voltage: 208/240VAC
nn Rated frequency: 50/60Hz
nn Primary exciting current: ≤90mA
nn Secondary no-load voltage: 27 ± 1 VAC
nn Secondary rated load voltage: 24 ± 1 VAC (AC 2.08A)
nn D.C. resistance (20 °C): n Rp1 (blk-red) = 44.41 W ± 10% n Rp2 (red-org) = 7.91 W ± 10% n Rs (blu-yel) = 0.75 W ± 10%
nn Insulation resistance: 500 VDC, 1 min., ≥ 100 M W
nn Coil temperature rise: ≤ 80 °C
nn Hi-pot test: 3000VAC, 1mA, 1S (P-S)
nn Working surrounding temperature: -10 to 70 °C
nn Working surrounding humidity: 35 to 90%
nn Storage surrounding temperature: -10 to 90 °C
nn Safety standard: UL, CSA
nn Insulation system: Class B (130 °C)
E223730C US
233402
50 VA 50/60 HZCLASS 2 NOT WET CLASS 3 WETISC-CLASS 130(B) INSULATION
PRI: SEC:
TIG WELD(2 PLACES)
1.250
[31.75]
2.625
[66.68]
3.625
[92.08]
1.47
5
[37.
47]
2.18
7
[55.
55]
0.032[0.81]
2.675
[67.95]
0.750
[19.05]
1.81
2
[46.
02]
BLACK AWG #18 12"+/-.5"LG..5"+/-.1" STRIP W/.250"INSULATED FEMALE Q.C.
ORANGE AWG #18 12"+/-.5"LG..5"+/-.1" STRIP W/.250"INSULATED FEMALE Q.C.
RED AWG #18 12"+/-.5"LG..5"+/-.1" STRIP W/.250"INSULATED FEMALE Q.C.
ø 0.188[ø 4.76]
3.12
5
[79.
38]
YELLOW AWG #18 12"+/-.5"LG..5"+/-.1" STRIP W/.250"INSULATED FEMALE Q.C.
BLUE AWG #18 12"+/-.5"LG..5"+/-.1" STRIP W/.250"INSULATED FEMALE Q.C.
COM 208 240
BLK RED ORG
24VAC
BLU YEL
24V240V
blk
org
blu
yel
red208V
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 36 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
09 12 15 18 24 30 36
Nylon washable filter 14-1/4" x 18-1/2" 14-1/4" x 18-1/2" 14-1/4" x 22-1/2" 14-1/4" x 22-1/2" 19" x 28-3/4" 19" x 28-3/4" 19" x 28-3/4"
Nylon washable filter
ConstructionZehnder Rittling’s heavy duty, industrial grade washable air filters are designed with a corrosion-resistant aluminum u-channel frame enclosing nylon filter media. The nylon media is woven around a coated wire internal frame, providing strength and rigidity. Standard frames are nominal 1/2" thick.
Physical dataFrame: Aluminum U-channelMedia: PolyamideSupport grille: Coated wire
Important featuresnn Rigid corrosion-resistant aluminum u-channel framenn Support grilles internal to media for exceptional strengthnn Nylon filter media is acid resistantnn MERV 4 ratingnn Stands up to repeat cleanings for long service lifenn Low pressure drop over a broad range of airflows
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 37 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
ConstructionZehnder Rittling’s heavy duty, industrial grade filters are designed with a one-piece moisture-resistant chipboard frame enclosing media. Standard frames are nominal 1" thick (3/4" actual). The fiberglass media filter consists of continuous-filament fibers bonded together with thermo-setting resin.
Support grilles of perforated corrosion resistant steel or expanded metal are provided on both sides of the filter. The media pads and support grilles are continuously glued to the inside perimeter of the frame, resulting in exceptional strength and rigidity. This design virtually eliminates the possibility of media sag within the frame.
Physical data n Frame: One-piece moisture-resistant chipboard n Media: Fiberglass n Support grille: Perforated corrosion-resistant steel or expanded wire on both sides of the filter
n Sealant: Hot-melt resin
Pressure drop n 0.07" w.g. @ 300 fpm
1" spun glass throwaway filter
Features n One-piece moisture-resistant chipboard frame prevents broken corners
n Support grilles on both sides for exceptional strength n Media and grilles continuously glued to the inside perimeter of the frame for rigidity
n Filters are UL 900 Class 2 listed n MERV 4 rating
DimensionsUnit size 09 12 15 18 24 30 36
Filter
Number 1 1 1 1 1 1 1
Length, in. 18-1/2 18-1/2 22-1/2 22-1/2 28-3/4 28-3/4 28-3/4
Width, in. 14-1/4 14-1/4 14-1/4 14-1/4 19 19 19
Thickness, in. 1 1 1 1 1 1 1
All dimensions ± 1/8"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 38 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Aluminum discharge grille, single deflection
Dimensional data
Grille size A B C D
16" x 14" 17-11/16" 15-11/16" 15-11/16" 13-11/16"
14" x 12" 15-11/16" 13-11/16" 13-11/16" 11-11/16"
12" x 10" 13-11/16" 11-11/16" 11-11/16" 9-11/16"
10" x 8" 11-11/16" 9-11/16" 9-11/16" 7-11/16"
Supply grille arrangements
Unit SizeSingle
dischargeDouble
dischargeTriple
discharge
09 14" x 12" 10" x 8" 10" x 8"
12 14" x 12" 10" x 8" 10" x 8"
15 14" x 12" 10" x 8" 10" x 8"
18 14" x 12" 10" x 8" 10" x 8"
24 16" x 14" 12" x 10" 12" x 10"
30 16" x 14" 12" x 10" 12" x 10"
36 16" x 14" 12" x 10" 12" x 10"
Notesnn Dimensions are in inchesnn All dimensions are +/- 1/4nn Discharge grilles are shipped loose for field installationnn Construction is roll formed aluminum frame and bladesnn Standard finish is powder coated and will be the same color as the return grillenn Mounting hardware includednn All listed dimensions are approximate and are subject to change without notice
Individually adjustable blades
1-1/4"
1-7/8"
5/8"
D
A
C
B
1-1/8"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 39 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Aluminum discharge grille, double deflection
Notesnn Dimensions are in inchesnn All dimensions are +/- 1/4nn Discharge grilles are shipped loose for field installationnn Construction is roll formed aluminum frame and bladesnn Standard finish is powder coated and will be the same color as the return grillenn Mounting hardware includednn All listed dimensions are approximate and are subject to change without notice
C
A9/16"
B
5/32"1-1/4"
1-7/8"
Mounting holes 3/16" (countersunk)
2/3"
Horizontal andvertical deflection blades
5/32"
1-1/4"
1-7/8"
2/3"
D
Dimensional data
Grille size A B C D
16" x 14" 17-11/16" 15-11/16" 15-11/16" 13-11/16"
14" x 12" 15-11/16" 13-11/16" 13-11/16" 11-11/16"
12" x 10" 13-11/16" 11-11/16" 11-11/16" 9-11/16"
10" x 8" 11-11/16" 9-11/16" 9-11/16" 7-11/16"
Supply grille arrangements
Unit SizeSingle
dischargeDouble
dischargeTriple
discharge
09 14" x 12" 10" x 8" 10" x 8"
12 14" x 12" 10" x 8" 10" x 8"
15 14" x 12" 10" x 8" 10" x 8"
18 14" x 12" 10" x 8" 10" x 8"
24 16" x 14" 12" x 10" 12" x 10"
30 16" x 14" 12" x 10" 12" x 10"
36 16" x 14" 12" x 10" 12" x 10"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 40 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Notesnn All dimensions are in inchesnn All dimensions are ± 1/4nn Discharge grilles are shipped loose for field installationnn Vertical blades in the front, horizontal blades in the back, both individually adjustable and on 2/3" spacingnn Opposed blade damper with slide operatornn Aluminum roll formed blade with semi-airfoil designnn Pressure fit nylon pivot pins (rattle-free and non-loosening)nn Aluminum extruded frame with mechanically locked cornersnn Countersunk screw holesnn Standard finish is powder coated and will be the same color as the return grillenn Mounting hardware includednn All listed dimensions are approximate and are subject to change without notice
Aluminum discharge grille, double deflection with opposed blade damper
Dimensional data
Grille size A B C D
16" x 14" 17-11/16" 15-11/16" 15-11/16" 13-11/16"
14" x 12" 15-11/16" 13-11/16" 13-11/16" 11-11/16"
12" x 10" 13-11/16" 11-11/16" 11-11/16" 9-11/16"
10" x 8" 11-11/16" 9-11/16" 9-11/16" 7-11/16"
Supply grille arrangements
Unit SizeSingle
dischargeDouble
dischargeTriple
discharge
09 14" x 12" 10" x 8" 10" x 8"
12 14" x 12" 10" x 8" 10" x 8"
15 14" x 12" 10" x 8" 10" x 8"
18 14" x 12" 10" x 8" 10" x 8"
24 16" x 14" 12" x 10" 12" x 10"
30 16" x 14" 12" x 10" 12" x 10"
36 16" x 14" 12" x 10" 12" x 10"
Individually adjustable blades on 2/3" spacing
Slideoperator
1-1/4"
5/8"D
A
B
2-13/16"
One piece extruded frame
2/3"
C
5/32"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 41 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
1
2
3
5
4
Holes to secure frame to studs (typical)
6
7
1
2
3
5
4
Holes to secure frame to studs (typical)
6
7
21-1/8"
26-9/32"
58"63-5/32"
1-3/8"Floor
1-3/8"Floor
63-29/32" 58-3/4"
27-1/8"32-9/32"
2-15/16"
55-1/4"
56"
2-15/16"
21-1/8"
26-9/32"
58"63-5/32"
1-3/8"Floor
1-3/8"Floor
63-29/32" 58-3/4"
27-1/8"32-9/32"
2-15/16"
55-1/4"
56"
2-15/16"
Available for sizes 09-18
Available for sizes 24-36Allen lock, removable
Item number Description Quantity
09 Return panel 1
12 Quarter turn fastener 1
15 Door stop 3
18 Screw 10
24 Pivot angle 2
30 Frame 1
36 Frame support 1
Standard removable perimeter return air panel
Notesnn Seal between the frame and cabinet with a weather serial gasket (provided with cabinet) to avoid air from being pulled in from the wall cavitynn Do not attach frame to cabinetnn Frame support shipped with cabinetnn Door assemblies shipped separately
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 42 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
21-1/8"
26-9/32"
63-5/32" 58"
27-1/8"
32 9/32"
63-29/32" 58-3/4"
2-15/16"
55-1/4"
56"
2-15/16"
Available for sizes 09-18
Available for sizes 24-36Key lock or Allen lock
Item number Description Quantity
1 Return panel 1
2Quarter turn fastener or
key lock2
3 Door stop 2
4 Screw 12
5 Hinge 2
6 Frame 1
7 Frame support 1
Optional hinged perimeter return air panel
Notesnn Seal between the frame and cabinet with a weather serial gasket (provided with cabinet) to avoid air from being pulled in from the wall cavitynn Do not attach frame to cabinetnn Frame support shipped with cabinetnn Door assemblies shipped separately
Holes to secure frame to studs (typical)
2
1
3
6
5
7
4
Holes to secure frame to studs (typical)
2
1
3
6
5
7
4
21-1/8"
26-9/32"
63-5/32" 58"
27-1/8"
32 9/32"
63-29/32" 58-3/4"
2-15/16"
55-1/4"
56"
2-15/16"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 43 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Available for Sizes 09-18
Available for Sizes 24-36Allen lock, removable
Item number Description Quantity
1 Return panel 1
2 Quarter turn fastener 1
3 Frame 1
4 Frame support 1
Optional removable louvered return air panel
Notesnn Seal between the frame and cabinet with a weather serial gasket (provided with cabinet) to avoid air from being pulled in from the wall cavitynn Do not attach frame to cabinetnn Frame support shipped with cabinetnn Door assemblies shipped separately
Holes To Secure Frame To Studs (Typical)
1
2
3
4
Holes To Secure Frame To Studs (Typical)
1
2
3
4
61-1/8"
24-3/16"
17-11/16"
24-29/32"
30 3/16"
61-7/8" 19-11/16"
24-29/32"
2-15/16"
2-15/16"
1-3/8"Floor
21-1/8"
26-9/32"
58"63-5/32"
63-29/32" 58-3/4"
27-1/8"
32-9/32"
2-15/16"
55-11/32"
2-15/16"
1-3/8"Floor
61-1/8"
24-3/16"
17-11/16"
24-29/32"
30 3/16"
61-7/8" 19-11/16"
24-29/32"
2-15/16"
2-15/16"
1-3/8"Floor
21-1/8"
26-9/32"
58"63-5/32"
63-29/32" 58-3/4"
27-1/8"
32-9/32"
2-15/16"
55-11/32"
2-15/16"
1-3/8"Floor
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 44 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Sound attenuating insulation
Specifications
nn Grey
nn Wave soldering 3/4", trough 3/8"
nn Peak distance 1-3/8"
nn GB/T10808
nn Density (16/ft3) 1.44 GB/T10808
nn Tensile strength (psi) ≥ 14.5 GB/T10808
nn Elongation % ≥ 140 GB/T10808
nn Incombustibility through CA117 section A part I
nn The sound absorption co-efficient (db) 0.85 GB/T18696
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 45 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Fiberglass insulation
DescriptionFlexible duct liner insulation is made from strong, glass fibers bonded with a thermosetting resin. The airstream surface is protected with a reinforced coating system, which combines a state-of-the-art acrylic coating with a flexible glass mat reinforcement to provide a smooth airstream surface.
Advantages n Improves indoor environmental quality by helping to control both temperature and sound.
n The tough, acrylic polymer coating helps guard against the incursion of dust or dirt into the substrate, minimizing the potential for biological growth.
n Coating is formulated with an immobilized, EPA-registered, protective agent to protect the coating from potential growth of fungus and bacteria. Duct liner meets all requirements for fungi and bacterial resistance. Tests were conducted in accordance with ASTM C 1338 and ASTM G 21 (fungi testing) and ASTM G 22 (bacteria resistance testing). Note: As with any type of surface, microbial growth may occur in accumulated duct system dirt, given certain conditions. This risk is minimized with proper design, filtration, maintenance and operation of the HVAC system.
n The reinforced coating surface provides superior resistance to penetration of incidental water into the fiber glass wool core.
n GREENGUARD® certification is proof that the product meets the Environmental Institute’s indoor air quality standards for VOCs.
Thermal performanceThickness R-value Conductance
in mm hr•ft2•°F/Btu m2•°C/W Btu/(hr•ft2•°F) W/m2•°C
1/2 13 2.2 0.38 0.46 2.61
R-value and conductance are calculated from the material thermal conductivity tested in accordance with ASTM C 518 at 75 °F (24 °C) mean temperature
Sound absorption coefficients (type “A” mounting)
ThicknessSound absorption coefficient at frequency
(cycles per second) of
in mm 125 250 500 1000 2000 4000 NRC
1/2 13 0.07 0.20 0.44 0.66 0.84 0.93 0.55
Coefficients were tested in accordance with Test Method ASTM C 423-90 and ASTM E 795
General properties n Operating temperature (max.): ASTM C 411 250 °F (121 °C)
n Air velocity (max.): ASTM C 1071 6,000 fpm (30.5 m/sec) n Water repellency: INDA IST 80.6-92 n Fungi resistance: ASTM C 1338 Does not breed or promote
n Fungi resistance: ASTM G 21 No growth n Bacteria resistance: ASTM G 22 No growth
Surface burning characteristics n Meets the surface burning characteristics and limited combustibility of the following standards: standard/test method
� ASTM E 84 � UL 723 � NFPA 255 � NFPA 90A and 90B, FHC 25/50 and limited combustibility
� NFPA 259 � CAN/ULC S102-M88
n Flame spread: not over 25 n Smoke developed: not over 50
Specification compliancenn ASTM C 1071, Type Inn ASTM G 21 and G 22nn ICC Compliantnn California Title 24nn ASHRAE 62-2001nn SMACNA Application Standards for Duct Linersnn NAIMA Fibrous Glass Duct Liner Installation Standardnn Canada: CGSB 51-GP-11M and CAN/CGSB 51.11
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 46 Page ______ of ______
UsesThe recommended temperature usage range is -70 °F to 220 °F (-57 °C to 105 °C) according to method of application. With full adhesive coverage attachment, the surface to which it is applied may operate to a limit of 180°F (82 °C).
Conforms to NFPA 90A and NFPA 90B requirements.
Resistance to moisture vapor flowThe closed-cell structure of the insulation prevents moisture from wicking and makes it an efficient insulation.
Physical dataPhysical properties Test methods
Thermal conductivity Btu • in./h • ft2 • °F (W/mK)
n 75 °F mean temperature (24 °C) n 90 °F mean temperature (32 °C)
0.25 (0.36) 0.256 (0.037)
ASTM C 177 or C 518
Water vapor permeabilityPerm-in. [Kg/(s•m•Pa)]
0.05 (0.725 x 10–13) ASTM E 96, Procedure A
Flame spread and smoke developed index through 1" (25 mm)*
25/50ASTM E 84CAN/ULC S102
Mold growthFungi resistanceBacterial resistance
UL181ASTM G21/C1338ASTM G22
Meets requirementsMeets requirementsMeets requirements
Water absorption, % by volume 0.2% ASTM C 209
Upper use limit 180/220 °F (82/105 °C)
Lower use limitj -297 °F (-183 °C)
Ozone resistance Good
Density, typical rangek 3.0 to 6.0 lbs./ft3 ASTM D 1622 D 1667
Performance approved through continuing supervision by Factory Mutual (FM) approvals.j At temperatures below -20 °F (-29 °C), elastomeric insulation starts to become less flexible.
However, this characteristic does not affect thermal efficiency or water vapor permeability of the insulation.
k Reference ONLY.
Closed cell insulation
Specification complianceInsulation developed to meet:nn ASTM C 534, Type II — Sheet Grade 1nn ASTM C 1534nn ASTM E 84nn NFPA 255nn UL 723nn CAN/ULC S-102nn UL 94 5V-A, V-0, File E55798nn NFPA 90A, 90Bnn UL 181nn ASTM G21/C1338nn ASTM G22nn ASTM D 1056, 2B1nn MIL-P-15280J, FORM Snn MIL-C-3133C (MIL STD 670B), Grade SBE 3nn MEA 107-89Mnn City of Los Angeles – RR 7642
Flexible, elastomeric thermal insulation, black in color. It is furnished with a smooth skin on one side which forms the outer exposed insulation surface. It is manufactured without the use of CFC’s, HCFC’s, or HFC’s. It is also formaldehyde-free, low VOCs, dust free, fiber free and resists mold and mildew.
Factory mutual (FM) approvalsThermal conductivity
n 0.25 BTU=in/hr. ft2 °F
Water vapor transmission: n 0.05 perm-inch
Fire rating n Will not contribute significantly to fire (simulated end use testing)
As tested by ASTM E 84 “Method of Test for Surface Burning Characteristics for Building Materials” and CAN/ULC S-102, has a flame-spread index of less than 25 and a smoke-developed index of less than 50.
Note: Numerical flammability ratings alone may not define the performance of products under actual fire conditions. They are provided only for use in the selection of products to meet limits specified.
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 47 Page ______ of ______
n Optionally installed when multiple, opposed supply grilles are used to eliminate sight lines between living spaces and minimize noise carryover
Sight/sound baffle
Back
Front
Sight/soundbaffle
Back
Front
Rig
ht
Left
Rig
ht
Left
Sight/soundbaffle
ISO view without top/front panel
Sight/soundbaffle
20-gaugegalvanneal
1/4" closed cell insulation
16.0"
17.2" (sizes 09-18)
.9"
.6"
16.0"
23.2"(sizes 24-36)
Top view
Top view
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 48 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Steel braided single hose assembly
Features
nn All metal hose with a 302/304 stainless steel braidnn All male pipe threads are shipped with thread sealant already applied, eliminating the need for Teflon® tape, capped and ready for installation nn The permanently installed end fittings eliminate the possibility of bands or clamps loosening and creating leaksnn Carbon steel fittings and union reduce the possibility of over-torquing, a common problem with brass and other soft metals
Specifications
nn Designed for VS series water source heat pump applications
nn Temperature range of -40 °F (-40 °C) to 212 °F (100 °C)
nn Maximum working pressure1/2": 400 psi (2756 kPa)3/4": 400 psi (2756 kPa)
nn Fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1)
nn EPTF-White Santoprene core with ANSI 302/304 stainless steel outer braidnn Swivel connector with female JIC fitting
Unit sizes
09, 12 15-36
Hose I.D. (in.) 1/2 3/4
Approximate hose O.D. 0.700" 0.975"
Length (ft./cm) 3/91.4 3/91.4
Working pressure (PSI/kPa) 400 psi 400 psi
Minimum burst at ambient temperature (70 °F) (PSI/kPa)
1600 psi 1600 psi
Minimum bend radius (in./mm) 2.5/63.5 4/101.6
Temperature range -40 °F to 212 °F -40 °F to 212 °F
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 49 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Ball valve
Description A full port forged brass ball valve with a 1/4" NPT port for pressure or temperature taps. Ideal for heating system balancing. 600 psig working pressure.
Construction
Body Brass
Ball Brass, hard chrome plate
Stem Brass
O-ring Buna-N
Nut and lock washer Zinc plated steel
Stem packing seat PTFE
Seat PTFE
Gland nut Brass
Handle Zinc plated steel, plasticoated
End cap Brass
Dimensions
Size L D H R W
1/2" 2.48" 0.59" 1.89" 0.76" 3.65"
3/4" 2.69" 0.75" 2.11" 0.77" 4.65"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 50 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Autoflow valve
B
A
1/2" or 3/4 SWT 1/2" or 3/4 SWT
Cartridge cap
FLOW
Dimensional dataSize A B Weight Cv
1/2" 2.80" 1.80" 0.46 lbs. 9
3/4" 3.82" 2.50" 0.95 lbs. 14
Flow rate selectionsSize PSID (range) GPM (± 5.0%)
1/2" 2-45 0.5, 1.0, 1.5, 2.0, 2.5, 3.0
3/4"2-45
0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 5.0, 6.0, 7.0, 8.0
5-50 9.0, 10.5
Materials and design dataBody Forged brass ASTM B283, 600 WOG, 325 °F
Cap and cartridge seal Viton (green)/EPDM O-rings
Cartridge cap Forged brass ASTM B283
Flow cartridge Removable, stainless steel/brass
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 51 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Y strainer
Materials and design datann Body: hot forged brass ASTM B283 600 WOG, 325 °Fnn Cap seal: Vitonnn Filter screen: 20 mesh, 304 stainless steelnn Strainer cap: forged brass ASTM B283 with 1/4" NPT port
DimensionsSize A B Weight (lbs.) Filter area
1/2" 2.80 1.80 0.38 2.70
3/4" 3.82 2.50 0.82 7.30
Dimensions in inches
A
B1/2" or 3/4" SWT1/2" or 3/4" SWT
1/4" NPT
Flow
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 52 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
On/off control valve
Table 1 Valve body and actuators model chartModel temperature range
Valve body 32° to 200 °F (fluid) @ 104 °F (ambient) (0 to 93 °C @ 40 °C)
Actuator 32° to 200 °F (fluid) @ 104 °F (ambient) (0 to 93 °C @ 40 °C)
Table 2 Dimensions
Valve body size
A B C D
1/2" sweat1-5/16" (33 mm)
15/16" (23 mm)
1-5/16" (33 mm)
3-5/16" (84 mm)
3/4" sweat1-3/8"
(35 mm)15/16"
(23 mm)1-11/16" (43 mm)
3-3/8" (86 mm)
Table 3 Flow coefficients and maximum close-off pressure differential
Port dia.
General close-off DP High close-off DP
2-way control valve
Close-off DP psi (kPa)
2-way control valve
Close-off DP psi (kPa)
1/2" 3.5 25 (172) 1 75 (517)
3/4" 3.5 25 (172) 2.5 50 (344)
* Based on valve body only
Featuresnn Hysteresis synchronous motor for long lifenn Spring return operation provides a fail-safenn Actuator mounts directly onto valve body without need for linkages or calibrationnn Manual override lever nn Actuator can be replaced without any tools, or removal of valve from system
Valve body assemblynn Service: hot and chilled water models, up to 50% glycolnn System static pressure limits: 300 psi (2068.4 kPa)nn Close-off: refer to Table 3nn Fluid/ambient temperature limits: refer to Table 1nn Seat leakage: ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way)nn Body: forged brassnn Stem: nickel-platednn Seat: brassnn Paddle: Buna N
Actuatornn Voltage: 24 Vac @ 50/60 Hz, 120 Vac @ 60 Hznn Power requirements: 6.5 watts, 7.5 Vann Control signal: on/off, 2 position, spring returnnn Timing, full open to full close: 25 sec. max and 9 sec.max. spring returnnn Materials: stainless steel base plate, aluminum covernn Ambient temperature limits
� Shipping & storage: -40 to 160 °F (-40 to 71°C) � Operating: Refer to Table 1
nn Humidity: 5 to 95% relative humidity, non-condensingnn Agency listings
� UL873: Underwriters Laboratories (File #E9429 Category Temp. Indicating and Regulating Equip.)
� CUL: UL Listed for use in Canada by Underwriters Laboratory
� Canadian Standards C22.2 No. 24 � European Community: EMC Directive (89/336/EEC)Low Voltage Directive (72/23/EEC)
Valve with general close-off actuator
Poweroff
ABCoil
2-way valve withnormally closed actuator
2-WAY B
3-3/16"
1-1/8"
A A
3-WAY C
3-1/4"
3-11/16"
2-3/8"
D
A-PORTB-PORT
1/4"
2-1/8"
2-3/8"
Revised April 2015. Zehnder Rittling periodically makes changes to the design and/or specifications of its products. As a result, the design and specifications of each product at the time of order may be different than as described herein. Please contact Zehnder Rittling's Sales Support staff at 844-934-6337 for specific information on current design and specifications. Designs, specifications and other information contained herein are not express warranties, which are only as expressly set forth by Zehnder Rittling in its terms and conditions of sale. The latest version of this document is available at www.zehnder-rittling.com.
Vertical Stack Water Source Heat Pump Submittal Set: 53 Page ______ of ______
Vertical Stack Water Source Heat Pump Submittal Data English, IP Units
Warranty
Zehnder Rittling guarantees its products to be free from defects in material and workmanship for a period of twelve months from date of unit start-up or 18 months from date of shipment from our factory, whichever comes first.
Should there be any defects in the good(s), the purchaser should promptly notify Zehnder Rittling. Upon receipt of written consent from Zehnder Rittling, the purchaser shall return the defective good(s) to the factory for inspection with freight prepaid. If inspection shows the goods to be defective, Zehnder Rittling will at its discretion repair or replace the said item(s).
Defects arising from damage due to shipment, improper installation, negligence or misuse by others are not covered by this warranty.
This warranty is extended only to the original purchaser from Zehnder Rittling.
IMPORTANT: Approved submittal documentation, specific to each project, supersedes the general guidelines contained within this document.
Zehnder Rittling · 100 Rittling Boulevard · Buffalo, NY USA 14220T 844-934-6337 (844-ZEHNDER) · F [email protected] · www.zehnder-rittling.com
© Z
ehnd
er R
ittlin
g A
ugus
t 20
14,
Eng
lish,
sub
ject
to
cha
nge
with
out
no
tice