verifying the firmware version on the mx/mxa/qx actuator digital and analog controls group flowserve...

10
Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Upload: samuel-mills

Post on 26-Mar-2015

233 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Verifying the Firmware Version on the MX/MXa/QX Actuator

Digital and Analog Controls Group

Flowserve FCD

Lynchburg, VA

Page 2: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware

• Tells the actuator how to operate

• WINDOWS for the actuator

• Essential information when addressing customer problems

Page 3: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Upgrades

• Address functional deficiencies not found during initial testing ESD Modulation CRC

• Enhances the feature functionality of the actuator Option board functionality Comm Loss in Network Options MXa SSMR

Page 4: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Verifying the Firmware Version

• Enter the SETUP Menu

• Enter the DIAGNOSTIC Menu

• Enter the IDENTIFICATION Sub-menu

• Toggle through the options to the Firmware Version

Page 5: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Verification Procedure

100% OPENSTATUS OK

SETUP?

Enter the SETUP Menu

Toggle the REMOTE/STOP/LOCAL knob from STOP to REMOTE to LOCAL and back to STOP. Toggle the OPEN/CLOSE knob to OPEN, then CLOSE and then to OPEN

Page 6: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Verification Procedure

SETUPENGLISH?

SETUP?

CHANGESETTINGS?

Enter the DIAGNOSTICS Menu

“YES”“YES”CHANGE

SETTINGS?

“NO” VIEWSETTINGS?

VIEWDIAGNOSTICS?

“NO”

Page 7: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Verification Procedure

VIEWDIAGNOSTICS?

VIEWHARDWARE?

Enter the identification Sub-Menu

“YES” “NO”

VIEWMOTOR STATUS?

VIEWERROR CODE?

MX

MXa

Page 8: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Verification Procedure

VIEWMOTOR STATUS?

VIEWERROR CODE?

VIEWMOTOR STATUS?

Enter the IDENTIFICATION Sub-Menu

“NO”

“NO”

MX

MXa

VIEWPOWER SUPPLY?

VIEWPOWER SUPPLY?

“NO” “NO”

“NO”VIEW

IDENTIFICATION?

VIEWIDENTIFICATION?

Page 9: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Firmware Verification Procedure

VIEWIDENTIFICATION?

TAG? SERIAL #01234567

Navigating the IDENTIFICATION Sub-Menu to find the Firmware version

ORDER #01234567

FIRMWARE REV.08/10.0

“YES” “YES” “YES” “YES”

When the firmware version has been verified, cycle the REMOTE/STOP/LOCAL knob to either LOCAL or REMOTE and then

back to STOP to return to the normal display

Page 10: Verifying the Firmware Version on the MX/MXa/QX Actuator Digital and Analog Controls Group Flowserve FCD Lynchburg, VA

Seeking a Solution

• When seeking a solution to a customer’s problem, collect the critical data MX, MXa or QX Firmware version Options Configuration parameters Description of the problem Actuator display