VAMP 321 Arc Flash Protection
Technical presentationJuha Rintala
Product Manager
04.06.2012 v9
VAMP 321 Arc Flash Protection
New central unit for arc flash protectionGeneral
• A new design based on long experience in arc protection systems since 1994
• Developed in cooperation with customers user friendliness in mind
• Based on the proven VAMP 221 arc protection system and technology from the VAMP protection IED’s
• Modular design enable long service life forward and backward
• Optimized to mid and high-end arc protection systems
• Relies the same VAM I/O units as VAMP 221 system
VAMP 321 Arc Flash Protection
New central unit for arc flash protectionGeneral
• Supports existing VAMP 221 system based VAM I/O units, cabling and sensors
• Retrofit possible• Two* arc sensors interfaces for
the central unit with basic options
• Incoming cable termination (light only) compartment protection
*) Optionally• Ten (10) point sensors • One (1) fibre loop and eight (8) point
sensors
VAMP 321 Arc Flash Protection
Features
HMI• 128x64 or 128x128 LCD
display
• 16 programmable two-colour, red and green led alarms with user configurable texts
• Two programmable function keys with a password control possibility
• USB-B interface for PC setup
• Keypad
VAMP 321 Arc Flash Protection
Features
LCD dot matrix display for• Single line mimic• Arc flash protection event-
buffering• Measurements, I, U, THD,
phasors• System status view
VAMP 321 Arc Flash Protection
Features
Function keys• Used for operator control
commands for the system such as
• Object control• Stage blocking• System reset• System installation
• Program function have a password control
VAMP 321 Arc Flash Protection
Features
Programmable two-colour led alarms• User configurable channel texts slide in
the text pocket• Allows indication of arc system status,
channel, zone, latch, object status, etc.
VAMP 321 Arc Flash Protection
Optional Features
Conventional high speed binary inputs and outputs with Basic I/O option
• BI 3 pc’s, rated voltage +18 .. 265 V dc, rated burden 5 mA
• BO 3 pc’s, rated voltage + 30 V dc, maximum load 20 mA
• Used e.g. for transfer and receipt of light (L>) and current (I>)
Fibre high speed binary inputs and outputs with Fibre I/O option
• BI 2 pc’s, Single mode fibre, max link 2.7 km
• BO 2 pc’s, Single mode fibre, max link 2.7 km
• Used e.g. for transfer and receipt of light (L>) and current (I>)
VAMP 321 Arc Flash Protection
Features
VAMPSET for system configuration• Similar look and feeling as with
other VAMP IEDs• Arc specific settings menus
VAMP 321 Arc Flash Protection
Features
VAMPSET for Arc flash protection status and information
• Arc protection specific informative menus• Can be used to help commissioning and testing
VAMP 321 Arc Flash Protection
Features
Current settings for internalmeasurements Selection for master unit in multi-central unit systems
Release all latched stages
Independent adjustable time delay for all stages. Useful in delayed arc applications
Eight (8) independent arc protection stages, which can be configured to be L> or L>&I>
Install of the system
Clear I/O unit’s registers
Send internal current (I> or Io>) to external units (VAM 4C)
VAMP 321 Arc Flash Protection
Features
Arc current matrix setting view
• Specify the source of current for arc stages
Current source selection
Stage selection
Internal current (Phase currents or neutral current)
External current (I/O units or other central units)
High-speed binary inputs
VAMP 321 Arc Flash Protection
Features
Arc light setting view• Specify the source
of light for each independent arc stages
Stage selection
Light source selection
Internal sensors
Arc light in zones 1 to 4 (I/O units)
High-speed binary inputs
VAMP 321 Arc Flash Protection
Features
Arc output setting view
• Link the arc stages to outputs
Stage outputs
Latch for stage output
Output to internal output relays
Output to internal high-speed binary outputs
Arc stage status transfer to I/O unit’s zones 1...4
Output to high speed trip outputs
VAMP 321 Arc Flash Protection
Features
Matrix views• Correlation between
different views
&
Note ! If no current source has been selected, stage operates as ”light only” L> principle
VAMP 321 Arc Flash Protection
Features
Programmable stages for extended performance
• Detection of harmonics in the power distribution
• Used for alarming and triggering disturbance recorder
• Pre-conditional cable termination fault detection
• Pre-alarm on LV system neutral wiring dimensioning problems
• detect overheating in neutral cable before cable burn as neutral wire is not fused
• 3rd harmonic can cause up to 1,7 x In current to neutral cable)
VAMP 321 Arc Flash Protection
Features
Disturbance recorder• Gives additional data to
the fault evaluation• Triggering from arc
protection signals, BI, DI, logic, programmable stage, etc.
• Enable predictive fault clearance together with programmable stage
VAMP 321 Arc Flash Protection
IP 54 casing (front)
• Robust aluminium case, protected against corrosion
• Adjustable fixtures• Flexible installation
VAMP 321 Arc Flash Protection
Connections
VAMP 321 Arc Flash Protection
Application
Fault in the cable termination will be tripped on light only criteria through T2 of VAMP 321.Fault in the cable termination or current transformer will be tripped on light only criteria through T2 upstream.
Fault in the bus bar will be tripped on light & current criteria trough T1. Should the CB fail to operate a circuit breaker failure protection CBFP trips upstream breaker via T3.
Possible fault in the outgoing feeder is tripped by T1 contact of the VAMP 321 and simultaneously through output of VAM I/O unit
VAMP 321 Arc Flash Protection
Overall dimensions
VAMP 321 Arc Flash Protection
Mounting
VAMP 321 Arc Flash Protection
VAMP 321 Arc Flash Protection
X
Supply voltage [V]A = 80 .. 265Vac/dcB = 18 .. 48Vdc
VAMP 321 Arc Flash Protection
X
I/O Card IA = NoneB = 3 x BI/BO, 2 x Arc sensor, T2, T3, T4C = Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4
VAMP 321 Arc Flash Protection
X
I/O Card IIA = NoneB = Digital I/O; 6 x DI, 4 x DOC = 5 x RTD
VAMP 321 Arc Flash Protection
X
I/O Card IIIA = NoneB = Digital I/O; 6 x DI, 4 x DOC = 5 x RTD
VAMP 321 Arc Flash Protection
X
I/O Card IVA = NoneB = Digital I/O; 6 x DI, 4 x DOC = 5 x RTDD = 2 x IGBT High speed outputs (Excludes I/O Card III, slot 4)E = VAM 3QD control cardF = VAM 3TD/3ED control interfaceG = Reserved for future use
VAMP 321 Arc Flash Protection
X X
I/O Option card IA = NoneB = Digital I/O; 4 x BIC = Digital I/O; 4 x BOD = 4 x Arc sensorE = Digital I/O; 4 x DO
I/O Option card IIA = NoneB = Digital I/O; 4 x BIC = Digital I/O; 4 x BOD = 4 x Arc sensorE = Digital I/O; 4 x DO
VAMP 321 Arc Flash Protection
X
Analog measurement card [A, V]A = 3L + Io (5A / 1A) + UB = 3L + Io (5A) + U, Ring lug terminalsC = 3L + Io (1A) + U, Ring lug terminalsD = LPCT sensor inputs
VAMP 321 Arc Flash Protection
X X
Communication interface IA = NoneB = RS232C = RS232 + Ethernet RJ-45D = RS232 + Ethernet LC
Communication interface IIA = NoneB = RS232
VAMP 321 Arc Flash Protection
X X
Display typeA = 128 x 64 LCD matrixB = 128 x 128 LCD matrix
DI treshold voltage1 = 24 VDC / 110 VAC2 = 110 VDC / 220 VAC3 = 220 VDC
Applications