TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 1 of 10
DOBLE ENGINEERING AFRICA
TRANSFORMER DIAGNOSTIC TESTING AT VALCO ALUMINIUM
This report was prepared on the 25th May 2015 by:
Kamendren Govender
Principal Engineer
CLIENT: VALCO ALUMINIUM
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 2 of 10
REPORT DETAILS
CLIENT Volta Aluminium Company Limited
ADDRESSEE
SITE Line 5
JOB DESCRIPTION Transformer Condition Assessment
REPORT PREPARED BY Kamendren Govender
DATE REPORT COMPLETED 25th May 2015
REPORT AUTHORISED BY Luwendran Moodley
CLIENT ORDER NUMBER
Copyright © 2007 Doble Engineering Africa Limited
All rights reserved. No part of this publication may be produced stored in a retrieval system or transmitted in any form by any means electronic mechanical photocopying recording or otherwise without the prior written permission of Doble.
Indemnity This document may not be distributed or used outside the client for whom it is prepared except with written authorization from Doble. Doble disclaims all liability for any loss damage injury or other consequence whatsoever arising from any unauthorized use howsoever caused including any such resulting from error omission or negligence in its application.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 3 of 10
Table of Contents 1. Executive Summary...............................................................................................4
1.1. Findings ..............................................................................................................4 1.2. Recommendations ..............................................................................................4 2. Analysis and Observations ......................................................................................5
2.1. Transformer Details ..........................................................................................5 2.2. Condition Analysis ...........................................................................................5 2.2.1. Electrical Test Findings ......................................................................................5
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 4 of 10
1. Executive Summary
1.1. Findings
Doble Engineering Africa was requested by Valco Aluminium to perform diagnostic tests and analysis on a transformer based on electrical tests. This report covers the final findings based on our studies of the transformer with serial number: AE69700T1 manufactured by Fuji Electric and located at Line 5. The power factor results are high and not within acceptable limits. This is indicative of insulation contamination.
The ratio test revealed no significant concerns with all ratios being within the acceptable limits. The DC winding resistance tests results are within acceptable limits. The Sweep Frequency Response Analysis (SFRA) revealed no winding deformation on the 13.8/16.4 kV windings for all phases. The moisture content is within acceptable values. The DGA signature is indicative of a normal operating transformer.
1.2 Recommendations Given the findings, Doble Engineering Africa recommends the following: Furan measurements to assess the condition of the insulation Annual monitoring of winding power factor results
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 5 of 10
2. Analysis and Observations
2.1 Transformer Details
The transformers details are given in Table 1.
Table 1: Transformers Details
Substation Line 5
Unit VR5
Serial Number AE69700T1
Manufacturer Fuji Electric
Year of Manufacturer 1968
Voltage 13.8/16.4 kV
VA Rating 93.5 MVA
2.2 Condition Analysis
2.2.1 Electrical Test Findings
2.2.1.1 Windings Insulation
Results and Analysis The winding power factor values are given in Table 2.
Table 2: Winding Power Factor and Capacitance Test Results
Measured Voltage (kV) Power Factor (%) Capacitance (pF)
S, L, and SL to ground 8 1.05 38 134.00
The power factor results are high and not within acceptable limits. This is indicative of insulation contamination.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 6 of 10
2.2.1.2 Ratio Test Results and Analysis
The results of the ratio test for each phase and tap position shall be within 0.5 % of the nameplate data. The results from the ratio tests are given in Table 4.
a) S Winding to L Winding
Table 4: Ratio Test Results
Tap Red Phase Yellow Phase Blue Phase
67 1.001 1.002 1.002
The ratio measurements are within acceptable limits. 2.2.1.3 DC Winding Resistance
Results and Analysis The DC winding resistance tests were performed on all windings and are shown on Tables 5 and 6.
a) S Winding
Table 5: S DC Winding Resistance Test Results
Tap Red Phase Yellow Phase Blue Phase
Resistance (m) Resistance (m) Resistance (m)
67 15.01 14.76 14.76
The DC winding resistance is within acceptable limits. b) L Winding
Table 6: L DC Winding Resistance Test Results
Tap Red Phase Yellow Phase Blue Phase
Resistance (m) Resistance (m) Resistance (m)
67 18.03 17.91 17.92
The DC winding resistance test results are within acceptable limits.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 7 of 10
2.2.1.4 SFRA Test
Results and Analysis The results from the SFRA tests are given in Figures 1 to 3.
a) S Winding Open Circuit
Figure 1: S Winding Open Circuit
The comparison between the phases finds that the responses demonstrate a characteristic pattern and has good correspondence across the entire frequency range. These responses do not indicate winding deformation.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 8 of 10
b) S Winding Short Circuit
Figure 2: S Winding Short Circuit
The short circuit response revealed no resistance change between the phases. These responses do not indicate winding deformation.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 9 of 10
c) L Winding Open Circuit
Figure 3: L Winding Open Circuit
The comparison between the phases finds that the responses demonstrate a characteristic pattern and has good correspondence across the entire frequency range. These responses do not indicate winding deformation.
TRANSFORMER CONDITION ASSESSMENT
Project No: File: Valco Aluminium_AE69700T1 Page 10 of 10
2.2.1.5 Oil Analysis
a) Moisture Content The moisture content (16 ppm) is at acceptable values.
b) DGA
Figure 4 below shows the DGA history of the oil.
Figure 4: DGA Signature
The DGA signature is indicative of a normal operating transformer.