v-ii series vrf - squarespace · v-ii series vrf these newly designed compact outdoor units are...

11
V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP (135.0kW) in 2HP increments and a connectable indoor unit capacity ratio of up to 150% (202.5kW). • High efficiency operation • Space saving / high EER combinations • Total piping length 1000m max. • High static pressure of 80 Pa. • Easy installation with automatic address setting • Extensive range of controller options including new Touch Panel Controller

Upload: others

Post on 11-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

V-II series vrf

These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP (135.0kW) in 2HP increments and a connectable indoor unit capacity ratio of up to 150% (202.5kW).

• High efficiency operation

• Space saving / high EER combinations

• Total piping length 1000m max.

• High static pressure of 80 Pa.

• Easy installation with automatic address setting

• Extensive range of controller options including new Touch Panel Controller

Page 2: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

8, 10, 12HP 14, 16HP

High Efficiency

Significantly improved EER/COP

New innovative technology

The efficiency of the V-II system is significantly improved by the use of a DC twin rotary compressor, inverter technology and a large heat exchanger.

DC Fan motor: High performance and high efficiency compact DC fan motor

4-face heat exchanger: This new coil design increases the heat exchanger surface area by approximately 1.7 times compared with the previous model.

Sine-wave DC inverter control:Use of sine wave DC inverter control allows high efficiency and energy savings.

DC twin rotary compressor:High performance DC twin rotary compressor maximises efficiency from low speed to high speed operation

Front intake port is designed to prevent decreasing airflow when multiple outdoor units are installed.

* “EER/COP” is the coefficient of performance [ = capacity (kW) ÷ input power (kW) ].

* EER/COP values are based on our own testing method.*1. The data refers to a 8HP outdoor unit.

0 3.0 3.5 4.0 EER 0 3.0 3.5 4.0 COP

Cooling Heating

3.2 3.7V series

V-IIseries

4.07 4.37*1 *1

Cooling EER

27% increase!

Heating COP

18% increase!

Previous model V-II series

Surface area

1.7 times!

V-II series vrf

Page 3: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

The minimum and maximum temperature range can be specified maximising energy savings but still providing thermal comfort conditions.

The operating capacity can be controlled in four steps. Peak power consumption can be limited avoiding supply company maximum demand penalty charges.

Economy operation can be set by remote controller. The temperature setting is offset automatically over a certain period of time.

Each air conditioner is equipped with an OFF timer that automatically stops operation when a fixed time has elapsed from the start of operation. This prevents energy being wasted. (Note: Except simple remote controller)

Energy Efficiency Combination

Various Energy Saving Features

Choice of space saving or energy efficiency combinations

Room temperature set point limitation Peak cut operation

Economy operation

Auto-off timer

[ Space saving combination ] [ Energy efficiency combination ]

For 16HP

For 24HP

For 28HP

18%energy saving !

12%energy saving !

10%energy saving !

16HP 8HP

8HP12HP

16HP

8HP

8HP

8HP 8HP

12HP

12HP 12HP

8HP

Operation setting (System Controller)

Set Temp.

Set Temp.

˚C3028262422201816141210

Heating Cooling Heating settemp. range

Original Settemp. limitation

Set pointlimitation setting

Cooling settemp. range

Time

Control device

Signal input

Peak cutCapacity

Setting level W

Down

UpUp

DownDown

Down

Economy operation

Economy operation

Heating Set Temperature

Cooling Set Temperature

Economy operationControl Temperature

Economy operationControl Temperature

MAX. -4˚C

MAX. +2˚C

Page 4: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

             

Overall piping length 1000m

An overall piping length of 1000m allows for a variety of applications.

High static pressure of 80Pa

The outdoor unit can have a condenser hood easily connected with a static pressure of 80Pa standard. This allows outdoor units to be installed within plant rooms in high rise buildings.

Installation Example

Large diameter fan and DC motor have been used allowing an external static pressure of 80Pa. This is approximately 2.6 times greater than the previous model.

Powerful discharge with an external static pressure of 80Pa.

Design Versatility

Actual pipe length

150m max.

Previous model V-II series

Pipe length from firstseparation tube to thefarthest indoor unit

60m max.

Height difference betweenoutdoor and indoor units

50m max.

For the outdoor unit positioned below : 40m max.

Height difference betweenindoor and indoor units

15m max.

80Paas standard

Total pipe length

1000m max.

Page 5: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

Life-extending operation

Outdoor unit rotation function. The compressor starting order is rotated so that the running time is shared.

Backup operation

If one of two compressors malfunctions, it will not affect the operation of the other outdoor units.

Outdoor UnitsIf one of the compressors fails, a back-up operation will be performed by the remaining compressors.

Blue fin heat exchanger

Corrosion resistance of the heat exchanger has been improved by the introduction of blue fin treatment to the outdoor unit’s heat exchanger.

Remote monitoring

The Web Monitoring system allows you to view system operation at all times over the internet ensuring trouble free operation.

The operating VRF network system in the building can be monitored in real time over the Internet.

Indoor unit continuous operationEach indoor unit is controlled individually on the system network. This allows all indoor units to continue to operate unaffected even if an error should occur at any indoor unit on the VRF network system.

Reliability

DC2

DC3

DC1

DC2

DC1

DC3

Rotation

Rotation

Blue finheat exchanger

Monitoring Side

Internetor

Public Telephone Line

VRF Network System SideCobalt Blue protection

Standard chromate protection

Aluminium base material

Hydrophilic coating

Note: The inverter compressors start in priority. Rotate function is alternated by the start / stop timing of the compressors

Rotation

Failure

Outdoor unit

Transmissionline

USB adaptor(Field supplied)

Indoor unit

WebMonitoring Tool

Page 6: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

Outdoor units specifications

Space Saving CombinationRating Capacity HP 8 10 12 14 16 18 20 22 24

Combination Model Name AJYA72LALH AJYA90LALH AJY108LALH AJY126LALH AJY144LALH AJY162LALH AJY180LALH AJY198LALH AJY216LALHUnit 1 AJYA72LALH AJYA90LALH AJY108LALH AJY126LALH AJY144LALH AJYA90LALH AJY108LALH AJY108LALH AJY108LALHUnit 2 AJYA72LALH AJYA72LALH AJYA90LALH AJY108LALHUnit 3

Max. Connectable Indoor Unit *1 15 16 17 21 24 32 32 32 35Connectable Indoor Unit Capacity kW 11.2 - 33.6 14.0 - 42.0 16.8 - 50.2 20.0 - 60.0 22.4 - 67.2 25.2 - 75.6 28.0 - 83.9 30.8 - 92.3 33.5 - 100.5Power Source 3-phase 4 wire , 400 V, 50Hz

Capacity Cooling kW 22.40 28.00 33.50 40.00 45.00 50.40 55.90 61.50 67.00Heating 25.00 31.50 37.50 45.00 50.00 56.50 62.50 69.00 75.00

Input power Cooling kW 5.51 7.73 9.62 11.53 14.17 13.24 15.13 17.35 19.24Heating 5.72 7.83 9.28 11.45 12.60 13.55 15.00 17.11 18.56

EER Cooling - 4.07 3.62 3.48 3.47 3.18 3.81 3.69 3.54 3.48COP Heating - 4.37 4.02 4.04 3.93 3.97 4.17 4.17 4.03 4.04Air Volume m3/h 11100 11100 11100 13000 13000 11100×2 11100×2 11100×2 11100×2

Sound Pressure Level *2 Cooling dB(A) 56 58 58 60 61 60 60 61 61Heating dB(A) 58 59 60 61 61 62 62 63 63

Maximum External Static Pressure Pa 80 80 80 80 80 80 80 80 80Compressor Motor Output kW 3.9 3.9 3.9+4.5 3.9+4.5 3.9+4.5 3.9×2 3.9×2+4.5 3.9×2+4.5 3.9×2+4.5×2Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690 1690 1690 1690 1690 1690Width mm 930 930 930 1240 1240 930×2 930×2 930×2 930×2Depth mm 765 765 765 765 765 765 765 765 765

Weight kg 220 220 275 296 296 220+220 275+220 275+220 275+275Refrigerant charge kg 11.2 11.2 11.8 11.8 11.8 11.2×2 11.8+11.2 11.8+11.2 11.8×2

Pipe Sizes Liquid inches 1/2 (12.70mm) 1/2 (12.70mm) 1/2 (12.70mm) 1/2 (12.70mm) 1/2 (12.70mm) 5/8 (15.88mm) 5/8 (15.88mm) 5/8 (15.88mm) 5/8 (15.88mm)Gas inches 7/8 (22.20mm) 7/8 (22.20mm) 1-1/8 (28.58mm) 1-1/8 (28.58mm) 1-1/8 (28.58mm) 1-1/8 (28.58mm) 1-1/8 (28.58mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm)

Operating Range Cooling ˚C DB -15 to 46 -15 to 46 -15 to 46 -15 to 46 -15 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21

Rating Capacity HP 26 28 30 32

Combination Model Name AJY234LALH AJY252LALH AJY270LALH AJY288LALHUnit 1 AJY126LALH AJY144LALH AJY144LALH AJY144LALHUnit 2 AJY108LALH AJY108LALH AJY126LALH AJY144LALHUnit 3

Max. Connectable Indoor Unit *1 39 42 45 48Connectable Indoor Unit Capacity kW 36.8 - 110.3 39.3 - 117.8 42.5 - 127.5 45.0 - 135.0Power Source 3-phase 4 wire , 400 V, 50Hz

Capacity Cooling kW 73.50 78.50 85.00 90.00Heating 82.50 87.50 95.00 100.00

Input power Cooling kW 21.15 23.79 25.70 28.34Heating 20.73 21.88 24.05 25.20

EER Cooling - 3.48 3.30 3.31 3.18COP Heating - 3.98 4.00 3.95 3.97Air Volume m3/h 13000+11100 13000+11100 13000×2 13000×2

Sound Pressure Level *2 Cooling dB(A) 62 63 64 64Heating dB(A) 64 64 64 64

Maximum External Static Pressure Pa 80 80 80 80Compressor Motor Output kW 3.9×2+4.5×2 3.9×2+4.5×2 3.9×2+4.5×2 3.9×2+4.5×2Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690Width mm 930+1,240 930+1,240 1,240×2 1,240×2Depth mm 765 765 765 765

Weight kg 296+275 296+275 296+296 296+296Refrigerant charge kg 11.8×2 11.8×2 11.8×2 11.8×2

Pipe Sizes Liquid inches 5/8 (15.88mm) 5/8 (15.88mm) 3/4 (19.05mm) 3/4 (19.05mm)Gas inches 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm)

Operating Range Cooling ˚C DB -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21

Page 7: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

Space Saving Combination

Rating Capacity HP 42 44 46 48

Combination Model Name AJY378LALH AJY396LALH AJY414LALH AJY432LALHUnit 1 AJY144LALH AJY144LALH AJY144LALH AJY144LALHUnit 2 AJY126LALH AJY144LALH AJY144LALH AJY144LALHUnit 3 AJY108LALH AJY108LALH AJY126LALH AJY144LALH

Max. Connectable Indoor Unit *1 48 48 48 48Connectable Indoor Unit Capacity kW 59.3 - 177.8 61.8 - 185.3 65.0 - 195.0 67.5 - 202.5Power Source

Capacity Cooling kW 118.50 123.50 130.00 135.00Heating 132.50 137.50 145.00 150.00

Input power Cooling kW 35.32 37.96 39.87 42.51Heating 33.33 34.48 36.65 37.80

EER Cooling - 3.36 3.25 3.26 3.18COP Heating - 3.98 3.99 3.96 3.97Air Volume m3/h 13000×2 + 11100 13000×2 + 11100 13000×3 13000×3

Sound Pressure Level *2 Cooling dB(A) 65 65 65 66Heating dB(A) 65 65 66 66

Maximum External Static Pressure Pa 80 80 80 80Compressor Motor Output kW 3.9×3+4.5×3 3.9×3+4.5×3 3.9×3+4.5×3 3.9×3+4.5×3Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690Width mm 930+1,240×2 930+1,240×2 1,240×3 1,240×3Depth mm 765 765 765 765

Weight kg 296+296+275 296+296+275 296+296+296 296+296+296Refrigerant charge kg 11.8×3 11.8×3 11.8×3 11.8×3

Pipe Sizes Liquid inches 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm)Gas inches 1-5/8 (41.27mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm)

Operating Range Cooling ˚C DB -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21

Outdoor units specifications (continued)

Rating Capacity HP 34 36 38 40

Combination Model Name AJY306LALH AJY324LALH AJY342LALH AJY360LALHUnit 1 AJY108LALH AJY108LALH AJY126LALH AJY144LALHUnit 2 AJY108LALH AJY108LALH AJY108LALH AJY108LALHUnit 3 AJYA90LALH AJY108LALH AJY108LALH AJY108LALH

Max. Connectable Indoor Unit *1 48 48 48 48Connectable Indoor Unit Capacity kW 47.5 - 142.5 50.3 - 150.8 53.5 - 160.5 56.0 - 168.0Power Source

Capacity Cooling kW 95.00 100.50 107.00 112.00Heating 106.50 112.50 120.00 125.00

Input power Cooling kW 26.97 28.86 30.77 33.41Heating 26.39 27.84 30.01 31.16

EER Cooling - 3.52 3.48 3.48 3.35COP Heating - 4.04 4.04 4.00 4.01Air Volume m3/h 11100×3 11100×3 13000 + 11100×2 13000 + 11100×2

Sound Pressure Level *2 Cooling dB(A) 63 63 64 64Heating dB(A) 64 65 65 65

Maximum External Static Pressure Pa 80 80 80 80Compressor Motor Output kW 3.9×3+4.5×2 3.9×3+4.5×3 3.9×3+4.5×3 3.9×3+4.5×3Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690Width mm 930×3 930×3 930×2+1,240 930×2+1,240Depth mm 765 765 765 765

Weight kg 275+275+220 275+275+275 296+275+275 296+275+275Refrigerant charge kg 11.8×2+11.2 11.8×3 11.8×3 11.8×3

Pipe Sizes Liquid inches 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm)Gas inches 1-3/8 (34.92mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm)

Operating Range Cooling ˚C DB -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21

Page 8: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

* 1 Minimum connectable indoor unit number is 2. However ARXC72 and ARXC90 can be used signal connection.

* 2 The noise value is the value when measured in an anechoic room.

When measured in the actual installed state, surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Rating Capacity HP 32 34 36 40 42 44

Combination Model Name AJY288LALHH AJY306LALHH AJY324LALHH AJY360LALHH AJY378LALHH AJY396LALHHUnit 1 AJY108LALH AJY126LALH AJY126LALH AJY126LALH AJY126LALH AJY144LALHUnit 2 AJY108LALH AJY108LALH AJY126LALH AJY126LALH AJY126LALH AJY126LALHUnit 3 AJYA72LALH AJYA72LALH AJYA72LALH AJY108LALH AJY126LALH AJY126LALH

Max. Connectable Indoor Unit *1 48 48 48 48 48 48Connectable Indoor Unit Capacity kW 44.9 - 134.1 48.0 - 143.8 51.2 - 153.6 56.8 - 170.2 60.0 - 180.0 62.5 - 187.5Power Source 3-phase 4 wire , 400 V, 50Hz

Capacity Cooling kW 89.40 95.90 102.40 113.50 120.00 125.00Heating 100.00 107.50 115.00 127.50 135.00 140.00

Input power Cooling kW 24.75 26.66 28.57 32.68 34.59 37.23Heating 24.28 26.45 28.62 32.18 34.35 35.50

EER Cooling - 3.61 3.60 3.58 3.47 3.47 3.36COP Heating - 4.12 4.06 4.02 3.96 3.93 3.94Air Volume m3/h 11100×3 13000 + 11100×2 13000×2 + 11100 13000×2 + 11100 13000×3 13000×3

Sound Pressure Level *2 Cooling dB(A) 62 63 64 64 65 65Heating dB(A) 64 64 65 65 66 66

Maximum External Static Pressure Pa 80 80 80 80 80 80Compressor Motor Output kW 3.9×3+4.5×2 3.9×3+4.5×2 3.9×3+4.5×2 3.9×3+4.5×3 3.9×3+4.5×3 3.9×3+4.5×3Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690 1690 1690Width mm 930×3 930×2 + 1240 930 + 1240×2 930 + 1240×2 1240×3 1240×3Depth mm 765 765 765 765 765 765

Weight kg 275+275+220 296+275+220 296+296+220 296+296+275 296+296+296 296+296+296Refrigerant charge kg 11.8×2+11.2 11.8×2+11.2 11.8×2+11.2 11.8×3 11.8×3 11.8×3

Pipe Sizes Liquid inches 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm) 3/4 (19.05mm)Gas inches 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm) 1-5/8 (41.27mm)

Operating Range Cooling ˚C DB -5 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21

Rating Capacity HP 16 22 24 26 28 30

Combination Model Name AJY144LALHH AJY198LALHH AJY216LALHH AJY234LALHH AJY252LALHH AJY270LALHHUnit 1 AJYA72LALH AJY126LALH AJYA72LALH AJYA90LALH AJY108LALH AJY126LALHUnit 2 AJYA72LALH AJYA72LALH AJYA72LALH AJYA72LALH AJYA72LALH AJYA72LALHUnit 3 AJYA72LALH AJYA72LALH AJYA72LALH AJYA72LALH

Max. Connectable Indoor Unit *1 30 33 36 39 42 45Connectable Indoor Unit Capacity kW 22.4 - 67.2 31.2 - 93.6 33.6 - 100.8 36.4 - 109.2 39.2 - 117.4 42.4 - 127.2Power Source 3-phase 4 wire , 400 V, 50Hz

Capacity Cooling kW 44.80 62.40 67.20 72.80 78.30 84.80Heating 50.00 70.00 75.00 81.50 87.50 95.00

Input power Cooling kW 11.02 17.04 16.53 18.75 20.64 22.55Heating 11.44 17.17 17.16 19.27 20.72 22.89

EER Cooling - 4.07 3.66 4.07 3.88 3.79 3.76COP Heating - 4.37 4.08 4.37 4.23 4.22 4.15Air Volume m3/h 11100×2 13000 + 11100 11100×3 11100×3 11100×3 13000 + 11100×2

Sound Pressure Level *2 Cooling dB(A) 59 61 61 62 62 63Heating dB(A) 59 62 61 62 63 63

Maximum External Static Pressure Pa 80 80 80 80 80 80Compressor Motor Output kW 3.9×2 3.9×2+4.5 3.9×3 3.9×3 3.9×3+4.5 3.9×3+4.5Heat Exchanger Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin Blue Fin

DimensionsHeight mm 1690 1690 1690 1690 1690 1690Width mm 930×2 930 + 1240 930×3 930×3 930×3 930×2 + 1240Depth mm 765 765 765 765 765 765

Weight kg 220+220 296+220 220+220+220 220+220+220 275+220+220 296+220+220Refrigerant charge kg 11.2×2 11.8+11.2 11.2×3 11.2×3 11.8+11.2×2 11.8+11.2×2

Pipe Sizes Liquid inches 1/2 (12.70mm) 5/8 (15.88mm) 5/8 (15.88mm) 5/8 (15.88mm) 5/8 (15.88mm) 3/4 (19.05mm)Gas inches 1-1/8 (28.58mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm) 1-3/8 (34.92mm)

Operating Range Cooling ˚C DB -5 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46Heating ˚C WB -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21 -20 to 21

Energy Efficiency Combination

Note: Specifications are based on the following conditions. Cooling : Indoor temperature of 27°C DB / 19°C WB, and outdoor temperature of 35°C DB/24°C WB. Heating : Indoor temperature of 20°C DB / (15°C WB), and outdoor temperature of 7°C DB / 6°C WB.

Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.When cooling operation will be conducted at outdoor air temperature below -5°C, the outdoor unit must be installed in a position that is higher than or equal to those of indoor units

Page 9: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

Model Nominal Capacity Dimensions (HxWxD) Room Air Circulation Noise Levels (Sound Pressure)

Indoor Cooling kW Heating kW mm (high) m3/h dB(A) - L / M / H

Floor Ceiling

ABYA12LBTH 3.60 4.00 199x990x665 660 28 / 32 / 36

ABYA14LBTH 4.50 5.00 199x990x665 780 34 / 36 / 40

ABYA18LBTH 5.60 6.30 199x990x665 1,000 35 / 39 / 46

ABYA24LBTH 7.10 8.00 199x990x665 1,000 37 / 42 / 47

Ceiling

ABYA30LBTH 9.00 10.00 240x1,660x700 1,630 33 / 38 / 42

ABYA36LBTH 11.20 12.50 240x1,660x700 1,690 34 / 38 / 45

ABYA45LBTH 12.50 14.00 240x1,660x700 2,010 35 / 42 / 48

ABYA54LBTH 14.00 16.00 240x1,660x700 2,270 36 / 45 / 51

Compact Duct

ARXB07LALH 2.20 2.80 217x663x595 370 24 / 26 / 29

ARXB09LALH 2.80 3.20 217x663x595 440 27 / 29 / 31

ARXB12LALH 3.60 4.00 217x953x595 590 25 / 28 / 30

ARXB14LALH 4.50 5.00 217x953x595 800 30 / 32 / 33

ARXB18LALH 5.60 6.30 217x953x595 890 30 / 34 / 36

Slim Duct

ARXD07LATH 2.20 2.80 198x700x620 550 22 / 25 / 28

ARXD09LATH 2.80 3.20 198x700x620 600 24 / 26 / 29

ARXD12LATH 3.60 4.00 198x700x620 600 24 / 27 / 30

ARXD14LATH 4.50 5.00 198x700x620 800 28 / 32 / 34

ARXD18LATH 5.60 6.30 198x900x620 940 28 / 32 / 34

ARXD24LATH 7.10 8.00 198x900x620 1,330 29 / 32 / 35

Duct

ARXA24LATH 7.10 8.00 270x1,135x700 1,280 34 / 36 / 38

ARXA30LATH 9.00 10.00 270x1,135x700 1,280 36 / 38 / 40

ARXA36LATH 11.20 12.50 270x1,135x700 1,720 39 / 41 / 43

ARXA45LATH 12.50 14.00 270x1,135x700 1,720 39 / 41 / 43

Low Static Duct

ARXB24LATH 7.10 8.00 270x1,135x700 1,100 25 / 27 / 31

ARXB30LATH 9.00 10.00 270x1,135x700 1,410 29 / 32 / 34

ARXB36LATH 11.20 12.50 270x1,135x700 1,710 33 / 35 / 37

ARXB45LATH 12.50 14.00 270x1,135x700 1,970 36 / 38 / 41

High Static Duct

ARXC36LATH 11.20 12.50 400x1,050x500 2,600 32 / 38 / 45

ARXC45LATH 12.50 14.00 400x1,050x500 3,500 42 / 45 / 49

ARXC60LATH 18.00 20.00 400x1,050x500 3,500 42 / 45 / 49

ARXC72LATH 22.40 25.00 450x1,550x700 3,900 45 / 48 / 51

ARXC90LATH 25.00 28.00 450x1,550x700 4,300 49 / 51 / 53

Compact Wall Mounted

ASYA07LACH 2.20 2.80 275x790x215 490 27 / 33 / 35

ASYA09LACH 2.80 3.20 275x790x215 500 27 / 33 / 36

ASYA12LACH 3.60 4.10 275x790x215 560 31 / 35 / 39

ASYA14LACH 4.50 5.00 275x790x215 670 32 / 37 / 44

ASYE07LACH 2.20 2.80 275x790x215 490 26 / 32 / 34

ASYE09LACH 2.80 3.20 275x790x215 500 26 / 32 / 35

ASYE12LACH 3.60 4.10 275x790x215 560 30 / 34 / 38

ASYE14LACH 4.40 5.00 275x790x215 680 30 / 35 / 43

Wall Mounted

ASYA18LACH 5.60 6.30 320x998x228 840 35 / 39 / 41

ASYA24LACH 7.10 8.00 320x998x228 1,100 35 / 43 / 48

ASYA30LACH 8.00 9.00 320x998x228 1,240 35 / 45 / 52

Compact Cassette

AUXB07LALH 2.20 2.80 245x570x570 540 25 / 30 / 34

AUXB09LALH 2.80 3.20 245x570x570 550 25 / 30 / 35

AUXB12LALH 3.60 4.10 245x570x570 600 27 / 34 / 37

AUXB14LALH 4.50 5.00 245x570x570 680 27 / 34 / 38

AUXB18LALH 5.60 6.30 245x570x570 710 27 / 35 / 41

AUXB24LALH 7.10 8.00 245x570x570 1,030 30 / 44 / 50

Cassette

AUXD18LALH 5.60 6.30 246x840x840 1,150 29 / 30 / 36

AUXD24LALH 7.10 8.00 246x840x840 1,280 29 / 33 / 38

AUXA30LALH 9.00 10.00 288x840x840 1,600 33 / 38 / 40

AUXA36LALH 11.20 12.50 288x840x840 1,800 33 / 38 / 44

AUXA45LALH 12.50 14.00 288x840x840 1,900 33 / 39 / 46

AUXA54LALH 14.00 16.00 288x840x840 2,000 33 / 39 / 47

Page 10: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

Connectable indoor unit number

up to 48Wide variation of indoor units

12 types, 55 models

Connectable indoor unit capacity

Ratio up to 150%

* Available Summer 2011

V-II VRF ACCESSORIES

Description Part Number

Wireless Remote Controller UTYLNHY

Wired Remote Controller UTYRNKY

Simple Remote Controller (with Master Control) UTYRSKY

Simple Remote Controller (without Master Control) UTYRHKY

Group Remote Controller UTYCGGY

Touch Panel Controller UTYDTGY

Central Remote Controller* UTYDCGY

System Controller UTYAPGX

Service Tool (Software) UTYASGX

Web Monitoring Tool UTYAMGX

Signal Amplifier UTYVSGX

Network Convertor UTYVGGX

"Network Convertor for ""LONWORKS"" UTYVLGX

BACnet Gateway UTYABGX

External Switch Controller UTYTEKX

IR Receiver Kit for Cassette UTYLRHYB1

IR Receiver Unit for Duct UTBYWB

Indoor Separation Tube - Indoor Capa Total 180 or more UTRBP567X

Indoor Separation Tube - Indoor Capa Total 91 to 180 UTRBP180X

Indoor Separation Tube - Indoor Capa Total 90 or less UTRBP090X

Outdoor Separation Tube UTRCP567X

Header - 6 connections - Small Diameter UTRH0906L

Header - 6 connections - Large Diameter UTRH1806L

Header - 8 connections - Small Diameter UTRH0908L

Header - 8 connections - Large Diameter UTRH1808L

Remote Sensor Unit UTDRS100

Flange (Round) for Duct indoor unit UTDRF204

Long Life Filter UTDLF25NA

Long Life Filter UTDLF60KA

High capacity connection

Page 11: V-II series vrf - Squarespace · V-II series vrf These newly designed compact outdoor units are smart and cutting edge. They come with an extensive line-up from 8HP (22.3kW) to 48HP

FG Eurofred Limited, Unit 150, Centennial Park, Centennial Avenue, Elstree, Borehamwood, Herts WD6 3SG. Tel +44 (0)20 8731 3450 Fax +44 (0)20 8731 3451 www.fgeurofred.co.uk

Cooling & Heating capacities are based on the following conditions:Cooling: Indoor Temp.: 27°C DB/19°C WB, Outdoor Temp.: 35°C DB/24°C WB Heating: Indoor Temp.: 20°C DB, Outdoor Temp.: 7°C DBNote: Fuse ratings shown are only for information. Any fuses or MCB’s installed on-site should be sized in accordance with I.E.E. regulations.

For full installation details contact FG Eurofred or your local distributor.

Fujitsu air conditioning products are available from FG Eurofred and local distributors.

Distributed by:

The company reserves the right to make any variation in specification to the equipment described or to withdraw or replace products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form any part of any contract. All equipment and services are supplied subject to FG Eurofred's Terms and Conditions of Sale.

ISO 9001Certified number:09 100 89394

Fujitsu General (Thailand) Co., Ltd.

ISO 14001Certified number:09 104 9245

ISO 9001Certified number:09 100 79269

Fujitsu General Shanghai) Co., Ltd.

ISO 14001Certified number:104692

Certificate: 09 100 79269