Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
UPS – Evoluzione Tecnologica e
Riferimenti Normativi
presso
Edificio Fermi - Aula Corbino
![Page 2: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/2.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
![Page 3: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/3.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
![Page 4: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/4.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
4
![Page 5: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/5.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
Roma, 26 Giugno 2012
IMPIANTI DI ALIMENTAZIONE E STAZIONI DI ENERGIA
![Page 6: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/6.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
6
SISTEMI DI ALIMENTAZIONE PER TELECOMUNICAZIONI IN REGIME DI CONTINUITÀ ASSOLUTA
• Esigenza di disponibilità elevatissima:
– Il servizio deve essere sempre garantito.
– I costi in caso di interruzione del servizio sono alti.
– I costi di esercizio e manutenzione dipendono
fortemente dall’architettura di sistema adottata.
![Page 7: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/7.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
7
La rete di distribuzione pubblica dell’energia non
garantisce continuità assoluta sulla fornitura elettrica
• I sistemi TLC richiedono:
– alimentazione senza soluzione di continuità in c.c. e in
c.a. (alimentazione di sicurezza): apparati TLC, apparati
di controllo e supervisione;
– alimentazione con soluzione di continuità in c.a.
(alimentazione di riserva): apparati CDZ e di supporto.
SISTEMI DI ALIMENTAZIONE PER TELECOMUNICAZIONI IN REGIME DI CONTINUITÀ ASSOLUTA
![Page 8: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/8.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
8
• PASSATO 99,9
• PRESENTE 99,99
• FUTURO 99,9999
SCENARIO EVOLUTIVO DELLE ESIGENZE DI
DISPONIBILITA’
PER I SISTEMI DI TLC
SISTEMI DI ALIMENTAZIONE PER TELECOMUNICAZIONI IN REGIME DI CONTINUITÀ ASSOLUTA
![Page 9: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/9.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
9
INTERFACCIA ELETTRICA in c.a. e in c.c.
ETS 300 132-1 Corrente alternata: tensione nominale 230/400Vac
tolleranza statica: ± 10%
t < 500 ms: ± 15%
t < 2 ms: ± 40%
ETS 300 132-2 Corrente continua: tensione nominale - 48Vcc
intervallo di tolleranza: -40.5 -57.6 V
(dVcc/dt) max = 5 V/ms
![Page 10: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/10.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
10
Schema di un impianto di alimentazione
RETE
G.E.
Alimentazione senza soluzione
di continuiità in c.a.
Alimentazione con soluzione di
continuità in c.a. per CDZ
Alimentazione senza soluzione
di continuità in c.c.
![Page 11: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/11.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
11
Architettura centralizzata in c.c.
S.E.
Autocommutatore
Batterie
Quadro Distribuzione
di sala
![Page 12: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/12.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
12
Apparati TLC
Riducendo la distribuzione in c.c. si converge verso
l'architettura decentrata o di sala.
Architettura centralizzata in c.c.
![Page 13: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/13.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
13
Architettura decentrata o di sala in c.c.
MET
Condotto schermato RETE (AC)
Collettore +
Autocommutatore Batterie
S.E.
Collettore +
Autocommutatore Batterie
S.E.
![Page 14: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/14.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
14
Architettura distribuita o di fila in c.c.
Apparati TLC
Eliminando in pratica la distribuzione in c.c. si converge verso
l'architettura distribuita o di fila.
![Page 15: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/15.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
15
Architettura distribuita o di fila in c.c.
MET
Condotto schermato RETE (AC)
Collettore +
Autocommutatore
Collettore +
Autocommutatore
S.E. in c.c.
Vano Batterie
![Page 16: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/16.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
16
Architettura centralizzata in c.a.
Apparati TLC
![Page 17: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/17.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
17
BATTERIE DI ACCUMULATORI - COLLEGAMENTI
![Page 18: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/18.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
18
ACCUMULATORI
![Page 19: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/19.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
19
Stazioni di Energia in c.c.
-48Vc.c.
Da 30Ampere, ad alcune migliaia di Ampere
![Page 20: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/20.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
20
Stazioni di Energia in c.a. (INV) - c.c./c.a.
230Vc.a.monofase o 400Vc.a.
Da 1500W, ad alcune centinaia di kW
![Page 21: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/21.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
21
Gruppi di continuità (UPS)- c.a./c.a.
230Vc.a.monofase (da 400VA a 30kVA)
400Vc.a. Trifase (da 10 a 900kVA)
Cos'è un UPS?
Un gruppo statico di continuità o UPS (Uninterruptible Power Supply) è un sistema in grado di fornire energia elettrica di alta
qualità, senza interruzioni.
Un generatore non può essere considerato un UPS perché, in caso di disturbi elettrici, intercorrerà sempre un intervallo di
tempo tra l'interruzione dell'alimentazione elettrica e l'entrata in funzione del generatore in standby. Questo lasso di tempo è
necessario affinché un generatore ripristini l'alimentazione elettrica dopo un'interruzione di rete. Anche una breve interruzione
di corrente può comportare danni alle apparecchiature, perdita di dati e conseguenti perdite finanziarie, per questo è
necessario proteggere il proprio lavoro con i gruppi statici di continuità.
I sistemi UPS non solo offrono protezione da qualsiasi tipo di interruzione dell'alimentazione elettrica, ma sono anche in
grado di filtrare un'ampia tipologia di disturbi che colpiscono l'alimentazione di rete, offrendo ai carichi più sensibili
un'alimentazione perfetta.
In poche parole, l’UPS svolge due funzioni:
L'UPS filtra i disturbi provenienti dall'alimentazione di rete.
L'UPS fornisce alimentazione ai carichi in caso di interruzioni dell'alimentazione di rete.
![Page 22: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/22.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
22
Schema a blocchi di un UPS
INGRESSO RADDRIZZATORE
BY-PASS MANUALE
INGRESSO RISERVA
BY PASS STATICO
INVERTER RADDRIZZATORE
BATTERIE
![Page 23: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/23.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
23
GRUPPO ELETROGENO
![Page 24: UPS Evoluzione](https://reader030.vdocuments.mx/reader030/viewer/2022021422/5a6e135f7f8b9ac0678b5477/html5/thumbnails/24.jpg)
Technical Infrastructures TIS - Technical Infrastructures
Federico Di Carlo
24
ASPETTI CIRCA:
• Ecocompatibilità e Ambiente
• Risparmio Energetico
• Impianti alternativi:
•Solare
•Eolico
•Celle a combustibile (H2)