ups dpa upscale 120kva (6x20kva) · ups dpa upscale 120kva (6x20kva) ... ups dpa upscale 120kva...

40
Ingenieurbüro EMV-Technik Solothurn UPS DPA UPSCALE 120kVA (6x20kVA) Measuring of emitted spectra according to product standard and Test of the immunity according to standard EN 62040-2:05 EN 62040-2:05 Newave SA Test report Ber090819 Of August 19th, 2009

Upload: phamkhue

Post on 21-Apr-2018

259 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Ingenieurbüro EMV-Technik Solothurn

UPS DPA UPSCALE 120kVA(6x20kVA)

Measuring of emitted spectra according to product standard

and

Test of the immunity according to standard

EN 62040-2:05

EN 62040-2:05

Newave SA

Test report Ber090819

Of August 19th, 2009

Page 2: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 2 of 40

http://www.emvtechnik.ch

Contents

CONTENTS 2

1. INTRODUCTION 4

1.1. MANUFACTURER 41.2. CONDITIONS OF TEST 41.3. STANDARDS AND SPECIFICATIONS 51.4. RESPONSIBLE ENGINEER 51.5. ATTEST 6

2. PLAN OF TESTING 7

2.1. SPECTRUM MEASUREMENT 72.1.1. LIMITS OF EMISSION 72.2. IMMUNITY 82.2.1. MINIMUM REQUIREMENTS FOR UPS OF CATEGORIE C2 AND C3 82.2.2. PERFORMANCE CRITERIA FOR IMMUNITY TESTS 9

3. MEASUREMENTS AND TESTS 10

3.1. MEASUREMENT OF THE EMITTED SPECTRA 103.1.1. CONDUCTED EMISSIONS (DBV) 103.1.2. RADIATED EMISSIONS (DBV/M) 193.2. MEASUREMENT OF IMMUNITY TEST 273.2.1. IMMUNITY TO RADIO FREQUENCY EM-FIELD, AMPLITUDE MODULATED 273.2.2. IMMUNITY TO ELECTROSTATIC DISCHARGE ESD 30

Page 3: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 3 of 40

http://www.emvtechnik.ch

3.2.3. IMMUNITY TO FAST TRANSIENTS (BURSTS) 323.2.4. TEST MIT ENERGIEREICHEN IMPULSEN (SURGE) 35

5. EQUIPMENT 37

5.1. EQUIPMENT OF MEASURING SPECTRA 375.2. EQUIPMENT OF TESTING IMMUNITY 38

6. ILLUSTRATION 39

Page 4: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 4 of 40

http://www.emvtechnik.ch

1. Introduction

1.1. Manufacturer

Company’s name Newave SA

Adressvia Luserte, Sud 9,

CH-6572 Quartino

Get in touch with Mr. Marbach, Filippo

PHONE +41-91 850 2929

FAX +41-91-840 1254

MAIL TO: [email protected]

1.2. Conditions of test

Device under testUPS DPA UPSCALE 120kVA (6x20kVA),

series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA 000048 / DPA000079 / DPA 000076

PURPOSE Modular UPS Cabinet Configuration 4x400Vac // 4x400Vac

PLACE OF ACTION Industrial aereas

CUT DOWN ON USING This equipment should not be installed in domestic aereas

Place of testingTest Office Newave, Quartino and EMC Test center Swisscom Ostermundigen, August19th, 2009

PLAN OF TESTING

The test was made with the UPS 120kVA (6x20kVA) in the following conditions:

Rated input voltage

Normal mode of operation

Linear load at rated active output power

Measuring of the spectra in worst case conditionUPS of category C3 (EN62040-2:05)

TESTING GROUND See §4.

CONDITIONS OF 23°C / 1010mbar / 60%RH

Page 5: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 5 of 40

http://www.emvtechnik.ch

ENVIRONS

1.3. Standards and specifications

IEC REQUIREMENTS EMC 2004/108/EG

Basic standard Emission EN 61000-6-4:07

Basic standard Immunity EN 61000-6-2:05

Standard CISPR Emission IEC/CISPR 11:03+A:06

Product standard EmissionEN 62040-2:05 with limit for Category C3 UPS

EN 62040-2:05 + with limit Category C3 UPS for UPS (table 2)

Product standard ImmunityEN 62040-2:05 with minimum requirements for UPS Category C2(table 6)

1.4. Responsible Engineer

Company’s name Ing. Büro EMV-Technik

AdressHans Huber-Strasse 41,

CH- 4502 Solothurn

Get in touch with Mr. Jakob Jordi, dipl.el.ing. ETH

PHONE +41-32-623 49 79

FAX +41-32-623 69 52

MAIL TO: [email protected]

Page 6: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 6 of 40

http://www.emvtechnik.ch

1.5. Attest

Statement

The UPS DPA UPSCALE type: 120kVA (6x20kVA)

conforms with the requirements of the

EMC Directive 2004/108/EG

by its design and type of construction.

Basic standard(Emission)

EN 61000-6-4:07

Basic standard(Immission)

EN 61000-6-2:05

Product standard(Emission)

EN 62040-2:05Radio interferenceRFI

150kHz30MHz

30MHz1GHz

Limit Category C3UPS √

ESDEN 61000-4-2:95+A1:98 √

EM-Field RF(AM)

EN 61000-4-3:02+A1:02 √

Burst EN 61000-4-4:04 √

Product standard(Immission) EN 62040-2:05 EMC-Immunity

SurgeEN 61000-4-5:95+A1:01 √

√ Test passed successfully

Θ Test not passed

Ingenieurbüro EMV-Technik

Jakob Jordi, dipl.el.ing.ETHZ

Solothurn, 27. Oktober 2009

Page 7: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 7 of 40

http://www.emvtechnik.ch

2. Plan of testing

2.1. Spectrum measurement

2.1.1.Limits of emission

Measuring Frequency Limit In > 16A Limit In <16A Productstandard

30MHz<f<230MHz 50dbμV/m QP 40dbμV/m QPLimits of radiatedemission (dbμV/m)

Distance: 10m230MHz<f<1GHz 50dbμV/m QP 47dbμV/m QP

EN 62040-2:05

150kHz<f<500kHz100dbμV QP

90dbμV AV

79dbμV QP

66dbμV AV

500kHz<f<5MHz86dbμV QP

76dbμV AV

73dbμV QP

60dbμV AV

Limits of mainsterminal inter-ference voltage(dbμV)

4 x 400Vac/200kVA5MHz<f<30MHz

90…70dbμV QP

80…60dbμV AV

60dbμV QP

60dbμV AV

EN 62040-2:05

Page 8: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 8 of 40

http://www.emvtechnik.ch

2.2. Immunity

2.2.1.Minimum requirements for UPS of categorie C2 and C3

Table 6 of standard EN 62040-2:05

PortStandard of test

method Level Unit Performance Result

Enclosure port

Radio frequency EM-field

AM modulatedEN 6100-4-3

80…1000

10

80%

MHz

V/m

AM1kHz

A √

Electrostatic discharge ESD EN 6100-4-2±8.0

±15.0

kV contact

kV air

B √

Signal and Control ports

Fast transient (Burst) EN 61000-4-4

±1.0

5/50

5

kV

τr/τh ns

kHz

B √

High voltage (Surge) EN 61000-4-5±1.0

1,2/50

kV

τr/τh μsB √

DC power port

Fast transient (Burst) EN 61000-4-4

±2.0

5/50

5

kV

τr/τh ns

kHz

B √

AC power port (input /output)

Fast transient (Burst) EN 61000-4-4

±4.0

5/50

5

kV

τr/τh ns

kHz

B √

High voltage (Surge) EN 61000-4-5±2.0 (L/L)

±4.0(L/PE)

kV B √

√ Test passed successfully

Θ Test not passed

Page 9: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 9 of 40

http://www.emvtechnik.ch

2.2.2.Performance criteria for immunity tests

Table 4 Criterion A Criterion B

External and internal indi-cations and metering

Change only during test Change only during test

Control signals to externaldevices No change

Change only temporarily in consis-tency with the actual UPS mode ofoperation

Mode of operation No change Change only temporarily

The UPS DPA UPSCALE / 120kVA (6x20kVA) is resistant to the re-quired immunity tests in accordance with criterion A.

Page 10: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 10 of 40

http://www.emvtechnik.ch

3. Measurements and tests

3.1. Measurement of the emitted spectra

3.1.1.Conducted emissions (dbV)

Coducted emissionUPS DPA UPSCALE 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA 000062 / DPA 000048 / DPA 000079 / DPA 000076

August 19th, 2009

MeasuringPassive probe, type ESH2-Z3 by Rhode+Schwarz on AC input / output power ports inthe frequency range of 150kHz < f < 30MHz

Limits

Blue: Peak

Quasi Peak

Green: Average

+ Average

With reference to the blue line of the diagram

With reference to the blue line of the diagram

With reference to the green line of the diagram

With reference to the green line of the diagram

Standard EN 62040-2:05 with limit Category C3 UPS of EN 62040-2:05

Place of measuring Test Office Newave, Quartino and EMC Test center Swisscom Ostermundigen

Spectrum analyzer

Minimal Level

Maximal Level

Bandwidth IFBW

0db

90db

10kHz

Detection

Final Detection

Peak / Average

Quasi Peak (Time 1 Sek.)

150kHz < f < 1MHzStep

Time / step

f = 2kHz

t = 2ms

1MHz < f < 10MHzStep

Time / step

f = 9kHz

t = 1msParameter

10MHz < f < 30MHzStep

Time / step

f = 20kHz

t = 1ms

Page 11: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 11 of 40

http://www.emvtechnik.ch

Measuring No. S11Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC input power port, neutralline

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 12: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 12 of 40

http://www.emvtechnik.ch

Measuring No. S12Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC input power port, Phase L1

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 13: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 13 of 40

http://www.emvtechnik.ch

Measuring No. S13Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC input power port, Phase L2

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 14: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 14 of 40

http://www.emvtechnik.ch

Measuring No. S14Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC input power port, Phase L3

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 15: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 15 of 40

http://www.emvtechnik.ch

Measuring No. S15Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC output power port, Neutralline

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 16: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 16 of 40

http://www.emvtechnik.ch

Measuring No. S16Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC output power port, Phase L1

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 17: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 17 of 40

http://www.emvtechnik.ch

Measuring No. S17Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC output power port, Phase L2

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 18: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 18 of 40

http://www.emvtechnik.ch

Measuring No. S18Ber090819

UPS DPA UPSCALE, 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

MeasuringAC output power port, Phase L3

Frequency range: 150kHz / 30MHz

Operating condition The UPS has been switched on

Mode 50% of load, I = 68A

ResultThe requested limits for Category C3 UPS of EN 62040-2:05 are respectedby peak values and average values

Page 19: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 19 of 40

http://www.emvtechnik.ch

3.1.2.Radiated emissions (dbV/m)

Radiated emission

UPS DPA UPSCALE, type 120kVA (6x20kVA),

Series no: DPA 000052 / DPA 000053 / DPA 000062 / DPA 000048 / DPA 000079 / DPA 000076

October 21st, 2009

Measuring Enclosure port in the frequency range 30MHz < f <300MHz < 1GHz

Standard EN 62040-2:05 with limit Category C3 UPS of EN 62040-2:05

Place of measuring Test Office Newave

Operating condition -

Mode -

AntennaBifocus antenna type HK 116 by Rhode + Schwarz

Distance: 10m, Height: 2m, Polarisation: vertical / horizontal

Spectrum analyzer

Minimal Level

Maximal Level

Bandwidth IFBW

0db

90db

120kHz

Detection

Final Detection

Peak

Quasi Peak (1 Sek.)

30MHz < f < 100MHzStep

Time / step

f = 80kHz

t = 2ms

100MHz < f < 300MHzStep

Time / step

f = 100kHz

t = 1msParameter

300MHz < f < 1000MHzStep

Time / step

f = 120kHz

t = 1ms

Page 20: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 20 of 40

http://www.emvtechnik.ch

Measuring No. F01Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

October 21st, 2009

Measuring Enclosure port, Frequency range: 30MHz / 100MHz

Operating condition The UPS has been switched off

Mode ---

Antenna

Backside of the UPS

Height: 2m, distance: 10m

Polarisation: horizontal

Suppression of interfe-rence

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 10dbV

Page 21: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 21 of 40

http://www.emvtechnik.ch

Measuring No. F02Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

October 21st, 2009

Measuring Enclosure port, Frequency range: 30MHz / 300MHz

Operating condition The UPS has been switched off

Mode ----

Antenna

Backside of the UPS

Height: 2m, distance: 10m

Polarisation: vertical

Suppression of interfe-rence

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 10dbV

Page 22: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 22 of 40

http://www.emvtechnik.ch

Measuring No. F03Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

October 21st, 2009

Measuring Enclosure port, Frequency range: 30MHz / 300MHz

Operating condition The UPS has been switched on

Mode With 6 modules, with Load (I=24A)

Antenna

Backside of the UPS

Height: 2m, distance: 10m

Polarisation: vertical

Suppression of interfe-rence

Result

The requested limit for Category C3 UPS of EN 62040-2:05 is not respectedin the frequency range f<40MHz

We see the same exceeding values like the SWISSCOM measurement.(Page 20/21)

The worst case we get of the backside of UPS wiht vertical antennapolarisation

Page 23: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 23 of 40

http://www.emvtechnik.ch

Measuring No. F23Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

October 21st, 2009

Measuring Enclosure port, Frequency range: 30MHz / 100MHz

Operating conditionThe UPS has been switched off

The UPS has been switched on

Mode With 6 Modules and load (I = 24A)

Antenna

Backside of the UPS

Height: 2m, distance: 10m

Polarisation: vertikal

Suppression of interfe-rence

The neutral lines for input/output at the backside motherboards are separated. Nocommon neutral line.

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 3dbV

Page 24: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 24 of 40

http://www.emvtechnik.ch

Measuring No. F24

Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

Measuring Enclosure port, Frequency range: 30MHz / 100MHz, front side

Operating conditionModul 1 /2/3/4/5/6

UPS has been switched off

Mode With 6 Modules and load (I = 24A)

Antenna

Back side of the UPS

Height: 2m, distance: 10m

Polarisation: horizontal

Suppression of interfe-rence

The neutral lines for input/output at the backside motherboards are separated. Nocommon neutral line.

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 10dbμV/m

Page 25: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 25 of 40

http://www.emvtechnik.ch

Measuring No. F25

Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

Measuring Enclosure port, Frequency range: 30MHz / 100MHz, left side

Operating conditionModul 1 /2/3/4/5/6

UPS has been switched off

Mode With 6 Modules and load (I = 24A)

Antenna

Left side of the UPS

Height: 2m, distance: 10m

Polarisation: vertical

Suppression of interfe-rence

The neutral lines for input/output at the backside motherboards are separated. Nocommon neutral line.

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 6dbμV/m

Page 26: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 26 of 40

http://www.emvtechnik.ch

Measuring No. F26

Ber090819

UPS DPA UPSCALE, type 120kVA (6x20kVA),Series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

Measuring Enclosure port, Frequency range: 30MHz / 100MHz, front side

Operating condition Modul 1 /2/3/4/5/6

Mode With 6 Modules and load (I = 24A)

Antenna

Front side of the UPS

Height: 2m, distance: 10m

Polarisation: vertical

Suppression of interfe-rence

The neutral lines for input/output at the backside motherboards are separated. Nocommon neutral line.

ResultThe requested limit for Category C3 UPS of EN 62040-2:05 is respected.

The least value respects the limit with 6dbμV/m

Page 27: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 27 of 40

http://www.emvtechnik.ch

3.2. Measurement of immunity test

3.2.1. Immunity to radio frequency EM-field, amplitude modulated

Enclosure portUPS DPA UPSCALE, type 120kVA (6x20kVA),

series no: DPA 000052 / DPA 000053 / DPA 0000 62/ DPA 000048 / DPA 000079 / DPA 000076

August 19th, 2009

StandardEN 62040-2:05 with requirements for Category C3 UPS of EN 62040-2:05

Electromagnetic field (EM radiation) according to EN 61000-4-3:06

Place of testing EMC test lab Swisscom, Bern

Intensity E = 10V/m

ModulationAM: Modulation: f = 1kHz, Amplitude: 80%

PM: Modulation: f = 200Hz Amplitude 50%Level

Range of frequency80MHz 1000MHz with AM

900MHz 5MHz with PM

Amplifier Type 200W: type 200W1000M7 by AMPLIFIER RESEARCH

Signal generator 80MHz 1000MHz Type SME03 by Rohde & Schwarz

Field probe 80MHz 1000MHz Type HI-442IG by Holaday

Antenna 80MHz 1000MHz Type AT5080 by Amplifier Research

Operating conditionNormal operating condition with linear load 3x18kW connected to theUPS output.

Place of testing Test Office Newave, Quartino and EMC Test center Swisscom Ostermundigen

Suppressions The front door is correct earthed by two bond straps

Result

The nominal UPS voltage (230Vac) at the output changed during the testless than 55.2mV.

The requested performance for Category C3 UPS of EN 62040-2:05 is o.k.

Acceptance criterion A.

Horizontal polarityof the antenna

Front side

55.2mV

Front side

27.9mV

Front side

21.1mV

Front side

18.0mVStandard deviationduring test

Vertical polarity ofthe antenna

Front side

16.2mV

Left side

19.5mV

Back side

18.2mV

Right side

18.4mV

Page 28: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA) dipl. ing. J. Jordi, EMV-Technik Solothurn Page 28 of 40

http://www.emvtechnik.ch

EM-radiation test DPA Upscale 120KVAhorizontal antenna with E=10V/m

234.0

234.2

234.4

234.6

234.8

235.0

235.2

235.4

235.6

235.8

236.0

0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1'000.0

UP

Sou

tpu

tvo

ltage

L3/

N(V

olt)

Frequency (MHz)

Front side Left side Back sideRight side Average

Page 29: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA) dipl. ing. J. Jordi, EMV-Technik Solothurn Page 29 of 40

http://www.emvtechnik.ch

EM-radiation test DPA Upscale 120KVAvertical antenna with E=10V/m

234.0234.2234.4234.6234.8235.0235.2235.4

235.6235.8236.0

0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1'000.0

UP

Sou

tpu

tvo

ltage

L3/

N(V

Frequency (MHz)

Front side Left side Back sideRight side Average

Page 30: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 30 of 40

http://www.emvtechnik.ch

3.2.2.Immunity to Electrostatic discharge ESD

Enclosure port

120kVA (6x20kVA),

series no: DPA 000052 / DPA 000053 / DPA 000062 / DPA 000048 / DPA 000079 / DPA 000076

August 19th, 2009

StandardEN 62040-2:05 with requirements for Category C3 UPS of EN 62040-2:05

Electrostatic discharge ESD according to EN 61000-4-2:95+A1:98

Phenomenon 10 discharges to all the exposed points of the enclosure and instrument panel.

Place of testing Test Office Newave, Quartino and EMC Test center Swisscom Ostermundigen

Equipment Type NSG 431 by SCHAFFNER

LevelU = 15kV: discharge in air

U = 8kV: discharge with contact

Mode Normal operating condition

Suppression No additional suppressions are needed

ResultThe requested performance for Category C3 UPS of EN 62040-2:05 is re-spected.

Acceptance criterion A

Page 31: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA) dipl. ing. J. Jordi, EMV-Technik Solothurn Page 31 of 40

http://www.emvtechnik.ch

Newave SA DUT UPS DPA UPSCALE August 19th, 2009

CH-6572 Quartino TYPE 120kVA (6x20kVA) Series no.DPA 000052 / DPA 000053 / DPA 000062 / DPA 000048 / DPA 000079 / DPA000076

Testno.

Phenomenon Testpoint

NSG Amplitude Parameter Suppression Result

1. ESD DisplayMCS

Indicatorboard

right side

431±8kV contact

±15kV air

Normal operatingcondition

Original conditionU = ±15kV: sufficent operating condition

The test passes the criterion A

2.ESD DisplayMCS

Indicatorboard

left side431

±8kV contact

±15kV air

Normal operatingcondition Original condition

U = ±15kV: sufficent operating condition

The test passes the criterion A

3.ESD DisplayMCS

Indicatorboard

431±8kV contact

±15kV air

Normal operatingcondition

Original conditionU = ±15kV: sufficent operating condition

The test passes the criterion A

4.ESD DisplayATS

Indicatorboard

right side431

±8kV contact

±15kV air

Normal operatingcondition Original condition

U = ±15kV : sufficent operating condition

The test passes the criterion A

Page 32: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 32 of 40

http://www.emvtechnik.ch

3.2.3.Immunity to fast transients (Bursts)

AC+DC power ports

Signal+control ports

UPS DPA UPSCALE 120kVA (6x20kVA),

series no: DPA 000052 / DPA 000053 / DPA 0000 62/ DPA 000048 / DPA 000079 / DPA 000076

August 19th, 2009

StandardEN 62040-2:05 with requirements for Category C3 UPS of EN 62040-2:05

Fast transient Burst according to EN 61000-4-4:04

Equipment Type NSG 1025 by Schaffner

Level U = 4kV: to all the power (input / output) battery and control lines

Place of testing Test Office Newave, Quartino and EMC Test center Swisscom Ostermundigen

Mode Normal operating condition with 30% of nominal load

Result

The requested performance for Category C3 UPS of EN 62040-2:05 is re-spected.

Acceptance criterion A

Page 33: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and
Page 34: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA) dipl. ing. J. Jordi, EMV-Technik Solothurn Page 34 of 40

http://www.emvtechnik.ch

Newave SA DUT UPS DPA UPSCALE August 19th, 2009

CH-6572 Quartino TYPE 120kVA (6x20kVA)Seriesno.

DPA 000052 / DPA 000053 / DPA 0000 62/ DPA 000048 / DPA 000079 / DPA 000076

Testno.

Coupling Test point NSG Amplitude Parameter Suppression Result

1.CDN 300Couplingnetwork

AC-inputpower port3P+N PE

Bursts 4.0kVNormal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

2.CDN 300Couplingnetwork

AC-outputpower port3P+N PE

Bursts 4.0kVNormal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

3.CDN 300Couplingnetwork

Batterylines PE Bursts 4.0kV

Normal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

4.HF-currentclamp EM100

Flatband J5for parallelsignals

Bursts 4.0kVNormal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

5.HF-currentclamp EM100

SignallineJD1(RS232)

Bursts 4.0kVNormal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

6.HF-currentclamp EM100

SignallineUSB Bursts 4.0kV

Normal operatingcondition with 30%of nominal load

Original conditionU = 4.0kV: Sufficient operating

The test passes criterion A

Page 35: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 35 of 40

http://www.emvtechnik.ch

3.2.4.Test mit energiereichen Impulsen (Surge)

AC+DC power ports

Signal+control ports

UPS DPA UPSCALE 120kVA (6x20kVA),

series no: DPA 000052 / DPA 000053 / DPA0000 62 / DPA 000048 / DPA 000079 / DPA

000076

August 19th, 2009

StandardEN 62040-2:05 with requirements for Category C3 UPS of EN 62040-2:05

RF-common mode according to EN 61000-4-6:96+A1:01

Equipment Type NSG 651 by SCHAFFNER

Level Amplitude U = 4kV

Coupling In the mains 4 x 400Vac/200kVA

Place of testing Test Office Newave, Quartino and EMC Test center Swisscom Ostermundigen

Operating condition Normal operating condition with 30% of nominal load

Suppression No additional suppressions are needed

Resulte

The requested performance for Category C3 UPS of EN 62040-2:05 is re-spected.

Acceptance criterion A

Page 36: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA) dipl. ing. J. Jordi, EMV-Technik Solothurn Page 36 of 40

http://www.emvtechnik.ch

Newave SA DUT UPS DPA UPSCALE August 19th, 2009

CH-6572 Quartino TYPE 120kVA (6x20kVA) Series no.DPA 000052 / DPA 000053 / DPA 0000 62 / DPA000048 / DPA 000079 / DPA 000076

Test

Phenomenon

Test point NSG Amplitude Parameter Suppression Result

01CDN110couplingnetwork

Mains 4 x400Vac/200kVAinput

Surge2.0kV (L/L)

±4.0kV(L/PE)

Normaloperatingcondition

No additional suppressionsare needed

U = 4.0kV: Sufficient operating

The test passes criterion A

02CDN110couplingnetwork

Mains 4 x400Vac/200kVA

Surge2.0kV (L/L)

±4.0kV(L/PE)

Normaloperatingcondition

No additional suppressionsare needed

U = 2.0kV: Sufficient operating

The test passes criterion A

03CDN110couplingnetwork

Battery lines Surge2.0kV (asym)

±1.0kV (sym)

Normaloperatingcondition

No additional suppressionsare needed

U = 2.0kV: Sufficient operating

The test passes criterion A

03CDN110couplingnetwork

Signalline JD1 Surge2.0kV (asym)

±1.0kV (sym)

Normaloperatingcondition

No additional suppressionsare needed

U = 2.0kV: Sufficient operating

The test passes criterion A

Page 37: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 37 of 40

http://www.emvtechnik.ch

5. Equipment

5.1. Equipment of measuring spectra

EQUIPMENT MANUFACTURER FREQUENCY CALIBRATING TOLERANCE

Line impedance50ΏLISN

RHODE & SCHWARZTyp: ESH-2-Z5

Serie No. 338.5219-52

10kHz / 30MHz

4x400Vac / 34A17.3.07 R&S Munich 0.5db

Spectum analyzer

150kHz / 1000MHz

RHODE & SCHWARZTyp: ESPC-K1

Serie No. 843.820-013150kHz / 1GHz 17.3.07 R&S Munich 0.5db

Passive probe

1500Ώ

RHODE & SCHWARZTyp: ESH2-Z3

Serie No. 299.7810.52

150kHz / 30MHz 17.3.07 R&S Munich 0.5db

X-Wing BiLog An-tenne

26MHz / 2GHz

ADVANTEC

Typ: CBL6140A

Serie No. 843.832-016

30MHz / 2GHz 1db

Logarithmic an-tenna

300MHz / 1000MHz

RHODE & SCHWARZTyp: HL 223

Serie No. 843.990-010

200MHz / 1.3GHz 17.3.07 R&S Munich 1db

Loop antenna

150kHz / 30MHz

RHODE & SCHWARZTyp: HFH2-Z2

Serie No. 335.4711-5210kHz / 30MHz 17.3.07 R&S Munich +1db / -2db

Used equipment is marked by highlight.

Page 38: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 38 of 40

http://www.emvtechnik.ch

5.2. Equipment of testing immunity

SIGNAL EQUIPMENT CALIBRATION PULSE RISE TIME LEVEL

Fast single pulseSpikes

NSG 1025

No. 154-9025

23.8.07SCHAFFNER

100ns 5ns 200V / 5kV

Fast transientBursts

NSG 1025

No. 154-9025

23.8.07SCHAFFNER

80ns/Puls

15ms/Burst5ns 200V/5kV

Coupling network3P+N+E

CDN 300

No. 118-894523.8.07

SCHAFFNER4x420Vac/16A

HF-current clampEM 100

No. 8735254.5.06 LUETHI 150kHz/230MHz

Energie ImpulseSurges

NSG 651

No. 158-9307

23.8.07SCHAFFNER

1.2/50s 8/20s 0.2kV/6.6kV

Coupling networkSurges P+N+E.

CDN 110

No. 118-932023.8.07

SCHAFFNER

Coupling networkSignal lines.

CDN 116

No. 118-9507

23.8.07SCHAFFNER

Electrostatic di-scharge ESD

NSG 432

No. 00105

23.8.07SCHAFFNER

<1ns 0...25kV 5%

Page 39: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 39 of 40

http://www.emvtechnik.ch

6. Illustration

Fig. 6.1. Measuring of radiated EMI (emission)

Page 40: UPS DPA UPSCALE 120kVA (6x20kVA) · UPS DPA UPSCALE 120kVA (6x20kVA) ... UPS DPA UPSCALE 120kVA (6x20kVA), series no: DPA 000052 / DPA 000053 / DPA 0000 62 / DPA ... Quartino and

Newave SA Test report of August 19th, 2009

UPS DPA UPSCALE 120kVA(6x20kVA)

dipl. ing. J. Jordi, EMV-Technik Solothurn Page 40 of 40

http://www.emvtechnik.ch

Fig. 6.2. Test of the immunity of EMI-immission