UUCCMM--CCLLDD OOppeerraattiinngg aanndd ccoonnttrrooll pprriinncciipplleess ooff tthhee eelleeccttrroonniicc mmoodduulleeTTRRAANNEE AADDAAPPTTIIVVEE CCOONNTTRROOLL uusseedd oonn hheelliiccaall--rroottaarryy uunniittss eeqquuiippppeedd wwiitthhCCHHHHNN aanndd CCHHHHBB ccoommpprreessssoorrss..
UCM-CLDOperating and controlprinciples
InstallationOperationMaintenance
L80 IM 025 E
-
2These Installation, Operation, and Maintenanceinstructions are given as a guide to good practice in theinstallation, start-up, operation, and periodicmaintenance by the user of UCM-CLD modules.
They do not contain the full service proceduresnecessary for the continued successful operation of thisequipment. The services of a qualified servicetechnician should be employed, through the medium ofa maintenance contract with a reputable servicecompany.
FFoorreewwoorrdd
Warranty is based on the general terms and conditionsof the manufacturer. The warranty is void if theequipment is modified or repaired without the writtenapproval of the constructor, if the operating limits areexceeded, or if either the control system or theelectrical wiring is modified.
Damage due to misuse, lack of maintenance, or failureto comply with the manufacturer's instructions, is notcovered by the warranty obligation.
WWaarrrraannttyy
On arrival, inspect the unit before signing the deliverynote. Specify any damage on the delivery note, andsend a registered letter of protest to the last carrier ofthe goods within 72 hours of delivery. Notify the localsales office at the same time.The unit should be totally inspected within 7 days ofdelivery. If any concealed damage is discovered, send a
registered letter of protest to the carrier within 7 daysof delivery and notify the local sales office.Units are shipped with the refrigerant operating orholding charge, and should be examined with anelectronic leak detector to determine the hermeticintegrity of the unit. The refrigerant charge is notincluded in the standard Warranty Cover.
RReecceeppttiioonn
About this manualCautions appear at appropriate places in thisinstruction manual. Your personal safety and theproper operation of this machine require that youfollow them carefully.
The manufacturer assumes no liability for installationsor servicing performed by unqualified personnel.
GGeenneerraall iinnffoorrmmaattiioonn
American Standard Inc. 2000
-
3IInnddeexx
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Principles of operation of the UCM-CLD module
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Operators interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Default description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Unit operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Compressor operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Chiller report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Refrigerant report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Compressor report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Operators settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Service settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Service tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Description of the operation
Diagnostics
-
4Figure 1: Operators interface
General information
This regulation assembly is composed of 6 electronicmodules which have each their own 115V powersupply and communicate with each other via a seriallink. Each module has a set of functions which areassociated to make the unit regulation.Each module has the following name linked to itsfunctions.- MCSP (Motor Compressor Start and Protection):
safety, protection and control of the helical-rotarycompressor as well as all associated components.
- CPM (Chiller Protection and Management): safety,protection, and control of the chiller.
- EXV (Electronic Expansion Valve): control of bothelectrical expansion valves.
- CSR (Communication and Setpoint Reset): control ofthe serial communication, unit external setpoints, andice-making mode (optional module).
- Local CLD (Local Clear Language Display): operatorsinterface located in the unit: front panel (softwareversion and number displayed at power-up).
- Remote LCD (Remote Clear Language Display):operators interface located up to 1500 m from theunit at the operators, and which can communicatewith up to four units of the same type (optionalmodule).
- TCI IV, IPCB (Tracer Communication Interface 4,Inter-Processor Communication Buffer): protection ofthe unit internal communication bus from the externalinterferences existing in the unit (optional module,compulsory when using a remote CLD, and whichmust be factory-mounted).
CompressorReport
RefrigerantReport
ChillerReport
CustomReport
Select Report Group
DiagnosticsServiceTests
ServiceSettings
OperatorSettings
Alarm
AutoEnterPrevious
StopCancelNext
Select Setting Group
ADAPTIVE CONTROL
Principles of operation of the module UCM-CLD
-
5Figure 2: Control and regulation panel mounted on helical-rotary units equipped with UCM-CLD
Operators interface (Figure 1)
Digital displayThe display of control regulation and operatingparameters, as well as diagnostic and error messages,is made on a two-line 40-character liquid crystaldisplay.When powering-up the system, the display is not litand the message Self-test in progress is displayed inorder to make sure the display operates properly.The screen allows to display:- The error codes.- The settings of the various setpoints.- The specified temperature and pressure values.- The status of operating parameters and various
options.
KeyboardA 16-key touch pad allows the operator to move withinthe various menus and to modify their parameters andsetpoints.The keys are divided into two groups.
Menu keys- Chiller Report menu- Custom Report menu- Refrigerant menu- Compressor menu
- Operator settings menu- Service settings menu- Service test menu- Diagnostics menuThese 8 keys allow to access each of these menus.
Control keys- + key- - key- Previous key- Next key- Enter key- Cancel key- Auto key- Stop keyThese 8 keys allow the operator to move within thevarious menus and to modify their parameters.
Remark: All the menus and setpoints cannot beaccessed by the chillers operator; Service Settingsand Service Test menus are protected by a passwordand are reserved for Trane engineers.
-
6The whole information is gathered in various menusaccording to the location of the sensor and/or thefunction performed.
Chiller report menuThis menu gathers the information relating to the liquidchiller (reading only). Active setpoints and their origins,chilled water, air temperature, current draws, are foundin this menu.
Custom report menuThis menu is peculiar because originally it does notinclude any information at all. However, the operatorcan build his own menu which is comprised of read-only information, by simply pressing the + key when inother menus. To remove information from this menu,simply press the - key when displayed.
Refrigerant report menuThis menu gathers the information, read-only, relatingto the refrigerant. Refrigerant pressures andtemperatures at various points of the refrigerant circuitcan be found in this menu.
Compressor report menuThis menu gathers the information, read-only, relatingto the compressor. Voltages and amps, hour and startcounters, as well as oil temperature (GP compressoronly) can be found in this menu.
Operator settings menuThis menu comprises all the particular setpoints andoperating modes existing in the unit and which areaccessible by the usual operator of the chiller. Inaddition, the following can be programmed: chilledwater pump operation, temperature resets, ice-makingoperation, and low ambient limit.
Service settings menuThis menu has three access levels. The first onecontains information which can be adjusted by thecustomer such as the unit voltage, the validation ofover/under voltage protection, the display language,and the programmable relay function of the units. Thekeyboard can also be locked if the relating function isvalidated. A second level contains the setpointsadjusted by the service engineer to adapt the operationof the unit to a particular site, such as the address ofthe serial link, the water and refrigerant limitparameters, and so forth. The third level contains theconfiguration and protection information: number ofcircuits, compressors and fans, compressor amps andexpansion valve settings.
Service tests menuThis menu allows the operator to perform some testswhen the unit is in operation or during the initial start-up of the unit: expansion valve test, circuit locking, orpump-out.
Diagnostics menuThis menu contains all the information on the currentfaults or faults that occurred in the past. It allows thepossibility to reset a manual reset fault or to erase thehistoric list of faults.
Description of the operation
Previous keyPressing the Previous key allows the operator toscroll up to the previous information in the currentmenu. All the display items are looped, so it ispossible to scroll from the first item to the last one.
Next keyPressing the Next key allows the operator to scrolldown to the next information in the current menu. Allthe display items are looped, so it is possible to scrollfrom the last item to the first one.
+ keyIf this information displayed is a read-only item,pressing the + key will add it to the operators menu.if the information can be modified, the value isincreased by 1. Pressing the key for longer than 1second will increase the value of 1 every .25 seconds.A logical stop prevents an adjustment higher than themaximum value; a message is displayed to indicatethis status.
- keyIf the information displayed is a read-only item,pressing the - key will remove it from the operatorsmenu. If the information can be modified, the value isincreased by 1. Pressing the key for longer than 1second will increase the value of 1 every .25 seconds.A logical stop prevents an adjustment higher than themaximum value; a message is displayed to indicatethis status.
Enter keyPressing this key allows the validation of a value afterit has been modified by pressing the + or - key.
Cancel keyPressing this key allows the cancellation of a valueafter it has been modified by pressing the + or - keyand to come back to the original value.
Auto keyPressing this key (green) allows the unit to come backin auto mode if it was previously placed in stop modewith the stop key. The unit cannot be forced into automode if it has been stopped by an external contact orthe serial link. When the unit is stopped by the remoteinterface (Remote CLD), the local auto mode orderis prioritary.
Stop keyPressing this key (red) allows the unit to go into stopmode. In every case, and wherever the origin (excepta local stop), the stop order and stop status havepriority over a run order. The stop generated is a softstop, meaning the unit unloads before stopping.
-
Chiller report: status, water temperatures and setpointsPress (Next) (Previous) to continue
Next
Unit model(service setting menu)
all others RTXA
Mode: [OPERATING MODE]Request setpoint source: [SETPOINT SOURCE]
Chiller Mode: [OPERATING MODE]Request setpoint source: [SETPOINT SOURCE]
Heat Mode: [OPERATING MODE]Request setpoint source: [SETPOINT SOURCE]
Next
Compressors on A, B, C, D, NONECircuits locked out CIRCUIT 1, CIRCUIT 2, NONE
Next
[Operating mode]Making ice,ice-making complete All others
Active ice termination setpoint XXX CEvaporator entering water temperature XXX.X C
Active chilled water setpoint XXX CEvaporator leaving water temperature XXX.X C
Active hot water setpoint XXX CLeaving water temperature XXX.X C
Next
Evaporator entering water temperature XXX.X CEvaporator leaving water temperature XXX.X C
Next
Fan control(Service Setting Menu)
Disable Enable
Condenser entering water temperature XXX.X CCondenser leaving water temperature XXX.X C
Water heat recovery entering water temperature XXX.X CWater heat recovery leaving water temperature XXX.X C
Next
Active current limit setpoint XXX %Chiller % Rated load amps XXX %
Next
* Outdoor air temperature XXX.X C** Zone temperature XXX.X C
7
[operating mode] will be one ofResetStopped by Local DisplayStopped by Remote DisplayStopped by TracerStopped by External SourceAutoWaiting, Restart InhibitStartingRunningRunning, Current LimitRunning, Condenser LimitRunning, Evaporator LimitStoppingMaking iceice-making completeLow ambient temperature lockoutElectronic expansion valve testManufacturing testService pumpdown
* Dashes will be displayed if the sensor is openor shorted and neither outdoor air reset orlow ambient lockout is enabled.
** Dashes will be displayed if the zonetemperature sensor is open or shorted orzone reset is disabled.
Next
Next
Next
Chiller report
Chillerreport
-
Refrigerant temperature and pressure reportPress (Next) (Previous) to continue
Next
All others RTXA
Circuit 1 Circuit Mode: [Circuit mode]
Next
Circuit 1 evaporator refrigerant pressure XXX barCircuit 1 condenser refrigerant pressure XXX bar
Next
Circuit 1 compressor suction refrigerant temperature XXX.X CCircuit 1 saturated evaporator refrigerant temperature XXX.X C
Next
Circuit 1 saturated condenser refrigerant temperature XXX.X C
Next
All others RTXA
Circuit 2 Circuit Mode: [Circuit mode]
Next
Circuit 2 evaporator refrigerant pressure XXX barCircuit 2 condenser refrigerant pressure XXX bar
Next
Circuit 2 compressor suction refrigerant temperature XXX.X CCircuit 2 saturated evaporator refrigerant temperature XXX.X C
Next
Circuit 2 saturated condenser refrigerant temperature XXX.X C
Next
8
Refrigerant report
Refrigerantreport
The possible replacement to
CoolingHeatingDefrostingHeat to DefrostDefrost to HeatCool to HeatHeat to Cool
-
Compressor report: Mode, Hours, Starts, Rated load ampsPress (Next) (Previous) to continue
Next
Compressors on A, B, C, D, NONECircuits locked out Circuit 1, Circuit 2, NONE
Next
% line volts XXX %
Next
* Compressor A mode [MODE]
Next
Compressor A % Rated load amps, average XXX %Compressor A % Rated load amps, high phase XXX %
Next
Tonnage of unit130-400 Tons 70-125 Tons
Compressor A entering oil temperature XXX C
Next
Compressor A starts XXXXXCompressor A running hours XXXXX
Next
After review of last compressor Compressor B, C, D
9
* Display will change according to compressorreviewing
Compressor A modeCompressor B modeCompressor C modeCompressor D mode
[MODE]StoppedLocked outWaiting for restart inhibit timeStartingRunningRun-condenser limitRun-evaporator limitRun-current limitStoppingService pumpdown
Compressor report
Compressorreport
-
10
Chiller operation settings and setpointsPress (Next) (previous) to continue
Next
Setpoint source [SOURCE]Press (+) (-) to change setting
Next
All others RTXA
Front panel chilled water setpoint XXX CPress (+) (-) to change setting
Next
External chilled water setpoint [Disable/Enable]Press (+) (-) to change setting
Next
Design delta temperature setpoint XXX CPress (+) (-) to change setting
Front Panel Chilled Water Setpoint XXX CPress (+) (-) to change setting
Front Panel Hot Water Setpoint XXX CPress (+) (-) to change setting
External Chilled Water Setpoint [Disable/Enable]Press (+) (-) to change setting
External Hot Water Setpoint [Disable/Enable]Press (+) (-) to change setting
Cooling Design Delta Temperature Setpoint XXX CPress (+) (-) to change setting
Heating Design Delta Temperature Setpoint XXX CPress (+) (-) to change setting
Differential to start setpoint XXX CPress (+) (-) to change setting
Next
[SOURCE]LocalTracer
Operator settings
Operatorsettings
Default = 6.7CSelect = - 17.8 to 18.3C* If Limited by cutout setpoint, (+) to change isdisplayed, refer to the section on Leaving watertemperature cutout and Low refrigeranttemperature cutout.
Default = Disable
Default = 5.5 CSelect = -16 to +2CThis is difference between the entering andleaving chilled water temperature.
Default = 1.1CSelect = 16.6 to 1.1CThe temperature which is added the chilled watersetpoint, at which the chiller will start.
-
11
Default = ON. Manual override of chilled waterpump off delayAUTO = activates the Chilled water pump offdelay
Chilled water pump [ON, AUTO]Press (+) (-) to change setting
Next
Chilled water pump off delay [MINUTES]Press (+) (-) to change setting
Next
Front panel current limit setpoint XXX %Press (+) (-) to change setting
Next
External current limit setpoint [Disable/Enable]Press (+) (-) to change setting
Next
Low ambient lockout [Disable/Enable]Press (+) (-) to change setting
Next
Low ambient lockout(Operator settings menu)
Enable Disable
Low ambient lockout setpoint XXX CPress (+) (-) to change setting
Next
[MINUTES]Default = 10 minutesSelect = 1 minute to 30 minutesThe time period that the chilled water pump willrun, once the stop signal is given to the chiller.
Default = 120%Select = 40% to 120%
Default = Disable
Default = Disable
Default = -6.6CSelect: -28C to 16C
-
12
Default = DisableSelect = Return waterZoneOutdoor air
[TYPE]Return water
Default = 50%Range = 10% to 120%
ZoneDefault = 100%Range = 50% to 300%
OutdoorDefault = 10%Range = -80% to 80%
[TYPE]Return:
Default = 2,7CRange = 0 to 11C
ZoneDefault = 25CRange = 10 to 55C
OutdoorDefault = 32CRange = 10 to 55C
[TYPE]Return water
Default = 2,7CRange = 0 to 11C
ZoneDefault = -15CRange = 0 to 11C
OutdoorDefault = 2,7CRange = 0 to 11C
Default = Disable
Default = -3CSelect = -7 to -1C
Chilled water reset type [TYPE]Press (+) (-) to change setting
Next
Type of chilled water reset selected above
Return waterZoneOutdoor air Disable
[TYPE] type, reset ratio XXX %Press (+) (-) to change setting
Next
[TYPE] type, start reset setpoint XXX CPress (+) (-) to change setting
Next
[TYPE] type, max reset setpointPress (+) (-) to change setting
Next
Ice machine control [Disable/Enable]Press (+) (-) to change setting
Panel ice termination setpoint XXX FPress (+) (-) to change setting
Next
-
13
* If the keypad is locked and a diagnostic occurs,the alarm light will flash if applicable but thediagnostic screen will not be displayed until thekeypad is unlocked.
** Once the keypad is locked the PREVIOUS andENTER key need to be pressed simultaneouslyto unlock the keypad.
Default = DisableThe optional under/over voltage transformer isneeded for this feature.
Default = 460Selections = 200, 220, 230, 346, 380, 415, 460, 500,575.
Default = 120 secondsselect = 30 to 120 secondsThe time period between power-up or stop and theinitiation of the compressor start sequence, whenthere is a call for cooling.
Default = Disable
[UNITS]SIEnglish
[LANGUAGE]English / Franais / Espanol / Nippon / Italiano / Deutsch / Nederlands
Default = 1Select = 1 to 12
Default = Disable
Service settingsServicesettings
*
Service settings, enable and unitsPress (Next) (Previous) to continue
Next
Status of keypad/display lock feature(Service setting menu)
Enable Disable
Press (Enter) to lock display and keypadpassword will be required to unlock
Next Next
Depress either Enter or Next
Enter
***DISPLAY AND KEYPAD ARE LOCKED ****** ENTER PASSWORD TO UNLOCK ***
** Previous Enter
Display will return toChiller operating mode
under chiller report
Under/Over voltage protection [Disable/Enable]Press (+) (-) to change setting
Next
Unit line voltage [VOLT] VPress (+) (-) to change setting
Next
Restart inhibit time XXX SECPress (+) (-) to change setting
Next
Balanced compressor start and hours [Disable/Enable]Press (+) (-) to change setting
Next
Display units [UNITS]Press (+) (-) to change setting
Next
Language [LANGUAGE]Press (+) (-) to change setting
Next
** Programmable relay setup XXPress (+) (-) to change setting
Next
External circuit lockout [Disable/Enable]Press (+) (-) to change setting
Next
*** Password required for further accessPlease enter password
Next
-
14
Service tests: pumpdown, electronic expansion valve,compressor, lockout
Press (Next) (Previous) to continue
Next
Service pumpdown, compressor A [Disable/Enable]Press (+) (-) to change setting
Next
Is there a compressor B ?Yes No
Service pumpdown, compressor B [Disable/Enable]Press (+) (-) to change setting
Next
Is there a compressor C ?Yes No
Service pumpdown, compressor C [Disable/Enable]Press (+) (-) to change setting
Next
Is there a compressor D ?Yes No
Service pumpdown, compressor D [Disable/Enable]Press (+) (-) to change setting
Next
Electronic expansion valve test, circuit 1Press (+) (-) to change setting
Next
Electronic expansion valve test, circuit 2Press (+) (-) to change setting
Next
Compressor test, compressor A [Disable/Enable]Press (+) (-) to change setting
Next
Is there a compressor B ?Yes No
Compressor test, compressor B [Disable/Enable]Press (+) (-) to change setting
Next
Is there a compressor C ?Yes No
Compressor test, compressor C [Disable/Enable]Press (+) (-) to change setting
Next
Default = DisableMust be manually enabled by sevice personnelfrom the UCM. The unit must be in STOP/RESETand can be performed only once for every power-up of the UCM. Restart inhibit will be prepositionedand the compressor selected will start and run forone minute. Manual closing of the liquid line anglevalve will be required.
Default = Disable
Default = Disable
Default = Disable
Default = DisableElectronic expansion valve test will be initiatedwhen the unit is in STOP/RESET and Electronicexpansion valve test is set to enable. The mode willautomatically be reset to disable upon completionof the test.
Default = Disable
Default = DisableAllows service personnel to override the lead/lagfunction and start the compressor of concern. Afterthe compressor starts, the display willautomatically return to D.
Default = Disable
Default = Disable
Service testsService
tests
-
15
Is there a compressor D ?Yes No
Compressor test, compressor D [Disable/Enable]Press (+) (-) to change setting
Next
Circuit lockout, circuit 1 [UNLOCK/LOCKOUT]Press (+) (-) to change setting
Next
Circuit lockout, circuit 2 [UNLOCK/LOCKOUT]Press (+) (-) to change setting
Next
Default = Disable
Default = UNLOCKIf the setting is changed to LOCKOUT, the circuitwill become non-operational. The setting must bemanually changed to UNLOCK to regainoperation of the circuit.
Default = UNLOCK
-
16
If there are no diagnostic messages, the selected menuitem will be displayed continuously. If the diagnosticskey is pressed and there are no active diagnostics, thereadout on the display will be:
NO ACTIVE DIAGNOSTICS PRESENT
When a system malfunction occurs, one of thefollowing appropriate diagnostic messages will bedisplayed:
*** A machine shutdown has occurred ! ***
A machine shutdown occurred
but has cleared press (Next)
*** A circuit shutdown has occurred ! ***
A circuit shutdown occurred
but has cleared press (Next)
*** Informational warning ***
An informational warning occurred
but has cleared press (Next)
When a circuit shutdown - manual reset (CMR) or amachine shutdown - manual reset (MMR) occurs, thered LED to the right of the display will flash. Otherwisethis alarm LED is de-energized.
If more than one diagnostic is present, only the highestpriority active diagnostic will be explained in detail. Forexample, if the diagnostics occur in the following orderbefore the operator returns - IFW, MMR, CMR - thedisplay will read:
*** A machine shutdown has occurred ! ***
because the MMR has the highest priority. However, asthe operator moves through the diagnostic menu to theLast diagnostic, the [Diagnostic description] willshow the CMR diagnostic as well as the IFW. If theNext key is pressed, the display will show all theother active and historic diagnostics.
The active diagnostic priorities, listed from highest tolowest are:
Machine shutdown - manual reset (MMR)Machine shutdown - automatic reset (MAR)
Circuit shutdown - manual reset (CMR)Circuit shutdown - automatic reset (CAR)
Informational warning (IFW)
The following flowchart shows the display readoutsfound under the diagnostics menu. By following thesteps shown in the flowchart, a brief description of thediagnostic can be viewed. Use the Next key to enter themain diagnostic menu, where the diagnostic can becleared.
Diagnostics
-
17
NoDiagnostic present
YesOther
Type of diagnostic
MMR/MAR Active
*** A machine shutdown has occurred ! ***Press (Next) for diagnostic info
Next
MARType of machine shutdown
MMR
[Diagnostic description]Latched fault - manual reset required
Next
All others RTXA
Mode at fault: [OPERATING MODE]Compressors running at fault: [A, B, C, D]
[Unit operating mode] [Operating mode]Compressors running at fault: [A, B, C, D]
Next
Press (Enter) to reset controland clear all active diagnostics
Enter
NextPress Enter or Next
Enter
Machine will unload if loadedand display will automatically
return to MODE in the chiller report
[DIAGNOSTIC DESCRIPTION]Active fault - May clear automatically
Next
All others RTXA
Mode at fault: [Operating mode]Compressors running at fault: [A, B, C, D]
[Unit operating mode] [Operating mode]Compressors running at fault: [A, B, C, D]
OtherType of diagnostic
MAR inactive
*** A circuit shutdown has occurred ! ***Press (Next) for diagnostic information
Next
DiagnosticsDiagnostics
[Unit operating mode]
Cooling ModeHeating ModeDefrost Mode
Note:MMR: Machine shutdown manual reset.MAR: Machine shutdown automatic reset.CMR: Circuit shutdown manual reset.CAR: Circuit shutdown automatic reset.IFW: Informational warning.
-
18
OtherType of diagnostic
CMR/ CAR active
Latched fault - manual reset requiredPress (Next) for more
Next
CARType of circuit shutdown
CMR
Latched fault - manual reset requiredPress (Next) for more
Next
Circuit 2Did diagnostic occuron Circuit 1 or Circuit 2?
Circuit 1
Press (Enter) toreset circuit 1 diagnostics
Next Enter
Reset Circuit 1 diagnostic
Press (Enter) toreset circuit 2 diagnostics
Next Enter
Reset Circuit 2 diagnostic
Active fault - can clear automaticallyPress (Next) for more
NextOther
Type of diagnostic
CAR inactive
A circuit shutdown occurredbut has cleared Press (Next)
NextIFW inactive
Type of diagnostic
IFW active
*** Informational warning ***Press (Next) for diagnostic info
Next
Note:MMR: Machine shutdown manual reset.MAR: Machine shutdown automatic reset.CMR: Circuit shutdown manual reset.CAR: Circuit shutdown automatic reset.IFW: Informational warning.
-
19
An informational warning occurredbut has cleared Press (Next)
Next
No active diagnostics presentPress (Next) (Previous) to continue
Next
NoAre there diagnosticsin history ?
Yes
Diagnostic status report followsPress (Next) (Previous) to continue
Next
Last diagnostic:[DIAGNOSTIC DESCRIPTION]
NextNext
[DIAGNOSTIC DESCRIPTION][DIAGNOSTIC TYPE]
No historic diagnostics presentPress (Next) (Previous) to continue
Next
Press (Enter) toclear diagnostic history
Next
Press (Enter) toreset circuit 1 diagnostics
Next
Press (Enter) toreset circuit 2 diagnostics
Next
Press (Enter) to reset controland clear all active diagnostics
Next
Next
Press Enter or Next
Enter
Machine will unload if loaded anddisplay will automatically return to
MODE in the chiller report.
-
20
Defaults descriptionFault 87Check External Chilled Water Setpoint: IFW - Value out of range
Fault 89Check External Current Limit Setpoint: IFW - Value out of range
Fault 8AChilled Water Flow (Entering Water Temperature): MMR 1) Entering water temperature
< leaving water temperature2) No water flow3) Defective Evaporator sensor
Fault 8EEvaporator Entering Water Temperature Sensor: MMR - Defective sensor
Fault 8FCondenser Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 90Condenser Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 93Evaporator Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 94Evaporator Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 9ACondenser Entering Water Temperature Sensor: IFW - Defective sensor
Fault 9bCondenser Leaving Water Temperature Sensor: IFW - Defective sensor
Fault A0Zone Temperature Sensor: IFW - Defective sensor
Fault A1Outdoor Air Temperature Sensor: IFW - Defective sensor
Fault AbEvaporator Leaving Water Temperature Sensor: MMR - Defective sensor
Fault b5Low Pressure Cutout - Circuit 1: CMR - Low pressure switch open
Fault b6Low Pressure Cutout - Circuit 2: CMR - Low pressure switch open
Fault bAOverload trip - Compressor A: CMR - Current exceeded
Fault bbOverload Trip - Compressor B: CMR - Current exceeded
Fault bCOverload trip - Compressor C: CMR - Current exceeded
Fault bdOverload trip - Compressor D: CMR - Current exceeded
Fault bEHigh Pressure Cutout - Compressor C: CMR - High pressure too high
Fault bFHigh Pressure Cutout - Compressor D: CMR - High pressure too high
-
21
Fault C5Low Chilled Water Temperature (Unit Off): IFW - Antifreeze protection
Fault C6Low Chilled Water Temperature (Unit On): MAR - Antifreeze protection
Fault CAContactor - Compressor A: MMR - Welded compressor contactor
Fault CbContactor - Compressor B: MMR - Welded compressor contactor
Fault CCContactor - Compressor C: MMR - Welded compressor contactor
Fault CdContactor - Compressor D: MMR - Welded compressor contactor
Fault d7Over Voltage: MAR - Voltage 10% > nominal
Fault d8Under Voltage: MAR - Voltage 10% < nominal
Fault EdChilled Water Flow Interlock: MAR - Flow switch open more than 6 seconds
Fault F5High Pressure Cutout - Compressor A: MMR - High pressure too high
Fault F6High Pressure Cutout - Compressor B: MMR - High pressure too high
Fault FdEmergency Stop Input: MMR - Emergency stop input open
Fault 180Starter Transition - Compressor A: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 181Starter Transition - Compressor B: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 182Starter Transition - Compressor C: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 183Starter Transition - Compressor D: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 184Phase Reversal - Compressor A: CMR - Phase reversed
Fault 185: Phase reversal - Compressor B CMR - Phase reversed
Fault 186Phase reversal - Compressor C: CMR - Phase reversed
Fault 187Phase reversal - Compressor D: CMR - Phase reversed
Fault 190Low Superheat - Circuit 1: CMR - Superheat < 1C during more than
1333C x seconds
-
22
Fault 191Low Superheat - Circuit 2: CMR - Superheat < 1C during more than 1333C x seconds
Fault 194Low Evaporator Refrigerant Temperature. - Circuit 1: CMR - Refrigerant temperature < setpoint during more than
30C x seconds
Fault 195Low Evaporator Refrigerant Temperature. - Circuit 2: CMR - Refrigerant temperature < setpoint during more than
30C x seconds
Fault 198Low Oil Flow - Compressor A: CMR - Oil flow switch open during more than 20 seconds
Fault 199Low Oil Flow - Compressor B: CMR - Oil flow switch open during more than 20 seconds
Fault 19Alow Oil Flow - Compressor C: CMR - Oil flow switch open during more than 20 seconds
Fault 19bLow Oil Flow - Compressor D: CMR - Oil flow switch open during more than 20 seconds
Fault 19CPhase Loss - Compressor A: CMR - Loss of 1 or more phases
Fault 19dPhase Loss - Compressor B: CMR - Loss of 1 or more phases
Fault 19EPhase Loss - Compressor C: CMR - Loss of 1 or more phases
Fault 19FPhase Loss - Compressor D: CMR - Loss of 1 or more phases
Fault 1A0Power Loss - Compressor A: CAR - Loss of all three phases in operation
Fault 1A1Power Loss - Compressor B: CAR - Loss of all three phases in operation
Fault 1A2Power Loss - Compressor C: CAR - Loss of all three phases in operation
Fault 1A3Power Loss - Compressor D: CAR - Loss of all three phases in operation
Fault 1A4Tracer Communication Loss: IFW - Loss of external information
Fault 1A5Oil Flow Control - Compressor A: CMR - Problem on oil circuit
Fault 1A6Oil Flow Control - Compressor B: CMR - Problem on oil circuit
Fault 1A7Oil Flow Control - Compressor C: CMR - Problem on oil circuit
Fault 1A8Oil Flow Control - Compressor D: CMR - Problem on oil circuit
Fault 1A9Electronic expansion valve Electric Drive Circuit - Refrigerant Circuit 1: CMR 1) Electronic expansion valve wiring
2) Defective UCM3) Defective Electronic expansion valve4) Defective Electronic expansion valve relay
-
23
Fault 1AAElectronic expansion valve Electric Drive Circuit - Refrigerant Circuit 2: CMR 1) Electronic expansion valve wiring
2) Defective UCM3) Defective Electronic expansion valve4) Defective Electronic expansion valve relay
Fault 1AdMemory Error Type I: IFW - Non Volatile Random Access Memory [NOVRAM}
problem, unit is placed on default setting operatingFault 1AELow Differential Pressure - Circuit 1: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1AFLow Differential Pressure - Circuit 2: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1b2Severe Phase Unbalance - Compressor A: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b3Severe Phase Unbalance - Compressor B: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b4Severe Phase Unbalance - Compressor C: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b5Severe Phase Unbalance - Compressor D: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b6Compressor Overload Setting - Compressor A: IFW - Check setting of compressor overload
Fault 1b7Compressor Overload Setting - Compressor B: IFW - Check setting of compressor overload
Fault 1b8Compressor Overload Setting - Compressor C: IFW - Check setting of compressor overload
Fault 1b9Compressor Overload Setting - Compressor D: IFW - Check setting of compressor overload
Fault 1bAPhase Unbalance - Compressor A: CMR - Phase imbalance >15%
Fault 1bbPhase Unbalance - Compressor B: CMR - Phase imbalance >15%
Fault 1bCPhase Unbalance - Compressor C: CMR - Phase imbalance >15%
Fault 1bdPhase Unbalance - Compressor D: CMR - Phase imbalance >15%
Fault 1bEWinding Temperature - Compressor A: CMR - Winding temperature > 105C
Fault 1bFWinding Temperature - Compressor B: CMR - Winding temperature > 105C
Fault 1C0Winding Temperature - Compressor C: CMR - Winding temperature > 105C
Fault 1C1Winding Temperature - Compressor D: CMR - Winding temperature > 105C
-
24
Fault 1C6High Differential Pressure - Circuit 1: CMR - LB/High pressure differential > 24,5 bar
Fault 1C7High Differential Pressure - Circuit 2: CMR - LB/High pressure differential > 24,5 bar
Fault 1d1Memory Error Type II: IFW - RAM error
Fault 1d2Memory Error Type III: IFW - RAM error
Fault 1d3Compressor Suction Temperature Sensor - Circuit 1: CMR - Defective sensor
Fault 1d4Compressor Suction Temperature Sensor - Circuit 2: CMR - Defective sensor
Fault 1d7Phase Reversal Protection Lost - Compressor A: CMR - Phase reversal protection not operative
Fault 1d8Phase Reversal Protection Lost - Compressor B: CMR - Phase reversal protection not operative
Fault 1d9Phase Reversal Protection Lost - Compressor C: CMR - Phase reversal protection not operative
Fault 1dAPhase Reversal Protection Lost - Compressor D: CMR - Phase reversal protection not operative
Fault 1dbSlaved Electronic expansion valve Electronic Drive Circuit - Refrigerant Circuit 1: CMR - Electronic expansion valve electric drive defective
Fault 1dCSlaved Electronic expansion valve Electronic Drive Circuit - Refrigerant Circuit 2: CMR - Electronic expansion valve electric drive defective
Fault 1ddHigh Oil Temperature - Compressor A: CMR - Oil temperature > 77C
Fault 1dEHigh Oil Temperature - Compressor B: CMR - Oil temperature > 77C
Fault 1dFHigh Oil Temperature - Compressor C: CMR - Oil temperature > 77C
Fault 1E0High Oil Temperature - Compressor D: CMR - Oil temperature > 77C
Fault 1E1Oil System Fault - Compressor A: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E2Oil System Fault - Compressor B: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E3Oil System Fault - Compressor C: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E4Oil System Fault - Compressor D: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E5Entering Oil Temperature Sensor - Compressor A: CMR - Defective sensor
-
25
Fault 1E6Entering Oil Temperature Sensor - Compressor B: CMR - Defective sensor
Fault 1E7Entering Oil Temperature Sensor - Compressor C: CMR - Defective sensor
Fault 1E8Entering Oil Temperature Sensor - Compressor D: CMR - Defective sensor
Fault 2A1Condenser Fan Variable Speed Drive Fault - Circuit 1: IFW - Defective fan speed controller after 5 attempts
Fault 2A2Condenser Fan Variable Speed Drive Fault - Circuit 2: IFW - Defective fan speed controller after 5 attempts
Note:MMR: Machine shutdown manual reset.MAR: Machine shutdown automatic reset.CMR: Circuit shutdown manual reset.CAR: Circuit shutdown automatic reset.IFW: Informational warning.
Communication failures
Fault 410Loss of Local Display Panel Communication
Fault 412Chiller Module to Option Module Communication Failure
Fault 413Chiller Module to Electronic expansion valve Module Communication Failure
Fault 414Chiller Module to Compressor A Module Communication Failure
Fault 415Chiller Module to Compressor B Module Communication Failure
Fault 416Chiller Module Compressor C Module Communication Failure
Fault 417Chiller Module to Compressor D Module Communication Failure
Fault 418Chiller Module to Slaved Electronic expansion valve Module Communication Failure
Fault 431Electronic expansion valve Module to Chiller Module Communication Failure
Fault 434Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 435Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 436Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 437Electronic expansion valve Module to Compressor D Module Communication Failure
Fault 441Compressor A Module to Chiller Module Communication Failure
Fault 443Compressor A Module to Electronic expansion valve Module Communication Failure
-
26
Fault 445Compressor A Module to Compressor B Module Communication Failure
Fault 451Compressor B Module to chiller Module Communication Failure
Fault 453Compressor B Module to Electronic expansion valve Module Communication Failure
Fault 454Compressor B Module to Compressor A Module Communication Failure
Fault 461Compressor C Module to Chiller Module Communication Failure
Fault 463Compressor C Module to Electronic expansion valve Module Communication Failure
Fault 467Compressor C Module to Compressor D Module Communication Failure
Fault 471Compressor D Module to Chiller Module Communication Failure
Fault 473Compressor D Module to Electronic expansion valve Module Communication Failure
Fault 476Compressor D Module to Compressor C Module Communication Failure
Fault 481Slaved Electronic expansion valve Module to Chiller Module Communication Failure
Fault 483Slaved Electronic expansion valve Module to Electronic expansion valve Module Communication Failure
Fault 484Slaved Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 485Slaved Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 486Slaved Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 487Slaved Electronic expansion valve Module to Compressor D Module Communication Failure
Unit operating mode
Mode A00Stopped
Mode A01, A02Auto
Mode A17Service Pump down
Mode A70Waiting, Restart Inhibit
Mode A72Starting
Mode A74Running
-
27
Mode A75Running, Current Limit
Mode A76Running, Condenser Limit
Mode A77Running, Evaporator Limit
Mode A7EStopping
Mode A88Reset
Mode A100Stopped by Source
Mode A101Ice Making Complete
Mode A118Electronic expansion valve Test
Mode A174Making Ice
Mode A175Making Ice, Condenser Limit
Mode A177Making Ice, Evaporator Limit
Mode A200Low Ambient Temperature Lockout
Mode A234Manufacturing TestStopped By TracerStopped By Remote Display
Compressor operating mode
Mode 00Stopped
Mode 16Locked Out
Mode 17Service Pumpdown
Mode 70Restart Inhibited
Mode 72Starting
Mode 74Running
Mode 75Run - Current Limit
Mode 76Run - Condenser Limit
Mode 77Run - Evaporator Limit
Mode 7EStopping
-
MMaaiinntteennaannccee ccoonnttrraacctt
It is strongly recommended that you sign amaintenance contract with your local Service Agency.This contract provides regular maintenance of yourintallation by a specialist in our equipment. Regularmaintenance helps ensure that any malfunction isdetected and corrected quickly and minimizes the
possibility that serious damage will occur. Finally,regular maintenance helps ensure the maximumoperating life of your equipment. Failure to followthese installation and maintenance instructions mayaffect your warranty.
TTrraaiinniinngg
The equipment described in this manual is the result ofmany years of research and continuous development.To assist you in obtaining the best use of it, andmaintaining it in perfect operating condition over along period of time, the manufacturer has available arefrigeration and air conditioning service school. Theprincipal aim of this is to give operators and
maintenance technicians a better knowledge of theequipment they are using, or that is under their charge.Emphasis is particularly given to the importance ofperiodic checks on the unit operating parameters aswell as on preventive maintenance, which can reducethe cost of owning the unit by helping avoid seriousand costly breakdown.
Literature Order Number L80 IM 025 E
Date July 2000
Supersedes L80 IM 025 E - 1297
Stocking Location La Crosse
Since The Trane Company has a policy of continuous product improvement, it reserves the right tochange design and specifications without notice.
Socit Trane Socit Anonyme au capital de 41500 000 F Siege Social: 1 rue des Amriques 88190Golbey France Siret 306 050 188-00011 RSC Epinal B 306 050 188Numro didentification taxe intracommunanutaire: FR 83 3060501888
The Trane CompanyAn American Standard Companywww.trane.com
For more information contactYour local sales office ore-mail us at [email protected]
This publication is a general guide to install, use and properly maintain our products. The informationgiven may be different from the specification for a particular country or for a specific order. In thisevent, please refer to your nearest office.
All rights reserved. No part of this publication may be reproduced or transmitted in any form or byany means without the written authorization of the manufacturer.