Electrical Notes & Articles Sharing Abstracts,Notes on various Electrical Engineering Topics. Typical Limiting Values of SubStation Equipments. MARCH 31, 2011 12 COMMENTS (HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/03/31/TYPICAL‑LIMITING‑ VALUES‑OF‑SUBSTATION‑EQUIPMENTS/#COMMENTS) Typical Limiting Values of Sub Station Electrical Equipments. 1. Transformer / Reactor: Sr. No. Equipment / test data Permissible limits Reference A) Transformer oil a) BDV ‑At the time of first charging 600 kV (Gap – 2.5 mm) – Minimum IS – 1866 ‑During O&M 50 kV (Gap – 2.5 mm) – Minimum IS – 1867 b) Moisture content IS – 1868 ‑At the time of first charging 15 PPM (Max.) IS – 1869 ‑During O&M 25 PPM (Max.) IS – 1870 c) Resistivity at 90 degree C 0.1‑1012 Ohm‑CM (Min.) IS – 1871 d) Acidity 0.2 mg KOH/gm (Max.) IS – 1872 e) IFT at 27 degree C 0.018 N/M (Min.) IS – 1873 f) Tan delta at 90 degree C 0.20 (Max.) IS – 1874 g) Flash point 126 Deg. C (Min.) IS – 1875 B) Vibration level for reactors 200 Microns (Peak to Peak) IS – 1876 60 Microns (Average) IS – 1877 C) Tan delta for bushing at 20 Deg. C 0.007* IEC – 137 D) Capacitance for bushing + 5% variation IEC – 138 E) IR value for winding 1000 M‑Ohm By 5.0/10.0 kV Megger IEC – 139 F) Tan delta for windings at 20 Deg. C 0.007* IEEE/C57.12.90.1980 G) Contact resistance of bushing terminal connectors 10 M. Ohm / Connector NGC.UK Recommendations H) Turret Neutral CT ratio errors 39 IS – 2705 2. Circuit Breakers

Upload: anil-marturi

Post on 06-Sep-2015

23 views

Category:

Documents


1 download

DESCRIPTION

gjklgl

TRANSCRIPT

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 1/7

    ElectricalNotes&Articles

    SharingAbstracts,NotesonvariousElectricalEngineeringTopics.

    TypicalLimitingValuesofSubStationEquipments.

    MARCH31,2011 12COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/03/31/TYPICALLIMITINGVALUESOFSUBSTATIONEQUIPMENTS/#COMMENTS)

    TypicalLimitingValuesofSubStationElectricalEquipments.

    1.Transformer/Reactor:

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A)

    Transformeroil

    a)BDV

    Atthetimeoffirstcharging 600kV(Gap2.5mm)Minimum IS1866

    DuringO&M 50kV(Gap2.5mm)Minimum IS1867

    b)Moisturecontent IS1868

    Atthetimeoffirstcharging 15PPM(Max.) IS1869

    DuringO&M 25PPM(Max.) IS1870

    c)Resistivityat90degreeC 0.11012OhmCM(Min.) IS1871

    d)Acidity 0.2mgKOH/gm(Max.) IS1872

    e)IFTat27degreeC 0.018N/M(Min.) IS1873

    f)Tandeltaat90degreeC 0.20(Max.) IS1874

    g)Flashpoint 126Deg.C(Min.) IS1875

    B)Vibrationlevelforreactors 200Microns(PeaktoPeak) IS1876

    60Microns(Average) IS1877

    C) Tandeltaforbushingat20Deg.C0.007* IEC137

    D) Capacitanceforbushing +5%variation IEC138

    E) IRvalueforwinding 1000MOhmBy5.0/10.0kVMeggerIEC139

    F) Tandeltaforwindingsat20Deg.C0.007* IEEE/C57.12.90.1980

    G) Contactresistanceofbushingterminalconnectors10M.Ohm/Connector NGC.UK

    Recommendations

    H) TurretNeutralCTratioerrors 39 IS2705

    2.CircuitBreakers

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 2/7

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) DewpointofSF6gas DewpointvaluesasperAnnexureII

    B) Dewpointofoperatingair 45Deg.CatATM.Pressure

    C)

    CBOperatingtimings 400kV220KV

    a)Closingtime(Max.) 150MS200MS

    b)Triptime(Max.) 25MS35MS

    c)Close/triptime,Polediscrepancy

    PhasetoPhase(Max.) 3.33MS3.33MS

    Breaktobreak(Max.)ofsamephase 2.5MS2.5MS

    D)

    PIRtime

    BHELmake 1216MSManufacturersRecommendations

    ABBmake 812MSManufacturersRecommendations

    NGEFmake 812MSManufacturersRecommendations

    M&Gmake 812MSManufacturersRecommendations

    TELKmake 812MSManufacturersRecommendations

    ABBmake(HVDC) 812MSManufacturersRecommendations

    E)PIRopeningtimepriortoopeningofmaincontacts(ABB,CGL,NGEFmakeCBs) 5MS(Min.)atratedpressure

    ManufacturersRecommendations

    F)Pirandmaincontactsoverlaptime[BHEL,M&G,ABB(imported)makeCBs] 6MS(Min.)atratedpressure

    ManufacturersRecommendations

    G) Tandeltaofgradingcapacitors 0.007at20Deg.C

    H) CapacitanceofgradingcapacitorsWithin+10%/5%oftheratedvalue IEC359

    I) ContactresistanceofCB 150M.Ohm

    J) ContactresistanceofCBterminalconnector 10M.OhmperconnectorNGC,UKrecommendations

    K)

    IRvalue:

    1.Phaseearth 1000MOhm(Min.)by5.0/10.0kVMegger

    2.Acrossopencontacts 1000MOhm(Min.)by5.0/10.0kVMegger

    3.Controlcables 50MOhm(Min.)by0.5kVMegger

    L)

    Pressureswitchsettings

    SF6gaspressureswitches Within+0.1Barofsetvalue

    Operatingairpr.Switches Within+0.1Barofsetvalue

    Operatingoilpr.Switches Within+0.1Barofsetvalue

    M)

    BDVofoilusedforMOCB

    Atthetimeoffilling 40kVat2.5mmGap(Min.) Mfgs.Recommendation

    DuringO&M 20kVat2.5mmGap.(Min.) Mfgs.Recommendation

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 3/7

    3.CurrentTransformer

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A)

    IRvalue

    1.Primaryearth 1000MOhm(Min.)by5.0/10.0kVMegger

    2.Secondaryearth 50MOhm(Min.)by0.5kVMegger

    3.Controlcables 50MOhm(Min.)by0.5kVMegger

    B) Tandeltavalue 0.007*at20Deg.C

    C) TerminalConnector 10MOhmperconnectorNGC,UKRecommendations

    D) CTratioerrors +3%Protectioncores IS2705

    D) CTratioerrors +1%Meteringcores IS2706

    4.CapacitiveVoltage

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) TanDelta 0.007*at20Deg.C

    B) Capacitance Within+10%/5%oftheratedvalue IEC358

    C Contactresistanceofterminalconnector 10MOhmperconnectorNGC,UKRecommendations

    D)

    IRValue IRValue

    1.Primaryearth 1000MOhm(Min.)by5.0/10.0kVMegger

    2.Secondaryearth 50MOhm(Min.)by0.5kVMegger

    3.Controlcables 50MOhm(Min.)by0.5kVMegger

    E)

    EMUtankoilparameters EMUtankoilparameters

    a)BDV(Min.) 30kV(Gap.2.5mm) IS1866

    b)Moisturecontent(Max.) 35ppm do

    c)Resistivityat90Deg.C 0.11012Ohm.CM do

    d)Acidity 0.5mgkOH/gm(Max.) do

    e)IFTat27Deg.C 0.018N/M(Min.) do

    f)Tandeltaat90Deg.C 1.0Max. do

    g)Flashpoint 125Deg.C(Min.) do

    F) CVTvoltageratioerrors +5%protectioncores IEEE/C93.1.1990

    F) CVTvoltageratioerrors +0.5%meteringcores IEC186

    5.Isolators

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) Contactresistance 300MOhm.(Max.)

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 4/7

    B) Contactresistanceofterminalconnector 10MOhmperconnector

    NGC,UKRecommendations

    C)

    IRvalue

    1.Phaseearth 1000MOhm(Min.)by5.0/10.0kVMeggerNGC,UKRecommendations

    2.Acrossopencontacts 1000MOhm(Min.)by5.0/10.0kVMeggerNGC,UKRecommendations

    3.Controlcables 50MOhm(Min.)by0.5kVMegger

    6.SurgeArrester

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) Leakagecurrent 500MAmp.(Resistive) Hitachi,JapanRecom.

    B) IRvalue 1000MOhm.(Min.) Hitachi,JapanRecom.

    7.Miscellaneous

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) Stationearthresistance 1.0Ohm(Max.)

    B)

    Thermovisionscanning

    Temp.upto15Deg.C(aboveambient) Normal

    Temp.above1550Deg.C(aboveambient) Alert

    Temp.above50Deg.C(aboveambient) Tobeimmediatelyattended

    C) TerminalconnectorsContactresistance 10MOhmperconnectorHGC,UKRecommendations

    D)

    IRvalues

    1.Allelectricalmotors 50MOhm(Min.)by0.5kVMegger

    2.Controlcables 50MOhm(Min)by0.5kVMegger

    3.Lt.Transformers 100M.Ohm(Min.)byMegger

    4.Lt.Switchgears 100MOhm(Min.)by0.5kVMegger

    8.Batteries

    Sr.No. Equipment/testdata Permissiblelimits Reference

    A) Terminalconnectorresistance 10MOhm+20% ANSI/IEEE4501989

    B) Specificgravity 1200+5GM/Lat27Deg.C

    TemperatureCorrectionFactorforTanDeltaMeasurement

    Sr.No. OiltemperatureDeg.C Correctionfactor(K)

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 5/7

    1 10 0.8

    2 15 0.9

    3 20 1.0

    4 25 1.12

    5 30 1.25

    6 35 1.40

    7 40 1.55

    8 45 1.75

    9 50 1.95

    10 55 2.18

    11 60 2.42

    12 65 2.70

    13 70 3.00IfTanDeltaofbushing/winding/CVT/CTismeasuredatoiltemperatureTDeg.C.ThenTanDeltaat20Deg.Cshallbeasgivenbelow:

    TanDeltaat20Deg.C=TanDeltaatTempTDeg.C/FactorK.

    DewPointLimitsforSF6GasinEHVCircuitBreakers

    Sr.No MakeofC.B DewpointatratedPr.Deg.C

    CorrespondingdewpointatAtmospheric.Pr. Remarks

    1 BHEL15 36

    Atthetimeofcommissioning

    7 29 DuringO&M

    5 27 Critical

    2 M&G 39

    Atthetimeofcommissioning

    32 DuringO&M

    3 CGL15 35

    Atthetimeofcommissioning

    10 31 DuringO&M

    4 ABB15 35

    Atthetimeofcommissioning

    5 26 DuringO&M

    5 NGEF15 36

    Atthetimeofcommissioning

    7 29 DuringO&MNote:DewpointofSF6gasvarieswithpressureatwhichmeasurementiscarriedout.Soitistobeensuredthatifmeasurementisdoneatpressureotherthanatmosphericpressure,itneedstobeconvertedtotheatmosphericpressure.

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 6/7

    FILEDUNDERUNCATEGORIZED

    AboutJignesh.ParmarJigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13yearsexperienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectricalProjects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputyManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectricalEngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.HeisTechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeandhelptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

    12ResponsestoTypicalLimitingValuesofSubStationEquipments.

    S.Krishnamurthysays:July25,2011at6:44amVeryusefulinformationforallsubstationoperating&maintenancepersonnel.Allequipmentsdataisindicatedinoneplace.Bestwishes.

    S.K.MURTHY

    ReplyVVNRaosays:December17,2011at5:13amHappytoseetheusefulinformation.Ifpossiblepleaseaddrangeandcriticalityoftandeltavaluesandalsotheinternationalstandaredsofclearancesinasubstationaswellasinlines.

    Replyvighneshsays:January3,2012at11:20amiamunabletolocateIEC139pertainingtoIRvaluesofwindings.WhatshallbercommendedvaluesofIR?

    ReplySsatishShindesays:May25,2012at5:50amThanxforprovidinginstantimportantinformation.

    Replymasoomkhansays:July4,2012at10:09amcananyoneprovide380EHVSurgearresterpowerfactor10KVTESTpermissibilelimits

    ReplyTikaramwaghadesays:July19,2012at1:04pmThisparametersisexcellencetoimpruvecomfidenceinequptesting

    ReplyDineshSinghsays:July31,2012at11:04amThanksforprovidingimportantlimitinginformation.

    Replyvinodrathodsays:June10,2013at2:42pmthanksbosscontinuewithstudy

    About these ads (https://wordpress.com/about-these-ads/)

  • 7/13/2015 TypicalLimitingValuesofSubStationEquipments.|ElectricalNotes&Articles

    https://electricalnotes.wordpress.com/2011/03/31/typicallimitingvaluesofsubstationequipments/ 7/7

    ReplykirankumarGudlasays:July17,2013at7:25amAtthetimeoffirstcharging

    600kV(Gap2.5mm)Minimum

    Correctedis

    60kV(Gap2.5mm)Minimum

    Replysiptrunkingprovidersays:July29,2013at7:12pmHi,ithinkthatisawyouvisitedmysitethusicametoreturnthefavor.

    Imattemptingtofindthingstoenhancemywebsite!Isupposeitsoktousesomeofyourideas!!

    ReplyAnilPrajapatisays:October8,2013at4:49pmItswonderfulandyouhaveexplainedeverythinginverysimplebutinpowerfulandeffectivewayEr.AnilPrajapati,Jodhpur

    ReplyAAAXXXsays:February4,2015at1:50amWhenIwillgofortestingof100MVAtransformerturretcttesting,whattestsIhavetotake?andminimumandmaximumvaluesofthetestswithunit.

    Reply

    CreateafreewebsiteorblogatWordPress.com.

    TheEnterpriseTheme.

    Follow

    FollowElectricalNotes&Articles

    BuildawebsitewithWordPress.com