RESYS Type A earth leakage relays Protection for personnel and equipment ADAPTED PROTECTION IMPROVED IMMUNITY ERGONOMICS The differential relays in the RESYS range provide optimised protection and monitoring for electrical installations: combined with an automatic tripping device, they ensure protection for personnel and equipment. As a preventive measure, they also signal the appearance of earthing faults.

Upload: vandung

Post on 31-Aug-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

RESYS

Type A earth leakage relaysProtection for personnel and equipment

ADAPTED PROTECTION

IMPROVED IMMUNITY

ERGONOMICS

The differential relays in the RESYS range provide optimised protection and monitoring for electrical installations: combined with an automatic tripping device, they ensure protection for personnel and equipment. As a preventive measure, they also signal the appearance of earthing faults.

CO

UV

251

A -

SIT

E 13

6 A

- G

AM

ME

291

AFI

P 4

0013

- 0

4 / 1

3 -

Pho

to: M

artin

Ber

nhar

t - R

éalis

atio

n: S

OC

OM

EC

- T

o he

lp p

rote

ct th

e en

viro

nmen

t, th

is d

ocum

ent h

as b

een

prin

ted

on P

EFC

pap

er (P

rogr

amm

e fo

r th

e E

ndor

sem

ent o

f For

est C

ertif

icat

ion)

www.socomec.com

Non

con

trac

tual

doc

umen

t. ©

201

3, S

ocom

ec S

A. A

ll rig

hts

rese

rved

.

hEAD OffICE

SOCOMEC GROUPS.A. SOCOMEC capital 10 951 300 €R.C.S. Strasbourg B 548 500 149B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE

INTERNATIONAL SALES DEPARTmENT

SOCOMEC1, rue de Westhouse - B.P. 60010 F - 67235 Benfeld Cedex - FRANCETel. +33 (0)3 88 57 41 41 Fax +33 (0)3 88 74 08 [email protected]

YOUR DISTRIBUTOR

RESYSType A earth leakage relays

• Protection of personnel against indirect contacts (TT earthing arrangement) or in case of non-interconnected earths (IT system) and in the presence of long lengths of cable (TN or IT systems).

• Protection of installations against the risks of fire or explosion generated by earth leakage currents in areas classed as BE2 or BE3.

• Protection of the machine park (motors, rotating machinery) and reduction of the downtime because of the faults which may occur in the monitored network.

• Continuity of the power supply for strategic applications or in isolated sites (RESYS M40R)If the fault is not permanent, simple reclosing may be sufficient to re-establish the power supply and ensure continuity of service in the absence of a maintenance team.

Conformity to standards• IEC 60755• IEC 62020• IEC 60947-2• IEC 60364

Benefits Applications• Adaptedprotection

Type A earth leakage relays assures tripping when detecting a residual differential alternating sinusoidal currents or pulsed continuous residual currents where DC component remains below 6 mA.

• Improvedimmunityto EMC disturbances and reduced random tripping by means of the TRMS measurement (true root mean square).

• Ergonomics- Instantaneous display of permanent

leakage currents.- Compact flush-mounted and modular

units with LED bargraph.- Adjustment of IΔn from 0.03 to 30 A- Time delay from 0 to 10 s.- Alarm or pre-alarm configurable by the

user in positive or negative security mode.

Visit our website:www.socomec.com/en/resys

To find out more

flcd-

url_

065_

a_gb

RESYS

resy

s_08

4_a

Remotely trippable switches from 32 to 1800 A

Also available

ide_

021_

a

ide_

021_

a

Differential toroidal transformers are essential to the operation of the RESYS.The∆ICrangeiscomplete,practicalandinnovative(patentedaccessories).Learnmoreonourwebsite.

Core balance transformers

tore

_046

_a

tore

_035

_a

300 m A

RESYS M40R

RESYS P40

RESYS M40

BE 2BE 3

Auxiliary power supply Us RESYS M40 RESYS P40 RESYS M40R

115 VAC4941 3723

4942 37114941 3724

230 VAC 4942 3723400 VAC 4941 3740 - 4941 374112 … 125 VDC 4941 3602 4942 3602 -

I

tFault current.