ttaalogloguue ac - knurr usa · - and we respond with quality, flexi-bility, speed and perfect...

149
Miracel 19Rack EMC 19Rack ETS Rack Smaract Outdoor Cabinet Street Cabinet Outdoor Wall Case Thermal Management DC-UPS RMS T elec om Spe c i a l Ca t alogue T elec om Spe c i a l Ca t alogue Outdoor- and Indoor-Solutions

Upload: dangdang

Post on 16-May-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

Miracel 19“ Rack

EMC 19“ Rack

ETS Rack

Smaract

Outdoor Cabinet

Street Cabinet

Outdoor Wall Case

ThermalManagement

DC-UPS

RMS

TelecomSpecialCatalogue

TelecomSpecialCatalogue

Outdoor- and Indoor-Solutions

Page 2: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I

K N Ü R R A G

Page 3: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

K N Ü R R A G

II

Page 4: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

III

K N Ü R R A G

Welcome.

This special catalogue will serve to

help you with your selection and will

pinpoint those products that you

really need to meet your require-

ments in the telecommunications

area.

Page 5: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

K N Ü R R A G

IV

19” Racks 19” Enclosures Outdoor Racks

Modular Chassis Bus Systems Active Components

Thermal Management Socket Strips Workstation Systems

Mobile WorkstationsControl Consoles Assembly Furniture

Page 6: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

V

K N Ü R R A G

Our customers set the requirements

- and we respond with quality, flexi-

bility, speed and perfect service.

Worldwide, we are recognised as a

particularly reliable partner in the

areas of telecommunications and

data communication, server and net-

work technology, medical technology

and, of course, security, automation

and traffic control technology.

The product diversity and quality

provided by Knürr has been constantly

setting traditionally recognised high

standards for several decades. Our

standardised and customer-specific

technologies are the mirror image

of innovative engineering know-how,

which characterises and provides

the impetus for the markets in which

we operate.

Perfected solutions developed with

mechanical, electronic and thermal

components qualify us as one of the

global market leaders for highly

developed, modular rack and enclo-

sure systems in the indoor and out-

door area, especially for applica-

tions in the telecommunications area.

Workstation systems require uni-

form spatial concepts - complex

technological integration with the

highest functionality available! And

this we guarantee.

Mobile equipment carriers from

Knürr are also instrumental in crea-

ting efficiency and autonomy in the

laboratory, OP area, office or in the

workshop.

The global presence, the innovative

and aesthetic design, a mature

palette of standard products and the

recognised high degree of integration

competence, all supplemented by

outstanding time-to-market results

and above all the unsurpassed

quality, can have but one conclusion:

Page 7: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

C O N T E N T

VI

1IndoorSystems

2.3TecorasOutdoor CabinetStrong pointsProducts

2.11TecorasStreet CabinetStrong pointsProductsAccessories

2.23TecorasOutdoor Wall CaseStrong pointsProductsAccessories

2OutdoorSystems

1.3miracel 19” RackStrong pointsProducts

1.12EMC 19” RackDouble panelledStrong pointsProductsAccessories

1.21EMC 19” RackSingle panelledStrong pointsProductsAccessories

1.31ETS RackStrong pointsProducts

1.37smaractStrong pointsProductsAccessories

Page 8: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

VII

45.2RMScompactCapabilitiesProductsAccessoriesSensors

Power SupplySystems 6

6.2Standards and RegulationsProtection ratingsEMC InterferencesHeat transferFire behaviour

6.8Index

TechnicalSection3

4.2Rectifier/DC Powerand Backup SystemsStrong pointsTechnical dataProducts

4.10Distribution BoxProducts

ThermalManagement 5System

Monitoring

3.4Indoordart fan unitStrong pointsProductsAccessories

3.10Heat exchangerProducts

3.12Cooling unitProducts

3.15OutdoorTecorasStrong pointsProducts

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 9: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

VIII

Rapid service

Express Articles

Fast express delivery service,seamless ordering system,attractive prices and a market–oriented offer - that’s Knürr efficiency!

Every express article that iscorrespondingly identifed inthis catalogue leaves ourEuropean central stores 24hours after your order isreceived: qualitative high-grade, standardised solutions,with which you are alwaysdecisively ahead of the compe-tition.

Our sales offices are also avai-lable for you worldwide, wherecompetent technicians andsales engineers will personal-ly take care of your specialrequirements.Why not use these advantagesto your own benefit.

Express articles

in 24 hours ex plant:

With Knürr you are always

ahead of the competition

Page 10: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

IX

T E L E C O M S P E C I A L C ATA L O G U E

Products &Solutions Page X

Capabilities• Design & Prototyping Page XVIII

• Integration Page XXI

Page 11: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

X

Mobile NetworksProducts and Solutions

Mobile Networks

Knürr Tecoras product range

Indoor Rack, mobile base

stations, Siemens AG, Germany

Outdoor Cabinet, mobile base

stations, Siemens AG, Germany

Outdoor Cabinet, GSM base station

Telfort, Netherlands

Outdoor Cabinet, GSM base station

Telfort, Netherlands

Outdoor cabinet, Radio Base station

Nortel Networks

6

5

4

3

2

1

TEC002972

TEC200821

Indoor and Outdoor

Base stations for

GSM/UMTS/PMR/WLL

Base stations for mobile net-

works have to provide high

reliability. Tecoras Indoor

racks and Outdoor cabinets

offer an excellent solution for

such applications. Customer

specific requirements can

easily and cost effectively be

implemented due to the plat-

form design.

TEC002983

Page 12: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XI

T E L E C O M S P E C I A L C ATA L O G U E

TEC002954

TEC002965

TEC003166

Page 13: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XII

Outdoor Cabinets

Outdoor Wall Case

ETS rack, DSLAM, Nortel Networks

Broadband, Siemens AG4

3

2

1

Site Support Cabinet (SSC)

for transmission equipment

and DC-backups

Tecoras Outdoor Cabinet with

double walls, thermal manage-

ment system and modular

power supplies including batte-

ries are an excellent base for

Site Support Cabinets. The

modular extendable cabinets

ensure the possibility of future

system expansion.

Repeater

The optionally vented enclosures

for wall and pole mounting,

e.g. antenna and/or repeater

box, are part of the Tecoras

range for telecommunication

solutions.

TEC00010/TEC000871

TEC002482

Page 14: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XIII

T E L E C O M S P E C I A L C ATA L O G U E

Wireline NetworksProducts and Solutions

Wireline Networks

TEC000964

Indoor and Outdoor solutions for access networks

Both miracel Indoor Racks and Tecoras Outdoor

Cabinets are a suitable basis for access network

applications. These usually comprise a DC-UPS

System.

TEC200213

Page 15: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XIV

Telecom Solutions xDSL

With Knürr you will always

find an experienced partner

for complete solutions. Our

Indoor and Outdoor systems

are suitable for broadband

access points.

MIR200611

ISP/ASP

We can provide you with an

optimal rack solution for

colocation systems based on

the following features:

- Based on miracel platform

- Flexible installation space

- Compatible with standard

19“ servers

- Optimal cable management

- Thermal management

- Locking and security

provisions

SON201332

ISP Indoor Rack

ETS Rack assembling

Bavarian radio, tansmission station

Street Cabinet, PrimaCom

Data Center, Techdata, Munich5

4

3

2

1

Wireline NetworksProducts and Solutions

Wireline Networks

Page 16: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XV

T E L E C O M S P E C I A L C ATA L O G U E

CablingKnürr Data Center Competence

Cabling

MIR201825 KON200505

Structured cable

management in rack

systems plays a cen-

tral economic role.(Ask for the brochure!)

Cable TVProducts and Solutions

Cable TV

Tecoras Street Cabinets offer

an excellent mechanical and

thermal protection for CATV

equipment.

DAC201333 TEC800024

Page 17: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XVI

Transport EngineeringProducts and Solutions

Transport Engineering

Railway Solutions

Cost-effective Outdoor Cabinets with thermal manage-

ment systems replace container and concrete shelter

solutions for controlling railway crossings and points.

TEC003001

TEC003002

Outdoor Cabinet HEC for railway crossing and

point control

Street Cabinet, Greek State Railway, OSE Greece

Street Cabinet

Traffic Control Center, Deutsche Bahn AG,

Munich, Germany

4

3

2

1

Page 18: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XVII

T E L E C O M S P E C I A L C ATA L O G U E

Traffic Solutions

The comprehensive configur-

able Tecoras Street Cabinets

range with a whole set of

accessories is ideally suited

for traffic control, tunnel sur-

veillance and toll stations.

Traffic Control TechnologyKnürr Technical Furniture

Traffic Control Technology

TEC002573

MIR201824 KON200504

Complex solutions:

Functional furniture

with the technical

integration of many

active components.

Page 19: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XVIII

Design & PrototypingCapabilities

Design & Prototyping

We cost-effectively integrate the

customer’s corporate identity

into our product platforms

through Knürr’s international

industrial design capabilitiy.

This consequently results in a

customer-unique product.

Complete solution on a platform basis

Customer specific solutions can be cost-effec-

tively implemented in very little time through

tested and certified product platforms. This is

our answer to short Time-to-Market.

Page 20: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XIX

T E L E C O M S P E C I A L C ATA L O G U E

Climate calculation

We ensure that the customer

equipment always operates at

the right temperature. Climatic

calculations and simulations

are verified in our own climatic/

acoustics laboratory.

TEC00279

MIR20128

MIR20129

MIR20130

Solidness calculation

Top technologies and metho-

dologies. e.g. FEM Analysis

are used to cut development

time and cost for complex

testing.

Page 21: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XX

EMC Solutions

High shielding protection against

electromagnetic interferences

is provided by applying an inno-

vative connection technology

and reducing the number of

components, as well as through

careful selection of materials

with highly conductive surfaces.

MIR202142 MIR202163

MIR202134

Structured cabling

System integration and cab-

ling of thermal management

systems, power distribution

and supply, customer equip-

ment and functional testing

are all part of our value-added

service offers.

MEC20086TEC000731 TEC20095

SON20142

Design & PrototypingCapabilities

Design & Prototyping

Dynamic seismic test

In accordance with the FEM

Method, vibrations were simula-

ted in test labs that guarantee

earthquake stability of zone 4

with high loads in compliance

with the Bellcore Standard.

Page 22: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XXI

T E L E C O M S P E C I A L C ATA L O G U E

Dynamic seismic test

Simulation, FEM Method

Dynamic seismic test in accordance

with Bellcore Standard

Static tensile tests

Final check on ETS system racks

in the in-house test facility.

5

4

3

2

1

IntegrationCapabilities

Integration

HEI00429 HEI00430 HEI00431 HEI00432 HEI00433

Level 1

Mechanical assembly

Level 2

Electromechanical assembly

Level 3

Electronic enclosure system

Level 4

Active cards and software

Level 5

Black box & drop ship

TEC201265

Final check

The knowledge and experience

that Knürr can draw on enable

us to provide several levels of

support that reflect the needs

of your company and your

customers:

From Level 1 (assembly of

mechanical components) to

Level 5 (complete turnkey

solutions, starting from design,

through assembly and delivery

to the end user, to follow-on

training and support).

Page 23: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XXII

Power supply dimensioning

and arrangement

Configurable modular Power

Supply Units combined with

additional battery back-up,

monitoring and customised

distribution units provide opti-

mal compliance with system

requirements. AC distribution

units can be adopted according

to international standards and

with country specific outlets.

DI-STRIPKnürr Socket Strips

DI-STRIPYou will find the complete

range in the current

Knürr Network Special

Catalogue.

Request via:

www.knuerr.com

HEI00393

IntegrationCapabilities

Integration

HEI00400

The Knürr Group can help take

your product from the drawing

board to your customer’s faci-

lity, with comprehensive design,

program management, assem-

bly, testing, shipment, training,

and support services.

Page 24: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

XXIII

T E L E C O M S P E C I A L C ATA L O G U E

RMS

The Rack Monitoring System

can monitor all environmental

and security events in your net-

work. Sensors permanently

check system conditions and

operational status. Via different

interfaces, the events can be

evaluated remotely, and appro-

piate alarms set.

@Lock

Standard locking systems can

be replaced with electromechan-

ical locking components, allow-

ing simplified administration,

logging and control of access

rights.

Electrical safety

Safety through over-voltage and

lightning protection.

Input box consisting of:

- Monitored over-voltage protection

- Line filter for mains

- Bush-type filter for signal cables

- Supply thermal block HEI00394

MIR20115

VHP00208

RMS20013

Sensors

Safety ensured through early

fire and smoke detection with

special sensors.

IntegrationCapabilities

Integration

Page 25: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E L E C O M S P E C I A L C ATA L O G U E

XXIV

It is practically irrelevant where you are: if you would like to get to know the Knürr Group’s range of

products and services, there are numerous platforms readily at your disposal. With international repre-

sentation in 32 countries world-wide, domestic companies and overseas subsidiaries, we are

strategically best situated for your requirements.

On the Internet at www.knuerr.com, in addition to all the latest

news, you can find our entire product range including technical

data, press releases and background reports and specialist

articles. Knürr product experts will be able to answer your que-

stions at numerous secialist exhibitions both at home and abro-

ad and will offer comprehensive advice.

Should you wish to realise your workstation system plans with

the Knürr Group, we will happily come and visit you.

Want to get to knowus better?We are always justa click away.

www.knuerr.com

Page 26: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1IndoorSystemsmiracel 19” Rack 1.3 to 1.11

EMC 19” Rack 1.12 to 1.30

ETS Rack 1.31 to 1.36

smaract 1.37 to 1.52

1.1

I N D O O R S Y S T E M S

Page 27: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

Indoor Systems

miracel 19” RackStrong Points 1.5

Products 1.9

EMC 19” Rack,Double panelled

Strong Points 1.13

Products 1.16

Accessories 1.17

EMC 19” Rack,Single panelled

Strong Points 1.22

Products 1.26

Accessories 1.27

ETS RackStrong Points 1.32

Products 1.34

smaractStrong Points 1.38

Products 1.40

Accessories 1.42

1.2

I N D O O R S Y S T E M S

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 28: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2miracel19” Rack 1.4 to 1.11

EMC 19” Rack 1.12 to 1.30

1.3

I N D O O R S Y S T E M S

Page 29: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.4

miracel, the product platform with highflexibility for different applications like ...

... Servers ... Cabling

... power supply ... Mobile communications

MIR

20

17

1

MIR

20

17

3

MIR

20

17

5

TEC

20

06

5

Page 30: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.5

I N D O O R S Y S T E M S

Front doors

Side panel Ventilation lid

Rear panel

Vertical extrusion (T-slot/mounting holes)

19” Swing frame

Basic rack

Trim extrusion

Side panelMulti-functional strut

Rack bottomcover

Rack plinth, mobile

Rack plinth, stationary

Rack bottom covers

MIR00145

Modularity by availability of different components

Page 31: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.6

miracel, tested intensively, e.g.Earthquake zone 4, EMC

MIR00227

Page 32: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.7

I N D O O R S Y S T E M S

B B1 X

[mm] [mm] [mm]

600 535 485

700 635 585

800 735 685

900 835 785

T T1 Y

[mm] [mm] [mm]

600 530 485

800 730 685

900 830 785

1000 930 885

Material- Extruded aluminium- Corner piece, die-castaluminium- Covers, sheet steel, zinc passi-

vated- Doors, sheet steel or with

single safety glass panel,4 mm and 6 mm (double doors)

Installation dimensions in

accordance with IEC 297-3

and IEC 917

- Height: 23 HU / 37 HU / 41 HU /46 HU(1 HU (or 1U) = 44.45 mm)66 Module / 74 module / 82module (1 module = 25 mm)- Width: 482.6 mm (19” design),535 mm (20 module design)

Space solution

- 82% of the surface area asuseable surface for installationand cable routing- Cross-connecting (jumpering)

space, front 123 mm, and 73 mm- Door opening angle 180°

Configuration

- Stationary, on levelling feet- Stationary with plinth- Mobile with plinth and lock

Finish / Colour

- Basic rack, polished- Door trim, black, RAL 9011- Visible cover surfaces, powder-coated, light-grey RAL 7035 ordark-grey RAL 7021

Static load rating

- 5000 N With stationary model- 3000 N With mobile model

Heat transfer

Dissipation power with- Closed cover, up to500 W- Vent lid, up to 700 W

Tests according to the model

- Vibration test in accordancewith MIL-STD 810 E- IP Test in accordance with IEC529- UL Test 1244- NEMA 12 Standard- EMC Shielding attenuation inaccordance with MIL-STD 285(10 MHz - 30 MHz) and VG95 373 part 15 (30 MHZ-1GHz)- Vibrations and shock test inaccordance with ETS 300 019- Seismic test, Bellcore (NEBS)TR-NWT 000063 zone 4- Earth continuity, VDE 0 100 T540

Additional standards and tests onrequest.

Rack suites

To set up a rack suite with anumber of racks (n) you require- all racks (n) minus 1 without

side panels and one rack withside panels - in a rack suite, per connection,

you require one set of rackconnectors

miracel 19” RackTechnical data

Vertical extrusion with mounting holesSteel for 19" racks

19" Server extrusion

Vertical extrusion with T-slotAluminium for 19” structure

7,5

17

32

,5

44

,661

14,8

Vertical extrusion with T-slot

Aluminium, for metric structure, 20 module

MIR00307

MIR00308

MIR00309

MIR20041

MIR00332

Page 33: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.8

Forward-thinking

Flexibility and security for the

future by integrating 19” andmetric technology.

Modular construction

Includes easy mounting of allnon-standard electronic installa-tions - variable and at integrated

19” or 25 mm increments.

Can be extended at any time

System extensions can be easily

implemented while retaining theIP protection rating.

3

2

1 Cable management

Guaranteed orderly and space-saving cable routing.

Adaption to the installation site,

cable routing selectable with anextensive range of accessory

components.

Flexible ventilation components

Always the best ventilation soluti-

on with the corresponding choiceof accessory components. In this

way, by utilising perforated bot-tom covers, top covers and doors,

the airflow can be specificallyadapted to the installed compo-nents.

5

4

miracelStrong points

MIR201221

TEC000283

MIR005214

MIR004274

MIR001914

MIR200525

MIR004065

MIR001392

Page 34: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.9

I N D O O R S Y S T E M S

miracelWidth 600 mm and 800 mm with mounting hole extrusion

With fixed 19”-built-in unit on the frontand rear

Installation of chaissis runners and19”-shelves possible

For built-in units in accordance withIEC 297-3

For the installation of- 19” Components on the front and rear- Equipment with maximum width of450 mm- Installation accessories

Jumpering compartment- Front 73 mm

Load rating- 5000 N static

Tests- Earthing according to VDE 0100 part 540- Vibration test according to MIL-STD810 E

Material / Finish- Basic rack, extruded aluminium,polished- Corner piece die-cast aluminium- Multifunctional frames and 19” angularextrusions sheet steel, zinc-plated

Supply schedule1 Basic unit4 19” Sheet steel angular extrusions withmounting holes

2 Multifunctional frames for cable clam-ping and universal assembly options4 Levelling feet (0-25 mm)

How supplied- Assembled

Please noteRack suitesIn a rack suite, per connection you requirea set of suite connectors BN 01.130.935.7

MIR00196

W H D HU/U h d kg Model Order no. UP

591 1196 585 23 1052 440 13 01.130.190.0 1 unit

591 1596 585 32 1452 440 15 01.130.192.0 1 unit

591 1796 585 37 1652 440 16 01.130.193.0 1 unit

591 1996 585 41 1852 440 17 01.130.194.0 1 unit

591 2196 585 46 2052 440 18 01.130.195.0 1 unit

591 1196 785 23 1052 640 14 01.130.280.0 1 unit

591 1596 785 32 1452 640 16 01.130.282.0 1 unit

591 1796 785 37 1652 640 17 01.130.283.0 1 unit

591 1996 785 41 1852 640 18 01.130.284.0 1 unit

591 2196 785 46 2052 640 19 01.130.285.0 1 unit

791 1196 585 23 1052 440 14 01.130.226.0 1 unit

791 1596 585 32 1452 440 16 01.130.228.0 1 unit

791 1796 585 37 1652 440 17 01.130.229.0 1 unit

791 1996 585 41 1852 440 18 01.130.230.0 1 unit

791 2196 585 46 2052 440 19 01.130.231.0 1 unit

791 1196 785 23 1052 640 15 01.130.316.0 1 unit

791 1596 785 32 1452 640 17 01.130.318.0 1 unit

791 1796 785 37 1652 640 18 01.130.319.0 1 unit

791 1996 785 41 1852 640 19 01.130.320.0 1 unit

791 2196 785 46 2052 640 22 01.130.321.0 1 unit

MIR00300

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 35: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.10

miracelWithout front door width 600 mm

With fixed 19”-built-in unit on the frontand rear

Installation of chaissis runners and19”-shelves possible

For built-in units in accordance withIEC 297-3

For the installation of- 19” Components on the front and rear- Equipment with maximum width of450 mm- Installation accessories

Jumpering compartment- Front 73 mm

Load rating- 5000 N static

Tests- Earthing according to VDE 0100 P 540- Vibration test according to MIL-STD810 E

Material / Finish- Basic rack, extruded aluminium- Corner piece die-cast aluminium- Covers and trim extrusions zinc-plated

sheet steel, powder-coated textured- Multifunctional member and 19”-extru-

sions sheet steel, zinc-plated

Colour- Basic unit polished- Visible surface of the cover RAL 7035light grey- Trim extrusions RAL 5008 grey-blue

Supply schedule1 Basic unit4 19” Sheet steel angular extrusions withmounting holes

2 Multifunctional menbers for cable clam-ping and universal assembly options1 Cover, closed1 Rear panel with quick locking2 Side panels with quick locking2 Horizontal decorative extrusions on thefront

2 Vertical decorative extrusions on thefront4 Levelling feet (0-25 mm)

How supplied- Assembled

MIR00466

MIR00540

W H D HU/U h d kg Model Order no. UP

600 1200 600 23 1052 440 42 01.131.068.1 1 unit

600 1600 600 32 1452 440 52 01.131.070.1 1 unit

600 1800 600 37 1652 440 57 01.131.071.1 1 unit

600 2000 600 41 1852 440 62 01.131.072.1 1 unit

600 2200 600 46 2052 440 66 01.131.073.1 1 unit

600 1200 800 23 1052 640 48 01.131.074.1 1 unit

600 1600 800 32 1452 640 58 01.131.076.1 1 unit

600 1800 800 37 1652 640 63 01.131.077.1 1 unit

600 2000 800 41 1852 640 69 01.131.078.1 1 unit

600 2200 800 46 2052 640 75 01.131.079.1 1 unit

MIR00540

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 36: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.11

I N D O O R S Y S T E M S

miracel IP 55With a single-winged glass door width 600 mm

With fixed 19”-built-in unit on the frontand rear

For built-in units in accordance withIEC 297-3

Door opening angle 180°

For the installation of- 19” Components on the front and rear- Equipment with maximum width of450 mm- Installation accessories

Jumpering compartment- Front 73 mm

Load rating- 5000 N static

Degree of protection- IP 55

Tests- Earthing according to VDE 0100 P 540- Vibration test according to MIL-STD810 E- IP test according to DIN 40 050 / IEC 529

Material / Finish- Basic rack, extruded aluminium,polished- Corner pieces, die-cast aluminium,polished- Covers zinc-plated sheet steel,powder-coated textured- Doors, sheet steel, powder-coated

structure, glass infill front door, singlesecurity-glass panel, 4 mm- Multifunctional members and19”-extrusions sheet steel, zinc-plated

Colour- Door trim RAL 9011 black- Visible surface of the cover RAL 7035light grey

Supply schedule1 Basic unit4 19” Sheet steel angular extrusions withmounting holes

2 Multifunctional menbers for cable clam-ping and universal assembly options1 Cover, closed, IP 551 Front door, single-winged, single secu-

rity glass panel, with handle and fixingfor locking cylinders, IP 551 Rear panel with quick locking, IP 552 Side panels with quick locking, IP 551 Base, closed, IP 554 Levelling feet (0-25 mm)

How supplied- Assembled

Please noteRack suitesTo create a rack series with the racknumber n, you require:

(n-1) racks without side panels1 rack with side panels

In a rack suite, per connection you requirea set of suite connectors BN 01.130.935.7

MIR00467

MIR00301

W H D HU/U h d kg Model Order no. UP

600 1200 600 23 1052 440 55 01.132.268.1 1 unit

600 1600 600 32 1452 440 69 01.132.270.1 1 unit

600 1800 600 37 1652 440 75 01.132.271.1 1 unit

600 2000 600 41 1852 440 80 01.132.272.1 1 unit

600 2200 600 46 2052 440 86 01.132.273.1 1 unit

600 1200 800 23 1052 640 65 01.132.274.1 1 unit

600 1600 800 32 1452 640 76 01.132.276.1 1 unit

600 1800 800 37 1652 640 83 01.132.277.1 1 unit

600 2000 800 41 1852 640 90 01.132.278.1 1 unit

600 2200 800 46 2052 640 96 01.132.279.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 37: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.12

MIR00452

miracel double panelled EMC rack

Page 38: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.13

I N D O O R S Y S T E M S

MIR004531

MIR004542

MIR004553

Continuous high-grade stainless

steel EMC springs and foam IPseal for protection against elec-tromagnetic radiation and envi-

ronmentals.

Rear connection panel for univer-

sal cable entry mounted with

shortened rear panel or rear

door.

Reliable cable feed with strainrelief.

Simple operation:

Expose braided shield, push

through cable with plug, clampcable with seal.

Perforated top and bottomcovers for thermal managementin racks with simultaneous EMCshielding.

Perforated top and bottom covers

for thermal management in rackswith integrated cable entry andsimultaneous EMC shielding.

6

5

4

3

2

1

miracel 19”-EMC-Rack Double-panelled EMC conceptStrong points

MIR003304

MIR004565

MIR004586

Page 39: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.14

The diagramm below shows the

EMC design of miracel racks.

EMC shielding is provided by asecond metal case inside the

powder-coated covers.

The reliable, long-life contact

between the covers and the basicrack is guaranteed by a stainless-

steel spring, developed andpatented by Knürr.

The EMC spring permits covers

to be opened and closed ergono-mically with application of mini-

mum closing force while maintai-ning an enduring and reliablecontact.

The ideal combination of materi-

als in EMC through panls, EMCspring and basic rack with lowpotential differences guarantees

long life for contact points.

Extern IP seals also protect the

stainless-steel springs against

aggressive environmental condi-tions.

Technical datamiracel 19”-Rack EMC, double panelled EMC concept

EMC trough panel

High-grade steel spring IP Seal Door hinge

EMC trough panel

Door lock-and-release lever

High-grade steel spring

IP Seal

Quick-release fastener

IP Side panel

Page 40: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.15

I N D O O R S Y S T E M S

EMC Measurements were carriedout by the army’s Bundeswehr

university, Institute for Electron-ics (Prof. Dr. Schmeer), at

Munich, in a shielded anechoicchamber.

Measurements were carried out

in accordance with the following

standards:

MIL-STD 285(10 kHz - 30 MHz)VG 95373 part 15(30 MHz - 1 GHz)

EMC Test results

miracel, closedWidth 600 mm, depth 600 mm,37 U

2

1

miracel 19” Rack EMC, double panelled EMC concept

Technical data EMC Test results

MIR20196

MIR20197

Page 41: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.16

miracel 19” Rack, EMC width 600 mmdouble panelled EMC concept

With increased EMC shielding attenuationcompared with standard rack

With fixed 19”-built-in unit on the frontand rear

For built-in units in accordance withIEC 297-3

Door opening angle 180°

For the installation of- 19” Components on the front and rear- Equipment with maximum width of450 mm- Installation accessories

Jumpering compartment- Front 73 mm

Load rating- 5000 N static

Degree of protection- IP 55

Tests- Earthing according to VDE 0100 T 540- Vibration test accordance with MIL-STD810 E- IP test accordance with DIN 40 050 /

IEC 529- EMC in accordance with MIL-STD 285(10 kHz - 30 MHz)- EMC in accordance with VG 95 373 part15 (30 MHz - 1 GHz)

Material / Finish- Basic unit aluminium, crome-plated

yellow- EMC panel zinc-plated- EMC-contact springs stainless steel- Corner piece die-cast aluminium- Covers zinc-plated sheet steel,powder-coated structure- Doors, sheet steel, powder-coated

structure- Multifunctional members and 19” angularextrusions sheet steel, zinc-plated

Colour- Door trim RAL 9011 black- Visible surface of the cover RAL 7035light grey

Supply schedule1 Basic unit EMC4 19” Sheet steel angular extrusions withmounting holes1 Cover EMC, closed1 Front door, single-winged, sheet steel,

with handle and fixing for locking cylin-ders1 Rear panel EMC; sheet steel2 Side panels EMC with quick locking1 Base EMC, closed4 Levelling feet (0-25 mm)

How supplied- Assembled

MIR00449

MIR00301

W H D HU/U h d kg Model Order no. UP

600 1800 600 37 1652 440 122 01.134.053.1 1 unit

600 2000 600 41 1852 440 131 01.134.054.1 1 unit

600 2200 600 46 2052 440 140 01.134.055.1 1 unit

600 1800 800 37 1652 640 133 01.134.059.1 1 unit

600 2000 800 41 1852 640 145 01.134.060.1 1 unit

600 2200 800 46 2052 640 154 01.134.061.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 42: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.17

I N D O O R S Y S T E M S

MIR00460

MIR00461

MIR00330

miracel EMCConnection baord with flexible cable entry

For EMC miracel with double panelledEMC concept

EMC connection board rear, with cableentry

Compatible EMC sheet steel door shorte-ned or EMC rear panel shortened, alsoavailable

Degree of protection- IP 54

Material / Finish- Cable entry, zinc passivated- Cover, powder coated, textured,

RAL 7035 light-grey

Supply schedule1 Cable entry, complete1 CoverEMC sealsCross-sealingMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.134.800.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 43: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.18

MIR00464

miracel EMC Sheet steel door, shortenedFor use with an EMC cable inlet, rear

For EMC miracel with double panelledEMC concept

With use of an EMC cable entry, rear side

MaterialSheet steel

Finish- Sheet steel door powder-coated lightgrey, textured RAL 7035 light grey- EMC tray, zinc passivated

Supply schedule1 Sheet steel door1 EMC tray incl. EMC springDesign trimMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 2000 600 1600 01.134.637.1 1 unit

600 2000 800 1600 01.134.638.1 1 unit

600 2200 600 1800 01.134.639.1 1 unit

600 2200 800 1800 01.134.640.1 1 unit

MIR00465

miracel EMC Rear panel, shortenedFor use with an EMC cable inlet, rear

For EMC miracel with double panelledEMC concept

With use of an EMC cable entry, rear side

MaterialSheet steel

Finish- Rear panel: powder-coated, textured

RAL 7035 light grey- EMC tray, zinc passivated

Supply schedule1 Rear panel1 EMC tray incl. EMC springMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 2000 600 1600 01.134.649.1 1 unit

600 2000 800 1600 01.134.651.1 1 unit

600 2200 600 1800 01.134.653.1 1 unit

600 2200 800 1800 01.134.655.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 44: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.19

I N D O O R S Y S T E M S

MIR00463

miracel EMC tray, perforatedFor bottom / top cover

For EMC miracel with double panelledEMC concept

For ventilation with convection or inconjunction with the ventilation unit

Retention of the EMC shielding

Finish- Zinc passivated

Supply schedule1 EMC Panel bottom / top coverperforated4 Distance bolts for top cover

How supplied- In batches

Please noteThe outer cover must be raised, distancebolts for this are included.

W H D HU/U h d kg Model Order no. UP

600 800 01.134.876.0 1 unit

MIR00456

MIR00459

MIR00458

miracel EMC tray, perforated with cable entryFor bottom / top cover

For EMC miracel with double panelledEMC concept

For entry for cable with plug

Suitable for different cables beside oneanother

For ventilation with convection or inconjunction with the ventilation unit

Retention of the EMC shielding

Finish- Zinc passivated

Supply schedule1 EMC Panel, complete4 Distance bolts for top cover

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 800 01.134.921.0 1 unit

Page 45: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.20

MIR00462

miracel EMCFan installation set

For EMC miracel with double panelledEMC concept

For mounting in the rack upper frame,use only in conjunction with perforatedEMC panel

Fan unit can be retrofitted on 6 fans,cables are pre-configured

Individual fan for upgrading,order no. 03.210.245.9

Includes thermostat (10 - 60° C)

Includes 2 fans (117 m3/h)

Fully wired with 2.5 m power supply leadand plug

Finish- Cover, zinc passivated

Supply schedule1 Airmatic ventilation unit with two fans

and thermostat2 Cover plates2 Mounting brackets

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 800 01.134.961.0 1 unit

MIR00457

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 46: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

TEC20065

1.21

I N D O O R S Y S T E M S

miracel single panelled EMC rack

Page 47: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.22

Different top cover, door and bot-tom cover variants permit therequired passive air convection tobe attained depending on theprevailing climatic conditions andin accordance with requirements.

Additional ventilation unit is alsoavailable in the top-cover area tomeet enhanced cooling require-ments.

In accordance with IEC 297 for19” installations and IEC 917 formetric installations

In three height variants

(37, 41, 46 U), two depth variants

(400 mm, 600 mm) and one stan-dard with (600 mm).

EMC 19” RackSingle panelled EMC concept (Tecoras indoors)

TEC00045

Page 48: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.23

I N D O O R S Y S T E M S

EMC Shielding- EMC Shielding comes as stan-

dard with EMC-compatibledesign and the use of suitableseals, combined with IP protec-tion rating to IP 43.

1 EMC suites

- A baying kit permits severalracks to be combined and forma rack suite including cross

wiring of the components andmaintenance of EMC shieldingand IP protection rating.

Cable feed- Accessory components permitan option of top and bottomcable feed.

Ventilation concept

- Perforated bottom and topcovers permit natural convec-tion.

- A fan unit can be mounted inthe top cover outside the instal-lation area to enhance theaction of convection.

- Perforated doors provide anair-intake surface over the enti-re rack height to meet higher

flow-rate requirements.

4

3

2

miracel 19”-EMC Rack, Single-panelled EMC conceptStrong points (Tecoras Indoor)

TEC200951

TEC000282 TEC000293 TEC000724

Page 49: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.24

miracel 19”-EMC Rack, single panelled EMC concept

Technical data (Tecoras Indoor)

Top Cover

- closed- perforated- closed or perforated, with cable inlet

Rear panel

Side panel

Basic rack

Front door

- closed- perforated- double doors, closed or perforated

Bottom cover

- closed- perforated- closed or perforated with cable inlet

Small and few gaps

Labyrinth effects

Use of modern bendingtechnology

EMC-compatible design

Use of EMC/IP sealings

Use of highly conductive sheetmetal (zink coated)

Technical data

miracel 19” Rack EMC, single panelled EMC concept

TEC00440 Door hingeEMC/IP Seal

Door panel

Frame extrusions Side panel

Page 50: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.25

I N D O O R S Y S T E M S

EMC Measurements were carriedout by the army’s Bundeswehruniversity, Institute for Electron-ics (Prof. Dr. Schmeer), atMunich, in a shielded anechoicchamber.

Tests were conied out in accor-dance with the following stan-dards:- MIL 285- VG 95373 part 15

Tested rackW 600, D 600, H 2000,closed version

miracel 19”-EMC Rack, single panelled EMC concept

Technical data EMC Test results

TEC20095

TEC00082

Dimensions

Installation height h mm 1652 1852 2052

HE/U 37 41 46

Modul 66 74 82

Overall height H mm 1800 2000 2200

Installation width b mm 482,6 (19”) 482,6 (19”) 482,6 (19”)

alternative Modul 20 20 20

Overall width B mm 600 600 600

Installation depth t mm 235 235 235

alternative mm 435 435 435

Overall depth T mm 400 400 400

alternative mm 600 600 600

Page 51: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.26

TEC00106

EMC 19” Rack, nominal width 600 mmSingle panelled EMC-concept (Tecoras Indoor)

Suitable for applications with higherrequirements for EMC shielding, e.g. intelecommunications technology

With fixed 19”-built-in unit on the front

For built-in units in accordance withIEC 297-3

Door opening angle 180°

For the installation of- 19” Components on the front- Equipment with maximum construction

width of 450 mm- Installation accessories

Jumpering compartment- Front 73 mm

Load rating- 5000 N static

Degree of protection- IP 43

Heat dissipation- Loss of power up to 500 Watt as

standard

Tests- Earthing in accordance with

VDE 0100 T 540- Vibration test in accordance with

MIL-STD 810 E- Vibration and shock test in accordance

with ETS 300019- IP test according to DIN 40 050 / IEC 529- EMC in accordance with MIL-STD 285(10 kHz - 30 MHz)- EMC in accordance with VG 95 373

Teil 15 (30 MHz - 1 GHz)

Material / Finish- Basic rack, aluminium extrusions,polished- Die-cast aluminium corner pieces- Covers, sheet steel zinc-platedpowder-coated textured- Door, sheet steel zinc-plated, powder-

coated textured- Rear panel, sheet steel, zinc-plated,powder-coated textured

Colour- Visible cover surfaces powder-coated

RAL 7035 light grey

Supply schedule1 Basic rack2 19” Steel extrusions with mountingholes1 Cover, closed1 Front door, single-winged, sheet steel,

with handle and fixing for lockingcylinders1 Rear panel with quick locking2 Side panels, bolted1 Base, closed4 Levelling feet (0-25 mm)

How supplied- Assembled

W H D HU/U h d kg Model Order no. UP

600 1800 400 37 1652 235 52 01.171.009.1 1 unit

600 2000 400 41 1852 235 56 01.171.010.1 1 unit

600 2200 400 46 2052 235 61 01.171.011.1 1 unit

600 1800 600 37 1652 435 60 01.171.021.1 1 unit

600 2000 600 41 1852 435 65 01.171.022.1 1 unit

600 2200 600 46 2052 435 70 01.171.023.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 52: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.27

I N D O O R S Y S T E M S

TEC00284

Door EMC, perforatedSingle panelled EMC concept (Tecoras Indoor)

Offers air intake surface across the entirerack height with greater air requirementsof the built-in units

Retention of the EMC shielding

Material / Finish- Sheet steel, 1.5 mm heat zinc-plated,

visible surfaces, powder-coated textured

Colour- RAL 7035 light grey

Supply schedule1 EMC door, perforatedMounting hardware

How supplied- Preassembled

W H D HU/U h d kg Model Order no. UP

600 1800 37 01.171.195.1 1 unit

600 2000 41 01.171.196.1 1 unit

600 2200 46 01.171.197.1 1 unit

TEC00283

Door EMC, double wingedSingle panelled EMC concept (Tecoras Indoor)

Lower space requirements in depth whendoor open

Retention of the EMC shielding

Material / Finish- Sheet steel, 1.0 mm heat zinc-plated,powder-coated textured

Colour- RAL 7035 light grey

Supply schedule1 EMC door, double-wingedMounting hardware

How supplied- Preassembled

W H D HU/U h d kg Model Order no. UP

600 1800 37 01.171.207.1 1 unit

600 2000 41 01.171.208.1 1 unit

600 2200 46 01.171.209.1 1 unit

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM-Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 53: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.28

TEC00287

Top cover EMC, closed with cable entrySingle panelled EMC concept (Tecoras Indoor)

Easily removable panel for individualprocessing

To enter cables from above

Retention of the EMC shielding

Material / Finish- Sheet steel, 1.5 mm heat zinc-plated,

visible surfaces, powder-coated textured- Cable inlet plate zinc-plated

Colour- RAL 7035 light grey

Supply schedule1 EMC cover, closed with cable entryMounting hardware

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.107.1 1 unit

600 600 01.171.109.1 1 unit

TEC00286

Top cover EMC, perforatedSingle panelled EMC concept (Tecoras Indoor)

To improve rack cooling by naturalconvection and supported convection bymeans of a fan installation

Retention of the EMC shielding

Material / Finish- Sheet steel, 1.5 mm, heat zinc-plated,

visible surfaces, powder-coated textured

Colour- RAL 7035 light grey

Supply schedule1 EMC cover, perforatedMounting hardware

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.087.1 1 unit

600 600 01.171.089.1 1 unit

TEC00288

Top cover, EMC perforated, with cable entrySingle-panelled EMC concept (Tecoras-Indoor)

To improve rack cooling by naturalconvection and supported convection bymeans of a fan installation

Cable entry panel can be easily removeddue to the simple EMC connector systemand can be provided with suitable cutoutsfor cable entries or fitting of EMC filters

Retention of the EMC shielding

Material / Finish- Sheet steel, zinc passivated, powder-

coated, textured, RAL 7035 light-grey- Cable entry: Sheet steel, zinc passivated

Colour- RAL 7035 light grey

Supply schedule1 Top cover, perforated, with cable entryMounting hardware

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.117.1 1 unit

600 600 01.171.119.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 54: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.29

I N D O O R S Y S T E M S

TEC00291

Bottom EMC closed, with cable entrySingle panelled EMC concept (Tecoras-Indoor)

Easily removable board for individualadaptation

Cable entry panel can be easily removeddue to the simple EMC connector systemand can be provided with suitable cutoutsfor cable entries or fitting of EMC filters

Retention of the EMC shielding

Material- Sheet steel, zinc passivated

Supply schedule1 Bottom cover, closed, with cable entryMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.251.0 1 unit

600 600 01.171.253.0 1 unit

TEC00292

Bottom EMC perforated, with cable entrySingle panelled EMC concept (Tecoras-Indoor)

To improve rack cooling by naturalconvection and supported convection bymeans of a fan installation

Cable entry panel can be easily removeddue to the simple EMC connector systemand can be provided with suitable cutoutsfor cable entries or fitting of EMC filters

Retention of the EMC shielding

Prepared for inserting a filter mat underthe bottom cover

Material- Sheet steel, zinc passivated

Supply schedule1 Bottom cover, perforated, with cableentry

Mounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.271.0 1 unit

600 600 01.171.273.0 1 unit

TEC00290

Bottom EMC perforatedsingle panelled EMC concept (Tecoras-Indoor)

To improve rack cooling by naturalconvection and supported convection bymeans of a fan installation

Retention of the EMC shielding

Prepared for inserting a filter mat underthe bottom cover

Material- Sheet steel, zinc passivated

Supply schedule1 Bottom cover, perforatedMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.261.0 1 unit

600 600 01.171.263.0 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 55: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.30

SMA20058

Replacement filter mats

For perforated bottom covers (Tecoras-Indoor)

For bottom cover with perforation Material- Filedon

Supply schedule1 Set at 5 items

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

600 400 01.171.217.9 1 unit

600 600 01.171.219.9 1 unit

TEC00282

Suite connector, EMCSingle-panelled, EMC concept (Tecoras-Indoor)

For the mechanical, stable connection ofcabinet and rack suites

Expansion of systems in operationpossible from outside

Retention of the EMC shielding values

Retention of the IP protection rating

Supply schedule2 Suite connectors, vertical1 Suite connector, bottom1 Suite connector, topMounting material

How supplied- In batches

W H D HU/U h d kg Model Order no. UP

1800 400 01.171.176.1 1 unit

1800 600 01.171.178.1 1 unit

2000 400 01.171.181.1 1 unit

2000 600 01.171.183.1 1 unit

2200 400 01.171.186.1 1 unit

2200 600 01.171.188.1 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 56: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1ETS Rack

1.32 to 1.36

1.31

I N D O O R S Y S T E M S

Page 57: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.32

ApprovalThe ETS racks have the DeutscheTelekom certificate of approval.

Ventilation

The rack construction design

favours natural convection.

Flexibility

- The height-adjustable wallmounting allows flexiblemounting for the rack to matchsurrounding environments.

- Optional cable entry over grid

flooring or hollow flooring.

1

ETS RackStrong points

TEC00280

Rear panel

Cable mounting rails

Cover closed with cable inlet

Basic rack

Front door

- closed- perforated

Page 58: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.33

I N D O O R S Y S T E M S

TEC00083

TEC000301

The ETS system rack complies withETS 300 119-3 (EuropeanTelecommunications Standard) andthe technical supply conditions5805-3158 of Deutsche Telekom forinstallation in accordance with IEC917 and IEC 297.

Material- Basic rack, sheet steel 2.0 mm- Doors and rear panel,

sheet steel 1.0 mm- Roof, sheet steel 1.5 mm- Plinth trim, sheet steel

2.0 mm

Finish- Vertical posts and mounting

brackets for cable grid connec-tion, zinc passivated andchrome-plated (Fe/Zn 6-12 cB)- Basic racks, doors, rear panel

and plinth trim, powder-coatedRAL 7032, pebble grey textured

ConfigurationStationary, on levelling feet

Static loads- Maximum load with uniformdistribution: 2300 N- Maximum permissible load with

cable runway and cable: 1900 N- Maximum compressive load on

the floor exerted by feet:490 N/cm2

Tecoras ETS RackTechnical data

ETS Rack Dimensioning

W H D CW w h d

600 2200 300 500 515 2052 240

Page 59: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.34

ETS Rack H 2200, d 240 weldedFor installations in accordance with IEC 917 and IEC 297

ETS System rack complies with ETS300 119-3 (European TelecommunicationsStandard) and the technical supply conditions5805-3158 of Deutsche Telekom for installati-ons in accordance with IEC 917 and IEC 297.

Standard features

- Welded version, height 2200 mmconsists of:1 Basic rack

consisting of 2 side panels and4 bracing struts

2 Levelling feet4 Cable restraints2 ESD Jacks

30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 300 82M 2050 240 ETS Rack 01.100.001.3 1 unit

Front door closed 01.100.010.3 1 unit

Front door perforated 01.100.011.3 1 unit

Rear panet 01.100.021.3 1 unit

Root, closed 01.100.031.3 1 unit

Plinth trim with option for socket 01.100.053.3 1 unit

ETS Rack H 2200, d 240 flat packedFor installations in accordance with IEC 917 and IEC 297

Standard features

- Flat pack version, height 2200 mm,for mounting on-site, consisting of:2 Side panels4 Bracing struts2 Levelling feet4 Cable restraints2 ESD Jacks2 L Rails with cable holder for

connection to the cable gridMounting material30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 300 82M 2050 240 ETS Rack 01.100.003.3 1 unit

ETS Rack H 2200, d 170 weldedFor installations in accordance with IEC 917 and IEC 297

Standard features

- Welded version, height 2200 mm withrecessed side panels and recessedmounting level for 170 mm installationdepth consisting of:1 Basic rack

consisting of 2 side panels and4 bracing struts8 Cable covers2 Levelling feet4 Cable restraints2 ESD Jacks2 L Rails with cable holder for

connection to the cable grid30 Caged nuts M6 (pack)

TEC00090

W H D HU/U h d Model Order no. UP

600 2200 300 82M 2050 170 ETS Rack 01.100.004.3 1 unit

TEC00251

Page 60: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.35

I N D O O R S Y S T E M S

TEC00251

ETS Rack H 2200, d 170, earth quake proofedFor installations in accordance with IEC 917 and IEC 297

Standard features

- Welded version, height 2200 mm withrecessed side panels and recessedmounting level for 170 mm installationdepth, earthquake-proof in accordancewith Telcordia GR-63-CORE zone 4,consisting of:1 Basic rack

consisting of 1 bottom cover, 1 topcover and 2 side panels8 Cable covers4 Cable restraints2 ESD Jacks2 L Rails with cable holder for

connection to the cable grid30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 300 82M 2050 170 ETS Rack 01.100.005.3 1 unit

ETS Rack H 1800, d 240, weldedFor installations in accordance with IEC 917 and IEC 297

Standard features

- Welded version, height 1800 mmconsisting of:1 Basic rack

consisting of 2 side panels and4 bracing struts

2 Levelling feet3 Cable restraints2 ESD Jacks2 L Rails with cable holder for

connection to the cable grid30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 300 66M 1650 240 ETS Rack 01.100.006.3 1 unit

ETS Rack H 2200, d 480, weldedFor installations in accordance with IEC 917 and IEC 297

Standard features

- Welded version, height 2200 mmand depth 600 mm consisting of:1 Basic rack

consisting of 2 side panels and4 bracing struts4 Levelling feet4 Cable restraints2 ESD Jacks2 L Rails with cable holder for

connection to the cable grid30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 600 82M 2050 480 ETS Rack 01.100.007.3 1 unit

Page 61: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.36

ETS Rack H 2200, d 240, weldedFor 23” Installations

Standard features- Welded version, height 2200 mmand depth 300 mm consisting of:1 Basic rackconsisting of 2 side panels and4 bracing struts

4 Levelling feet

4 Cable restraints

2 ESD Jacks

2 L Rails with cable holder for

connection to the cable grid30 Caged nuts M6 (pack)

W H D HU/U h d Model Order no. UP

600 2200 300 82M 2050 240 ETS Rack 01.100.008.3 1 unit

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 62: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2smaractCompact Rack 1.38 to 1.52

1.37

I N D O O R S Y S T E M S

Page 63: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.38

Access

Access from all sides is atime-saving factor with, forexample, system integrationor maintanence.

First-class design

Low weight with innovative frameconcept. Nevertheless, highstability with new triangularextrusions.

Grows with requirements

Easy expansion with stackablecomponents.

Cable management

No matter how complex, Knürrcreates the right solutions.

EMC and IPmodelsThe compact rack can be equip-ped at any time to meet IP orEMC standards.(Also in combination with IP/EMCmodel)

Forward-thinking

Flexibility with the integration of19” technology.Choice of 6 heights from 9HU to24 HU.

6

5

4

3

2

1

smaractStrong points

SMA200053

SMA200044

SMA200171

SMA200062

SMA200565

SMA200466

Page 64: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.39

I N D O O R S Y S T E M S

Material- Extruded aluminium- Corner connector, die-castaluminium

- Covers, sheet steel- Doors, sheet steel or with

single security glass panel,opening angle, 180°

19” Installations in accordancewith IEC 297-3

- Height: 9 HU to 24 HU1HU (or 1U) = 44.45 mm

- Width: 482.6 mm (19”)

Models- IP 20- IP 54- EMC

Space provided

- 82% of the basic surface asuseable surface for installationand cable routing

Configuration

- Stationary, on levelling feet- Mobile on castors with lock

Finish- Basic rack, polished- Covers, powder-coated, RAL

7035 light-grey, textured

Static load- 2000 N With stationary model

How supplied

- Fully assembled

Tests in line with model

- Safety in accordance with EN50298 and EN 60950

- Protective conductor / earth inaccordance withDIN VDE 0701-1

- Vibration test in accordancewith MIL-STD 810 E

- Vibration and shock test inaccordance with DIN EN300019-2-2

- IP Test in accordance with DINEN 60529

- EMC Shielding attenuation inaccordance with IEEE-STD-299and VG 95 373 part 15 (30 MHz -1 GHz)

- Plastic components comply withUL 94-VO

smaract 19” Compact Rack, In Accordance with IEC 297

Technical data

Page 65: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.40

smaract 19” Compact RackWith glass door

W H D HU/U h d kg Model Order no. UP

478 600 9 16 Type 1 02.110.007.1 1 unit

612 600 12 20 Type 1 02.110.012.1 1 unit

745 600 15 24 Type 1 02.110.017.1 1 unit

879 600 18 28 Type 1 02.110.022.1 1 unit

1012 600 21 32 Type 1 02.110.027.1 1 unit

1145 600 24 36 Type 1 02.110.032.1 1 unit

478 800 9 19 Type 1 02.110.009.1 1 unit

612 800 12 23 Type 1 02.110.014.1 1 unit

745 800 15 27 Type 1 02.110.019.1 1 unit

879 800 18 31 Type 1 02.110.024.1 1 unit

1012 800 21 35 Type 1 02.110.029.1 1 unit

1145 800 24 39 Type 1 02.110.034.1 1 unit

478 600 9 16 Type 2 02.110.057.1 1 unit

612 600 12 20 Type 2 02.110.062.1 1 unit

745 600 15 24 Type 2 02.110.067.1 1 unit

879 600 18 28 Type 2 02.110.072.1 1 unit

1012 600 21 32 Type 2 02.110.077.1 1 unit

1145 600 24 36 Type 2 02.110.082.1 1 unit

478 800 9 19 Type 2 02.110.059.1 1 unit

612 800 12 23 Type 2 02.110.064.1 1 unit

745 800 15 27 Type 2 02.110.069.1 1 unit

879 800 18 31 Type 2 02.110.074.1 1 unit

1012 800 21 35 Type 2 02.110.079.1 1 unit

1145 800 24 39 Type 2 02.110.084.1 1 unit

SMA20024

- For installations in accordance withIEC 297-3- Removable covers

VariantsType 1- With 19”-T-slot extrusionType 2- With 19”-mounting holes extrusion

Load rating- 2000 N static

Material- Basic rack: extruded aluminium- Covers: sheet steel

Finish- Basic rack: polished- Covers: powder-coated textured

Colour- RAL 7035 light grey

Supply scheduleType 11 Basic rack2 Side panels, closed, both sides, hinged1 Top cover, closed1 Glass front door1 Rear door with cable entry, lockable,prepared for ventilation unit

2 19” Aluminium vertical extrusions, atthe front with T-slot1 Earthing set4 Levelling feetType 21 Basic rack2 Side panels, closed, both sides, hinged1 Top cover, closed1 Glass front door1 Rear door with cable entry, lockable,prepared for ventilation unit

2 19” Sheet steel vertical extrusion, at thefront with mounting holes1 Earthing set4 Levelling feet

How supplied- Assembled

SMA20026

Dimensions in mm: W = WIdth HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation height = Express Articled = Useful depth

Page 66: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.41

I N D O O R S Y S T E M S

smaract 19” Compact RackEnclosure without door

- For built-in units in accordance withIEC 297-3

- Removable covers

Load rating- 2000 N static

Material- Basic rack: extruded aluminium- Covers: sheet steel

Finish- Basic rack: polished- Covers: powder-coated textured

Colour- RAL 7035 light grey

Supply schedule1 Basic rack2 Side panels, closed, both sides, hinged1 Cover, closed1 Panel frame, at the front1 Rear door with cable entry, lockable,

prepared for ventilation unit2 19” Aluminium vertical extrusions, at

the front, with T-slot1 Earthing set4 Levelling feet

How supplied- Assembled

W H D HU/U h d kg Model Order no. UP

478 600 9 16 02.110.107.1 1 unit

745 600 15 24 02.110.117.1 1 unit

1012 600 21 28 02.110.127.1 1 unit

478 800 9 19 02.110.109.1 1 unit

745 800 15 25 02.110.119.1 1 unit

1012 800 21 31 02.110.129.1 1 unit

SMA20025

SMA20027

SMA20042

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM-Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 67: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.42

smaract 19” Sheet Steel Extrusion with mounting holes

- For installation at the front and rear

Material / Finish- 19” Extrusions: sheet steel zinc-plated- Mounting bracket: sheet steel

zinc-plated

Supply schedule2 19” Extrusions with mounting holes

4 Mounting bracket

Mounting hardware

How supplied- Flat-packed kit

SMA20104

SMA20106

W H D HU/U h d kg Model Order no. UP

9 02.111.156.9 1 unit

12 02.111.157.9 1 unit

15 02.111.158.9 1 unit

18 02.111.159.9 1 unit

21 02.111.160.9 1 unit

24 02.111.161.9 1 unit

smaract 19” Aluminium Extrusions with T-Slot

- For installation at the front and rear

Material / Finish- 19” Extrusions: extruded aluminium

polished- Mounting bracket: sheet steel

zinc-plated

Supply schedule2 19” Extrusions with T-Slot,

includes increment slide4 Mounting brackets

Mounting hardware

How supplied- Flat-packed kit

SMA20103

SMA20105

W H D HU/U h d kg Model Order no. UP

9 02.111.146.9 1 unit

12 02.111.147.9 1 unit

15 02.111.148.9 1 unit

18 02.111.149.9 1 unit

21 02.111.150.9 1 unit

24 02.111.151.9 1 unit

Page 68: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.43

I N D O O R S Y S T E M S

smaract Cover / base closed

Material / Finish- Sheet steel, powder-coated texture

Colour- RAL 7035 light grey

Supply schedule1 Base closedMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 02.111.052.1 1 unit

800 02.111.054.1 1 unitSMA20028

smaract Perforated base with filter mat

- For cooling using air convection Material / Finish- Base: sheet steel powder-coated texture- Filter mat: filedon

Colour- RAL 7035 light grey

Supply schedule1 Perforated base with filter matMounting Hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 02.111.062.9 1 unit

800 02.111.064.9 1 unit

SMA20029

smaract Replacement filter mat

- For use in connection with perforated base Material / FinishFiledon

Supply schedule5 Replacement filter mats

How supplied- Flat-packed kit

SMA20058 W H D HU/U h d kg Model Order no. UP

600 02.111.068.9 1 unit

800 02.111.069.9 1 unit

Page 69: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.44

smaract Rear door closed

Material / Finish- Sheet steel, powder-coated texture

Colour- RAL 7035 light grey

Supply schedule1 Rear door closedMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

9 02.111.076.1 1 unit

12 02.111.077.1 1 unit

15 02.111.078.1 1 unit

18 02.111.079.1 1 unit

21 02.111.080.1 1 unit

24 02.111.081.1 1 unit

SMA20031

smaract Ventilation unit

- Easy add-on on the rear panel- With two axial fans- With thermostat

Material / Finish- Sheet steel zinc-plated

Supply schedule1 Ventilation unit ready for connection

with thermostatMounting hardware

How supplied- Preassembled

W H D HU/U h d Model Order no. UP

02.111.180.9 1 unitSMA20033

smaract Twin castor

- Height 50 mm

Load rating- 500 N per castor- 1500 N max. statical total load per rack

Material- Polyamide

Colour- RAL 9011 graphite black

Supply schedule2 Twin castor2 Lockable castors

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

9 02.111.175.9 1 unitSMA20034

Page 70: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.45

I N D O O R S Y S T E M S

SMA20091

SMA20095

smaract Plinth

- Stationary

- Cable entry possible on all sides

- Trims front and rear with vent slots andinsert option for filter mats

Material / Finish- Sheet steel, powder-coated texture

Colour- RAL 7035 light grey

Supply schedule4 Plinth corners2 Trims, closed2 Trims, with vent slotsMounting material

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 100 600 02.111.201.1 1 unit

600 100 800 02.111.203.1 1 unit

SMA20098

smaract Plinth trim with cable entry

- For use in conjunction with the plinth

Material / Finish- Sheet steel, powder-coated texture

Colour- RAL 7035 light grey

Supply schedule1 Trim with cable entry1 Brush stripMounting material

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 02.111.206.9 1 unit

MIR20140

smaract Filter mat for plinth trim

- For installation in the plinth trim on thefront and rear

Material / Finish- Filedon

Supply schedule2 Filter mats

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 01.130.532.9 1 unit

Page 71: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.46

smaract Stacking Set

- Fixed connection to stack the small racks

Material / Finish- Steel cold rolled zinc-plated

Supply schedule4 Stack elementsMounting hardware

How supplied- Flat-packed kit

SMA20035

W H D HU/U h d kg Model Order no. UP

02.111.171.9 1 set

120

30

90

60

°

MIR00319

Mounting Set, Floor Fixing

- For fixing the rack to the floor, e.g. withsuitable dowels and screws set in concerte

Material- Sheet steel 3 mm

Finish- Zinc passivated

Supply schedule4 Clamping plate

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

01.130.934.7 1 set

smaract Eyebolt Set

- For hanging up crane hooks

Load rating- 1900 N per ring screw

Material- Tool steel, forged

Supply schedule4 Jack rings M8

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

M8 01.243.440.9 1 unit

MEC00074

smaract Wall-Mounting Bracket

W H D HU/U h d kg Model Order no. UP

600 02.111.220.9 1 set

Load rating- 500 N static

Material / Finish- Steel sheet, powder-coated, textured

Colour- RAL 7035 light grey

Supply schedule2 Wall-mounting bracketsDrill hole templateMounting material

How supplied- In batches

SMA20085

SMA20094

Page 72: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.47

I N D O O R S Y S T E M S

smaract 19” Enclosure, EMC, with sheet steel door

- For installation in accordance withIEC 297-3

- Removable covers

Load rating- 2000 N static

Material- Basic rack: extruded aluminium- Covers: sheet steel- EMC spring: stainless steel

Finish- Basic rack: polished- Covers: powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Basic rack2 Side panels, EMC, closed, hinged onboth sides

1 Top cover, EMC, closed1 Bottom cover, EMC, closed1 Front door, EMC, closed1 Rear door, EMC, closed, screwed2 19” Aluminium vertical extrusions,

front, with T-Slot, incl. increment slide1 Earthing set4 Levelling feet

How supplied- Assembled

W H D HU/U h d kg Model Order no. UP

600 879 600 18 36 02.110.322.1 1 unit

600 879 800 18 40 02.110.324.1 1 unit

SMA20065

SMA20059 TEC20098

EMC measurements were carried out byPlem Electronic GmbH, Frontenhausen

Tests were conied out in accordance withthe following standard: VG 95373 part 15

Tested rackW600, D 600, H 1150, closed version

Page 73: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.48

smaract Connection panel EMC, closed

- EMC shielded- Screwed

Material- Cover: sheet steel- EMC spring: stainless steel

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 131,3 3 02.111.351.1 1 set

SMA20148

smaract Connection panel EMC, with cable entry

- EMC shielded- Screwed

Material- Cover: sheet steel- EMC spring: stainless steel- EMC sealing extrusion: rubber with

stainless steel mash

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel with cable entry2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 131,3 3 02.111.361.1 1 set

SMA20145

SMA20137

SMA20137

Page 74: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.49

I N D O O R S Y S T E M S

smaract Connection panel EMC, for fan unit

- EMC shielded- Screwed

Material- Cover: sheet steel- EMC spring: stainless steel

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel for fan unit2 BracketsMounting hardware

How supplied- Flat-packed kit

NoteFitting ventilation unit: 02.111.180.9

W H D HU/U h d kg Model Order no. UP

600 264,6 6 02.111.372.1 1 set

SMA20150

smaract Rear panel EMC, closed

- EMC shielded- Screwed

Material- Cover: sheet steel- EMC spring: stainless steel

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel for fan unit2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 556,3 12 02.111.354.1 1 set

600 689,6 15 02.111.355.1 1 set

SMA20152

SMA20137

SMA20135

Page 75: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.50

smaract 19” Enclosure IP54, with glass door

- For installations in accordance withIEC 297-3

- Removable covers

Load rating- 2000 N static

Degree of protection- IP 54

Material- Basic rack: extruded aluminium- Covers: sheet steel- Foam sealing: polyurethane

Finish- Basic rack: polished- Covers: powder-coated textured

Colour- RAL 7035 light grey

Supply schedule1 Basic rack2 Side panels, IP 54, closed, hinged onboth sides

1 Top cover, IP 54, closed1 Bottom cover, IP 54, closed1 Glass front door IP 541 Rear door, IP 54, closed, screwed2 19” Aluminium vertical extrusions,

front, with T-Slot, incl. increment slide1 Earthing set4 Levelling feet

How supplied- Assembled

SMA20062W H D HU/U h d kg Model Order no. UP

600 612 600 12 28 02.110.212.1 1 unit

600 879 600 18 36 02.110.222.1 1 unit

600 1146 600 24 44 02.110.232.1 1 unit

600 612 800 12 32 02.110.214.1 1 unit

600 879 800 18 40 02.110.224.1 1 unit

600 1146 800 24 48 02.110.234.1 1 unit

SMA20108

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 76: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

1.51

I N D O O R S Y S T E M S

smaract Connection panel IP 54, closed

- IP 54 protection rating- Screwed

Material- Cover: sheet steel- Foam sealing: polyurethane

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 131,3 3 02.111.301.1 1 set

SMA20148

smaract Connection panel IP 54, with cable entry

- Possible seal up: IP 54- Screwed

Material- Cover: sheet steel- Foam sealing: polyurethane- Sealing extrusion: foam-rubber seal

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel with cable entry2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 131,3 3 02.111.311.1 1 set

SMA20139

SMA20138

SMA20138

Page 77: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D O O R S Y S T E M S

1.52

smaract Connection panel IP 54, for fan unit

- IP 54 protection rating- Screwed

Material- Covers: sheet steel- Foam sealing: polyurethane- Exit filter: ABS plastic, UL94 V-0

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel for fan unit2 BracketsMounting hardware

How supplied- Flat-packed kit

NoteFitting ventilation unit: 02.111.180.9

W H D HU/U h d kg Model Order no. UP

600 264,6 6 02.111.322.1 1 set

SMA20143

smaract Rear panel IP 54, closed

- IP 54 protection rating- Screwed

Material- Covers: sheet steel- Foam sealing: polyurethane

Finish- Powder-coated textured

Colour

- RAL 7035 light grey

Supply schedule1 Connection panel for fan unit2 BracketsMounting hardware

How supplied- Flat-packed kit

W H D HU/U h d kg Model Order no. UP

600 289,6 6 02.111.302.1 1 set

600 422,9 9 02.111.303.1 1 set

600 556,3 12 02.111.304.1 1 set

600 689,6 15 02.111.305.1 1 set

600 823 18 02.111.306.1 1 set

600 956,3 21 02.111.307.1 1 set

SMA20141

SMA20138

SMA20136

Page 78: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2OutdoorSystemsOutdoor Cabinet 2.3 to 2.9

Street Cabinet 2.11 to 2.21

Outdoor Wall Case 2.23 to 2.28

2.1

O U T D O O R S Y S T E M S

Page 79: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

Outdoor Systems

Tecoras

Outdoor CabinetStrong Points 2.4

Products 2.7

Tecoras

Street CabinetStrong Points 2.12

Products 2.15

AccessoriesVertical Extrusion 2.18

Battery Tray 2.18

Depth Strut 2.18

Compact Cabinet Lamp 2.19

Door Contact Switch 2.19

Cable Entry 2.20

Plinths 2.20

Mounting Panel 2.21

Tecoras

Outdoor Wall CaseStrong Points 2.24

Products 2.25

AccessoriesBattery Tray 2.27

19” Adapter 2.27

Wall Mounting 2.28

O U T D O O R S Y S T E M S

2.2

Page 80: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2TecorasOutdoor Cabinet 2.40 bis 2.9

2.3

O U T D O O R S Y S T E M S

Page 81: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.4

Individual configuration

- Identical basic and add-onmodules can be easily extendedin modular form to multiplecombinations

- Future security due to installa-tion space and adaption for 19”,metric and non-standard equip-ment, extensive accessory

range- Easy transport of individual mo-

dules and add-on at installationsite

- Damaged covers can be easilyand service-friendly exchanged

Sophisticated engineering

and design

- The use of software tools likePro Mechanica supports tailo-red solutions for all kinds ofenvironmental and mechanicalstress

2

1 Certified safety

- The cabinets meet require-ments in accordance with IEC721, ETS 300 019 and GR-487-CORE

- Minimum 25 dB shielding atte-nuation in accordance with IEC61 587-3

- Earthquake-proof to zone 4 inaccordance with Telcordia GR-63-CORE

- Vibration test in accordancewith IEC 68-2-6, IEC 68-2-29

- Environmentally tested inaccordance withIEC 68-2-1, IEC 68-2-2,IEC 68-2-5, IEC 68-2-56,IEC 60 529

Integrated thermalmanagement

- The integration of the heatexchanger in the enclosure wallensures an increase of the avai-lable usage space by more than15%

- Use of extensive cooling for thefirst time with low cabinet

depths (‹ 400 mm) for use inpublic access areas

- Disruptions of air flow are pre-vented with large spatial sepa-ration of air entry and exitpoints

4

3

TEC000881

Tecoras OutdoorStrong Points

TEC200752

TEC200802 TEC20079 IP-Kammer3

TEC001244

Page 82: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.5

O U T D O O R S Y S T E M S

Tecoras Outdoor Cabinet

Solar protection roof for basiccabinet with add-on enclosure

Rear cover

Rear panel

Basic rack

Solar protection roof

Cover

Corner extrusions

Side covers

Side panel

Door, closed

Add-on enclosurePlinth cover Plinth

Bottom cover

Plinth trim Door for

air-conditionir

Grey shaded parts with double wall version

only

TEC00332

TEC00319

Page 83: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.6

EMC SealingIn standard

IP Protection rating

- IP 55

External covers finish

Powder-coated, RAL 7035 light-grey, outdoor quality in accordan-ce with GSB International, coarsetexture

Load rating

Static up to 4000 N

Options

- Tecoras thermal componentsfor door installation (seethermal management)- Heat exchanger- Cooling unit- Heating (see thermal manage-ment)- Vertical installation extrusions,19” or metric (see accessories)- Cable entry panel (see accesso-

ries)- Cable entry troughs with and

without filter box (see accesso-ries)- Tecoras power supplies andpower distribution (see powersupply systems)

Single or double skinned outdoorenclosure for installation of- 19“ and metric components- Non-standard equipment

Main unit

- Basic frame of extruded alumi-nium AIMgSi0,5 with die-castaluminium corner connectors,polished- Bottom and top cover, rearpanel, corner extrusions andside panels of chrome-platedaluminium AIMg3,1,5 und 2 mm, polished

External covers

- Of 2 mm colourless chrome-plated aluminium AIMg3- 2 Side covers- Rear cover screwed from theinside- Solar protection roof, hinged- All screwing and connectingelements on the inside

Door

Double skinned closed or ventedfor installation of Tecoras ther-mal components- Can be used as front and reardoor, door hinges on right orleft - Strong hidden die-cast alumini-

um hinges- Swing handle for profile half

cylinder with saw protection- Triple interlocking system- The intervening ‘tongue’ in the

rack extrusion ensures highlocking pressure with lowassembly input Door locking with openingangles 90º and 135º

Tecoras OutdoorTechnical data

Page 84: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

TEC00443

2.7

O U T D O O R S Y S T E M S

- Double skinned, outdoor enclosure withadd-on capability for installation of- 19” and metric components- Non-standard units with maximuminstallation width, 535 mm- Different cabinet combinations can be

constructed from the same basicmodules.- Double cabinets or triple cabinets are

created by adding-on one or two add-oncabinets ( = basic cabinet without sidecovers and side panels). The extensionis made instead of the side cover.- These combinations can also be moun-

ted on the right or left with an add-onenclosure.

Supply schedule1 Main unit consisting of basic frame, top

and bottom cover, rear panel, 2 corner extrusions1 Rear panel2 Side panels2 Side covers1 Solar protection roof, 110 mm height1 Front door, hinged on right, closed or

vented1 Plinth, 210 mm height, galvanised sheet

steel with 2 side covers, 1 removablefront and rear trim1 Earthing set1 Cable entry panel, closed

Thermal management basic equipping- Naturally ventilated double panels- Naturally ventilated roof

How suppliedFully assembled

TEC00098

W H D HU/U h d kg Model Order no. UP

700 1000 405 895 20 330 63 closed 01.901.003.1 1 unit

700 1180 405 1075 24 330 69 closed 01.901.005.1 1 unit

700 1400 405 1295 29 330 76 closed 01.901.007.1 1 unit

700 1580 405 1475 33 330 81 closed 01.901.009.1 1 unit

700 1000 705 895 20 630 81 closed 01.901.013.1 1 unit

700 1180 705 1075 24 630 88 closed 01.901.015.1 1 unit

700 1400 705 1295 29 630 97 closed 01.901.017.1 1 unit

700 1580 705 1475 33 630 104 closed 01.901.019.1 1 unit

700 1000 405 895 20 330 63 vented 01.901.103.1 1 unit

700 1180 405 1075 24 330 69 vented 01.901.105.1 1 unit

700 1400 405 1295 29 330 76 vented 01.901.107.1 1 unit

700 1580 405 1475 33 330 81 vented 01.901.109.1 1 unit

700 1000 705 895 20 630 81 vented 01.901.113.1 1 unit

700 1180 705 1075 24 630 88 vented 01.901.115.1 1 unit

700 1400 705 1295 29 630 97 vented 01.901.117.1 1 unit

700 1580 705 1475 33 630 104 vented 01.901.119.1 1 unit

Tecoras Basic Cabinet W 700Front door right, closed / vented

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 85: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.8

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Supply schedule1 Main unit consisting of basic frame, top

and bottom cover, rear panel, 2 cornerextrusions1 Rear panel1 Solar protection roof, 110 mm height1 Front door, hinged on right, closed1 Plinth, 210 mm height, galvanised sheet

steel, 1 removable front and rear trim1 Earthing set1 Cable entry panel, closed1 Add-on set

Thermal management basic equipping- Naturally ventilated rear panel- Naturally ventilated roof

How suppliedFully assembled

Tecoras Add-On Cabinet W 635Front door right, closed / vented

W H D HU/U h d kg Model Order no. UP

635 1000 405 895 20 330 49 closed 01.901.303.1 1 unit

635 1180 405 1075 24 330 52 closed 01.901.305.1 1 unit

635 1400 405 1295 29 330 57 closed 01.901.307.1 1 unit

635 1580 405 1475 33 330 61 closed 01.901.309.1 1 unit

635 1000 705 895 20 630 59 closed 01.901.313.1 1 unit

635 1180 705 1075 24 630 62 closed 01.901.315.1 1 unit

635 1400 705 1295 29 630 67 closed 01.901.317.1 1 unit

635 1580 705 1475 33 630 71 closed 01.901.319.1 1 unit

635 1000 705 895 20 630 59 vented 01.901.413.1 1 unit

635 1180 705 1075 24 630 62 vented 01.901.415.1 1 unit

635 1400 705 1295 29 630 67 vented 01.901.417.1 1 unit

635 1580 705 1475 33 630 71 vented 01.901.419.1 1 unit

TEC00098

- Double skinned compact outdoor enclosurewith double door and central bracket forinstallation of- 2 x 19” and metric components for

cabinet width 1270 mm- Non-standard units with maximuminstallation width, 890 and 1100 mm

- Expansion of the cabinet combinations withadd-on cabinets and add-on enclosures isalso an option

Thermal management basic equipping- Ventilated double panels- Ventilated roof

Double door- Closed or ventilated for using thermal

components - Double door with central bracket- Right and left door can be locked sepa-

rately

Supply schedule1 Main unit consisting of basic frame, top

and bottom cover, 2 side panels, rearpanel, 2 corner extrusions

2 Side covers1 Rear panel cover1 Solar protection roof, 110 mm height1 Double door, hinged on right and left,

closed1 Plinth, 210 mm height, galvanised sheet

steel, with 2 side covers, 1 removablefront and rear trim1 Earthing set2 Cable entry panels, closed

TEC00146

Tecoras Double Door Cabinet W 1270doors closed

W H D HU/U h d kg Model Order no. UP

1270 1000 405 895 20 330 108 01.901.531.1 1 unit

1270 1180 405 1075 24 330 117 01.901.532.1 1 unit

1270 1400 405 1295 29 330 129 01.901.533.1 1 unit

1270 1580 405 1475 33 330 138 01.901.534.1 1 unit

1270 1000 705 895 20 630 136 01.901.536.1 1 unit

1270 1180 705 1075 24 630 147 01.901.537.1 1 unit

1270 1400 705 1295 29 630 161 01.901.538.1 1 unit

1270 1580 705 1475 33 630 172 01.901.539.1 1 unit

Page 86: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.9

O U T D O O R S Y S T E M S

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Double skinned outdoor enclosure withintegrated air-to-air heat exchanger withenclosure protection rating IP 55 forinstallation of:- 19” and metric components- Non-standard units with maximuminstallation width 535 mm (standardcabinet) and 2 x 535 mm(double cabinet)

Integrated heat exchanger principle- Integration of the heat exchanger in theexternal panels- Fans and electronic control board instal-led in the roof for maximum useablespace- Optimised positioning of air entry andexit ensures lowest wind disruption ofthe airflow - Sound pressure level, less than 55 dB(A)

at 1 m distance, in accordance withISO 7779

Thermal management basic equipping- Active ventilated and ribbed side and

rear panels- One fan module with 2 fans with integra-

ted electronic control board 48 VDC forexternal and internal circulation forstandard cabinet with 700 mm width- Two fan modules each with 2 fans withintegrated electronic control board 48VDC for external and internal circulationfor standard cabinet with 1335 mmwidth- Active solar protection with roof fan

Standard cabinet W 700 supply schedule1 Basic frame with bottom cover and 2

corner extrusions 2 Double skinned ribbed side panels withinternal channel plates1 Double skinned ribbed rear panel withinternal channel plate1 Fan module with 2 fans 48 VDC,

thermostat regulated1 Solar protection roof, 195 mm height1 Double skinned front door, hinged on

right, closed1 Plinth, 210 mm height, galvanised sheet

steel, with 2 side covers, 1 removablefront and rear trim1 Earthing set1 Cable entry panel

Double cabinet W 1335 supply scheduleThe double cabinet consists of basic andadd-on cabinets:2 Basic frames with bottom cover and 4

corner extrusions, assembled togetherwith add-on connectors

2 Double skinned ribbed side panels withinternal channel plates

2 Double skinned ribbed rear panels withinternal channel plates

2 Fan modules with 2 fans 48 VDC, ther-mostat regulated

2 Solar protection roofs, 195 mm height2 Double skinned front doors, hinged on

right and left, closed2 Plinths, 210 mm height, galvanised

sheet steel, with 2 side covers,2 removable trims, front and rear

2 Earthing sets2 Cable entry panels, closed

How suppliedFully assembled

Tecoras Heat Exchanger Cabinet

TEC00149

W H D HU/U h d kg Model (*) Order no. UP

700 1000 405 850 19 330 83 28 W/K 01.900.003.1 1 unit

700 1180 405 1030 22 330 89 40 W/K 01.900.005.1 1 unit

700 1400 405 1250 28 330 96 43 W/K 01.900.007.1 1 unit

700 1580 405 1430 32 330 101 48 W/K 01.900.009.1 1 unit

700 1000 705 850 19 630 101 48 W/K 01.900.023.1 1 unit

700 1180 705 1030 22 630 108 55 W/K 01.900.025.1 1 unit

700 1400 705 1250 28 630 117 58 W/K 01.900.027.1 1 unit

700 1580 705 1430 32 630 124 63 W/K 01.900.029.1 1 unit

1335 1000 405 850 19 300 143 55 W/K 01.900.401.1 1 unit

1335 1180 405 1030 22 300 152 68 W/K 01.900.402.1 1 unit

1335 1400 405 1250 28 300 164 70 W/K 01.900.403.1 1 unit

1335 1580 405 1430 32 300 174 78 W/K 01.900.404.1 1 unit

1335 1000 705 850 19 600 171 73 W/K 01.900.411.1 1 unit

1335 1180 705 1030 22 600 182 85 W/K 01.900.412.1 1 unit

1335 1400 705 1250 28 600 196 88 W/K 01.900.413.1 1 unit

1335 1580 705 1430 32 600 207 98 W/K 01.900.414.1 1 unit

* The max. specific cooling capacity refersto the difference between the intake tem-perature of the ambient air and the returntemperature of the interal air

Page 87: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

Rapid service

Express Articles

Fast express delivery service,seamless ordering system,

attractive prices and a market–

oriented offer - that’s Knürr

efficiency!

Every express article that is

correspondingly identifed in

this catelogue leaves our

European central stores 24

hours after your order is

received: qualitative high-

grade, standardised solutions,

with which you are always

decisively ahead of the compe-tition.

Our sales offices are also avai-lable for you worldwide, where

competent technicians andsales engineers will personal-ly take care of your specialrequirements.

Why not use these advantagesto your own benefit.

Express articles

in 24 hours ex plant:

With Knürr you are always

ahead of the competition

Page 88: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2TecorasStreet Cabinet 2.120 bis 2.21

2.11

O U T D O O R S Y S T E M S

Page 89: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.12

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Innovative solution

Street Cabinet side and rear panelsare fabricated from one piece. Thisenables a design with a minimumamount of joints.

Thermal protection

The filter fan installed in the topcover (type Street Cabinet FAN)ensures that hot spots are pre-vented and consequently providesthermal protection for installedequipment.

1

Integrated thermal management

The air-to-air heat exchangerintegrated in the rear panel(Street Cabinet HEC) enablesoptimal cooling in the smallestinstallation area on with protec-tion rating IP 55.

Easy configuration

Together with the enclosure, theearth plinth available as anaccessory made of fibre-glassreinforced polyester provides acompletely configurable ready toconnect system. The compatibil-ity of the connection dimensionswith plinths in accordance withDIN 43629 allows unlimitedexchange of enclosures ofexisting installations.

Functional accessories

The mounting panel with 19”adapter provides flexible upgradewith 19” components and DINrails or non-standard units usedin an application.

Space economy

Space-saving operational ele-ments, displays, telecommunica-tions distributors and power sup-ply components can be mountedin the enclosure with side door.Various front and side doorlocking devices allow separaterights of access.

5

4

3

2

TEC002471

TEC002582

TEC002573

TEC002664

TEC002645

Tecoras Street CabinetStrong points

Page 90: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.13

O U T D O O R S Y S T E M S

Tecoras Street cabinet

Cladding (L-shaped / U-shaped) Solar protection roof

TEC00312

Cover

Basic rack

Corner extrusion

Door, closed

Bottom cover

Side door

Partition panel

The Tecoras Street cabinets SC, FANand HEC are available in the follo-wing versions:- a basic version with a front door- a basic version with a front door

and an additional side door- a version with a double door on thefront

W H D HU/U w h d kg Model Order no. UP

640 780 375 15 535 675 Street Cabinet SC

740 780 475 15 635 675 Street Cabinet SC

1210 780 15 1105 675 Street Cabinet SC

640 1000 375 20 535 895 Street Cabinet FAN

740 1000 475 20 635 895 Street Cabinet FAN

1210 1000 20 1105 895 Street Cabinet FAN

640 1180 375 24 535 1075 Street Cabinet FAN

740 1180 475 24 635 1075 Street Cabinet FAN

1210 1180 24 1105 1075 Street Cabinet FAN

640 780 400 14 535 630 Street Cabinet HEC

740 780 500 14 635 630 Street Cabinet HEC

1210 780 14 1105 630 Street Cabinet HEC

640 1000 400 19 535 850 Street Cabinet HEC

740 1000 500 19 635 850 Street Cabinet HEC

1210 1000 19 1105 850 Street Cabinet HEC

640 1180 400 23 535 1030 Street Cabinet HEC

740 1180 500 23 635 1030 Street Cabinet HEC

1210 1180 23 1105 1030 Street Cabinet HEC

Page 91: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.14

IP Protection rating

- IP 55 For model with closeddoor

- IP 54 For model with ventilateddoor

External covers finish

- Powder-coated, RAL 7035light-grey, outdoor quality inaccordance with GSBInternational, coarse texture

Options

- 1 Plinth, 210 mm height,galvanised sheet steel, withremovable front trim(see accessories)

- 1 Fibre-glass reinforced poly-ester plinth (see accessories)

- Heating (see thermal manage-ment)

- Vertical installation extrusions,19” or metric (see accessories)

- Mounting panel(see accessories)

- Cable entry panel, closed(see accessories)

- Cabinet made of galvanisedsheet steel

Single skinned outdoor enclosure foruse in public access areas with amaximum depth of 500 mm andmaximum height of 1290 mm forinstallation of- 19” and metric components- Non-standard equipment for DIN

rails and fixing mounting panels

Main unit

- Basic frame of extruded alumi-nium AIMgSi0,5 with die-castaluminium corner connectors,polished

- Top and bottom cover of chro-me-plated aluminium AIMg3,2 mm, polished

External covers

- Of 2 mm colourles chrome-plated aluminium AIMg3

- One-piece jacket functioning asside piece and rear panel

- Solar protection roof, screwed- All screwing and connection

elements on the inside

Door

- Standard door or double doorwithout central bracket insingle skinned version, closedor ventilated

- Double skinned door for enclo-sure with increased EMC pro-tection

- Swing handle for profile halfcylinder with saw protection

- Triple interlocking system:The intervening ‘tongue’ in therack extrusion ensures highlocking strength with lowassembly input

- Hidden hinges- Door locking with openingangles 90º and 135º

- The optional side door on theright or left is set up in thesame way as the front door

Tecoras Street CabinetTechnical data

TEC00352

Page 92: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.15

O U T D O O R S Y S T E M S

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

TEC00359

Cost-effective single skinned outdoor enclo-sure for installation of- 19” and metric components- Non-standard units with maximum installa-

tion widths, 535 mm and 1105 mm for DINrails and for fixing mounting panel

Supply schedule, SC1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof1 Front door, sealing on right1 Earthing set

Supply schedule, SC with side door

1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof, 110 mm height1 Front door, hinged on right1 Earthing set1 Corner extrusion of basic frame1 Side door, left or right1 Partition panel

Supply schedule, SC with double door

1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof, 110 mm height1 Front door as double door1 Earthing set

How suppliedFully assembled

Tecoras Street Cabinet SCAluminium

W H D HU/U w h d kg Model Order no. UP

640 780 375 15 535 675 335 Street Cabinet 01.917.000.1 1 unit

640 780 475 15 535 675 435 Street Cabinet 01.917.005.1 1 unit

740 780 375 15 635 675 335 Street Cabinet 01.917.010.1 1 unit

740 780 475 15 635 675 435 Street Cabinet 01.917.015.1 1 unit

640 1000 375 20 535 895 335 Street Cabinet 01.917.001.1 1 unit

640 1000 475 20 535 895 435 Street Cabinet 01.917.006.1 1 unit

740 1000 375 20 635 895 335 Street Cabinet 01.917.011.1 1 unit

740 1000 475 20 635 895 435 Street Cabinet 01.917.016.1 1 unit

640 1180 375 24 535 1075 335 Street Cabinet 01.917.002.1 1 unit

640 1180 475 24 535 1075 435 Street Cabinet 01.917.007.1 1 unit

740 1180 375 24 635 1075 335 Street Cabinet 01.917.012.1 1 unit

740 1180 475 24 635 1075 435 Street Cabinet 01.917.017.1 1 unit

740 780 375 15 635 675 335 with side door 01.917.020.1 1 unit

740 780 475 15 635 675 435 with side door 01.917.030.1 1 unit

740 1000 375 20 635 895 335 with side door 01.917.022.1 1 unit

740 1000 475 20 635 895 435 with side door 01.917.032.1 1 unit

740 1180 375 24 635 1075 335 with side door 01.917.024.1 1 unit

740 1180 475 24 635 1075 435 with side door 01.917.034.1 1 unit

1210 780 375 15 1105 675 335 with double door 01.917.040.1 1 unit

1210 780 475 15 1105 675 435 with double door 01.917.045.1 1 unit

1210 1000 375 20 1105 895 335 with double door 01.917.041.1 1 unit

1210 1000 475 20 1105 895 435 with double door 01.917.046.1 1 unit

1210 1180 375 24 1105 1075 335 with double door 01.917.042.1 1 unit

1210 1180 475 24 1105 1075 435 with double door 01.917.047.1 1 unit

Page 93: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.16

Dimensions in mm: W = Width, H = Height, D = Depth, d = Useful depth in the entry filter area minus 13 mm, ESD = ESD versi-

on,1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Cost-effective single skinned outdoor

enclosure for installation of- 19” and metric components- Non-standard equipment with maximuminstallation width 535 mm for DIN railsand for fixing mounting panels

Front door

- Ventilated, with entry filter for air intake- Standard or double door without central

bracket- With double door, right and left door

cannot be locked separately

Supply schedule, SC Fan with side door

1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof, 110 mm height1 Front door, hinged on right1 Axial fan 230 VAC, mounted on the top

cover1 Earthing set1 Corner extrusion of basic frame1 Side door, left or right1 Partition panel

Supply schedule , SC Fan with doubledoor

1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof, 110 mm height2 Axial fans 230 VAC, mounted on the top

cover1 Front door as double door1 Earthing set

Supply schedule, SC Fan with doubledoor

1 Basic frame with top and bottom cover1 Jacket, U-shaped as side panels and

rear panel1 Solar protection roof, 110 mm height1 Axial fan 230 VAC, mounted on the top

cover1 Front door, sealing on right1 Earthing set

How suppliedFully assembled

Tecoras Street Cabinet Fan

W H D HU/U w h d* Specitif cooling capacity Order no. UP

640 780 375 15 535 675 330 01.917.050.1 1 unit

640 1000 375 20 535 895 330 01.917.051.1 1 unit

640 1180 375 24 535 1075 330 01.917.052.1 1 unit

640 780 475 15 535 675 430 01.917.055.1 1 unit

640 1000 475 20 535 895 430 01.917.056.1 1 unit

640 1180 475 24 535 1075 430 01.917.057.1 1 unit

740 780 375 15 635 657 330 01.917.060.1 1 unit

740 1000 375 20 635 895 330 01.917.061.1 1 unit

740 1180 375 24 635 1075 330 01.917.062.1 1 unit

740 780 475 15 635 675 430 01.917.065.1 1 unit

740 1000 475 20 635 895 430 01.917.066.1 1 unit

740 1180 475 24 635 1075 430 01.917.067.1 1 unit

740 780 375 15 635 657 330 with side door 01.917.070.1 1 unit

740 1000 375 20 635 895 330 with side door 01.917.072.1 1 unit

740 1180 375 24 635 1075 330 with side door 01.917.074.1 1 unit

740 780 475 15 635 657 430 with side door 01.917.080.1 1 unit

740 780 475 20 635 675 430 with side door 01.917.082.1 1 unit

740 1000 475 24 635 895 430 with side door 01.917.084.1 1 unit

1210 780 375 15 1105 675 330 with double door 01.917.090.1 1 unit

1210 1000 375 20 1105 895 330 with double door 01.917.091.1 1 unit

1210 1180 375 24 1105 1075 330 with double door 01.917.092.1 1 unit

1210 780 475 15 1105 675 430 with double door 01.917.095.1 1 unit

1210 1000 475 20 1105 895 430 with double door 01.917.096.1 1 unit

1210 1180 475 24 1105 1075 430 with double door 01.917.097.1 1 unit

* Useable depth is reduced by 13 mm in thearea of the filter

TEC00363

Page 94: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.17

O U T D O O R S Y S T E M S

TEC00364

Cost-effective single skinned outdoor

enclosure with air-to-air heat exchanger

integrated in the rear panel for installa-tion of- 19” and metric components- Non-standard equipment with maximuminstallation widths, 535 mm and 1105mm for DIN rails and for fixing moun-ting panels

Integrated heat exchanger principle- Integration of the heat exchanger

system in the external panels- Fans and electronic control board instal-led in the roof for maximum useablespace- Optimised postioning of air entry andexit ensures lowest wind disruption ofthe airflow - Sound pressure level, less than 55 dB(A)

at 1 m distance, in accordance withISO 7779

Front door

- Closed- Standard or double door without central

bracket- With double door, right and left door

cannot be locked separately

Supply schedule, SC HEC with side door

1 Basic frame with top and bottom cover1 Side panel1 Double skinned ribbed rear panel withinternal channel plate1 Solar protection roof, 110 mm height1 Front door, hinged on right1 Fan module with 2 fans 48 VDC, moun-

ted on the top cover, thermostat regula-ted

1 Earthing set1 Corner extrusion of basic frame1 Side door, left or right1 Partition panel

Supply schedule, SC HEC1 Basic frame with top and bottom cover2 Side panels1 Double skinned ribbed rear panel withinternal channel plate1 Solar protection roof, 110 mm height1 Front door, hinged on right1 Fan module with 2 fans 48 VDC, moun-

ted on the top cover, thermostat regula-ted1 Earthing set

Supply schedule, SC HEC with doubledoor

1 Basic frame with top and bottom cover2 Side panels1 Double skinned ribbed rear panel withinternal channel plate1 Solar protection roof, 110 mm height1 Front door as double door1 Fan module with 2 fans 48 VDC, moun-

ted on the top cover, thermostat regula-ted1 Earthing set

How suppliedEach fully assembled

* The max. specific cooling capacity refersto the difference between the intaketemperature of the ambiant air and thereturn temperature of the internal air

Tecoras Street Cabinet HEC

W H D HU/U w h d Specific cooling capacity (*) Order no. UP

640 780 375 14 535 630 310 13 W/K 01.917.200.1 1 unit

640 1000 375 19 535 850 310 15 W/K 01.917.201.1 1 unit

640 1180 375 23 535 1030 310 18 W/K 01.917.202.1 1 unit

640 780 475 14 535 630 410 13 W/K 01.917.205.1 1 unit

640 1000 475 19 535 850 410 15 W/K 01.917.206.1 1 unit

640 1180 475 23 535 1030 410 18 W/K 01.917.207.1 1 unit

740 780 375 14 635 630 310 13 W/K 01.917.210.1 1 unit

740 1000 375 19 635 850 310 15 W/K 01.917.211.1 1 unit

740 1180 375 23 635 1030 310 18 W/K 01.917.212.1 1 unit

740 780 475 14 635 630 410 13 W/K 01.917.215.1 1 unit

740 1000 475 19 635 850 410 15 W/K 01.917.216.1 1 unit

740 1180 475 23 635 1030 410 18 W/K 01.917.217.1 1 unit

740 780 375 14 635 630 310 13 W/K with side door 01.917.220.1 1 unit

740 1000 375 19 635 850 310 15 W/K with side door 01.917.222.1 1 unit

740 1180 375 23 635 1030 310 18 W/K with side door 01.917.224.1 1 unit

740 780 475 14 635 630 410 13 W/K with side door 01.917.230.1 1 unit

740 1000 475 19 635 850 410 15 W/K with side door 01.917.232.1 1 unit

740 1180 475 23 635 1030 410 18 W/K with side door 01.917.234.1 1 unit

1210 780 375 14 1105 630 310 25 W/K with double door 01.917.240.1 1 unit

1210 1000 375 19 1105 850 310 30 W/K with double door 01.917.241.1 1 unit

1210 1180 375 23 1105 1030 310 33 W/Kwith double door 01.917.242.1 1 unit

1210 780 475 14 1105 630 410 25 W/K with double door 01.917.245.1 1 unit

1210 1000 475 19 1105 850 410 30 W/K with double door 01.917.246.1 1 unit

1210 1180 475 23 1105 1030 410 33 W/K with double door 01.917.247.1 1 unit

* The max. specific cooling capacity refersto the difference between the intaketemperature of the ambient air and thereturn temperature of the interal air

TEC20050

Page 95: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.18

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

TEC00327

TEC00333

- With mounting holes for caged nuts- For 19” (EN60 297) or metric installations(EN 60 917)

MaterialExtruded aluminium, polished

Supply schedule2 Vertical extrusions with mountingmaterial

Vertical Extrusion with Mounting Holes

W H D HU/U w h d kg Model Order no. UP

15 19” installation 01.908.001.0 1 unit

20 19” installation 01.908.002.0 1 unit

24 19” installation 01.908.003.0 1 unit

29 19” installation 01.908.005.0 1 unit

33 19” installation 01.908.006.0 1 unit

27 M metric installation 01.908.201.0 1 unit

36 M metric installation 01.908.202.0 1 unit

43 M metric installation 01.908.203.0 1 unit

52 M metric installation 01.908.205.0 1 unit

59 M metric installation 01.908.206.0 1 unit

TEC00330

- For safe securing and fixing of batteries inTecoras Outdoor Cabinets and StreetCabinets- Load rating 130 kg

MaterialZinc passivated sheet steel, 2 mm

FinishPowder-coatedRAL 7035 light-grey, coarse texture

Supply schedule1 Battery tray1 Anti-slip mat of Neopren4 Fixing straps, 4 tightening straps withpolyamid Velcro fastener

Mounting material

Battery Tray

W H D HU/U w h d kg Model Order no. UP

640 400 220 bottom mounted 01.908.300.1 1 unit

640 700 400 bottom mounted 01.908.301.1 1 unit

640 700 400 extrusion mounted 01.908.302.1 1 unit

- For the secure mounting of shortenedvertical extrusions and for cable manage-ment in Tecoras Outdoor Cabinets andStreet Cabinets

MaterialStainless steel, 1.5 mm, polished

Supply schedule1 Deep strut with mounting material

Depth Strut

W H D HU/U w h d kg Model Order no. UP

400 01.908.100.0 1 unit

700 01.908.101.0 1 unit

Page 96: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.19

O U T D O O R S Y S T E M S

FeaturesWith mounting bracketEnergy-effective lampOn / Off switchWith coverSafety socket optionally

ApprovalVDE

Protection rating IP20

Operating temperature- 30 to +60º C

Technical data- Operating voltage48 VDC or 230 V/50 Hz- Light material

Compact fluorescent lamp withintegrated starter- Power consumption11 W =̂ 75 W filament lamp- Light intensity900 Lm- Interference suppressionin accordance with VDE 0712, IEC 82- Connections

2-or 3-pole screw terminal, 2.5 mm2

with strain relief

Compact Cabinet Lamp

W H D HU/U w h d kg Model Order no. UP

400 70 65 DC 01.908.711.9 1 unit

400 70 65 AC 01.908.712.9 1 unit

ELM00135

- Switching voltage 200 V DC, 0.5 AContact rating 10 W- Activation with door opening and closing- The magnet is fitted into the cam of thelatching system

Supply schedule1 Door contact switch with 1.5 m long

cable1 Mounting bracketMounting material1 Magnet

Door Contact SwitchMagnetically

W H D HU/U w h d kg Model Order no. UP

01.908.701.0 1 unitELM00137

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 97: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.20

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

- For space-saving and safe cable penetrationin Tecoras Outdoor Cabinets und StreetCabinets- Mounting in the bottom cover of the

cabinets- Mounting of the cable entry trough andfilter box underneath the vertical extru-sions, resulting in optimal space utiliza-tion

- Cable entry panels, cable entry troughs canbe interchanged with one another- Filter box is suitable for installation of ACdistributors, overvoltage protectors,bushing-type filters and mains filters

Material- Aluminium 2 mm, colourless

chrome-plated, polished

Supply schedule1 Closed cable entry panelor1 Cable entry trough (option: 1 cable entry

trough with filter box, EMC shielded, notequipped)

Each with mounting material

Cable Entry Panels and Troughs / Filter Box Shielded

W H D HU/U w h d Model Order no. UP

390 145 cable entry panel closed 01.908.605.8 1 unit

490 145 cable entry panel closed 01.908.601.8 1 unit

490 145 cable entry trough 01.908.660.8 1 unit

490 145 cable entry trough with filter 01.908.661.8 1 unit

TEC00444

- For vandalism-proof and stable installationof Tecoras outdoor Street Cabinets

MaterialStainless steel, 2 mm

FinishPowder-coatedRAL 7035 light-grey, outdoor quality inaccordance with GSB International,coarse textured

Design- Welded frame with removable front trim- The front trim can only be removed

when the door of the cabinet is open- The bolting of the plinth to the cabinet isnot externally accessible

Supply schedule1 Plinth1 Front trimMounting material for mounting thecabinet on to the plinth

Metal Plinth

W H D HU/U w h d Model Order no. UP

640 210 375 0 01.914.305.1 1 unit

740 210 375 1 01.914.303.1 1 unit

1210 210 375 2 01.914.307.1 1 unit

640 210 475 0 01.914.306.1 1 unit

740 210 475 1 01.914.304.1 1 unit

1210 210 475 2 01.914.308.1 1 unit

TEC00245

TEC00273

Page 98: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.21

O U T D O O R S Y S T E M S

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Design- Self-bearing design- The front trim can only be removed

when the cabinet door has first beenopened- The bolting of the plinth to the cabinet isnot externally accessible

Supply schedule1 Plinth, flat-packed in2 Side panels1 Rear panel1 Partitioned front panel, stabilization

rails1 Adaption set

How suppliedFlat-packed kit

MaterialFibre-glass reinforced polyester for weather-resistant soil installations ofTecoras Street Cabinets- Easily mounted- Comfortable transport weight (max. 20 kg)- Compatible with DIN 43629 part 2,

standard plinth for cable distributor andinstrument cabinet

Colour

Grey, similar to RAL 9002

Fibre-Glass Reinforced Polyester Plinth

W H D HU/U w h d Model Order no. UP

591 900 375 495 0 01.914.394.1 1 unit

786 900 375 690 1 01.914.395.1 1 unit

1116 900 375 1020 2 01.914.396.1 1 unit

591 900 475 495 0 01.914.397.1 1 unit

786 900 475 690 1 01.914.398.1 1 unit

1116 900 475 1020 2 01.914.399.1 1 unit

TEC00243

TEC00272

MaterialGalvanised sheet steeel, 2 mm, polished

Supply schedule1 Mounting panel with mounting material

Option:19” adapter 3 HU for fixing to themounting panel

- For mounting installations for DIN rail fixingand non-standard equipment in TecorasOutdoor Cabinets and Street Cabinets withadaption options for 19” modular chassis’

Mounting Panel

W H D HU/U w h d Model Order no. UP

535 15 01.908.751.7 1 unit

535 20 01.908.752.7 1 unit

535 24 01.908.753.7 1 unit

535 29 01.908.754.7 1 unit

535 33 01.908.755.7 1 unit

TEC00249

Page 99: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

Rapid service

Express Articles

Fast express delivery service,seamless ordering system,

attractive prices and a market–

oriented offer - that’s Knürr

efficiency!

Every express article that is

correspondingly identifed in

this catelogue leaves our

European central stores 24

hours after your order is

received: qualitative high-

grade, standardised solutions,

with which you are always

decisively ahead of the compe-tition.

Our sales offices are also avai-lable for you worldwide, where

competent technicians andsales engineers will personal-ly take care of your specialrequirements.

Why not use these advantagesto your own benefit.

Express articles

in 24 hours ex plant:

With Knürr you are always

ahead of the competition

Page 100: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2TecorasOutdoor Wall Case 2.240 bis 2.28

2.23

O U T D O O R S Y S T E M S

Page 101: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.24

Single skinned climatised and uncli-matised outdoor enclosures formounting on walls and poles andbase assembly, for installation of- 19” and metric components- Non-standard equipment for DIN

rails and fixing mounting panels

Integrated thermal management

The air-to-air heat exchanger inte-grated in the side panels (with wallcase HEC) enables optimalcooling with the smallest installationspace with protection rating IP 55.

Outdoor Wall CaseStrong points

TEC00329

IP Protection rating- IP 55 for model with closeddoor (Wall Case, Wall CaseHEC)

EMC ProtectionOptional

External covers finishPowder-coatedRAL 7035 light-grey Outdoor quality in accordancewith GSB International, coarsetexture

Load ratingStatic up to 500 N

Main unitWelded enclosure body of 3 mmchrome-plated aluminium AIMg3

External covers (only for wallenclosures with integrated heatexchanger)

- Of colourless chrome-platedaluminium AIMg3, 2 mm- Solar protection roof, screwed/

bolted- All bolting and connectionelements on the inside

Door

- Door closed or ventilated- Of colourless chrome-plated

aluminium AIMg3, 2 mm- Double skinned door model forenclosures with high EMC pro-tection rating- Door hinged right or left- Swing handle for profile half

cylinder- Double interlocking system- Hidden hinges- Door hinge to maximumopening angle of 150º

Outdoor Wall CaseTechnical data

Page 102: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.25

O U T D O O R S Y S T E M S

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Cost-effective outdoor wall enclosure for

installation of- Non-standard equipment with installati-on widths of 305 to 485 mm for DIN railsand fixing mounting panels- 19” Components (only for enclosure

width 585 mm)

Supply schedule1 Wall case with mounting straps formounting on the wall1 Front door, closed,hinged on left side1 Closed cable entry panel in the bottom1 Mounting panel of 2 mm zinc passivated

sheet steel, polished, mounted on therear side1 Earthing set

How suppliedFully assembled

OptionWith axial fan 230 V AC, controlled bythermostat

Outdoor Wall Case

W H D HU/U w h d Model Order no. UP

405 400 250 7 305 340 210 01.915.002.1 1 unit

485 400 250 7 385 340 210 01.915.004.1 1 unit

405 600 250 12 305 540 210 01.915.006.1 1 unit

485 600 250 12 385 540 210 01.915.008.1 1 unit

485 600 345 12 385 540 305 01.915.010.1 1 unit

585 600 345 12 485 540 305 01.915.012.1 1 unit

485 800 250 16 385 740 210 01.915.014.1 1 unit

485 800 345 16 385 740 305 01.915.016.1 1 unit

585 800 345 16 485 740 305 01.915.018.1 1 unit

TEC00121

TEC00329

Page 103: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.26

Double skinned outdoor wall case with air-to-air heat exchanger integrated in the sidepanels for installation of- 19” Components (for cabinet width 650 mm)- Non-standard equipment with installation

widths of 305 to 485 mm for DIN rails andfixing of mounting panels

Integrated heat exchanger principle- Integration of the heat transfer systemin the side panels- Fans and electronic control board instal-led in the roof for maximum useablespace- Optimised postioning of air entry andexit ensures lowest wind disruption ofthe airflow - Sound pressure level, less than 55 dB(A)

at 1 m distance, in accordance withISO 7779

Supply schedule1 Wall case2 Double skinned ribbed side panels withinternal channel plate1 Solar protection roof1 Front door, closed,hinged on right1 Fan module with 2 fans 48 VDC,mounted on the cover,thermostat regulated1 Closed cable entry panel in the bottom1 Earthing set

How suppliedFully assembled

Outdoor Wall Case HEC

TEC00150

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

TEC00125

W H D HU/U w h d Specific cooling capacity* Order no. UP

550 700 345 11 385 540 290 18 W/K 01.914.500.1 1 unit

650 700 345 11 485 540 290 18 W/K 01.914.502.1 1 unit

650 700 445 11 485 540 390 20 W/K 01.914.510.1 1 unit

550 900 345 15 385 740 290 20 W/K 01.914.504.1 1 unit

650 900 345 15 485 740 290 23 W/K 01.914.506.1 1 unit

650 900 445 15 485 740 390 23 W/K 01.914.508.1 1 unit

* The max. specific cooling capacity refersto the difference between the intaketemperature of the ambient air and thereturn temperature of the internal air

Page 104: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

2.27

O U T D O O R S Y S T E M S

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

- For safe securing and fixing of batteries inTecoras Outdoor Wall Cases- For mounting on the 19” installation- Load rating 60 kg

MaterialZinc passivated sheet steel, 2 mm,polished

Supply schedule1 Battery tray2 Chassis runners1 Anti-slip mat made of NeoprenMounting material

Battery Tray

W H D HU/U w h d kg Model Order no. UP

650 455 450 25 285 01.908.309.7 1 unit

TEC00361

- With mounting holes for caged nuts

MaterialAluminium, 2 mm, polished

Supply schedule2 Side panels with integrated 19”mounting holes

Mounting bracketMounting material

19” Adapter

W H D HU/U w h d kg Model Order no. UP

700 450 11 330 01.914.840.7 1 unit

900 750 15 330 01.914.841.7 1 unitTEC00362

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 105: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

O U T D O O R S Y S T E M S

2.28

- Wall mounting with/without pole support

Material- Frame, sheet steel and case extrusion of

steel- Console, stainless steel, 1.5 mm

Option- Pole mounting for fixing to the frame of

the wall mounting for pole diameters 50,100, 150 and 200 mm

- Material, stainless steel- Supply schedule: 2 clamps, 1 rear panel

for the frame, mounting material

Supply schedule1 Frame1 Console, consisting of 2 side panels1 Front trim with fastener1 Base cover

How suppliedFlat-packed kit

Wall Mounting for Wall Case HEC

W H D HU/U w h d kg Model Order no. UP

550 700 350 01.914.488.1 1 unit

650 700 350 01.914.489.1 1 unit

650 700 450 01.914.490.1 1 unit

550 900 350 01.914.491.1 1 unit

650 900 350 01.914.492.1 1 unit

650 900 450 01.914.493.1 1 unit

TEC00155

TEC00360

Dimensions in mm: W = Width, H = Height, D = Depth, ESD = ESD version

1 HU / U = Standard height unit (unit) = 44.45 mm, UP = Unit of packaging, kg = Weight

Final digit of order number:

.1 = RAL 7035 light-grey

Page 106: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3ThermalManagementIndoor 3.2 to 3.12

Outdoor 3.13 to 3.18

3.1

T H E R M A L M A N A G E M E N T

Page 107: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

ThermalManagementIndoor

dart fan unitStrong Points 3.5

dart fan units 3.6

Accessories 3.10

Heat exchanger 3.10

Cooling Unit 3.12

ThermalManagementOutdoor

Tecoras

Strong Points 3.16

Air-to-air Heat exchanger 3.18

Cooling unit 3.19

Heating unit 3.20

T H E R M A L M A N A G E M E N T

3.2

Page 108: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3TecorasIndoor 3.4 to 3.14

3.3

T H E R M A L M A N A G E M E N T

Page 109: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

LUF002691

LUF002681

LUF002782

0–1 1–2 2–3 3–4 4–5

Air speed in m/s

0–1 1–2 2–3 3–4 4–5

Air speed in m/s

T H E R M A L M A N A G E M E N T

3.4

Page 110: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.5

T H E R M A L M A N A G E M E N T

Easy filter change while

operating: Fresh air from outsideincreases the cooling perform-ance. A built-in filter mat therebyprotects your components fromcontamination.The filter mat is changed at thefront – this can be done while theunit is operating.The front panel is removed withquick-release fasteners.Downtimes are consequentlyavoided.

The airmatic 19” tangential fanis the ideal ventilation insert formodular chassis’ with printed cir-cuit boards in Eurocard format.A uniform cooling of the electro-nics is guaranteed with an evenlydistributed airflow over the entirewidth of the unit. The airflowmonitoring signals dirt build-upon the filter mat and fan failure ingood time, and consequently pro-tects the installations fromoverheating.

With increased requirements withregard to IP protection (water/dust)and very high power loss of the elec-tronics, heat exchangers and cool-ling equipment are utilised.

6

5Heat transfer by ventilation (forcedconvection) is a very effectivemethod.19” Fan units provide forced air flowthrough the enclosure.Hot spots are targetted and elimina-ted with single fans and fan frontpanels.Fan installation sets and stackablefans can also be integrated later on.

The specialised ventilation sys-tem of the dart fan unit providesuniform through flow for all elec-tronics that require cooling.Marginal areas are also cooled inthe process. Conventional posi-tioning of axial fans is known tocause numerous unventilatedareas.

No heat build-up under the fan:With modular chassis’ that liebelow the fan, the specialiseddesign of the 2 HU fan unit ena-bles air dissipation to the rear.

Automatic regulation of the ven-tilation with temperature sensor.By adapting to the actual require-ments, the fans attain longer life-spans and lower noise levels.

The 19” filter insert provides fil-tered air and thereby preventscontamination of your internalcomponents.

4

3

2

1

dart fan unitStrong points

LUF002054

LUF00279_13

LUF002715

LUF002066

Page 111: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

LUF00272

T H E R M A L M A N A G E M E N T

3.6

For vertical ventilation of 19” racks andenclosures

To prevent hot spots

Even air distribution across the entirewidth and depth of the fan unit

VariantsType 1- for input voltage 230 VAC / 50 HzType 2- for input voltage 115 VAC / 60 HzType 3- for input voltage 24 VDCType 4- for input voltage 48 VDC

Tests- Vibration test in accordance with

MIL-STD 810 E

Approvals- CE label in accordance with the lowpotential guidline 73/23/EWG, EMCguideline 89/336/EWG

Material- Sheet steel

Finish / Colour- Enclosure: zinc-plated- Front panel: powder-coated smooth

RAL 7035 light grey

Technical data single fanType 1- Voltage: 230 VAC (207-243 VAC)- Frequency: 50 Hz- Max. volume flow: 117 m3/h- Power consumption: 14 W- Noise freely blowing: 37 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2450 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:47500 h

Type 2- Voltage: 115 VAC (104-121 VAC)- Frequency: 60 Hz- Max. volume flow: 135 m3/h- Power consumption: 12 W- Noise freely blowing: 42 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2850 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:52500 h

Type 3- Voltage: 24 VDC (12-28 VDC)- Max. volume flow: 170 m3/h- Power consumption: 5 W- Noise freely blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:

62500 h

Type 4- Voltage: 48 VDC (43-53 VDC)- Max. volume flow: 117 m3/h- Power consumption: 6.5 W- Noise freely blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+65°C- Estimated life expectancy L10 at 40°C:52500 h

Supply scheduleType 11 Fan unit1 Power supply lead 2 m with safety plugType 21 Fan unit1 Power supply lead 2 m according to US

standardType 31 Fan unit1 Power supply lead 2 m without plugType 41 Fan unit1 Power supply lead 2 m without plug

Please note- For assembly chassis runner arenecessary

dart 19” vertical fan unit 1 U uncontrolled

WW HH DD nnuummbbeerr ooff ffaannss MMooddeell OOrrddeerr nnoo.. UUPP

193,5 3 230 VAC (207-243 VAC) 03.026.103.1 1 unit

385,5 6 230 VAC (207-243 VAC) 03.026.106.1 1 unit

193,5 3 115 VAC (104-121 VAC) 03.026.104.1 1 unit

385,5 6 115 VAC (104-121 VAC) 03.026.107.1 1 unit

193,5 3 24 VDC (12-28 VDC) 03.026.105.1 1 unit

385,5 6 24 VDC (12-28 VDC) 03.026.108.1 1 unit

193,5 3 48 VDC (43-53 VDC) 03.026.120.1 1 unit

385,5 6 48 VDC (43-53 VDC) 03.026.121.1 1 unit

LUF00274

Page 112: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.7

T H E R M A L M A N A G E M E N T

Increased cooling capacity through frontalair intake

Filter mat can be changed from frontduring operation without need of tools

Even air distribution across the entirewidth and depth of the fan unit

VariantsType 1- for input voltage 230 VAC / 50 HzType 2- for input voltage 115 VAC / 60 HzType 3- for input voltage 24 VDCType 4- for input voltage 48 VDC

Tests- Vibration test in accordance with

MIL-STD 810 E

Approvals- CE label in accordance with the lowpotential guidline 73/23/EWG,EMC guideline 89/336/EWG

Material- Enclosure, front panel: sheet steel

Finish / Colour- Enclosure: zinc-plated- Front panel: powder-coated smooth

RAL 7035 light grey

Technical data single fanType 1- Voltage: 230 VAC (207-243 VAC)- Frequency: 50 Hz- Max. volume flow: 117 m3/h- Power consumption: 14 W- Noise openly blowing: 37 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2450 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:47500 h

Type 2- Voltage: 115 VAC (104-121 VAC)- Frequency: 60 Hz- Max. volume flow: 135 m3/h- Power consumption: 12 W- Noise openly blowing: 42 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2850 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:52500 h

Type 3- Voltage: 24 VDC (12-28 VDC)- Max. volume flow: 170 m3/h- Power consumption: 5 W- Noise freely blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:

62500 h

Type 4- Voltage: 48 VDC (43-53 VDC)- Max. volume flow: 117 m3/h- Power consumption: 6.5 W- Noise freely blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+65°C- Estimated life expectancy L10 at 40°C:52500 h

Supply scheduleType 11 Fan unit1 Power supply lead 2 m with safety plug1 Filter mat viledon P15/150Type 21 Fan unit1 Power supply lead 2 m according to

US standard1 Filter mat viledon P15/150Type 31 Fan unit1 Power supply lead 2 m without plug1 Filter mat viledon P15/150Type 41 Fan unit1 Power supply lead 2 m without plug1 Filter mat viledon P15/150

How supplied- Assembled, wired and tested

dart 19” fan unit with frontal air intake 2 U uncontrolled

LUF00273

LUF00275

W H D number of fans Model Order no. UP

193,5 3 230 VAC (207-243 VAC) 03.026.203.1 1 unit

193,5 3 115 VAC (104-121 VAC) 03.026.204.1 1 unit

193,5 3 24 VDC (12-28 VDC) 03.026.205.1 1 unit

193,5 3 48 VDC (43-53 VDC) 03.026.122.1 1 unit

Page 113: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.8

Temperature measurement via PTC probewith 2 m line, plug-in a the rear

Nominal temperature at potentiometercan be set

Fan control of 30-100% of the nominalspeed, with failure of the temperatureprobe maximum speed

Individual fan monitoring

For vertical ventilation of 19” racks andenclosures

To prevent hot spots

Even air distribution across the entirewidth and depth of the fan unit

VariantsType 1- for input voltage 115/230 VAC(93-253 VAC), 50/60 Hz

Type 2- for input voltage 24 VDC(12 VDC-28 VDC)

Type 3- for input voltage 48 VDC (36-72 VDC)

Output signals

Optical display frontal (3 LED’s)- green system ok- red fan failure- red nominal temperature

exceeding

Acoustic error message(can be turned off via reset key) with:exceeding the nominal temperature- Fan failure

Floating contact (type changeovercontact, load rating 230 V / 1A, incl. signalline 2 m) on the rear to report errors with:exceeding the nominal temperature- Fan failure- Power failure

Tests- Vibration test in accordance with

MIL-STD 810 E

Approvals- CE label in accordance with the lowpotential guidline 73/23/EWG,EMC guideline 89/336/EWG

Material- Sheet steel

Finish / Colour- Enclosure: zinc-plated- Front panel: powder-coated smooth

RAL 7035 light grey

Technical data single fanType 1- Voltage: 24 VDC (12-28 VDC)- Max. volume flow: 170 m3/h- Power consumption: 5 W- Noise openly blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:

62500 h

Supply scheduleType 11 Fan unit1 Power supply lead 2 m with euro plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)Type 21 Fan unit1 Filter mat viledon P15/1501 Power supply lead 2 m without plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)Type 31 Fan unit1 Filter mat viledon P15/1501 Power supply lead 2 m without plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)

How supplied- Assembled, wired and tested

Please note- For assembly chassis runner arenecessary

dart 19” vertical fan unit 1 U speed-controlled

LUF00272

DAR20005

W H D number of fans Model Order no. UP

193,5 3 115/230 VAC (93-256 VAC) 03.026.113.1 1 unit

385,5 6 115/230 VAC (93-256 VAC) 03.026.116.1 1 unit

193,5 3 24 VDC (12-28 VDC) 03.026.115.1 1 unit

385,5 6 24 VDC (12-28 VDC) 03.026.118.1 1 unit

193,5 3 48 VDC (36-72 VDC) 03.026.130.1 1 unit

385,5 6 48 VDC (36-72 VDC) 03.026.131.1 1 unit

Page 114: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.9

T H E R M A L M A N A G E M E N T

Temperature measurement via PTC probewith 2 m line, plug-in a the rear

Nominal temperature at potentiometercan be set

Fan control of 30-100% of the nominalspeed, with failure of the temperatureprobe maximum speed

Individual fan monitoring

For vertical ventilation of 19” racks andenclosures

To prevent hot spots

Even air distribution across the entirewidth and depth of the fan unit

VariantsType 1- for input voltage 115/230 VAC(93-253 VAC), 50/60 Hz

Type 2- for input voltage 24 VDC(12 VDC-28 VDC)

Type 3- for input voltage 48 VDC(36-72 VDC)

Output signals

Optical display frontal (3 LED’s)- green system ok- red fan failure- red nominal temperature

exceeding

Acoustic error message(can be turned off via reset key) with:exceeding the nominal temperature- Fan failure

Floating contact (type changeovercontact, load rating 230 V / 1A, incl. signalline 2 m) on the rear to report errors with:exceeding the nominal temperature- Fan failure- Power failure

Tests- Vibration test in accordance with

MIL-STD 810 E

Approvals- CE label in accordance with the lowpotential guidline 73/23/EWG,EMC guideline 89/336/EWG

Material- Sheet steel

Finish / Colour- Enclosure: zinc-plated- Front panel: powder-coated smooth

RAL 7035 light grey

Technical data single fan- Voltage: 24 VDC (12-28 VDC)- Max. volume flow: 170 m3/h- Power consumption: 5 W- Noise openly blowing: 43 dB(A)- Bearing system: solid bearing- Nominal fan speed: 2900 min-1- Permitted environmental temperature-20...+70°C- Estimated life expectancy L10 at 40°C:

62500 h

Supply scheduleType 11 Fan unit1 Filter mat viledon P15/1501 Power supply lead 2 m with euro plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)Type 21 Fan unit1 Filter mat viledon P15/1501 Power supply lead 2 m without plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)Type 31 Fan unit1 Filter mat viledon P15/1501 Power supply lead 2 m without plug1 Temperature probe with cable 2 m1 Signal line 2 m (plug-in)

How supplied- Assembled, wired and tested

dart 19” fan unit with frontal air intake 2 U speed-controlled

LUF00273

DAR20004

W H D number of fans Model Order no. UP

193,5 3 115/230 VAC (93-256 VAC) 03.026.213.1 1 unit

193,5 3 24 VDC (12-28 VDC) 03.026.215.1 1 unit

193,5 3 48 VDC (36-72 VDC) 03.026.214.1 1 unit

Page 115: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.10

For Dart 19” fan unit front intake, 2 U Material- Viledon P15/150

Supply schedule1 Set at 5 items

How supplied- In batches

dart replacement filter

W H D HU/U w h d kg Model Order no. UP

01.171.217.9 1 unitSMA20058

Temperature control via thermostaticregulated magnet valve

High cooling output with low energyconsumption and extremely compact 2 HUdesign

No danger to electronics with dustdeposits and splash water

Uniform temperature distribution in thecabinet

Service-free operation without fan

Degree of protection- IP 44

Approvals- CE

Technical data

Electrical supply values(supply in the terminal strip)- Mains voltage: 230 V- Nominal frequency: 50 Hz- Nominal current: 0.4 A- Power consumption: 80 W

Power data- Effective cooling power L35W10: 1000 W

with 200l/h water throughput- Maximum cabinet air flow 180 m3/h,

speed controlled- Operating pressure: max. 10 bar- Temperature range: +1°C to +72°- Refrigerant: water, light oils or similar- Weight: 13 kg- Noise level: 52 dB(A) at 1 m distance

with maximum air output

Output signals- High temperature alarm

Material- Enclosure: stainless steel- Front panel: aluminium 3mm

Finish / Colour- Enclosures and front panel, powder-

coated, textured, RAL 7035 light grey- Handles, powder-coated, textured,

RAL 5008 grey blue

Supply schedule1 Heat exchanger1 Mains supply cable1 Supply cable for tube1 Supply coupling for tube1 Condensation tubeOperating instructions

How supplied- In flat packed kits

19” Heat exchanger, 1000 W

W H D HU/U w h d kg Model Order no. UP

443 87 405 03.032.320.1 1 unit

LUF20007

LUF20011

Page 116: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.11

T H E R M A L M A N A G E M E N T

Temperature control via water quantilyregulator

High cooling output with low energyconsumption and extremely compact 4 HUdesign

No danger to electronics with dustdeposits and splash water

Uniform temperature distribution in thecabinet

Service-free operation without fan

Degree of protection- IP 44

Approvals- CE

Technical data

Electrical supply values(supply in the terminal strip)- Mains voltage: 230 V- Nominal frequency: 50 Hz- Nominal current: 0.45 A- Power consumption: 100 W

Power data- Effective cooling power L35W10: 2000 W

with 200l/h water throughput- Maximum cabinet air flow 180 m3/h,

speed controlled- Operating pressure: max. 10 bar- Temperature range: +1°C to +72°- Refrigerant: water, light oils or similar- Weight: 16.5 kg- Noise level: 52 dB(A) at 1 m distance

with maximum air output

Output signals- High temperature alarm

Material- Enclosure: stainless steel- Front panel: aluminium 3mm

Finish / Colour- Enclosures and front panel, powder-

coated, textured, RAL 7035 light grey- Handles, powder-coated, textured,

RAL 5008 grey blue

Supply schedule1 Heat exchanger1 Mains supply cable1 Supply cable for tube1 Supply coupling for tube1 Condensation tubeOperating instructions

How supplied- In batches

19” Heat exchanger, 2000 W

W H D HU/U w h d kg Model Order no. UP

443 175 505 03.032.322.1 1 unit

LUF20006

LUF20010

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 117: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.12

Service-free operation with patentedconstruction without filter

High cooling output with compact design

CFC-free refrigerant, R 134a

Uniform temperature distribution in thecabinet

Approvals- CE

Degree of protection- IP 44

Technical data

Electrical supply values- Nominal voltage: 230 V- Nominal frequency: 50 Hz- Nominal current: 4.5 A- Max. starting current: 9 A- Power consumption: 850 W

Power data- Effective cooling power L35W35: 1000 W- Maximum cabinet air flow 360 m3/h,

speed-controlled- Maximum cabinet air flow 720 m3/h,

speed controlled- Temperature range: +20°C to +55°- Refrigerant: R134a (CFC-free)- Weight: 45 kg- Noise level: 70 dB(A) at 1 m distance

with maximum air output

Output signals(micro controller functions)- Required and alarm temperature can be

set per potentiometer- Alarm output per relay (normally openor closed)- Floating door contact switch as normally

closed- Connectable test mode

Material- Enclosure: stainless steel- Front panel: aluminium 3mm

Finish / Colour- Front panel, powder-coated, textured,

RAL 7035 light grey- Handles, powder-coated, textured,

RAL 5008 grey-blue

Supply schedule1 Cooling unit1 Mains supply cableOperating instructions

How supplied- In batches

Please note- Additional installation set is necessary.

Please ask.

19” Cooling unit, 6 HU 1000 W

W H D HU/U w h d kg Model Order no. UP

482,6 265,9 570 03.032.300.1 1 unit

LUF20002

LUF00213

Page 118: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.13

T H E R M A L M A N A G E M E N T

Service-free operation with patentedconstruction without filter

Automatic condensation vaporization

For adding-on on the rear panel, reardoor or side panel of a cabinet

Lowered installation possible

No loss of 19” installation space

Temperature control with micro controller

CFC-free refrigerant R 134a

No danger to electronics with dustdeposits and splash water

Uniform temperature distribution in thecabinet

Weight

- 39 kg

Degree of protection- IP 54

Approvals- CE label

Technical data

Electrical supply values

(supply in the terminal strip)- Nominal voltage: 230 V- Nominal frequency: 50 Hz- Nominal current: 2.8 A- Max. starting current: 12.7 A- Power consumption: 660 W

Power data- Effective cooling output L35W35: 820 W- Maximum cabinet air flow 180 m3/h,

speed controlled- Maximum cabinet air flow 360 m3/h,

speed controlled- Temperature range: +20°C to +55°- Refrigerant: R134a (CFC-free)- Noise level: 65 dB(A) at 1 m distance

with maximum air output

Output signals(micro controller functions)- Required and alarm temperature can be

set per potentiometer- Alarm output per relay (normally openor closed)- Floating door contact switch as normally

closed (24 VDC)- Connectable test mode

Material- Enclosure: sheet steel- Front panel: aluminium 3mm

Finish- Enclosure, powder-coated, textured

RAL 7035 light grey

Supply schedule1 Cooling unitOperating instructions

How supplied- In batches

Cooling unit add-on and installation, 820 W

W H D HU/U w h d kg Model Order no. UP

395 980 135 03.032.302.1 1 unitLUF20016

LUF20014

Page 119: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.14

Service-free operation with patentedconstruction without filter

Automatic condensation vaporization

For adding-on on the rear panel, reardoor or side panel of a cabinet

Lowered installation possible

No loss of 19” installation space

Temperature control with micro controller

CFC-free refrigerant R 134a

No danger to electronics with dustdeposits and splash water

Uniform temperature distribution in thecabinet

Weight- 50 kg

Degree of protection- IP 54

Approvals- CE label

Technical data

Electrical supply values(supply in the terminal strip)- Nominal voltage: 230 V- Nominal frequency: 50 Hz- Nominal current: 3.8 A- Max. starting current: 16 A- Power consumption: 720 W

Power data- Effective cooling output L35W35: 1400 W- Maximum cabinet air flow 250 m3/h,

speed controlled- Maximum cabinet air flow 430 m3/h,

speed controlled- Temperature range: +20°C to +55°- Refrigerant: R134a (CFC-free)- Noise level: 65 dB(A) at 1 m distance

with maximum air output

Output signals(micro controller functions)- Required and alarm temperature can be

set per potentiometer- Alarm output per relay (normally openor closed)- Floating door contact switch as normally

closed (24 VDC)- Connectable test mode

Material- Enclosure: sheet steel- Front panel: aluminium 3mm

Finish- Enclosure, powder-coated, textured

RAL 7035 light grey

Supply schedule1 Cooling unitOperating instructions

How supplied- In batches

Cooling unit add-on and installation, 1400 W

LUF20017

LUF20014

W H D HU/U w h d kg Model Order no. UP

395 1550 135 03.032.304.1 1 unit

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 120: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3TecorasOutdoor 3.13 to 3.18

3.15

T H E R M A L M A N A G E M E N T

Page 121: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.16

The permanent increase of heat

dissipation in electronic componentsand the higher packaging density ofthe equipment caused special re-quirements for thermal manage-ment in our enclosures. Knürr

established a climate competencecenter to propose our customer thebest solutions in thermal manage-ment.

Modularity- Adjustment to various tempe-

rature conditions through themechanical and electricalcompatibility of heat exchan-gers and cooling devices- Interface for alarm monitoring

and external sensors

Complete Product RangeComplete product range ist thebest condition to to fulfill allcustomer specification- K-HEX, Knürr Heat Exchanger- HEC, Heat Exchanger Cabinet- ACUR, Air Conditioning Unit- Filter Fan- Heater- Controller Board- Membrane Filter

Climatic chamber- Inter size: 3,0x3,0x3,0 m3

- Door size: 1,15x2,45 m2

- Temperature -45 ... +60°Crange:- Humidity range: 10 ... 95%

(at 10 ... 40°C)- Access for forklift truck

Measurement instruments/documentationData logger up to 80 chanels:- Temperature- Voltage- Current

- Revolutions

Measurement instruments:- Relative humidity- Velocity- PressureData export in all usually formats

4

3

2

1

Tecoras Thermal ManagementStrong points

TEC00087

TEC002793TEC000061

TEC200814

Page 122: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.17

T H E R M A L M A N A G E M E N T

Thermal design/CFDKnürr used several calculationtool to design the right thermalsotution.

The most powerful software isthe Computational FluidDynamics (CFD) program tocalculate temperature profilesand air flow velocities beforeprototyping.

As a service Knürr offers simula-tion reports and designed thethermal solution exact accordingthe specification.

Smoke TextSmoke visualize air flow.

Zones with low air flow becomevisible. These zones have risks ofhot spot. To avoid hot spots amodification of the configurationare proposed.

Acoustic noise emissionIn house semi-anchoic test floor

Acoustic-Measurement of airbor-ne noice according ISO 7779

Thermal chamber and acoustictest floor are next to each other.Knürr adjust the contrary specifi-cation requirements of lowairborne noise and high coolingperformance on an optimum way.

Acoustic noise absorberKnürr cabinets achieve very lowlevels of airborne noise emission.

Knürr used special designednoise absorber for low aousticnoise cabinets. This allows tooperate cabinets in areas withspecial aoustic noise limits.

8

7

6

5

Tecoras Thermal ManagementStrong points

TEC200805 TEC200726

TEC200737

TEC800018

Page 123: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T H E R M A L M A N A G E M E N T

3.18

High-capacity, compact air-to-air heatexchanger for door installation inTECORAS outdoor cabinets

Degree of protection- IP 55

Approvals- CE- UL approval- EN 60 950

Principle- Air-to-air heat exchanger with freelyprogrammable micro processor control- Countercurrent heat exchanger of epoxy

coated aluminium with extruded surface- Direct mounting on the inside of thedoor, Identical mounting principle anduniform screwing conditions for allthermal components- IP 55 interface between heat exchanger

and Tecoras door registered for patent- Air outlet grills, 90° oriented, no

thermal short circuit in the external air- From 163 mm installation depth, extru-

sion frame design and screw-free cover- Internal temperature-dependent fan

speed control guarantees optimal inter-nal cabinet temperature, maximumlifecycle and minimum noise emission- Filterless system, consequently, simple

cleaning is possible- Hidden cable entry on hinge side, no

cable and plug in the useful space of thecabinet- One variant for left and right door- Fan exchange in the internal andexternal circuit without dismounting theheat exchanger from the door- Individual fuse protection for eachfan on the control board, prefusingrequired- Customer-specific adaptations possible

with platform design

Technical data- Supply voltage, 48 VDC (optional 24 VDC)- Protection rating, IP 55 internal circuit /external circuit- Sound pressure level. 55 dB (A) at adistance of 1 m in accordance withISO 7779, in the built-in cabinet up to85 W/K

Material- Enclosure of aluminium, 1.5 mm,partially with extruded aluminium-Heat exchanger of 0.25 mm aluminium- Silicon-free seals

Supply schedule1 Heat exchanger1 Operating instructions

How supplied- Fully assembled

Tecoras Air-to-air heat exchanger (K-HEX)

W H D W/K V A Model Order no. UP

465 888 102 (118) 65 48 10 K-HEX 65 01.920.500.0 1 unit

465 1066 147 (163) 85 48 6 K-HEX 85 01.920.603.0 1 unit

565 1600 147 (163) 145 48 20 H-HEX 145 01.920.607.0 1 unit

565 1155 147 (163) 150 48 20 K-HEX 150 01.920.608.0 1 unit

TEC20062

See also: the current

Network Special Catalogue!Where you will find more products:

• 19” Rack systems

• Free-standing and wall cabinets

• TFT Drawers

• KVM Switches

• UPS Solutions

• RMS-System

• Thermal management

Page 124: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.19

T H E R M A L M A N A G E M E N T

High-capacity, compact cooling unit fordoor installation in TECORAS outdoorcabinets

Approvals- CE- UL approval

Principle- High-performance cooling unit with

roating piston compressor- CFC-free referigerant, R 134a- Safe condensation dissipation to theoutside- Direct mounting on the inside of thedoor, Identical mounting principle anduniform screwing conditions for allthermal components- IP 55 interface between heat exchanger

and Tecoras door registered for patent- Air outlet grills, 90° oriented, no

thermal short circuit in the external air- Adjustable air-break panel for minimi-

zing thermal short circuit in the internalcircuit- Adjustable internal cabinet temperatureguarantees optimal internal cabinettemperature, maximum lifecycle andminimum noise emission- Equipment failure alarm with adjustable

alarm temperature (internal cabinettemperature)- Filter-free system, easy cleaning is

consequently possible- Cable entry offset to the hinge side, no

cable and plug in the useful space of thecabinet- Test switch on the control board- One variant for left and right door- Fan exchange in the internal andexternal circuit without taking thecooling unit from the door

Technical data- Output data for cooling unit built into

Tecoras cabinet, determined in accor-dance with DIN 3168, without moisturetransport in the control cabinet- Supply voltage, 230 VDC / 120 VAC,50 Hz / 60 Hz- Continuous use temperature up to 52°C- Protection rating, IP 55, internal

circuit/external circuit- Noise pressure level, 55 dB (A) at adistance of 1 m in accordance withISO 7779, mounted cabinet up to 1800 W

Material- Enclosure of aluminium, 1.5 mm

Supply schedule1 Cooling unit1 Connection cable for AC1 Plug for operation without door contact

switch1 Operating instructions

How supplied- In fully assembled

Tecoras Cooling unit (ACU R)

TEC20060

(W) W H D (V) (Hz) (A) (A) (W) Model Order no. UP

380 466 326 114 (130) 230 50/60 1,5 3,3 320 ACU R 400 230 V/AC 01.920.912.0

800 466 888 157 (172) 230 50/60 2,4 11,5 550 ACU R 800 230 V/AC 01.920.900.0

800 466 888 157 (172) 120 50/60 4,8 23,0 550 ACU R 800 115 V/AC 01.920.901.0

1200 466 1066 157 (172) 230 50/60 4,5 15,0 800 ACU R 1200 230 V/AC 01.920.904.0

1200 466 1066 157 (172) 120 50/60 9,0 30,0 800 ACU R 1200 115 V/AC 01.920.905.0

1800 466 1066 157 (172) 230 50/60 5,0 22,0 1200 ACU R 1800 230 V/AC 01.920.906.0

1800 466 1066 157 (172) 120 50/60 10,0 44,0 1200 ACU R 1800 115 V/AC 01.920.907.0

2700 566 1600 157 (172) 230 50/60 8,0 30,0 1700 ACU R 2700 230 V/AC 01.920.910.0

Technical dataSupply voltage 230 VAC/50(60) Hz, Axialfan: air throughput 35 m3/h with 150 W,from 300 W 108 m3/h, 950 W 160 m3/h,Thermostat: temperature setting from0 to 60° CHeating element protection with tempera-ture monitor in the event of fan failureProtection rating IP 20

Supply schedule1 Heating fan, 230 VAC/50(60) Hz1 Thermostat with contact break1 Connecting cable, 1,5 mm2,1,5 m cable length1 Mounting panelMounting material

How suppliedFully assembled

Heating Unit

TEC00335

W H D W/K V A Model Order no. UP

108 85 139 150 01.910.900.9 1 unit

135 85 182 300 01.910.901.9 1 unit

135 85 182 400 01.910.902.9 1 unit

145 85 240 600 01.910.903.9 1 unit

145 100 200 950 01.910.908.9 1 unit

Page 125: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

3.20

Rapid service

Express Articles

Fast express delivery service,seamless ordering system,

attractive prices and a market–

oriented offer - that’s Knürr

efficiency!

Every express article that is

correspondingly identifed in

this catelogue leaves our

European central stores 24

hours after your order is

received: qualitative high-

grade, standardised solutions,

with which you are always

decisively ahead of the compe-tition.

Our sales offices are also avai-lable for you worldwide, where

competent technicians andsales engineers will personal-ly take care of your specialrequirements.

Why not use these advantagesto your own benefit.

Express articles

in 24 hours ex plant:

With Knürr you are always

ahead of the competition

Page 126: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

4Power supplySystemsPower Supplies/DC-UPS 4.2 to 4.10

4.1

P O W E R S U P P LY S Y S T E M S

Page 127: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

DC-UPSStrong Points 4.2

Products 4.4

Distribution BoxProducts 4.10

4.2

P O W E R S U P P LY S Y S T E M S

Temperature controlled charging

Optimal charge current

adaptation due to battery

temperature measurement,maximum permissible constant

current for minimum battery

charging time

Monitoring

Monitoring of Rectifier module,Battery tests, registering andlinking of connected monitoringsensor systems

Communication

Transmission of analysis andalarm data via serial and binary

interfaceDisplay of operating and alarmstates via LEDs and LC display

8

7

6Modular Design

Configuration and equipping tosuit requirements in case of:Redundancy and easy futureupgrade possible

High power density

Up to 7,2 kW with a dimension of19”x3Ux300 mm (WxHxD)

Hot SwapFast on line replacement ofRectifier and Battery Control-Unitwithout system shutdown

Wide input voltage rangeOperate in a variety of AC supplyconditions

Wide area of operation

Usable for all indoor and outdoorapplications; tested cold start

routines and ready to operate at

high ambient temperature

5

4

3

2

1

Rectifier/DC Power and Backup SystemsStrong points

TEC200851 TEC000136

TEC200882

TEC000118

Page 128: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

4.3

P O W E R S U P P LY S Y S T E M S

The power system

Consists of the following individualcomponents:- 1 to 5 (6 with 1200 W) piece of

200 W, 750 W or 1200 W rectifiermodules- Charge monitor module- Backplane for mounting theindividual modules- 19” Modular chassis

Height 3 HU (1 HU = 44.45 mm),depth 285 mm (200 W rectifier)or depth 340 mm (750 W rectifier)

Various freely-selectable combina-tion options can be designed withthe modular concept.The integrated charge controllermonitors the batteries in the UPSoperation and ensures optimal bat-tery charging.Using connected sensors anddepending on the requirements, itadditionally monitors the environ-mental conditions in the rack as wellas monitoring the power modulesand controlling battery tests.If an uninterruptible power supplyfunctionality is not required, thepower supply can also be operatedwithout batteries and chargecontroller.Depending on the number of PSUmodules, output power of up to1000 W, 3750 W or 7200 W, can berealized in each 200, 750 or 1200 Wstage.With output of up to 600 W or

2250 W (3 modules), a DC distributorcan be integrated in the modular

chassis.

TEC00056

DC Backup SystemsTechnical data, power system with battery buffer

Page 129: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

P O W E R S U P P LY S Y S T E M S

4.4

Power System, MAXI DC UPS 750 W

Technical dataOutput power 750 W with 230 V

AC supply500 W with 115 V ACsupply

Characteristic Current/voltagewith temperature-regulated adaption

Ventilation With convectionforced cooling withTu › 35º C

Operating temp. –10° C to +60° CrangeStorage temp. –40° C to +85° CrangeHumidity 30% to 95% (no

dewfall)Input voltage 100 V AC …240 V ACrange nominalEfficiency 90% at full load

(Ue = 240 V)Power factor › 0.9 in acc. with(with full load) EN 61000-3-2Input current 25 A with 265 V AClimitOutput power 750 W

(TU =25° C)Convection750 W (TU = 50° C)Fan(VL = 1.5 m/s)

Output voltage 48 V DCSetting range of the 42 V DC to 585 Voutput voltage DC, short circuit-

proofStandards EN 55022B,

EN 61000-3-2,EN 61000-4 part 2,3, 4, 5 level 3,ETS 300 339,ETS 300 342-2,GSM 11.22,EN 60950, VDE 0160

MTBF ›100,000 hrsDimensions Width 15 HP,

Height 3 HU,Depth 295 mm

Power System, MIDI DC UPS 200 W

Technical dataOutput power 200 W regulated at

115/230 V AC(230 V AC with con-vective cooling)

Regulation Current-regulated(with temperature-regulated adaption)

Efficiency › 85% at full loadPower factor › 0.8 in acc. with

EN 6100-3-2Ventilation ConvectionDerating From Tu 35° COperating temp. 0°C to +60° Crange (switch-off at

› 60° C)Storage temp. -40° C to +85° CrangeHumidity 30% to 95%

(no condensationmoisture)

Voltage range 100 V AC … 240 V ACInput current 5 AlimitOutput voltage 48 V DCStandards EN 55022B,

EN 61000-3-2,EN 6100-4 part 2-5,EN 50081-1,EN 50082-2,EN 60950,VDE 0160

MTBF › 100,000 hrsDimensions Width 15 HP

Height 3 HUDepth 220 mm

HEI00400

HEI00402

Page 130: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

4.5

P O W E R S U P P LY S Y S T E M S

Power System, MAXI II 1200 W

Technical dataOutput power 1200 W (25A @ 48 V)

at 230 VAC supplyCharacteristic Power/Voltage with

temperaturecontrolled adaptation

Ventilation Temperature con-trolled, highreliability fan

Operating temp. –10° C to +70° Crange (Output current is

derated above 50° C)Storage temp. –40° C to +85° CrangeHumidity 30% to 95%

(no moisturecondensation)

Input voltage 90 VAC ... 300 VACrange (220/240 V, 50/60 Hz

nominal)

Efficiency 90% (at 50 - 100%output current)

Power factor › 0,99 (at 50 - 100%output current)

Output power 1200 W (TU ‹ 50° C)Output voltage 48 VDCSetting range 43.2 V to 58 VStandards EN 55022B,

EN 61000-3-2,EN 61000-4 part2-5, EN 50081-1,EN 50082-2,EN 60950, VDE 0160

MTBF ›100,000 hrsDimensions Width 13 HP,

Height 3 HU,Depth 280 mm

Power System, MIDI 200 - 1000 Wfor external distribution

Dimension- Width 19”- Height 3 U with modular chassis- Depth 285 mm

Supply schedule1 Modular chassis, 3 HU equipped with- 1...5 PSU module 200 watt- Charge controller BCU

Please noteBattery configuration possible to suitrequirements, on separate battery tray.We are happy to be able to offer you theappropriate batteries for your requiredbackup times.

TEC20086

W H D P(W) h d kg Model Order no. UP

200 7,0 06.104.102.1 1 unit

400 8,1 06.104.202.1 1 unit

600 9,2 06.104.302.1 1 unit

800 10,3 06.104.402.1 1 unit

1000 11,4 06.104.502.1 1 unit

HEI00412

Power System, MIDI 200 - 600 Wwith integrated distribution

Dimension- Width 19”- Height 3 U- Depth 285 mm

Supply schedule1 Modular chassis, 3 HU equipped with

backplane, with- 1...3 PSU module 200 watt- Charge controller BCU- 1 DC distribution 3 HU with output

terminal and fuse protection

Please noteBattery configuration possible to suitrequirements, on separate battery tray.We are happy to be able to offer you theappropriate batteries for your requiredbackup times.

W H D P(W) h d kg Model Order no. UP

200 7,8 06.104.132.1 1 unit

400 9,0 06.104.232.1 1 unit

600 10,2 06.104.332.1 1 unit

HEI00414

Page 131: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

P O W E R S U P P LY S Y S T E M S

4.6

Dimensions in mm: W = Width, H = Height, D = Depth, h = Max. inst. height, d = Useful depth / chassis depth

HU/U = Standard height unit (Unit), UP = Unit of packaging, kg = Weight

P (W) = Output power, * = Backup time in minutes, ** = Backup time in hours

Final digit of order number:

.1 = RAL 7035

Power System, MIDI Compact I... IV DC UPS 200 - 600 Wwith integrated battery pack

19” DC UPS MIDI Compact I, 6 HUwith integrated battery pack

Dimensions- Width 19”- Height 6 HU- Depth 285 mm

Supply schedule1 Modular chassis, 6 HU equipped with- 1…3 Recitfier module, 200 W- Charge controller, 9 HP (without dis-play/ RS-232 interface)- Integrated battery pack, 13 Ah- Integrated DC distribution with outputfuses

19” DC UPS MIDI Compact II, 6 HU

Supply schedule same as Compact I,but with- Integrated DC distribution with circuit

breakers

19” DC UPS MIDI Compact III, 6 HUSupply schedule same as Compact I,but with- Charge controller, 9 HP with LC display/

RS-232 interface

19” DC UPS MIDI Compact IV, 6 HUSupply schedule same as Compact I,but with- Charge controller, 9 HP with LC display/

RS-232 interface- Integrated DC distribution with circuit

breakers

HEI00402

min* P(W) kg Model Order no. UP

180 200 31.0 UPS MIDI Compact I 06.104.111.1 1 unit

90 400 32.5 UPS MIDI Compact I 06.104.211.1 1 unit

45 600 34.0 UPS MIDI Compact I 06.104.311.1 1 unit

180 200 31.0 UPS MIDI Compact I 06.104.121.1 1 unit

90 400 32.5 UPS MIDI Compact II 06.104.221.1 1 unit

45 600 34.0 UPS MIDI Compact II 06.104.321.1 1 unit

180 200 31.0 UPS MIDI Compact III 06.104.112.1 1 unit

90 400 32.5 UPS MIDI Compact III 06.104.212.1 1 unit

45 600 34.0 UPS MIDI Compact III 06.104.312.1 1 unit

180 200 31.0 UPS MIDI Compact IV 06.104.122.1 1 unit

90 400 32.5 UPS MIDI Compact IV 06.104.222.1 1 unit

45 600 34.0 UPS MIDI Compact IV 06.104.322.1 1 unit

Power System, MIDI compact DC UPS 200 - 400 WUPS with integrated battery pack

Dimension- Width 19”- Height 3 U with modular chassis- Depth 285 mm

Supply schedule1 Modular chassis, 3 U equipped with- 1...2 Power supply module (PSU) withoutput power of 200 W each- Charge controller 9 HP- Integrated battery pack 4 Ah- Integrated DC distribution with circuit

breakers

min* P(W) kg Model Order no. UP

30 200 14,8 06.104.100.1 1 unit

10 400 16,0 06.104.200.1 1 unit

HEI00416

Page 132: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

4.7

P O W E R S U P P LY S Y S T E M S

Power System, MAXI 750 - 3750 Wwith external distribution

Dimension- Width 19”- Height 7 U- Depth 340 mm

Supply schedule1 Modular chassis, 3 U with backplane,

with- 1...5 PSU module 750 watt- Charge controller BCU

1 Fan unit 1 U1 AC / DC Distribution, 3 U with

- AC Input protection- Service sockets with RCCB- DC Output terminal with fuse protection

Please noteBattery configuration possible to suitrequirements, on separate battery tray.We are happy to be able to offer you theappropriate batteries for your requiredbackup times.

W H D P(W) h d kg Model Order no. UP

750 17,1 06.103.000.1 1 unit

1500 19,2 06.103.010.1 1 unit

2250 21,3 06.103.020.1 1 unit

3000 23,4 06.103.030.1 1 unit

3750 25,5 06.103.040.1 1 unit

HEI00400

Power System, MAXI 750 - 2250 Wwith integrated distribution

Dimension- Width 19”- Height 3 U- Depth 340 mm

Supply schedule1 Modular chassis, 3 U with backplane,

equipped with- 1...3 PSU module 750 watt- Charge controller BCU

1 DC Distribution, 3 U with outputterminal and fuse protection

Please noteBattery configuration possible to suitrequirements, on separate battery tray.We are happy to be able to offer you theappropriate batteries for your requiredbackup times.

W H D P(W) h d kg Model Order no. UP

750 9,4 06.103.001.1 1 unit

1500 11,5 06.103.011.1 1 unit

2250 13,6 06.103.021.1 1 unit

HEI00409

Power System, MAXI compact DC UPS 750 - 2250 Wwith integrated battery pack

Dimension- Width 19”- Height 6 U- Depth 340 mm

Supply schedule1 Modular chassis, 6 U equipped withbackplane, with- 1...3 PSU module 750 watt- Charge controller BCU

1 DC Distribution, 3 U with outputterminals with fuse protection

How supplied- In batches

min* W H D P(W) h d kg Model Order no. UP

40 750 32,9 06.103.002.1 1 unit

13 1500 35,0 06.103.012.1 1 unit

8 2250 37,1 06.103.022.1 1 unit

TEC20089

Page 133: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

P O W E R S U P P LY S Y S T E M S

4.8

Power System, MAXI II 1200 - 7200 Wwith external distribution

Dimension- Width 19”- Height 6 U- Depth 300 mm

Supply schedule1 Modular chassis, 3 U with backplane,

with- 1...6 PSU module 1200 watt- Charge controller BCU

1 AC / DC Distribution, 3 U with- AC Input protection- Service sockets with FI- DC Output terminal with fuse protection

How supplied- In batches

W H D P(W) h d kg Model Order no. UP

1200 17,1 03.013.500.1 1 unit

2400 19,2 03.013.501.1 1 unit

3600 21,3 03.013.502.1 1 unit

4800 23,4 03.013.503.1 1 unit

6000 25,5 03.013.504.1 1 unit

7200 27,6 03.013.505.1 1 unit

TEC20086

Power System, MAXI II 1200 - 3600 Wwith integrated distribution

Dimension- Width 19”- Height 3 U- Depth 300 mm

Supply schedule1 Modular chassis, 3 U with backplane,

equipped with- 1...3 PSU module 1200 watt- Charge controller BCU

1 DC Distribution, 3 U with outputterminal and fuse protection

Please noteBattery configuration possible to suitrequirements, on separate battery tray.We are happy to be able to offer you theappropriate batteries for your requiredbackup times.

How supplied- In batches

W H D P(W) h d kg Model Order no. UP

1200 9,4 03.013.510.1 1 unit

2400 11,5 03.013.511.1 1 unit

3600 13,6 03.013.512.1 1 unit

TEC20091

Power System, MAXI compact II DC UPS 1200 - 3600 Wwith integrated battery pack

Dimension- Width 19”- Height 6 U- Depth 300 mm

Supply schedule1 Modular chassis, 3 U with backplane,

equipped with- 1...3 PSU module 1200 watt- Charge controller BCU

1 Integrated battery pack 13 Ah1 DC distribution, 3 V with output

terminals with fuse protection

How supplied- In batches

min* W H D P(W) h d kg Model Order no. UP

18 1200 32,9 03.013.520.1 1 unit

7 2400 35,0 03.013.521.1 1 unit

3 3600 37,1 03.013.522.1 1 unit

TEC20090

Page 134: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

4.9

P O W E R S U P P LY S Y S T E M S

Power System, MINI DC UPS 25W1 U with integrated battery pack

Dimension- Width 19”- Height 1 U- Depth 225 mm

Supply schedulePower supply 48 V / 25 wattIntegrated battery pack for 4 hoursbackup time DC Output and signaloutputs via SUB-D socketAlarm messages for- Mains voltage- Charge regulator monitoring- Battery partial discharge- Battery deep discharge

W H D P(W) h d kg Model Order no. UP

25 4 5 06.104.900.1 1 unit

HEI00404

Page 135: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

P O W E R S U P P LY S Y S T E M S

4.10

Distribution Box

W H D Model Order no. UP

19” 3 HU 150 mm Pull-in 03.013.385.1 1 unit

19” 3 HU 158 mm Fixed installation 03.013.470.1 1 unit

WW HH DD MMooddeell OOrrddeerr nnoo.. UUPP

03.013.386.1 1 unit

- For mounting installation engineering DINrail components such as fuses, terminals,relays etc.- When installed, the mounting level can bepulled out to the front and interlocked, thusconsiderably facilitating the wiring of indivi-dual components Not with “fixed installation” model- Installation space for up to 22 installationdevices of 18 mm width each- Mounting of the TS35 DIN rail on severallevels due to simple plug-in connectionNot with “fixed installation model”- "Snap-in" mounting of DIN rail components - Free access to protective earth and neutral

conductor rail from the front- Different positioning options prepared for N

and PE railsNot with “fixed installation” model

- Cable entry at the back via double brushstrip (optional via bushing panel)- Internal strain relief and thus accessiblefrom the front- Front labelling above and below the installa-

tion space- Power uses for power distribution at 230 V

AC, but also in the low voltage range (e.g. 48V DC)On request: can be delivered ready equippedand cabledOther options and models available onrequest- 19" Chassis, 3 HU, depth 150 mm

Material / Finish- Covers, powder-coated

RAL 7035 light-grey, textured- Main unit, sheet steel, zinc passivated

Supply schedule1 Distribution boxIncluding N and PE rails, cable entry,strain relief, empty panel covers andearthing kit

How suppliedFully assembled

HEI00379

HEI00234

Distribution Box Bushing Panel

Alternative to cable entry via brush strip withmounting the distribution box in open racks

Material / FinishSheet steel, zinc passivated

Supply schedule1 Cable entry panel11 Bushing socketsMounting material

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 136: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

5SystemMonitoringRMScompact 5.2 to 5.6

5.1

S Y S T E M M O N I T O R I N G

Page 137: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

System

Monitoring

RMScompactStrong points 5.2

Products 5.4

Accessories19” Adapter Front Panel 5.4

Temperature Sensor 5.5

Humidity Sensor 5.5

Smoke Sensor 5.5

Door Contact Sensor 5.5

Water Sensor 5.6

Shock Sensor 5.6

Infrared Detector 5.6

RMS20013

Until now, system monitoring options were limited to active components.Now, with SNMP management systems, parameters such as data emer-gence, error rate, equipment configuration and, of course, downtime ofindividual connections or hardware components are all monitored. But thecauses for such downtimes remain for the most part unclear, and are onlyfirst realised on-site, i.e. in the server or network rack or cabinet.Observance of the required environmental parameters is, however, ofenormous importance for the fault-free operation of high-grade compo-nents. Inadmissible fluctuations in temperature, humidity or power supplyare frequently the cause of hardware defects, therefore constant automaticmonitoring is a fundamental requirement for securing operational functio-nality. With the rack monitoring systems available on the market today,these parameters and other factors can be recorded, and can often bepassed directly on to a superordinate management system. However,recording of conditions alone is often not enough to combat damage as thetime from occurance of a critical condition to initiation of combatative mea-sures, particularly with larger network environments, is often quite limited.In such cases it is extremely helpful if the monitoring system can automati-cally implement constructive measures (e. g. additional active fans). Whensuch incidents occur, the equipment should at least be able to immediatelysend a report (trap) to the management system, which for example, willthen notify those responsible for the network via e-mail or pager. Thisenables a sufficiently short reaction time and a swift location of the faultlocation and its subsequent elimination.With the option of connecting additional sensors like smoke detectors, doorcontacts etc., not only enclosures but entire rooms or building sections canbe monitored. In this way all environmental parameters of a computer cent-re can be easily recorded and evaluated.

Please address any questions to: [email protected]

RMS compact

The security system fornetwork and server racksand computer centres

5.2

S Y S T E M M O N I T O R I N G

Page 138: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

5.3

S Y S T E M M O N I T O R I N G

The main tasks that amodern rack monitoringsystem must perform:

• Guarantee a disturbance-free operation• Provide early detection of fault-provoking influences• Record all such incidents - Simplify service implementation with

automatic monitoring• Activate counteractive measures in the event of malfunctioning• Centrally control the conditions of material in use (filters, fill levels,meter readings, inspection intervals etc.)

RMS20026

Page 139: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

S Y S T E M M O N I T O R I N G

5.4

RMS20013

Description- Compact design - Zero unit solution(to be mounted outside the 19” installa-tion area)- 19” Installation with 1HU adapter frontpanel (optional)- Safe clamping of all connected cables

with integrated cable clamping bracket - Cost-effective, tidy installation with Plug

& Play concept- Convenient cabling with plug-in contacts- TCP/IP Connection via Ethernet(10 Base T)- Configuration via SNMP, Telnet and web

browser- Serial configuration via terminal emu-lation (e.g.. hyper terminal,...)- Telnet and web access are passwordprotected- Viewer and configuration software(free-of charge in supply schedule)- Freely programmable filter system(Boolean logic) for implementing anykind of alarm conditions - Compatible with current networkmanagement systems – HPOpenView,Cabletron Spectrum, Castlerock, IBMNetview, IBM Tivoli, MG-Soft, CompaqInsight Manager, SUN NetManager, etc.- Sensors for monitoring all current envi-

ronment influences (optional)- Monitored internal voltage supply for

sensor systems (no additional powersupply required)- Alarm via LED, relay or network mana-gement

- Firmware upgrade via serial interface orTFTP- Integration of external devices via V.24possible (on request)

Technical data- 2 Sensor inputs for temperature

sensors or temperature/humiditysensors- 8 Digital inputs, can be configured with

software- 8 Outputs 12VDC for voltage-

supply of external sensor system- 3 Digital outputs (relay, max. 5A with

230VAC)- Voltage supply: 100 – 240 VAC- Operating voltage: 12VDC

Approvals- CE Label in accordance withlow voltage guideline 73/23/EWG, EMCguideline 89/336/EWG

Colour- RAL 7021 dark-grey

Supply schedule1 RMS compact1 Power supply1 Mounting bracket1 Power supply mounting bracket1 Serial cable1 CD ROM (with manual, viewer and

configuration software, MIB file)

How suppliedFlat-packed kit

RMS compact

RMS compact

W H D Model Order no. UP

280 40 140 RMS compact 06.108.100.8 1 set

RMS20015

RMS20014

19” Adapter Front Panel

Description- Enables 19“ installation in racks

and enclosures- Prepared for simple and safe mountingof the RMS compact

Material- Sheet steel 1.5 mm

Finish- Powder-coated RAL 7021

Dark-grey

Supply schedule1 19“ Adapter front panel, 1HU

19” Adapter front panel

W H D Model Order no. UP

19” 44 1 06.108.130.8 1 unit

Dimensions in mm: W = Width HU = Standard height unitH = Height UP = Unit of packagingD = Depth kg = Weighth = Installation heightd = Useful depth = Express Article

Page 140: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

5.5

S Y S T E M M O N I T O R I N G

RMS20019 (similar to illustration)

Temperature/Humidity Sensor

Description- Insensitive to faults - No additional voltage supply required- Standard cable length, 4 m- Recalibration of the sensor not necessaryCalibration possible via configurationsoftware

Technical data- Temperature measuring range, 0-60°C- Accuracy: +/- 5%- Air measuring range 30-90°C- Accuracy: +/- 5%

Supply schedule1 Sensor with 4 m connection cable1 Mounting set

Temperature / air humidity sensor

Model Order no. UP

06.108.112.9 1 unit

RMS20005

Smoke Detector

Description- Visual smoke detector

German insurance accreditation (VdS)- For early detection of fire with smoke

build-up- Voltage supply via RMS compact- Standard cable length 4 m

Technical data- Operates from -20°C to +75°C

Supply schedule1 Sensor with 4 m connection cable1 Mounting set

Smoke detector

W H D Model Order no. UP

Ø 90 75 06.108.111.9 1 unit

RMS20006

Door Contact Sensor

Description- Magnet bridge sensor functions withevery magnetic conductive material (nospecial opposing object required)- Can also be used for monitoring sidepanels and roof- Standard cable length, 4 m

Technical data- Operates from -20°C to +70°C- Switching voltage, max. 200VDC- Switching current, max. 500mA

Supply schedule1 Sensor with 4 m connection cable1 Mounting set

Door contact sensor

W H D Model Order no. UP

06.108.115.9 1 unit

RMS20019 (similar to illustration)

Temperature Sensor

Description- Insensitive to faults - No additional voltage supply required- Standard cable length, 4 m- Recalibration of the sensor not necessaryCalibration possible via configurationsoftware

Technical data- Temperature measuring range, 0-60°C- Accuracy: +/- 5%

Supply schedule1 Sensor with 4 m connection cable1 Mounting set

Temperature sensor

Model Order no. UP

06.108.110.9 1 unit

Page 141: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

S Y S T E M M O N I T O R I N G

5.6

RMS20031

Water sensor

Description- Detection of presence water

Technical data- Operating voltage: max. 24 VDC

Supply schedule1 Sensor with 2 m connection cable1 Mounting bracket

W H D HU/U h d kg Model Order no. UP

06.108.117.9 1 unit

RMS20019

Shock sensor

Description- Detects vibrations- Protection against thievery- Reset with the Viewer-Software possible

Supply schedule1 Sensor with 4 m connection cable

W H D HU/U h d kg Model Order no. UP

06.108.113.9 1 unit

RMS20032

Passive infrared motion detector

Description- State of the art room monitoring

Technical data- German VdS-approval class A + B- Surface optics - range 2 - 16 m- Long distance optics 29 - 50 m- Curtain optics 17 - 30 m- Tamper monitoring- Digital fault evaluation- Corner or wallmounting

Supply schedule1 Sensor with 4 m connection cable1 Mounting set

W H D HU/U h d kg Model Order no. UP

06.108.114.9 1 unit

Page 142: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

6TechnicalSection 6.2 to 6.7

6.1

T E C H N I C A L S E C T I O N

Page 143: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

6.2

T E C H N I C A L S E C T I O N

Standards and Regulations

Protection ratings with enclosures (IP code)EN/IEC 60529

EMC Interference emission andEMC Interference immunity

EN 61000/55011/55022Protection of electronic equipment andsystems against electro-magnetic effects.The shielding protects against both theeffects of the external electro-magneticinfluence and the outward radiation ofelectro-magnetic energy.The shielding requires detailed know-howand extensive experience.

• The following should be taken intoaccount:- EMC justified construction- Highly-conductive surfaces- Material combinations with low potentialdifference- Low ohmic material connections- Seals- EMC Cable entry

Shielding measures on, for example, primusmodular chassis:

• Surface- Highly-conductive zinc passivated sheet

steel

– Shielding and optimal ventilation withsuitable perforation

– Optimal bonding of the side panels to thetop/bottom cover

– The bonding of front panel and rear panelon the modular chassis is made via theEMC spring

First SecondID Shock-hazard Foreign object ID Water protectiondigit protection protection digit

0 No special protection 0 No specialprotection

1 Against large-area Large foreign 1 Against verticallybody surfaces objects falling water

Diameter› 50 mm

2 Against finger or Medium-sized 2 Against diagonallysimilar size objects foreign objects falling water

Diameter (up to 15” vertical› 12 mm deviation)

3 Against tools, Small foreign 3 Against spalsh waterwires and similar objects (any direction,objects with dia. of Diameter up to 60º deviation› 2.5 mm › 2.5 mm from the vertical)

4 Against tools, Grainy foreign 4 Against spalsh waterwires and similar objects from all directionsobjects with dia. of Diameter› 1 mm › 1 mm

5 Full Dust-protected; 5 Against sprayedprotection dust deposits are from a nozzle,

permitted, but they are from all directionsnot allowed to build upand impair the function-ing of the equipment.

6 Fullprotection Dust-proof 6 Against flooding

7 Against immersion

8 Against submersion

Page 144: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

6.3

T E C H N I C A L S E C T I O N

Heat transferVDE 0660 Part 507, process fordetermining heating(identical to IEC 890)

LUF00083

LUF00087

Determining via diagram (alternative)

P0 = k x A x (Ti – Tu) (W)

- P0 Output that can be dissipated over therack surface

- k Heat transfer coefficient ~5 W/m2 K single-skinned3 W/m2 K double-skinned1 W/m2 K double-skinned insulated

- A Effective rack surface area- Ti Internal rack temperature- Tu Envir. air temperature- ∆T = Ti - Tu (K) Temperature difference- P0 › 0 : Heat output

- P0 ‹ 0 : Heat absorption

Examplek = 5 W/m2 K (sheet steel)A = 5.38 m2

Ti = 40º CTu = 20º C

P0 = 5 x 5.38 x (40 – 20) = 538W

There are 5 heat transfer options dependingon the dissipation power available. Selectionand dimensioning are made taking the envi-ronmental conditions into account, dependingon the istallation site (IP protection, noiselevel, room size and climate conditioning etc.)

1. Over the Rack Surface

Single enclosure, all sides,stand-aloneA = 1.8xHx(W+D)+1.4xWxD

Single enclosure, for wallmountingA = 1.4xWx(H+D)+1.8xDxH

Beginning-end enclosure,stand-aloneA = 1.4xDx(H+W)+1.8xWxH

Beginning-end enclosure,for wall mountingA = 1.4xHx(W+D)+1,4xWxD

Centre enclosure,stand-aloneA = 1.8xWxH+1.4xWxD+DxH

Centre enclosure, for wallmountingA = 1.4xWx(H+D)+DxH

Centre enclosure for wallmounting with covered roofsurfaceA = 1.4xWxH+0.7xWxD+DxH

Enclosure configuration in accordance with IEC 890

B = SchaltschrankbreiteH = SchaltschrankhöheT = Schaltschranktiefe

Calculation of the effective rack surface

P0 (W)

A (m2)

∆T

Page 145: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E C H N I C A L S E C T I O N

6.4

2. Direct Heat Exchange with Fans

Calculation of the required airflow volume

V = f (h) x Pv / ∆T (m3/h)

- V Required airflow volume- PV Dissipation power in the rack- Ti Internal rack temperature- Tu Envir. air temperature- ∆ T = Ti - Tu (K) Temperature

difference, Ti › Tu

- fh Auxiliary factor

ExamplePV = 1500 WTi = 35º CTu = 25º Ch = 1000 m

V = 3.5 x 1500/(35 – 25) = 525 m3/h

LUF00075 LUF00077

LUF00088

Determining via diagram

3. Heat Exchanger, Air / Air

Calculation of the required cooling output

QK = Pv – P0 (W)

- QK Required cooling output of the heatexchanger

- PV Dissipation power in the rack- P0 Output that can be dissipated over the

rack surface

ExamplePV = 1300 WP0 = 538 WTi = 40º CTu = 20º C (Ti › Tu)A = 5.38 m2

QK = 1300 – 538 = 762 W

LUF00080

V (m3/h)

PV (W)

∆T

Dependence h to f

h (m) f (m3k/wh)

0-100 3.1

100-250 3.2

250-500 3.3

500-750 3.4

750-1000 3.5

Page 146: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

6.5

T E C H N I C A L S E C T I O N

i.e. the device is sufficiently dimensioned forthe above-mentioned use

LUF00089

Determining via diagram

QK = - 1200 W

4. Cooling Unit with Refrigerant

Calculation of the required cooling output

QK = Pv – P0 (W)

- QK Required cooling output of the coolingunit

- PV Dissipation power in the rack- P0 Output that can be dissipated over the

rack surface

Worth notingAs in this case Ti = Tu › Ti is possible, theheat transfer output P0 can also benegative

Examplek = 5 W/m2

K x 1A = 5.38 m2

Ti = 30º CTu = 35º CPV = 500 W

P0 = k x A x (Ti – Tu) = – 134.5 WQk = PV– P0 = 500 – (– 134.5) = 634.5W

LUF00080LUF00082

i.e. the device is sufficiently dimensioned forthe above-mentioned use

LUF00090

Determining via diagram

QK = - 800 W

Qk (W)

Tu (K)

Qk (W)

Tu (°C)

Ti

Page 147: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

T E C H N I C A L S E C T I O N

6.6

Calculation of the required cooling output

QK = Pv – P0 (W)

- QK Required cooling output of the heatexchanger

- PV Dissipation power in the rack- P0 Output that can be dissipated over the

rack surface

Worth notingAs in this case Ti = Tu › Ti is possible, theheat transfer output P0 can also benegative

Examplek = 5 W/m2 k x 1A = 5.38 m2

PV = 1000 WTi = 30º CTu = 35º C

P0 = k x A x (Ti – Tu) = – 134.5 WQk = PV– P0 = 1000 – (– 134.5) = 1134.5W

Ti = 30º C(Tu = 35º)TW = 15º C

The environmental temperature has no influ-ence on the cooling output of the air/waterheat exchanger, but the water temperature TWdoes

LUF00255

5. Heat Exchanger, Air / Water

i.e. the device is sufficiently dimensioned forthe above-mentioned use

LUF00091

Determing via diagram

QK = - 1500 W

QK (W)

TW (°C)

Page 148: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

6.7

T E C H N I C A L S E C T I O N

Fire behaviour

• FlammabilityUL 94, The Standard for Flammability ofPlasic Materials for Parts in Devices andApplications equates with IEC 60607,60695-11-10, 60695-11-20, ISO 9772 and9773

• Ignition Resistance UL 746A, TheStandard for Polymeric Materials is similar to IEC 60112, 60695 and 60950.

DRAHTGEFLECHT

ca.45°

DRAHTGEFLECHT

PROBE

FTI20F

100 ± 1 mm

25 ± 1 mm

45 ± 2°

10 ± 1 mm

Set-up for investigating horizontal fire behaviour and vertical fire behaviour

Horizontal fire behaviour Vertical fire behaviour

PROBE

100 ± 1 mm

20 ± 1 mm

300 ± 10 mm

6 mm max.

ca. 50 mm

BAUMWOLLE

BUNSENBRENNER

Main criteria for foammaterial: Main criteria:

HBFBurning speed not › 40 mm / min. over100 mm burn length, self-extinguishingbefore the 125 mm point

• Heat of combustion in rescue routesVDE 0108Heat of combustion in rescue routes,maximum 7 kWh/m2, with use of halogen-free light plastic-sheathed leads andcables (VDE 0250,0266) with improved firebehaviour 14 VDE kWh/m2

HF1 HF2

Reheat time 80% ‹2s ‹2s

100% ‹10s ‹10s

Afterglow time m 30s m 30s

Burning drip no permitted

• Classifications in accordance with UL 94Vertical: Six classes for materials

that are frequently used inenclosures, structure com-ponents and insulators:5VA, 5VB, V-0, V-1, V-2, HBThree classes for thin filmmaterial: VTM-0, VTM-1,VTM-2

Horizontal: Three classes for foammaterial: HF-1, HF-2, HBF

V_0 V-1 V-2

Reheat time ‹10s ‹30s ‹30s

Overall burn time ‹50s ‹250s ‹250s

Burning drip no no permitted

Page 149: ttaalogloguue ac - Knurr USA · - and we respond with quality, flexi-bility, speed and perfect service. ... Rectifier/DC Power and Backup Systems Strong points Technical data Products

I N D E X

6.8

A

Access controlAccessories dart fan unit 3.10Accessories miracel EMCdouble panelled 1.27

Accessories miracel EMCsingle panelled 1.17

Accessories Outdoor Systems 2.18Accessories Outdoor Wall Case 2.27Accessories RMS 5.4Accessories smaract 19”

Compact Rack 1.42ACU Air Conditioning Unit Indoor 3.12ACU Air Conditioning Unit Outdoor 3.19

B

Battery Tray Outdoor Systems 2.18Battery Tray Outdoor Wall Case 2.27

C

Cable Entry Panel Outdoor Systems 2.20Compact Rack 1.37Connection Panel smaract 1.48, 1.49

1.51, 1.52Cooling Unit Indoor 3.12Cooling Unit Indoor 1000W 3.12Cooling Unit Indoor 1400W 3.14Cooling Unit Indoor 820W 3.13Cooling Unit Outdoor 3.19

D

dart fan unit 3.6DC-UPS 4.1Distribution Box 4.10Door Contact Sensor 5.5Door Contact Switch Outdoor Systems 2.19

E

EMC 19” Rack 1.12EMC 19” Rack doubled panelled 1.12EMC 19” Rack single panelled 1.21ETS Rack 1.31Extrusions Outdoor Systems 2.18

F

Fan unit 3.6Filter Box shielded 2.20Filter for dart fan 3.10

H

Heat Exchanger Indoor 3.10Heat Exchanger Indoor 1000W 3.10Heat Exchanger Indoor 2000W 3.11Heat Exchanger Outdoor 3.18Heating Unit Outdoor 3.20Humidity Sensor 5.5

I

Indoor systems 1.1Infrared Detector 5.6

L

Lamp Outdoor Systems 2.19

M

miracel 19” Rack 1.5miracel EMC 19” Rack 1.12miracel EMC 19”Rack doubled panelled 1.12miracel EMC 19”Rack single panelled 1.21miracel IP55 1.11Mounting Panel Outdoor Systems 2.21

O

Outdoor Systems 2.1

P

Plinth Outdoor Systems 2.20Plinth smaract 1.45Power Distribution 4.10Power Supplies 3.1Power System 1200-7200W 4.8Power System 200-1000W 4.5Power System 25W 4.9Power System 750-3750W 4.7

R

Rack Monitoring System 5.1Rear Panel smaract 1.49, 1.52RMScompact 5.1

S

Sensoric 5.5Shock Sensor 5.6“smaract 19”” Compact Rack” 1.37“smaract 19”” Enclosure EMC” 1.47“smaract 19”” Enclosure IP54” 1.50Smoke Sensor 5.5Street Cabinet 2.11

T

Tecoras Tecoras Cooling Unit 3.19Tecoras Heat Exchanger 3.18Tecoras Outdoor Cabinet 2.3Tecoras Outdoor Cabinet Add-On 2.8Tecoras Outdoor Cabinet Basic 2.7Tecoras Outdoor Cabinet Double Door 2.8Tecoras Outdoor Cabinet HEC 2.9Tecoras Outdoor Wall Case 2.23Tecoras Street Cabinet 2.11Tecoras Street Cabinet Fan 2.16Tecoras Street Cabinet HEC 2.17Tecoras Street Cabinet SC 2.15Temperature Sensor 5.5Thermal Management 3.1Thermal Management Indoor 3.3Thermal Management Outdoor 3.15

W

Wall Case 2.23Wall Mounting Kit Outdoor Wall Case 2.28Water Sensor 5.6