TROUBLESHOOTING COMPRESSORS
PROBLEM AREAS WHICH CAUSE COMPRESSOR
FAILURES :
FLOODING OF LIQUID REFRIGERANT INTO CCASE
FLOODED START
SLUGGING OF LIQUID REFRIGERANT / OIL INTO THECOMPRESSION AREAS OF THE COMPR.
LOSS OF LUBRICATION
CONTAMINATION OF REFR. SYSTEM WITH AIR, MOISTUREOR DIRT.
OVERHEATING OF THE COMPR. MOTOR, CYLINDER HEADVALVES, BEARINGS.
ELECTRICAL IRREGULARITIES IN VOLTAGE & CURRENT.
INCORRECT INSTALLATION.
-
8/13/2019 Troubleshooting Refr Systems
2/12
Sept. 2007 D.RAVINDRA
COMPRESSOR PROBLEMS
SYMPTOMS
NOISE
FAILURE TO PUMP PROPERLY OVERHEATING
MECHANICAL SEIZURE
FAILURE TO START
-
8/13/2019 Troubleshooting Refr Systems
3/12
Sept. 2007 D.RAVINDRA
REFRIGERANT FLOODBACK
LIQUID REFRIGERANT FINDS ITS WAY TO THE COMPRESSORDURING RUNNING CYCLE.
INTERNAL SYMPTOMS
WORN PISTONS, RINGS, CYLINDER WALLS, WRIST PINS /
HOLES, SCORED / BROKEN RODS, BEARINGS. DRAGGING ROTOR, SPOTBURNED MOTOR.
CORRECTION
ADJUST TEV TO INCREASE SUPERHEAT.
REDUCE CHARGE IN AN OVERCHARGED CAPILLARYSYSTEM.
CHECK IF COOLING LOAD IS TOO LOW.
USE SUCTION LINE ACCUMULATOR.
-
8/13/2019 Troubleshooting Refr Systems
4/12
Sept. 2007 D.RAVINDRA
REFRIGERANT MIGRATION
REFRIGERANT MIGRATES INTO COMPRESSOR
DURING OFF-CYCLE.
INTERNAL SYMPTOMS
BOTTOM BEARING WORN / SCORED.
DAMAGED INTERNAL COMPONENTS. FLOODED START.
CORRECTION
LIMIT REFRIGERANT CHARGE.
LOCATE COMPRESSOR IN WARM AMBIENT. USE CRANKCASE HEATER.
ADOPT PUMP DOWN CYCLE.
-
8/13/2019 Troubleshooting Refr Systems
5/12
Sept. 2007 D.RAVINDRA
SLUGGING
COMPRESSOR ATTEMPTING TO COMPRESS LIQUIDREFRIGERANT / OIL.
INTERNAL SYMPTOMS
BROKEN RODS AND / OR CRANKSHAFT, VALVE REEDS.
BLOWN CYLINDER HEAD & VALVE PLATE GASKET. LOOSE CYLINDER BOLTS.
CORRECTION
SAME AS FOR FLOODBACK AND MIGRATION. .
-
8/13/2019 Troubleshooting Refr Systems
6/12
Sept. 2007 D.RAVINDRA
OVERHEATING
INTERNAL SYMPTOMS VARNISHED, DISCOLOURD VALVE PLATE.
CAKED CARBON IN DISCHARGE AREA.
WORN RINGS, PISTONS, CYLINDERSM, REAR BEARINGS.
OVERHEATED VALVE REEDS. DISCOLOURED LUBRICANT.
CAUSES RAISE SUCTION PRESSURE, LOWER DISCHARGE
PRESSURE. REDUCE SUPERHEAT OF INCOMING SUCTION GAS.
INSULATE SUCTION LINE TO REDUCE HEAT PICK-UP.
OIL COOLER / LIQUID INJECTION.
-
8/13/2019 Troubleshooting Refr Systems
7/12Sept. 2007 D.RAVINDRA
AIR-COOLED CONDENSERS
PROBLEM
HIGH HEAD PRESSURE : COMPR. TRIPS ON HP SWITCH.
LOW HEAD PRESSURE
CAUSES / CORRECTION DIRTY , CLOGGED COIL : CLEAN COIL.
RESTRICTED AIR INLET / OUTLET.
SHORT CYCLING OF HOT DISCHARGE AIR.
FAN SPEED LOW / REVERSE ROTATION.
NON-CONDENSIBLES IN SYSTEM.
OVERCHARGING OF REFRIGERANT.
LOW AMBIENT TEMPERATURES : HEAD PRESSURE
CONTROL.
-
8/13/2019 Troubleshooting Refr Systems
8/12Sept. 2007 D.RAVINDRA
AIR-COOLED EVAPORATORS
PROBLEM
INADEQUATE COOLING CAPACITY.
FROSTING OR ICING OF COIL.
LOW SUCTION PRESSURE.
LOW TEMP. OF AIR OFF THE COIL.
CAUSES / CORRECTION
DIRTY , CLOGGED COIL : CLEAN COIL.
DIRTY AIR FILTERS.
RESTRICTED AIR INLET / OUTLET.
FAN SPEED LOW / REVERSE ROTATION. LOW REFRIGERANT CHARGE. .
UNVEVEN DISTRIBUTION TO COIL CIRCUITS.
-
8/13/2019 Troubleshooting Refr Systems
9/12
Sept. 2007 D.RAVINDRA
UNEVEN REFRIGERANT DISTRIBUTION TO
EVAPORATOR CIRCUITS
SYMPTOMS
SHORTAGE OF COOLING CAPACITY
NO CONDENSATION ON SOME EVAP. CIRCUITS
SOME CIRCUITS DRY, SOME SWEATING & SOME
FROSTED ON SAME EVAPORATOR COIL.
CAUSES
PLUGGED OR RESTRICTED DISTRIBUTOR TUBES
DISTRIBUTOR NOZZLE (ORIFICE) IMPROPERLY SIZED.
UNEVEN AIRFLOW OVER EVAPORATOR COIL.
-
8/13/2019 Troubleshooting Refr Systems
10/12
Sept. 2007 D.RAVINDRA
HUNTING OF EXPANSION VALVE
HUNTING IS A PHENOMENON OF UNSTABLE EXPANSIONVALVE OPERATION.
SYMPTOMS
UNSTABLE EVAPORATING PRESSURE
UNSTABLE SUCTION SUPERHEAT.
CAUSES
OVERSIZED EXPANSION VALVE
STICKING OR BINDING EXPANSION VALVE PARTS
LIGHT COOLING LOAD RAPID CHANGES IN COOLING LOAD
RAPID CHANGES IN CONDENSING TEMP. / PRESSURE.
INTERMITTENT FLASHING OF REFRIGERANT IN LIQUID LINE.
LONG EVAPORATOR REFRIGERATION CIRCUITS.
-
8/13/2019 Troubleshooting Refr Systems
11/12
Sept. 2007 D.RAVINDRA
EXPANSION VALVE OVERFEEDS
REFRIGERANT TO EVAPORATOR
SYMPTOMS INADEQUATE SUPERHEAT OR NO SUPERHEAT LIQUID FLOODBACK TO COMPRESSOR
LIQUID SLUGGING
EXCESSIVE OIL FOAMING IN COMPRESSOR CRANKCASE
CAUSES EXPANSION VALVE STUCK IN OPEN POSITION
OVERSIZED EXPANSION VALVE
SUPERHEAT SETTING ON VALVE TOO LOW
IMPROPER LOCATION OF SENSING BULB SENSING BULB LOOSE (NOT CLAMPED ON EVP OUTLET)
WRONG TYPE OF VALVE FOR THE REFRIGERANT USED
LIGHT COOLING LOAD
EXCESS OIL IN THE SYSTEM
-
8/13/2019 Troubleshooting Refr Systems
12/12
Sept. 2007 D.RAVINDRA
EXPANSION VALVE UNDERFEEDS
REFRIGERANT TO EVAPORATOR
SYMPTOMS HIGH SUPERHEAT
SHORTAGE OF COOLING CAPACITY
LOW COMPRESSOR DISCHARGE PRESSURE / TEMPERATURE
CAUSES EXPANSION VALVE STUCK IN CLOSED POSITION
LOSS OF GAS CHARGE IN POWER ELEMENT OF EXPN. VALVE
SUPERHEAT SETTING ON VALVE TOO HIGH
IMPROPER LOCATION OF SENSING BULB OF EXPN. VALVE
PLUGGED PRESSURE EQUALIZER LINE
WRONG TYPE OF VALVE FOR THE REFRIGERANT USED
INADEQUATE REFRIGERANT CHARGE IN SYSTEM
PLUGGED REFRIGERANT FILTER-DRIER / DISTRIBUTOR