    TROUBLESHOOTING COMPRESSORS

    PROBLEM AREAS WHICH CAUSE COMPRESSOR

    FAILURES :

    FLOODING OF LIQUID REFRIGERANT INTO CCASE

    FLOODED START

    SLUGGING OF LIQUID REFRIGERANT / OIL INTO THECOMPRESSION AREAS OF THE COMPR.

    LOSS OF LUBRICATION

    CONTAMINATION OF REFR. SYSTEM WITH AIR, MOISTUREOR DIRT.

    OVERHEATING OF THE COMPR. MOTOR, CYLINDER HEADVALVES, BEARINGS.

    ELECTRICAL IRREGULARITIES IN VOLTAGE & CURRENT.

    INCORRECT INSTALLATION.

  • 8/13/2019 Troubleshooting Refr Systems

    2/12

    Sept. 2007 D.RAVINDRA

    COMPRESSOR PROBLEMS

    SYMPTOMS

    NOISE

    FAILURE TO PUMP PROPERLY OVERHEATING

    MECHANICAL SEIZURE

    FAILURE TO START

  • 8/13/2019 Troubleshooting Refr Systems

    3/12

    Sept. 2007 D.RAVINDRA

    REFRIGERANT FLOODBACK

    LIQUID REFRIGERANT FINDS ITS WAY TO THE COMPRESSORDURING RUNNING CYCLE.

    INTERNAL SYMPTOMS

    WORN PISTONS, RINGS, CYLINDER WALLS, WRIST PINS /

    HOLES, SCORED / BROKEN RODS, BEARINGS. DRAGGING ROTOR, SPOTBURNED MOTOR.

    CORRECTION

    ADJUST TEV TO INCREASE SUPERHEAT.

    REDUCE CHARGE IN AN OVERCHARGED CAPILLARYSYSTEM.

    CHECK IF COOLING LOAD IS TOO LOW.

    USE SUCTION LINE ACCUMULATOR.

  • 8/13/2019 Troubleshooting Refr Systems

    4/12

    Sept. 2007 D.RAVINDRA

    REFRIGERANT MIGRATION

    REFRIGERANT MIGRATES INTO COMPRESSOR

    DURING OFF-CYCLE.

    INTERNAL SYMPTOMS

    BOTTOM BEARING WORN / SCORED.

    DAMAGED INTERNAL COMPONENTS. FLOODED START.

    CORRECTION

    LIMIT REFRIGERANT CHARGE.

    LOCATE COMPRESSOR IN WARM AMBIENT. USE CRANKCASE HEATER.

    ADOPT PUMP DOWN CYCLE.

  • 8/13/2019 Troubleshooting Refr Systems

    5/12

    Sept. 2007 D.RAVINDRA

    SLUGGING

    COMPRESSOR ATTEMPTING TO COMPRESS LIQUIDREFRIGERANT / OIL.

    INTERNAL SYMPTOMS

    BROKEN RODS AND / OR CRANKSHAFT, VALVE REEDS.

    BLOWN CYLINDER HEAD & VALVE PLATE GASKET. LOOSE CYLINDER BOLTS.

    CORRECTION

    SAME AS FOR FLOODBACK AND MIGRATION. .

  • 8/13/2019 Troubleshooting Refr Systems

    6/12

    Sept. 2007 D.RAVINDRA

    OVERHEATING

    INTERNAL SYMPTOMS VARNISHED, DISCOLOURD VALVE PLATE.

    CAKED CARBON IN DISCHARGE AREA.

    WORN RINGS, PISTONS, CYLINDERSM, REAR BEARINGS.

    OVERHEATED VALVE REEDS. DISCOLOURED LUBRICANT.

    CAUSES RAISE SUCTION PRESSURE, LOWER DISCHARGE

    PRESSURE. REDUCE SUPERHEAT OF INCOMING SUCTION GAS.

    INSULATE SUCTION LINE TO REDUCE HEAT PICK-UP.

    OIL COOLER / LIQUID INJECTION.

  • 8/13/2019 Troubleshooting Refr Systems

    7/12Sept. 2007 D.RAVINDRA

    AIR-COOLED CONDENSERS

    PROBLEM

    HIGH HEAD PRESSURE : COMPR. TRIPS ON HP SWITCH.

    LOW HEAD PRESSURE

    CAUSES / CORRECTION DIRTY , CLOGGED COIL : CLEAN COIL.

    RESTRICTED AIR INLET / OUTLET.

    SHORT CYCLING OF HOT DISCHARGE AIR.

    FAN SPEED LOW / REVERSE ROTATION.

    NON-CONDENSIBLES IN SYSTEM.

    OVERCHARGING OF REFRIGERANT.

    LOW AMBIENT TEMPERATURES : HEAD PRESSURE

    CONTROL.

  • 8/13/2019 Troubleshooting Refr Systems

    8/12Sept. 2007 D.RAVINDRA

    AIR-COOLED EVAPORATORS

    PROBLEM

    INADEQUATE COOLING CAPACITY.

    FROSTING OR ICING OF COIL.

    LOW SUCTION PRESSURE.

    LOW TEMP. OF AIR OFF THE COIL.

    CAUSES / CORRECTION

    DIRTY , CLOGGED COIL : CLEAN COIL.

    DIRTY AIR FILTERS.

    RESTRICTED AIR INLET / OUTLET.

    FAN SPEED LOW / REVERSE ROTATION. LOW REFRIGERANT CHARGE. .

    UNVEVEN DISTRIBUTION TO COIL CIRCUITS.

  • 8/13/2019 Troubleshooting Refr Systems

    9/12

    Sept. 2007 D.RAVINDRA

    UNEVEN REFRIGERANT DISTRIBUTION TO

    EVAPORATOR CIRCUITS

    SYMPTOMS

    SHORTAGE OF COOLING CAPACITY

    NO CONDENSATION ON SOME EVAP. CIRCUITS

    SOME CIRCUITS DRY, SOME SWEATING & SOME

    FROSTED ON SAME EVAPORATOR COIL.

    CAUSES

    PLUGGED OR RESTRICTED DISTRIBUTOR TUBES

    DISTRIBUTOR NOZZLE (ORIFICE) IMPROPERLY SIZED.

    UNEVEN AIRFLOW OVER EVAPORATOR COIL.

  • 8/13/2019 Troubleshooting Refr Systems

    10/12

    Sept. 2007 D.RAVINDRA

    HUNTING OF EXPANSION VALVE

    HUNTING IS A PHENOMENON OF UNSTABLE EXPANSIONVALVE OPERATION.

    SYMPTOMS

    UNSTABLE EVAPORATING PRESSURE

    UNSTABLE SUCTION SUPERHEAT.

    CAUSES

    OVERSIZED EXPANSION VALVE

    STICKING OR BINDING EXPANSION VALVE PARTS

    LIGHT COOLING LOAD RAPID CHANGES IN COOLING LOAD

    RAPID CHANGES IN CONDENSING TEMP. / PRESSURE.

    INTERMITTENT FLASHING OF REFRIGERANT IN LIQUID LINE.

    LONG EVAPORATOR REFRIGERATION CIRCUITS.

  • 8/13/2019 Troubleshooting Refr Systems

    11/12

    Sept. 2007 D.RAVINDRA

    EXPANSION VALVE OVERFEEDS

    REFRIGERANT TO EVAPORATOR

    SYMPTOMS INADEQUATE SUPERHEAT OR NO SUPERHEAT LIQUID FLOODBACK TO COMPRESSOR

    LIQUID SLUGGING

    EXCESSIVE OIL FOAMING IN COMPRESSOR CRANKCASE

    CAUSES EXPANSION VALVE STUCK IN OPEN POSITION

    OVERSIZED EXPANSION VALVE

    SUPERHEAT SETTING ON VALVE TOO LOW

    IMPROPER LOCATION OF SENSING BULB SENSING BULB LOOSE (NOT CLAMPED ON EVP OUTLET)

    WRONG TYPE OF VALVE FOR THE REFRIGERANT USED

    LIGHT COOLING LOAD

    EXCESS OIL IN THE SYSTEM

  • 8/13/2019 Troubleshooting Refr Systems

    12/12

    Sept. 2007 D.RAVINDRA

    EXPANSION VALVE UNDERFEEDS

    REFRIGERANT TO EVAPORATOR

    SYMPTOMS HIGH SUPERHEAT

    SHORTAGE OF COOLING CAPACITY

    LOW COMPRESSOR DISCHARGE PRESSURE / TEMPERATURE

    CAUSES EXPANSION VALVE STUCK IN CLOSED POSITION

    LOSS OF GAS CHARGE IN POWER ELEMENT OF EXPN. VALVE

    SUPERHEAT SETTING ON VALVE TOO HIGH

    IMPROPER LOCATION OF SENSING BULB OF EXPN. VALVE

    PLUGGED PRESSURE EQUALIZER LINE

    WRONG TYPE OF VALVE FOR THE REFRIGERANT USED

    INADEQUATE REFRIGERANT CHARGE IN SYSTEM

    PLUGGED REFRIGERANT FILTER-DRIER / DISTRIBUTOR