Trouble-Free ERV
Trouble-Free ERVfor over 20 years!
Trouble-Free ERV
What is RenewAire?
An advanced static-plate exchanger
Trouble-Free ERV
What does RenewAire do?
1. Transfers heat by conduction2. Transfers humidity using
hydroscopic resin
Trouble-Free ERV
Proven Technology
The largest selling ERV technology in the world for over 30 years
A leader in the North American market since 1983
10s of thousands of successful installations large and small RenewAire EV450
Trouble-Free ERV
Kuala Lumpur Point Barrow
Trouble-Free ERV
Why is ventilation necessary?Applicable local codesInternational Mechanical Code
• Requires “balanced” exhaust and make-upASHRAE 62 engineering standard for
“Acceptable Indoor Air Quality”Codes requiring energy recovery
• Ohio, Minnesota, CanadaSolve IAQ problems
Trouble-Free ERV
HOURS
05/26/951.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0M 1 2 3 4 5 6 7 8 9 10 11 N 1 2 3 4 5 6 7 8 9 10 11 M
PP
M C
O2
(T
HO
US
AN
DS
)
PRESCHOOL FACILITY- Before RenewAire HE450
OSHA800 PPMCO2 LIMIT
ASHRAE-1000 PPM CO2 LIMIT
IAQ - Case Study
Trouble-Free ERV
HOURS
05/28/951.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0M 1 2 3 4 5 6 7 8 9 10 11 N 1 2 3 4 5 6 7 8 9 10 11 M
PP
M C
O2
(T
HO
US
AN
DS
)
PRESCHOOL FACILITY- After RenewAire HE450 Installation
OSHA800 PPMCO2 LIMIT
ASHRAE-1000 PPM CO2 LIMIT
IAQ Case Study
TIME CLOCK TURNED OFF - HE450
TIME CLOCK TURNED OFF - HE450
TIME CLOCK TURNED OFF - HE450
TIME CLOCK TURNED OFF - HE450
Trouble-Free ERV
EPA “Tools for Schools”
Ventilation is a critical component
www.epa.gov/iaq
Trouble-Free ERV
Hospitality IAQ
Accommodation of smokers and non-smokers in bars and restaurants
Full time ventilation requirements 24/365 in hotels and motels
High ventilation rates in dedicated smoking areas, casinos and private clubs and lodges
Trouble-Free ERV
IAQ Case Study
Prime Time Sports Bar
Smoke control for patrons and employees
Trouble-Free ERV
Hospitality Industry IAQ
ERV is #1 recommendation
www.pmoptions.com
Trouble-Free ERV
Target MarketSchoolsMedical and veterinary clinicsNursing HomesHospitality facilities that accommodate
smokersFacilities with multiple ventilation
requirements
Trouble-Free ERV
Flushes Out ContaminantsDries Excess MoistureDispels OdorsCAN COST A LOT
But Ventilation with Energy Recovery Minimizes That Cost
CONVENTIONAL VENTILATION
Trouble-Free ERV
ERVs versus HRVsHeat Recovery Ventilators (HRVs) transfer
temperature differential only• Aluminum and plastic plate exchangers and
heat pipes
• Good for high humidity and high temperature applications
• Positive air stream separation
• Not often used for general building ventilation because of low efficiency
Trouble-Free ERV
HRVs Shortcomings?
Complex controls
Seasonal
•Adds humidity to the building in summer
Condensate pan and drain requiredActive defrost required anywhere north of FloridaLow overall efficiency
Temperature exchange only
Lifebreath 700 FD
Trouble-Free ERV
ERVs versus HRVs
Energy Recovery Ventilators (ERVs) transfer temperature and humidity differential• Desiccant wheels and enthalpic plate units• Best in cold climates and hot humid climates• High temperature and humidity transfer
efficiency• Not used for indoor pools etc.
Trouble-Free ERV
How are Wheels Vulnerable?
Complex controls
Cross contamination - purge air requiredParasitic power consumptionHigh (expensive) maintenanceFailure mode impacts HVAC load
•Wheel stops, recovery stops•Failure=100% outside air
Air leakage at seals – Lost Air
Semco FV2000
Trouble-Free ERV
Wheel Leakage Effects
Me
dia
Ro
tati
on
Exhaust Air
Outdoor AirDiameter Seals=Contamination
Circumference Seals= Lost Efficiency
Trouble-Free ERV
Lost Air EffectsSEMCO FV600 Not ARI Certified – SEMCO data
Outdoor Air Fresh Air Supply
Exhaust Air Room Air
PURGE AIR (150 CFM )
Me
dia
Ro
tati
on
450 CFM
Wheel Cross Section
600 CFM
600 CFM
450 CFM
Pressure = 0.00 Exhaust Air Transfer = 0.04% OACF = 1.33
Trouble-Free ERV
ARI-1060-2000
Air-to-Air Energy Recovery Ventilation Equipment Product Certification
Trouble-Free ERV
What is Certified?The energy recovery componentPerformance at “Standard Conditions”
• Winter - OA= 35°Fdb, 33°FwbRA= 70°Fdb, 58°Fwb
• Summer - OA= 95°Fdb, 78°FwbRA= 75°Fdb, 63°Fwb
Airflow, pressure drop, effectiveness, purge air (OACF), and cross contamination (EATR)
Trouble-Free ERV
Lost Air EffectsMicrometl ERV-AA Rated Airflow = 500CFM
Outdoor Air Fresh Air Supply
Exhaust Air Room Air
PURGE AIR (165 CFM )
Me
dia
Ro
tati
on
500 CFM
Wheel Cross Section
665 CFM
665 CFM
500 CFM
Pressure = 0.00 Exhaust Air Transfer = 0.2% OACF = 1.33
Trouble-Free ERV
Lost Air EffectsMicrometl ERV-AA Rated Airflow = 500CFM
Outdoor Air Fresh Air Supply
Exhaust Air Room Air
PURGE AIR (295 CFM )
Me
dia
Ro
tati
on
500 CFM
Wheel Cross Section
795 CFM
795 CFM
500 CFM
Pressure = +0.5 Exhaust Air Transfer = 0.0% OACF = 1.59
Trouble-Free ERV
Lost Air EffectsMicrometl ERV-AA Rated Airflow = 500CFM
Outdoor Air Fresh Air Supply
Exhaust Air Room Air
PURGE AIR (10 CFM )
Me
dia
Ro
tati
on
500 CFM
Wheel Cross Section
510 CFM
510 CFM
500 CFM
Pressure = -0.5 Exhaust Air Transfer = 9.9% OACF = 1.02
Trouble-Free ERV
Wheel Performance - A Delicate Balance
Low Efficiency
Low Cross Contamination High Efficiency
High Cross Contamination
Ventilation System Design
Trouble-Free ERV
Wheel Performance - A Delicate Balance
Low Efficiency
Low Cross Contamination High Efficiency
High Cross Contamination
Ventilation System Design
Trouble-Free ERV
Without Regular, Professional Service
System Failure !
Trouble-Free ERV
“Lost Air” is Significant in Wheels
Small wheels 15-30% purge air and still some exhaust air transfer
Small wheels over 50% purge air to achieve 0.0 exhaust air transfer
Large wheels typically 10-20%
Trouble-Free ERV
Desiccant Degradation
ARI-1060 testing was conducted on a desiccant wheel exchanger from a major US manufacturer
The unit was removed for testing after being used for an equivalent of four years in a residential application
Aged performance was compared to certified data for the product
Trouble-Free ERV
Desiccant Degradation Con’tCross leakage of exhaust air into fresh air
(EATR) increased from 10.0% to 19.5%, an increase of 95%
Sensible exchange efficiency decreased from 75.0% to 70%, a decrease of 7% due to increased leakage
Total exchange efficiency decreased from 70% to 58%, a decrease of 17% due mainly to desiccant degradation
Trouble-Free ERV
ARI Tests Clean Wheels
Close-up of wheel surface
H²O
H²O H²O
H²O
CO²
CO²
CO²
Formaldehyde
Trouble-Free ERV
Dirty Wheels Don’t Expose Desiccant
Close-up of wheel surface
H²O
H²OH²O
H²O
CO²
CO²
CO²
Formaldehyde
Trouble-Free ERV
Wheel Maintenance is Critical
Air-X-Change recommends buying a replacement wheel with each unit to switch out for cleaning
Seal adjustment and replacement
Trueing wheel
Belt or drive adjustment or replacement
Trouble-Free ERV
RenewAire is…
A clear alternative to
the wheel
Trouble-Free ERV
EV450
Positive air stream separation
No condensate or defrost
Simple to maintain
Reliable long term operation
RenewAire Static Plate ERV
Trouble-Free ERV
Certified Performance
Safety and durability - UL
Residential product performance - HVI
Commercial product performance - ARI
Trouble-Free ERV
Lost Air EffectsRenewAire EV450 Rated Airflow = 450 CFM
Outdoor Air
Exhaust Air Fresh Air Supply
450 CFM
Core Cross Section
459 CFM
459 CFM
Room Air
450 CFM
Pressure = 0.0 Exhaust Air Transfer = 0.0% OACF = 1.02
Trouble-Free ERV
Trouble-Free ERV
Trouble-Free ERV
Trouble-Free ERV
Trouble-Free ERV
RenewAire is a Proven Stable Technology To Build your Ventilation Design On!
Low Cross ContaminationHigh Efficiency
Ventilation System Design
Trouble-Free ERV
RenewAire Allows Equipment Downsizing
10 ton AC = 4000 CFM
25% OA = 1000 CFM
Load imposed by OA= Approx. 4 tons
Savings with RenewAire= Approx. 2.5 tons
Can provide same AC capacity with a 7.5 ton AC unit!!
Trouble-Free ERV
Simple Maintenance
Trouble-Free ERV
vs. Laminar FlowTurbulent Flow
Straight Air Passages •Laminar Flow•Doesn’t clog
Typical Velocity•200 - 500 ft./ min.
Static pressure loss•0.3 - 1.3 inch
RenewAire Technology
Trouble-Free ERV
Does the RenewAire Core Foul with Particulate?
As you can see particulate will mat on the low velocity entering faces of the core.
Trouble-Free ERV
Note that the air passages have no particulate accumulation.
Trouble-Free ERV
After vacuum cleaning with soft brush- air flow is fully restored.
Trouble-Free ERV
RenewAire
Core Warranty
Plus, Two year parts & manufacturing quality
warranty
Trouble-Free ERV
A Complete Line of Static-Plate ERVs
Residential and Small Commercial
Applied Products
RTEC – Roof Top End Connect
Outdoor Commercial
Indoor Commercial
“C” - Series (cabinet) 500-20,000 CFM “P” – Series (panelized) 1,500-unlimited CFM
Requires blowers and manifolds by others
5 models 250-3,700 CFM 1 or 3 phase multi-voltage 24 volt control
Available transition for various brand rooftop units
7 models 250-7,950 CFM 1 or 3 phase multi-voltage 24/120/230 volt control
Available vertical or horizontal duct connections
5 models 100-500 CFM Built-in 24 volt transformer/relay package
V H 11 models 250-7,950 CFM
1 or 3 phase multi-voltage 24/120/230 volt control
Trouble-Free ERV
Example
Integrated ERV/Fan Coil
in School Classroom
Trouble-Free ERV
Example
Integrated ERV/VAV box
in School Classroom
Trouble-Free ERV
Twenty-seven Twenty-seven EV450 units above EV450 units above suspended ceilingsuspended ceiling
Yellow Medicine East High School, MN
School Retrofit Installation
Trouble-Free ERV
HE2X900V with Packaged
Fan Coil
Wingspread
Trouble-Free ERV
Hospitality – Hotel Installation
Woodfield Suites
Madison, Wisconsin
Six roof-top stand-alone units- 24hr, 365 day operation
Trouble-Free ERV
School New Construction
Ballentine Elementary School
Columbia, South Carolina
Fourteen RTEC ERVs tied into Carrier and ICP roof top units
Trouble-Free ERV
ROOFTOP END- CONNECT SYSTEMS
ROOFTOP END- CONNECT SYSTEMS
Trouble-Free ERV
Tying the RTEC ERV and Rooftop a/c unit together
+ + +
RTEC RTEC ERVERV
FlangeFlange ScoopScoopRooftop Rooftop
a/ca/c
=Problem Solved
Trouble-Free ERV
HE900RTEC Connected to Trane Rooftop A/C
Trouble-Free ERV
C-Series Assembly of RenewAire cores in Stackable Cabinet500 CFM up to 4400 CFM
Up to five units can be stacked for up to 22,000 CFM
• Equipped with Standard 2” Pleated Filters• Double Wall Construction Available• Uses Separate Blowers
Custom & Applied Products
Trouble-Free ERV
Manifold Stack -(3)- C3000 Units
RETURN AIR
(from space)
SUPPLY AIR
(to space)
Packaged Air Conditioning Unit
Fresh Air Blower
Service Area
Exhaust Air Blower
OUTSIDE AIR
EXHAUSTAIR
RenewAire Applied Products
Cabinet - “C” Series - ERV Installed in Air Handling System
RenewAire
Trouble-Free ERV
Cabinet - “C” Series - ERV Installed in Air Handling System
Bob Johnson Hockey Training Facility
Trouble-Free ERV
Healthcare – Hospital Installation
Applied Products:two P3003 and two P3002
Holy Family HospitalManitowoc, Wisconsin
Trouble-Free ERV
RenewAire: Competitive Advantages
ARI Certified 0% cross contaminationWarranted against core degradation
for 10 yearsLowest maintenance costsFull commercial and residential lineCompetitive pricing