transformers - grand power systems · the daykin enclosed machine tool transformers will...

23
TRANSFORMERS by

Upload: others

Post on 12-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

TRANSFORMERS

by

Page 2: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

TRANSFORMERS

Grand Power Systems/Daykin Electric Corporation has designed a line of dry type transformers of the highest dependability. Our design engineers specify only quality materials to maximize the best electrical and thermal characteristics for years of reliable service. All Grand Power Systems line of Daykin transformers utilize 100% copper windings, premium grade silicon core steel, a superior insulation system and convenient terminations. The Grand Power Systems line of Daykin transformers meet or exceed all applicable , NEMA and Automotive Standards.

DAYKIN TRANSFORMERS

Please contact the factory for certified Transformer requirements.

Page 3: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

MACHINE TOOL & INDUSTRIAL CONTROL

SINGLE PHASE – OPEN CONSTRUCTION

Features

• and Listed (File No. E105527)• 100% copper windings• High quality silicon steel core material• Slotted mounting for easy installation• Easy access terminals that protect from

accidental electrical contact

• 55 degree centigrade temperature rise• Cooler operating temperature• Superior secondary voltage regulation

• 115 degree centigrade temperature rise• Outstanding secondary voltage regulation• Compact size

Machine Tool Transformer – TASeries Industrial Control Transformer – TFSeries

Page 4: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

MACHINE TOOL

SINGLEPHASE OPEN CONSTRUCTION – TASERIES – 55° C RISE

Primary240/480V230/460V220/440V

Secondary 120V 50/60 Hz 115V 50/60 Hz 55°C Rise 110V 50/60 Hz

PartNo.

VARating

A B C D E F

TA251 250 4.88 4.50 4.00 3.31 3.75 0.188 x 0.375TA501 500 5.25 5.25 4.50 4.00 4.38 0.281 x 0.406TA751 750 5.63 6.38 5.50 3.63 5.31 0.281 x 0.563

TA1001 1000 6.63 6.38 5.50 4.63 5.31 0.281 x 0.563TA1501 1500 7.88 6.38 5.50 6.25 5.31 0.281 x 0.563TA2001 2000 8.75 7.50 6.50 6.56 5.50 0.375 x 1.000TA3001 3000 9.50 7.50 6.50 7.31 5.50 0.375 x 1.000TA5001 5000 10.75 9.00 9.00 7.56 6.50 0.375 x 1.000

TASeries

Primary 480/575V Secondary 115V 50/60 Hz 55° C Rise

PartNo.

VARating

A B C D E F

TA251K 250 4.88 4.50 4.00 3.31 3.75 0.188 x 0.375TA501K 500 5.25 5.25 4.50 4.00 4.38 0.281 x 0.406TA751K 750 5.63 6.38 5.50 3.63 5.31 0.281 x 0.563

TA1001K 1000 6.63 6.38 5.50 4.63 5.31 0.281 x 0.563TA1501K 1500 7.88 6.38 5.50 6.25 5.31 0.281 x 0.563TA2001K 2000 8.75 7.50 6.50 6.56 5.50 0.375 x 1.000TA3001K 3000 9.50 7.50 6.50 7.31 5.50 0.375 x 1.000TA5001K 5000 10.75 9.00 9.00 7.56 6.50 0.375 x 1.000

TA-KSeries

Pri.208/220/230/240V380/400/416/440/460/480V500/550/575/600V

Sec.85/91/95/99V100/110/115/120V 50/60/Hz 55°C Rise125/130V

PartNo.

VARating

A B C D E F

TA251U 250 5.13 4.50 4.00 3.63 3.75 0.188 x 0.375TA501U 500 5.50 5.25 4.50 4.19 4.38 0.281 x 0.406TA751U 750 5.63 6.38 5.50 3.63 5.31 0.281 x 0.563

TA1001U 1000 6.63 6.38 5.50 4.63 5.31 0.281 x 0.563TA1501U 1500 7.88 6.38 5.50 6.25 5.31 0.281 x 0.563TA2001U 2000 9.00 7.50 6.50 6.82 5.50 0.375 x 1.000TA3001U 3000 9.63 7.50 6.50 7.44 5.50 0.375 x 1.000TA5001U 5000 10.75 9.00 9.00 7.56 6.50 0.375 x 1.000

TA-U Series

Page 5: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

INDUSTRIAL CONTROL

SINGLEPHASE OPEN CONSTRUCTION – TF SERIES –115° C RISE

Primary240/480V230/460V220/440V

Secondary120V 50/60 Hz115V 50/60 Hz 115°C Rise110V 50/60 Hz

PartNo.

VARating

A B C D E F

TF251 250 4.00 4.50 4.00 2.56 3.75 0.188 x 0.375TF501 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF751 750 5.38 5.25 4.50 4.00 4.38 0.281 x 0.406

TF1001 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

TF Series

Primary 480/575V Secondary 115V 50/60 Hz 55° C Rise

PartNo.

VARating

A B C D E F

TF251K 250 4.00 4.50 4.00 2.56 3.75 0.188 x 0.375TF501K 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF751K 750 5.38 5.25 4.50 4.00 4.38 0.281 x 0.406

TF1001K 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501K 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001K 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001K 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001K 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

TF-K Series

Pri.208/220/230/240V380/400/416/440/460/480V500/550/575/600V

Sec.85/91/95/99V100/110/115/120V 50/60 Hz 115°C Rise125/130V

PartNo.

VARating

A B C D E F

TF251U 250 4.63 4.50 4.00 3.13 3.13 0.188 x 0.375TF501U 500 5.13 5.25 4.50 3.63 4.38 0.281 x 0.406TF751U 750 6.00 5.25 4.50 4.56 4.38 0.281 x 0.406

TF1001U 1000 6.00 6.38 5.50 4.00 5.31 0.281 x 0.563TF1501U 1500 6.50 6.38 5.50 4.75 5.31 0.281 x 0.563TF2001U 2000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF3001U 3000 8.50 7.50 6.50 6.50 5.50 0.375 x 1.000TF5001U 5000 9.25 9.00 9.00 6.50 6.50 0.375 x 1.000

TF-U Series

Page 6: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

INDUSTRIAL CONTROL

SINGLEPHASE OPEN CONSTRUCTION – TF SERIES –115° C RISETF-J Series

Primary 230/460/575V Secondary 115V 50/60 Hz 115°C Rise

PartNo.

VARating

A B C D E F

TF501J 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF1001J 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501J 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001J 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001J 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001J 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

Primary 380V Secondary 110V 50/60 Hz 115°C Rise

PartNo.

VARating

A B C D E F

TF501L 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF1001L 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501L 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001L 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001L 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001L 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

TF-L Series

Primary 208V Secondary 120V 50/60 Hz 115°C Rise

PartNo.

VARating

A B C D E F

TF501M 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF1001M 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501M 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001M 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001M 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001M 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

TF-MSeries

Primary 460V Secondary 230VCT 50/60 Hz 115°C Rise

PartNo.

VARating

A B C D E F

TF501Q 500 4.50 5.25 4.50 3.06 4.38 0.281 x 0.406TF1001Q 1000 5.38 6.38 5.50 3.25 5.31 0.281 x 0.563TF1501Q 1500 6.00 6.38 5.50 4.25 5.31 0.281 x 0.563TF2001Q 2000 6.88 6.38 5.50 4.94 5.31 0.281 x 0.563TF3001Q 3000 7.63 7.50 6.50 5.63 5.50 0.375 x 1.000TF5001Q 5000 8.50 9.00 9.00 5.44 6.50 0.375 x 1.000

TF-Q Series

Page 7: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

MACHINE TOOL & INDUSTRIAL CONTROL

SINGLEPHASE – ENCLOSED

Features

The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected by a metal enclosure. This construction is particularly suitable where dirt or dust are present.

Keyhole note: 1000 VA and 1500 VA – 3/8” bolt 2000 VA through 7500 VA – 1/2” bolt.

• All copper windings

• Keyhole mounting for easy installation.

• Lifting holes for convenient mounting.

• Large cover and spacious connection compartment for ease of wiring.

• Epoxy encapsulated to protect against environment.

• High efficiency and excellent regulation.

• Flexible insulated lead wire, 12” length.

• insulation system (File No. 95780)

Page 8: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

MACHINE TOOL & INDUSTRIALCONTROL

SINGLEPHASE – ENCLOSEDTA-E Series

Primary240/480V230/460V220/440V

Secondary120V 50/60 Hz115V 50/60 Hz 55°C Rise 110V 50/60 Hz

PartNo.

VARating

A B C D E N

TA1001E 1000 12.25 7.63 8.50 5.38 6.56 2.25TA1501E 1500 12.25 7.63 8.50 5.38 6.56 2.25TA2001E 2000 13.75 8.75 9.38 6.50 7.88 2.31TA3001E 3000 13.75 8.75 9.38 6.50 7.88 2.31TA5001E 5000 17.25 10.25 10.63 7.88 11.00 2.50TA7501E 7500 17.25 10.25 10.63 7.88 11.00 2.50

TA-E Series

Primary240/480V230/460V220/440V

Secondary120V 50/60 Hz115V 50/60 Hz 155°C Rise 110V 50/60 Hz

PartNo.

VARating

A B C D E N

TF1001E 1000 12.25 7.63 8.50 5.38 6.56 2.25TF1501E 1500 12.25 7.63 8.50 5.38 6.56 2.25TF2001E 2000 12.25 7.63 8.50 5.38 6.56 2.25TF3001E 3000 13.75 8.75 9.38 6.50 7.88 2.31TF5001E 5000 17.25 10.25 10.63 7.88 11.00 2.50TF7501E 7500 17.25 10.25 10.63 7.88 11.00 2.50

TA-EK SeriesPrimary 480/575V Secondary 115V 50/60 Hz 55°C Rise

PartNo.

VARating

A B C D E N

TA1001EK 1000 12.25 7.63 8.50 5.38 6.56 2.25TA1501EK 1500 12.25 7.63 8.50 5.38 6.56 2.25TA2001EK 2000 13.75 8.75 9.38 6.50 7.88 2.31TA3001EK 3000 13.75 8.75 9.38 6.50 7.88 2.31TA5001EK 5000 17.25 10.25 10.63 7.88 11.00 2.50TA7501EK 7500 17.25 10.25 10.63 7.88 11.00 2.50

TF-EK SeriesPrimary 480/575V Secondary 115V 50/60 Hz 155°C Rise

PartNo.

VARating

A B C D E N

TF1001EK 1000 12.25 7.63 8.50 5.38 6.56 2.25TF1501EK 1500 12.25 7.63 8.50 5.38 6.56 2.25TF2001EK 2000 12.25 7.63 8.50 5.38 6.56 2.25TF3001EK 3000 13.75 8.75 9.38 6.50 7.88 2.31TF5001EK 5000 17.25 10.25 10.63 7.88 11.00 2.50TF7501EK 7500 17.25 10.25 10.63 7.88 11.00 2.50

Page 9: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

GENERAL PURPOSE

SINGLEPHASE OPEN & ENCLOSED CONSTRUCTION

Features

Daykin General Purpose Transformers are available in designs suitable for indoor or outdoor service. They are perfect for general applications such as lighting, heating and equipment loads in commercial, office buildings and industrial plants.

• Open construction available for use where adverse conditions do not exist or for mounting in existing enclosure.

• Enclosure construction available for use where dirt, corrosion or weather may be a factor.

• Enclosed units from 250 VA through 10 KVA are epoxy encapsulated in wall mount metal enclosures.

• Enclosed units from 15 KVAthrough 225 KVA are floor mount, ventilated construction.

• Many non-standard designs are available. Contact the factory for further information.

• insulation system (File No. 95780).

Page 10: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

GENERAL PURPOSE

SINGLEPHASE OPEN & ENCLOSED CONSTRUCTION

Primary 240/480V Secondary 120/240V 60 Hz TF 115°C Rise/TH 150°C Rise

KVARating

Open Enclosed

Part No. A B CConst.Type

Elec.Conn.

Part No. A B CConst.Type

Elec.Conn.

.250 TF250P 4.00 4.50 4.00 A GP1 TF250EP 9.25 5.50 6.13 B GP1

.500 TF500P 4.38 5.25 4.50 A GP1 TF500EP 10.25 6.25 6.75 B GP1

.750 TF750P 5.00 5.25 4.50 A GP1 TF750EP 10.25 6.25 6.75 B GP11.00 TF1000P 5.00 6.38 5.50 A GP1 TF1000EP 12.25 7.63 8.50 B GP11.5 TF1500P 5.50 6.38 5.50 A GP1 TF1500EP 12.25 7.63 8.50 B GP12 TF2000P 6.75 6.38 5.50 A GP1 TF2000EP 12.25 7.63 8.50 B GP13 TF3000P 7.00 7.50 6.50 A GP1 TF3000EP 13.75 8.75 9.38 B GP15 TF5000P 7.75 9.00 7.88 A GP1 TF5000EP 17.25 10.25 10.63 B GP1

7.5 TF7500P 9.00 9.00 7.88 A GP1 TF7500EP 17.25 10.25 10.63 B GP110 TF10000P 11.00 9.00 7.88 A GP1 TF10000EP 17.25 10.25 10.63 B GP115 TH15000P

ContactThe

Factory

A GP2 TH15000EP 22.25 16.25 14.25 C GP225 TH25000P A GP2 TH25000EP 24.25 20.25 18.25 C GP2

37.5 TH37500P A GP2 TH37500EP 24.25 20.25 18.25 C GP250 TH50000P A GP2 TH50000EP 24.25 20.25 18.25 C GP275 TH75000P A GP2 TH75000EP 27.25 25.25 24.25 C GP2

100 TH100000P A GP2 TH100000EP 27.25 25.25 24.25 C GP2

570/585/600 Volt

Primary 570/585/600V Secondary 120/240V 60 Hz 115° C Rise

KVARating

PartNumber

A B CConst.Type

1 TF1000EN-1017 12.25 7.63 8.50 B3 TF3000EN-1018 13.75 8.75 9.38 B5 TF5000EN-1019 17.25 10.25 10.63 B

7.5 TF7500EN-1020 17.25 10.25 10.63 B

Mulitple Volt

Primary 190/200/208/220/380/400/416/440V

Secondary 110/220V 50/60 Hz 115° C Rise

KVARating

PartNumber

A B CConst.Type

1 TF1000EN-1026 12.25 7.63 8.50 B3 TF3000EN-1027 13.75 8.75 9.38 B5 TF5000EN-1028 17.25 10.25 10.63 B

7.5 TF75000EN-1029 17.25 10.25 10.63 B

Single Phase Enclosed Construction

Single PhaseOpen & Enclosed Construction

Single PhaseEnclosed Construction

240/480 Volt

Page 11: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

GENERAL PURPOSE

THREEPHASE ENCLOSED

Features

• Large wiring compartment with access panel for convenient installation.

• All copper windings

• High quality silicon steel core for high efficiency and excellent performance.

• Available for indoor and outdoor service.

• Isolated windings for separate circuit protection.

• 3 KVA to 6 KVA Transformers are Type D construction.

• 9 KVA & Up Transformers are Type C construction.

• insulation system (File No. 95780)

Daykin Three Phase General Purpose Transformers are suitable for most installations. Typical applications include commercial, institutional, construction and industrial service

Applications

Options

• Open core and coil construction

• Electrostatic shield

• Special enclosures, including non-ventilated designs and galvanized construction

• Special voltage or frequency requirements

Contact the factory for more information on these and other special design requirements.

KVARating

480 Δ208Y / 120

480 Δ240Y / 139

240/480 Δ240Y / 139

240/480 Δ208Y / 120

480 Δ480Y / 277

600 Δ208Y / 120

600 Δ240Y / 139

480 Δ240 / 120CT

3 D3EA D3EB D3EC D3ED D3EF D3EJ D3EK D3EP6 D6EA D6EB D6EC D6ED D6EF D6EJ D6EK D6EP9 D9EA D9EB D9EC D9ED D9EF D9EJ D9EK D9EP

15 D15EA D15EB D15EC D15ED D15EF D15EJ D15EK D15EP25 D25EA D25EB D25EC D25ED D25EF D25EJ D25EK D25EP30 D30EA D30EB D30EC D30ED D30EF D30EJ D30EK D30EP

37.5 D37EA D37EB D37EC D37ED D37EF D37EJ D37EK D37EP45 D45EA D45EB D45EC D45ED D45EF D45EJ D45EK D45EP50 D50EA D50EB D50EC D50ED D50EF D50EJ D50EK D50EP75 D75EA D75EB D75EC D75ED D75EF D75EJ D75EK D75EP

100 D100EA D100EB D100EC D100ED D100EF D100EJ D100EK D100EP112.5 D112EA D112EB D112EC D112ED D112EF D112EJ D112EK D112EP150 D150EA D150EB D150EC D150ED D150EF D150EJ D150EK D150EP225 D225EA D225EB D225EC D225ED D225EF D225EJ D225EK D225EP

Elec. Conn. Pg. 16 1 1 3 3 1 1 1 2

Page 12: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

MOTOR DRIVE ISOLATION

THREEPHASE ENCLOSED

KVARating

MotorHP

Primary230V Delta

Primary460V Delta

Primary575V Delta

Secondary Secondary Secondary

230V Y 460V Y 230V Y 460V Y 230V Y 460V Y3 2 D3EN-895 D3EN-912 D3EN-929 D3EN-946 D3EN-963 D3EN-9806 3 D6EN-896 D6EN-913 D6EN-930 D6EN-947 D6EN-964 D6EN-981

7.5 5 D7EN-897 D7EN-914 D7EN-931 D7EN-948 D7EN-965 D7EN-98211 7.5 D11EN-898 D11EN-915 D11EN-932 D11EN-949 D11EN-966 D11EN-98315 10 D15EN-899 D15EN-916 D15EN-933 D15EN-950 D15EN-967 D15EN-98420 15 D20EN-900 D20EN-917 D20EN-934 D20EN-951 D20EN-968 D20EN-98527 20 D27EN-901 D27EN-918 D27EN-935 D27EN-952 D27EN-969 D27EN-98634 25 D34EN-902 D34EN-919 D34EN-936 D34EN-953 D34EN-970 D34EN-98740 30 D40EN-903 D40EN-920 D40EN-937 D40EN-954 D40EN-971 D40EN-98851 40 D51EN-904 D51EN-921 D51EN-938 D51EN-955 D51EN-972 D51EN-98963 50 D63EN-905 D63EN-922 D63EN-939 D63EN-956 D63EN-973 D63EN-99075 60 D75EN-906 D75EN-923 D75EN-940 D75EN-957 D75EN-974 D75EN-99193 75 D93EN-907 D93EN-924 D93EN-941 D93EN-958 D93EN-975 D93EN-992

118 100 D118EN-908 D118EN-925 D118EN-942 D118EN-959 D118EN-976 D118EN-993145 125 D145EN-909 D145EN-926 D145EN-943 D145EN-960 D145EN-977 D145EN-994175 150 D175EN-910 D175EN-927 D175EN-944 D175EN-961 D175EN-978 D175EN-995220 200 D220EN-911 D220EN-928 D220EN-945 D220EN-962 D220EN-979 D220EN-996

In addition to the above standard drive isolation transformers, Daykin has the capability of manufacturing isolation transformers for all major drives.

Features

• All copper windings

• Extra coil support to withstand mechanical forces associated with SCR drive duty cycles.

• Isolated windings to help deliver a clean wave to the drive and to aid in keeping SCRcontroller from sending transients into the line.

• Electrostatically shielded to reduce noise between the primary and secondary windings.

• Full capacity primary taps (1) 5% FCAN, (1) 5% FCBN

• insulation system (File No. 95780).

Page 13: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

GENERAL PURPOSE & MOTOR DRIVE ISOLATION

THREE PHASE ENCLOSED

SPECIFICATIONS AND DIMENSIONS

KVARating

Dimensions TemperatureRise (°C)

ConstructionTypeA B C

3 13.50 14.75 7.50 115 D

6 13.50 19.00 7.50 115 D

7.5 17.50 19.00 7.50 115 D

9 –15 22.25 16.25 14.25 115 C

20 –37.5 24.25 20.25 18.25 150 C

40 – 63 27.25 25.25 24.25 150 C

75 –150 32.25 29.25 28.25 150 C

175 – 225 46.25 31.25 28.25 150 C

Page 14: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

AUTOTRANSFORMERS

SINGLE & THREE PHASE OPEN & ENCLOSED CONSTRUCTIONWHEN A SIMPLE VOLTAGE ADJUSTMENT IS REQUIRED WITHOUT THE NEED FOR ISOLATIONThe Daykin Autotransformer is used when a simple voltage adjustment is required without the need for isolation. This device has only one winding per phase. Part of the winding is common to both primary and secondary circuits, thus providing no isolation.

Features

• insulation system (File No. E95780)

• All copper windings

• High quality silicon steel core material

• 150 degree centigrade temperature rise rating

• Compact size

• Non-isolated windings

Single Phase Enclosed

1-10 KVA in epoxy encapsulated enclosure

15-50 KVA in ventilated enclosure

Three Phase Enclosed

9 KVA in epoxy encapsulated enclosure

15-150 KVA in ventilated enclosure

KVARating

120/240/480V 120/240/600VOpen Enclosed Open Enclosed

1 TH1000N-1151 TH1000EN-1152 TH1000N-1167 TH1000EN-11683 TH3000N-1153 TH3000EN-1154 TH3000N-1169 TH3000EN-11705 TH5000N-1155 TH5000EN-1156 TH5000N-1171 TH5000EN-1172

7.5 TH7500N-1157 TH7500EN-1158 TH7500N-1173 TH7500EN-117410 TH10000N-1159 TH10000EN-1160 TH10000N-1175 TH10000EN-117615 TH15000N-1161 TH15000EN-1162 TH15000N-1177 TH15000EN-117825 TH25000N-1163 TH25000EN-1164 TH25000N-1179 TH25000EN-118050 TH50000N-1165 TH50000EN-1166 TH50000N-1181 TH50000EN-1182

Elec. Conn.Page 16 4 4 4 4

KVARating

240/480V Y 208/240/480/600V YOpen Enclosed Open Enclosed

9 D9N-1199 D9EN-1200 D9N-1217 D9EN-121815 D15N-1201 D15EN-1202 D15N-1219 D15EN-122025 D25N-1203 D25EN-1204 D25N-1221 D25EN-122230 D30N-1205 D30EN-1206 D30N-1223 D30EN-1224

37.5 D37N-1207 D37EN-1208 D37N-1225 D37EN-122650 D50N-1209 D50EN-1210 D50N-1227 D50EN-1228 75 D75N-1211 D75EN-1212 D75N-1229 D75EN-1230100 D100N-1213 D100EN-1214 D100N-1231 D100EN-1232150 D150N-1215 D150EN-1216 D150N-1233 D150EN-1234

Elec. Conn.Page 16 5 5 6 6

Single Phase 60 Hz

Three Phase 60 Hz

Page 15: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

CONSTANT VOLTAGE

SINUSOIDAL, HARMONIC NEUTRALIZED – TYPECVThe Daykin Constant Voltage Transformer will provide a highly regulated sine wave output with low harmonic distortion. This device is commonly used in applications where wave shape and voltage regulation are of primary importance.

• Voltage regulation ±3% for an input variation of ±15%

• Low harmonic distortion

• 500 VA through 3000 VA

• Input 120 VAC or 480 VAC

• NEMA 1 enclosed

• Single phase – 60 Hz

• Typical efficiency 90%

VARating

NominalInput Voltage

PartNumber

Approx.Wt. (LBS)

500 120 CV500-120 971000 120 CV1000-120 1251500 120 CV1500-120 1522000 120 CV2000-120 1713000 120 CV3000-120 239500 480 CV500-480 961000 480 CV1000-480 1241500 480 CV1500-480 1472000 480 CV2000-480 1803000 480 CV3000-480 223

Features

Type CV – 60 Hz Single Phase

120 Volt Output Regulated ±3%

Page 16: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

ELECTRICAL CONNECTIONS & SCHEMATICS

Page 17: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PART NUMBER EXPLANATION

T A

D 75 E

3001 E N

N

123*

123*

DESIGNATES SINGLE PHASE TRANSFORMER

TEMPERATURE RISE• A- 55° C RISE• B - 80° C RISE• F-115° C RISE• H-150° C RISE

ENCLOSED

NO SUFFIXFOR OPENCONSTRUCTION WITHTERMINALS

ENCLOSED

NO SUFFIXFOR OPENCONSTRUCTION WITHTERMINALS

VOLTAGE RATING

• N-NON STANDARD, MUST BE ACCOMPANIED BY 3 OR 4 DIGIT MFG. NO.*

• A–480 Δ – 208Y/120• B–480 Δ – 240Y• C–240/480 Δ – 240Y• D–240/480 Δ – 208-120Y• F–480 Δ – 480Y/277• J–600 Δ – 208Y/120• K–600 Δ – 240Y• P–480 Δ – 240YΔ/120 CT

4 WIRE

* NOTE: NON-STANDARD TEMP RISE NON-STANDARD VOLTAGE OR FREQUENCY STANDARD ENCLOSURE NON-STANDARD TAPS, SHIELDING, ETC. FUSE CLIP OPTION ON SECONDARY

VOLTAGE RATING

ACCOMPANIED BY 3 OR 4DIGIT MFG. NO.*• J-230/460/575 -115• K-460/575-115• L-380-110• M-208-120• P-240 x 480-240/120• Q-460-230 CT• U-UNIVERSAL PRI 208-600V SEC 85-130V• NO SUFFIX FOR 230/460 -115 TRIPLE RATED

VA RATING (3000)

KVARATING

DESIGNATES THREE PHASE TRANSFORMER

STANDARD THREE PHASETEMP CLASS: 1-5 KVA 115° C RISE

25 KVA UP 150° C RISE

STANDARD THREE PHASE FREQUENCY: 60 HERTZ

Page 18: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PRICE LIST 2019

MACHINE TOOL TRANSFORMERS SINGLE PHASE OPEN CONSTRUCTION . . . PAGE 4

INDUSTRIAL CONTROL TRANSFORMERS SINGLE PHASE OPEN CONSTRUCTION . . . PAGES 5 & 6

Note: Secondary fuses are not provided

TF-K SeriesPart No. VA Rating List PriceTF251K 250 $106.00

TF501K 500 $138.00

TF751K 750 $159.00

TF1001K 1000 $185.00

TF1501K 1500 $236.00

TF2001K 2000 $269.00

TF3001K 3000 $348.00

TF5001K 5000 $615.00

TF SeriesPart No. VA Rating List PriceTF251 250 $ 96.00

TF501 500 $125.00

TF751 750 $145.00

TF1001 1000 $169.00

TF1501 1500 $215.00

TF2001 2000 $245.00

TF3001 3000 $317.00

TF5001 5000 $559.00

TF-U SeriesPart No. VA Rating List PriceTF251U 250 $139.00

TF501U 500 $175.00

TF751U 750 $203.00

TF1001U 1000 $236.00

TF1501U 1500 $301.00

TF2001U 2000 $343.00

TF3001U 3000 $443.00

TF5001U 5000 $782.00

TF-J SeriesPart No.

VA Rating

List Price

TF501J 500 $146.00

TF1001J 1000 $178.00

TF1501J 1500 $229.00

TF2001J 2000 $255.00

TF3001J 3000 $349.00

TF5001J 5000 $792.00

TF-L SeriesPart No.

VA Rating

List Price

TF501L 500 $134.00

TF1001L 1000 $170.00

TF1501L 1500 $214.00

TF2001L 2000 $252.00

TF3001L 3000 $322.00

TF5001L 5000 $745.00

TF-M SeriesPart No.

VA Rating

List Price

TF501M 500 $135.00

TF1001M 1000 $171.00

TF1501M 1500 $215.00

TF2001M 2000 $253.00

TF3001M 3000 $323.00

TF5001M 5000 $746.00

TF-Q SeriesPart No.

VA Rating

List Price

TF501Q 500 $146.00

TF1001Q 1000 $178.00

TF1501Q 1500 $229.00

TF2001Q 2000 $255.00

TF3001Q 3000 $349.00

TF5001Q 5000 $792.00

TA-K SeriesPart No. VA Rating List PriceTA251K 250 $119.00

TA501K 500 $156.00

TA751K 750 $172.00

TA1001K 1000 $223.00

TA1501K 1500 $308.00

TA2001K 2000 $361.00

TA3001K 3000 $462.00

TA5001K 5000 $906.00

TA SeriesPart No. VA Rating List PriceTA251 250 $109.00

TA501 500 $142.00

TA751 750 $156.00

TA1001 1000 $203.00

TA1501 1500 $280.00

TA2001 2000 $328.00

TA3001 3000 $419.00

TA5001 5000 $823.00

TA-U SeriesPart No. VA Rating List PriceTA251U 250 $ 149.00

TA501U 500 $ 199.00

TA751U 750 $ 218.00

TA1001U 1000 $ 276.00

TA1501U 1500 $ 381.00

TA2001U 2000 $ 460.00

TA3001U 3000 $ 575.00

TA5001U 5000 $1,138.00

Page 19: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PRICE LIST 2019

MACHINE TOOL & INDUSTRIAL CONTROL TRANSFORMERS SINGLE PHASE ENCLOSED CONSTRUCTION . . . PAGE 8

TA-E SeriesPart No.

VA Rating

List Price

TA1001E 1000 $ 313.00TA1501E 1500 $ 351.00TA2001E 2000 $ 383.00TA3001E 3000 $ 474.00TA5001E 5000 $ 871.00TA7501E 7500 $1,070.00

TA-EK SeriesPart No.

VA Rating

List Price

TA1001EK 1000 $ 317.00TA1501EK 1500 $ 369.00TA2001EK 2000 $ 411.00TA3001EK 3000 $ 476.00TA5001EK 5000 $ 946.00TA7501EK 7500 $1,113.00

TF-E SeriesPart No.

VA Rating

List Price

TF1001E 1000 $250.00TF1501E 1500 $310.00TF2001E 2000 $400.00TF3001E 3000 $555.00TF5001E 5000 $776.00TF7501E 7500 $968.00

TF-EK SeriesPart No.

VA Rating

List Price

TF1001EK 1000 $ 275.00TF1501EK 1500 $ 342.00TF2001EK 2000 $ 440.00TF3001EK 3000 $ 611.00TF5001EK 5000 $ 854.00TF7501EK 7500 $1,066.00

GENERAL PURPOSE TRANSFORMERS SINGLE PHASE OPEN & ENCLOSED CONSTRUCTION . . PAGE 10

240/480 VoltPart No. KVA Rating List Price

– .250 –– .500 –– .750 –

TF1000P 1 $ 235.00TF1500P 1.5 $ 278.00TF2000P 2 $ 324.00TF3000P 3 $ 413.00TF5000P 5 $ 702.00TF7500P 7.5 $ 839.00

TF10000P 10 $1,293.00TH15000P 15

Contact The

Factory

TH25000P 25TH37500P 37.5TH50000P 50

– 75 –– 100 –

570/585/600 VoltPart No. KVA Rating List Price

TF1000EN-1017 1 $ 352.00TF3000EN-1018 3 $ 543.00TF5000EN-1019 5 $ 747.00TF7500EN-1020 7.5 $1,033.00

Multiple VoltPart No. KVA Rating List Price

TF1000EN-1026 1 $ 373.00TF3000EN-1027 3 $ 580.00TF5000EN-1028 5 $ 923.00TF7500EN-1029 7.5 $1,159.00

240/480 VoltPart No. KVA Rating List PriceTF250EP .250 $ 213.00TF500EP .500 $ 231.00TF750EP .750 $ 259.00

TF1000EP 1 $ 287.00TF1500EP 1.5 $ 331.00TF2000EP 2 $ 374.00TF3000EP 3 $ 465.00TF5000EP 5 $ 753.00TF7500EP 7.5 $ 891.00

TF10000EP 10 $1,344.00TH15000EP 15 $1,839.00TH25000EP 25 $2,732.00TH37500EP 37.5

Contact The

Factory

TH50000EP 50TH75000EP 75

TH100000EP 100

Page 20: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PRICE LIST 2019

KVA Rating

480 ∆ 208Y / 120

List Price

480 ∆ 240Y / 139

List Price

240/480 ∆ 240Y / 139

List Price

240/480 ∆ 208Y / 120

List Price

3 D3EA $ 844.00 D3EB $ 844.00 D3EC $ 886.00 D3ED $ 886.00

6 D6EA $1,060.00 D6EB $1,060.00 D6EC $1,114.00 D6ED $1,114.00

9 D9EA $1,197.00 D9EB $1,197.00 D9EC $1,258.00 D9ED $1,258.00

15 D15EA $1,428.00 D15EB $1,428.00 D15EC $1,500.00 D15ED $1,500.00

25 D25EA $1,880.00 D25EB $1,880.00 D25EC $1,974.00 D25ED $1,974.00

30 D30EA $2,155.00 D30EB $2,155.00 D30EC $2,263.00 D30ED $2,263.00

37.5 D37EA

Contact The

Factory

D37EB

Contact The

Factory

D37EC

Contact The

Factory

D37ED

Contact The

Factory

45 D45EA D45EB D45EC D45ED

50 D50EA D50EB D50EC D50ED

75 D75EA D75EB D75EC D75ED

100 D100EA D100EB D100EC D100ED

112.5 D112EA D112EB D112EC D112ED

150 D150EA D150EB D150EC D150ED

225 D225EA D225EB D225EC D225ED

KVA Rating

480 ∆ 480Y / 277

List Price

600 ∆ 208Y / 120

List Price

600 ∆ 240Y / 139

List Price

480 ∆ 240 / 120CT

List Price

3 D3EF $ 844.00 D3EJ $ 844.00 D3EK $ 844.00 D3EP $ 860.00

6 D6EF $1,060.00 D6EJ $1,060.00 D6EK $1,060.00 D6EP $1,082.00

9 D9EF $1,197.00 D9EJ $1,197.00 D9EK $1,197.00 D9EP $1,221.00

15 D15EF $1,428.00 D15EJ $1,428.00 D15EK $1,428.00 D15EP $1,457.00

25 D25EF $1,880.00 D25EJ $1,880.00 D25EK $1,880.00 D25EP $1,917.00

30 D30EF $2,155.00 D30EJ $2,155.00 D30EK $2,155.00 D30EP $2,198.00

37.5 D37EF

Contact The

Factory

D37EJ

Contact The

Factory

D37EK

Contact The

Factory

D37EP

Contact The

Factory

45 D45EF D45EJ D45EK D45EP

50 D50EF D50EJ D50EK D50EP

75 D75EF D75EJ D75EK D75EP

100 D100EF D100EJ D100EK D100EP

112.5 D112EF D112EJ D112EK D112EP

150 D150EF D150EJ D150EK D150EP

225 D225EF D225EJ D225EK D225EP

GENERAL PURPOSE TRANSFORMERS THREE PHASE ENCLOSED CONSTRUCTION . . . PAGE 11

Page 21: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PRICE LIST 2019

KVA Rating

Motor HP

Primary 230V Delta Primary 460V DeltaSecondary Secondary

230V Y List Price 460V Y List Price 230V Y List Price 460V Y List Price3 2 D3EN-895 $ 904.00 D3EN-912 $ 926.00 D3EN-929 $ 926.00 D3EN-946 $ 973.006 3 D6EN-896 $1,043.00 D6EN-913 $1,070.00 D6EN-930 $1,070.00 D6EN-947 $1,125.00

7.5 5 D7EN-897 $1,160.00 D7EN-914 $1,190.00 D7EN-931 $1,190.00 D7EN-948 $1,250.0011 7.5 D11EN-898 $1,332.00 D11EN-915 $1,366.00 D11EN-932 $1,366.00 D11EN-949 $1,435.0015 10 D15EN-899 $1,494.00 D15EN-916 $1,532.00 D15EN-933 $1,532.00 D15EN-950 $1,608.0020 15 D20EN-900 $1,877.00 D20EN-917 $1,925.00 D20EN-934 $1,925.00 D20EN-951 $2,021.0027 20 D27EN-901 $2,311.00 D27EN-918 $2,370.00 D27EN-935 $2,370.00 D27EN-952 $2,489.0034 25 D34EN-902 $2,613.00 D34EN-919 $2,681.00 D34EN-936 $2,681.00 D34EN-953 $2,815.0040 30 D40EN-903

Contact The

Factory

D40EN-920

Contact The

Factory

D40EN-937

Contact The

Factory

D40EN-954

Contact The

Factory

51 40 D51EN-904 D51EN-921 D51EN-938 D51EN-95563 50 D63EN-905 D63EN-922 D63EN-939 D63EN-95675 60 D75EN-906 D75EN-923 D75EN-940 D75EN-95793 75 D93EN-907 D93EN-924 D93EN-941 D93EN-958118 100 D118EN-908 D118EN-925 D118EN-942 D118EN-959145 125 D145EN-909 D145EN-926 D145EN-943 D145EN-960175 150 D175EN-910 D175EN-927 D175EN-944 D175EN-961220 200 D220EN-911 D220EN-928 D220EN-945 D220EN-962

KVA Rating

Motor HP

Primary 575V DeltaSecondary

230V Y List Price 460V Y List Price3 2 D3EN-963 $1,122.00 D3EN-980 $1,068.006 3 D6EN-964 $1,330.00 D6EN-981 $1,266.00

7.5 5 D7EN-965 $1,656.00 D7EN-982 $1,577.0011 7.5 D11EN-966 $1,874.00 D11EN-983 $1,785.0015 10 D15EN-967 $2,075.00 D15EN-984 $1,977.0020 15 D20EN-968 $2,569.00 D20EN-985 $2,447.0027 20 D27EN-969 $3,158.00 D27EN-986 $3,008.0034 25 D34EN-970 $3,572.00 D34EN-987 $3,402.0040 30 D40EN-971

Contact The

Factory

D40EN-988

Contact The

Factory

51 40 D51EN-972 D51EN-98963 50 D63EN-973 D63EN-99075 60 D75EN-974 D75EN-99193 75 D93EN-975 D93EN-992118 100 D118EN-976 D118EN-993145 125 D145EN-977 D145EN-994175 150 D175EN-978 D175EN-995220 200 D220EN-979 D220EN-996

MOTOR DRIVE ISOLATION TRANSFORMERS THREE PHASE ENCLOSED CONSTRUCTION... PAGE 12

Page 22: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

PRICE LIST 2019

AUTOTRANSFORMERS SINGLE & THREE PHASE OPEN & ENCLOSED CONSTRUCTION... PAGE 14

CONSTANT VOLTAGE TRANSFORMERS SINUSOIDAL, HARMONIC NEUTRALIZED - TYPE CV . . PAGE 15

120 Volt InputVA Rating Part Number List Price

500 CV500-120 $ 771.001000 CV1000-120 $ 994.001500 CV1500-120 $1,216.002000 CV2000-120 $1,439.003000 CV3000-120 $1,951.00

480 Volt InputVA Rating Part Number List Price

500 CV500-480 $ 807.001000 CV1000-480 $1,040.001500 CV1500-480 $1,278.002000 CV2000-480 $1,511.003000 CV3000-480 $2,049.00

KVA Rating

120/240/480V 120/240/600VOpen List Price Enclosed List Price Open List Price Enclosed List Price

1 TH1000N-1151 $ 238.00 TH1000EN-1152 $ 380.00 TH1000N-1167 $ 249.00 TH1000EN-1168 $ 391.003 TH3000N-1153 $ 314.00 TH3000EN-1154 $ 455.00 TH3000N-1169 $ 328.00 TH3000EN-1170 $ 470.005 TH5000N-1155 $ 382.00 TH5000EN-1156 $ 524.00 TH5000N-1171 $ 398.00 TH5000EN-1172 $ 541.00

7.5 TH7500N-1157 $ 466.00 TH7500EN-1158 $ 664.00 TH7500N-1173 $ 537.00 TH7500EN-1174 $ 680.0010 TH10000N-1159 $ 585.00 TH10000EN-1160 $ 800.00 TH10000N-1175 $ 616.00 TH10000EN-1176 $ 842.0015 TH15000N-1161 $ 766.00 TH15000EN-1162 $1,025.00 TH15000N-1177 $ 806.00 TH15000EN-1178 $1,078.0025 TH25000N-1163 $1,127.00 TH25000EN-1164 $1,191.00 TH25000N-1179 $1,051.00 TH25000EN-1180 $1,253.0050 TH50000N-1165 $1,498.00 TH50000EN-1166 $1,691.00 TH50000N-1181 $1,575.00 TH50000EN-1182 $1,779.00

Single Phase 60 Hz

KVA Rating

240/480V Y 208/240/480/600V YOpen List Price Enclosed List Price Open List Price Enclosed List Price

9 D9N-1199 $ 684.00 D9EN-1200 $ 835.00 D9N-1217 $ 867.00 D9EN-1218 $1,021.0015 D15N-1201 $ 797.00 D15EN-1202 $ 915.00 D15N-1219 $ 920.00 D15EN-1220 $1,038.0025 D25N-1203 $1,355.00 D25EN-1204 $1,498.00 D25N-1221 $1,378.00 D25EN-1222 $1,520.0030 D30N-1205 $1,507.00 D30EN-1206 $1,651.00 D30N-1223 $1,583.00 D30EN-1224 $1,725.00

37.5 D37N-1207 $1,569.00 D37EN-1208 $1,711.00 D37N-1225 $1,703.00 D37EN-1226 $1,844.0050 D50N-1209 $1,794.00 D50EN-1210 $1,859.00 D50N-1227 $2,231.00 D50EN-1228 $2,374.0075 D75N-1211 $2,846.00 D75EN-1212 $3,110.00 D75N-1229 $3,017.00 D75EN-1230 $3,281.00

100 D100N-1213 $3,046.00 D100EN-1214 $3,245.00 D100N-1231 $3,245.00 D100EN-1232 $3,444.00150 D150N-1215 $3,230.00 D150EN-1216 $3,538.00 D150N-1233 $3,700.00 D150EN-1234 $4,008.00

Three Phase 60 Hz

Page 23: TRANSFORMERS - Grand Power Systems · The Daykin Enclosed Machine Tool Transformers will accommodate most indoor applications. The coil and core are epoxy encapsulated and protected

by

GrandPowerSystems.com • Ph: (844) 383-8644 • [email protected]

FORMULAS & DEFINITIONS

TRANSFORMER DISCONNECT - NEMA 1 / IP22 GM2F1F SERIES

Autotransformer – is a transformer with one winding per phase. Part of the winding is common to both primary and secondary circuits, thus providing no isolation.Core Loss – Losses due to magnetization of the core and eddy currents produced within the core.Delta (Δ)– A common three phase connection in which the start of one winding is connected to the finish of the previous winding to form a closed loop.Dry Type Transformer – is a transformer which uses air as a cooling medium.Efficiency – The ratio of input power to output power usually expressed as a percentage.Electrostatic Shield – a grounded copper foil or sheet placed between two windings to reduce noise between the windings or the windings and ground.Exciting Current – The current which flows in the primary with the load disconnected, ie. The current necessary to energize the core.FCAN – Full capacity above normal taps.FCBN – Full capacity below normal taps.Impedance – The current limiting characteristic of a transformer, usually expressed as a percentage.Industrial Control Transformer – A transformer with excellent regulation and current inrush characteristics.Inrush Current – Initial start-up current of a device, usually exceeding the name plate rating.Insulating Transformer – Same as isolation transformer

Isolation Transformer – A transformer which insulates the primary winding from the secondary winding.KVA – Kilo volt ampere rating. Indicates the output a transformer can deliver.Machine Tool Transformer – A well regulated low reactance transformer. A low temperature rise and the best choice for very high inrush applications.Motor Drive Isolation Transformer – A three phase transformer specifically designed to match motor drive horsepower requirements and additional impedance.NEMA – National Electrical Manufacturers Association. Primary Winding – Source side winding of a transformer.Regulation (Voltage) – Is the difference between no load voltage and full load voltage and is usually expressed as a percentage.Secondary Winding – Load side winding of a transformer.Temperature Rise – Refers to the increase in operating temperature over ambient of a transformer due to load. Conventionally measured in degrees centigrade. – Underwriters Laboratories Inc. An independent testing organization. – UL listed to Canadian safety standardsWYE (Y) – A common secondary connection for three phase transformers in which the start of each winding is tied together. The load is then connected to the finish of each winding. Three phase autotransformers commonly use the WYE configuration.

KVA = Volts x Amps 1000

% Efficiency = Power Out x 100 Power In

Kilowatts = Volts x Amps x P. F. 1000

Horsepower = Volts x Amps x % Eff. x P. F. 746

Autotransformers

SINGLE PHASEKVA = Volts x Amps x 1.73 1000

% Efficiency = Power Out x 100 Power In

Kilowatts = Volts x Amps x 1.73 x P. F. 1000

Horsepower = Volts x Amps x 1.73 x % Eff. x P. F. 746

THREE PHASE