transformer size for large motor starting 1.6.14

6
:Transformer Detail: Transformer Size Transformer Secondary Voltage:(v2) % Impedance: (z) Allowable Voltage Drop in System: :Motor Detail ( Only One No of Motor): Motor Size: Volt (vm): (L-L) Power Factor: Motor KVA Motor Code: (Kva/Hp) InRush Current at Starting:(Enter If you know otherwise leave it blank) Enter Motor Full Load Current(Enter If you know otherwise leave it blank ) Motor Full Load Current: (ILM) Locaked Rotor Current Multiplier: (Min) Locaked Rotor Current Multiplier: (Max) Locaked Rotor Current (L1): (Min) Locaked Rotor Current (L2): (Max) Motor InRush KVA At Starting: (IrsM) How many times Motor Starts per Hours :Calculations: Full Load Current of Transformer : (ILX) Short Circuit Current at Transformer Secondary: (Isc) Max KVA of Transformer at Isc: Q1 Motor InRush KVA At Starting:(IrsM) Voltage Drop at Transformer Secondary Due to Motor inRush: (Vd) Transformer Secondary Voltage :Result: (1) Motor Full Load Current <= 65% Transformer Full Load Current (2) Voltage Drop at Transformer Secondary Due to Motor inRush (3) Transformer Size:(20% Added due to motor starts more than once/Hour) Size of Transformer is Adequate Calculation Formulas: ILX=KVA/(1.732xv2) ILM=(Kwx1000)/(1.732xVmxP.F) Isc=ILx/z Q1=(v2xISCxILMx1.732)/1000 IrsM=(VmxL2x1.732)/1000 Vd=IrsM/Q1 Code Letter (KVA per HP) -Locked Rotor Current Motor Code 1 A 2 B Calculate Transformer Size & Voltage drop due Motor

Upload: jithuraj

Post on 28-Jan-2016

229 views

Category:

Documents


1 download

DESCRIPTION

Tranformer sixzing

TRANSCRIPT

Page 1: Transformer Size for Large Motor Starting 1.6.14

:Transformer Detail:Transformer Size 1000 KVATransformer Secondary Voltage:(v2) 480 Volt% Impedance: (z) 5.75%Allowable Voltage Drop in System: 10%:Motor Detail ( Only One No of Motor):Motor Size: 300 KwVolt (vm): (L-L) 460 VoltPower Factor: 0.8Motor KVA 240 KVA

Motor Code: (Kva/Hp)

InRush Current at Starting:(Enter If you know otherwise leave it blank)Enter Motor Full Load Current(Enter If you know otherwise leave it blank )Motor Full Load Current: (ILM) 471 AmpLocaked Rotor Current Multiplier: (Min) 4.10Locaked Rotor Current Multiplier: (Max) 4.50Locaked Rotor Current (L1): (Min) 1930 AmpLocaked Rotor Current (L2): (Max) 2118 AmpMotor InRush KVA At Starting: (IrsM) 1687 KVAHow many times Motor Starts per Hours 2

:Calculations:Full Load Current of Transformer : (ILX) 1203 AmpShort Circuit Current at Transformer Secondary: (Isc) 20919 AmpMax KVA of Transformer at Isc: Q1 17391 KVAMotor InRush KVA At Starting:(IrsM) 1687 KVAVoltage Drop at Transformer Secondary Due to Motor inRush: (Vd) 10% 90%Transformer Secondary Voltage 433 Volt

:Result:(1) Motor Full Load Current <= 65% Transformer Full Load Current Yes(2) Voltage Drop at Transformer Secondary Due to Motor inRush Low(3) Transformer Size:(20% Added due to motor starts more than once/Hour) 1200 KvaSize of Transformer is Adequate

Calculation Formulas:ILX=KVA/(1.732xv2)ILM=(Kwx1000)/(1.732xVmxP.F)Isc=ILx/zQ1=(v2xISCxILMx1.732)/1000IrsM=(VmxL2x1.732)/1000Vd=IrsM/Q1

Code Letter (KVA per HP) -Locked Rotor CurrentMotor Code Min Max

1 A 3.152 B 3.16 3.55

Calculate Transformer Size & Voltage drop due to Starting of Large size MotorCalculate Transformer Size & Voltage drop due to Starting of Large size Motor

E24
If motor is to be started more than once per hour add 20% additional KVA
Page 2: Transformer Size for Large Motor Starting 1.6.14

3 C 3.56 44 D 4.1 4.55 E 4.6 56 F 5.1 5.67 G 5.7 6.38 H 6.4 7.19 J 7.2 8

### K 8.1 9### L 9.1 10### M 10.1 11.2### N 11.3 12.5### P 12.6 14### R 14.1 16### S 16.1 18### T 18.1 20### U 20.1 22.4### V 22.5

44.14.5

Page 3: Transformer Size for Large Motor Starting 1.6.14

:Transformer Detail:Transformer Size 1000Transformer Secondary Voltage:(v2) 480% Impedance: (z) 5.75%Allowable Voltage Drop in System: 10%:Motors Detail ( More Than One No of Motor):Total KW of Three Phase Motors: 300Total KW of Single Phase Motors: 5Volt: (L-L) 460Volt: (L-N) 266

Power Factor: 0.8

Locaked Rotor Current: (Max) 450%Total Three Phase Motors Full Load Current 471Total Single Phase Motors Full Load Current 24Total Motors Full Load Current 494Motor InRush KVA At Starting 1772

:Calculations:Full Load Current of Transformer : (IL) 1203Short Circuit Current at Transformer Secondary: (Isc) 20919Max KVA of Transformer at Isc 17391Motor InRush KVA At Starting 1772Voltage Drop at Transformer Secondary Due to Motor inRush 10.2%Transformer Secondary Voltage 431

:Result:(1) Motor Full Load Current <= 65% Transformer Full Load Current Yes(2) Voltage Drop at Transformer Secondary Due to Motor inRush High(3) Transformer Size: 1000Increase Size of Transformer

Jignesh.Parmar ,[email protected] , www.electricalnotes.wordpress.comCalculate Transformer Size & Voltage drop due to Starting of Large size MotorCalculate Transformer Size & Voltage drop due to Starting of Large size Motor

Page 4: Transformer Size for Large Motor Starting 1.6.14

KVAVolt

KwKwVoltVolt

AmpAmpAmpKVA

AmpAmpKVAKVA90%Volt

KVA

Jignesh.Parmar ,[email protected] , www.electricalnotes.wordpress.com