transformer outage rates, durations and … availability data...transformer voltage class: tads...

33
Outage Rates, Durations and Element Availability: Transformer Automatic and Non- Automatic Outages by Voltage Class Automatic Outages by Voltage Class Statistical Analysis Based on 2010-2013 TADS data Svetlana Ekisheva Senior Statistician Svetlana Ekisheva, Senior Statistician August 7, 2014

Upload: others

Post on 28-Feb-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Outage Rates, Durations and Element g ,Availability: Transformer Automatic and Non-Automatic Outages by Voltage ClassAutomatic Outages by Voltage Class

Statistical Analysis Based on 2010-2013 TADS dataSvetlana Ekisheva Senior StatisticianSvetlana Ekisheva, Senior Statistician August 7, 2014

Page 2: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Voltage Class: TADS Definition 1

1. Element 

The following are Elements for which TADS data are to beThe following are Elements for which TADS data are to be collected:   1. AC Circuits ≥ 200 kV (Overhead and Underground)

2 f i h 200 k l id l 2. Transformers with ≥ 200 kV low‐side voltage

3. AC/DC Back‐to‐Back Converters with ≥ 200 kV AC voltage, both sides

4. DC Circuits with ≥ +/‐200 kV DC voltage

An Element may also be referred to as a “TADS Element in the Manual. They have the same meaning.

htt // / /RAPA/t d /D t /2014 TADS Ahttp://www.nerc.com/pa/RAPA/tads/Documents/2014_TADS_Appendix_7%20041514.pdf

RELIABILITY | ACCOUNTABILITY2

Page 3: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Voltage Class: TADS Definition 13

• 13. Voltage Class 

The following voltages classes will be used for reporting purposes:The following voltages classes will be used for reporting purposes:  1. 200‐299 kV

2. 300‐399 kV

3 00 99 k 3. 400‐499 kV

4. 500‐599 kV

5. 600‐699 kV

For Transformers, the Voltage Class reported will be the high‐side voltage, even though the cut‐off voltage used in the definition is referenced on the low side Voltages are operating voltagesreferenced on the low‐side. Voltages are operating voltages.http://www.nerc.com/pa/RAPA/tads/Documents/2014_TADS_Appendix_7%20041514.pdf

RELIABILITY | ACCOUNTABILITY3

Page 4: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

2010-2013 TADS: Transformer Counts by Voltage Class

Transformers by Voltage Class (TADS 2010‐2013)

4%23%

13%

60%

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV

For the 200-299 kV voltage class only a subset of transformers (115.0 t f f 2010 2014) i t d i TADS

RELIABILITY | ACCOUNTABILITY4

transformer-years for 2010-2014) is reported in TADS

Page 5: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Automatic Outages(TADS 2010-2013)

Number of Transformer Outages (2010‐2013)

243

193

250

300

136

105100

150

200

14

62

3110

4929

0

50

100

0200‐299 kV 300‐399 kV 400‐599 kV 600‐799 kV All Transformers

 Automatic Sustained

RELIABILITY | ACCOUNTABILITY5

Page 6: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Average Annual Automatic Outage Rateper Transformer: Testing Homogeneity

0 120.14

Annual Outage Rate per Transformer by Voltage Class: Automatic vs. Sustained Outages (2010‐2013)

0.12

0.090.08 0.08 0.080.09

0.070.06

0.080.070.08

0.10

0.12

0 00

0.02

0.04

0.06

0.00200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

Automatic Outages Sustained

• All pair-wise annual automatic outage rate differences between voltage classes are not statistically significant

• All pair-wise annual sustained outage rate differences between lt l t t ti ti ll i ifi t

RELIABILITY | ACCOUNTABILITY6

voltage classes are not statistically significant

Page 7: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Average Annual Outage Ratesper Transformer by Voltage Class (2010-2013)

TADS Transformers: Annual Outage Rates per Transformer(2010‐2013)

0.11.3

1.6

3.0

1.7

All Transformers

0.1

1.3

2.4

1.7

2.9

1.8

3.0

400‐599 kV

600‐799 KV

0.1

0.1

0.91.01.1

300‐399 kV

0.10.30.4

0.5

0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5

200‐299 kV

RELIABILITY | ACCOUNTABILITY7

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5

All Outages Non‐Automatic Planned Operational Automatic Sustained

Page 8: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Average Outage Duration by Voltage Class (2010-2013)

Average Transformer Outage Duration (in Days) by Voltage Class (2010 2013)

17.6 17.2

14 6

17.7

16 0

18.0

20.0

by Voltage Class (2010‐2013) 

9.5

14.6

11.6

8.010.0

12.0

14.0

16.0

0 3

6.95.3

3.35.1

0 5

3.5

8.0

5.7

2 0

4.0

6.0

8.0

0.3 0.50.0

2.0

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

Automatic Sustained Planned Operational

RELIABILITY | ACCOUNTABILITY8

Automatic Sustained Planned Operational

Page 9: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Average Annual Non-Operational Time per Transformerby Voltage Class (2010-2013)

Average Annual Non‐Operational Time per T f (i D ) b V lt Cl (2010 2013)

13.414.0

16.0

Transformer (in Days) by Voltage Class (2010‐2013)

9.2 9.3 9.610.0

12.0

3.94.0

6.0

8.0

0.0

2.0

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

RELIABILITY | ACCOUNTABILITY9

200 299 kV 300 399 kV 400 599 kV 600 799 KV All Transformers

Page 10: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Mean Time of Continuous Operationby Voltage Class (2010-2013)

Mean Time of Continuous Operation (Days) for a Transformer by Voltage Class (TADS 2010‐2013)

680.8

600.0

700.0

800.0

316.2300 0

400.0

500.0

202.2

116.8

206.2

0 0

100.0

200.0

300.0

All MTOCOs by voltage class are statistically distinct

0.0200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

RELIABILITY | ACCOUNTABILITY10

Page 11: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Mean Time of Continuous OperationExcluding Non-Automatic Outages (2010-2013)

Mean Time of Continuous Operation excluding Non‐Operational Outages for a Transformer by 

V l Cl (i Y )

13 6

16.3

14.816.0

18.0

Voltage Class (in Years)

11.5

13.612.7

10.0

12.0

14.0

4.0

6.0

8.0

0.0

2.0

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

RELIABILITY | ACCOUNTABILITY11

All MTOCOs by voltage class are statistically equivalent

Page 12: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Unavailabilityby Voltage Class (2010-2013)

Transformer Unavailability by Outage Type by Voltage Class (2010 2013)

0.4%

3 0%

3.5%

4.0%

Class (2010‐2013)

0.6% 0.3%

1.2%

0.5%0.2% 0.3% 0.3%

1.5%

2.0%

2.5%

3.0%

1.0%1.7% 1.9% 2.1% 1.9%0.01%0.01%

0.0%

0.5%

1.0%

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

Transformer Unavailability due to Sustained outages

Transformer Unavailability due to Operational outages

RELIABILITY | ACCOUNTABILITY12

Transformer Unavailability due to Planned outages

Page 13: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Availabilityby Voltage Class (2010-2013)

TADS Transformer Availability  (2010‐2013)

98.9%

98.5%

99.0%

99.5%

97.5% 97.5% 97.4%

97 0%

97.5%

98.0%

96.3%

96.0%

96.5%

97.0%

95.0%

95.5%

200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All Transformers

RELIABILITY | ACCOUNTABILITY13

Page 14: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Unavailability by Year

Transformer Unavailability by Year ( )

3.00%

3.50%

(TADS 2010‐2013)

0.34%0.43%

0.57%

0.64%

0.33%

0.44% 0.06%

0.25%

1 50%

2.00%

2.50%

1.73%2.06% 2.18%

1.49%0.50%

1.00%

1.50%

0.00%2010 2011 2012 2013

Planned outages Operational outages Automatic sustained outages

RELIABILITY | ACCOUNTABILITY14

Page 15: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

200-299kV Transformers: Unavailability by Month

For the 200 299 kV voltage class only a subset of transformers (115 0

RELIABILITY | ACCOUNTABILITY15

For the 200-299 kV voltage class only a subset of transformers (115.0 transformer-years for 2010-2014) is reported in TADS

Page 16: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

300-399kV Transformers: Unavailability by Month

RELIABILITY | ACCOUNTABILITY16

Page 17: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

400-599kV Transformers: Unavailability by Month

RELIABILITY | ACCOUNTABILITY17

Page 18: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

600-799kV Transformers: Unavailability by Month

RELIABILITY | ACCOUNTABILITY18

Page 19: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformers: Unavailability by Month

RELIABILITY | ACCOUNTABILITY19

Page 20: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformers: Availability by Month

RELIABILITY | ACCOUNTABILITY20

Page 21: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

AC Circuit vs. TransformerAvailability by Year

TADS Element Availability by Year 

98.3%

98.1%98.0%

98.2%

98 0%98.2%98.4%98.6%

97.6%

97 1%97.2%

97.6%

97.4%97.6%97.8%98.0%

97.1%

96.6%96.8%97.0%97.2%

96.4%2010 2011 2012 2013

AC circuit Availability Transformer Availability

RELIABILITY | ACCOUNTABILITY21

Page 22: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Outage Rates: Summary

• From 2010 to 2013, TADS contains records of 4,951 Transformer outagesTransformer outages 243 (5% of the total) are automatic outages; 193 (4% of the total) are sustained outages

3,794 (77% of the total) are planned outages and 914 (18% of the total) are operational outages

h l f i• The average annual outage rate per transformer is 1.7.

•By voltage class, the annual outage rate increases with lt l ith th ll t t t f 0 5voltage class, with the smallest outage rate of 0.5 

outages per 200‐299 kV transformer and the biggest outage rate of 3 0 outages per 600‐799 kV transformer

RELIABILITY | ACCOUNTABILITY22

outage rate of 3.0 outages per 600 799 kV transformer 

Page 23: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Outage Durations: Summary

• From 2010 to 2013, combined Transformer outage duration was 75.5 years (out of 2871.8 transformer‐years):  7.7 years (10% of the total duration) was the duration of automatic sustained outages

53.4 years (71% of the total) was due to planned outages and 14.4 years (19% of the total) due to operational outages

• Average sustained outage duration over all voltage classes was 14 6 days the planned outage duration was 5 1 days and the14.6 days, the planned outage duration was 5.1 days, and the operational outage duration 5.7 days. There were significant differences in durations by outage types among the voltage lclasses.

• The annual non‐operational time per transformer was the largest for the 600‐799 kV (about 13 days) and the shortest for the 200‐

RELIABILITY | ACCOUNTABILITY23

for the 600 799 kV (about 13 days) and the shortest for the 200299 kV (4 days), with the overall average of 10 days a year. 

Page 24: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Transformer Availability: Summary

• Mean Time of Continuous Operation per transformer was on average 206 days g y The longest MTOCO was for a 200‐299 kV transformer (681 days) 

The smallest MTOCO (117 days) was for a 600‐799 kV transformer 

F th l t 4 ll t f il bilit b• For the last 4 years, overall transformer availability was above 97%.

• Transformer unavailability was on average 2.6% with the largest y g gunavailability of 3.7% for the 600‐799 kV voltage class

• 71% of overall transformer unavailability is due to planned toutages.

RELIABILITY | ACCOUNTABILITY24

Page 25: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

RELIABILITY | ACCOUNTABILITY25

Page 26: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

RELIABILITY | ACCOUNTABILITY26

Page 27: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

2010-2013 TADS Data

Transformer Outages (2010‐2013) 200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All TransformersNumber of transformers 115.0 667.3 1719.0 370.5 2871.8Number of Automatic Outages 14 62 136 31 243Number of Automatic Outages 14 62 136 31 243

Sustained 10 49 105 29 193Momentary 4 13 31 2 50

Total Automatic Outage Duration (Days) 3.4 465.0 1849.6 498.3 2816.4Average Sustained Outage Duration (Days) 0.3 9.5 17.6 17.2 14.6Annual Automatic Outage Rate per transformer 0.12 0.09 0.08 0.08 0.08Annual Automatic Outage Rate per transformer 0.12 0.09 0.08 0.08 0.08

Sustained 0.09 0.07 0.06 0.08 0.07Number of Non‐Automatic Outages 47 689 2888 1084 4708

Planned 38 605 2265 886 3794Operational 9 84 623 198 914

Total Non‐Automatic Outage Duration (Days) 443.5 5668.3 14132.7 4484.2 24728.7Planned 439.4 4185.7 11974.2 2890.8 19490.1

Operational 4.1 1482.7 2158.5 1593.3 5238.6Average Non‐Automatic Outage Duration (Days) 9.4 8.2 4.9 4.1 5.3

Planned 11.6 6.9 5.3 3.3 5.1Operational 0.5 17.7 3.5 8.0 5.7

Annual Non‐Automatic Outage Rate per transformer 0.41 1.03 1.68 2.93 1.64Planned 0.33 0.91 1.32 2.39 1.32

Operational 0.08 0.13 0.36 0.53 0.32

RELIABILITY | ACCOUNTABILITY27

Page 28: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

2010-2013 TADS Data (continued)

Transformer Outages (2010‐2013) 200‐299 kV 300‐399 kV 400‐599 kV 600‐799 KV All TransformersTotal Number of Outages 61 751 3024 1115 4951Total Outage Duration (Days) 446.8 6133.4 15982.4 4982.5 27545.1g ( y )Average Outage Duration (Hours) 175.8 196.0 126.8 107.2 133.5Annual Total Outage Rate per transformer 0.53 1.13 1.76 3.01 1.72Transformer Unavailability due to Sustained outages 0.01% 0.19% 0.29% 0.37% 0.27%Transformer Unavailability due to Planned outages 1.05% 1.72% 1.91% 2.14% 1.86%Transformer Unavailability due to Operational outages 0.01% 0.61% 0.34% 1.18% 0.50%Transformer Availability 98.9% 97.5% 97.5% 96.3% 97.4%Mean Time of Continuous Operation per Transformer (Days) 680.8 316.2 202.2 116.8 206.2Average Annual Non‐Operational Time per Transformer (Days) 3.9 9.2 9.3 13.4 9.6

RELIABILITY | ACCOUNTABILITY28

Page 29: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

2010-2013 TADS Data (continued)

TADS Transformer Unavailability 2010 2011 2012 2013Automatic sustained outages 0.33% 0.44% 0.06% 0.25%Non‐Automatic Outages 2.08% 2.48% 2.75% 2.13%

Operational outages 0.34% 0.43% 0.57% 0.64%Pl d t 1 73% 2 06% 2 18% 1 49%Planned outages 1.73% 2.06% 2.18% 1.49%

All Outages 2.41% 2.92% 2.80% 2.38%Transformer Availability 97.59% 97.08% 97.20% 97.62%Number of Transformers 691.3 705.2 713.4 761.9Total hours 6055788 6177552 6266505.6 6674244Total automatic sustained outage duration (Hours) 20185 77 26994 18 3525 95 16887 2Total automatic sustained outage duration (Hours) 20185.77 26994.18 3525.95 16887.2Total non‐automatic outage duration (Hours) 125739.1 153402.9 172213.1 142133.5Total Operational outage duration (Hours) 20866.7 26309.5 35836.3 42714.2Total Planned outage duration (Hours) 104872.4 127093.4 136376.9 99419.4Total outage duration 145924.8367 180397.1 175739.1 159020.7

RELIABILITY | ACCOUNTABILITY29

Page 30: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Statistical Methodology

• For comparison of the expected outage rates (year‐over‐year and for different voltage classes) the testing the homogeneityand for different voltage classes), the testing the homogeneity of Poisson frequencies was used 

• The tests are valid under assumption of the Poisson distribution of the occurrences of outages

• For comparison of the mean times of continuous operations (MTOCO) the ratio tests for two exponential means were used(MTOCO), the ratio tests for two exponential means were used

• The tests are valid under assumption of the Poisson distribution of the occurrences of outages; and Time of Continuous Operation has the exponential distribution

• The null hypotheses on the equality of the expected outage rates and the equality of the mean times were tested at the

RELIABILITY | ACCOUNTABILITY30

rates and the equality of the mean times were tested at the significance level of 0.05

Page 31: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Element Reliability Function

RELIABILITY | ACCOUNTABILITY31

Page 32: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

Reliability Calculation (Example)

t time (days) R(t)10 0.9520 0.9130 0 8630 0.86100 0.61365 0.16500 0 08

RELIABILITY | ACCOUNTABILITY32

500 0.08

Page 33: Transformer Outage rates, Durations and … Availability Data...Transformer Voltage Class: TADS Definition 1 1. Element The following are Elements for which TADS data are to be collected:

References

• P.G. Hoel. Testing the homogeneity of Poisson Frequencies. Annals of Mathematical Statistics (1945) pp 362‐368Annals of Mathematical Statistics (1945), pp. 362 368.

• L. Bain and M. Englehardt. Statistical Analysis of Reliability and Life‐Testing Models: Theory and Methods, Second Edition. CRC Press (1991)

RELIABILITY | ACCOUNTABILITY33