transformer metering yard erkdjhcbd& oh lines components

Upload: satheja

Post on 13-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    1/38

    TPS: ELE-QA- 00105 May 2010

    Technical Purchase SpecificationTransformer/Metering Yard & OH Lines Components

    Gamesa Wind Turbines Pvt Ltd

    No.489, GNT Road, Thandal kazhani,

    Vadagari Post,Chennai 600 052.

    INDIA

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    2/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 2 -

    11/22/33 KV TRANSFORMER & METERING YARD

    Components Used:

    1. Double pole steel Structure

    2. Horn Gap Fuse

    3. Lightning Arrestor

    4. Air Break Isolator

    5. Stay Wire

    6. Fencing

    7. Yard Light

    8. Earthing Electrode

    9. '0'-Gauge Copper/Transformer HT bushing termination

    10.CT/PT Metering Unit

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    3/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 3 -

    Specification of Components:

    11 KV SYSTEMS

    1. Double pole steel structurePlease refer the drawing:

    2. Horn Gap FuseItem No.

    Material 11 KV Horn Gap Fuse

    Description

    ReferenceStandard

    IS 1818, IS 9385

    Sr Parameters Values / Specification

    1 Nominal System Voltage 11 KV

    2 Highest System Voltage 12 KV

    3 Frequency 50 Hz

    4 No of Poles 3

    5 Base Channel

    ISMC 75X40 mm hotdip galvanized with two nos of 100x50x6

    mm bridge channel of galvanized

    6 Copper Parts Tinned

    7 Insulator

    Two nos of 11 KV post insulator per phase (Total 6 nos 11 KV

    post insulator for 3-phase) with creepage distance of not less

    than 25mm/KV

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    4/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 4 -

    Sr Parameters Values / Specification

    8 Terminal Connector Suitable tinned copper pad for copper/ACSR Conductor

    9 Arcing HornsCopper clad (or) brass with the size of not less than that 2

    SWG

    10 Fuse Length 205 mm (8 inch)

    11 Between post in each phase 610 mm

    12 Between Phase to Phase 915 mm

    13Bolting of the post to the

    live terminal305 mm

    14Live Terminal to the bottomof the horn

    254 mm

    15Bottom of the horn to the

    top of the horn457 mm

    16

    Angle of the horn rod oneither side of the each

    phase30 Degree

    17 Test to be Conducted All routine & type test as per IS 1818

    Reputed Make

    1) ADCO, Kolkata

    2) LAMCO, Hyderabad3) ELPRO International

    4) OBLUM, Hyderabad5) DANKE, Ahmedabad6) IPL Products, Chennai

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    5/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 5 -

    3. Lightning ArrestorItem No.

    Material 11 KV Lightning Arrestor

    DescriptionLighting arrestors shall be of structures mounted complete with allaccessories such as terminal connectors, earthing bolts suitable for 50x6

    mm GI flat etc. shall confirm to IEC-99-4

    ReferenceStandard

    IS: 2165-1977, IEC-99-4

    Sr Parameters Values / Specification

    1 Nominal System Voltage 11 KV

    2 Highest System Voltage 12 KV

    3 Frequency 50 Hz

    4 Arrestor Rating 9 KV (rms)

    5 Class Station

    6 Type Gapless type

    7 System Solidly earthed

    8

    Discharge Voltage KV

    (Crest) [8 x 20 m secondscurrent wave]

    5 kA

    9Maximum continuousoperating Voltage (MCOB)

    7.2 kV (rms)

    10Steep front dischargevoltage

    36 KV (Crest)

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    6/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 6 -

    Sr Parameters Values / Specification

    11Mounting bracket &earthing terminal

    Hot dip galvanized steel

    12 Line Terminal AL Alloy

    13Rated Lightning impulse

    withstand voltage (Peak)75 KV

    14

    Rated Power frequencyshort duration withstand

    voltage28 KV (rms)

    15 Creepage Distance 25 mm/KV Min

    16 Test to be Conducted All routine & type test as per IS:2165-1977, IEC-99-4

    Reputed Make

    1) LAMCO, Hyderabad

    2) ELPRO International

    3) OBLUM, Hyderabad

    4) Alstom

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    7/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 7 -

    4. Air Break Isolator/AB SwitchItem No.

    Material 11 KV Air Break Isolator

    Description

    Air break isolator shall be Double break center rotating horizontal

    mounting, mechanically gang operated complete with all accessories such

    as operating pipes, guides, supporting insulators, link work, lockingarrangement and bimetallic PG clamps etc shall confirm to IS 1818-1972

    ReferenceStandard

    IS 1818-1972

    Sr Parameters Values / Specification

    1 Nominal System Voltage 11 KV

    2 Highest System Voltage 12 KV

    3 Current Rating 400 Amps without exceeding temperature limit

    4 Frequency 50 Hz

    5 No of Poles 3

    6 Base Channel ISMC 75X40 mm Hot dip galvanized

    7 Copper parts Tinned

    8 InsulatorThree nos of 11 KV post Insulator per phase (Total 9 nos 11KV post insulator for 3-phase) with creepage distance of not

    less than 25 mm/kV

    9 Operating Pipe25 mm dia, Class-B, GI pipe, 3 mm thick shall confirm to IS1239 Part-I

    10 PG clamp Bimetallic strip suitable for copper terminals

    11 Contact pressure of switch 1/2 lb/Ampere

    12 Arcing Horn Copper clad with the size of 2 SWG

    13 Bearing Rotating parts shall be fitted with suitable bearing

    14 Locking Arrangement Locking arrangement shall provided with duplicate keys

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    8/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 8 -

    Sr Parameters Values / Specification

    15 Indication ON/OF indication at Operating Handle

    16 Short circuit current 16 KA for 3 Seconds

    17 Phase to phase clearance 915 mm

    18Distance between non

    rotating Insulator762 mm

    19 Male ContactSilver coated live contact on tubular arm of adequate

    strength

    20 Female ContactSpring Loaded finger type silver coated contacts of copper

    material

    21

    One-minute Power

    frequency withstandvoltage to earth and

    between poles

    35 KV (rms)

    22 Test to be conducted All routine & type test as per IS 1818-1972

    Reputed Make

    1) Sterling, Vadodara2) ELPRO International, Hyderabad

    3) ADCO, Kolkata

    5) PACTIL6) DANKE, Hyderabad7) IPL Products, Chennai

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    9/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 9 -

    5. Stay Wire

    a) The stay wire shall be of 7/8 SWG stranded steel wire (7/4.1mm) and ultimate tensilestrength of the guy wire is 6400 Kg for a safety factor of 2.5. The permissible tension in one

    guy is 2560 Kg.

    b) Two C type guy insulator to be used & minimum failing load of 88 KN and to be located 3mtr away from ground level

    c) The diameter of anchor rod & turn Buckle rod is 20 mm. The anchor rod length is 1800 mmwhile that of turnbuckle rod is 450 mm

    d) GI thimble to be used with anchor rod

    e) Inclination angle of stay wire is 30-40 degrees

    6. Fencing

    The height of the fencing shall be of 1.8 mtr. The fencing mesh shall be mesh 10 SWG GI, 50 mm x

    50 mm GI Chain Link, 50x6 mm MS Angle, 35 x 6 mm MS Angle and 25 x 3 mm MS flat for fencing

    fabrication.

    7. Yard Lighting

    a) The light fitting 40 watts, fluorescent light shall be provided of reputed make vizPhilips/Bajaj/Crompton Greaves etc.

    b) 10 Amps Double pole Miniature Circuit Breaker of 9 KA Interruption Capacity and 4 wayterminal block.

    8. Earthing Electrodes

    Ref Standard: IS 3043

    The earth electrode shall be of 40 mm dia, 10 mtrs long MS rod (Or) galvanized iron pipe 50.8 mm

    diameter, 5.5 mm thickness, 10 mtrs long.

    50x6 mm GI flat to be used for earth Connection and 2 Runs of 65x 8 mm GI flat to be used for

    Transformer neutral earth connection

    All earth pits are interconnected except LA earth

    Depth of Bore: 10 mtr

    Soil treatment: Bentonite Powder, Common salt, Charcoal etc mixed with clay or red soil tightly

    packed with throughout the 150 mm (6 inches) bore Individual Earth Resistance is less than 8Ohms & combined earth resistance is less than 1Ohm.

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    10/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 10 -

    9. '0' Gauge Copper/Transformer HT busing Termination

    One and Half inch Aluminum tubular bus shall be for bus bars at Breaker Yard and for 1650 KW

    m/c transformer bushing to Circuit Breaker termination. The aforesaid aluminum tubular bus shall

    meet the following requirements (Approved Makes INDAL/Hindalco/Balco/ALCAN)

    Sr Parameters Values / Specification

    1 Gauge 0

    2 Nominal Diameter 8.23 mm

    3 Area 52.19 Sqmm

    4 Weight 472.90 Kg/Km

    5 Current Carrying Capacity 150 Amps @ 27 degree and 203 Amps & 55.5 degree celcius

    Sr Parameters Values / Specification

    1 Outer Diameter 47.50 mm

    2 Inner Diameter 40.25 mm

    3 Thickness 3.625 mm

    4 Area 0.8 Sq.inches

    5 Weight 0.939 lb/ft

    6 Momemt of Inertia 0.3099 in4

    7 Section modulus 0.3262 in3

    8 Radius of gyration 0.6226 inches

    9 DC Resistance16.97 Micro-ohms per ft @ 20

    degree celcius

    10 Current carrying capacity 840 Amps

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    11/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 11 -

    10. CT/PT Metering Unit:

    Item No.

    Material11 KV CT/PT Combined Metering Unit/ Separate units (Dependingon EB)

    Description

    Outdoor Oil cooled Copper wound, Continuous duty, Combined current &potential transformer-50/5 A (Depending on no of machines connected),15 VA, Acc Class: 0.5 and 11KV/110 V, 100 VA accuracy class: 0.5

    (Accuracy class depending on EB requirements). If Separate VT ratio shall

    be (11/v3) kV/(110//v3) V.

    ReferenceStandard IS 2705/1992, IS 3156/1992

    Specification of Components:

    22 KV SYSTEMS

    1. Double pole steel structure

    Reference Drawing: PRV/GAMESA/850KW/22KV/1002

    2. Horn Gap Fuse

    Item No.

    Material 22 KV Horn Gap Fuse

    Description

    ReferenceStandard

    IS 1818, IS 9385

    Sr Parameters Values / Specification

    1 Nominal System Voltage 22 KV

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    12/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 12 -

    2 Highest System Voltage 24 KV

    3 Frequency 50 Hz

    4 No of Poles 3

    5 Base ChannelISMC 75X40 mm hot dip galvanized with two no of 100x50x6mm bridge channel of galvanized

    6 Copper Parts Tinned

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    13/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 13 -

    Sr Parameters Values / Specification

    7 InsulatorTwo nos of 22 KV post insulator per phase (Total 6 nos 22 KVpost insulator in 3-phase) with creepage distance of not lessthan 25mm/KV

    8 Terminal Connector Suitable tinned copper pad for copper/ACSR Conductor

    9 Arcing HornsCopper clad (or) brass with the size of not less than that 2SWG

    10 Fuse Length 255 mm (10 inch)

    11 Between post in each phase 650 mm

    12 Between Phase to Phase 1070 mm

    13Bolting of the post to the

    live terminal450 mm

    14Live Terminal to the bottomof the horn

    254 mm

    15Botton of the horn to thetop of the horn

    610 mm

    16

    Angle of the horn rod oneither side of the each

    phase

    30 Degree

    17 Test to be Conducted All routine & type test as per IS 1818

    Reputed Make

    1) ADCO, Kolkata

    2) LAMCO, Hyderabad3) ELPRO International

    4) OBLUM, Hyderabad5) IPL Products, Chennai

    6) DANKE, Hyderabad

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    14/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 14 -

    3. Lightning Arrestor

    Item No.

    Material 22 KV Lightning Arrestor

    DescriptionLighting arrestors shall be of structures mounted complete with allaccessories such as terminal connectors, earthing bolts suitable for 50x6

    mm GI flat etc. shall confirm to IEC-99-4

    ReferenceStandard

    IS:2165-1977, IEC-99-4

    Sr Parameters Values / Specification

    1 Nominal System Voltage 22 KV

    2 Highest System Voltage 24 KV

    3 Frequency 50 Hz

    4 Arrestor Rating 18 KV (rms)

    5 Class Station

    6 Type Gapless type

    7 System Solidly earthed

    8 9

    Discharge Voltage KV

    (Crest) [8 x 20 m seconds

    current wave] Maximumcontinuous operatingVoltage (MOCB)

    10 kA 14.4 kV (rms)

    10Steep front discharge

    voltage72 KV (Crest)

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    15/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 15 -

    Sr Parameters Values / Specification

    11Mounting bracket &earthing terminal

    Hot dip galvanized steel

    12 Line Terminal AL Alloy

    13Rated Lightning impulse

    withstand voltage (Peak)125 KV

    14Rated Power frequencyshort duration withstandvoltage

    50 KV (rms)

    15 Creepage Distance 25 mm/KV Min

    16 Test to be Conducted All routine & type test as per IS:2165-1977, IEC-99-4

    Reputed Make

    1) LAMCO, Hyderabad2) ELPRO International

    3) OBLUM, Hyderabad

    4) Alstom

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    16/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 16 -

    4. Air Break Isolator/AB Switch

    Item No.

    Material 22 KV Air Break Isolator

    Description

    Air break isolator shall be Double break center rotating horizontalmounting, mechanically hand operated complete with all accessories such

    as operating pipes, guides, supporting insulators, link work, locking

    arrangement and bimetallic PG clamps etc shall confirm to IS 1818-1972

    ReferenceStandard

    IS 1818-1972

    Sr Parameters Values / Specification

    1 Nominal System Voltage 22 KV

    2 Highest System Voltage 24 KV

    3 Current Rating 400 Amps without exceeding temperature limit

    4 Frequency 50 Hz

    5 No of Poles 3

    6 Base Channel ISMC 75X40 mm Hot dip galvanized

    7 Copper parts Tinned

    8 Insulator Three nos of 22 KV post Insulator per phase (Total 9 Nos of22 KV post insulator for 3-phase) with creepage distance ofnot less than 25 mm/kV

    9 Operating Pipe25 mm dia, Class-B, GI pipe, 3 mm thick shall confirm to IS1239 Part-I

    10 PG clamp Bimetallic strip suitable copper terminals

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    17/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 17 -

    Sr Parameters Values / Specification

    11 Contact pressure of switch 1/2 lb/Ampere

    12 Arcing Horn Copper clad with the size of 2 SWG

    13 Bearing Rotating parts shall be fitted with suitable bearing

    14 Locking Arrangement Locking arrangement shall provided with duplicate keys

    15 Indication ON/OF indication at Operating Handle

    16 Short circuit current 16 KA for 3 Seconds

    17 Phase to phase clearance 1070 mm

    18Distance between non

    rotating Insulator

    800 mm

    19 Male ContactSilver coated live contact on tubular arm of adequate

    strength

    20 Female ContactSpring Loaded finger type silver coated contacts of copper

    material

    21

    One-minute Powerfrequency withstandvoltage to earth and

    between poles

    55 KV (rms)

    22 Test to be conducted All routine & type test as per IS 1818-1972

    Reputed Make

    1) Sterling, Varodara

    2) ELPRO International, Hyderabad

    3) ADCO, Kolkata4) PACTIL

    5) IPL Products, Chennai

    6) DANKE, Ahmedabad

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    18/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 18 -

    5. Stay Wire:

    a) The stay wire shall be of 7/8 SWG stranded steel wire (7/4.1mm) and ultimate tensilestrength of the guy wire is 6400 Kg for a safety factor of 2.5. The permissible tension in oneguy is 2560 Kg

    b) Two C type guy insulator to be used & minimum failing load of 88 KN and to be located 3

    mtr away from ground level

    c) The diameter of anchor rod & turn Buckle rod is 20 mm. The anchor rod length is 1800 mmwhile that of turnbuckle rod is 450 mm

    d) GI thimble to be used with anchor rod

    e) Inclination angle of stay wire is 30-40 degrees

    6. Fencing

    The height of the fencing shall be of 1.8 mtr. The fencing mesh shall be mesh 10 SWG GI, 50

    mm x 50 mm GI Chain Link, 50x6 mm MS Angle, 35 x 6 mm MS Angle and 25 x 3 mm MSflat for fencing fabrication.

    7. Yard Lighting

    a) The light fitting 40 watts, fluorescent light shall be provided of reputed make vizPhilips/Bajaj/Crompton Greaves etc.

    b) 10 Amps Double pole Miniature Circuit Breaker of 9 KA Interruption Capacity and 4 wayterminal block.

    8. Earthing Electrodes:

    Ref Standard: IS 3043

    The earth electrode shall be of 40 mm dia, 10 mtrs long MS rod (Or) galvanized iron pipe 50.8

    mm diameter, 5.5 mm thickness, 10 mtrs long.

    50x6 mm GI flat to be used for earth Connection and 2 Runs of 65x 8 mm GI flat to be used for

    transformer neutral earth connection.

    All earth pits are interconnected except LA earth

    Depth of Bore: 10 mtr

    Soil treatment: Bentonite Powder, Common salt, Charcoal etc mixed with clay or red soil tightly

    Packed with throughout the 150 mm bore

    Individual Earth Resistance is less than 8 Ohms & combined earth resistance is less than 1Ohm.

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    19/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 19 -

    9. '0' Gauge Copper/Transformer HT busing Termination

    One and Half inch Aluminum tubular bus shall be for bus bars at Breaker Yard and for 1650 KWm/c transformer bushing to Circuit Breaker termination. The aforesaid aluminum tubular bus shallmeet the following requirements (Approved Makes INDAL/Hindalco/Balco/ALCAN)

    Sr Parameters Values / Specification

    1 Gauge 0

    2 Nominal Diameter 8.23 mm

    3 Area 52.19 Sqmm

    4 Weight 472.90 Kg/Km

    5 Current Carrying Capacity 150 Amps @ 27 degree and 203 Amps & 55.5 degree celcius

    Sr Parameters Values / Specification

    1 Outer Diameter 47.50 mm

    2 Inner Diameter 40.25 mm

    3 Thickness 3.625 mm

    4 Area 0.8 Sq.inches

    5 Weight 0.939 lb/ft

    6 Moment of Inertia 0.3099 in4

    7 Section modulus 0.3262 in3

    8 Radius of gyration 0.6226 inches

    9 DC Resistance 16.97 Micro-ohms per ft @ 20 degree celcius

    10 Current carrying capacity 840 Amps

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    20/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 20 -

    10. CT/PT Metering Unit

    Item No.

    Material22 KV CT/PT Combined Metering Unit/ Separate Units (Dependingon EB)

    Description

    Outdoor Oil cooled Copper wound, Continuous duty, Combined current &potential transformer-50/5 A (Depending on no of machines connected),

    15 VA, Acc Class: 0.5 and 22KV/110 V, 100 VA accuracy class: 0.5

    (Accuracy class depending on EB requirements) If Separate VT ratio shallbe (11/v3) kV/ (110//v3)V

    ReferenceStandard

    IS 2705/1992, IS 3156/1992

    Specification of Components:

    33 KV SYSTEMS

    1. Double pole steel structure

    Reference Drawing: PRV/GAMESA/850KW/33KV/1001

    2. Horn Gap Fuse

    Item No.

    Material 33 KV Horn Gap Fuse

    Description

    ReferenceStandard

    IS 1818, IS 9385

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    21/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 21 -

    Sr Parameters Values / Specification

    1 Nominal System Voltage 33 KV

    2 Highest System Voltage 36 KV

    3 Frequency 50 Hz

    4 No of Poles 3

    5 Base ChannelISMC 75X40 mm hot dip galvanized with two nos of

    100x50x6 mm bridge channel of galvanized

    6 Copper Parts Tinned

    7 InsulatorTwo nos of 33 kV post insulator per phase with creepage

    distance of not less than 25mm/KV

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    22/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 22 -

    Sr Parameters Values / Specification

    8 Terminal Connector Suitable tinned copper pad for copper/ACSR Conductor

    910

    Arcing Horns Fuse LengthCopper clad (or) brass with the size of not less than that 2SWG 381 mm (15 inch)

    11 Between post in each phase 790 mm

    12 Between Phase to Phase 1220 mm

    13Bolting of the post to the

    live terminal610 mm

    14Live Terminal to the bottomof the horn

    254 mm

    15Botton of the horn to the

    top of the horn765 mm

    16Angle of the horn rod oneither side of the each

    phase

    30 Degree

    17 Test to be Conducted All routine & type test as per IS 1818

    Reputed Make

    1) ADCO, Kolkata2) LAMCO, Hyderabad3) ELPRO International

    4) OBLAM, Hyderabad5) IPL Products, Chennai

    6) DANKE, Hyderabad

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    23/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 23 -

    3. Lightning Arrestor

    Item No.

    Material 33 KV Lightning Arrestor

    DescriptionLighting arrestors shall be of structures mounted complete with allaccessories such as terminal connectors, earthing bolts suitable for 50x6

    mm GI flat etc. shall confirm to IEC-99-4

    ReferenceStandard

    IS:2165-1977, IEC-99-4

    Sr Parameters Values / Specification

    1 Nominal System Voltage 33 KV

    2 Highest System Voltage 36 KV

    3 Frequency 50 Hz

    4 Arrestor Rating 30 KV (rms)

    5 Class Station

    6 Type Gapless type

    7 System Solidly earthed

    8

    Discharge Voltage KV

    (Crest) [8 x 20 m secondscurrent wave]

    10 kA

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    24/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 24 -

    Sr Parameters Values / Specification

    9Maximum continuousoperating Voltage (MOCB)

    24 kV (rms)

    10Steep front dischargevoltage

    90 KV (Crest)

    11Mounting bracket &

    earthing terminalHot dip galvanized steel

    12 Line Terminal AL Alloy

    13Rated Lightning impulsewithstand voltage (Peak)

    170 KV

    14

    Rated Power frequencyshort duration withstand

    voltage70 KV (rms)

    15 Creepage Distance 25 mm/KV Min

    16Test to be ConductedReputed Make

    All routine & type test as per IS:2165-1977, IEC-99-4

    1) LAMCO, Hyderabad2) ELPRO International

    3) OBLAM, Hyderabad

    4) Alstom

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    25/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 25 -

    4. Air Break Isolator/AB Switch

    Item No.

    Material 33 KV Air Break Isolator

    Description

    Air break isolator shall be Double break center rotating horizontalmounting, mechanically hand operated complete with all accessories such

    as operating pipes, guides, supporting insulators, link work, lockingarrangement and bimetallic PG clamps etc shall confirm to IS 1818-1972

    ReferenceStandard

    IS 1818-1972

    Sr Parameters Values / Specification

    1 Nominal System Voltage 33 KV

    2 Highest System Voltage 36 KV

    3 Current Rating 400 Amps without exceeding temperature limit

    4 Frequency 50 Hz

    5 No of Poles 3

    6 Base Channel ISMC 75X40 mm Hot dip galvanised

    7 Copper parts Tinned

    8 InsulatorSix nos of 22 KV post Insulator per phase (Total 18 nos 22KV post insulator for 3-phase) with creepage distance of not

    less than 25 mm/kV

    9 Operating Pipe25 mm dia, Class-B, GI pipe, 3 mm thick shall confirm to IS

    1239 Part-I

    10 PG clamp Bimetallic strips for copper terminals

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    26/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 26 -

    Sr Parameters Values / Specification

    11 Contact pressure of switch 1/2 lb/Ampere

    12 Arcing Horn Copper clad with the size of 2 SWG

    13 Bearing Rotating parts shall be fitted with suitable bearing

    14 Locking Arrangement Locking arrangement shall provided with duplicate keys

    15 Indication ON/OF indication at Operating Handle

    16 Short circuit current 16 KA for 3 Seconds

    17 Phase to phase clearance 1220 mm

    18Distance between non

    rotating Insulator

    800 mm

    19 Male ContactSilver coated live contact on tubular arm of adequate

    strength

    20 Female ContactSpring Loaded finger type silver coated contacts of copper

    material

    21

    One-minute Powerfrequency withstandvoltage to earth and

    between poles

    75 KV (rms)

    22 Test to be conducted All routine & type test as per IS 1818-1972

    Reputed Make

    1) Sterling, Varodara

    2) ELPRO International, Hyderabad

    3) ADCO, Kolkata4) PACTIL

    5) IPL Products, Chennai

    6) DANKE, Hyderabad

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    27/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 27 -

    5) Stay Wire:

    a) The stay wire shall be of 7/8 SWG stranded steel wire (7/4.1mm) and ultimate tensilestrength of the guy wire is 6400 Kg for a safety factor of 2.5. The permissible tension in one

    guy is 2560 Kg

    b) Two C type guy insulator to be used & minimum failing load of 88 KN and to be located 3

    mtr away from ground level

    c) The diameter of anchor rod & turn Buckle rod is 20 mm. The anchor rod length is 1800 mmwhile that of turnbuckle rod is 450 mm

    d) GI thimble to be used with anchor rod

    e) Inclination angle of stay wire is 30-40 degrees

    6) Fencing:The height of the fencing shall be of 1.8 mtr. The fencing mesh shall be mesh 10 SWG GI, 50 mm x

    50 mm GI Chain Link, 50x6 mm MS Angle, 35 x 6 mm MS Angle and 25 x 3 mm MS flat for fencing

    fabrication.

    7) Yard Lighting:

    a) The light fitting 40 watts, fluorescent light shall be provided of reputed make viz

    Philips/Bajaj/Crompton Greaves etc.

    b) 10 Amps Double pole Miniature Circuit Breaker of 9 KA Interruption Capacity and 4 way

    terminal block.

    8) Earthing Electrodes:

    Ref Standard: IS 3043

    Reference Drawing:

    The earth electrode shall be of 40 mm dia, 10 mtrs long MS rod (Or) galvanized iron pipe 50.8mm diameter, 5.5 mm thickness, 10 mtrs long.

    50x6 mm GI flat to be used for earth Connection and 2 Runs of 65x 8 mm GI flat to be used for

    transformer neutral earth connection.

    All earthpits are interconnected except LA earth

    Depth of Bore: 10-12 m

    Soil treatment: Bentonite Powder, Common salt, Charcoal etc mixed with clay or red soil tightly

    packed with throughout the 150 mm boreIndividual Earth Resistance is less than 8 Ohms & Combined earth resistance is less than 1Ohm

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    28/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 28 -

    9. '0' Gauge Copper/Transformer HT Bushing Termination

    One and Half inch Aluminium tubular bus shall be for b us bars at Breaker Yard and for 1650 KWm/c transformer bushing to Circuit Breaker termination. The aforesaid aluminum tubular bus shallmeet the following requirements (Approved Makes INDAL/Hindalco/Balco/ALCAN).

    Sr Parameters Values / Specification

    1 Gauge 0

    2 Nominal Diameter 8.23 mm

    3 Area 52.19 Sqmm

    4 Weight 472.90 Kg/Km

    5 Current Carrying Capacity 150 Amps @ 27 degree and 203 Amps & 55.5 degree celcius

    Sr Parameters Values / Specification

    1 Outer Diameter 47.50 mm

    2 Inner Diameter 40.25 mm

    3 Thickness 3.625 mm

    4 Area 0.8 Sq.inches

    5 Weight 0.939 lb/ft

    7 Momemt of Inertia 0.3099 in4

    8 Section modulus 0.3262 in3

    9 Radius of gyration 0.6226 inches

    10 DC Resistance 16.97 Micro-ohms per ft @ 20 degree celcius

    11 Current carrying capacity 840 Amps

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    29/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 29 -

    10. CT/PT Metering Unit

    Item No.

    Material33 KV CT/PT Combined Metering Unit/Separate Units (Dependingon EB)

    Description

    Out door Oil cooled Copper wound, Continuous duty, Combined current &potential transformer-50/5 A (Depending on no of machines connected) ,

    15 VA, Acc Class: 0.5 and 33KV/110 V, 100 VA accuracy class: 0.5

    (Accuracy class depending on EB requirements) If Separate VT ratio shallbe (11/v3) kV/ (110//v3)V

    ReferenceStandard

    IS 2705/1992, IS 3156/1992

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    30/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 30 -

    11/22/33 KV OVERHEAD LINES (INTERNAL+EXTERNAL)

    Components used at 11/22/33 kV Internal & External Lines:

    1) RSJ Joist Poles

    2) Reinforced Cement Concrete Poles

    3) Stay with Guy Insulators

    4) Pin Insulators

    5) Disc Insulators

    6) Cross Arms

    7) ACSR conductor

    Standard Clearance :

    11 kV 22 kV 33 kV

    Phase to Phase 460 mm 610 mm 915 mm

    Phase to Earth 305 mm 460 mm 610 mm

    Ground Clearance:

    Vertical Clearance to ground in Mtrs

    11 kV 22 kV 33 kV

    In rural areas and places inaccessible to Vehicular traffic 4.572 5.182 5.182

    In Village, towns and city areas along street 5.79 5.79 5.79

    In Village, towns and city area across street 6.096 6.096 6.096

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    31/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 31 -

    Specification of Components:

    1) RSJ Joist Poles:

    All poles must be painted with two coats of red oxide and one coat of aluminum paint before

    erection and final coating can be done after erection. Total DFT must be 80 microns minimum.

    Single Circuit Line:

    a) 9.50 Mtr long, 175x87x8 mm RSJ Joist pole shall be used for internal lines

    b) The base plate size 300x300x6 mm shall be welded to the bottom of the joist

    c) The factor of safety for RSJ Joist pole is 2

    Double Circuit Line:

    a) 11 Mtr long, 200x100x8 mm RSJ Pole must be used

    b) The base plate size 300x300x6 mm shall be welded to the bottom of the joistc) The factor of safety for RSJ Joist pole is 2

    The span length of line = 45 mtr (Max)

    Every fifth / seventh pole shall be cut point (provided with stay wires)

    In case of angle of deviation, Single pole with necessary stay arrangements, coil earthing, polenumbering, anti climbing devices (If required by EB), danger board in every cut-points to be

    provided

    Every fifth pole for RSJ pole shall be earthed as mentioned below

    Pole earthing shall be done with 8 SWG GI wires closely wound 115 turns of 50 mm dia. and

    burried in the earth nearby pole concrete at the depth of 1.5 mtr from ground level. The Earthresistance shall be of less than 10 Ohm. If achieving more than 10 ohms, multiple earthing

    arrangement shall be done till achieving of less than 10 Ohms.

    2) Reinforced Cement Concrete Poles (RCC):

    9.14 mtr, 256 Kg safe working load, concrete ratio shall be 1:1.5:3, factor of safety is 2.5

    The metal cross arm and the insulator pins shall be bonded together and earthed at every pole.

    Pole earthing shall be done with 8 SWG GI wires closely wound 115 turns of 50 mm dia. andburried in the earth nearby pole concrete at the depth of 1.5 mtr from ground level in every pole.

    The Earth resistance shall be of less than 10 Ohm. If achieving more than 10 ohms, multiple

    earthing arrangement shall be done till achieving of less than 10 Ohms.

    3) Stay with Guy Insulator:

    a) The stay wire shall be of 7/8 SWG stranded steel wire (7/4.1mm) and ultimate tensile

    strength of the guy wire is 6400 Kg for a safety factor of 2.5. The permissible tension in oneguy is 2560 Kg

    b) Two C type guy insulator to be used & minimum failing load of 88 KN and to be located 3

    mtr away from ground level

    c) The diameter of anchor rod & turnbuckle rod is 20 mm. The anchor rod length is 1800 mm

    while that of turnbuckle rod is 450 mm

    d) GI thimble to be used with anchor rod

    Inclination angle of stay wire is 30-40 degrees

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    32/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 32 -

    4) Pin Insulators

    Item No.

    Material 11/22/33 KV Pin Insulators

    ReferenceStandard

    IS: 731 RA 2001, BS: 137, IEC: 383

    Sr Standard Particulars 11kV 22kV 33kV

    1 Highest System Voltage 12 KV 24 KV 36 KV

    2 Creepage Distance minimum 280 mm 565 mm

    580 mm for lowpolluted area but 685

    mm Creepage to beused for highlypolluted site like

    Gujarat, Rameswaram

    3 Visible Discharge Voltage 9 KV 18 KV 27 KV

    4 Mechanical failing load 10 KN 10 KN 10 KN

    5Power Frequency withstand

    voltage (Wet)35 KV 70 KV 80 KV

    6Power Frequency withstand

    voltage (Dry)60 KV 90 KV 95 KV

    7Power Frequency Flashovervoltage (Wet)

    40 KV 75 KV 85 KV

    8Power Frequency Flashovervoltage (Dry)

    65 KV 95 KV 100 KV

    9Lighting impulse withstand

    voltage

    75 KV (Peak)160 KV

    (Peak)

    185 KV (Peak)

    10Power frequency under oilPuncture voltage test

    105 KV 170 KV 190 KV

    Reputed Make1) Birla Ngk (Jayashree)2) WS3) BHEL

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    33/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 33 -

    5) Disc Insulators

    a) B & S Type Disc Insulators:

    Item No.

    Material B & S Type Disc Insulators

    ReferenceStandard

    IS: 731 RA 2001, BS: 137, IEC: 383

    Sr Standard Particulars B & S Type

    1 Visible Discharge Voltage 9 KV

    2 Porcelain Diameter 255 mm

    3 Spacing 145 mm

    4 Creepage Distance 292 mm

    5 Electromechanical Strength 70 KN

    6 Power Frequency withstand voltage (Wet) 35 KV

    7 Power Frequency withstand voltage (Dry) 50 KV

    8 Power Frequency Flashover voltage (Wet) 45 KV

    9 Power Frequency Flashover voltage (Dry) 65 KV

    10 Impulse Flashover Voltage (Positive) 110 KV (peak)

    11 Impulse Flashover Voltage (Negative) 120 KV (Peak)

    12 Impulse Withstand Voltage 105 KV (Peak)

    13 Power frequency puncture voltage 105 KV

    14 Net Weight (Approx.) 5.2 Kgs

    15 Ball Socket Size 16 MmB

    Reputed Make1) Birla Ngk (Jayashree)2) WS

    3) BHEL

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    34/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 34 -

    b) T & C Type Disc Insulators

    Item No.

    Material T & C Type Disc Insulators

    ReferenceStandard

    IS: 731, BS: 137, IEC: 383

    Note: Composite/Elastomeric type Disc insulator can be used (Depending on EB Acceptance)

    Sr Standard Particulars T & C Type

    1 Porcelain Dia 255 mm

    2 Spacing 145 mm

    3 Total Creepage Distance 292 mm

    4 Combined Electro Mechanical Strength 90 KN

    5 Power Frequency withstand voltage (Wet) 35 KV

    6 Power Frequency withstand voltage (Dry) 50 KV

    7 Power Frequency Flashover voltage (Wet) 45 KV

    8 Power Frequency Flashover voltage (Dry) 65 KV

    9 Impulse Flashover Voltage (Positive) 110 KV (peak)

    10 Impulse Flashover Voltage (Negative) 120 KV (Peak)

    11 Impulse Withstand Voltage 105 KV (Peak)

    12 Power frequency puncture voltage 105 KV

    13 Net Weight (approx.) 5.5 Kgs

    Reputed Make 1) Birla Ngk (Jayashree)2) WS

    3) BHEL

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    35/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 35 -

    6) Cross Arms:

    All cross arms must be painted with two coat of red oxide and one coat of aluminum before fix into

    the pole and final coating will be given to achieve 80 microns.

    Line Voltage (KV)

    Vertical Clearance

    Bn. Top & Bottom Cond.

    (in cm)

    Size of V Cross-arm

    11 76.25920 mm long

    75 x 40 Channel

    22 91.41070 mm long

    75 x 40 Channel

    33 121.91370 mm long

    100x 50 mm Channel

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    36/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 36 -

    7) ACSR Conductors:

    Reference Standard: IS 398 (Part-2) : 1996

    All ACSR Conductor to be manufactured as per the above mentioned IS Standard

    SL No SPECIFIC REQUIREMENTS CODE NAME OF CONDUCTOR

    Rabbit Raccon Dog

    1Calculated equivalent area of aluminum (Sq.mm)

    52.21 77.83 103.6

    2Calculated DC resistance @ 20 degree C(Ohm/Km)

    0.54490 0.3656 0.2745

    Approximate Current carrying capacity in Amps40 degree C ambient

    a) 30 deg. C rise 148 197 2543

    b) 50 deg. C rise 183 245 311

    Stranding wire diameter

    a) Aluminum (No/dia. mm) 6/3.335 6/4.09 6/4.724

    b) Steel (No/dia. mm) 1/3.35 1/4.09 7/1.57

    5 Conductor dia (mm) 61.7 91.97 118.50

    Approximate weight (Kg/Km)

    b) Total a) Aluminum 214 145 318 215 394 2886

    c) Steel 69 103 106

    7 Approximate ultimate strength (Kg) 1860 2746 3299

    8 Calculated linear co-efficient per C x 106 18.99 18.99 19.53

    9Calculated final module of elasticity(Kg/cm6x106)

    0.809 0.809 0.735

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    37/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    - 37 -

    COYOTE CONDUCTOR SPECIFICATION

    Reference Standard: IS 398 (Part-2) : 1996

    SL. No Technical Particular Value

    1 Nominal Aluminum Area (Sqmm) 130

    2 Stranding & wire diameter aluminum+steel (Nos/mm) 26/2.54 + 7/1.191

    3 Calculated DC resistance @ 20 degree C (Ohm/Km) 0.2246

    4 Calculated AC resistance @ 65 degree C (Ohm/Km) 0.2663

    5 Calculated AC resistance @ 75 degree C (O hm/Km) 0.2754

    6 Current capacity @ 65 degree C (Amps) 292

    7 Current capacity @ 65 degree C (Amps) 358

    Important:

    1. All component manufacturers' test certificate must be shown to Gamesaon request at site,

    failing which will be treated as rejection of the components. But, all certificate copy must beforwarded to Gamesa along with invoice.

    2. If sub contractor wish to use any other makes other than as specified above, details of makecan be forwarded to Gamesa QA for approval. Only after written approval from QA, thespecified make can be used.

    3. Identification of earth pits, measured earth resistance value and date of measurement mustbe displayed on earth pits before commissioning of WTG.

    4. All earth pit handle must be painted for corrosion protection with black paint.

    5. Anticorrosive black paint must be applied on RSJ joist pole in DP for the height of 300mm

    from coping.

    6. Petroleum jelly must be applied on AB switch contact points for smooth operation.

    7. ON / OFF indication must be marked on AB switch operating handle and lock arrangement

    must be provided.

    8. Earth pit connection diagram as constructed must be drawn on transformer plinth.

    9. Transformer and CT/PT metering unit HT bushing must be covered with empire tape.Terminal connector supplied with transformer to be used for transformer HT

    bushing to Zero copper termination.

  • 7/27/2019 Transformer Metering Yard erkdjhcbd& OH Lines Components

    38/38

    Document Type:

    TPS - Technical Purchase Specification

    Specification Number :

    ELE-QA-001

    Prepared By: Venkatesan Approved By: S.Subbian Approval Dt.: 05 May 10 Rev : 00 Rev Date : 05 May 10

    10. Fire buckets with canopy must be provided in the yard (Two numbers of fire buckets with dryriver sand with canopy).

    11. Safety items like, first aid box (Redi medi make), fire extinguisher (CO2), rubber mat, earth

    discharge rod and first aid chart must be provided at tower.

    12. Precommissioning checks on transformer, power cables and earth resistance will be recordedin prescribed checklist given by Gamesa.

    13. Two nos yard light to be provided for G58 transformer Yard

    14. Yard drainage path to be provided by using PVC pipe during civil work of yard wall.

    15. 40 mm gravel to be filled around the transformer plinth and cable area to be covered by riversand by using bricks arrangement as specified in the drawing.

    16. DEHN GUARD Earthing should be connected with LA Earth. 6 mtr 1core x 10 Sq.mm supplied

    with capacitor panel for DEHN GUARD earth connection.

    17. Cable length from tower to transformer must be used as is (22 mtr for G58) and looping mustbe done outside and inside the transformer yard. 12 times x OD of the cable bending radius to

    be maintained for circle loop.

    18. 1 KV megger to be used for transformer LV-E insulation resistance testing and 2.5 KV megger

    to be used for HV-LV & HV- E insulation resistance measurements. 5/10 KV megger to be

    used for XLPE cable insulation resistance tests.

    19. For Earth resistance measurement, 0-20/200 Ohms, 160 rpm, 3-Pole with selector switch

    megger to be used.

    20. 'I' Clamp-50 x65x6 mm angle, 50x6 clamps and 5/8'' GI nut and bolts to be used foroverhead lines.

    The contractor should be well acquainted with IE Rules 1956, The Electricity Act 2003,Indian Telegraphic Act 1889, EB Rules, and CEIG rules and all the EB & CEIG

    requirements must be fulfilled for installations.

    Note: In case of doubt or clarification, contact [email protected] or

    [email protected]