trane submittal - 3 split system heat pump model 1 phase … · 2017. 10. 3. · 2.5 ton split...

14
Product Specifications OUTDOOR UNIT POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS) COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLED START COMPONENTS INSULATION/SOUND BLANKE T COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL REFRIGERANT LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ. CHARGING SPECIFICATION SUBCOOLING DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) M4AC4018D1000AA TAG: _________________________________ 1.5 Ton Split System Air Conditioner - 1 Phase M4AC4018D1000AA SUBMITTAL M4AC4018D1000AA 208/230/1/60 10.4 15 SCROLL 1 - 1 208/230/1/60 7.7 - 48.0 NO PROPELLER 17-3/4 - 1 1600 1 - 1/8 1075 208/230/1/60 0.70 PLATE FIN 2 - 21 8.9 3/16 ORIFICE 5 LBS. - 2 OZ. YES 3/4 3/8 8º F W X H X D 22-9/10x26-1/4x22-9/10 128 121 NO NO M4AC4018D1000AA Model H W L LIQUID VALVE SIZE GAS VALVE SIZE 633 (24-15/16) 554 (21-7/8) 3/8 3/4 Ameristar NOTE: All dimensions are in mm/inches. 554 (21-7/8) SUCTION LINE CONNECTION CONTROL WIRING 7/8” (22.2mm) KNOCKOUT 1-11/32” (34.5mm) LIQUID LINE CONNECTION SERVICE FITTING SERVICE FITTING POWER WIRING SEE DETAIL A DETAIL A HOLE 1-3/32” (27.8mm) NOTE: GRILL APPEARANCE MAY VARY. SERVICE ACCESS ALLOW 24” CLEARANCE AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE W ACCESS VALVLE FOR LOW PRESSURE NOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR OR REFRIGERANT CHARGE. DIRECT-1

Upload: others

Post on 07-Mar-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4018D1000AA

TAG: _________________________________

1.5 Ton Split SystemAir Conditioner - 1 Phase M4AC4018D1000AA

SUBMITTAL

M4AC4018D1000AA208/230/1/60

10.415

SCROLL1 - 1

208/230/1/607.7 - 48.0

NOPROPELLER

17-3/4 - 1

16001 - 1/81075

208/230/1/600.70

PLATE FIN2 - 21 8.93/16

ORIFICE

5 LBS. - 2 OZ.YES3/43/8

8º FW X H X D

22-9/10x26-1/4x22-9/10

128121

NONO

M4AC4018D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

633 (24-15/16) 554 (21-7/8) 3/8 3/4

Ameristar

NOTE: All dimensions are in mm/inches.

554 (21-7/8)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

DIRECT-1

Page 2: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 3: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4024D1000AA

TAG: _________________________________

2.0 Ton Split SystemAir Conditioner - 1 Phase M4AC4024D1000AA

SUBMITTAL

M4AC4024D1000AA208/230/1/60

13.420

SCROLL1 - 1

208/230/1/6010.1 - 52

NOPROPELLER

18-7/8 - 1

18001 - 1/8 1075

208/230/1/600.7

PLATE FIN2 - 21103/16

ORIFICE

5 LBS. - 5 OZ.YES3/43/8

8º FW X H X D

24-7/10x26-1/4x24-7/10

139132

NONO

M4AC4024D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

633 (24-15/16) 600 (23-5/8) 3/8 3/4

Ameristar

NOTE: All dimensions are in mm/inches.

600 (23-5/8)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

DIRECT-1

Page 4: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 5: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4030D1000AA

TAG: _________________________________

2.5 Ton Split SystemAir Conditioner - 1 Phase M4AC4030D1000AA

SUBMITTAL

M4AC4030D1000AA208/230/1/60

14.725

SCROLL1 - 1

208/230/1/6010.9 - 63

NOPROPELLER

23 - 1DIRECT-1

26501 - 1/6 825

208/230/1/601.0

PLATE FIN2 - 21133/16

ORIFICE

5 LBS. - 12OZ.YES3/43/8

8º FW X H X D29x26-1/4x29

157148

NONO

M4AC4030D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

633 (24-15/16) 710 (28) 3/8 3/4

Ameristar

NOTE: All dimensions are in mm/inches.

710 (28)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

Page 6: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 7: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4036D1000AA

TAG: _________________________________

3.0 Ton Split SystemAir Conditioner - 1 Phase M4AC4036D1000AA

SUBMITTAL

M4AC4036D1000AA208/230/1/60

19.430

SCROLL1 - 1

208/230/1/6014.7 - 75

NOPROPELLER

23-5/8 - 1DIRECT-1 2700

1 - 1/6 825

208/230/1/601.0

PLATE FIN1 - 21

143/16

ORIFICE

5 LBS. - 14OZ.YES3/43/8

8º FW X H X D

30-1/5x26-1/4x30-1/5

163154

NONO

M4AC4036D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

633 (24-15/16) 740 (29-1/8) 3/8 3/4

Ameristar

NOTE: All dimensions are in mm/inches.

740 (29-1/8)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

Page 8: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 9: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4042D1000AA

TAG: _________________________________

3.5 Ton Split SystemAir Conditioner - 1 Phase M4AC4042D1000AA

SUBMITTAL

M4AC4042D1000AA208/230/1/60

21.635

SCROLL1 - 1

208/230/1/6015.9 - 112.3

NOPROPELLER

23 - 1DIRECT-1

37001 - 1/31075

208/230/1/601.70

PLATE FIN2 - 21

173/16

ORIFICE

7 LBS. - 16OZ.YES3/43/8

8º FW X H X D29x34-1/2x29

201190

NONO

M4AC4042D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

843 (33-3/16) 710 (28) 3/8 3/4

Ameristar

NOTE: All dimensions are in mm/inches.

710 (28)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

Page 10: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 11: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Product Specifications OUTDOOR UNIT

POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)

COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT

OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS

OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL

REFRIGERANT

LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.

CHARGING SPECIFICATION SUBCOOLING

DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

M4AC4048D1000AA

TAG: _________________________________

4.0 Ton Split SystemAir Conditioner - 1 Phase M4AC4048D1000AA

SUBMITTAL

M4AC4048D1000AA208/230/1/60

24.640

SCROLL1 - 1

208/230/1/6018.3 - 108

NOPROPELLER

23 - 1DIRECT-1

37001 - 1/31075

208/230/1/601.70

PLATE FIN2 - 21173/16

ORIFICE

7 LBS. - 16OZ.YES7/83/8

8º FW X H X D29x34-1/2x29

201190

NONO

M4AC4048D1000AA

Model H W L LIQUID VALVE SIZE GAS VALVE SIZE

843 (33-3/16) 710 (28) 3/8 7/8

Ameristar

NOTE: All dimensions are in mm/inches.

710 (28)

SUCTION LINE CONNECTION

CONTROL WIRING 7/8” (22.2mm)

KNOCKOUT 1-11/32” (34.5mm)

LIQUID LINE CONNECTION

SERVICE FITTING

SERVICE FITTING

POWER WIRING SEE DETAIL A

DETAIL A

HOLE 1-3/32” (27.8mm)

NOTE: GRILL APPEARANCE MAY VARY.

SERVICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.

Page 12: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order Numbe r SS-PRC007-EN

File Numbe r —

Supersede s SS-PRC007-EN 2/0 2

Stocking Locatio n PI Louisville & Webb/Mason Houston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesThermostats When choosing a thermostat,choose a non-programmable electric thermostat series. Please refer to the thermostat electrical manual wiring schematic.

Liquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/24/17

Page 13: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

P ro d u c t S p e c i f i c a t i o n s O U T D O O R U N I T P O W E R C O N N S . — V / P H / H Z M I N . B R C H . C I R . A M P A C I T Y B R . C I R . P R O T . R T G . - M A X . ( A M P S ) C O M P R E S S O R N O . U S E D - N O . S P E E D S V O L T S / P H / H Z R . L . A M P S - L . R . A M P S F A C T O R Y I N S T A L L E D S T A R T C O M P O N E N T S I N S U L A T I O N / S O U N D B L A N K E T C O M P R E S S O R H E A T O U T D O O R F A N D I A . ( I N . ) - N O . U S E D TY P E D R I V E - N O. S P E E D S C F M @ 0 . 0 I N . W . G . N O . M O T O R S - H P M O T O R S P E E D R . P . M . V O L T S / P H / H Z F . L . A M P S O U T D O O R C O I L — T Y P E R O W S - F . P . I . F A C E A R E A ( S Q . F T . ) T U B E S I Z E ( I N . ) R E F R I G E R A N T C O N T R O L R E F R I G E R A N T L B S . — R - 4 1 0 ( O . D . U N I T ) F A C T O R Y S U P P L I E D L I N E S I Z E - I N . O . D . G A S L I N E S I Z E - I N . O . D . L I Q . C H A R G I N G S P E C I F I C A T I O N S U B C O O L I N G D I M E N S I O N S C R A T E D ( I N . ) W E I G H T S H I P P I N G ( L B S . ) N E T ( L B S . )

M4AC4060C1000AA

TAG: ____________________________ _ _ _ _ _

5.0 T o n S p l i t S y s te m A i r Conditioner - 1 Phase M4AC4060C1000AA

S U B M I T T A L

M4AC4060C1000AA2 0 8 / 2 3 0 / 1 / 6 0

2845

S C R O L L 1 - 1

2 0 8 / 2 3 0 / 1 / 6 0 21 - 127.9

N O PROPELLER 23-5 / 8 - 1D I R E C T - 1

1 - 1 / 3 107 5

2 0 8 / 2 3 0 / 1 / 6 0 1.70

PLATE FIN 3 - 2118.4 3/16

O R I F I C E

7 L B S . - 12O Z . Y E S 7 / 8 3 / 8

8 º F W X H X D

30-1 / 5 x 34-1 / 2x30-1 / 5

214203

N O N O

M4AC4060C1000AA

M o d e l H W L L I Q U I D V A L VE S I Z E GAS V A L VE S I Z E

84 3 (33-3/16) 740 (29-1 / 8 ) 3 / 8 7 / 8

A m e r i s t a r

NOTE: All dimensions are in mm/inches.

740 (29-1 / 8 )

SUCTION LINE CONNECTION

CONTRO L WIRING 7/8” (22.2mm)

KNOCKOU T 1- 1 1/32” (34.5mm)

LIQUID LINE CONNECTION

SE R VICE FITTING

SE R VICE FITTING

POWER WIRING SEE DE T AI L A

DE T AI L A

HOLE 1-3/32” (27.8mm)

NOTE: GRIL L APPEARANCE M A Y V A R Y .

SE R VICE ACCESS ALLOW 24” CLEARANCE

AIR INLETS LOUVERED P ANELS ALLOW 12” MINIMUM CLEARANCE

W

ACCESS V A L VLE FOR LOW PRESSURE NOTE: ON L Y ADOPTED B Y HE A T PUM P , CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER V A L VE-SUCTION T O COMPRESSOR OR REFRIGERAN T CHARGE.

3800

Page 14: Trane Submittal - 3 Split System Heat Pump Model 1 Phase … · 2017. 10. 3. · 2.5 Ton Split System Air Conditioner - 1 Phase M4AC4030D1000AA SUBMITTAL M4AC4030D1000AA 208/230/1/60

Literature Order N um be r SS-PRC007-EN

File Num be r —

Supersede s SS-PRC007- EN 2/0 2

Stocking Locatio n PI Louisville & W ebb/M ason H ouston

Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

MechanicalSpecification Options

General

Casing

Refrigerant Controls

Scroll Compressor

Condenser Coil

Optional accessoriesLiquid line drier —

Ameristar

The M4AC40 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.

Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.

Refrigeration system controls include condenserfan, compressor contactor.

Features include low vibration and noise.

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.

It is used to filter out impurities and water in the system, ensures system clean and dry.

Revised 09/19/17