trane full brochure

80
Split System Cooling Product & Performance Data PUB. NO. TWE5-PRC002-EN-08-17-03 50 Hz Air Handler Models TWE030CA TWE040CA TWE050CA Condensing Models TTB0520 2TTB0524-536AA 2TTA0030-060AD TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM 1

Upload: james-cheney

Post on 28-Nov-2014

881 views

Category:

Documents


40 download

TRANSCRIPT

Page 1: Trane Full Brochure

Split SystemCooling Product& Performance Data

PUB. NO. TWE5-PRC002-EN-08-17-03

50 Hz

Air Handler ModelsTWE030CATWE040CATWE050CA

Condensing ModelsTTB05202TTB0524-536AA2TTA0030-060AD

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM1

Page 2: Trane Full Brochure

© 2003 American Standard Inc. All Rights Reserved 2 TWE5-PRC002-EN-08-17-03

GeneralFeatures

Split System Cooling Units . . .The Evolution Continues

technology and customer research todevelop the next generation of leadershipoutdoor products.

Couple the Trane reputation for reliabilityand durability with the above mentionedmission and accomplishments and youcontinue to have systems that prove“It’s Hard to Stop a Trane®. ”

2TTB0, 2TTA0 split systems represent aproduct that is not only an engineer’sdream, it’s also a customer’s dream. Thedesign team’s mission and accomplish-ment is enhanced performance andefficiency, improved reliability anddurability, and improved installabilityand serviceability.

Trane’s experienced design team applied“six sigma principles”, the latest computer

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM2

Page 3: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 3

Contents

General Features 2

Features and Benefits 4Condensing Units 4Air Handling Units 4Optional Equipment 5Low Outdoor Ambient Cooling 5

Selection Procedure 6Model Number Nomenclature for Condensing Units 6Model Number Nomenclature for Air Handlers 6

General Data 7TWE030CA40B 7TWE040CA40C 7TWE050CA50D 7TTB520CA00B0 82TTB0524AA000A 82TTB0530AA000A 82TTB0536AA000A 82TTA0030AD000A 92TTA0040AD000A 92TTA0050AD000A 92TTA0060AD000A 9

Performance Data 10TTB/TWE Cooling 102TTB/TWE Cooling 102TTA/TWE Cooling 16Evaporator Fan Performance 23Air Pressure Drop 24

Minimum Airflow (CFM) Heater Matrix 25

Electrical Data 26

Dimensions 30

Convertibility 34

Mechanical Specification Options 35Condensing Units 35Air Handling Units 36

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM3

Page 4: Trane Full Brochure

4 TWE5-PRC002-EN-08-17-03

• Climatuff® compressor• Efficiency up to 10 SEER• All aluminum Spine Fin™ coil• Duratuff™ base, fast complete drain,

weather proof• WeatherGuard™ fasteners

• New appearance with enhancedconsumer cues

• New tarpaulin gray cabinet withanthracite gray base

• Quick-Sess™ cabinet, service accessand refrigerant connections with full coilprotection

• Corrosion resistant finish• High/low pressure & temperature

protection• Liquid line filter-drier• Easy single side service• Brazed or flared connections• Multi-use liquid and suction line

service valves

Condensing Units(2TTB05_AA, 2TTA00_AD)

• Easy top & fan removal• Full length control and service valve

cover• Sure Fast™ seams louver panel

removal• HCFC-22 refrigerant• S.E.E.T. design testing• 100% line run test• Low ambient to 55°F as shipped• Low ambient to 40°F with

EDC accessory AY28X079• Low ambient to 30°F with EDC

accessory AY28X079 and TXV

2TTB05 &2TTA00

Features andBenefits

TWE

Air Handling Units(2TWE0_CA)

• Provision for 1-1/8 inches thick fieldsupplied electrostatic filter

• Reversible Duct Flanges – Fits up to1-1/2 inches duct board

• Improve controls access with controlbox mounted next to blower.

• 40 VA transformer with 5 amp automo-tive style fuse on 3 tons and less

• 5 Amp automotive style fuse replacesBussman “red cap” fuse on 3.5 to 5 tonmodels

• Blower mounting brackets improved –Front access to screw with power driver

• Improved bottom carton cushioning• 1 inch thick foil faced insulation for all

models

• Electrical, refrigerant, condensate andblower access convertible to either side

• Corrosion resistant galvanized steelwith attractive finish

• Internally enhanced finned coil tubes• Direct drive motor• Standard filters• Multi-speed blower• 220 volt primary and 24 volt secondary

transformer• Insulated cabinet• External access to heater circuit

breakers• Start kits are not required• Built-in indoor fan delay function for

increased efficiency. No kit required.• Improved filter access and latch –

Eliminate current T-bar and shippingbracket.

• Ships horizontal• Six way convertibility – horizontal (left

and right), upflow, downflow (front andrear access)

TTB05

• Vertical Air Discharge• High Efficiency TRANE Climatuff®

Compressor• Powder Paint finish• Brazed or flare connections

• Flexibility in application• Quality and reliability• Uniform covering for a smooth,

attractive and corrosion-resistant finish

Condensing Units(TTB05_CA)

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM4

Page 5: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 5

Optional Equipment

OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [✓✓✓✓✓] indicates accessories included).Indoor Thermostats — Htg./Clg. Programmable Thermostat .................................................................................TAYSTAT300C [ ]

Electronic, 2-Stg. Htg./1 Clg. .............................................................................................TAYSTAT302C [ ]Prog., 5/2 Day, Manual, 1 Htg./1 Clg. .................................................................................. TAYSTAT340 [ ]Prog., 5/2 Day, Manual, 2 (Gas) 1 Htg./1 Clg. ..................................................................... TAYSTAT350 [ ]Electronic, 1 Htg. (Gas)/1 Clg. (Non Prog.) .......................................................................... TAYSTAT370 [ ]Electronic, 1 Htg. (Elec.)/1 Clg. (Non Prog.)2 ..................................................................... TAYSTAT371 [ ]Electronic, 2 Htg. (Gas)/1 Clg. (Non Prog.) .......................................................................... TAYSTAT380 [ ]Manual, 2-Stg. Htg./1 Clg. ................................................................................................... TAYSTAT241 [ ]Heating/Cooling — Horizontal ................................................................................................. AY28X092 [ ]Cooling Only with Fan Switch .............................................................................................. BAYSTAT304 [ ]Heating/Cooling — Vertical .................................................................................................BAYSTAT305 [ ]Two-Stage Heating/Cooling — Horizontal1 ......................................................................... BAY28X183 [ ]One-Stage Heating/Cooling — Horizontal1 ......................................................................... BAY28X182 [ ]Thermostat Locking Cover3 ................................................................................................. BAY28X190 [ ]

Outdoor Thermostat ............................................................................................................................................... TAYSTAT250B [ ]Sub-base BAY28X182, 183 (Manual changeover)2 ................................................................................................. BAY28X185 [ ]Evaporator Defrost Control .......................................................................................................................................... AY28X079 [ ]Fan Delay Relay Kit ................................................................................................................................................... BAY24X045 [ ]5 Minute Delay Relay ............................................................................................................................................ TAYASCT501A [ ]Outdoor Temperature Sensor ............................................................................................................................... TAYSENS100A [ ]Start Kit 1.5-5 ton) ................................................................................................................................................... BAYKSKT257 [ ]Extreme Conditions Mounting Kit (2TTB05_AA, 2TTA0_AD) ................................................................................. BAYECMT001 [ ]Seacoast Kit ...........................................................................................................................................................BAYSEAC001 [ ]1 Requires sub-base2 Specifically designed for electric heat applications (instant on fan)3 Not for use with programmable thermostats

BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)5/8" ODM (90° bend, one end), 5/8" and 1/4" tubing ............................................................................................ TAYREFLN1__* [ ]3/4" ODM (90° bend, one end), 3/4" and 5/16" tubing .......................................................................................... TAYREFLN2__* [ ]7/8" ODM (90° bend, one end), 7/8" and 3/8" tubing ............................................................................................ TAYREFLN3__* [ ]1-1/8" ODM (90° bend, one end), 1-1/8" and 3/8" tubing ...................................................................................... TAYREFLN4__* [ ]* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.

Example: TAYREFLN220

Features andBenefits

Low Outdoor Ambient Cooling

Low Ambient As EvaporatorCooling Manufactured Defrost Control

FCCV Accutron™ 55°F 40°FThermal Expansion Valve (TXV) 55°F 30°F

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM5

Page 6: Trane Full Brochure

6 TWE5-PRC002-EN-08-17-03

Refrigerant Type2 = R-224 = R-410A

TRANE

Product TypeW = Split Heat PumpT = Split Cooling

Product FamilyZ = LEADERSHIP - 2 STAGEX = LEADERSHIPR = REPLACEMENT / RETAILB = BASICA = LIGHT COMMERCIAL

Family SEER0 =̃ 10 2 =̃ 12 4 =̃ 141 =̃ 11 3 =̃ 13 6 =̃ 16 8 =̃ 18

Unit PartsIdentifier

Minor DesignModifications

SecondaryFunction

Power Supply1 = 200 - 230 / 1 / 60 or 208 - 230 / 1 / 603 = 200 - 230 / 3 / 604 = 460 / 3 / 60A = 220 / 1 / 50D = 380-415 / 3 / 50

Major Design Modifications

Nominal Capacity in 000’s of BTU’s

Split System Connections 1 - 6 Tons0 = Brazed5 = Flare

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

2 T T B 0 5 3 6 A A 0 0 0 A A

SelectionProcedure

Model Number Nomenclature for Condensing Units (2TTB05, 2TTA00)

Product TypeTW = Split System Component

Heat Pump Compatible

Airflow ConfigurationE = Convertible

Refrigerant Connections0 = Brazed

Nominal Net CoolingCapacity30 = 30 MBh40 = 40 MBh50 = 50 MBh

Major Design Modification

ProductService Change

Minor DesignModification

Not Used

Refrigerant Flow Control4 = Accutron™ Flow Control/Check Valve5 = Bleed TXV

Electrical CharacteristicsA = 220V/1/50

Model Number Nomenclature for Air Handlers

1 2 3 4 5 6 7 8 9 10 11 12

T W E 0 3 0 C A 4 0 A 0

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM6

Page 7: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 7

TWE Product SpecificationsModel TWE030CA40B TWE040CA40C TWE050CA50DPower Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50Indoor Coil - Type Plate Fin Plate Fin Plate Fin

Rows 3 3 3Fins per inch (Fins per 25.4 mm) 14 14 14Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58)Tube Size in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)Refrigerant Control FCCV FCCV FCCVDrain Conn. Size in. (mm) 3/4 NPT 3/4 NPT 3/4 NPTDuct Connections See Outline Drawing See Outline Drawing See Outline Drawing

Indoor Fan - Type Centrifugal Centrifugal CentrifugalNo. Used 1 1 1Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4)Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0)Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3Airflow (High)

CFM @ 0.0 in. w.g. See Fan Performance Table See Fan Performance Table See Fan Performance TableCMH @ 0.0 Pa See Fan Performance Table See Fan Performance Table See Fan Performance Table

No. Motors - HP 1 - 1/3 1 - 1/3 1 - 3/4Motor RPM 1000 900 900Volts/Ph/Hz 220/1/50 220/1/50 220/1/50F.L. Amps 2.6 2.1 4.5L.R. Amps 3.3 4.2 10.1

FiltersVertical Applications

Filter Furnished Yes Yes YesType Furnished Throwaway Throwaway High VelocityNo.-Size-Thickness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1

Horizontal ApplicationsFilter Furnished No No NoType Recommended See Note Below See Note Below See Note BelowNo.-Size-Thickness See Note Below See Note Below See Note Below

Refrigerant Line SizeLine Size ID Gas in. (mm) 7/8 (22.23) 1-1/8 (28.56) 1-1/8 (28.56)Line Size ID Liquid in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Dimensions (H x W x D)Crated - in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5

- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597)Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0

- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)Weight Ibs. (kg)

Shipping 125 (56.7) 165 (74.8) 198 (898)Net 115 (52.2) 150 (68.0) 183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:Low Velocity Filter: Face Area (sq ft) = CFM/300High Velocity Filter: Face Area (sq ft) = CFM/500

GeneralData TWE

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM7

Page 8: Trane Full Brochure

8 TWE5-PRC002-EN-08-17-03

TTB/2TTB Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsMin. Brch. Cir. AmpacityBr. Cir. Max. (Amps)Prot. Rtg. } Min. (Amps)

Compressor - TypeNo. Used - No. SpeedsVolts/Ph/HzR.L. Amps 6 - L.R. AmpsFactory Installed

Start Components 7Insulation/Sound BlanketCompressor Heat

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3CMH @ 0.0 mm. w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg)ShippingNet

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE

SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

TTB520CA00B0200/230/1/50

PER LOCAL CODES142020

CLIMATUFF®

1200/230/1/50

9.6 - 66

NONONO

PROPELLER1

13.7 (348)DIRECT - 1

1300602

1 - 1/81620

200/230/1/501.1

SPINE FIN™1

24 (.945)6.62 (.615)3/8 (9.52)

3-LBS., 6-OZ. (110)NOM.

3/4 (0.053)5/16 (1.35)

24-3/4 X 20 X 20(629 X 508 X 508)

SEE OUTLINE DRAWINGS

121 (54.9)117 (53.1)

GeneralData TTB/2TTB

2TTB0530AA000A200/230/1/50

172520

CLIMATUFF®

1 - 1200/230/1/5012.9 - 77.9

NONONO

PROPELLER1

19 (483)DIRECT - 1

1825

31031 - 1/81075

200/230/1/500.9

SPINE FIN™1

24 (0.945)9.72 (0.90)3/8 (9.53)

4-LBS., 12-OZ. (2.16)YES

7/8 (22.2)3/8 (9.53)

.065

30.1 x 26.7 x 30.2(765 x 678 x 767)

178 (80.9)159 (72.3)

2TTB0536AA000A200/230/1/50

264040

CLIMATUFF®

1 - 1200/230/1/50

19.9 - 124

YESNONO

PROPELLER1

19 (483)DIRECT - 1

2075

35281 - 1/41075

200/230/1/501.3

SPINE FIN™1

24 (0.945)11.32 (1.05)3/8 (9.53)

5-LBS., 15-OZ. (2.70)YES

7/8 (22.2)3/8 (9.53)

.069

33.2 x 26.7 x 30.2(843 x 678 x 767)

215 (97.7)195 (88.6)

2TTB0524AA000A200/230/1/50

162520

CLIMATUFF®

1 - 1200/230/1/5012.2 - 74.8

NONONO

PROPELLER1

19 (483)DIRECT - 1

1825

31031 - 1/81075

200/230/1/500.9

SPINE FIN™1

24 (0.945)9.72 (0.90)3/8 (9.53)

4-LBS., 0-OZ. (1.82)YES

3/4 (19.1)5/16 (7.94)

.059

30.1 x 26.7 x 30.2765 x 678 x 767

175 (79.5)156 (70.9)

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM8

Page 9: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 9

GeneralData 2TTA

2TTA Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsMin. Brch. Cir. AmpacityBr. Cir. Max. (Amps)Prot. Rtg. } Min. (Amps)

Compressor - TypeNo. Used - No. SpeedsVolts/Ph/HzR.L. Amps 6 - L.R. AmpsFactory Installed

Start Components 7Insulation/Sound BlanketCompressor Heat

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3CMH @ 0.0 mm. w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg) Shipping Net

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE

SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

2TTA0040AD000A380/415/3/50

91515

CLIMATUFF®

1 - 1380/415/3/50

10 - 51

NONOYES

PROPELLER1

19 (483)DIRECT - 1

2075

35281 - 1/41075

380/415/3/500.7

SPINE FIN™1

24 (0.945)13.75 (1.28)

3/8 (9.53)

6-LBS., 13-OZ. (3.10)YES

1-1/8 (28.54)3/8 (9.53)

.075

33.2 x 26.7 x 30.2(843 x 678 x 767)

216 (98.2)196 (89.1)

2TTA0060AD000A380/415/3/50

142020

CLIMATUFF®

1 - 1380/415/3/50

9 - 73

NONOYES

PROPELLER1

27.6 (701)DIRECT - 1

3525

59931 - 1/6825

380/415/3/500.7

SPINE FIN™1

24 (0.945)27.75 (2.59)

3/8 (9.53)

10-LBS., 0-OZ. (4.55)YES

1-1/8 (28.54)3/8 (9.53)

.089

46.4 x 35.1 x 38.7(1179 x 892 x 983)

298 (135.5)263 (119.5)

2TTA0050AD000A380/415/3/50

122020

CLIMATUFF®

1 - 1380/415/3/50

14 - 70

NONOYES

PROPELLER1

23 (584)DIRECT - 1

3075

52281 - 1/4825

380/415/3/501.00

SPINE FIN™1

24 (0.945)18.75 (1.74)

3/8 (9.53)

7-LBS., 7-OZ. (3.38)YES

1-1/8 (28.54)3/8 (9.53)

.083H X W X D

38 x 30.1 x 33.8(965 x 765 x 859)

254 (115.5)227 (103.2)

2TTA0030AD000A380/415/3/50

71515

CLIMATUFF®

1 - 1380/415/3/50

8.3 - 46

NONOYES

PROPELLER1

19 (483)DIRECT - 1

2075

35281 - 1/41075

380/415/3/500.7

SPINE FIN™1

24 (0.945)11.32 (1.05)

3/8 (9.53)

5-LBS., 15-OZ. (2.70)YES

7/8 (22.2)3/8 (9.53)

.069

33.2 x 26.7 x 30.2(843 x 678 x 767)

207 (94.1)187 (85.0)

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM9

Page 10: Trane Full Brochure

10 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

TTB520CA-B WITH TWE030CA4 AT 700 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 18.4 15.6 16.9 18.2 18.8* 19.3* 1.41 47.285 63 19.9 13.1 14.4 15.7 17.0 18.2 1.45 51.1

67 21.3 10.4 11.7 12.9 14.2 15.5 1.50 55.371 22.8 7.6 8.9 10.1 11.4 12.7 1.55 59.559 18.1 15.5 16.7 18.0 18.5* 19.0* 1.47 47.5

90 63 19.4 13.0 14.2 15.5 16.8 18.1 1.52 51.467 20.9 10.2 11.5 12.8 14.0 15.3 1.57 55.671 22.3 7.4 8.7 10.0 11.2 12.5 1.62 59.959 17.7 15.3 16.6 17.8* 18.2* 18.6* 1.54 47.8

95 63 19.0 12.8 14.1 15.3 16.6 17.9 1.59 51.767 20.4 10.0 11.3 12.6 13.9 15.1 1.63 55.971 21.8 7.2 8.5 9.8 11.1 12.3 1.68 60.259 17.2 15.1 16.4 17.4* 17.8* 18.2* 1.61 48.1

100 63 18.5 12.6 13.9 15.1 16.4 17.7 1.66 52.067 19.8 9.8 11.1 12.4 13.7 14.9 1.70 56.271 21.2 7.0 8.3 9.6 10.8 12.1 1.75 60.559 16.8 14.9 16.2 17.0* 17.4* 17.8* 1.68 48.4

105 63 18.0 12.4 13.7 14.9 16.2 17.5 1.73 52.467 19.3 9.6 10.9 12.2 13.4 14.7 1.78 56.671 20.6 6.8 8.1 9.4 10.6 11.9 1.82 60.959 15.8 14.5 15.8 16.2* 16.6* 17.0* 1.83 49.1

115 63 16.9 12.0 13.2 14.5 15.8 17.0* 1.87 53.167 18.1 9.2 10.5 11.8 13.0 14.3 1.92 57.371 19.4 6.4 7.7 8.9 10.2 11.5 1.96 61.659 15.3 14.3 15.4* 15.8* 16.2* 16.6* 1.91 49.5

120 63 16.4 11.8 13.0 14.3 15.6 16.6* 1.95 53.467 17.6 9.0 10.3 11.5 12.8 14.1 1.99 57.771 18.7 6.2 7.5 8.7 10.0 11.3 2.03 62.0

2TTB0524AA WITH TWE030CA4 AT 900 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 23.9 21.1 22.8 24.1* 24.7* 25.3* 2.40 48.385 63 25.7 17.8 19.5 21.2 22.9 24.6 2.46 52.1

67 27.6 14.2 15.9 17.6 19.3 20.9 2.52 56.371 29.6 10.5 12.2 13.9 15.5 17.2 2.58 60.559 23.6 21.0 22.7 23.9* 24.5* 25.1* 2.50 48.4

90 63 25.4 17.7 19.4 21.1 22.8 24.5 2.56 52.367 27.3 14.1 15.8 17.5 19.1 20.8 2.62 56.471 29.3 10.4 12.1 13.7 15.4 17.1 2.68 60.759 23.3 20.9 22.6 23.7* 24.3* 24.9* 2.59 48.6

95 63 25.1 17.6 19.3 21.0 22.7 24.3 2.65 52.567 27.0 14.0 15.6 17.3 19.0 20.7 2.71 56.671 28.9 10.2 11.9 13.6 15.3 17.0 2.78 60.859 22.6 20.5 22.2 23.1* 23.7* 24.2* 2.67 49.0

100 63 24.3 17.3 18.9 20.6 22.3 24.0 2.73 52.967 26.2 13.6 15.3 17.0 18.7 20.4 2.79 57.171 28.0 9.9 11.6 13.3 15.0 16.7 2.85 61.359 21.9 20.2 21.9* 22.5* 23.0* 23.6* 2.76 49.5

105 63 23.6 16.9 18.6 20.3 22.0 23.6* 2.81 53.367 25.3 13.3 15.0 16.7 18.3 20.0 2.87 57.571 27.1 9.6 11.3 13.0 14.6 16.3 2.93 61.759 20.4 19.5 20.7* 21.2* 21.8* 22.3* 2.92 50.3

115 63 22.0 16.2 17.9 19.6 21.3 22.3* 2.97 54.267 23.6 12.6 14.3 16.0 17.7 19.4 3.02 58.471 25.3 8.9 10.6 12.3 14.0 15.7 3.08 62.659 19.7 19.2 20.1* 20.6* 21.1* 21.6* 3.01 50.8

120 63 21.2 15.9 17.6 19.3 21.0 21.6* 3.05 54.667 22.8 12.3 14.0 15.7 17.3 19.0 3.10 58.871 24.4 8.6 10.3 12.0 13.6 15.3 3.15 63.1

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 625 825TOTAL CAP. X0.99 X1.02SENS. CAP. X0.95 X1.08COMPR. KW X0.99 X1.01A.D.P. -1.1 1.4

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 20500 BTUHAIRFLOW = 725 CFMAPP. DEW PT. = 56.2 DEG. FCOMPRESSOR POWER = 1638 WATTSI.D. FAN POWER = 310 WATTSO.D. FAN POWER = 130 WATTSE.E.R. = 9.40 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 3/4 SUCT.AND 5/16 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 775 1025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.5 1.2

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 27000 BTUHAIRFLOW = 900 CFMAPP. DEW PT. = 56.6 DEG. FCOMPRESSOR POWER = 2143 WATTSI.D. FAN POWER = 425 WATTSO.D. FAN POWER = 146 WATTSS.E.E.R. = 10.19 BTUH/WATTE.E.R. = 9.33 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 3/4 SUCT.AND 5/16 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM10

Page 11: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 11

Performance DataCooling Metric Units

TTB520CA-B WITH TWE030CA4 AT 1189 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 5.4 4.6 5.0 5.3 5.5* 5.7* 1.429.4 17.2 5.8 3.8 4.2 4.6 5.0 5.3 1.5

19.4 6.2 3.0 3.4 3.8 4.2 4.5 1.521.7 6.7 2.2 2.6 3.0 3.3 3.7 1.515.0 5.3 4.5 4.9 5.3 5.4* 5.6* 1.5

32.2 17.2 5.7 3.8 4.2 4.5 4.9 5.3 1.519.4 6.1 3.0 3.4 3.8 4.1 4.5 1.621.7 6.5 2.2 2.5 2.9 3.3 3.7 1.615.0 5.2 4.5 4.9 5.2* 5.3* 5.4* 1.5

35.0 17.2 5.6 3.8 4.1 4.5 4.9 5.2 1.619.4 6.0 2.9 3.3 3.7 4.1 4.4 1.621.7 6.4 2.1 2.5 2.9 3.3 3.6 1.715.0 5.0 4.4 4.8 5.1* 5.2* 5.3* 1.6

37.8 17.2 5.4 3.7 4.1 4.4 4.8 5.2 1.719.4 5.8 2.9 3.3 3.6 4.0 4.4 1.721.7 6.2 2.1 2.4 2.8 3.2 3.5 1.815.0 4.9 4.4 4.7 5.0* 5.1* 5.2* 1.7

40.6 17.2 5.3 3.6 4.0 4.4 4.7 5.1 1.719.4 5.7 2.8 3.2 3.6 3.9 4.3 1.821.7 6.0 2.0 2.4 2.8 3.1 3.5 1.815.0 4.6 4.2 4.6 4.7* 4.9* 5.0* 1.8

46.1 17.2 5.0 3.5 3.9 4.2 4.6 5.0* 1.919.4 5.3 2.7 3.1 3.5 3.8 4.2 1.921.7 5.7 1.9 2.3 2.6 3.0 3.4 2.015.0 4.5 4.2 4.5* 4.6* 4.7* 4.9* 1.9

48.9 17.2 4.8 3.5 3.8 4.2 4.6 4.9* 2.019.4 5.2 2.6 3.0 3.4 3.8 4.1 2.021.7 5.5 1.8 2.2 2.5 2.9 3.3 2.0

2TTB0524AA WITH TWE030CA4 AT 1528 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 7.0 6.2 6.7 7.1* 7.2* 7.4* 2.429.4 17.2 7.5 5.2 5.7 6.2 6.7 7.2 2.5

19.4 8.1 4.2 4.7 5.2 5.7 6.1 2.521.7 8.7 3.1 3.6 4.1 4.5 5.0 2.615.0 6.9 6.2 6.7 7.0* 7.2* 7.4* 2.5

32.2 17.2 7.4 5.2 5.7 6.2 6.7 7.2 2.619.4 8.0 4.1 4.6 5.1 5.6 6.1 2.621.7 8.6 3.0 3.5 4.0 4.5 5.0 2.715.0 6.8 6.1 6.6 6.9* 7.1* 7.3* 2.6

35.0 17.2 7.4 5.2 5.7 6.2 6.7 7.1 2.719.4 7.9 4.1 4.6 5.1 5.6 6.1 2.721.7 8.5 3.0 3.5 4.0 4.5 5.0 2.815.0 6.6 6.0 6.5 6.8* 6.9* 7.1* 2.7

37.8 17.2 7.1 5.1 5.5 6.0 6.5 7.0 2.719.4 7.7 4.0 4.5 5.0 5.5 6.0 2.821.7 8.2 2.9 3.4 3.9 4.4 4.9 2.815.0 6.4 5.9 6.4* 6.6* 6.7* 6.9* 2.8

40.6 17.2 6.9 5.0 5.4 5.9 6.4 6.9* 2.819.4 7.4 3.9 4.4 4.9 5.4 5.9 2.921.7 7.9 2.8 3.3 3.8 4.3 4.8 2.915.0 6.0 5.7 6.1* 6.2* 6.4* 6.5* 2.9

46.1 17.2 6.4 4.7 5.2 5.7 6.2 6.5* 3.019.4 6.9 3.7 4.2 4.7 5.2 5.7 3.021.7 7.4 2.6 3.1 3.6 4.1 4.6 3.115.0 5.8 5.6 5.9* 6.0* 6.2* 6.3* 3.0

48.9 17.2 6.2 4.7 5.2 5.7 6.2 6.3* 3.019.4 6.7 3.6 4.1 4.6 5.1 5.6 3.121.7 7.1 2.5 3.0 3.5 4.0 4.5 3.2

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1061 1401TOTAL CAP. X0.99 X1.02SENS. CAP. X0.95 X1.08COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 6.01 KWAIRFLOW = 1231 CMHCOMPRESSOR POWER = 1638 WATTSI.D. FAN POWER = 310 WATTSO.D. FAN POWER = 130 WATTSE.E.R. = 9.40 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.AND 5/16 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1316 1741TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 7.91 KWAIRFLOW = 1528 CMHCOMPRESSOR POWER = 2143 WATTSI.D. FAN POWER = 425 WATTSO.D. FAN POWER = 146 WATTSS.E.E.R. = 10.19 BTUH/WATTE.E.R. = 9.33 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.AND 5/16 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM11

Page 12: Trane Full Brochure

12 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

2TTB0530AA WITH TWE030CA4 AT 1000 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 26.7 23.4 25.3 26.8* 27.5* 28.2* 2.79 48.085 63 28.7 19.8 21.6 23.5 25.3 27.2 2.86 51.9

67 30.7 15.8 17.6 19.4 21.3 23.1 2.93 56.171 32.8 11.6 13.5 15.3 17.2 19.0 3.01 60.459 26.4 23.3 25.1 26.6* 27.3* 27.9* 2.91 48.2

90 63 28.3 19.6 21.5 23.3 25.2 27.0 2.98 52.167 30.3 15.6 17.5 19.3 21.2 23.0 3.05 56.371 32.4 11.5 13.4 15.2 17.0 18.9 3.13 60.659 26.1 23.1 25.0 26.3* 27.0* 27.6* 3.03 48.4

95 63 28.0 19.5 21.3 23.2 25.0 26.9 3.10 52.367 30.0 15.5 17.3 19.2 21.0 22.9 3.18 56.571 32.1 11.4 13.2 15.1 16.9 18.8 3.25 60.759 25.2 22.7 24.6 25.6* 26.3* 26.9* 3.13 48.9

100 63 27.1 19.1 20.9 22.8 24.6 26.5 3.20 52.867 29.0 15.1 16.9 18.8 20.6 22.5 3.28 57.071 31.0 11.0 12.8 14.7 16.5 18.4 3.36 61.259 24.3 22.3 24.2 24.9* 25.5* 26.1* 3.24 49.4

105 63 26.1 18.7 20.5 22.4 24.2 26.1 3.31 53.367 28.0 14.7 16.5 18.4 20.2 22.1 3.38 57.571 30.0 10.6 12.4 14.3 16.1 18.0 3.46 61.759 22.6 21.5 22.8* 23.5* 24.0* 24.6* 3.45 50.3

115 63 24.3 17.9 19.7 21.6 23.4 24.6* 3.51 54.267 26.0 13.9 15.7 17.6 19.4 21.3 3.58 58.471 27.8 9.8 11.7 13.5 15.3 17.2 3.65 62.759 21.7 21.1 22.1* 22.7* 23.3* 23.8* 3.56 50.8

120 63 23.3 17.5 19.4 21.2 23.0 23.8* 3.62 54.767 25.0 13.5 15.3 17.2 19.0 20.9 3.68 58.971 26.8 9.4 11.3 13.1 15.0 16.8 3.75 63.2

2TTB0530AA WITH TWE040CA4-B AT 1100 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 28.7 25.7 27.8 29.1* 29.8* 30.5* 2.71 48.485 63 30.7 21.5 23.6 25.7 27.8 29.9 2.78 52.4

67 32.8 16.9 19.0 21.1 23.2 25.3 2.85 56.671 35.0 12.2 14.3 16.4 18.5 20.6 2.93 61.059 28.3 25.5 27.6 28.8* 29.5* 30.1* 2.83 48.6

90 63 30.3 21.3 23.4 25.5 27.6 29.8 2.90 52.667 32.3 16.7 18.8 20.9 23.0 25.1 2.98 56.871 34.5 12.0 14.1 16.3 18.4 20.5 3.06 61.259 27.9 25.3 27.4 28.5* 29.1* 29.8* 2.96 48.8

95 63 29.9 21.1 23.3 25.4 27.5 29.6 3.03 52.867 31.9 16.5 18.7 20.8 22.9 25.0 3.11 57.071 34.0 11.9 14.0 16.1 18.2 20.3 3.18 61.359 26.9 24.9 27.0* 27.7* 28.3* 28.9* 3.06 49.2

100 63 28.9 20.7 22.8 24.9 27.0 28.9* 3.13 53.267 30.8 16.1 18.2 20.3 22.4 24.6 3.21 57.471 32.9 11.5 13.6 15.7 17.8 19.9 3.29 61.859 26.0 24.5 26.2* 26.9* 27.5* 28.1* 3.16 49.7

105 63 27.9 20.3 22.4 24.5 26.6 28.1* 3.24 53.667 29.8 15.7 17.8 19.9 22.0 24.1 3.31 57.971 31.8 11.0 13.2 15.3 17.4 19.5 3.39 62.259 24.1 23.7 24.6* 25.2* 25.8* 26.4* 3.38 50.5

115 63 25.9 19.5 21.6 23.7 25.8 26.4* 3.45 54.567 27.6 14.9 17.0 19.1 21.2 23.3 3.52 58.771 29.5 10.2 12.3 14.4 16.6 18.7 3.59 63.059 23.2 23.2* 23.8* 24.4* 25.0* 25.6* 3.49 50.9

120 63 24.8 19.1 21.2 23.3 25.0* 25.6* 3.55 54.967 26.6 14.5 16.6 18.7 20.8 22.9 3.62 59.171 28.4 9.8 11.9 14.0 16.1 18.3 3.69 63.5

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 30000 BTUHAIRFLOW = 1000 CFMAPP. DEW PT. = 56.5 DEG. FCOMPRESSOR POWER = 2591 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 149 WATTSS.E.E.R. = 9.95 BTUH/WATTE.E.R. = 8.96 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.98 X1.01SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 32000 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 57.2 DEG. FCOMPRESSOR POWER = 2660 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 149 WATTSS.E.E.R. = 11.00 BTUH/WATTE.E.R. = 9.80 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM12

Page 13: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 13

Performance DataCooling Metric Units

2TTB0530AA WITH TWE030CA4 AT 1698 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 7.8 6.9 7.4 7.9* 8.1* 8.3* 2.829.4 17.2 8.4 5.8 6.3 6.9 7.4 8.0 2.9

19.4 9.0 4.6 5.2 5.7 6.2 6.8 2.921.7 9.6 3.4 4.0 4.5 5.0 5.6 3.015.0 7.7 6.8 7.4 7.8* 8.0* 8.2* 2.9

32.2 17.2 8.3 5.7 6.3 6.8 7.4 7.9 3.019.4 8.9 4.6 5.1 5.7 6.2 6.7 3.021.7 9.5 3.4 3.9 4.5 5.0 5.5 3.115.0 7.6 6.8 7.3 7.7* 7.9* 8.1* 3.0

35.0 17.2 8.2 5.7 6.2 6.8 7.3 7.9 3.119.4 8.8 4.5 5.1 5.6 6.2 6.7 3.221.7 9.4 3.3 3.9 4.4 5.0 5.5 3.315.0 7.4 6.7 7.2 7.5* 7.7* 7.9* 3.1

37.8 17.2 7.9 5.6 6.1 6.7 7.2 7.8 3.219.4 8.5 4.4 5.0 5.5 6.0 6.6 3.321.7 9.1 3.2 3.8 4.3 4.8 5.4 3.415.0 7.1 6.5 7.1 7.3* 7.5* 7.6* 3.2

40.6 17.2 7.6 5.5 6.0 6.6 7.1 7.6 3.319.4 8.2 4.3 4.8 5.4 5.9 6.5 3.421.7 8.8 3.1 3.6 4.2 4.7 5.3 3.515.0 6.6 6.3 6.7* 6.9* 7.0* 7.2* 3.5

46.1 17.2 7.1 5.2 5.8 6.3 6.9 7.2* 3.519.4 7.6 4.1 4.6 5.2 5.7 6.2 3.621.7 8.1 2.9 3.4 4.0 4.5 5.0 3.715.0 6.4 6.2 6.5* 6.7* 6.8* 7.0* 3.6

48.9 17.2 6.8 5.1 5.7 6.2 6.7 7.0* 3.619.4 7.3 4.0 4.5 5.0 5.6 6.1 3.721.7 7.9 2.8 3.3 3.8 4.4 4.9 3.8

2TTB0530AA WITH TWE040CA4-B AT 1868 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.4 7.5 8.1 8.5* 8.7* 8.9* 2.729.4 17.2 9.0 6.3 6.9 7.5 8.1 8.8 2.8

19.4 9.6 5.0 5.6 6.2 6.8 7.4 2.821.7 10.3 3.6 4.2 4.8 5.4 6.0 2.915.0 8.3 7.5 8.1 8.4* 8.6* 8.8* 2.8

32.2 17.2 8.9 6.2 6.9 7.5 8.1 8.7 2.919.4 9.5 4.9 5.5 6.1 6.7 7.4 3.021.7 10.1 3.5 4.1 4.8 5.4 6.0 3.115.0 8.2 7.4 8.0 8.4* 8.5* 8.7* 3.0

35.0 17.2 8.8 6.2 6.8 7.4 8.1 8.7 3.019.4 9.3 4.8 5.5 6.1 6.7 7.3 3.121.7 10.0 3.5 4.1 4.7 5.3 5.9 3.215.0 7.9 7.3 7.9* 8.1* 8.3* 8.5* 3.1

37.8 17.2 8.5 6.1 6.7 7.3 7.9 8.5* 3.119.4 9.0 4.7 5.3 5.9 6.6 7.2 3.221.7 9.6 3.4 4.0 4.6 5.2 5.8 3.315.0 7.6 7.2 7.7* 7.9* 8.1* 8.2* 3.2

40.6 17.2 8.2 5.9 6.6 7.2 7.8 8.2* 3.219.4 8.7 4.6 5.2 5.8 6.4 7.1 3.321.7 9.3 3.2 3.9 4.5 5.1 5.7 3.415.0 7.1 6.9 7.2* 7.4* 7.6* 7.7* 3.4

46.1 17.2 7.6 5.7 6.3 6.9 7.6 7.7* 3.519.4 8.1 4.4 5.0 5.6 6.2 6.8 3.521.7 8.6 3.0 3.6 4.2 4.9 5.5 3.615.0 6.8 6.8* 7.0* 7.1* 7.3* 7.5* 3.5

48.9 17.2 7.3 5.6 6.2 6.8 7.3* 7.5* 3.519.4 7.8 4.2 4.9 5.5 6.1 6.7 3.621.7 8.3 2.9 3.5 4.1 4.7 5.4 3.7

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 8.79 KWAIRFLOW = 1698 CMHCOMPRESSOR POWER = 2591 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 149 WATTSS.E.E.R. = 9.95 BTUH/WATTE.E.R. = 8.96 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.98 X1.01SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.38 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2660 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 149 WATTSS.E.E.R. = 11.00 BTUH/WATTE.E.R. = 9.80 BTUH/WATTNOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.

AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM13

Page 14: Trane Full Brochure

14 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

2TTB0536AA WITH TWE030CA4 AT 1100 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 32.4 27.1 29.1 31.1 32.7* 33.6* 3.21 47.085 63 35.0 23.3 25.3 27.3 29.3 31.3 3.30 50.7

67 37.8 19.0 21.0 23.0 25.0 27.0 3.39 54.771 40.6 14.6 16.6 18.6 20.6 22.6 3.48 58.859 32.0 26.9 28.9 30.9 32.4* 33.2* 3.34 47.2

90 63 34.6 23.1 25.1 27.1 29.1 31.1 3.43 50.967 37.3 18.8 20.8 22.8 24.8 26.8 3.53 55.071 40.1 14.4 16.4 18.4 20.4 22.4 3.63 59.159 31.6 26.7 28.7 30.7 32.0* 32.9* 3.48 47.4

95 63 34.2 22.9 24.9 26.9 28.9 30.9 3.57 51.267 36.9 18.6 20.6 22.6 24.6 26.6 3.67 55.271 39.7 14.2 16.2 18.2 20.2 22.3 3.76 59.359 30.5 26.2 28.2 30.2 31.2* 32.0* 3.59 48.1

100 63 33.0 22.3 24.4 26.4 28.4 30.4 3.68 51.867 35.6 18.1 20.1 22.1 24.1 26.1 3.78 55.871 38.3 13.7 15.7 17.7 19.7 21.7 3.87 59.959 29.4 25.7 27.7 29.5* 30.3* 31.1* 3.71 48.7

105 63 31.8 21.8 23.8 25.8 27.9 29.9 3.79 52.467 34.3 17.5 19.6 21.6 23.6 25.6 3.89 56.471 36.9 13.2 15.2 17.2 19.2 21.2 3.98 60.659 27.1 24.6 26.6 27.7* 28.5* 29.2* 3.94 49.8

115 63 29.4 20.8 22.8 24.8 26.8 28.8 4.02 53.667 31.7 16.5 18.5 20.5 22.5 24.5 4.10 57.771 34.2 12.1 14.1 16.2 18.2 20.2 4.19 61.859 26.0 24.1 26.1* 26.8* 27.5* 28.2* 4.06 50.4

120 63 28.2 20.3 22.3 24.3 26.3 28.2* 4.14 54.267 30.5 16.0 18.0 20.0 22.0 24.0 4.21 58.271 32.8 11.6 13.6 15.6 17.7 19.7 4.29 62.4

2TTB0536AA WITH TWE040CA4-B AT 1400 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 35.5 32.0 34.6 36.1* 37.1* 38.0* 3.21 48.685 63 38.2 26.9 29.5 32.2 34.8 37.4 3.30 52.5

67 41.1 21.3 23.9 26.5 29.1 31.7 3.40 56.671 44.0 15.5 18.1 20.7 23.4 26.0 3.50 60.959 35.0 31.8 34.4 35.7* 36.6* 37.5* 3.36 48.8

90 63 37.7 26.7 29.3 31.9 34.5 37.2 3.45 52.767 40.5 21.0 23.7 26.3 28.9 31.5 3.55 56.871 43.4 15.3 17.9 20.5 23.1 25.8 3.65 61.159 34.5 31.5 34.2 35.3* 36.2* 37.1* 3.50 49.0

95 63 37.1 26.4 29.1 31.7 34.3 36.9 3.60 52.967 39.9 20.8 23.4 26.0 28.7 31.3 3.69 57.071 42.8 15.0 17.7 20.3 22.9 25.5 3.80 61.359 33.2 31.0 33.3* 34.3* 35.1* 36.0* 3.61 49.5

100 63 35.8 25.9 28.5 31.1 33.7 36.0* 3.71 53.467 38.5 20.2 22.9 25.5 28.1 30.7 3.80 57.571 41.2 14.5 17.1 19.7 22.3 25.0 3.90 61.859 32.0 30.4 32.3* 33.2* 34.0* 34.9* 3.72 49.9

105 63 34.5 25.3 27.9 30.5 33.2 34.9* 3.81 53.867 37.0 19.7 22.3 24.9 27.5 30.1 3.91 58.071 39.7 13.9 16.5 19.2 21.8 24.4 4.01 62.259 29.5 29.3 30.3* 31.1* 31.9* 32.7* 3.95 50.9

115 63 31.8 24.2 26.8 29.4 31.9* 32.7* 4.04 54.767 34.2 18.6 21.2 23.8 26.4 29.0 4.12 58.971 36.7 12.8 15.4 18.1 20.7 23.3 4.22 63.259 28.2 28.4* 29.2* 30.0* 30.8* 31.5* 4.07 51.3

120 63 30.5 23.6 26.3 28.9 30.8* 31.5* 4.15 55.267 32.8 18.0 20.6 23.2 25.9 28.5 4.23 59.471 35.2 12.3 14.9 17.5 20.1 22.8 4.32 63.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.98 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.8 1.4

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 37000 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 55.4 DEG. FCOMPRESSOR POWER = 2959 WATTSI.D. FAN POWER = 541 WATTSO.D. FAN POWER = 187 WATTSS.E.E.R. = 10.48 BTUH/WATTE.E.R. = 9.43 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1225 1575TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.3 1.0

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 40000 BTUHAIRFLOW = 1430 CFMAPP. DEW PT. = 57.2 DEG. FCOMPRESSOR POWER = 3114 WATTSI.D. FAN POWER = 410 WATTSO.D. FAN POWER = 187 WATTSS.E.E.R. = 11.61 BTUH/WATTE.E.R. = 10.31 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM14

Page 15: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 15

Performance DataCooling Metric Units

2TTB0536AA WITH TWE030CA4 AT 1868 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.5 7.9 8.5 9.1 9.6* 9.8* 3.229.4 17.2 10.3 6.8 7.4 8.0 8.6 9.2 3.3

19.4 11.1 5.6 6.2 6.7 7.3 7.9 3.421.7 11.9 4.3 4.9 5.4 6.0 6.6 3.515.0 9.4 7.9 8.5 9.1 9.5* 9.7* 3.3

32.2 17.2 10.1 6.8 7.4 7.9 8.5 9.1 3.419.4 10.9 5.5 6.1 6.7 7.3 7.9 3.521.7 11.7 4.2 4.8 5.4 6.0 6.6 3.615.0 9.3 7.8 8.4 9.0 9.4* 9.6* 3.5

35.0 17.2 10.0 6.7 7.3 7.9 8.5 9.1 3.619.4 10.8 5.4 6.0 6.6 7.2 7.8 3.721.7 11.6 4.2 4.7 5.3 5.9 6.5 3.815.0 8.9 7.7 8.3 8.8 9.1* 9.4* 3.6

37.8 17.2 9.7 6.5 7.1 7.7 8.3 8.9 3.719.4 10.4 5.3 5.9 6.5 7.1 7.6 3.821.7 11.2 4.0 4.6 5.2 5.8 6.4 3.915.0 8.6 7.5 8.1 8.6* 8.9* 9.1* 3.7

40.6 17.2 9.3 6.4 7.0 7.6 8.2 8.8 3.819.4 10.0 5.1 5.7 6.3 6.9 7.5 3.921.7 10.8 3.9 4.5 5.0 5.6 6.2 4.015.0 7.9 7.2 7.8 8.1* 8.4* 8.6* 3.9

46.1 17.2 8.6 6.1 6.7 7.3 7.9 8.4 4.019.4 9.3 4.8 5.4 6.0 6.6 7.2 4.121.7 10.0 3.5 4.1 4.7 5.3 5.9 4.215.0 7.6 7.1 7.6* 7.9* 8.1* 8.3* 4.1

48.9 17.2 8.3 5.9 6.5 7.1 7.7 8.3* 4.119.4 8.9 4.7 5.3 5.9 6.4 7.0 4.221.7 9.6 3.4 4.0 4.6 5.2 5.8 4.3

2TTB0536AA WITH TWE040CA4-B AT 2378 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 10.4 9.4 10.1 10.6* 10.9* 11.1* 3.229.4 17.2 11.2 7.9 8.6 9.4 10.2 11.0 3.3

19.4 12.0 6.2 7.0 7.8 8.5 9.3 3.421.7 12.9 4.5 5.3 6.1 6.9 7.6 3.515.0 10.3 9.3 10.1 10.5* 10.7* 11.0* 3.4

32.2 17.2 11.0 7.8 8.6 9.3 10.1 10.9 3.519.4 11.9 6.2 6.9 7.7 8.5 9.2 3.521.7 12.7 4.5 5.2 6.0 6.8 7.6 3.715.0 10.1 9.2 10.0 10.3* 10.6* 10.9* 3.5

35.0 17.2 10.9 7.7 8.5 9.3 10.0 10.8 3.619.4 11.7 6.1 6.9 7.6 8.4 9.2 3.721.7 12.5 4.4 5.2 5.9 6.7 7.5 3.815.0 9.7 9.1 9.8* 10.0* 10.3* 10.5* 3.6

37.8 17.2 10.5 7.6 8.4 9.1 9.9 10.5* 3.719.4 11.3 5.9 6.7 7.5 8.2 9.0 3.821.7 12.1 4.2 5.0 5.8 6.5 7.3 3.915.0 9.4 8.9 9.5* 9.7* 10.0* 10.2* 3.7

40.6 17.2 10.1 7.4 8.2 8.9 9.7 10.2* 3.819.4 10.8 5.8 6.5 7.3 8.1 8.8 3.921.7 11.6 4.1 4.8 5.6 6.4 7.1 4.015.0 8.6 8.6 8.9* 9.1* 9.3* 9.6* 4.0

46.1 17.2 9.3 7.1 7.9 8.6 9.3* 9.6* 4.019.4 10.0 5.4 6.2 7.0 7.7 8.5 4.121.7 10.8 3.8 4.5 5.3 6.1 6.8 4.215.0 8.3 8.3* 8.6* 8.8* 9.0* 9.2* 4.1

48.9 17.2 8.9 6.9 7.7 8.5 9.0* 9.2* 4.219.4 9.6 5.3 6.0 6.8 7.6 8.4 4.221.7 10.3 3.6 4.4 5.1 5.9 6.7 4.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.98 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 10.84 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2959 WATTSI.D. FAN POWER = 541 WATTSO.D. FAN POWER = 187 WATTSS.E.E.R. = 10.48 BTUH/WATTE.E.R. = 9.43 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2080 2675TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 11.72 KWAIRFLOW = 2428 CMHCOMPRESSOR POWER = 3114 WATTSI.D. FAN POWER = 410 WATTSO.D. FAN POWER = 187 WATTSS.E.E.R. = 11.61 BTUH/WATTE.E.R. = 10.31 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM15

Page 16: Trane Full Brochure

16 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

2TTA0030AD WITH TWE030CA4 AT 1000 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 30.5 25.3 27.1 29.0 30.6* 31.4* 2.88 46.485 63 32.9 21.7 23.6 25.4 27.3 29.1 2.95 50.5

67 35.4 17.7 19.6 21.5 23.3 25.2 3.03 54.571 38.0 13.7 15.5 17.4 19.2 21.1 3.11 58.659 30.1 25.1 26.9 28.8 30.3* 31.1* 3.00 46.9

90 63 32.5 21.5 23.4 25.2 27.1 28.9 3.08 50.767 35.0 17.6 19.4 21.3 23.1 25.0 3.15 54.771 37.5 13.5 15.3 17.2 19.0 20.9 3.23 58.959 29.7 24.9 26.7 28.6 30.0* 30.8* 3.13 47.2

95 63 32.0 21.3 23.2 25.0 26.9 28.7 3.21 51.067 34.5 17.4 19.2 21.1 22.9 24.8 3.28 55.071 37.0 13.3 15.2 17.0 18.9 20.7 3.36 59.159 28.6 24.3 26.2 28.1 29.1* 29.8* 3.24 47.9

100 63 30.8 20.8 22.6 24.5 26.3 28.2 3.31 51.667 33.2 16.8 18.7 20.5 22.4 24.2 3.38 55.771 35.7 12.8 14.6 16.5 18.3 20.2 3.46 59.959 27.4 23.8 25.7 27.5* 28.2* 28.9* 3.34 48.5

105 63 29.6 20.3 22.1 24.0 25.8 27.7 3.41 52.367 31.9 16.3 18.1 20.0 21.9 23.7 3.48 56.471 34.3 12.2 14.1 15.9 17.8 19.6 3.56 60.659 25.2 22.8 24.6 25.6* 26.3* 27.0* 3.56 49.8

115 63 27.2 19.2 21.1 22.9 24.8 26.6 3.62 53.667 29.3 15.2 17.1 18.9 20.8 22.6 3.69 57.771 31.5 11.2 13.0 14.9 16.7 18.6 3.75 61.959 24.0 22.3 24.1* 24.8* 25.4* 26.0* 3.67 50.4

120 63 26.0 18.7 20.5 22.4 24.2 26.0* 3.73 54.267 28.0 14.7 16.6 18.4 20.3 22.1 3.79 58.471 30.1 10.7 12.5 14.4 16.2 18.1 3.85 62.6

2TTA0030AD WITH TWE040CA4-B AT 1100 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 32.5 27.5 29.6 31.7 33.0* 33.8* 2.81 47.185 63 35.0 23.3 25.5 27.6 29.7 31.8 2.88 51.0

67 37.5 18.8 20.9 23.0 25.1 27.2 2.96 55.271 40.2 14.2 16.3 18.4 20.5 22.6 3.04 59.459 32.0 27.2 29.3 31.4 32.6* 33.4* 2.94 47.4

90 63 34.4 23.1 25.2 27.3 29.4 31.5 3.01 51.367 36.9 18.6 20.7 22.8 24.9 27.0 3.09 55.471 39.5 13.9 16.0 18.1 20.2 22.4 3.17 59.759 31.5 27.0 29.1 31.2 32.2* 33.0* 3.07 47.6

95 63 33.9 22.9 25.0 27.1 29.2 31.3 3.14 51.567 36.4 18.3 20.4 22.6 24.7 26.8 3.22 55.771 38.9 13.7 15.8 17.9 20.0 22.1 3.30 59.959 30.3 26.4 28.5 30.4* 31.2* 31.9* 3.17 48.2

100 63 32.6 22.3 24.4 26.5 28.6 30.7 3.24 52.167 35.0 17.8 19.9 22.0 24.1 26.2 3.32 56.371 37.4 13.1 15.2 17.4 19.5 21.6 3.40 60.559 29.0 25.9 28.0 29.4* 30.2* 30.9* 3.27 48.8

105 63 31.3 21.8 23.9 26.0 28.1 30.2 3.35 52.767 33.6 17.2 19.3 21.4 23.5 25.6 3.42 56.971 35.9 12.6 14.7 16.8 18.9 21.0 3.50 61.159 26.6 24.8 26.7* 27.4* 28.1* 28.8* 3.49 49.9

115 63 28.6 20.6 22.7 24.9 27.0 28.8* 3.55 53.867 30.7 16.1 18.2 20.3 22.4 24.5 3.62 58.071 32.9 11.5 13.6 15.7 17.8 19.9 3.69 62.359 25.4 24.2 25.7* 26.4* 27.0* 27.7* 3.60 50.5

120 63 27.3 20.1 22.2 24.3 26.4 27.7* 3.66 54.467 29.3 15.6 17.7 19.8 21.9 24.0 3.72 58.671 31.4 10.9 13.0 15.2 17.3 19.4 3.79 62.9

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 34500 BTUHAIRFLOW = 1000 CFMAPP. DEW PT. = 55.0 DEG. FCOMPRESSOR POWER = 2662 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 184 WATTSS.E.E.R. = 11.07 BTUH/WATTE.E.R. = 9.91 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.97 X1.02SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 36500 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 55.9 DEG. FCOMPRESSOR POWER = 2742 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 184 WATTSS.E.E.R. = 12.31 BTUH/WATTE.E.R. = 10.90 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM16

Page 17: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 17

Performance DataCooling Metric Units

2TTA0030AD WITH TWE030CA4 AT 1698 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.9 7.4 7.9 8.5 9.0* 9.2* 2.929.4 17.2 9.6 6.4 6.9 7.4 8.0 8.5 3.0

19.4 10.4 5.2 5.7 6.3 6.8 7.4 3.021.7 11.1 4.0 4.5 5.1 5.6 6.2 3.115.0 8.8 7.4 7.9 8.4 8.9* 9.1* 3.0

32.2 17.2 9.5 6.3 6.9 7.4 7.9 8.5 3.119.4 10.3 5.2 5.7 6.2 6.8 7.3 3.221.7 11.0 4.0 4.5 5.0 5.6 6.1 3.215.0 8.7 7.3 7.8 8.4 8.8* 9.0* 3.1

35.0 17.2 9.4 6.2 6.8 7.3 7.9 8.4 3.219.4 10.1 5.1 5.6 6.2 6.7 7.3 3.321.7 10.8 3.9 4.5 5.0 5.5 6.1 3.415.0 8.4 7.1 7.7 8.2 8.5* 8.7* 3.2

37.8 17.2 9.0 6.1 6.6 7.2 7.7 8.3 3.319.4 9.7 4.9 5.5 6.0 6.6 7.1 3.421.7 10.5 3.8 4.3 4.8 5.4 5.9 3.515.0 8.0 7.0 7.5 8.1* 8.3* 8.5* 3.3

40.6 17.2 8.7 5.9 6.5 7.0 7.6 8.1 3.419.4 9.3 4.8 5.3 5.9 6.4 6.9 3.521.7 10.0 3.6 4.1 4.7 5.2 5.7 3.615.0 7.4 6.7 7.2 7.5* 7.7* 7.9* 3.6

46.1 17.2 8.0 5.6 6.2 6.7 7.3 7.8 3.619.4 8.6 4.5 5.0 5.5 6.1 6.6 3.721.7 9.2 3.3 3.8 4.4 4.9 5.4 3.815.0 7.0 6.5 7.1* 7.3* 7.4* 7.6* 3.7

48.9 17.2 7.6 5.5 6.0 6.6 7.1 7.6* 3.719.4 8.2 4.3 4.9 5.4 5.9 6.5 3.821.7 8.8 3.1 3.7 4.2 4.7 5.3 3.8

2TTA0030AD WITH TWE040CA4-B AT 1868 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.5 8.1 8.7 9.3 9.7* 9.9* 2.829.4 17.2 10.3 6.8 7.5 8.1 8.7 9.3 2.9

19.4 11.0 5.5 6.1 6.7 7.4 8.0 3.021.7 11.8 4.2 4.8 5.4 6.0 6.6 3.015.0 9.4 8.0 8.6 9.2 9.6* 9.8* 2.9

32.2 17.2 10.1 6.8 7.4 8.0 8.6 9.2 3.019.4 10.8 5.4 6.1 6.7 7.3 7.9 3.121.7 11.6 4.1 4.7 5.3 5.9 6.6 3.215.0 9.2 7.9 8.5 9.1 9.4* 9.7* 3.1

35.0 17.2 9.9 6.7 7.3 7.9 8.6 9.2 3.119.4 10.7 5.4 6.0 6.6 7.2 7.9 3.221.7 11.4 4.0 4.6 5.2 5.9 6.5 3.315.0 8.9 7.7 8.4 8.9* 9.1* 9.3* 3.2

37.8 17.2 9.6 6.5 7.1 7.8 8.4 9.0 3.219.4 10.3 5.2 5.8 6.4 7.1 7.7 3.321.7 11.0 3.8 4.5 5.1 5.7 6.3 3.415.0 8.5 7.6 8.2 8.6* 8.8* 9.1* 3.3

40.6 17.2 9.2 6.4 7.0 7.6 8.2 8.8 3.319.4 9.8 5.0 5.7 6.3 6.9 7.5 3.421.7 10.5 3.7 4.3 4.9 5.5 6.2 3.515.0 7.8 7.3 7.8* 8.0* 8.2* 8.4* 3.5

46.1 17.2 8.4 6.0 6.7 7.3 7.9 8.4* 3.519.4 9.0 4.7 5.3 5.9 6.6 7.2 3.621.7 9.6 3.4 4.0 4.6 5.2 5.8 3.715.0 7.4 7.1 7.5* 7.7* 7.9* 8.1* 3.6

48.9 17.2 8.0 5.9 6.5 7.1 7.7 8.1* 3.719.4 8.6 4.6 5.2 5.8 6.4 7.0 3.721.7 9.2 3.2 3.8 4.5 5.1 5.7 3.8

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 10.11 KWAIRFLOW = 1698 CMHCOMPRESSOR POWER = 2662 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 184 WATTSS.E.E.R. = 11.07 BTUH/WATTE.E.R. = 9.91 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.97 X1.02SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 10.69 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2742 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 184 WATTSS.E.E.R. = 12.31 BTUH/WATTE.E.R. = 10.90 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM17

Page 18: Trane Full Brochure

18 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

2TTA0040AD WITH TWE040CA4-B AT 1500 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 38.5 34.5 37.3 39.1* 40.1* 41.0* 3.58 48.485 63 41.4 29.0 31.8 34.6 37.4 40.2 3.71 52.3

67 44.4 23.0 25.8 28.6 31.4 34.1 3.84 56.571 47.5 16.8 19.6 22.4 25.2 28.0 3.97 60.859 37.9 34.2 37.0 38.6* 39.6* 40.5* 3.74 48.7

90 63 40.8 28.8 31.6 34.3 37.1 39.9 3.88 52.667 43.7 22.7 25.5 28.3 31.1 33.9 4.01 56.771 46.8 16.5 19.3 22.1 24.9 27.7 4.16 61.059 37.3 34.0 36.8 38.1* 39.1* 40.0* 3.91 48.9

95 63 40.1 28.5 31.3 34.1 36.9 39.7 4.04 52.867 43.0 22.4 25.2 28.0 30.8 33.6 4.19 57.071 46.1 16.3 19.1 21.9 24.6 27.4 4.34 61.259 35.8 33.3 35.9* 36.8* 37.7* 38.6* 4.04 49.5

100 63 38.5 27.8 30.6 33.4 36.2 38.6* 4.18 53.467 41.3 21.7 24.5 27.3 30.1 32.9 4.33 57.571 44.2 15.6 18.4 21.2 24.0 26.7 4.48 61.859 34.2 32.6 34.6* 35.5* 36.4* 37.2* 4.16 50.0

105 63 36.8 27.1 29.9 32.7 35.4 37.2* 4.31 53.967 39.5 21.0 23.8 26.6 29.4 32.2 4.47 58.171 42.3 14.9 17.7 20.5 23.3 26.0 4.62 62.459 31.1 31.1* 32.0* 32.8* 33.6* 34.5* 4.42 51.1

115 63 33.5 25.7 28.5 31.3 33.6* 34.5* 4.58 55.067 36.0 19.6 22.4 25.2 28.0 30.8 4.74 59.271 38.5 13.5 16.3 19.1 21.9 24.7 4.91 63.559 29.5 29.8* 30.7* 31.5* 32.3* 33.0* 4.55 51.6

120 63 31.8 25.0 27.8 30.6 32.3* 33.0* 4.71 55.567 34.2 19.0 21.8 24.5 27.3 30.1 4.88 59.771 36.6 12.8 15.6 18.4 21.2 24.0 5.05 64.0

2TTA0040AD WITH TWE050CA5-C AT 1500 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 39.7 34.8 37.7 40.0* 41.0* 41.9* 3.69 48.085 63 42.6 29.3 32.1 34.9 37.8 40.6 3.82 51.9

67 45.6 23.2 26.0 28.8 31.6 34.5 3.95 56.171 48.8 17.0 19.8 22.6 25.4 28.2 4.09 60.459 38.7 34.4 37.2 39.2* 40.2* 41.1* 3.84 48.3

90 63 41.6 28.9 31.7 34.5 37.3 40.1 3.97 52.267 44.5 22.7 25.6 28.4 31.2 34.0 4.11 56.471 47.6 16.5 19.3 22.2 25.0 27.8 4.25 60.759 37.8 34.0 36.8 38.4* 39.4* 40.3* 3.98 48.6

95 63 40.5 28.4 31.2 34.1 36.9 39.7 4.12 52.667 43.4 22.3 25.1 27.9 30.8 33.6 4.26 56.871 46.4 16.1 18.9 21.7 24.5 27.4 4.41 61.159 36.5 33.4 36.2 37.4* 38.3* 39.1* 4.13 49.1

100 63 39.2 27.9 30.7 33.5 36.3 39.1 4.27 53.067 41.9 21.7 24.6 27.4 30.2 33.0 4.42 57.271 44.8 15.5 18.3 21.2 24.0 26.8 4.57 61.559 35.2 32.8 35.3* 36.3* 37.2* 38.0* 4.28 49.5

105 63 37.8 27.3 30.1 32.9 35.7 38.0* 4.42 53.567 40.5 21.2 24.0 26.8 29.6 32.4 4.58 57.771 43.2 14.9 17.8 20.6 23.4 26.2 4.74 62.059 32.7 31.7 33.3* 34.1* 34.9* 35.7* 4.57 50.4

115 63 35.0 26.2 29.0 31.8 34.6 35.7* 4.73 54.367 37.5 20.0 22.9 25.7 28.5 31.3 4.89 58.671 40.1 13.8 16.6 19.5 22.3 25.1 5.06 62.859 31.4 31.2 32.2* 33.0* 33.8* 34.6* 4.72 50.8

120 63 33.7 25.6 28.4 31.2 33.8* 34.6* 4.88 54.767 36.1 19.5 22.3 25.1 27.9 30.7 5.05 59.071 38.5 13.3 16.1 18.9 21.7 24.5 5.22 63.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1300 1700TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 43000 BTUHAIRFLOW = 1498 CFMAPP. DEW PT. = 57.0 DEG. FCOMPRESSOR POWER = 3591 WATTSI.D. FAN POWER = 423 WATTSO.D. FAN POWER = 175 WATTSS.E.E.R. = 11.18 BTUH/WATTE.E.R. = 9.86 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1300 1700TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 43500 BTUHAIRFLOW = 1546 CFMAPP. DEW PT. = 57.1 DEG. FCOMPRESSOR POWER = 3593 WATTSI.D. FAN POWER = 521 WATTSO.D. FAN POWER = 175 WATTSS.E.E.R. = 10.99 BTUH/WATTE.E.R. = 9.63 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM18

Page 19: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 19

Performance DataCooling Metric Units

2TTA0040AD WITH TWE040CA4-B AT 2547 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.3 10.1 10.9 11.5* 11.7* 12.0* 3.629.4 17.2 12.1 8.5 9.3 10.1 11.0 11.8 3.7

19.4 13.0 6.7 7.6 8.4 9.2 10.0 3.821.7 13.9 4.9 5.7 6.6 7.4 8.2 4.015.0 11.1 10.0 10.8 11.3* 11.6* 11.9* 3.7

32.2 17.2 12.0 8.4 9.3 10.0 10.9 11.7 3.919.4 12.8 6.7 7.5 8.3 9.1 9.9 4.021.7 13.7 4.8 5.7 6.5 7.3 8.1 4.215.0 10.9 10.0 10.8 11.2* 11.5* 11.7* 3.9

35.0 17.2 11.7 8.4 9.2 10.0 10.8 11.6 4.019.4 12.6 6.6 7.4 8.2 9.0 9.8 4.221.7 13.5 4.8 5.6 6.4 7.2 8.0 4.315.0 10.5 9.8 10.5* 10.8* 11.0* 11.3* 4.0

37.8 17.2 11.3 8.1 9.0 9.8 10.6 11.3* 4.219.4 12.1 6.4 7.2 8.0 8.8 9.6 4.321.7 13.0 4.6 5.4 6.2 7.0 7.8 4.515.0 10.0 9.6 10.1* 10.4* 10.7* 10.9* 4.2

40.6 17.2 10.8 7.9 8.8 9.6 10.4 10.9* 4.319.4 11.6 6.2 7.0 7.8 8.6 9.4 4.521.7 12.4 4.4 5.2 6.0 6.8 7.6 4.615.0 9.1 9.1* 9.4* 9.6* 9.8* 10.1* 4.4

46.1 17.2 9.8 7.5 8.4 9.2 9.8* 10.1* 4.619.4 10.5 5.7 6.6 7.4 8.2 9.0 4.721.7 11.3 4.0 4.8 5.6 6.4 7.2 4.915.0 8.6 8.7* 9.0* 9.2* 9.5* 9.7* 4.6

48.9 17.2 9.3 7.3 8.1 9.0 9.5* 9.7* 4.719.4 10.0 5.6 6.4 7.2 8.0 8.8 4.921.7 10.7 3.8 4.6 5.4 6.2 7.0 5.1

2TTA0040AD WITH TWE050CA5-C AT 2547 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.6 10.2 11.0 11.7* 12.0* 12.3* 3.729.4 17.2 12.5 8.6 9.4 10.2 11.1 11.9 3.8

19.4 13.4 6.8 7.6 8.4 9.3 10.1 4.021.7 14.3 5.0 5.8 6.6 7.4 8.3 4.115.0 11.3 10.1 10.9 11.5* 11.8* 12.0* 3.8

32.2 17.2 12.2 8.5 9.3 10.1 10.9 11.7 4.019.4 13.0 6.7 7.5 8.3 9.1 10.0 4.121.7 13.9 4.8 5.7 6.5 7.3 8.1 4.315.0 11.1 10.0 10.8 11.3* 11.5* 11.8* 4.0

35.0 17.2 11.9 8.3 9.1 10.0 10.8 11.6 4.119.4 12.7 6.5 7.4 8.2 9.0 9.8 4.321.7 13.6 4.7 5.5 6.4 7.2 8.0 4.415.0 10.7 9.8 10.6 11.0* 11.2* 11.5* 4.1

37.8 17.2 11.5 8.2 9.0 9.8 10.6 11.5 4.319.4 12.3 6.4 7.2 8.0 8.8 9.7 4.421.7 13.1 4.5 5.4 6.2 7.0 7.9 4.615.0 10.3 9.6 10.3* 10.6* 10.9* 11.1* 4.3

40.6 17.2 11.1 8.0 8.8 9.6 10.5 11.1* 4.419.4 11.9 6.2 7.0 7.9 8.7 9.5 4.621.7 12.7 4.4 5.2 6.0 6.9 7.7 4.715.0 9.6 9.3 9.8* 10.0* 10.2* 10.5* 4.6

46.1 17.2 10.3 7.7 8.5 9.3 10.1 10.5* 4.719.4 11.0 5.9 6.7 7.5 8.4 9.2 4.921.7 11.7 4.0 4.9 5.7 6.5 7.4 5.115.0 9.2 9.1 9.4* 9.7* 9.9* 10.1* 4.7

48.9 17.2 9.9 7.5 8.3 9.1 9.9* 10.1* 4.919.4 10.6 5.7 6.5 7.4 8.2 9.0 5.121.7 11.3 3.9 4.7 5.5 6.4 7.2 5.2

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2208 2887TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.60 KWAIRFLOW = 2544 CMHCOMPRESSOR POWER = 3591 WATTSI.D. FAN POWER = 423 WATTSO.D. FAN POWER = 175 WATTSS.E.E.R. = 11.18 BTUH/WATTE.E.R. = 9.86 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT. AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2208 2887TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.75 KWAIRFLOW = 2626 CMHCOMPRESSOR POWER = 3593 WATTSI.D. FAN POWER = 521 WATTSO.D. FAN POWER = 175 WATTSS.E.E.R. = 10.99 BTUH/WATTE.E.R. = 9.63 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM19

Page 20: Trane Full Brochure

20 TWE5-PRC002-EN-08-17-03

Performance DataCooling English Units

2TTA0050AD WITH TWE040CA4-B AT 1500 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 46.9 38.6 41.4 44.2 46.9* 48.0* 4.44 46.185 63 50.3 33.2 36.0 38.8 41.6 44.4 4.58 50.3

67 53.9 27.0 29.9 32.7 35.5 38.3 4.74 54.571 57.6 20.8 23.6 26.4 29.2 32.0 4.89 58.759 46.3 38.3 41.2 44.0 46.5* 47.5* 4.64 46.4

90 63 49.7 32.9 35.7 38.5 41.3 44.1 4.79 50.667 53.3 26.8 29.6 32.4 35.2 38.0 4.95 54.771 56.9 20.5 23.3 26.1 28.9 31.7 5.11 58.959 45.7 38.1 40.9 43.7 46.0* 47.1* 4.84 47.0

95 63 49.1 32.6 35.4 38.2 41.0 43.8 5.00 50.867 52.6 26.5 29.3 32.1 34.9 37.7 5.16 55.071 56.2 20.2 23.1 25.9 28.7 31.5 5.32 59.259 44.0 37.3 40.1 42.9 44.6* 45.8* 5.01 47.6

100 63 47.3 31.8 34.6 37.4 40.2 43.0 5.16 51.567 50.7 25.7 28.5 31.3 34.1 36.9 5.33 55.671 54.2 19.5 22.3 25.1 27.9 30.7 5.49 59.959 42.4 36.5 39.3 42.1 43.3* 44.4* 5.18 48.3

105 63 45.5 31.0 33.8 36.6 39.4 42.2 5.33 52.167 48.8 24.9 27.7 30.5 33.4 36.2 5.50 56.371 52.2 18.7 21.5 24.3 27.1 29.9 5.66 60.559 39.1 35.0 37.8 39.6* 40.6* 41.6* 5.52 49.5

115 63 42.0 29.5 32.3 35.1 37.9 40.7 5.68 53.467 45.1 23.4 26.2 29.0 31.8 34.6 5.84 57.671 48.2 17.2 20.0 22.8 25.6 28.4 6.00 61.859 37.4 34.2 37.0 38.2* 39.2* 40.2* 5.70 50.1

120 63 40.3 28.7 31.5 34.3 37.1 39.9 5.85 54.067 43.2 22.6 25.4 28.3 31.1 33.9 6.01 58.271 46.2 16.4 19.2 22.1 24.9 27.7 6.17 62.4

2TTA0050AD WITH TWE050CA5-C AT 1800 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 49.5 42.8 46.1 49.5 50.7* 51.9* 4.81 47.685 63 53.1 36.2 39.5 42.9 46.2 49.6 4.96 51.5

67 56.8 28.9 32.2 35.6 38.9 42.3 5.12 55.771 60.6 21.4 24.8 28.1 31.5 34.8 5.28 60.059 48.4 42.3 45.6 48.6* 49.9* 51.0* 5.00 47.9

90 63 51.9 35.7 39.0 42.4 45.7 49.1 5.15 51.967 55.5 28.4 31.7 35.1 38.4 41.8 5.31 56.171 59.3 20.9 24.3 27.6 31.0 34.3 5.48 60.459 47.3 41.8 45.1 47.7* 48.9* 50.0* 5.19 48.3

95 63 50.7 35.2 38.5 41.9 45.2 48.6 5.34 52.267 54.3 27.9 31.2 34.6 37.9 41.3 5.51 56.471 57.9 20.4 23.8 27.1 30.5 33.8 5.68 60.759 46.0 41.2 44.5 46.6* 47.8* 48.8* 5.38 48.7

100 63 49.2 34.5 37.9 41.2 44.6 47.9 5.54 52.667 52.7 27.2 30.6 33.9 37.3 40.6 5.70 56.971 56.2 19.8 23.1 26.5 29.8 33.2 5.87 61.259 44.6 40.5 43.9 45.4* 46.6* 47.6* 5.57 49.1

105 63 47.8 33.9 37.3 40.6 43.9 47.3 5.73 53.167 51.1 26.6 29.9 33.3 36.6 40.0 5.89 57.371 54.5 19.2 22.5 25.8 29.2 32.5 6.07 61.659 41.8 39.3 42.1* 43.2* 44.2* 45.1* 5.95 49.9

115 63 44.8 32.6 36.0 39.3 42.7 45.1* 6.11 53.967 47.9 25.3 28.7 32.0 35.4 38.7 6.28 58.171 51.1 17.9 21.2 24.6 27.9 31.3 6.45 62.459 40.4 38.7 40.9* 42.0* 42.9* 43.9* 6.15 50.4

120 63 43.3 32.0 35.4 38.7 42.1 43.9* 6.31 54.367 46.3 24.7 28.1 31.4 34.7 38.1 6.47 58.671 49.4 17.3 20.6 24.0 27.3 30.7 6.64 62.9

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1300 1700TOTAL CAP. X0.97 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.98 X1.01A.D.P. -1.8 1.4

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 52500 BTUHAIRFLOW = 1494 CFMAPP. DEW PT. = 54.9 DEG. FCOMPRESSOR POWER = 4475 WATTSI.D. FAN POWER = 464 WATTSO.D. FAN POWER = 217 WATTSS.E.E.R. = 11.01 BTUH/WATTE.E.R. = 9.79 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 54000 BTUHAIRFLOW = 1750 CFMAPP. DEW PT. = 56.1 DEG. FCOMPRESSOR POWER = 4533 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 217 WATTSS.E.E.R. = 10.54 BTUH/WATTE.E.R. = 9.34 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM20

Page 21: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 21

Performance DataCooling Metric Units

2TTA0050AD WITH TWE040CA4-B AT 2547 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 13.7 11.3 12.1 13.0 13.7* 14.1* 4.429.4 17.2 14.7 9.7 10.5 11.4 12.2 13.0 4.6

19.4 15.8 7.9 8.8 9.6 10.4 11.2 4.721.7 16.9 6.1 6.9 7.7 8.6 9.4 4.915.0 13.6 11.2 12.1 12.9 13.6* 13.9* 4.6

32.2 17.2 14.6 9.6 10.5 11.3 12.1 12.9 4.819.4 15.6 7.9 8.7 9.5 10.3 11.1 4.921.7 16.7 6.0 6.8 7.6 8.5 9.3 5.115.0 13.4 11.2 12.0 12.8 13.5* 13.8* 4.8

35.0 17.2 14.4 9.6 10.4 11.2 12.0 12.8 5.019.4 15.4 7.8 8.6 9.4 10.2 11.0 5.221.7 16.5 5.9 6.8 7.6 8.4 9.2 5.315.0 12.9 10.9 11.7 12.6 13.1* 13.4* 5.0

37.8 17.2 13.9 9.3 10.1 11.0 11.8 12.6 5.219.4 14.9 7.5 8.4 9.2 10.0 10.8 5.321.7 15.9 5.7 6.5 7.4 8.2 9.0 5.515.0 12.4 10.7 11.5 12.3 12.7* 13.0* 5.2

40.6 17.2 13.3 9.1 9.9 10.7 11.5 12.4 5.319.4 14.3 7.3 8.1 8.9 9.8 10.6 5.521.7 15.3 5.5 6.3 7.1 7.9 8.8 5.715.0 11.5 10.3 11.1 11.6* 11.9* 12.2* 5.5

46.1 17.2 12.3 8.6 9.5 10.3 11.1 11.9 5.719.4 13.2 6.9 7.7 8.5 9.3 10.1 5.821.7 14.1 5.0 5.9 6.7 7.5 8.3 6.015.0 11.0 10.0 10.8 11.2* 11.5* 11.8* 5.7

48.9 17.2 11.8 8.4 9.2 10.0 10.9 11.7 5.819.4 12.7 6.6 7.4 8.3 9.1 9.9 6.021.7 13.5 4.8 5.6 6.5 7.3 8.1 6.2

2TTA0050AD WITH TWE050CA5-C AT 3057 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 14.5 12.5 13.5 14.5 14.9* 15.2* 4.829.4 17.2 15.6 10.6 11.6 12.6 13.5 14.5 5.0

19.4 16.6 8.5 9.4 10.4 11.4 12.4 5.121.7 17.8 6.3 7.3 8.2 9.2 10.2 5.315.0 14.2 12.4 13.4 14.2* 14.6* 14.9* 5.0

32.2 17.2 15.2 10.5 11.4 12.4 13.4 14.4 5.219.4 16.3 8.3 9.3 10.3 11.3 12.2 5.321.7 17.4 6.1 7.1 8.1 9.1 10.0 5.515.0 13.9 12.2 13.2 14.0* 14.3* 14.6* 5.2

35.0 17.2 14.9 10.3 11.3 12.3 13.2 14.2 5.319.4 15.9 8.2 9.1 10.1 11.1 12.1 5.521.7 17.0 6.0 7.0 7.9 8.9 9.9 5.715.0 13.5 12.1 13.0 13.7* 14.0* 14.3* 5.4

37.8 17.2 14.4 10.1 11.1 12.1 13.1 14.0 5.519.4 15.4 8.0 9.0 9.9 10.9 11.9 5.721.7 16.5 5.8 6.8 7.8 8.7 9.7 5.915.0 13.1 11.9 12.9 13.3* 13.7* 13.9* 5.6

40.6 17.2 14.0 9.9 10.9 11.9 12.9 13.9 5.719.4 15.0 7.8 8.8 9.8 10.7 11.7 5.921.7 16.0 5.6 6.6 7.6 8.6 9.5 6.115.0 12.2 11.5 12.3* 12.7* 13.0* 13.2* 5.9

46.1 17.2 13.1 9.6 10.5 11.5 12.5 13.2* 6.119.4 14.0 7.4 8.4 9.4 10.4 11.3 6.321.7 15.0 5.2 6.2 7.2 8.2 9.2 6.415.0 11.8 11.3 12.0* 12.3* 12.6* 12.9* 6.2

48.9 17.2 12.7 9.4 10.4 11.3 12.3 12.9* 6.319.4 13.6 7.2 8.2 9.2 10.2 11.2 6.521.7 14.5 5.1 6.0 7.0 8.0 9.0 6.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2208 2887TOTAL CAP. X0.97 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.98 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 15.38 KWAIRFLOW = 2537 CMHCOMPRESSOR POWER = 4475 WATTSI.D. FAN POWER = 464 WATTSO.D. FAN POWER = 217 WATTSS.E.E.R. = 11.01 BTUH/WATTE.E.R. = 9.79 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 15.82 KWAIRFLOW = 2972 CMHCOMPRESSOR POWER = 4533 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 217 WATTSS.E.E.R. = 10.54 BTUH/WATTE.E.R. = 9.34 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM21

Page 22: Trane Full Brochure

22 TWE5-PRC002-EN-08-17-03

Performance DataCooling

Performance DataCooling

Metric Units

English Units

2TTA0060AD WITH TWE050CA5-C AT 1800 CFMO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 55.2 45.5 48.9 52.2 55.4* 56.6* 5.23 46.185 63 59.3 39.0 42.3 45.7 49.0 52.4 5.33 50.3

67 63.5 31.7 35.0 38.4 41.7 45.1 5.43 54.471 67.9 24.2 27.6 30.9 34.3 37.6 5.53 58.759 54.3 45.1 48.4 51.8 54.6* 55.9* 5.50 46.8

90 63 58.3 38.5 41.9 45.2 48.6 51.9 5.61 50.667 62.4 31.2 34.6 37.9 41.3 44.6 5.72 54.871 66.7 23.8 27.1 30.5 33.8 37.2 5.83 59.059 53.3 44.6 48.0 51.3 53.8* 55.1* 5.77 47.1

95 63 57.2 38.1 41.4 44.8 48.1 51.5 5.89 50.967 61.3 30.8 34.1 37.5 40.8 44.2 6.01 55.171 65.5 23.3 26.7 30.0 33.4 36.7 6.14 59.359 52.0 44.0 47.4 50.7 52.8* 54.1* 6.08 47.5

100 63 55.8 37.4 40.8 44.1 47.5 50.8 6.21 51.467 59.8 30.2 33.5 36.9 40.2 43.6 6.35 55.571 63.9 22.7 26.1 29.4 32.8 36.1 6.49 59.859 50.7 43.4 46.8 50.1 51.7* 53.0* 6.38 47.9

105 63 54.4 36.8 40.2 43.5 46.9 50.2 6.53 51.867 58.3 29.6 32.9 36.3 39.6 43.0 6.68 56.071 62.4 22.1 25.5 28.8 32.2 35.5 6.84 60.259 48.1 42.2 45.6 48.4* 49.7* 50.8* 6.96 48.7

115 63 51.7 35.6 39.0 42.3 45.7 49.0 7.15 52.667 55.4 28.4 31.7 35.1 38.4 41.8 7.35 56.871 59.2 20.9 24.3 27.6 31.0 34.3 7.56 61.159 46.8 41.6 45.0 47.3* 48.6* 49.7* 7.24 49.1

120 63 50.3 35.0 38.4 41.7 45.1 48.4 7.46 53.067 53.9 27.8 31.1 34.5 37.8 41.2 7.69 57.271 57.6 20.3 23.7 27.0 30.4 33.7 7.92 61.5

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.7 1.3

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 61000 BTUHAIRFLOW = 1750 CFMAPP. DEW PT. = 54.8 DEG. FCOMPRESSOR POWER = 5033 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 224 WATTSS.E.E.R. = 11.08 BTUH/WATTE.E.R. = 9.76 BTUH/WATT

NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COIL

2TTA0060AD WITH TWE050CA5-C AT 3057 CMHO.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 16.2 13.3 14.3 15.3 16.2* 16.6* 5.229.4 17.2 17.4 11.4 12.4 13.4 14.4 15.4 5.3

19.4 18.6 9.3 10.3 11.3 12.2 13.2 5.421.7 19.9 7.1 8.1 9.1 10.0 11.0 5.515.0 15.9 13.2 14.2 15.2 16.0* 16.4* 5.5

32.2 17.2 17.1 11.3 12.3 13.2 14.2 15.2 5.619.4 18.3 9.1 10.1 11.1 12.1 13.1 5.721.7 19.5 7.0 7.9 8.9 9.9 10.9 5.815.0 15.6 13.1 14.1 15.0 15.8* 16.1* 5.8

35.0 17.2 16.8 11.2 12.1 13.1 14.1 15.1 5.919.4 18.0 9.0 10.0 11.0 12.0 13.0 6.021.7 19.2 6.8 7.8 8.8 9.8 10.8 6.115.0 15.2 12.9 13.9 14.9 15.5* 15.9* 6.1

37.8 17.2 16.3 11.0 12.0 12.9 13.9 14.9 6.219.4 17.5 8.8 9.8 10.8 11.8 12.8 6.321.7 18.7 6.7 7.6 8.6 9.6 10.6 6.515.0 14.9 12.7 13.7 14.7 15.1* 15.5* 6.4

40.6 17.2 15.9 10.8 11.8 12.7 13.7 14.7 6.519.4 17.1 8.7 9.6 10.6 11.6 12.6 6.721.7 18.3 6.5 7.5 8.4 9.4 10.4 6.815.0 14.1 12.4 13.4 14.2* 14.6* 14.9* 7.0

46.1 17.2 15.1 10.4 11.4 12.4 13.4 14.4 7.219.4 16.2 8.3 9.3 10.3 11.3 12.2 7.321.7 17.3 6.1 7.1 8.1 9.1 10.0 7.615.0 13.7 12.2 13.2 13.9* 14.2* 14.6* 7.2

48.9 17.2 14.7 10.3 11.3 12.2 13.2 14.2 7.519.4 15.8 8.1 9.1 10.1 11.1 12.1 7.721.7 16.9 5.9 6.9 7.9 8.9 9.9 7.9

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 17.87 KWAIRFLOW = 2972 CMHCOMPRESSOR POWER = 5033 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 224 WATTSS.E.E.R. = 11.08 BTUH/WATTE.E.R. = 9.76 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM22

Page 23: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 23

PerformanceData

Evaporator Fan Performance

Blower Performance — TWE040CA40C — Wet CoilEXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)

UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)220 VOLTS 220 VOLTS

CFM CMH Hl MED LO Hl MED LO700 1188.6 0.58 (144.5)750 1273.5 0.61 (152.0) 0.55 (137.0)800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5)850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5)900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1)

1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6)1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2)1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7)1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8)1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3)1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9)1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5)1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8)1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9)1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9)1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance — TWE030CA40B — Wet CoilEXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)

UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)220 VOLTS 220 VOLTS

CFM CMH Hl MED LO Hl MED LO600 1018.8 0.72 (179.4) 0.71 (176.9)650 1103.7 0.62 (154.4) 0.61 (152.0)700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6)750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1)800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7)850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3)900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7)

1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3)1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0)1100 1867.8 0.31 (77.2) 0.31 (77.2)1150 1952.7 0.20 (49.8) 0.22 (54.8)1200 2037.6 0.08 (19.9) 0.10 (24.9)

NOTES:Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM23

Page 24: Trane Full Brochure

24 TWE5-PRC002-EN-08-17-03

Air Pressure Drop (Inches) – Electric Heaters

Pressure Drop For Electric Heaters In Air Handler Models

NUMBER OF RACKS1 2 3 4 5

AIRFLOW AIRFLOW AIR PRESSURE DROPCFM CMH IN. W.G. (PASCALS)600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5)

1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9)1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9)1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4)1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4)1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4)1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4)1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3)1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3)1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3)1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3)2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)

NOTES:1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.2. Heater model numbers may have additional suffix digits.

PerformanceData

Blower Performance — TWE050CA50D — Wet CoilEXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)

UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)220 VOLTS 220 VOLTS

CFM CMH Hl MED LO Hl MED LO900 1528.2950 1613.1 0.63 (156.9)1000 1698.0 0.61 (152.0) 0.62 (154.4)1050 1782.9 0.58 (144.5) 0.60 (149.5)1100 1867.8 0.54 (134.5) 0.57 (142.0)1150 1952.7 0.50 (124.6) 0.53 (132.0)1200 2037.6 0.45 (112.1) 0.49 (122.1)1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6)1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7)1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7)1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3)1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8)1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4)1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0)1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6)1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2)1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7)1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8)1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4)1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4)1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5)1950 3311.1 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

Evaporator Fan Performance

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM24

Page 25: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 25

Minimum Airflow (CFM)Heater Matrix

A Heater Matrix for All TWEMINIMUM HEATING AIRFLOW CFM – HEATER MATRIX

AIRHANDLER HEATER MODEL NUMBER BAYHTR—

MODELNUMBER

1405 000BRKPDC

4.80kw

1408 000BRKPDC

7.68kw

1410 000BRKPDC

3410 0009.60kw

1415 BRK15.36kw

3415 00015.36kw

1419 BRK19.20kw

1425 BRK24.96kw

NUMBER OFHEATER RACKS 1 2 2 2 2 4 5

NUMBER OFCIRCUITS 1 1 1 2 1 2 3

TWE030C L/L L/L L/L L/L L/L — —

TWE040C L/L L/L L/L L/L L/L L/H L/H

TWE050C L/L L/L L/L L/L L/L L/H L/H

(Example: L=Low, M=Medium, H=High Speed)Cooling/Heat Pump Air FlowAS = Heater application is affected based on whether the outdoor unit is a heat pump or cooling unit.PS = Minimum speed tap varies based on air handler installation position.

000 = Pigtails, BRK = Contains circuit breakers, PDC = Contains Pull DisconnectRBR = Contains recessed circuit breaker (for 14" deep TVF018-024 Models only)RPD = contains recessed pull disconnect (for 14" deep TV0F18-024 Models only)* For upflow position only minimum setting is 1200

CAUTION: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local electrical codes.

HEATER RACKSHEATER NO. OF

MODEL NO. RACKSBAY96X1405 1BAY96X1406 2BAY96X1408 2BAY96X1410 2BAY96X1411 3BAY96X1415 3BAY96X1419 4BAY96X1421 4BAY96X1426 5BAY96X3411 3BAY96X3415 3

THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM25

Page 26: Trane Full Brochure

26 TWE5-PRC002-EN-08-17-03

ElectricalData

TTB0520 System Wiring Diagram

From Dwg. 21D150992 P01

Legend

Symbols

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM26

Page 27: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 27

ElectricalData

2TTB0524-0536AA System Wiring Diagram

Legend

Symbols

NOTES:

1. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE.

2. IF ODT-A IS NOT USED, ADD JUMPER BETWEEN W1 & W2 AT AIR HANDLER.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM27

Page 28: Trane Full Brochure

28 TWE5-PRC002-EN-08-17-03

ElectricalData

2TTA0030-060AD System Wiring Diagram

Legend

Symbols

NOTES:

1. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE.

2. IF ODT-A IS NOT USED, ADD JUMPER BETWEEN W1 & W2 AT AIR HANDLER.

3. LOW VOLTAGE (24 V.) FIELD WIRING MUST BE 18 AWG MIN.

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM28

Page 29: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 29

ElectricalData

TWE030-050C System Wiring Diagram

NOTES:

1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION

2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEEDCHANGE FOR HEATING/COOLING OPERATION IS DESIRED.

3. A 220V HIGH VOLTAGE CONTROL IN TTB5-C/2TTB05-A NEEDS TO BECHANGED WITH 24V LOW VOLTAGE CONTROL KIT (ACYLVCR006A)WHEN MATCHED WITH TWE-C AIR HANDLING UNITS.

Legend

Symbols

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM29

Page 30: Trane Full Brochure

30 TWE5-PRC002-EN-08-17-03

Dimensions

TWE030-050C Outline DrawingALL DIMENSIONS ARE IN INCHES (MM)

MINIMUM UNIT CLEARANCE SALETO COMBUSTIBLE SERVICE CLEARANCE

MATERIAL (REQUIRED) (RECOMMENDED)SIDES 0 (0) 2 (50.8)FRONT 0 (0) 21 (533.4)BACK 0 (0) 0 (0)

INLET DUCT 0 (0) 1 (25.4)OUTLET DUCT 1 (25.4)

MODEL NO. A B C D E FTWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV

(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV

(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV

(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)

FLOWCONTROL

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM30

Page 31: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 31

Dimensions

TTB520CA Outline DrawingAll dimensions are in inches (mm)

FLARE NUT TORQUE

TORQUE FT-LBS (NEWTON METERS)

APPLIED TUBE SIZE MINIMUM MAXIMUM1/4 (6.35) 8 (11.0) 10 (14.0)

5/16 (7.94) 10 (14.0) 15 (20.0)3/8 (9.52) 15 (20.0) 25 (34.0)

1/2 (12.70) 25 (34.0) 35 (47.0)5/8 (15.88) 40 (54.0) 55 (75.0)3/4 (19.05) 50 (68.0) 60 (81.0)

BACK-UPHEX SIZE

7/8 - 14 = 7/8 (22)

7/16 - 20 = 7/16

(11)11/16 - 14 = 11/16

(27)1/2 - 20 = 1/2

(13)

From Dwg. 21D151122 Rev. 0

1 INCH = (25.40 MILLIMETERS)PT. NO. A B C DP02 11/16

1/2 3/45/16

14 UNS-2A 20UNF-2A (19) (8)

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM31

Page 32: Trane Full Brochure

32 TWE5-PRC002-EN-08-17-03

Dimensions

2TTB0524-536AA Outline DrawingAll dimensions are in inches (mm)

From Dwg. 21D153509 Rev. 1

MODELS BASE FIG. A B C D E F G H J K L M

2TTB0524AA 2 1 561 (25-5/8) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18) 1-1/16–14 UNF- 2A 1/2–20 UNF- 2A

2TTB0530AA 2 1 561 (25-5/8) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 127 (5) 57 (2-1/4) 181 (7-1/8) 44 (1-3/4) 457 (18) 1-1/16–14 UNF- 2A 1/2–20 UNF- 2A

2TTB0536AA 2 1 730 (28-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 1-1/16–14 UNF- 2A 1/2–20 UNF- 2A

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM32

Page 33: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 33

Dimensions

2TTA0030-060AD Outline DrawingAll dimensions are in inches (mm)

From Dwg. 21D153074 Rev. 5

MODELS BASE FIG. A B C D E F G H J K

2TTA0030AD 2 2 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 7/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TTA0040AD 2 2 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 1-1/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TTA0050AD 3 1 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20)

2TTA0060AD 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM33

Page 34: Trane Full Brochure

34 TWE5-PRC002-EN-08-17-03

Convertibility

TWE030 Through 050 ConvertibilitySix (6) Way Convertibility

One Unit - 4 Applications Easy Conversion to Opposite Side Access

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM34

Page 35: Trane Full Brochure

TWE5-PRC002-EN-08-17-03 35

MechanicalSpecification Options

GeneralThe unit shall be fully charged from thefactory for matched indoor section and upto 15 feet of piping. This unit must bedesigned to operate at outdoor ambienttemperatures as high as 115°F. Coolingcapacities shall be matched with a wideselection of air handlers. Exterior must bedesigned for outdoor application.

CasingUnit casing is constructed of heavygauge, galvanized steel and painted witha weather-resistant powder paint.Corrosion and weatherproof CMBP-G30Duratuff™ base.(2TTB/2TTA)

Refrigerant ControlsRefrigeration system controls includecondenser fan and compressorcontactor. High and low pressure controlsare inherent to the compressor. Anotherstandard feature is the liquid line dryer.

CompressorThe Climatuff® compressor featuresinternal over temperature and pressureprotector, total dipped hermetic motorand thermostatically controlled sumpheater. Other features include: roto locksuction and discharge refrigerationconnections, centrifugal oil pump, andlow vibration and noise.

Condenser CoilThe Spine Fin™ coil shall be continuouslywrapped, corrosion resistant all alumi-num with minimum brazed joints. Thiscoil is 3/8 inch O.D. seamless aluminumglued to a continuous aluminum fin. Coilsare lab tested to withstand 2,000 poundsof pressure per square inch. The outdoorcoil provides low airflow resistance andefficient heat transfer. The coil is pro-tected on all four sides by louveredpanels and has a 10 year limited warranty.

Low Ambient CoolingAs manufactured, this unit has a coolingcapability to 55°F. The addition of anevaporator defrost control permitsoperation to 40°F. The addition of anevaporator defrost control with TXVpermits low ambient cooling to 30°F.

AccessoriesThermostats — Heating/Cooling(manual and automatic changeover).Sub-base to match thermostat andlocking thermostat cover.

Evaporator Defrost Control — See LowAmbient Cooling.

Outdoor Thermostat — Supplementalheat outdoor ambient lockout from46 to –10°F.

Condensing Units

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM35

Page 36: Trane Full Brochure

P.I.

Trane has a policy of continuous product and product data improvement and it reserves the right to changedesign and specifications without notice.

TraneA business ofAmerican Standard Companieswww.trane.com

MechanicalSpecification Options

GeneralBlower coil units shall be completelyfactory assembled including coil, conden-sate drain pan, fan, motor, filters andcontrols in an insulated casing that canbe applied in horizontal or verticalconfiguration.

This new line of TWE-C air handlersprovides exclusive compact size com-bined with simple four-way convertibilityin three sizes. The unit ships in the righthand horizontal configuration andconverts to vertical upflow just bystanding the unit on end. No toolsrequired. Simple coil rotation providesdownflow and horizontal left applications.

The four-way convertibility provides youinventory benefits and service/installationflexibility. The simple conversion providesopposite side access for installationand service.

CasingUnits shall have rugged sheet metal andsteel frame construction and shall bepainted with an enamel finish. Casingshall be insulated and knockouts shallbe provided for electrical power andcontrol wiring.

Refrigerant CircuitsThe TWE units shall have a singlerefrigerant circuit. TWE03-040C refriger-ant circuit shall be controlled by a flowcontrol check valve (FCCV). TheTWE050C refrigerant circuit shall becontrolled by a factory-installed thermalexpansion valve.

CoilAluminum fin surface shall be mechani-cally bonded to 3/8-inch OD coppertubing. Coils shall be factory pressureand leak tested.

FanForward curved, dynamically andstatically balanced with three-speeddirect drive shall be standard, fan motorbearing shall be permanently lubricated.

ControlsFan contactor, and plug-in module foraccessory electric heat control shall beincluded. TWE models shall also includecheck valves.

FiltersFilters shall be included as standard.

AccessoriesElectric Heaters — Shall be available ina wide range of capacities and voltageswith various staging options and plug incontrol wiring. Heaters shall fit insideinternal compartment.

Air Handling Units

TWE5_PRC002_EN_081703.PMD 9/15/2003, 4:38 PM36

Page 37: Trane Full Brochure

Split SystemHeat Pump Product& Performance Data

PUB. NO. TWE5-PRC001-EN-08-17-03

50 Hz

Air Handler ModelsTWE030CATWE040CATWE050CA

Condensing Models2TWB0012-036AA2TWA0030-060AD

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM1

Page 38: Trane Full Brochure

© 2003 American Standard Inc. All Rights Reserved 2 TWE5-PRC001-EN-08-17-03

GeneralFeatures

Split System Heat Pump Units . . .The Evolution Continues

technology, and customer research todevelop the next generation of leadershipoutdoor products.

Couple the Trane reputation for reliabilityand durability with the above mentionedmission and accomplishments and youcontinue to have systems that prove“It’s Hard to Stop a Trane®. ”

2TWB0/2TWA0 split systems representa product that is not only an engineer’sdream, it's also a customer’s dream.The design team’s mission and accom-plishment is enhanced performanceand efficiency, improved reliability anddurability, and improved installabilityand serviceability.

Trane’s experienced design team applied“six sigma principles”, the latest computer

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM2

Page 39: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 3

Contents

General Features 2

Features and Benefits 4Condensing Units 4Air Handling Units 4Optional Equipment 5Low Outdoor Ambient Cooling 5

Selection Procedure 6Model Number Nomenclature for Condensing Units 6Model Number Nomenclature for Air Handlers 6

General Data 7TWE030CA40B 7TWE040CA40C 7TWE050CA50D 72TWB0012AA000A 82TWB0018AA000A 82TWB0024AA000A 82TWB0030AA000A 82TWB0036AA000A 82TWA0030AD000A 92TWA0040AD000A 92TWA0050AD000A 92TWA0060AD000A 9

Performance Data 102TWB/TWE Cooling 102TWA/TWE Cooling 162TWB/TWE Heating 202TWA/TWE Heating 26Evaporator Fan Performance 30Air Pressure Drop 32

Minimum Airflow (CFM) Heater Matrix 33

Electrical Data 34

Dimensions 37

Convertibility 40

Mechanical Specification Options 41Condensing Units 41Air Handling Units 42

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM3

Page 40: Trane Full Brochure

4 TWE5-PRC001-EN-08-17-03

Features andBenefits

• Climatuff® compressor

• All aluminum Spine Fin™ coil

• DuraTuff™ base, fast complete drain,weather proof

• New cabinet with polystate graycabinet

• Quick-Sess™ cabinet, service accessand refrigerant connections with full coilprotection

• Corrosion resistant finish and fastners

• Internal high/low pressure & tempera-ture protection

• Liquid line filter-drier

• Easy single side service

• Multi-use liquid and suction lineservice valves

• Brazed connections

• Easy top & fan removal

• Full length control cover

• HCFC-22 refrigerant

• S.E.E.T. design testing

• 100% line run test

• Low ambient cooling to 55°F asshipped

• Low ambient to 40°F withEDC accessory AY28X084

• Low ambient cooling to 30°F withEDC accessory AY28X084 and TXV

Condensing Units(2TWB00_AA, 2TWA00_AD)

Features• Ships horizontal

• Six way convertibility-horizontal (leftand right), upflow, downflow (frontand rear access)

• Electrical, refrigerant, condensate andblower access convertible to either side

• Corrosion resistant galvanized steelwith attractive finish

• Internally enhanced finned coil tubes

• Direct drive motor

• Standard filters

• Multi-speed blower

• 220 volt primary and 24 volt secondarytransformer

• Insulated cabinet

• External access to heater circuitbreakers

• Start kits are not required

• Built-in indoor fan delay function forincreased efficiency. No kit required.

New Features• Improved filter access and latch –

Eliminate current T-bar and shippingbracket.

• Provision for 1-1/8 inches thick fieldsupplied electrostatic filter

• Reversible Duct Flanges – Fits up to1-1/2 inches duct board

• Improve controls access with controlbox mounted next to blower.

• 40 VA transformer with 5 amp automo-tive style fuse on 3 tons and less

• 5 Amp automotive style fuse replacesBussman “red cap” fuse on 3.5 to 5 tonmodels

• Blower mounting brackets improved –Front access to screw with power driver

• Improved bottom carton cushioning

• 1 inch thick foil faced insulation for allmodels

Air Handling Units(2TWE0_CA)

TWE

2TWB00 & 2TWA00

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM4

Page 41: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 5

Low Outdoor Ambient Cooling

Low Ambient As EvaporatorCooling Manufactured Defrost Control

FCCV Accutron™ 55°F 40°FThermal Expansion Valve (TXV) 55°F 30°F

Optional Equipment

OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [✓✓✓✓✓] indicates accessories included).Indoor Thermostats — Elec. Setback Thermostat ..................................................................................................TAYSTAT500C [ ]

Prog., 5/2 Day, Manual ........................................................................................................ TAYSTAT540 [ ]Electronic, 2 Htg./1 Clg. (Non Prog.) .................................................................................... TAYSTAT570 [ ]Automatic Heat/Cool (Two Stage Heating) ........................................................................... BAY28X138A [ ]Manual Seasonal Selector Heat/Cool (Two Stage Heating) .............................................. BAYSTAT239A [ ]

Locking Thermostat Cover ......................................................................................................................................... BAY28X190 [ ]Humidistat ............................................................................................................................................................... BAYSTAT253 [ ]Outdoor Thermostats 46°F. to – 10°F. (Adjustable) ................................................................................................ TAYSTAT250B [ ]Evaporator Defrost Control Kit ..................................................................................................................................... AY28X084 [ ]Indoor Fan Delay Relay ............................................................................................................................................. BAY24X045 [ ]5 Minute Delay Relay 1 ....................................................................................................................................... TAYASCT501A [ ]Outdoor Temperature Sensor (TAYSTAT500C) ..................................................................................................... TAYSENS100A [ ]Snow Legs – Base and Cap 4" High ....................................................................................................................... BAYLEGS002 [ ]Snow Legs – addition 4" extension (used with BAYLEGS002) ................................................................................ BAYLEGS003 [ ]Start Kit (1-5 ton models) ........................................................................................................................................ BAYKSKT257 [ ]Extreme Conditions Mounting Kit ........................................................................................................................... BAYECMT001 [ ]Seacoast Kit ...........................................................................................................................................................BAYSEAC001 [ ]Isolators .................................................................................................................................................................... BAYISLT101 [ ]Low Ambient Kit ..................................................................................................................................................... BAYLOAM103 [ ]1 Do not use with programmable thermostats

BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)5/8" ODM (90° bend, one end), 5/8" and 1/4" tubing ............................................................................................ TAYREFLN1__* [ ]3/4" ODM (90° bend, one end), 3/4" and 5/16" tubing .......................................................................................... TAYREFLN2__* [ ]7/8" ODM (90° bend, one end), 7/8" and 3/8" tubing ............................................................................................ TAYREFLN3__* [ ]3/4" ODM (90° bend, one end), 1-1/8" and 3/8" tubing ......................................................................................... TAYREFLN4__* [ ]* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.

Example: TAYREFLN220

Features andBenefits

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM5

Page 42: Trane Full Brochure

6 TWE5-PRC001-EN-08-17-03

Refrigerant Type2 = R-224 = R-410A

TRANE

Product TypeW = Split Heat PumpT = Split Cooling

Product FamilyZ = LEADERSHIP - 2 STAGEX = LEADERSHIPR = REPLACEMENT / RETAILB = BASICA = LIGHT COMMERCIAL

Family SEER0 =̃ 10 2 =̃ 12 4 =̃ 141 =̃ 11 3 =̃ 13 6 =̃ 16 8 =̃ 18

Unit PartsIdentifier

Minor DesignModifications

SecondaryFunction

Power Supply1 = 200 - 230 / 1 / 60 or 208 - 230 / 1 / 603 = 200 - 230 / 3 / 604 = 460 / 3 / 60A = 220 / 1 / 50D = 380-415 / 3 / 50

Major Design Modifications

Nominal Capacity in 000’s of BTU’s

Split System Connections 1 - 6 Tons0 = Brazed5 = Flare

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

2 T W B 0 0 3 6 A A 0 0 0 A A

SelectionProcedure

Model Number Nomenclature for Condensing Units

Product TypeTW = Split System Component

Heat Pump Compatible

Airflow ConfigurationE = Convertible

Refrigerant Connections0 = Brazed

Nominal Net CoolingCapacity30 = 30 MBh40 = 40 MBh50 = 50 MBh

Major Design Modification

ProductService Change

Minor DesignModification

Not Used

Refrigerant Flow Control4 = Accutron™ Flow Control/Check Valve5 = Bleed TXV

Electrical CharacteristicsA = 220V/1/50

Model Number Nomenclature for Air Handlers

1 2 3 4 5 6 7 8 9 10 11 12

T W E 0 3 0 C A 4 0 A 0

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM6

Page 43: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 7

TWE Product SpecificationsModel TWE030CA40B TWE040CA40C TWE050CA50DPower Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50Indoor Coil - Type Plate Fin Plate Fin Plate Fin

Rows 3 3 3Fins per inch (Fins per 25.4 mm) 14 14 14Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58)Tube Size in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)Refrigerant Control FCCV FCCV FCCVDrain Conn. Size in. (mm) 3/4 NPT 3/4 NPT 3/4 NPTDuct Connections See Outline Drawing See Outline Drawing See Outline Drawing

Indoor Fan - Type Centrifugal Centrifugal CentrifugalNo. Used 1 1 1Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4)Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0)Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3Airflow (High)

CFM @ 0.0 in. w.g. See Fan Performance Table See Fan Performance Table See Fan Performance TableCMH @ 0.0 Pa See Fan Performance Table See Fan Performance Table See Fan Performance Table

No. Motors - HP 1 - 1/3 1 - 1/3 1 - 3/4Motor RPM 1000 900 900Volts/Ph/Hz 220/1/50 220/1/50 220/1/50F.L. Amps 2.6 2.1 4.5L.R. Amps 3.3 4.2 10.1

FiltersVertical Applications

Filter Furnished Yes Yes YesType Furnished Throwaway Throwaway High VelocityNo.-Size-Thickness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1

Horizontal ApplicationsFilter Furnished No No NoType Recommended See Note Below See Note Below See Note BelowNo.-Size-Thickness See Note Below See Note Below See Note Below

Refrigerant Line SizeLine Size ID Gas in. (mm) 7/8 (22.23) 1-1/8 (28.56) 1-1/8 (28.56)Line Size ID Liquid in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Dimensions (H x W x D)Crated - in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5

- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597)Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0

- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)Weight Ibs. (kg)

Shipping 125 (56.7) 165 (74.8) 198 (898)Net 115 (52.2) 150 (68.0) 183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:Low Velocity Filter: Face Area (sq ft) = CFM/300High Velocity Filter: Face Area (sq ft) = CFM/500

GeneralData TWE

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM7

Page 44: Trane Full Brochure

8 TWE5-PRC001-EN-08-17-03

2TWB Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsMin. Brch. Cir. AmpacityBr. Cir. Max. (Amps)Prot. Rtg. } Min. (Amps)

Compressor - TypeNo. Used - No. SpeedsVolts/Ph/HzR.L. Amps 6 - L.R. AmpsFactory Installed

Start Components 7Insulation/Sound BlanketCompressor Heat

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3CMH @ 0.0 mm. w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg)ShippingNet

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE

SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

GeneralData 2TWB

2TWB0036AA000A200/230/1/50

264540

CLIMATUFF®

1 - 1200/230/1/50

19.9 - 124

YESNOYES

PROPELLER 1

23 (584)DIRECT - 1

2775

47181 - 1/6825

200/230/1/501.4

SPINE FIN™1

24 (0.945)15.18 (1.41)3/8 (9.53)

6 LBS., 8 OZ. (2.95)YES

7/8 (22.2)3/8 (9.53)

.071

38 x 30.1 x 33.8965 x 765 x 859

254 (115.5)227 (103.2)

2TWB0030AA000A200/230/1/50

173030

CLIMATUFF®

1 - 1200/230/1/50

12.9 - 78

NONOYES

PROPELLER 1

19 (483)DIRECT - 1

2075

35281 - 1/41075

200/230/1/501.3

SPINE FIN™1

24 (0.945)11.32 (1.05)3/8 (9.53)

5 LBS., 15 OZ. (2.70)YES

7/8 (22.2)3/8 (9.53)

.061

33.2 x 26.7 x 30.2843 x 678 x 767

192 (87.3)172 (78.2)

2TWB0024AA000A200/230/1/50

172520

CLIMATUFF®

1 - 1200/230/1/50

12.2 - 82

NONOYES

PROPELLER 1

19 (483)DIRECT - 1

2075

35281 - 1/41075

200/230/1/501.3

SPINE FIN™1

24 (0.945)13.75 (1.28)3/8 (9.53)

4 LBS., 11 OZ. (2.13)YES

3/4 (19.1)5/16 (7.94)

.057

33.2 x 26.7 x 30.2843 x 678 x 767

193 (87.7)173 (78.6)

2TWB0018AA000A200/230/1/50

132020

CLIMATUFF®

1 - 1200/230/1/50

9.6 - 66

NONOYES

PROPELLER 1

19 (483)DIRECT - 1

1825

31031 - 1/81075

200/230/1/500.9

SPINE FIN™1

24 (0.945)9.72 (0.90)3/8 (9.53)

4 LBS., 8 OZ. (2.05)YES

3/4 (19.1)5/16 (7.94)

.051

30.1 x 26.7 x 30.2765 x 678 x 767

179 (81.4)160 (72.7)

2TWB0012AA000A200/230/1/50

101515

CLIMATUFF®

1 - 1200/230/1/50

7.2 - 47

NONOYES

PROPELLER 1

19 (483)DIRECT - 1

1300

22101 - 1/81075

200/230/1/500.9

SPINE FIN™1

24 (0.945)9.72 (0.90)3/8 (9.53)

4 LBS., 5 OZ. (1.96)YES

5/8 (15.9)1/4 (6.35)

.045

30.1 x 26.7 x 30.2765 x 678 x 767

170 (77.3)151 (68.6)

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM8

Page 45: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 9

GeneralData 2TWA

2TWA Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsMin. Brch. Cir. AmpacityBr. Cir. Max. (Amps)Prot. Rtg. } Min. (Amps)

Compressor - TypeNo. Used - No. SpeedsVolts/Ph/HzR.L. Amps 6 - L.R. AmpsFactory Installed

Start Components 7Insulation/Sound BlanketCompressor Heat

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3CMH @ 0.0 mm. w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg) Shipping Net

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE

SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

2TWA0030AD000A380/415/3/50

71515

CLIMATUFF®

1 - 1380/415/3/50

5.5 - 46

NONOYES

PROPELLER 1

19 (483)DIRECT - 1

2775

47181 - 1/41075

380/415/3/50.7

SPINE FIN™1

24 (0.945)15.18 (1.41)3/8 (9.53)

5 LBS., 12 OZ. (2.61)YES

7/8 (22.2)3/8 (9.53)

.071

33.2 x 26.7 x 30.2843 x 678 x 767

212 (96.4)192 (87.3)

2TWA0040AD000A380/415/3/50

91515

CLIMATUFF®

1 - 1380/415/3/50

6.4 - 51

NONOYES

PROPELLER 1

23 (584)DIRECT - 1

3075

52281 - 1/4825

380/415/3/501.0

SPINE FIN™1

24 (0.945)15.18 (1.41)3/8 (9.53)

8 LBS., 6 OZ. (3.81)YES

1 -1/8 (28.5)3/8 (9.53)

.075

38 x 30.1 x 33.8965 x 765 x 859

254 (115.5)226 (102.7)

2TWA0050AD000A380/415/3/50

122020

CLIMATUFF®

1 - 1380/415/3/50

9.0 - 70

NONOYES

PROPELLER 1

27.6 (701)DIRECT - 1

3675

62481 - 1/6825

380/415/3/50.7

SPINE FIN™1

24 (0.945)21.99 (2.04)3/8 (9.53)

9 LBS., 8 OZ. (4.32)YES

1 -1/8 (28.5)3/8 (9.53)

.086

38.4 x 35.1 x 38.7975 x 892 x 983

289 (131.4)256 (116.4)

2TWA0060AD000A380/415/3/50

122020

CLIMATUFF®

1 - 1380/415/3/50

9.0 - 74

NONOYES

PROPELLER 1

27.6 (701)DIRECT - 1

3300

56101 - 1/4825

380/415/3/501.0

SPINE FIN™2

24 (0.945)27.86 (2.59)3/8 (9.53)

14 LBS., 1 OZ. (6.39)YES

1 -1/8 (28.5)3/8 (9.53)

.086

46.4 x 35.1 x 38.71179 x 892 x 983

329 (149.5)293 (133.2)

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM9

Page 46: Trane Full Brochure

10 TWE5-PRC001-EN-08-17-03

2TWB0012AA WITH TWE030CA4 AT 450 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 13.7 11.5 12.4 13.3 13.9* 14.2* 1.41 47.185 63 14.8 9.8 10.7 11.6 12.5 13.4 1.42 50.9

67 16.0 7.9 8.8 9.7 10.6 11.5 1.43 55.071 17.2 6.0 6.9 7.8 8.7 9.6 1.45 59.259 13.5 11.4 12.3 13.2 13.8* 14.1* 1.46 47.3

90 63 14.6 9.7 10.6 11.5 12.4 13.3 1.47 51.167 15.8 7.8 8.7 9.6 10.5 11.4 1.48 55.271 17.0 5.9 6.8 7.7 8.6 9.5 1.50 59.459 13.3 11.3 12.2 13.1 13.6* 14.0* 1.51 47.5

95 63 14.4 9.6 10.5 11.4 12.3 13.2 1.52 51.367 15.6 7.8 8.7 9.6 10.4 11.3 1.53 55.371 16.8 5.9 6.7 7.6 8.5 9.4 1.54 59.559 12.9 11.1 12.0 12.9* 13.3* 13.6* 1.56 48.0

100 63 13.9 9.4 10.3 11.2 12.1 13.0 1.57 51.867 15.1 7.6 8.5 9.3 10.2 11.1 1.58 55.871 16.3 5.6 6.5 7.4 8.3 9.2 1.59 60.059 12.4 10.9 11.8 12.5* 12.9* 13.2* 1.61 48.5

105 63 13.5 9.2 10.1 11.0 11.9 12.8 1.62 52.267 14.6 7.4 8.2 9.1 10.0 10.9 1.62 56.371 15.7 5.4 6.3 7.2 8.1 9.0 1.63 60.559 11.5 10.5 11.4 11.8* 12.1* 12.5* 1.72 49.4

115 63 12.5 8.8 9.7 10.6 11.5 12.4 1.72 53.267 13.5 6.9 7.8 8.7 9.6 10.5 1.71 57.371 14.6 5.0 5.9 6.8 7.7 8.6 1.71 61.5

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 400 500TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.3 1.1

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 15700 BTUHAIRFLOW = 450 CFMAPP. DEW PT. = 55.3 DEG. FCOMPRESSOR POWER = 1098 WATTSI.D. FAN POWER = 342 WATTSO.D. FAN POWER = 93 WATTSS.E.E.R. = 9.88 BTUH/WATTE.E.R. = 9.41 BTUH/WATTNOTE: RATED WITH 25 FEET OF 5/8 SUCT.

AND 1/4 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWB0018AA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 19.2 16.9 18.2 19.3* 19.9* 20.3* 1.95 48.185 63 20.7 14.2 15.6 16.9 18.3 19.6 1.99 52.0

67 22.2 11.3 12.7 14.0 15.4 16.7 2.02 56.171 23.8 8.4 9.7 11.1 12.4 13.8 2.06 60.459 19.1 16.8 18.1 19.2* 19.7* 20.2* 2.03 48.2

90 63 20.5 14.2 15.5 16.9 18.2 19.5 2.07 52.167 22.1 11.3 12.6 14.0 15.3 16.7 2.10 56.271 23.7 8.3 9.7 11.0 12.4 13.7 2.14 60.559 18.9 16.7 18.1 19.1* 19.6* 20.1* 2.11 48.3

95 63 20.4 14.1 15.4 16.8 18.1 19.5 2.15 52.267 21.9 11.2 12.6 13.9 15.2 16.6 2.18 56.371 23.5 8.3 9.6 11.0 12.3 13.6 2.22 60.659 18.3 16.5 17.8 18.6* 19.1* 19.6* 2.17 48.7

100 63 19.8 13.8 15.2 16.5 17.9 19.2 2.21 52.667 21.3 11.0 12.3 13.6 15.0 16.3 2.24 56.871 22.8 8.0 9.4 10.7 12.1 13.4 2.27 61.059 17.8 16.2 17.5 18.2* 18.7* 19.1* 2.24 49.2

105 63 19.2 13.6 14.9 16.3 17.6 19.0 2.27 53.067 20.6 10.7 12.1 13.4 14.7 16.1 2.30 57.271 22.1 7.8 9.1 10.5 11.8 13.1 2.33 61.459 16.7 15.7 16.8* 17.3* 17.7* 18.1* 2.37 50.0

115 63 18.0 13.1 14.4 15.8 17.1 18.1* 2.39 53.867 19.4 10.2 11.6 12.9 14.2 15.6 2.41 58.071 20.8 7.3 8.6 10.0 11.3 12.7 2.44 62.2

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 600 800TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.98 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 21800 BTUHAIRFLOW = 675 CFMAPP. DEW PT. = 56.0 DEG. FCOMPRESSOR POWER = 1625 WATTSI.D. FAN POWER = 387 WATTSO.D. FAN POWER = 148 WATTSS.E.E.R. = 10.06 BTUH/WATTE.E.R. = 9.47 BTUH/WATTNOTE: RATED WITH 25 FEET OF 3/4 SUCT.

AND 5/16 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWB0024AA WITH TWE030CA4 AT 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 23.9 21.1 22.8 24.1* 24.7* 25.3* 2.40 48.385 63 25.7 17.8 19.5 21.2 22.8 24.5 2.45 52.1

67 27.5 14.1 15.8 17.5 19.2 20.9 2.50 56.371 29.5 10.4 12.1 13.8 15.5 17.2 2.55 60.659 23.7 21.0 22.7 23.9* 24.6* 25.2* 2.50 48.4

90 63 25.5 17.7 19.4 21.1 22.8 24.5 2.55 52.267 27.4 14.1 15.8 17.5 19.1 20.8 2.59 56.471 29.3 10.4 12.1 13.7 15.4 17.1 2.64 60.659 23.6 20.9 22.6 23.8* 24.5* 25.0* 2.60 48.5

95 63 25.4 17.7 19.3 21.0 22.7 24.4 2.65 52.367 27.2 14.0 15.7 17.4 19.1 20.8 2.69 56.571 29.2 10.3 12.0 13.7 15.4 17.1 2.74 60.759 22.9 20.6 22.3 23.3* 23.9* 24.5* 2.68 48.9

100 63 24.7 17.4 19.0 20.7 22.4 24.1 2.72 52.767 26.5 13.7 15.4 17.1 18.8 20.5 2.76 56.971 28.4 10.0 11.7 13.4 15.1 16.8 2.81 61.159 22.2 20.3 22.0 22.7* 23.4* 23.9* 2.76 49.2

105 63 24.0 17.1 18.7 20.4 22.1 23.8 2.80 53.167 25.8 13.4 15.1 16.8 18.5 20.2 2.84 57.371 27.6 9.7 11.4 13.1 14.8 16.5 2.88 61.559 20.9 19.7 21.1* 21.7* 22.2* 22.8* 2.92 50.0

115 63 22.6 16.5 18.1 19.8 21.5 22.8* 2.95 53.967 24.3 12.8 14.5 16.2 17.9 19.6 2.98 58.071 26.0 9.2 10.8 12.5 14.2 15.9 3.01 62.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 775 1025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.6 1.2

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 27300 BTUHAIRFLOW = 900 CFMAPP. DEW PT. = 56.5 DEG. FCOMPRESSOR POWER = 2086 WATTSI.D. FAN POWER = 425 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 10.24 BTUH/WATTE.E.R. = 9.58 BTUH/WATTNOTE: RATED WITH 25 FEET OF 3/4 SUCT.

AND 5/16 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

Performance DataCooling English Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM10

Page 47: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 11

Performance DataCooling Metric Units

2TWB0012AA WITH TWE030CA4 AT 764 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 4.0 3.4 3.6 3.9 4.1* 4.2* 1.429.4 17.2 4.3 2.9 3.1 3.4 3.7 3.9 1.4

19.4 4.7 2.3 2.6 2.8 3.1 3.4 1.421.7 5.0 1.8 2.0 2.3 2.5 2.8 1.515.0 4.0 3.3 3.6 3.9 4.0* 4.1* 1.5

32.2 17.2 4.3 2.8 3.1 3.4 3.6 3.9 1.519.4 4.6 2.3 2.5 2.8 3.1 3.3 1.521.7 5.0 1.7 2.0 2.3 2.5 2.8 1.515.0 3.9 3.3 3.6 3.8 4.0* 4.1* 1.5

35.0 17.2 4.2 2.8 3.1 3.3 3.6 3.9 1.519.4 4.6 2.3 2.5 2.8 3.0 3.3 1.521.7 4.9 1.7 2.0 2.2 2.5 2.8 1.515.0 3.8 3.3 3.5 3.8* 3.9* 4.0* 1.6

37.8 17.2 4.1 2.8 3.0 3.3 3.5 3.8 1.619.4 4.4 2.2 2.5 2.7 3.0 3.3 1.621.7 4.8 1.6 1.9 2.2 2.4 2.7 1.615.0 3.6 3.2 3.5 3.7* 3.8* 3.9* 1.6

40.6 17.2 4.0 2.7 3.0 3.2 3.5 3.8 1.619.4 4.3 2.2 2.4 2.7 2.9 3.2 1.621.7 4.6 1.6 1.8 2.1 2.4 2.6 1.615.0 3.4 3.1 3.3 3.5* 3.5* 3.7* 1.7

46.1 17.2 3.7 2.6 2.8 3.1 3.4 3.6 1.719.4 4.0 2.0 2.3 2.5 2.8 3.1 1.721.7 4.3 1.5 1.7 2.0 2.3 2.5 1.7

2TWB0018AA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 5.6 5.0 5.3 5.7* 5.8* 5.9* 2.029.4 17.2 6.1 4.2 4.6 5.0 5.4 5.7 2.0

19.4 6.5 3.3 3.7 4.1 4.5 4.9 2.021.7 7.0 2.5 2.8 3.3 3.6 4.0 2.115.0 5.6 4.9 5.3 5.6* 5.8* 5.9* 2.0

32.2 17.2 6.0 4.2 4.5 5.0 5.3 5.7 2.119.4 6.5 3.3 3.7 4.1 4.5 4.9 2.121.7 6.9 2.4 2.8 3.2 3.6 4.0 2.115.0 5.5 4.9 5.3 5.6* 5.7* 5.9* 2.1

35.0 17.2 6.0 4.1 4.5 4.9 5.3 5.7 2.219.4 6.4 3.3 3.7 4.1 4.5 4.9 2.221.7 6.9 2.4 2.8 3.2 3.6 4.0 2.215.0 5.4 4.8 5.2 5.4* 5.6* 5.7* 2.2

37.8 17.2 5.8 4.0 4.5 4.8 5.2 5.6 2.219.4 6.2 3.2 3.6 4.0 4.4 4.8 2.221.7 6.7 2.3 2.8 3.1 3.5 3.9 2.315.0 5.2 4.7 5.1 5.3* 5.5* 5.6* 2.2

40.6 17.2 5.6 4.0 4.4 4.8 5.2 5.6 2.319.4 6.0 3.1 3.5 3.9 4.3 4.7 2.321.7 6.5 2.3 2.7 3.1 3.5 3.8 2.315.0 4.9 4.6 4.9* 5.1* 5.2* 5.3* 2.4

46.1 17.2 5.3 3.8 4.2 4.6 5.0 5.3* 2.419.4 5.7 3.0 3.4 3.8 4.2 4.6 2.421.7 6.1 2.1 2.5 2.9 3.3 3.7 2.4

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 679 849TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 4.60 KWAIRFLOW = 764 CMHCOMPRESSOR POWER = 1098 WATTSI.D. FAN POWER = 342 WATTSO.D. FAN POWER = 93 WATTSS.E.E.R. = 9.88 BTUH/WATTE.E.R. = 9.41 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 5/8 IN. SUCT.AND 1/4 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1019 1358TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.98 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 6.39 KW

AIRFLOW = 1146 CMHCOMPRESSOR POWER = 1625 WATTSI.D. FAN POWER = 387 WATTSO.D. FAN POWER = 148 WATTSS.E.E.R. = 10.06 BTUH/WATTE.E.R. = 9.47 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.AND 5/16 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

2TWB0024AA WITH TWE030CA4 AT 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 7.0 6.2 6.7 7.1* 7.2* 7.4* 2.429.4 17.2 7.5 5.2 5.7 6.2 6.7 7.2 2.5

19.4 8.1 4.1 4.6 5.1 5.6 6.1 2.521.7 8.6 3.0 3.5 4.0 4.5 5.0 2.515.0 6.9 6.2 6.7 7.0* 7.2* 7.4* 2.5

32.2 17.2 7.5 5.2 5.7 6.2 6.7 7.2 2.519.4 8.0 4.1 4.6 5.1 5.6 6.1 2.621.7 8.6 3.0 3.5 4.0 4.5 5.0 2.615.0 6.9 6.1 6.6 7.0* 7.2* 7.3* 2.6

35.0 17.2 7.4 5.2 5.7 6.2 6.7 7.1 2.719.4 8.0 4.1 4.6 5.1 5.6 6.1 2.721.7 8.6 3.0 3.5 4.0 4.5 5.0 2.715.0 6.7 6.0 6.5 6.8* 7.0* 7.2* 2.7

37.8 17.2 7.2 5.1 5.6 6.1 6.6 7.1 2.719.4 7.8 4.0 4.5 5.0 5.5 6.0 2.821.7 8.3 2.9 3.4 3.9 4.4 4.9 2.815.0 6.5 5.9 6.4 6.7* 6.9* 7.0* 2.8

40.6 17.2 7.0 5.0 5.5 6.0 6.5 7.0 2.819.4 7.6 3.9 4.4 4.9 5.4 5.9 2.821.7 8.1 2.8 3.3 3.8 4.3 4.8 2.915.0 6.1 5.8 6.2* 6.4* 6.5* 6.7* 2.9

46.1 17.2 6.6 4.8 5.3 5.8 6.3 6.7* 3.019.4 7.1 3.8 4.2 4.7 5.2 5.7 3.021.7 7.6 2.7 3.2 3.7 4.2 4.7 3.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1316 1741TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 8.00 KWAIRFLOW = 1528 CMHCOMPRESSOR POWER = 2086 WATTSI.D. FAN POWER = 425 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 10.24 BTUH/WATTE.E.R. = 9.58 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.AND 5/16 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM11

Page 48: Trane Full Brochure

12 TWE5-PRC001-EN-08-17-03

Performance DataCooling English Units

2TWB0030AA WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 26.8 23.5 25.3 27.0* 27.7* 28.3* 2.80 48.085 63 28.8 19.8 21.7 23.5 25.4 27.2 2.87 51.9

67 30.8 15.8 17.7 19.5 21.4 23.2 2.93 56.171 32.9 11.7 13.5 15.4 17.2 19.1 3.00 60.459 26.6 23.4 25.2 26.8* 27.5* 28.1* 2.93 48.2

90 63 28.5 19.7 21.6 23.4 25.3 27.1 2.99 52.167 30.6 15.7 17.6 19.4 21.3 23.1 3.06 56.371 32.7 11.6 13.4 15.3 17.1 19.0 3.13 60.559 26.4 23.3 25.1 26.6* 27.3* 27.9* 3.05 48.3

95 63 28.3 19.6 21.5 23.3 25.2 27.0 3.11 52.267 30.3 15.6 17.5 19.3 21.2 23.0 3.18 56.471 32.4 11.5 13.4 15.2 17.1 18.9 3.25 60.659 25.5 22.9 24.7 25.8* 26.5* 27.1* 3.16 48.8

100 63 27.4 19.2 21.1 22.9 24.8 26.6 3.22 52.767 29.3 15.2 17.1 18.9 20.8 22.6 3.29 56.971 31.4 11.1 13.0 14.8 16.7 18.5 3.36 61.159 24.6 22.5 24.3 25.1* 25.8* 26.4* 3.27 49.3

105 63 26.4 18.8 20.7 22.5 24.4 26.2 3.33 53.267 28.3 14.8 16.7 18.5 20.4 22.2 3.39 57.471 30.3 10.7 12.6 14.4 16.3 18.1 3.46 61.659 22.8 21.7 23.0* 23.7* 24.3* 24.8* 3.49 50.2

115 63 24.6 18.0 19.9 21.7 23.6 24.8* 3.54 54.167 26.4 14.0 15.9 17.7 19.6 21.4 3.60 58.371 28.2 9.9 11.8 13.6 15.5 17.3 3.66 62.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 30400 BTUHAIRFLOW = 1000 CFMAPP. DEW PT. = 56.4 DEG. FCOMPRESSOR POWER = 2566 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 9.91 BTUH/WATTE.E.R. = 9.06 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWB0030AA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 28.5 25.5 27.6 28.9* 29.6* 30.2* 2.74 48.485 63 30.5 21.3 23.4 25.5 27.6 29.7 2.80 52.4

67 32.5 16.7 18.8 20.9 23.0 25.1 2.87 56.671 34.7 12.0 14.1 16.2 18.3 20.4 2.94 61.059 28.2 25.3 27.4 28.6* 29.3* 30.0* 2.86 48.6

90 63 30.2 21.2 23.3 25.4 27.4 29.5 2.93 52.567 32.2 16.6 18.7 20.8 22.9 25.0 3.00 56.871 34.3 11.9 14.0 16.1 18.2 20.3 3.07 61.159 27.8 25.2 27.3 28.4* 29.0* 29.7* 2.99 48.7

95 63 29.8 21.0 23.1 25.2 27.3 29.4 3.06 52.767 31.9 16.4 18.5 20.6 22.7 24.8 3.13 56.971 34.0 11.8 13.9 16.0 18.1 20.2 3.20 61.359 26.9 24.7 26.8 27.6* 28.2* 28.8* 3.10 49.2

100 63 28.8 20.6 22.7 24.8 26.9 28.8* 3.16 53.167 30.8 16.0 18.1 20.2 22.3 24.4 3.23 57.471 32.8 11.4 13.5 15.6 17.7 19.8 3.30 61.759 25.9 24.3 26.1* 26.8* 27.4* 28.0* 3.21 49.6

105 63 27.8 20.2 22.3 24.4 26.4 28.0* 3.27 53.667 29.7 15.6 17.7 19.8 21.9 24.0 3.34 57.871 31.7 11.0 13.1 15.1 17.2 19.3 3.40 62.159 24.0 23.5 24.5* 25.1* 25.7* 26.3* 3.43 50.5

115 63 25.7 19.3 21.4 23.5 25.6 26.3* 3.49 54.467 27.5 14.8 16.9 19.0 21.0 23.1 3.55 58.771 29.4 10.1 12.2 14.3 16.4 18.5 3.61 63.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.98 X1.01SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 32000 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 57.1 DEG. FCOMPRESSOR POWER = 2651 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 10.90 BTUH/WATTE.E.R. = 9.84 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWB0036AA WITH TWE030CA4 AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 33.1 27.4 29.4 31.4 33.2* 34.0* 3.30 46.385 63 35.7 23.5 25.5 27.5 29.5 31.5 3.38 50.4

67 38.5 19.2 21.2 23.2 25.2 27.2 3.47 54.471 41.3 14.8 16.8 18.8 20.8 22.8 3.56 58.659 32.8 27.2 29.2 31.2 33.0* 33.8* 3.44 46.5

90 63 35.4 23.4 25.4 27.4 29.4 31.4 3.53 50.667 38.2 19.1 21.1 23.1 25.1 27.1 3.62 54.671 41.0 14.7 16.7 18.7 20.7 22.7 3.71 58.759 32.5 27.1 29.1 31.1 32.7* 33.6* 3.59 47.0

95 63 35.1 23.2 25.3 27.3 29.3 31.3 3.68 50.867 37.9 19.0 21.0 23.0 25.0 27.0 3.77 54.871 40.7 14.6 16.6 18.6 20.6 22.6 3.86 58.959 31.4 26.5 28.6 30.6 31.9* 32.7* 3.72 47.6

100 63 34.0 22.7 24.7 26.7 28.7 30.7 3.80 51.467 36.6 18.5 20.5 22.5 24.5 26.5 3.89 55.471 39.4 14.1 16.1 18.1 20.1 22.1 3.98 59.559 30.3 26.0 28.0 30.0 31.0* 31.8* 3.85 48.2

105 63 32.8 22.2 24.2 26.2 28.2 30.2 3.93 52.067 35.4 17.9 19.9 22.0 24.0 26.0 4.02 56.071 38.1 13.6 15.6 17.6 19.6 21.6 4.11 60.159 28.1 25.0 27.0 28.5* 29.3* 30.0* 4.11 49.4

115 63 30.4 21.2 23.2 25.2 27.2 29.2 4.19 53.267 32.9 16.9 18.9 20.9 22.9 24.9 4.27 57.271 35.4 12.6 14.6 16.6 18.6 20.6 4.35 61.4

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.97 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.8 1.5

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 38100 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 55.0 DEG. FCOMPRESSOR POWER = 3067 WATTSI.D. FAN POWER = 541 WATTSO.D. FAN POWER = 177 WATTSS.E.E.R. = 10.49 BTUH/WATTE.E.R. = 9.56 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM12

Page 49: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 13

Performance DataCooling Metric Units

2TWB0030AA WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 7.9 6.9 7.4 7.9* 8.1* 8.3* 2.829.4 17.2 8.4 5.8 6.4 6.9 7.4 8.0 2.9

19.4 9.0 4.6 5.2 5.7 6.3 6.8 2.921.7 9.6 3.4 4.0 4.5 5.0 5.6 3.015.0 7.8 6.9 7.4 7.9* 8.1* 8.2* 2.9

32.2 17.2 8.4 5.8 6.3 6.9 7.4 7.9 3.019.4 9.0 4.6 5.2 5.7 6.2 6.8 3.121.7 9.6 3.4 3.9 4.5 5.0 5.6 3.115.0 7.7 6.8 7.4 7.8* 8.0* 8.2* 3.0

35.0 17.2 8.3 5.7 6.3 6.8 7.4 7.9 3.119.4 8.9 4.6 5.1 5.7 6.2 6.7 3.221.7 9.5 3.4 3.9 4.5 5.0 5.5 3.315.0 7.5 6.7 7.2 7.6* 7.8* 7.9* 3.2

37.8 17.2 8.0 5.6 6.2 6.7 7.3 7.8 3.219.4 8.6 4.5 5.0 5.5 6.1 6.6 3.321.7 9.2 3.3 3.8 4.3 4.9 5.4 3.415.0 7.2 6.6 7.1 7.4* 7.6* 7.7* 3.3

40.6 17.2 7.7 5.5 6.1 6.6 7.1 7.7 3.319.4 8.3 4.3 4.9 5.4 6.0 6.5 3.421.7 8.9 3.1 3.7 4.2 4.8 5.3 3.515.0 6.7 6.4 6.7* 6.9* 7.1* 7.3* 3.5

46.1 17.2 7.2 5.3 5.8 6.4 6.9 7.3* 3.519.4 7.7 4.1 4.7 5.2 5.7 6.3 3.621.7 8.3 2.9 3.5 4.0 4.5 5.1 3.7

2TWB0030AA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.4 7.5 8.1 8.5* 8.7* 8.8* 2.729.4 17.2 8.9 6.2 6.9 7.5 8.1 8.7 2.8

19.4 9.5 4.9 5.5 6.1 6.7 7.4 2.921.7 10.2 3.5 4.1 4.7 5.4 6.0 2.915.0 8.3 7.4 8.0 8.4* 8.6* 8.8* 2.9

32.2 17.2 8.8 6.2 6.8 7.4 8.0 8.6 2.919.4 9.4 4.9 5.5 6.1 6.7 7.3 3.021.7 10.0 3.5 4.1 4.7 5.3 5.9 3.115.0 8.1 7.4 8.0 8.3* 8.5* 8.7* 3.0

35.0 17.2 8.7 6.2 6.8 7.4 8.0 8.6 3.119.4 9.3 4.8 5.4 6.0 6.7 7.3 3.121.7 10.0 3.5 4.1 4.7 5.3 5.9 3.215.0 7.9 7.2 7.9 8.1* 8.3* 8.4* 3.1

37.8 17.2 8.4 6.0 6.7 7.3 7.9 8.4* 3.219.4 9.0 4.7 5.3 5.9 6.5 7.1 3.221.7 9.6 3.3 4.0 4.6 5.2 5.8 3.315.0 7.6 7.1 7.6* 7.9* 8.0* 8.2* 3.2

40.6 17.2 8.1 5.9 6.5 7.1 7.7 8.2* 3.319.4 8.7 4.6 5.2 5.8 6.4 7.0 3.321.7 9.3 3.2 3.8 4.4 5.0 5.7 3.415.0 7.0 6.9 7.2* 7.4* 7.5* 7.7* 3.4

46.1 17.2 7.5 5.7 6.3 6.9 7.5 7.7* 3.519.4 8.1 4.3 5.0 5.6 6.2 6.8 3.521.7 8.6 3.0 3.6 4.2 4.8 5.4 3.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 8.91 KW

AIRFLOW = 1698 CMHCOMPRESSOR POWER = 2566 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 9.91 BTUH/WATTE.E.R. = 9.06 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.98 X1.01SENS. CAP. X0.93 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.38 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2651 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 10.90 BTUH/WATTE.E.R. = 9.84 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

2TWB0036AA WITH TWE030CA4 AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.7 8.0 8.6 9.2 9.7* 10.0* 3.329.4 17.2 10.5 6.9 7.5 8.1 8.6 9.2 3.4

19.4 11.3 5.6 6.2 6.8 7.4 8.0 3.521.7 12.1 4.3 4.9 5.5 6.1 6.7 3.615.0 9.6 8.0 8.6 9.1 9.7* 9.9* 3.4

32.2 17.2 10.4 6.9 7.4 8.0 8.6 9.2 3.519.4 11.2 5.6 6.2 6.8 7.4 7.9 3.621.7 12.0 4.3 4.9 5.5 6.1 6.7 3.715.0 9.5 7.9 8.5 9.1 9.6* 9.8* 3.6

35.0 17.2 10.3 6.8 7.4 8.0 8.6 9.2 3.719.4 11.1 5.6 6.2 6.7 7.3 7.9 3.821.7 11.9 4.3 4.9 5.4 6.0 6.6 3.915.0 9.2 7.8 8.4 9.0 9.3* 9.6* 3.7

37.8 17.2 10.0 6.7 7.2 7.8 8.4 9.0 3.819.4 10.7 5.4 6.0 6.6 7.2 7.8 3.921.7 11.5 4.1 4.7 5.3 5.9 6.5 4.015.0 8.9 7.6 8.2 8.8 9.1* 9.3* 3.8

40.6 17.2 9.6 6.5 7.1 7.7 8.3 8.8 3.919.4 10.4 5.2 5.8 6.4 7.0 7.6 4.021.7 11.2 4.0 4.6 5.2 5.7 6.3 4.115.0 8.2 7.3 7.9 8.4* 8.6* 8.8* 4.1

46.1 17.2 8.9 6.2 6.8 7.4 8.0 8.6 4.219.4 9.6 5.0 5.5 6.1 6.7 7.3 4.321.7 10.4 3.7 4.3 4.9 5.4 6.0 4.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.97 X1.02SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 11.16 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 3067 WATTSI.D. FAN POWER = 541 WATTSO.D. FAN POWER = 177 WATTSS.E.E.R. = 10.49 BTUH/WATTE.E.R. = 9.56 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM13

Page 50: Trane Full Brochure

14 TWE5-PRC001-EN-08-17-03

Performance DataCooling English Units

2TWB0036AA WITH TWE040CA4-B AT 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 36.4 32.6 35.2 36.9* 37.9* 38.7* 3.26 48.585 63 39.2 27.4 30.0 32.7 35.3 37.9 3.35 52.4

67 42.0 21.7 24.4 27.0 29.6 32.2 3.44 56.571 45.0 15.9 18.6 21.2 23.8 26.4 3.53 60.859 36.0 32.4 35.0 36.6* 37.6* 38.4* 3.42 48.6

90 63 38.8 27.2 29.9 32.5 35.1 37.8 3.51 52.567 41.6 21.6 24.2 26.8 29.5 32.1 3.60 56.771 44.6 15.8 18.4 21.0 23.7 26.3 3.69 60.959 35.7 32.2 34.8 36.3* 37.3* 38.1* 3.58 48.8

95 63 38.4 27.1 29.7 32.3 35.0 37.6 3.67 52.667 41.2 21.4 24.0 26.7 29.3 31.9 3.76 56.871 44.2 15.6 18.3 20.9 23.5 26.1 3.85 61.059 34.4 31.6 34.3 35.2* 36.2* 37.0* 3.70 49.3

100 63 37.0 26.5 29.1 31.8 34.4 37.0 3.79 53.167 39.8 20.8 23.5 26.1 28.7 31.3 3.88 57.371 42.6 15.1 17.7 20.3 22.9 25.6 3.98 61.559 33.1 31.0 33.3* 34.2* 35.1* 35.9* 3.83 49.7

105 63 35.7 25.9 28.5 31.2 33.8 35.9* 3.92 53.667 38.3 20.3 22.9 25.5 28.1 30.8 4.01 57.871 41.1 14.5 17.1 19.7 22.4 25.0 4.10 62.059 30.6 29.9 31.2* 32.1* 32.9* 33.7* 4.09 50.7

115 63 33.0 24.8 27.4 30.0 32.7 33.7* 4.17 54.667 35.5 19.1 21.8 24.4 27.0 29.6 4.26 58.771 38.0 13.4 16.0 18.6 21.3 23.9 4.35 63.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1225 1575TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.3 1.1

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 41000 BTUHAIRFLOW = 1350 CFMAPP. DEW PT. = 56.5 DEG. FCOMPRESSOR POWER = 3201 WATTSI.D. FAN POWER = 356 WATTSO.D. FAN POWER = 177 WATTSS.E.E.R. = 11.89 BTUH/WATTE.E.R. = 10.65 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM14

Page 51: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 15

Performance DataCooling Metric Units

2TWB0036AA WITH TWE040CA4-B AT 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 10.7 9.6 10.3 10.8* 11.1* 11.3* 3.329.4 17.2 11.5 8.0 8.8 9.6 10.3 11.1 3.3

19.4 12.3 6.4 7.1 7.9 8.7 9.4 3.421.7 13.2 4.7 5.4 6.2 7.0 7.7 3.515.0 10.5 9.5 10.3 10.7* 11.0* 11.3* 3.4

32.2 17.2 11.4 8.0 8.8 9.5 10.3 11.1 3.519.4 12.2 6.3 7.1 7.9 8.6 9.4 3.621.7 13.1 4.6 5.4 6.2 6.9 7.7 3.715.0 10.5 9.4 10.2 10.6* 10.9* 11.2* 3.6

35.0 17.2 11.3 7.9 8.7 9.5 10.3 11.0 3.719.4 12.1 6.3 7.0 7.8 8.6 9.3 3.821.7 13.0 4.6 5.4 6.1 6.9 7.6 3.815.0 10.1 9.3 10.0 10.3* 10.6* 10.8* 3.7

37.8 17.2 10.8 7.8 8.5 9.3 10.1 10.8 3.819.4 11.7 6.1 6.9 7.6 8.4 9.2 3.921.7 12.5 4.4 5.2 5.9 6.7 7.5 4.015.0 9.7 9.1 9.8* 10.0* 10.3* 10.5* 3.8

40.6 17.2 10.5 7.6 8.4 9.1 9.9 10.5* 3.919.4 11.2 5.9 6.7 7.5 8.2 9.0 4.021.7 12.0 4.2 5.0 5.8 6.6 7.3 4.115.0 9.0 8.8 9.1* 9.4* 9.6* 9.9* 4.1

46.1 17.2 9.7 7.3 8.0 8.8 9.6 9.9* 4.219.4 10.4 5.6 6.4 7.1 7.9 8.7 4.321.7 11.1 3.9 4.7 5.4 6.2 7.0 4.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2080 2675TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.01 KWAIRFLOW = 2293 CMHCOMPRESSOR POWER = 3201 WATTSI.D. FAN POWER = 356 WATTSO.D. FAN POWER = 177 WATTSS.E.E.R. = 11.89 BTUH/WATTE.E.R. = 10.65 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM15

Page 52: Trane Full Brochure

16 TWE5-PRC001-EN-08-17-03

Performance DataCooling English Units

2TWA0030AD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 30.0 24.9 26.8 28.6 30.2* 31.0* 3.03 46.885 63 32.4 21.4 23.2 25.1 26.9 28.7 3.11 50.5

67 34.8 17.4 19.2 21.1 22.9 24.8 3.20 54.671 37.3 13.3 15.2 17.0 18.9 20.7 3.29 58.859 29.7 24.8 26.6 28.5 30.0* 30.7* 3.17 46.9

90 63 32.1 21.2 23.1 24.9 26.8 28.6 3.25 50.767 34.5 17.3 19.1 21.0 22.8 24.6 3.34 54.871 37.0 13.2 15.1 16.9 18.7 20.6 3.43 59.059 29.4 24.6 26.5 28.3 29.7* 30.5* 3.30 47.1

95 63 31.7 21.1 22.9 24.8 26.6 28.5 3.39 50.967 34.1 17.1 19.0 20.8 22.7 24.5 3.48 55.071 36.6 13.1 14.9 16.8 18.6 20.4 3.57 59.159 28.2 24.1 25.9 27.7 28.7* 29.5* 3.41 47.8

100 63 30.4 20.5 22.4 24.2 26.0 27.9 3.50 51.667 32.8 16.6 18.4 20.2 22.1 23.9 3.58 55.771 35.2 12.5 14.4 16.2 18.0 19.9 3.68 59.959 27.0 23.5 25.3 27.1* 27.8* 28.5* 3.52 48.5

105 63 29.1 19.9 21.8 23.6 25.5 27.3 3.60 52.467 31.4 16.0 17.8 19.7 21.5 23.4 3.69 56.471 33.7 11.9 13.8 15.6 17.5 19.3 3.78 60.659 24.6 22.4 24.2 25.1* 25.8* 26.4* 3.74 49.9

115 63 26.6 18.8 20.7 22.5 24.4 26.2 3.82 53.767 28.6 14.9 16.7 18.6 20.4 22.3 3.90 57.871 30.7 10.8 12.7 14.5 16.4 18.2 3.99 62.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.98 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 34200 BTUHAIRFLOW = 1000 CFMAPP. DEW PT. = 55.0 DEG. FCOMPRESSOR POWER = 2859 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 10.36 BTUH/WATTE.E.R. = 9.39 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWA0030AD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 32.1 27.2 29.3 31.4 32.7* 33.5* 3.00 47.285 63 34.5 23.1 25.2 27.3 29.4 31.5 3.09 51.1

67 37.0 18.6 20.7 22.8 24.9 27.0 3.18 55.371 39.6 13.9 16.0 18.1 20.2 22.3 3.27 59.659 31.7 27.0 29.1 31.2 32.3* 33.1* 3.14 47.4

90 63 34.1 22.9 25.0 27.1 29.2 31.3 3.23 51.367 36.6 18.4 20.5 22.6 24.7 26.8 3.32 55.571 39.1 13.7 15.8 17.9 20.0 22.2 3.41 59.859 31.3 26.8 28.9 31.0 32.0* 32.8* 3.28 47.7

95 63 33.6 22.7 24.8 26.9 29.0 31.1 3.36 51.567 36.1 18.2 20.3 22.4 24.5 26.6 3.46 55.771 38.6 13.5 15.7 17.8 19.9 22.0 3.55 60.059 29.8 26.2 28.3 30.0* 30.8* 31.5* 3.39 48.3

100 63 32.1 22.1 24.2 26.3 28.4 30.5 3.48 52.267 34.4 17.5 19.6 21.7 23.8 25.9 3.57 56.471 36.9 12.9 15.0 17.1 19.2 21.3 3.67 60.759 28.4 25.5 27.6 28.9* 29.6* 30.3* 3.51 49.0

105 63 30.6 21.4 23.5 25.6 27.7 29.8 3.60 52.967 32.8 16.9 19.0 21.1 23.2 25.3 3.69 57.171 35.1 12.3 14.4 16.5 18.6 20.7 3.78 61.459 25.5 24.2 25.8* 26.5* 27.2* 27.8* 3.75 50.3

115 63 27.5 20.1 22.2 24.3 26.4 27.8* 3.83 54.267 29.5 15.6 17.7 19.8 21.9 24.0 3.91 58.471 31.6 11.0 13.1 15.2 17.3 19.4 4.00 62.7

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 950 1250TOTAL CAP. X0.98 X1.02SENS. CAP. X0.94 X1.06COMPR. KW X0.98 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 36200 BTUHAIRFLOW = 1125 CFMAPP. DEW PT. = 56.0 DEG. FCOMPRESSOR POWER = 2982 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 11.28 BTUH/WATTE.E.R. = 10.12 BTUH/WATTNOTE: RATED WITH 25 FEET OF 7/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWA0040AD WITH TWE040CA4-B AT 1300 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 38.3 30.2 32.5 34.8 37.1 38.9* 3.31 44.985 63 41.3 25.8 28.1 30.4 32.7 35.0 3.41 48.8

67 44.4 20.9 23.2 25.5 27.8 30.1 3.53 52.971 47.7 15.8 18.1 20.4 22.7 25.0 3.64 57.159 37.6 29.9 32.2 34.5 36.8 38.3* 3.44 45.3

90 63 40.6 25.5 27.8 30.1 32.4 34.7 3.55 49.167 43.6 20.6 22.9 25.1 27.4 29.7 3.67 53.271 46.8 15.5 17.8 20.1 22.4 24.7 3.79 57.459 36.9 29.6 31.9 34.2 36.5 37.7* 3.58 45.6

95 63 39.8 25.2 27.5 29.8 32.1 34.3 3.70 49.467 42.8 20.2 22.5 24.8 27.1 29.4 3.82 53.571 45.9 15.2 17.5 19.8 22.1 24.4 3.94 57.759 36.0 29.2 31.5 33.8 36.1* 37.0* 3.73 46.0

100 63 38.8 24.8 27.1 29.3 31.6 33.9 3.85 49.867 41.7 19.8 22.1 24.4 26.7 29.0 3.97 53.971 44.8 14.8 17.1 19.4 21.7 24.0 4.09 58.159 35.0 28.8 31.1 33.4 35.4* 36.2* 3.88 46.3

105 63 37.8 24.4 26.6 28.9 31.2 33.5 4.00 50.267 40.6 19.4 21.7 24.0 26.3 28.6 4.12 54.371 43.6 14.4 16.7 19.0 21.3 23.6 4.25 58.559 33.2 28.0 30.3 32.6 33.9* 34.7* 4.18 47.1

115 63 35.8 23.6 25.8 28.1 30.4 32.7 4.30 51.067 38.5 18.6 20.9 23.2 25.5 27.8 4.43 55.171 41.3 13.6 15.9 18.2 20.5 22.8 4.56 59.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1150 1500TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01A.D.P. -1.4 1.4

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 43000 BTUHAIRFLOW = 1325 CFMAPP. DEW PT. = 53.7 DEG. FCOMPRESSOR POWER = 3236 WATTSI.D. FAN POWER = 360 WATTSO.D. FAN POWER = 232 WATTSS.E.E.R. = 12.25 BTUH/WATTE.E.R. = 10.74 BTUH/WATTNOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM16

Page 53: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 17

Performance DataCooling Metric Units

2TWA0030AD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.8 7.3 7.9 8.4 8.8* 9.1* 3.029.4 17.2 9.5 6.3 6.8 7.4 7.9 8.4 3.1

19.4 10.2 5.1 5.6 6.2 6.7 7.3 3.221.7 10.9 3.9 4.5 5.0 5.5 6.1 3.315.0 8.7 7.3 7.8 8.4 8.8* 9.0* 3.2

32.2 17.2 9.4 6.2 6.8 7.3 7.9 8.4 3.319.4 10.1 5.1 5.6 6.2 6.7 7.2 3.321.7 10.8 3.9 4.4 5.0 5.5 6.0 3.415.0 8.6 7.2 7.8 8.3 8.7* 8.9* 3.3

35.0 17.2 9.3 6.2 6.7 7.3 7.8 8.4 3.419.4 10.0 5.0 5.6 6.1 6.7 7.2 3.521.7 10.7 3.8 4.4 4.9 5.4 6.0 3.615.0 8.3 7.1 7.6 8.1 8.4* 8.6* 3.4

37.8 17.2 8.9 6.0 6.6 7.1 7.6 8.2 3.519.4 9.6 4.9 5.4 5.9 6.5 7.0 3.621.7 10.3 3.7 4.2 4.7 5.3 5.8 3.715.0 7.9 6.9 7.4 7.9* 8.1* 8.4* 3.5

40.6 17.2 8.5 5.8 6.4 6.9 7.5 8.0 3.619.4 9.2 4.7 5.2 5.8 6.3 6.9 3.721.7 9.9 3.5 4.0 4.6 5.1 5.7 3.815.0 7.2 6.6 7.1 7.4* 7.6* 7.7* 3.7

46.1 17.2 7.8 5.5 6.1 6.6 7.1 7.7 3.819.4 8.4 4.4 4.9 5.4 6.0 6.5 3.921.7 9.0 3.2 3.7 4.2 4.8 5.3 4.0

2TWA0030AD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.4 8.0 8.6 9.2 9.6* 9.8* 3.029.4 17.2 10.1 6.8 7.4 8.0 8.6 9.2 3.1

19.4 10.8 5.4 6.1 6.7 7.3 7.9 3.221.7 11.6 4.1 4.7 5.3 5.9 6.5 3.315.0 9.3 7.9 8.5 9.1 9.5* 9.7* 3.1

32.2 17.2 10.0 6.7 7.3 7.9 8.6 9.2 3.219.4 10.7 5.4 6.0 6.6 7.2 7.9 3.321.7 11.5 4.0 4.6 5.2 5.9 6.5 3.415.0 9.2 7.9 8.5 9.1 9.4* 9.6* 3.3

35.0 17.2 9.8 6.7 7.3 7.9 8.5 9.1 3.419.4 10.6 5.3 5.9 6.6 7.2 7.8 3.521.7 11.3 4.0 4.6 5.2 5.8 6.4 3.515.0 8.7 7.7 8.3 8.8* 9.0* 9.2* 3.4

37.8 17.2 9.4 6.5 7.1 7.7 8.3 8.9 3.519.4 10.1 5.1 5.7 6.4 7.0 7.6 3.621.7 10.8 3.8 4.4 5.0 5.6 6.2 3.715.0 8.3 7.5 8.1 8.5* 8.7* 8.9* 3.5

40.6 17.2 9.0 6.3 6.9 7.5 8.1 8.7 3.619.4 9.6 5.0 5.6 6.2 6.8 7.4 3.721.7 10.3 3.6 4.2 4.8 5.4 6.1 3.815.0 7.5 7.1 7.6* 7.8* 8.0* 8.1* 3.8

46.1 17.2 8.1 5.9 6.5 7.1 7.7 8.1* 3.819.4 8.6 4.6 5.2 5.8 6.4 7.0 3.921.7 9.3 3.2 3.8 4.5 5.1 5.7 4.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.98 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 10.02 KWAIRFLOW = 1698 CMHCOMPRESSOR POWER = 2859 WATTSI.D. FAN POWER = 437 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 10.36 BTUH/WATTE.E.R. = 9.39 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1613 2123TOTAL CAP. X0.98 X1.02SENS. CAP. X0.94 X1.06COMPR. KW X0.98 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 10.61 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2982 WATTSI.D. FAN POWER = 309 WATTSO.D. FAN POWER = 181 WATTSS.E.E.R. = 11.28 BTUH/WATTE.E.R. = 10.12 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

2TWA0040AD WITH TWE040CA4-B AT 2208 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.2 8.8 9.5 10.2 10.9 11.4* 3.329.4 17.2 12.1 7.6 8.2 8.9 9.6 10.3 3.4

19.4 13.0 6.1 6.8 7.5 8.1 8.8 3.521.7 14.0 4.6 5.3 6.0 6.7 7.3 3.615.0 11.0 8.8 9.4 10.1 10.8 11.2* 3.4

32.2 17.2 11.9 7.5 8.1 8.8 9.5 10.2 3.519.4 12.8 6.0 6.7 7.4 8.0 8.7 3.721.7 13.7 4.5 5.2 5.9 6.6 7.2 3.815.0 10.8 8.7 9.3 10.0 10.7 11.0* 3.6

35.0 17.2 11.7 7.4 8.1 8.7 9.4 10.0 3.719.4 12.5 5.9 6.6 7.3 7.9 8.6 3.821.7 13.4 4.5 5.1 5.8 6.5 7.1 3.915.0 10.5 8.6 9.2 9.9 10.6* 10.8* 3.7

37.8 17.2 11.4 7.3 7.9 8.6 9.3 9.9 3.819.4 12.2 5.8 6.5 7.1 7.8 8.5 4.021.7 13.1 4.3 5.0 5.7 6.4 7.0 4.115.0 10.3 8.4 9.1 9.8 10.4* 10.6* 3.9

40.6 17.2 11.1 7.1 7.8 8.5 9.1 9.8 4.019.4 11.9 5.7 6.4 7.0 7.7 8.4 4.121.7 12.8 4.2 4.9 5.6 6.2 6.9 4.315.0 9.7 8.2 8.9 9.6 9.9* 10.2* 4.2

46.1 17.2 10.5 6.9 7.6 8.2 8.9 9.6 4.319.4 11.3 5.4 6.1 6.8 7.5 8.1 4.421.7 12.1 4.0 4.7 5.3 6.0 6.7 4.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1953 2547TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.60 KWAIRFLOW = 2250 CMHCOMPRESSOR POWER = 3236 WATTSI.D. FAN POWER = 360 WATTSO.D. FAN POWER = 232 WATTSS.E.E.R. = 12.25 BTUH/WATTE.E.R. = 10.74 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM17

Page 54: Trane Full Brochure

18 TWE5-PRC001-EN-08-17-03

Performance DataCooling English Units

2TWA0040AD WITH TWE050CA5-C AT 1600 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 40.1 36.1 39.0 40.8* 41.9* 42.9* 3.61 48.585 63 43.2 30.2 33.2 36.2 39.2 42.2 3.72 52.4

67 46.4 23.8 26.8 29.8 32.8 35.7 3.83 56.571 49.7 17.3 20.2 23.2 26.2 29.2 3.95 60.859 39.2 35.7 38.6 40.1* 41.1* 42.1* 3.77 48.8

90 63 42.2 29.8 32.8 35.8 38.8 41.8 3.89 52.767 45.3 23.4 26.4 29.4 32.3 35.3 4.00 56.871 48.6 16.8 19.8 22.8 25.8 28.8 4.13 61.159 38.3 35.2 38.2 39.3* 40.3* 41.3* 3.93 49.1

95 63 41.2 29.4 32.4 35.4 38.4 41.3* 4.05 53.067 44.3 23.0 26.0 28.9 31.9 34.9 4.17 57.171 47.4 16.4 19.4 22.4 25.4 28.4 4.30 61.459 37.1 34.7 37.3* 38.3* 39.3* 40.2* 4.09 49.5

100 63 39.9 28.9 31.9 34.8 37.8 40.2* 4.21 53.467 42.9 22.4 25.4 28.4 31.4 34.4 4.34 57.571 45.9 15.9 18.9 21.9 24.8 27.8 4.47 61.859 35.9 34.2 36.3* 37.3* 38.3* 39.2* 4.25 49.8

105 63 38.7 28.4 31.3 34.3 37.3 39.2* 4.38 53.767 41.5 21.9 24.9 27.9 30.9 33.8 4.51 57.971 44.5 15.4 18.3 21.3 24.3 27.3 4.65 62.259 33.6 33.2 34.4* 35.3* 36.2* 37.0* 4.57 50.6

115 63 36.1 27.3 30.3 33.3 36.2* 37.0* 4.71 54.567 38.8 20.9 23.8 26.8 29.8 32.8 4.85 58.771 41.5 14.3 17.3 20.3 23.3 26.2 4.99 63.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1400 1800TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01A.D.P. -1.2 1.0

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 44200 BTUHAIRFLOW = 1575 CFMAPP. DEW PT. = 57.0 DEG. FCOMPRESSOR POWER = 3403 WATTSI.D. FAN POWER = 529 WATTSO.D. FAN POWER = 232 WATTSS.E.E.R. = 11.67 BTUH/WATTE.E.R. = 10.17 BTUH/WATTNOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWA0050AD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 49.2 42.5 45.9 49.2 50.5* 51.7* 4.67 47.785 63 52.9 36.0 39.3 42.7 46.0 49.3 4.78 51.5

67 56.8 28.8 32.1 35.5 38.8 42.1 4.91 55.771 60.8 21.4 24.8 28.1 31.4 34.8 5.04 59.959 48.2 42.1 45.4 48.4* 49.7* 50.8* 4.87 48.0

90 63 51.9 35.6 38.9 42.2 45.6 48.9 4.99 51.867 55.6 28.3 31.7 35.0 38.3 41.7 5.12 56.071 59.6 21.0 24.3 27.6 31.0 34.3 5.24 60.259 47.2 41.6 45.0 47.6* 48.9* 50.0* 5.08 48.3

95 63 50.8 35.1 38.4 41.8 45.1 48.4 5.20 52.167 54.5 27.9 31.2 34.6 37.9 41.2 5.32 56.371 58.3 20.5 23.9 27.2 30.5 33.9 5.45 60.659 46.0 41.1 44.4 46.6* 47.8* 48.9* 5.28 48.6

100 63 49.5 34.5 37.9 41.2 44.5 47.9 5.40 52.567 53.1 27.3 30.6 34.0 37.3 40.6 5.53 56.771 56.8 19.9 23.3 26.6 29.9 33.3 5.66 61.059 44.7 40.5 43.8 45.6* 46.7* 47.8* 5.49 49.0

105 63 48.1 34.0 37.3 40.6 44.0 47.3 5.61 52.967 51.6 26.7 30.1 33.4 36.7 40.1 5.73 57.171 55.2 19.4 22.7 26.0 29.4 32.7 5.86 61.459 42.2 39.4 42.4* 43.6* 44.6* 45.6* 5.92 49.8

115 63 45.4 32.8 36.1 39.5 42.8 45.6* 6.03 53.767 48.7 25.6 28.9 32.3 35.6 38.9 6.14 57.971 52.1 18.2 21.6 24.9 28.2 31.6 6.26 62.1

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01A.D.P. -1.4 1.1

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 54300 BTUHAIRFLOW = 1750 CFMAPP. DEW PT. = 56.0 DEG. FCOMPRESSOR POWER = 4376 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 189 WATTSS.E.E.R. = 11.05 BTUH/WATTE.E.R. = 9.78 BTUH/WATTNOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

2TWA0060AD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP. DEWD.B. W.B. CAP. 72 74 76 78 80 KW PT.

59 54.2 44.9 48.3 51.6 54.5* 55.8* 5.21 46.685 63 58.1 38.4 41.7 45.1 48.4 51.8 5.30 50.5

67 62.3 31.1 34.4 37.8 41.1 44.5 5.40 54.671 66.5 23.7 27.0 30.3 33.7 37.0 5.50 58.959 53.2 44.5 47.8 51.2 53.7* 55.0* 5.48 46.9

90 63 57.1 37.9 41.3 44.6 48.0 51.3 5.59 50.867 61.1 30.6 34.0 37.3 40.7 44.0 5.70 55.071 65.3 23.2 26.5 29.9 33.2 36.6 5.81 59.259 52.2 44.0 47.4 50.7 52.9* 54.2* 5.75 47.2

95 63 56.1 37.5 40.8 44.2 47.5 50.8 5.87 51.167 60.0 30.2 33.5 36.9 40.2 43.6 5.99 55.371 64.1 22.7 26.1 29.4 32.8 36.1 6.12 59.659 48.4 42.2 45.6 48.6* 49.8* 50.9* 6.77 48.5

100 63 51.9 35.7 39.0 42.3 45.7 49.0 6.92 52.467 55.6 28.4 31.7 35.1 38.4 41.7 7.08 56.671 59.4 21.0 24.3 27.6 31.0 34.3 7.25 60.859 44.5 40.5 43.8 45.4* 46.5* 47.6* 7.78 49.6

105 63 47.7 33.9 37.2 40.6 43.9 47.2 7.97 53.667 51.1 26.6 29.9 33.3 36.6 40.0 8.17 57.871 54.6 19.2 22.5 25.9 29.2 32.6 8.38 62.159 36.7 36.8* 37.8* 38.8* 39.7* 40.6* 9.76 51.9

115 63 39.4 30.4 33.7 37.1 39.7* 40.6* 10.05 55.967 42.2 23.1 26.5 29.8 33.1 36.5 10.36 60.171 45.1 15.7 19.1 22.4 25.8 29.1 10.67 64.4

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X1.00 X1.01A.D.P. -1.6 1.3

VALUES AT 95/80/67 RATING CONDITIONSGROSS CAPACITY = 59800 BTUHAIRFLOW = 1750 CFMAPP. DEW PT. = 55.0 DEG. FCOMPRESSOR POWER = 5059 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 11.09 BTUH/WATTE.E.R. = 9.58 BTUH/WATTNOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.

AND 3/8 LIQUID LINE* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM18

Page 55: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 19

Performance DataCooling Metric Units

2TWA0040AD WITH TWE050CA5-C AT 2717 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.7 10.6 11.4 12.0* 12.3* 12.6* 3.629.4 17.2 12.7 8.8 9.7 10.6 11.5 12.4 3.7

19.4 13.6 7.0 7.9 8.7 9.6 10.5 3.821.7 14.6 5.1 5.9 6.8 7.7 8.6 4.015.0 11.5 10.5 11.3 11.7* 12.0* 12.3* 3.8

32.2 17.2 12.4 8.7 9.6 10.5 11.4 12.2 3.919.4 13.3 6.9 7.7 8.6 9.5 10.3 4.021.7 14.2 4.9 5.8 6.7 7.6 8.4 4.115.0 11.2 10.3 11.2 11.5* 11.8* 12.1* 3.9

35.0 17.2 12.1 8.6 9.5 10.4 11.3 12.1* 4.119.4 13.0 6.7 7.6 8.5 9.3 10.2 4.221.7 13.9 4.8 5.7 6.6 7.4 8.3 4.315.0 10.9 10.2 10.9* 11.2* 11.5* 11.8* 4.1

37.8 17.2 11.7 8.5 9.3 10.2 11.1 11.8* 4.219.4 12.6 6.6 7.4 8.3 9.2 10.1 4.321.7 13.4 4.7 5.5 6.4 7.3 8.1 4.515.0 10.5 10.0 10.6* 10.9* 11.2* 11.5* 4.3

40.6 17.2 11.3 8.3 9.2 10.0 10.9 11.5* 4.419.4 12.2 6.4 7.3 8.2 9.1 9.9 4.521.7 13.0 4.5 5.4 6.2 7.1 8.0 4.715.0 9.8 9.7 10.1* 10.3* 10.6* 10.8* 4.6

46.1 17.2 10.6 8.0 8.9 9.8 10.6* 10.8* 4.719.4 11.4 6.1 7.0 7.9 8.7 9.6 4.821.7 12.2 4.2 5.1 5.9 6.8 7.7 5.0

2TWA0050AD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 14.4 12.5 13.4 14.4 14.8* 15.1* 4.729.4 17.2 15.5 10.5 11.5 12.5 13.5 14.4 4.8

19.4 16.6 8.4 9.4 10.4 11.4 12.3 4.921.7 17.8 6.3 7.3 8.2 9.2 10.2 5.015.0 14.1 12.3 13.3 14.2* 14.6* 14.9* 4.9

32.2 17.2 15.2 10.4 11.4 12.4 13.4 14.3 5.019.4 16.3 8.3 9.3 10.3 11.2 12.2 5.121.7 17.5 6.2 7.1 8.1 9.1 10.0 5.215.0 13.8 12.2 13.2 13.9* 14.3* 14.6* 5.1

35.0 17.2 14.9 10.3 11.3 12.2 13.2 14.2 5.219.4 16.0 8.2 9.1 10.1 11.1 12.1 5.321.7 17.1 6.0 7.0 8.0 8.9 9.9 5.415.0 13.5 12.0 13.0 13.7* 14.0* 14.3* 5.3

37.8 17.2 14.5 10.1 11.1 12.1 13.0 14.0 5.419.4 15.6 8.0 9.0 10.0 10.9 11.9 5.521.7 16.6 5.8 6.8 7.8 8.8 9.8 5.715.0 13.1 11.9 12.8 13.4* 13.7* 14.0* 5.5

40.6 17.2 14.1 10.0 10.9 11.9 12.9 13.9 5.619.4 15.1 7.8 8.8 9.8 10.8 11.7 5.721.7 16.2 5.7 6.7 7.6 8.6 9.6 5.915.0 12.4 11.5 12.4* 12.8* 13.1* 13.4* 5.9

46.1 17.2 13.3 9.6 10.6 11.6 12.5 13.4* 6.019.4 14.3 7.5 8.5 9.5 10.4 11.4 6.121.7 15.3 5.3 6.3 7.3 8.3 9.3 6.3

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2378 3057TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.95 KWAIRFLOW = 2675 CMHCOMPRESSOR POWER = 3403 WATTSI.D. FAN POWER = 529 WATTSO.D. FAN POWER = 232 WATTSS.E.E.R. = 11.67 BTUH/WATTE.E.R. = 10.17 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.98 X1.01SENS. CAP. X0.94 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 15.91 KWAIRFLOW = 2972 CMHCOMPRESSOR POWER = 4376 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 189 WATTSS.E.E.R. = 11.05 BTUH/WATTE.E.R. = 9.78 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

2TWA0060AD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 15.9 13.2 14.2 15.1 16.0* 16.3* 5.229.4 17.2 17.0 11.3 12.2 13.2 14.2 15.2 5.3

19.4 18.3 9.1 10.1 11.1 12.0 13.0 5.421.7 19.5 6.9 7.9 8.9 9.9 10.8 5.515.0 15.6 13.0 14.0 15.0 15.7* 16.1* 5.5

32.2 17.2 16.7 11.1 12.1 13.1 14.1 15.0 5.619.4 17.9 9.0 10.0 10.9 11.9 12.9 5.721.7 19.1 6.8 7.8 8.8 9.7 10.7 5.815.0 15.3 12.9 13.9 14.9 15.5* 15.9* 5.8

35.0 17.2 16.4 11.0 12.0 13.0 13.9 14.9 5.919.4 17.6 8.8 9.8 10.8 11.8 12.8 6.021.7 18.8 6.7 7.6 8.6 9.6 10.6 6.115.0 14.2 12.4 13.4 14.2* 14.6* 14.9* 6.8

37.8 17.2 15.2 10.5 11.4 12.4 13.4 14.4 6.919.4 16.3 8.3 9.3 10.3 11.3 12.2 7.121.7 17.4 6.2 7.1 8.1 9.1 10.0 7.315.0 13.0 11.9 12.8 13.3* 13.6* 13.9* 7.8

40.6 17.2 14.0 9.9 10.9 11.9 12.9 13.8 8.019.4 15.0 7.8 8.8 9.8 10.7 11.7 8.221.7 16.0 5.6 6.6 7.6 8.6 9.6 8.415.0 10.8 10.8* 11.1* 11.4* 11.6* 11.9* 9.8

46.1 17.2 11.5 8.9 9.9 10.9 11.6* 11.9* 10.119.4 12.4 6.8 7.8 8.7 9.7 10.7 10.421.7 13.2 4.6 5.6 6.6 7.6 8.5 10.7

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X1.00 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 17.52 KWAIRFLOW = 2972 CMHCOMPRESSOR POWER = 5059 WATTSI.D. FAN POWER = 731 WATTSO.D. FAN POWER = 179 WATTSS.E.E.R. = 11.09 BTUH/WATTE.E.R. = 9.58 BTUH/WATT

NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCT.AND 3/8 IN. LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM19

Page 56: Trane Full Brochure

20 TWE5-PRC001-EN-08-17-03

Performance DataHeating English Units

2TWB0012AA WITH TWE030CA4 AT 450 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.002 3.77 3.65 3.59 3.53 .887 .908 .919 .9297 4.85 4.68 4.60 4.51 .919 .941 .953 .964

12 5.93 5.71 5.60 5.50 .951 .975 .987 .99817 7.01 6.75 6.61 6.48 .983 1.01 1.02 1.0322 7.61 7.32 7.17 7.02 1.02 1.04 1.06 1.0727 8.21 7.89 7.73 7.57 1.05 1.08 1.10 1.1132 8.81 8.46 8.28 8.11 1.09 1.12 1.13 1.1537 9.40 9.03 8.84 8.65 1.12 1.15 1.17 1.1942 10.0 9.60 9.40 9.20 1.16 1.19 1.21 1.2247 13.5 12.9 12.7 12.4 1.18 1.21 1.22 1.2452 14.6 14.0 13.7 13.4 1.21 1.24 1.26 1.2857 15.7 15.0 14.7 14.3 1.24 1.27 1.29 1.3162 16.7 16.0 15.7 15.3 1.27 1.31 1.33 1.3467 17.8 17.1 16.7 16.3 1.30 1.34 1.36 1.3872 18.9 18.1 17.7 17.3 1.34 1.37 1.39 1.41

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 450 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 400 500HEATING CAP. X0.98 X1.02COMPR. KW X1.01 X0.99VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 450 CFMHEATING CAP. (HIGH TEMP.) = 12936 BTUHHEATING CAP. (LOW TEMP.) = 6745 BTUHCOMPR. POWER (HIGH TEMP.) = 773 WATTSCOMPR. POWER (LOW TEMP.) = 573 WATTSHSPF (MIN DHR) = 6.98COEFF. OF PERF. (HIGH TEMP.) = 3.13COEFF. OF PERF. (LOW TEMP.) = 1.95OUTDOOR FAN POWER = 93 WATTSINDOOR FAN POWER = 342 WATTSNOTE: RATED WITH 25 FEET OF 5/8 SUCTION

AND 1/4 LIQUID LINE

2TWB0018AA WITH TWE030CA4 AT 700 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 5.21 5.10 5.04 4.99 1.16 1.20 1.22 1.25-3 6.47 6.32 6.25 6.18 1.20 1.25 1.27 1.292 7.73 7.55 7.46 7.36 1.24 1.29 1.32 1.347 8.99 8.77 8.66 8.55 1.28 1.33 1.36 1.39

12 10.3 10.0 9.87 9.74 1.32 1.38 1.41 1.4417 11.5 11.2 11.1 10.9 1.36 1.42 1.45 1.4822 12.0 11.7 11.5 11.4 1.38 1.44 1.47 1.5027 12.5 12.1 12.0 11.8 1.40 1.47 1.50 1.5332 12.9 12.6 12.4 12.3 1.42 1.49 1.52 1.5537 13.4 13.1 12.9 12.7 1.44 1.51 1.54 1.5742 13.9 13.5 13.3 13.2 1.46 1.53 1.56 1.5947 19.1 18.6 18.3 18.1 1.61 1.69 1.73 1.7652 20.3 19.8 19.5 19.2 1.66 1.73 1.77 1.8157 21.6 21.0 20.7 20.4 1.70 1.78 1.82 1.8662 22.9 22.2 21.9 21.6 1.74 1.82 1.86 1.9067 24.1 23.5 23.1 22.8 1.78 1.87 1.91 1.9572 25.4 24.7 24.3 24.0 1.82 1.91 1.95 2.00

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 700 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 600 800HEATING CAP. X0.98 X1.02COMPR. KW X1.02 X0.99VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 675 CFMHEATING CAP. (HIGH TEMP.) = 18480 BTUHHEATING CAP. (LOW TEMP.) = 11151 BTUHCOMPR. POWER (HIGH TEMP.) = 1145 WATTSCOMPR. POWER (LOW TEMP.) = 878 WATTSHSPF (MIN DHR) = 7.83COEFF. OF PERF. (HIGH TEMP.) = 3.21COEFF. OF PERF. (LOW TEMP.) = 2.30OUTDOOR FAN POWER = 148 WATTSINDOOR FAN POWER = 387 WATTSNOTE: RATED WITH 25 FEET OF 3/4 SUCTION

AND 5/16 LIQUID LINE

2TWB0024AA WITH TWE030CA4 AT 900 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 7.29 7.14 7.06 6.99 1.57 1.64 1.67 1.70-3 8.82 8.64 8.54 8.45 1.63 1.69 1.73 1.762 10.4 10.1 10.0 9.90 1.68 1.75 1.78 1.827 11.9 11.6 11.5 11.4 1.73 1.80 1.84 1.87

12 13.4 13.1 13.0 12.8 1.78 1.86 1.89 1.9317 15.0 14.6 14.5 14.3 1.83 1.91 1.95 1.9922 15.9 15.5 15.4 15.2 1.86 1.94 1.98 2.0227 16.8 16.4 16.2 16.0 1.90 1.98 2.02 2.0632 17.8 17.4 17.1 16.9 1.93 2.01 2.05 2.0937 18.7 18.3 18.0 17.8 1.96 2.04 2.09 2.1342 19.6 19.2 18.9 18.7 1.99 2.08 2.12 2.1647 24.2 23.6 23.3 23.0 2.14 2.24 2.28 2.3352 25.7 25.1 24.8 24.5 2.19 2.29 2.34 2.3957 27.3 26.6 26.3 26.0 2.25 2.35 2.40 2.4562 28.8 28.1 27.8 27.4 2.30 2.40 2.45 2.5067 30.4 29.6 29.2 28.9 2.35 2.46 2.51 2.5672 31.9 31.1 30.7 30.3 2.40 2.51 2.56 2.62

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 900 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 775 1025HEATING CAP. X0.98 X1.02COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 900 CFMHEATING CAP. (HIGH TEMP.) = 23620 BTUHHEATING CAP. (LOW TEMP.) = 14629 BTUHCOMPR. POWER (HIGH TEMP.) = 1631 WATTSCOMPR. POWER (LOW TEMP.) = 1304 WATTSHSPF (MIN DHR) = 7.92COEFF. OF PERF. (HIGH TEMP.) = 3.09COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 425 WATTSNOTE: RATED WITH 25 FEET OF 3/4 SUCTION

AND 5/16 LIQUID LINE

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM20

Page 57: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 21

Performance DataHeating Metric Units

2TWB0012AA WITH TWE030CA4 AT 764 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-16.7 1.1 1.1 1.1 1.0 0.9 0.9 0.9 0.9-13.9 1.4 1.4 1.3 1.3 0.9 0.9 1.0 1.0-11.1 1.7 1.7 1.6 1.6 1.0 1.0 1.0 1.0-8.3 2.1 2.0 1.9 1.9 1.0 1.0 1.0 1.0-5.6 2.2 2.1 2.1 2.1 1.0 1.0 1.1 1.1-2.8 2.4 2.3 2.3 2.2 1.0 1.1 1.1 1.10.0 2.6 2.5 2.4 2.4 1.1 1.1 1.1 1.12.8 2.8 2.6 2.6 2.5 1.1 1.1 1.2 1.25.6 2.9 2.8 2.8 2.7 1.2 1.2 1.2 1.28.3 4.0 3.8 3.7 3.6 1.2 1.2 1.2 1.2

11.1 4.3 4.1 4.0 3.9 1.2 1.2 1.3 1.313.9 4.6 4.4 4.3 4.2 1.2 1.3 1.3 1.316.7 4.9 4.7 4.6 4.5 1.3 1.3 1.3 1.319.4 5.2 5.0 4.9 4.8 1.3 1.3 1.4 1.422.2 5.5 5.3 5.2 5.1 1.3 1.4 1.4 1.4

2TWB0018AA WITH TWE030CA4 AT 1189 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 1.5 1.5 1.5 1.5 1.2 1.2 1.2 1.3-19.4 1.9 1.9 1.8 1.8 1.2 1.3 1.3 1.3-16.7 2.3 2.2 2.2 2.2 1.2 1.3 1.3 1.3-13.9 2.6 2.6 2.5 2.5 1.3 1.3 1.4 1.4-11.1 3.0 2.9 2.9 2.9 1.3 1.4 1.4 1.4-8.3 3.4 3.3 3.3 3.2 1.4 1.4 1.5 1.5-5.6 3.5 3.4 3.4 3.3 1.4 1.4 1.5 1.5-2.8 3.7 3.5 3.5 3.5 1.4 1.5 1.5 1.50.0 3.8 3.7 3.6 3.6 1.4 1.5 1.5 1.52.8 3.9 3.8 3.8 3.7 1.4 1.5 1.5 1.65.6 4.1 4.0 3.9 3.9 1.5 1.5 1.6 1.68.3 5.6 5.4 5.4 5.3 1.6 1.7 1.7 1.8

11.1 5.9 5.8 5.7 5.6 1.7 1.7 1.8 1.813.9 6.3 6.2 6.1 6.0 1.7 1.8 1.8 1.916.7 6.7 6.5 6.4 6.3 1.7 1.8 1.9 1.919.4 7.1 6.9 6.8 6.7 1.8 1.9 1.9 2.022.2 7.4 7.2 7.1 7.0 1.8 1.9 2.0 2.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 764 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 679 849HEATING CAP. X0.98 X1.02COMPR. KW X1.01 X0.99VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 764 CMHHEATING CAP. (HIGH TEMP.) = 3.79 KWHEATING CAP. (LOW TEMP.) = 1.98 KWCOMPR. POWER (HIGH TEMP.) = 773 WATTSCOMPR. POWER (LOW TEMP.) = 573 WATTSHSPF (MIN DHR) = 6.98COEFF. OF PERF. (HIGH TEMP.) = 3.13COEFF. OF PERF. (LOW TEMP.) = 1.95OUTDOOR FAN POWER = 93 WATTSINDOOR FAN POWER = 342 WATTSNOTE: RATED WITH 7.62 METERS OF 5/8 IN.

SUCTION AND 1/4 LIQUID LINE

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1189 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1019 1358HEATING CAP. X0.98 X1.02COMPR. KW X1.02 X0.99VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1146 CMHHEATING CAP. (HIGH TEMP.) = 5.41 KWHEATING CAP. (LOW TEMP.) = 3.27 KWCOMPR. POWER (HIGH TEMP.) = 1145 WATTSCOMPR. POWER (LOW TEMP.) = 878 WATTSHSPF (MIN DHR) = 7.83COEFF. OF PERF. (HIGH TEMP.) = 3.21COEFF. OF PERF. (LOW TEMP.) = 2.30OUTDOOR FAN POWER = 148 WATTSINDOOR FAN POWER = 387 WATTSNOTE: RATED WITH 7.62 METERS OF 3/4 IN.

SUCTION AND 5/16 LIQUID LINE

2TWB0024AA WITH TWE030CA4 AT 1528 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 2.1 2.1 2.1 2.0 1.6 1.6 1.7 1.7-19.4 2.6 2.5 2.5 2.5 1.6 1.7 1.7 1.8-16.7 3.0 3.0 2.9 2.9 1.7 1.8 1.8 1.8-13.9 3.5 3.4 3.4 3.3 1.7 1.8 1.8 1.9-11.1 3.9 3.8 3.8 3.8 1.8 1.9 1.9 1.9-8.3 4.4 4.3 4.2 4.2 1.8 1.9 2.0 2.0-5.6 4.7 4.5 4.5 4.5 1.9 1.9 2.0 2.0-2.8 4.9 4.8 4.7 4.7 1.9 2.0 2.0 2.10.0 5.2 5.1 5.0 5.0 1.9 2.0 2.0 2.12.8 5.5 5.4 5.3 5.2 2.0 2.0 2.1 2.15.6 5.7 5.6 5.5 5.5 2.0 2.1 2.1 2.28.3 7.1 6.9 6.8 6.7 2.1 2.2 2.3 2.3

11.1 7.5 7.4 7.3 7.2 2.2 2.3 2.3 2.413.9 8.0 7.8 7.7 7.6 2.3 2.3 2.4 2.516.7 8.4 8.2 8.1 8.0 2.3 2.4 2.5 2.519.4 8.9 8.7 8.6 8.5 2.3 2.5 2.5 2.622.2 9.3 9.1 9.0 8.9 2.4 2.5 2.6 2.6

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1528 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1316 1741HEATING CAP. X0.98 X1.02COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1528 CMHHEATING CAP. (HIGH TEMP.) = 6.92 KWHEATING CAP. (LOW TEMP.) = 4.29 KWCOMPR. POWER (HIGH TEMP.) = 1631 WATTSCOMPR. POWER (LOW TEMP.) = 1304 WATTSHSPF (MIN DHR) = 7.92COEFF. OF PERF. (HIGH TEMP.) = 3.09COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 425 WATTSNOTE: RATED WITH 7.62 METERS OF 3/4 IN.

SUCTION AND 5/16 LIQUID LINE

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM21

Page 58: Trane Full Brochure

22 TWE5-PRC001-EN-08-17-03

Performance DataHeating English Units

2TWB0030AA WITH TWE030CA4 AT 1000 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 8.66 8.49 8.41 8.33 1.87 1.96 2.01 2.062 10.6 10.4 10.3 10.2 1.94 2.04 2.09 2.147 12.6 12.3 12.2 12.1 2.02 2.12 2.17 2.23

12 14.5 14.2 14.1 13.9 2.10 2.20 2.26 2.3117 16.5 16.1 16.0 15.8 2.17 2.28 2.34 2.4022 17.0 16.6 16.5 16.3 2.22 2.33 2.39 2.4527 17.5 17.1 16.9 16.7 2.26 2.38 2.44 2.5032 18.0 17.6 17.4 17.2 2.31 2.43 2.49 2.5537 18.5 18.1 17.9 17.7 2.35 2.48 2.54 2.6042 19.0 18.6 18.4 18.2 2.40 2.53 2.59 2.6647 28.2 27.6 27.3 27.0 2.62 2.77 2.84 2.9152 30.2 29.5 29.2 28.9 2.70 2.85 2.92 2.9957 32.1 31.4 31.1 30.7 2.78 2.93 3.00 3.0862 34.1 33.3 33.0 32.6 2.85 3.01 3.09 3.1767 36.1 35.3 34.9 34.5 2.93 3.09 3.17 3.2572 38.0 37.2 36.7 36.3 3.00 3.17 3.25 3.34

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1000 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 875 1125HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1000 CFMHEATING CAP. (HIGH TEMP.) = 27612 BTUHHEATING CAP. (LOW TEMP.) = 16141 BTUHCOMPR. POWER (HIGH TEMP.) = 2151 WATTSCOMPR. POWER (LOW TEMP.) = 1668 WATTSHSPF (MIN DHR) = 6.96COEFF. OF PERF. (HIGH TEMP.) = 2.91COEFF. OF PERF. (LOW TEMP.) = 2.06OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 437 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

2TWB0030AA WITH TWE040CA4-B AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 8.14 7.98 7.89 7.81 1.73 1.83 1.88 1.932 10.1 9.94 9.83 9.73 1.79 1.89 1.95 2.007 12.2 11.9 11.8 11.6 1.85 1.96 2.02 2.07

12 14.2 13.9 13.7 13.6 1.91 2.03 2.08 2.1417 16.2 15.8 15.7 15.5 1.98 2.09 2.15 2.2122 16.7 16.4 16.2 16.0 2.01 2.13 2.19 2.2527 17.3 16.9 16.7 16.5 2.05 2.17 2.24 2.3032 17.8 17.4 17.2 17.1 2.09 2.21 2.28 2.3437 18.4 18.0 17.8 17.6 2.13 2.25 2.32 2.3842 18.9 18.5 18.3 18.1 2.16 2.29 2.36 2.4347 28.2 27.6 27.3 27.0 2.35 2.49 2.57 2.6452 30.2 29.6 29.2 28.9 2.41 2.56 2.64 2.7157 32.3 31.5 31.2 30.8 2.47 2.63 2.70 2.7862 34.3 33.5 33.1 32.7 2.54 2.69 2.77 2.8567 36.3 35.5 35.1 34.6 2.60 2.76 2.84 2.9272 38.3 37.4 37.0 36.6 2.66 2.83 2.91 2.99

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 950 1250HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 27658 BTUHHEATING CAP. (LOW TEMP.) = 15867 BTUHCOMPR. POWER (HIGH TEMP.) = 2007 WATTSCOMPR. POWER (LOW TEMP.) = 1608 WATTSHSPF (MIN DHR) = 7.47COEFF. OF PERF. (HIGH TEMP.) = 3.23COEFF. OF PERF. (LOW TEMP.) = 2.20OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 309 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

2TWB0036AA WITH TWE030CA4 AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 7.66 7.55 7.49 7.44 1.86 1.95 2.00 2.05-3 10.2 10.1 9.97 9.89 1.98 2.09 2.14 2.192 12.8 12.6 12.5 12.3 2.10 2.22 2.27 2.337 15.3 15.1 14.9 14.8 2.23 2.35 2.41 2.47

12 17.9 17.6 17.4 17.3 2.35 2.48 2.55 2.6117 20.4 20.1 19.9 19.7 2.47 2.61 2.68 2.7522 21.6 21.3 21.1 20.9 2.57 2.72 2.79 2.8627 22.8 22.4 22.2 22.0 2.67 2.82 2.90 2.9832 24.0 23.6 23.4 23.2 2.76 2.93 3.01 3.0937 25.3 24.8 24.6 24.4 2.86 3.03 3.11 3.2042 26.5 26.0 25.7 25.5 2.96 3.14 3.22 3.3147 35.8 35.1 34.8 34.4 3.21 3.40 3.50 3.5952 38.3 37.6 37.3 36.9 3.33 3.53 3.63 3.7457 40.9 40.1 39.7 39.4 3.45 3.66 3.77 3.8862 43.4 42.6 42.2 41.8 3.58 3.80 3.91 4.0267 46.0 45.1 44.7 44.3 3.70 3.93 4.04 4.1672 48.5 47.6 47.2 46.7 3.82 4.06 4.18 4.30

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 950 1250HEATING CAP. X0.98 X1.01COMPR. KW X1.03 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 35184 BTUHHEATING CAP. (LOW TEMP.) = 20137 BTUHCOMPR. POWER (HIGH TEMP.) = 2683 WATTSCOMPR. POWER (LOW TEMP.) = 1897 WATTSHSPF (MIN DHR) = 7.74COEFF. OF PERF. (HIGH TEMP.) = 3.01COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 177 WATTSINDOOR FAN POWER = 541 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM22

Page 59: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 23

Performance DataHeating Metric Units

2TWB0030AA WITH TWE030CA4 AT 1698 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.5 2.5 2.5 2.4 1.9 2.0 2.0 2.1-16.7 3.1 3.0 3.0 3.0 1.9 2.0 2.1 2.1-13.9 3.7 3.6 3.6 3.5 2.0 2.1 2.2 2.2-11.1 4.2 4.2 4.1 4.1 2.1 2.2 2.3 2.3-8.3 4.8 4.7 4.7 4.6 2.2 2.3 2.3 2.4-5.6 5.0 4.9 4.8 4.8 2.2 2.3 2.4 2.5-2.8 5.1 5.0 5.0 4.9 2.3 2.4 2.4 2.50.0 5.3 5.2 5.1 5.0 2.3 2.4 2.5 2.52.8 5.4 5.3 5.2 5.2 2.3 2.5 2.5 2.65.6 5.6 5.4 5.4 5.3 2.4 2.5 2.6 2.78.3 8.3 8.1 8.0 7.9 2.6 2.8 2.8 2.9

11.1 8.8 8.6 8.6 8.5 2.7 2.8 2.9 3.013.9 9.4 9.2 9.1 9.0 2.8 2.9 3.0 3.116.7 10.0 9.8 9.7 9.6 2.8 3.0 3.1 3.219.4 10.6 10.3 10.2 10.1 2.9 3.1 3.2 3.322.2 11.1 10.9 10.8 10.6 3.0 3.2 3.3 3.3

2TWB0030AA WITH TWE040CA4-B AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.4 2.3 2.3 2.3 1.7 1.8 1.9 1.9-16.7 3.0 2.9 2.9 2.9 1.8 1.9 2.0 2.0-13.9 3.6 3.5 3.5 3.4 1.9 2.0 2.0 2.1-11.1 4.2 4.1 4.0 4.0 1.9 2.0 2.1 2.1-8.3 4.7 4.6 4.6 4.5 2.0 2.1 2.2 2.2-5.6 4.9 4.8 4.7 4.7 2.0 2.1 2.2 2.3-2.8 5.1 5.0 4.9 4.8 2.0 2.2 2.2 2.30.0 5.2 5.1 5.0 5.0 2.1 2.2 2.3 2.32.8 5.4 5.3 5.2 5.2 2.1 2.3 2.3 2.45.6 5.5 5.4 5.4 5.3 2.2 2.3 2.4 2.48.3 8.3 8.1 8.0 7.9 2.3 2.5 2.6 2.6

11.1 8.8 8.7 8.6 8.5 2.4 2.6 2.6 2.713.9 9.5 9.2 9.1 9.0 2.5 2.6 2.7 2.816.7 10.0 9.8 9.7 9.6 2.5 2.7 2.8 2.819.4 10.6 10.4 10.3 10.1 2.6 2.8 2.8 2.922.2 11.2 11.0 10.8 10.7 2.7 2.8 2.9 3.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1698 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1486 1910HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1698 CMHHEATING CAP. (HIGH TEMP.) = 8.09 KWHEATING CAP. (LOW TEMP.) = 4.73 KWCOMPR. POWER (HIGH TEMP.) = 2151 WATTSCOMPR. POWER (LOW TEMP.) = 1668 WATTSHSPF (MIN DHR) = 6.96COEFF. OF PERF. (HIGH TEMP.) = 2.91COEFF. OF PERF. (LOW TEMP.) = 2.06OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 437 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1613 2123HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 8.10 KWHEATING CAP. (LOW TEMP.) = 4.65 KWCOMPR. POWER (HIGH TEMP.) = 2007 WATTSCOMPR. POWER (LOW TEMP.) = 1608 WATTSHSPF (MIN DHR) = 7.47COEFF. OF PERF. (HIGH TEMP.) = 3.23COEFF. OF PERF. (LOW TEMP.) = 2.20OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 309 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

2TWB0036AA WITH TWE030CA4 AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 2.2 2.2 2.2 2.2 1.9 2.0 2.0 2.0-19.4 3.0 3.0 2.9 2.9 2.0 2.1 2.1 2.2-16.7 3.8 3.7 3.7 3.6 2.1 2.2 2.3 2.3-13.9 4.5 4.4 4.4 4.3 2.2 2.3 2.4 2.5-11.1 5.2 5.2 5.1 5.1 2.3 2.5 2.5 2.6-8.3 6.0 5.9 5.8 5.8 2.5 2.6 2.7 2.8-5.6 6.3 6.2 6.2 6.1 2.6 2.7 2.8 2.9-2.8 6.7 6.6 6.5 6.4 2.7 2.8 2.9 3.00.0 7.0 6.9 6.9 6.8 2.8 2.9 3.0 3.12.8 7.4 7.3 7.2 7.1 2.9 3.0 3.1 3.25.6 7.8 7.6 7.5 7.5 3.0 3.1 3.2 3.38.3 10.5 10.3 10.2 10.1 3.2 3.4 3.5 3.6

11.1 11.2 11.0 10.9 10.8 3.3 3.5 3.6 3.713.9 12.0 11.7 11.6 11.5 3.5 3.7 3.8 3.916.7 12.7 12.5 12.4 12.2 3.6 3.8 3.9 4.019.4 13.5 13.2 13.1 13.0 3.7 3.9 4.0 4.222.2 14.2 13.9 13.8 13.7 3.8 4.1 4.2 4.3

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1613 2123HEATING CAP. X0.98 X1.01COMPR. KW X1.03 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 10.31 KWHEATING CAP. (LOW TEMP.) = 5.90 KWCOMPR. POWER (HIGH TEMP.) = 2683 WATTSCOMPR. POWER (LOW TEMP.) = 1897 WATTSHSPF (MIN DHR) = 7.74COEFF. OF PERF. (HIGH TEMP.) = 3.01COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 177 WATTSINDOOR FAN POWER = 541 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM23

Page 60: Trane Full Brochure

24 TWE5-PRC001-EN-08-17-03

2TWB0036AA WITH TWE040CA4-B AT 1400 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 7.16 7.05 6.99 6.94 1.75 1.86 1.91 1.97-3 9.83 9.67 9.58 9.50 1.85 1.97 2.03 2.082 12.5 12.3 12.2 12.1 1.95 2.08 2.14 2.207 15.2 14.9 14.8 14.6 2.05 2.19 2.25 2.32

12 17.8 17.5 17.4 17.2 2.15 2.30 2.37 2.4417 20.5 20.1 19.9 19.8 2.25 2.40 2.48 2.5622 21.8 21.4 21.2 21.0 2.33 2.49 2.57 2.6527 23.1 22.7 22.5 22.2 2.41 2.58 2.66 2.7432 24.4 23.9 23.7 23.5 2.50 2.67 2.75 2.8437 25.7 25.2 25.0 24.7 2.58 2.75 2.84 2.9342 26.9 26.5 26.2 26.0 2.66 2.84 2.93 3.0247 36.5 35.8 35.5 35.2 2.86 3.06 3.16 3.2652 39.2 38.5 38.1 37.7 2.96 3.17 3.28 3.3857 41.9 41.1 40.7 40.3 3.07 3.28 3.39 3.5062 44.5 43.7 43.3 42.8 3.17 3.39 3.50 3.6267 47.2 46.3 45.9 45.4 3.27 3.50 3.62 3.7372 49.9 48.9 48.4 48.0 3.37 3.61 3.73 3.85

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1400 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1225 1575HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1350 CFMHEATING CAP. (HIGH TEMP.) = 35733 BTUHHEATING CAP. (LOW TEMP.) = 20058 BTUHCOMPR. POWER (HIGH TEMP.) = 2533 WATTSCOMPR. POWER (LOW TEMP.) = 1871 WATTSHSPF (MIN DHR) = 8.40COEFF. OF PERF. (HIGH TEMP.) = 3.40COEFF. OF PERF. (LOW TEMP.) = 2.43OUTDOOR FAN POWER = 177 WATTSINDOOR FAN POWER = 356 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

Performance DataHeating English Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM24

Page 61: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 25

2TWB0036AA WITH TWE040CA4-B AT 2378 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 2.1 2.1 2.0 2.0 1.8 1.9 1.9 2.0-19.4 2.9 2.8 2.8 2.8 1.9 2.0 2.0 2.1-16.7 3.7 3.6 3.6 3.5 2.0 2.1 2.1 2.2-13.9 4.5 4.4 4.3 4.3 2.0 2.2 2.3 2.3-11.1 5.2 5.1 5.1 5.0 2.2 2.3 2.4 2.4-8.3 6.0 5.9 5.8 5.8 2.3 2.4 2.5 2.6-5.6 6.4 6.3 6.2 6.2 2.3 2.5 2.6 2.7-2.8 6.8 6.7 6.6 6.5 2.4 2.6 2.7 2.70.0 7.1 7.0 6.9 6.9 2.5 2.7 2.8 2.82.8 7.5 7.4 7.3 7.2 2.6 2.8 2.8 2.95.6 7.9 7.8 7.7 7.6 2.7 2.8 2.9 3.08.3 10.7 10.5 10.4 10.3 2.9 3.1 3.2 3.3

11.1 11.5 11.3 11.2 11.0 3.0 3.2 3.3 3.413.9 12.3 12.0 11.9 11.8 3.1 3.3 3.4 3.516.7 13.0 12.8 12.7 12.5 3.2 3.4 3.5 3.619.4 13.8 13.6 13.4 13.3 3.3 3.5 3.6 3.722.2 14.6 14.3 14.2 14.1 3.4 3.6 3.7 3.8

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2378 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2080 2675HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2293 CMHHEATING CAP. (HIGH TEMP.) = 10.47 KWHEATING CAP. (LOW TEMP.) = 5.88 KWCOMPR. POWER (HIGH TEMP.) = 2533 WATTSCOMPR. POWER (LOW TEMP.) = 1871 WATTSHSPF (MIN DHR) = 8.40COEFF. OF PERF. (HIGH TEMP.) = 3.40COEFF. OF PERF. (LOW TEMP.) = 2.43OUTDOOR FAN POWER = 177 WATTSINDOOR FAN POWER = 356 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

Performance DataHeating Metric Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM25

Page 62: Trane Full Brochure

26 TWE5-PRC001-EN-08-17-03

2TWA0030AD WITH TWE030CA4 AT 1000 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 8.86 8.70 8.62 8.55 1.91 2.03 2.08 2.142 11.0 10.8 10.7 10.6 2.00 2.12 2.18 2.247 13.2 12.9 12.8 12.7 2.09 2.22 2.28 2.35

12 15.3 15.0 14.9 14.7 2.18 2.32 2.38 2.4517 17.4 17.1 16.9 16.8 2.27 2.41 2.49 2.5622 17.9 17.5 17.3 17.2 2.32 2.47 2.54 2.6127 18.3 17.9 17.8 17.6 2.37 2.52 2.59 2.6732 18.7 18.4 18.2 18.0 2.42 2.57 2.65 2.7237 19.1 18.8 18.6 18.4 2.46 2.62 2.70 2.7842 19.6 19.2 19.0 18.8 2.51 2.67 2.75 2.8347 30.3 29.7 29.4 29.1 2.81 3.00 3.09 3.1852 32.5 31.8 31.5 31.2 2.90 3.09 3.19 3.2857 34.6 33.9 33.6 33.2 2.99 3.19 3.29 3.3962 36.8 36.0 35.6 35.3 3.08 3.29 3.39 3.4967 38.9 38.1 37.7 37.3 3.17 3.38 3.49 3.6072 41.1 40.2 39.8 39.4 3.26 3.48 3.59 3.70

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1000 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 875 1125HEATING CAP. X0.99 X1.01COMPR. KW X1.03 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1000 CFMHEATING CAP. (HIGH TEMP.) = 29711 BTUHHEATING CAP. (LOW TEMP.) = 17106 BTUHCOMPR. POWER (HIGH TEMP.) = 2378 WATTSCOMPR. POWER (LOW TEMP.) = 1796 WATTSHSPF (MIN DHR) = 6.91COEFF. OF PERF. (HIGH TEMP.) = 2.89COEFF. OF PERF. (LOW TEMP.) = 2.06OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 437 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

2TWA0030AD WITH TWE040CA4-B AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 8.37 8.21 8.13 8.06 1.76 1.89 1.95 2.012 10.6 10.4 10.3 10.2 1.84 1.97 2.03 2.107 12.8 12.6 12.4 12.3 1.91 2.05 2.12 2.19

12 15.0 14.7 14.6 14.4 1.99 2.13 2.21 2.2817 17.3 16.9 16.7 16.6 2.07 2.22 2.29 2.3722 17.7 17.4 17.2 17.0 2.11 2.26 2.34 2.4127 18.2 17.8 17.6 17.5 2.15 2.30 2.38 2.4632 18.7 18.3 18.1 17.9 2.18 2.34 2.42 2.5137 19.1 18.7 18.5 18.4 2.22 2.39 2.47 2.5542 19.6 19.2 19.0 18.8 2.26 2.43 2.51 2.6047 30.6 30.0 29.6 29.3 2.52 2.71 2.81 2.9052 32.8 32.1 31.8 31.5 2.60 2.79 2.89 2.9957 35.0 34.3 33.9 33.6 2.67 2.88 2.98 3.0862 37.3 36.5 36.1 35.7 2.75 2.96 3.06 3.1767 39.5 38.7 38.3 37.8 2.83 3.04 3.15 3.2672 41.7 40.8 40.4 40.0 2.90 3.12 3.23 3.34

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 950 1250HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 30013 BTUHHEATING CAP. (LOW TEMP.) = 16951 BTUHCOMPR. POWER (HIGH TEMP.) = 2219 WATTSCOMPR. POWER (LOW TEMP.) = 1726 WATTSHSPF (MIN DHR) = 7.46COEFF. OF PERF. (HIGH TEMP.) = 3.23COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 309 WATTSNOTE: RATED WITH 25 FEET OF 7/8 SUCTION

AND 3/8 LIQUID LINE

2TWA0040AD WITH TWE040CA4-B AT 1300 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 9.23 9.08 9.01 8.93 1.94 2.05 2.11 2.172 12.0 11.8 11.7 11.6 2.05 2.17 2.23 2.297 14.8 14.6 14.5 14.3 2.15 2.28 2.35 2.41

12 17.7 17.3 17.2 17.0 2.26 2.40 2.46 2.5317 20.5 20.1 19.9 19.7 2.37 2.51 2.58 2.6522 21.4 21.1 20.9 20.7 2.45 2.60 2.67 2.7527 22.4 22.0 21.8 21.6 2.53 2.68 2.76 2.8432 23.4 23.0 22.8 22.6 2.61 2.77 2.85 2.9337 24.4 23.9 23.7 23.5 2.69 2.86 2.94 3.0242 25.3 24.9 24.7 24.5 2.77 2.94 3.03 3.1147 37.3 36.6 36.3 36.0 3.01 3.20 3.29 3.3852 40.1 39.4 39.0 38.7 3.11 3.31 3.41 3.5157 42.9 42.1 41.7 41.4 3.22 3.42 3.53 3.6362 45.7 44.9 44.5 44.1 3.33 3.54 3.64 3.7567 48.5 47.6 47.2 46.8 3.43 3.65 3.76 3.8772 51.3 50.4 49.9 49.5 3.54 3.77 3.88 3.99

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1300 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1150 1500HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1325 CFMHEATING CAP. (HIGH TEMP.) = 36683 BTUHHEATING CAP. (LOW TEMP.) = 20141 BTUHCOMPR. POWER (HIGH TEMP.) = 2601 WATTSCOMPR. POWER (LOW TEMP.) = 1918 WATTSHSPF (MIN DHR) = 7.91COEFF. OF PERF. (HIGH TEMP.) = 3.35COEFF. OF PERF. (LOW TEMP.) = 2.34OUTDOOR FAN POWER = 232 WATTSINDOOR FAN POWER = 360 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION

AND 3/8 LIQUID LINE

Performance DataHeating English Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM26

Page 63: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 27

2TWA0030AD WITH TWE030CA4 AT 1698 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.6 2.5 2.5 2.5 1.9 2.0 2.1 2.1-16.7 3.2 3.2 3.1 3.1 2.0 2.1 2.2 2.2-13.9 3.9 3.8 3.8 3.7 2.1 2.2 2.3 2.3-11.1 4.5 4.4 4.4 4.3 2.2 2.3 2.4 2.5-8.3 5.1 5.0 5.0 4.9 2.3 2.4 2.5 2.6-5.6 5.2 5.1 5.1 5.0 2.3 2.5 2.5 2.6-2.8 5.4 5.2 5.2 5.2 2.4 2.5 2.6 2.70.0 5.5 5.4 5.3 5.3 2.4 2.6 2.7 2.72.8 5.6 5.5 5.4 5.4 2.5 2.6 2.7 2.85.6 5.7 5.6 5.6 5.5 2.5 2.7 2.8 2.88.3 8.9 8.7 8.6 8.5 2.8 3.0 3.1 3.2

11.1 9.5 9.3 9.2 9.1 2.9 3.1 3.2 3.313.9 10.1 9.9 9.8 9.7 3.0 3.2 3.3 3.416.7 10.8 10.5 10.4 10.3 3.1 3.3 3.4 3.519.4 11.4 11.2 11.0 10.9 3.2 3.4 3.5 3.622.2 12.0 11.8 11.7 11.5 3.3 3.5 3.6 3.7

2TWA0030AD WITH TWE040CA4-B AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.5 2.4 2.4 2.4 1.8 1.9 2.0 2.0-16.7 3.1 3.0 3.0 3.0 1.8 2.0 2.0 2.1-13.9 3.8 3.7 3.6 3.6 1.9 2.0 2.1 2.2-11.1 4.4 4.3 4.3 4.2 2.0 2.1 2.2 2.3-8.3 5.1 5.0 4.9 4.9 2.1 2.2 2.3 2.4-5.6 5.2 5.1 5.0 5.0 2.1 2.3 2.3 2.4-2.8 5.3 5.2 5.2 5.1 2.2 2.3 2.4 2.50.0 5.5 5.4 5.3 5.2 2.2 2.3 2.4 2.52.8 5.6 5.5 5.4 5.4 2.2 2.4 2.5 2.55.6 5.7 5.6 5.6 5.5 2.3 2.4 2.5 2.68.3 9.0 8.8 8.7 8.6 2.5 2.7 2.8 2.9

11.1 9.6 9.4 9.3 9.2 2.6 2.8 2.9 3.013.9 10.3 10.0 9.9 9.8 2.7 2.9 3.0 3.116.7 10.9 10.7 10.6 10.5 2.8 3.0 3.1 3.219.4 11.6 11.3 11.2 11.1 2.8 3.0 3.2 3.322.2 12.2 12.0 11.8 11.7 2.9 3.1 3.2 3.3

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1698 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1486 1910HEATING CAP. X0.99 X1.01COMPR. KW X1.03 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1698 CMHHEATING CAP. (HIGH TEMP.) = 8.71 KWHEATING CAP. (LOW TEMP.) = 5.01 KWCOMPR. POWER (HIGH TEMP.) = 2378 WATTSCOMPR. POWER (LOW TEMP.) = 1796 WATTSHSPF (MIN DHR) = 6.91COEFF. OF PERF. (HIGH TEMP.) = 2.89COEFF. OF PERF. (LOW TEMP.) = 2.06OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 437 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1613 2123HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 8.79 KWHEATING CAP. (LOW TEMP.) = 4.97 KWCOMPR. POWER (HIGH TEMP.) = 2219 WATTSCOMPR. POWER (LOW TEMP.) = 1726 WATTSHSPF (MIN DHR) = 7.46COEFF. OF PERF. (HIGH TEMP.) = 3.23COEFF. OF PERF. (LOW TEMP.) = 2.24OUTDOOR FAN POWER = 181 WATTSINDOOR FAN POWER = 309 WATTSNOTE: RATED WITH 7.62 METERS OF 7/8 IN.

SUCTION AND 3/8 LIQUID LINE

2TWA0040AD WITH TWE040CA4-B AT 2208 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.7 2.7 2.6 2.6 1.9 2.0 2.1 2.2-16.7 3.5 3.5 3.4 3.4 2.0 2.2 2.2 2.3-13.9 4.3 4.3 4.2 4.2 2.2 2.3 2.3 2.4-11.1 5.2 5.1 5.0 5.0 2.3 2.4 2.5 2.5-8.3 6.0 5.9 5.8 5.8 2.4 2.5 2.6 2.7-5.6 6.3 6.2 6.1 6.1 2.5 2.6 2.7 2.8-2.8 6.6 6.4 6.4 6.3 2.5 2.7 2.8 2.80.0 6.9 6.7 6.7 6.6 2.6 2.8 2.8 2.92.8 7.1 7.0 6.9 6.9 2.7 2.9 2.9 3.05.6 7.4 7.3 7.2 7.2 2.8 2.9 3.0 3.18.3 10.9 10.7 10.6 10.5 3.0 3.2 3.3 3.4

11.1 11.7 11.5 11.4 11.3 3.1 3.3 3.4 3.513.9 12.6 12.3 12.2 12.1 3.2 3.4 3.5 3.616.7 13.4 13.2 13.0 12.9 3.3 3.5 3.6 3.819.4 14.2 13.9 13.8 13.7 3.4 3.7 3.8 3.922.2 15.0 14.8 14.6 14.5 3.5 3.8 3.9 4.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2208 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1953 2547HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2250 CMHHEATING CAP. (HIGH TEMP.) = 10.75 KWHEATING CAP. (LOW TEMP.) = 5.90 KWCOMPR. POWER (HIGH TEMP.) = 2601 WATTSCOMPR. POWER (LOW TEMP.) = 1918 WATTSHSPF (MIN DHR) = 7.91COEFF. OF PERF. (HIGH TEMP.) = 3.35COEFF. OF PERF. (LOW TEMP.) = 2.34OUTDOOR FAN POWER = 232 WATTSINDOOR FAN POWER = 360 WATTSNOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.

SUCTION AND 3/8 LIQUID LINE

Performance DataHeating Metric Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM27

Page 64: Trane Full Brochure

28 TWE5-PRC001-EN-08-17-03

2TWA0040AD WITH TWE050CA5-C AT 1600 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 9.83 9.68 9.60 9.53 2.11 2.23 2.29 2.352 12.7 12.5 12.4 12.3 2.21 2.33 2.40 2.467 15.6 15.3 15.2 15.1 2.30 2.44 2.50 2.57

12 18.5 18.1 18.0 17.8 2.40 2.54 2.61 2.6817 21.3 21.0 20.8 20.6 2.49 2.64 2.71 2.7922 22.3 21.9 21.7 21.5 2.56 2.72 2.79 2.8727 23.3 22.9 22.7 22.5 2.63 2.79 2.87 2.9532 24.3 23.9 23.7 23.4 2.70 2.87 2.95 3.0337 25.3 24.8 24.6 24.4 2.77 2.94 3.03 3.1142 26.3 25.8 25.6 25.3 2.84 3.02 3.11 3.1947 38.6 37.9 37.6 37.2 3.06 3.25 3.34 3.4452 41.5 40.7 40.3 40.0 3.15 3.35 3.45 3.5557 44.3 43.5 43.1 42.7 3.25 3.45 3.55 3.6662 47.2 46.4 45.9 45.5 3.34 3.55 3.66 3.7767 50.1 49.2 48.7 48.3 3.44 3.66 3.76 3.8772 53.0 52.0 51.5 51.1 3.53 3.76 3.87 3.98

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1600 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1400 1800HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1575 CFMHEATING CAP. (HIGH TEMP.) = 37841 BTUHHEATING CAP. (LOW TEMP.) = 20922 BTUHCOMPR. POWER (HIGH TEMP.) = 2486 WATTSCOMPR. POWER (LOW TEMP.) = 1875 WATTSHSPF (MIN DHR) = 7.85COEFF. OF PERF. (HIGH TEMP.) = 3.40COEFF. OF PERF. (LOW TEMP.) = 2.32OUTDOOR FAN POWER = 232 WATTSINDOOR FAN POWER = 529 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION

AND 3/8 LIQUID LINE

2TWA0050AD WITH TWE050CA5-C AT 1800 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 12.0 11.9 11.8 11.7 2.58 2.71 2.78 2.84-3 15.4 15.1 15.0 14.9 2.73 2.87 2.94 3.012 18.7 18.4 18.2 18.1 2.87 3.02 3.09 3.177 22.0 21.6 21.4 21.2 3.01 3.17 3.25 3.33

12 25.3 24.9 24.6 24.4 3.15 3.32 3.41 3.4917 28.6 28.1 27.9 27.6 3.30 3.48 3.57 3.6622 29.7 29.2 29.0 28.7 3.41 3.60 3.69 3.7927 30.9 30.3 30.1 29.8 3.52 3.72 3.82 3.9232 32.0 31.4 31.2 30.9 3.64 3.84 3.95 4.0537 33.1 32.6 32.3 32.0 3.75 3.97 4.07 4.1842 34.3 33.7 33.4 33.0 3.87 4.09 4.20 4.3147 48.5 47.6 47.2 46.7 4.15 4.39 4.51 4.6352 51.8 50.9 50.4 49.9 4.29 4.54 4.67 4.7957 55.1 54.1 53.6 53.1 4.43 4.70 4.83 4.9662 58.4 57.4 56.8 56.3 4.58 4.85 4.98 5.1267 61.8 60.6 60.0 59.5 4.72 5.00 5.14 5.2872 65.1 63.9 63.3 62.7 4.86 5.15 5.30 5.44

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1800 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1575 2025HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1750 CFMHEATING CAP. (HIGH TEMP.) = 47491 BTUHHEATING CAP. (LOW TEMP.) = 28015 BTUHCOMPR. POWER (HIGH TEMP.) = 3465 WATTSCOMPR. POWER (LOW TEMP.) = 2547 WATTSHSPF (MIN DHR) = 7.81COEFF. OF PERF. (HIGH TEMP.) = 3.17COEFF. OF PERF. (LOW TEMP.) = 2.36OUTDOOR FAN POWER = 189 WATTSINDOOR FAN POWER = 731 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION

AND 3/8 LIQUID LINE

2TWA0060AD WITH TWE050CA5-C AT 1800 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 20.1 20.0 19.9 19.9 4.64 4.96 5.12 5.28-3 23.3 23.2 23.2 23.1 4.68 5.00 5.16 5.322 26.5 26.4 26.4 26.3 4.72 5.04 5.20 5.377 29.8 29.7 29.6 29.6 4.75 5.08 5.24 5.41

12 33.0 32.9 32.8 32.8 4.79 5.12 5.29 5.4517 36.2 36.1 36.0 36.0 4.83 5.16 5.33 5.4922 36.9 36.8 36.7 36.7 4.75 5.08 5.24 5.4027 37.6 37.5 37.4 37.3 4.67 5.00 5.16 5.3232 38.3 38.2 38.1 38.0 4.60 4.91 5.07 5.2337 39.0 38.9 38.8 38.7 4.52 4.83 4.99 5.1442 39.7 39.5 39.5 39.4 4.45 4.75 4.90 5.0547 55.7 55.5 55.4 55.3 5.04 5.39 5.57 5.7552 58.9 58.7 58.6 58.5 5.08 5.43 5.61 5.7957 62.2 61.9 61.8 61.7 5.12 5.47 5.65 5.8362 65.4 65.2 65.0 64.9 5.15 5.51 5.69 5.8767 68.6 68.4 68.2 68.1 5.19 5.55 5.73 5.9172 71.9 71.6 71.5 71.3 5.23 5.59 5.77 5.96

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1800 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1575 2025HEATING CAP. X0.99 X1.01COMPR. KW X1.03 X0.97VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1750 CFMHEATING CAP. (HIGH TEMP.) = 55384 BTUHHEATING CAP. (LOW TEMP.) = 36031 BTUHCOMPR. POWER (HIGH TEMP.) = 4494 WATTSCOMPR. POWER (LOW TEMP.) = 4257 WATTSHSPF (MIN DHR) = 7.57COEFF. OF PERF. (HIGH TEMP.) = 2.99COEFF. OF PERF. (LOW TEMP.) = 2.02OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 731 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION

AND 3/8 LIQUID LINE

Performance DataHeating English Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM28

Page 65: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 29

2TWA0040AD WITH TWE050CA5-C AT 2717 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.9 2.8 2.8 2.8 2.1 2.2 2.3 2.3-16.7 3.7 3.7 3.6 3.6 2.2 2.3 2.4 2.5-13.9 4.6 4.5 4.5 4.4 2.3 2.4 2.5 2.6-11.1 5.4 5.3 5.3 5.2 2.4 2.5 2.6 2.7-8.3 6.2 6.2 6.1 6.0 2.5 2.6 2.7 2.8-5.6 6.5 6.4 6.4 6.3 2.6 2.7 2.8 2.9-2.8 6.8 6.7 6.7 6.6 2.6 2.8 2.9 3.00.0 7.1 7.0 6.9 6.9 2.7 2.9 3.0 3.02.8 7.4 7.3 7.2 7.1 2.8 2.9 3.0 3.15.6 7.7 7.6 7.5 7.4 2.8 3.0 3.1 3.28.3 11.3 11.1 11.0 10.9 3.1 3.3 3.3 3.4

11.1 12.2 11.9 11.8 11.7 3.2 3.3 3.5 3.513.9 13.0 12.7 12.6 12.5 3.3 3.5 3.5 3.716.7 13.8 13.6 13.4 13.3 3.3 3.5 3.7 3.819.4 14.7 14.4 14.3 14.2 3.4 3.7 3.8 3.922.2 15.5 15.2 15.1 15.0 3.5 3.8 3.9 4.0

2TWA0050AD WITH TWE050CA5-C AT 3057 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 3.5 3.5 3.5 3.4 2.6 2.7 2.8 2.8-19.4 4.5 4.4 4.4 4.4 2.7 2.9 2.9 3.0-16.7 5.5 5.4 5.3 5.3 2.9 3.0 3.1 3.2-13.9 6.4 6.3 6.3 6.2 3.0 3.2 3.3 3.3-11.1 7.4 7.3 7.2 7.1 3.2 3.3 3.4 3.5-8.3 8.4 8.2 8.2 8.1 3.3 3.5 3.6 3.7-5.6 8.7 8.6 8.5 8.4 3.4 3.6 3.7 3.8-2.8 9.1 8.9 8.8 8.7 3.5 3.7 3.8 3.90.0 9.4 9.2 9.1 9.1 3.6 3.8 4.0 4.12.8 9.7 9.6 9.5 9.4 3.8 4.0 4.1 4.25.6 10.0 9.9 9.8 9.7 3.9 4.1 4.2 4.38.3 14.2 13.9 13.8 13.7 4.2 4.4 4.5 4.6

11.1 15.2 14.9 14.8 14.6 4.3 4.5 4.7 4.813.9 16.1 15.9 15.7 15.6 4.4 4.7 4.8 5.016.7 17.1 16.8 16.6 16.5 4.6 4.8 5.0 5.119.4 18.1 17.8 17.6 17.4 4.7 5.0 5.1 5.322.2 19.1 18.7 18.5 18.4 4.9 5.2 5.3 5.4

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2717 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2378 3057HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2675 CMHHEATING CAP. (HIGH TEMP.) = 11.09 KWHEATING CAP. (LOW TEMP.) = 6.13 KWCOMPR. POWER (HIGH TEMP.) = 2486 WATTSCOMPR. POWER (LOW TEMP.) = 1875 WATTSHSPF (MIN DHR) = 7.85COEFF. OF PERF. (HIGH TEMP.) = 3.40COEFF. OF PERF. (LOW TEMP.) = 2.32OUTDOOR FAN POWER = 232 WATTSINDOOR FAN POWER = 529 WATTSNOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.

SUCTION AND 3/8 LIQUID LINE

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 3057 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2675 3439HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2972 CMHHEATING CAP. (HIGH TEMP.) = 13.91 KWHEATING CAP. (LOW TEMP.) = 8.21 KWCOMPR. POWER (HIGH TEMP.) = 3465 WATTSCOMPR. POWER (LOW TEMP.) = 2547 WATTSHSPF (MIN DHR) = 7.81COEFF. OF PERF. (HIGH TEMP.) = 3.17COEFF. OF PERF. (LOW TEMP.) = 2.36OUTDOOR FAN POWER = 189 WATTSINDOOR FAN POWER = 731 WATTSNOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.

SUCTION AND 3/8 LIQUID LINE

2TWA0060AD WITH TWE050CA5-C AT 3057 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 5.9 5.9 5.8 5.8 4.6 5.0 5.1 5.3-19.4 6.8 6.8 6.8 6.8 4.7 5.0 5.2 5.3-16.7 7.8 7.7 7.7 7.7 4.7 5.0 5.2 5.4-13.9 8.7 8.7 8.7 8.7 4.8 5.1 5.2 5.4-11.1 9.7 9.6 9.6 9.6 4.8 5.1 5.3 5.4-8.3 10.6 10.6 10.5 10.5 4.8 5.2 5.3 5.5-5.6 10.8 10.8 10.8 10.8 4.8 5.1 5.2 5.4-2.8 11.0 11.0 11.0 10.9 4.7 5.0 5.2 5.30.0 11.2 11.2 11.2 11.1 4.6 4.9 5.1 5.22.8 11.4 11.4 11.4 11.3 4.5 4.8 5.0 5.15.6 11.6 11.6 11.6 11.5 4.4 4.8 4.9 5.18.3 16.3 16.3 16.2 16.2 5.0 5.4 5.6 5.8

11.1 17.3 17.2 17.2 17.1 5.1 5.4 5.6 5.813.9 18.2 18.1 18.1 18.1 5.1 5.5 5.7 5.816.7 19.2 19.1 19.0 19.0 5.2 5.5 5.7 5.919.4 20.1 20.0 20.0 20.0 5.2 5.6 5.7 5.922.2 21.1 21.0 20.9 20.9 5.2 5.6 5.8 6.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 3057 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2675 3439HEATING CAP. X0.99 X1.01COMPR. KW X1.03 X0.97VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/ 6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2972 CMHHEATING CAP. (HIGH TEMP.) = 16.23 KWHEATING CAP. (LOW TEMP.) = 10.56 KWCOMPR. POWER (HIGH TEMP.) = 4494 WATTSCOMPR. POWER (LOW TEMP.) = 4257 WATTSHSPF (MIN DHR) = 7.57COEFF. OF PERF. (HIGH TEMP.) = 2.99COEFF. OF PERF. (LOW TEMP.) = 2.02OUTDOOR FAN POWER = 179 WATTSINDOOR FAN POWER = 731 WATTSNOTE: RATED WITH 7.62 METERS OF 1-1/8 IN.

SUCTION AND 3/8 LIQUID LINE

Performance DataHeating Metric Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM29

Page 66: Trane Full Brochure

30 TWE5-PRC001-EN-08-17-03

PerformanceData

Evaporator Fan PerformanceBlower Performance — TWE030CA40B — Wet Coil

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)

220 VOLTS 220 VOLTSCFM CMH Hl MED LO Hl MED LO600 1018.8 0.72 (179.4) 0.71 (176.9)650 1103.7 0.62 (154.4) 0.61 (152.0)700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6)750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1)800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7)850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3)900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7)

1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3)1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0)1100 1867.8 0.31 (77.2) 0.31 (77.2)1150 1952.7 0.20 (49.8) 0.22 (54.8)1200 2037.6 0.08 (19.9) 0.10 (24.9)

NOTES:Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance — TWE040CA40C — Wet CoilEXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)

UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)220 VOLTS 220 VOLTS

CFM CMH Hl MED LO Hl MED LO700 1188.6 0.58 (144.5)750 1273.5 0.61 (152.0) 0.55 (137.0)800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5)850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5)900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1)

1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6)1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2)1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7)1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8)1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3)1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9)1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5)1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8)1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9)1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9)1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM30

Page 67: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 31

PerformanceData

Blower Performance — TWE050CA50D — Wet CoilEXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)

UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)220 VOLTS 220 VOLTS

CFM CMH Hl MED LO Hl MED LO900 1528.2950 1613.1 0.63 (156.9)1000 1698.0 0.61 (152.0) 0.62 (154.4)1050 1782.9 0.58 (144.5) 0.60 (149.5)1100 1867.8 0.54 (134.5) 0.57 (142.0)1150 1952.7 0.50 (124.6) 0.53 (132.0)1200 2037.6 0.45 (112.1) 0.49 (122.1)1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6)1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7)1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7)1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3)1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8)1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4)1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0)1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6)1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2)1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7)1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8)1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4)1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4)1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5)1950 3311.1 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

Evaporator Fan Performance

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM31

Page 68: Trane Full Brochure

32 TWE5-PRC001-EN-08-17-03

PerformanceData

Air Pressure Drop (Inches) - Electric Heaters

Pressure Drop For Electric Heaters In Air Handler Models

NUMBER OF RACKS1 2 3 4 5

AIRFLOW AIRFLOW AIR PRESSURE DROPCFM CMH IN. W.G. (PASCALS)600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5)

1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9)1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9)1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4)1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4)1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4)1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4)1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3)1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3)1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3)1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3)2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)

NOTES:1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.2. Heater model numbers may have additional suffix digits.

HEATER RACKSHEATER NO. OF

MODEL NO. RACKSBAY96X1405 1BAY96X1406 2BAY96X1408 2BAY96X1410 2BAY96X1411 3BAY96X1415 3BAY96X1419 4BAY96X1421 4BAY96X1426 5BAY96X3411 3BAY96X3415 3

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM32

Page 69: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 33

Minimum Airflow (CFM)Heater Matrix

A Heater Matrix for All TWEMINIMUM HEATING AIRFLOW CFM – HEATER MATRIX

AIRHANDLER HEATER MODEL NUMBER BAYHTR—

MODELNUMBER

1405 000BRKPDC

4.80kw

1408 000BRKPDC

7.68kw

1410 000BRKPDC

3410 0009.60kw

1415 BRK15.36kw

3415 00015.36kw

1419 BRK19.20kw

1425 BRK24.96kw

NUMBER OFHEATER RACKS 1 2 2 2 2 4 5

NUMBER OFCIRCUITS 1 1 1 2 1 2 3

TWE030C L/L L/L L/L L/L L/L — —

TWE040C L/L L/L L/L L/L L/L L/H L/H

TWE050C L/L L/L L/L L/L L/L L/H L/H

(Example: L=Low, M=Medium, H=High Speed)Cooling/Heat Pump Air FlowAS = Heater application is affected based on whether the outdoor unit is a heat pump or cooling unit.PS = Minimum speed tap varies based on air handler installation position.

000 = Pigtails, BRK = Contains circuit breakers, PDC = Contains Pull DisconnectRBR = Contains recessed circuit breaker (for 14" deep TVF018-024 Models only)RPD = contains recessed pull disconnect (for 14" deep TV0F18-024 Models only)* For upflow position only minimum setting is 1200

CAUTION: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local electrical codes.

THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM33

Page 70: Trane Full Brochure

34 TWE5-PRC001-EN-08-17-03

ElectricalData

2TWB0012-0536AA System Wiring Diagram

Legend

Symbols

NOTES:

1. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE.

2. IF ODT-A IS NOT USED, ADD JUMPER BETWEEN W1 & W2 AT AIR HANDLER.

3. LOW VOLTAGE (24 V.) FIELD WIRING MUST BE 18 AWG MIN.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM34

Page 71: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 35

ElectricalData

2TWA0030-060AD System Wiring Diagram

Legend

Symbols

NOTES:

1. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE.

2. IF ODT-A IS NOT USED, ADD JUMPER BETWEEN W1 & W2 AT AIR HANDLER.

3. LOW VOLTAGE (24 V.) FIELD WIRING MUST BE 18 AWG MIN.

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM35

Page 72: Trane Full Brochure

36 TWE5-PRC001-EN-08-17-03

ElectricalData

TWE030-050C System Wiring Diagram

NOTES:

1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION

2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEEDCHANGE FOR HEATING/COOLING OPERATION IS DESIRED.

3. A 220V HIGH VOLTAGE CONTROL IN TTB5-C NEEDS TO BE CHANGEDWITH 24V LOW VOLTAGE CONTROL KIT (ACYLVCR006A) WHEN MATCHEDWITH TWE-C AIR HANDLING UNITS.

Legend

Symbols

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM36

Page 73: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 37

Dimensions

TWE030-050C Outline DrawingALL DIMENSIONS ARE IN INCHES (MM)

MINIMUM UNIT CLEARANCE SALETO COMBUSTIBLE SERVICE CLEARANCE

MATERIAL (REQUIRED) (RECOMMENDED)SIDES 0 (0) 2 (50.8)FRONT 0 (0) 21 (533.4)BACK 0 (0) 0 (0)

INLET DUCT 0 (0) 1 (25.4)OUTLET DUCT 1 (25.4)

MODEL NO. A B C D E FTWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV

(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV

(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV

(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)

FLOWCONTROL

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM37

Page 74: Trane Full Brochure

38 TWE5-PRC001-EN-08-17-03

Dimensions

2TWB0012-036AA Outline DrawingAll dimensions are in inches (mm)

From Dwg. 21D153509 Rev. 1

MODELS BASE FIG. A B C D E F G H J K L M

2TWB0012AA 2 1 651( 25-5/8)

724(28-1/2)

651( 25-5/8) 5/8 1/4 127

(5)57

(2-1/4)181

(7-1/8)44

(1-3/4)457(18) 7/8-14 UNF- 2A 7/16-20 UNF- 2A

2TWB0018AA 2 1 651( 25-5/8)

724(28-1/2)

651( 25-5/8) 3/4 5/16 127

(5)57

(2-1/4)181

(7-1/8)44

(1-3/4)457(18) 1 1/16-14 UNF- 2A 1/2-20 UNF- 2A

2TWB0024AA 2 1 730(28-3/4)

724(28-1/2)

651( 25-5/8) 3/4 5/16 137

(5-3/4)65

(2-5/8)210

(8-1/4)57

(2-1/4)457(18) 1 1/16-14 UNF- 2A 1/2-20 UNF- 2A

2TWB0030AA 2 1 730(28-3/4)

724(28-1/2)

651( 25-5/8) 3/4 3/8 137

(5-3/4)65

(2-5/8)210

(8-1/4)57

(2-1/4)457(18) 1 1/16-14 UNF- 2A 1/2-20 UNF- 2A

2TWB0036AA 3 1 832(32-3/4)

829(32-5/8)

756(29-3/4) 3/4 3/8 137

(5-3/4)86

(3-3/8)210

(8-1/4)79

(3-1/8)508(20) 1 1/16-14 UNF- 2A 1/2-20 UNF- 2A

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM38

Page 75: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 39

Dimensions

2TWA0030-060AD Outline DrawingAll dimensions are in inches (mm)

MODELS BASE FIG. A B C D E F G H J K

2TWA0030AD 2 2 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 7/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TWA0040AD 3 2 832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 137 (5-3/8) 86 (3-3/8) 210 (8-1/4) 79 (3-1/8) 508 (20)

2TWA0050AD 4 1 841 (33-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

2TWA0060AD 4 1 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

From Dwg. 21D153074 Rev. 6

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM39

Page 76: Trane Full Brochure

40 TWE5-PRC001-EN-08-17-03

Convertibility

TWE030 Through 050 ConvertibilitySix (6) Way Convertibility

One Unit - 4 Applications Easy Conversion to Opposite Side Access

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM40

Page 77: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 41

MechanicalSpecification Options

GeneralThe 2TWB0/2TWA0 is fully charged fromthe factory for up to 15 feet of piping. Thisunit is designed to operate at outdoorambient temperatures as high as 115°F.Cooling capacities are matched with awide selection of air handlers. Exterior isdesigned for outdoor application.

CasingUnit casing is constructed of heavygauge, G90 galvanized steel and paintedwith a weather-resistant powder paint onall louvers, panels, prepaint on all otherpanels. Corrosion and weatherproofCMBP-G30 DuraTuff™ base.

Refrigerant ControlsRefrigeration system controls includecondenser fan, compressor contactorand high pressure switch. High and lowpressure controls are inherent to thecompressor. A factory installed liquid linedrier is standard.

CompressorThe Climatuff® compressor featuresinternal over temperature and pressureprotection and total dipped hermeticmotor. Other features include: roto locksuction and discharge refrigerantconnections, centrifugal oil pump and lowvibration and noise.

Condenser CoilThe outdoor coil provides low airflowresistance and efficient heat transfer. Thecoil is protected on all four sides bylouvered panels and has a 5 yearlimited warranty.

Low Ambient CoolingAs manufactured, this unit has a coolingcapability to 55°F. The addition of anevaporator defrost control permitsoperation to 40° F. The addition of anevaporator defrost control with TXVpermits low ambient cooling to 30° F.

AccessoriesThermostats — Cooling only andheat/cooling (manual and automaticchangeover). Sub-base to match thermo-stat and locking thermostat cover.

Evaporator Defrost Control — See LowAmbient Cooling.

Condensing Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM41

Page 78: Trane Full Brochure

42 TWE5-PRC001-EN-08-17-03

MechanicalSpecification Options

GeneralBlower coil units shall be completelyfactory assembled including coil, conden-sate drain pan, fan, motor, filters andcontrols in an insulated casing that canbe applied in horizontal or verticalconfiguration.

This new line of TWE-C air handlersprovides exclusive compact size com-bined with simple four-way convertibilityin three sizes. The unit ships in the righthand horizontal configuration andconverts to vertical upflow just bystanding the unit on end. No toolsrequired. Simple coil rotation providesdownflow and horizontal left applications.

The four-way convertibility provides youinventory benefits and service/installationflexibility. The simple conversion providesopposite side access for installationand service.

CasingUnits shall have rugged sheet metal andsteel frame construction and shall bepainted with an enamel finish. Casingshall be insulated and knockouts shall beprovided for electrical power andcontrol wiring.

Refrigerant CircuitsThe TWE units shall have a singlerefrigerant circuit. TWE03-040C refriger-ant circuit shall be controlled by a flowcontrol check valve (FCCV). TheTWE050C refrigerant circuit shall becontrolled by a factory-installed thermalexpansion valve.

CoilAluminum fin surface shall be mechani-cally bonded to 3/8-inch OD coppertubing. Coils shall be factory pressureand leak tested.

FanForward curved, dynamically andstatically balanced with three-speeddirect drive shall be standard, fan motorbearing shall be permanently lubricated.

ControlsFan contactor, and plug-in module foraccessory electric heat control shall beincluded. TWE models shall also includecheck valves.

FiltersFilters shall be included as standard.

AccessoriesElectric Heaters — Shall be available ina wide range of capacities and voltageswith various staging options and plug incontrol wiring. Heaters shall fit insideinternal compartment.

Air Handling Units

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM42

Page 79: Trane Full Brochure

TWE5-PRC001-EN-08-17-03 43

Notes

TWE5_PRC001_EN_081703.PMD 9/15/2003, 3:07 PM43

Page 80: Trane Full Brochure

Trane has a policy of continuous product and product data improvement and it reserves the right to changedesign and specifications without notice.

TraneA business ofAmerican Standard Companieswww.trane.com

File Number TWE5-PRC001-EN-08-17-03

Supersedes TWE5-PRC001-EN-10-15-99

Stocking Location — P.I.