Tracer AdaptiView™ Control for EarthWise™ CenTraVac™ Chillers November 2010 CTV-PRB009-EN Engineering Bulletin

Upload: nguyenphuc

Post on 10-May-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

Tracer AdaptiView™ Control

for EarthWise™ CenTraVac™ Chillers

November 2010 CTV-PRB009-EN

Engineering Bulletin

Page 2: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

Copyright

© 2010 Trane All rights reserved

This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

Trane and its logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.

Warnings, Cautions, and Notices

Warnings, cautions, and notices are provided in appropriate places throughout this document:

�WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

�CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE: Indicates a situation that could result in equipment or property-damage-only accidents.

Page 3: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

Table of Contents

CTV-PRB009-EN, 03 Nov 2010 3

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Features Supported by Tracer AdaptiView Control . . . . . . . . . . . . . . . . . . . . . . . . . 5

Operator Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Increased Serviceability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

AdaptiView™ Control and the AdaptiView Display . . . . . . . . . . . . . . . . . . . . . 8

AdaptiView Display Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

The Tracer™ TU Service Tool (Tracer TU for Chillers) . . . . . . . . . . . . . . . . . . 21Tracer TU Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Laptop Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Accuracy of Analog to Digital Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Control and Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Hardwire Control Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Control Options (EPRO and WFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Total Building Automation by Trane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Chiller Plant Control by Trane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Chiller by Trane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Field Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Heat Exchanger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Motor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

EarthWise Purge Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Phase Voltage Sensors – 3-Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Chilled-Water Reset (Based on Returned Chilled Water Temperature) . . . . 31

Hot-Water Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Ice-Making Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Optional Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Heat Recovery/Auxiliary Condenser (ACOS) . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Hot-Gas Bypass (HGBP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Chilled-Water Reset (CWR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Gas-Powered Chiller (GENR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Free Cooling (FRCL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Extended Operation (EXOP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Base-Loading Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Ice-Making Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Page 4: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

4 CTV-PRB009-EN, 03 Nov 2010

Hot-Water Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Refrigerant Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Enhanced Flow Management Package (WFC) . . . . . . . . . . . . . . . . . . . . . . . . . 35Enhanced Flow Management Package . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Variable Flow Stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Adaptive Frequency Drive (AFD) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Enhanced Protection (EPRO) Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Standard Protections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Monitored Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Starter Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Adaptive Frequency Drive Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Main Processor Defective Sensor or LLID Diagnostics . . . . . . . . . . . . . . . . . 47

Main Processor Purge Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Main Processor Unit-Level Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Main Processor Communication Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . 50

Report Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Page 5: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 5

Introduction

This bulletin provides information about Tracer AdaptiView™control as applied to CVHE, CVHF, CVHG, CDHF and CDHG chillers.

You can also use this bulletin as a reference for standard and optional features and to obtain specific data point communication information.

By designing a fourth-generation unit controller with software and smart sensors (rather than hardware modules) at its core, Trane’s controls engineers have provided AdaptiView control-equipped chillers with improved communication capabilities, accuracy, serviceability, and adaptability.

Features Supported by Tracer AdaptiView Control

With AdaptiView control, system designers can take advantage of energy saving strategies, which allow the CenTraVac™ chiller to be used with unsurpassed efficiency. AdaptiView control provides and supports the following key features:

Intuitive user interface with a graphical color touch-screen

The AdaptiView display is a touch-sensitive, 12-inch diagonal color liquid crystal display (LCD) that uses color graphics and animation to ensure ease of use. The touch-sensitive interface allows you to view the chiller graphically and receive a status indication accompanied by subsubsystem animations. (See “AdaptiView™ Control and the AdaptiView Display,” p. 8.)

You can navigate easily between the primary chiller subsystems including the: compressor, evaporator, condenser, motor, and purge. For each subsystem, you can view status and detailed operating parameters. In addition, alarms, reports, trending, and settings can all be accessed quickly from the main screen. AdaptiView control supports 24 languages with English as the default.

Feedforward adaptive control

Feedforward is an open-loop, predictive control strategy designed to anticipate and compensate for load changes. It uses the Evaporator Entering Water Temperature and, optionally, the Evaporator Flow Rate as indicators of load change. This allows the controller to respond faster to system changes and maintain stable leaving water temperatures (± 0.5 °F).

Soft loading

AdaptiView control uses soft loading except during manual operation. Large adjustments due to load or setpoint changes are made gradually, preventing the compressor from cycling unnecessarily. It does this by internally filtering the setpoints to avoid reaching the differential-to-stop or the current limit too quickly. Soft loading applies to the Leaving Chilled Water Temperature and Current Limit setpoints. These setpoints can be adjusted to facilitate faster loading times.

Adaptive Control™

Whenever AdaptiView control senses that it can no longer meet its primary objective (maintaining Leaving Chilled Water Temperature) without triggering a protective shutdown, it focuses on the most critical secondary objective. When the secondary objective is no longer critical, the controller reverts to its primary objective. As an example, if the tower temperature was to rise above normal for an extended period of time, the control would sense this and send a caution signal. It might even hold or unload the chiller to keep it on line until the system problem is resolved.

Fast Restarts - Quick Loadup

AdaptiView control allows the CenTraVac chiller to restart within 93 seconds—a standard product capability. If the chiller shuts down on a nonlatching diagnostic, the diagnostic has 30–60 seconds to clear itself and initiate a fast restart. This includes momentary power losses. In addition, when

Page 6: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

6 CTV-PRB009-EN, 03 Nov 2010

Features Supported by Tracer AdaptiView Control

the chiller is started, the load up time can be as fast as three minutes. This restart time can be cut in half by using a UPS power source to supply control power. (See Restart Time with AdaptiView (UC800) in CTV-SVN018-EN.)

Enhanced Flow Management Package and variable-primary flow (VPF) with an

AFD

Handling evaporator flow rate changes up to 30% per minute with or without AFDs is another standard capability of AdaptiView chillers. The Enhanced Flow Management Package is an optional control feature for CenTraVac chillers. The Enhanced Flow Management Package allows the chiller to accommodate higher than typical flow rate changes (up to 50% per minute) while providing stable chilled water temperatures, even in combination with an Adaptive Frequency Drive™ (AFD). (See “Enhanced Flow Management Package,” p. 35 for a more detailed description.)

Chilled-water systems that vary the water flow through chiller evaporators have caught the attention of engineers, contractors, building owners, and operators. Varying the water flow reduces the energy consumed by pumps, while requiring no extra energy for the chiller. This strategy can be a significant source of energy savings, depending on the application.

Using the optional Enhanced Flow Management Package, AdaptiView control reliably accommodates higher variable evaporator water flow changes and virtually eliminates its effect on the chilled-water temperature.

Previous controllers could not accommodate variable water flow in combination with variable-speed drives. Water-flow compensation reacts so quickly that this energy- saving combination is now possible.

Adaptive Frequency Drive (AFD)

For AFD equipped chillers, the combination of speed control and Inlet Guide Vane Position is now optimized mathematically and controlled simultaneously. The increased performance of the microprocessor allows the chiller to operate longer at higher efficiency and with greater stability.

Revolutionary EarthWise™Purge

AdaptiView control equipped chillers feature a high-efficiency purge, which includes an auto-regenerating carbon canister to return reclaimed refrigerant back to the chiller automatically. The EarthWise Purge is more aggressive in auto-adaptive mode than its predecessor. Adaptive mode uses historical purge data to determine when to purge and for how long, keeping the chiller at peak operating efficiency. Finally, today’s purge operates as a leak detector. Any significant purge run time can warn a technician of a potential leak.

Chiller tower optimization

Tracer™SC system controller chiller-tower optimization extends Adaptive Control to the rest of the chiller plant. Chiller tower optimization is a patented control algorithm for managing the chiller and cooling-tower subsystem.

It considers the chiller load and real-time ambient conditions, then optimizes the tower setpoint temperature to maximize the efficiency of the subsystem.

34°F leaving water temperature

Another benefit of Feedforward Adaptive Control is the ability to operate the CenTraVac chiller at low leaving evaporator water temperatures without the use of glycol.

Colder water is generally used in wide delta-T systems, reducing the pumping energy required and making it less expensive to deliver cooling capacity over long distances. For this reason, 34°F leaving water temperatures are frequently used in district cooling applications, but can also be used in comfort cooling applications.

Consult CenTraVac Product Management when making chiller two- or three-pass selections using 34°F to 36°F leaving- water temperatures. Adherence to standard installation procedures (for

Page 7: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 7

Features Supported by Tracer AdaptiView Control

example, strainer upstream of waterbox, waterbox temperature sensor) is important when implementing low leaving-water temperatures.

Cold condenser water

The CenTraVac has a large operating map. For the past two decades the ability to operate at cold condenser water temperatures (for example, at 55 °F) has been documented and demonstrated. (See Condenser Water Temperature Control for CenTraVac™Centrifugal Chiller Systems with Tracer AdaptiView Controls (CTV-PRB006-EN) for more details on Trane’s condenser water temperature capabilities.) This document covers the required minium pressure differential between the evaporator and condenser. It also discusses various head pressure control options. So, the question that you must answer is, “What is the optimal tower temperature given the application and location?” Trane suggests that an optimization is best based on the combined minimum energy consumption between the chiller and tower. (See Chiller System Design and Control (SYS-ADM001-EN) for more information on condenser water temperature controler optimization.)

Chiller communications options

A variety of control interface options are available to communicate CenTraVac data to other BAS systems. Trane offers options that communicate through BACnet and MODBUS protocols directly from the chiller. LonTalk® options are available as well. Trane also offers full building or chiller plant control capabilities coordinated and managed by Tracer SC. See “Communication Options,” p. 26 for some system configurations.

Page 8: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

8 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Tracer AdaptiView™control panel, which includes the UC800, supports two operator/technician interfaces, which are described in this section.

• The AdaptiView display

• The Tracer TU service tool

Increased Serviceability

The previous Trane chiller controllers (Tracer™ CH530 with the DynaView™) included a smaller, character-based, two-color user interface that presented the chiller data necessary for daily tasks. Service or maintenance tasks were performed using the TechView™ service tool.

The AdaptiView control panel adds a level of sophistication that improves service technician effectiveness and minimizes chiller downtime. AdaptiView control provides a user interface (the AdaptiView display) and a main processor (the UC800) that protects the chiller and optimizes chiller efficiency. The Tracer TU service tool succeeds TechView for performing service and maintenance tasks.

Tracer TU serves as the interface to all CenTraVac chillers, and customizes itself based on the properties of the chiller with which it is communicating. Therefore, service technicians have to familiarize themselves with only one service tool interface.

The panel bus is easy to troubleshoot using LED verification of sensors. Only the defective device is replaced. (Captive screws ensure that the appropriate mounting hardware is available.)

AdaptiView™ Control and the AdaptiView Display

AdaptiView control is the unit-mounted controller and serves as the microprocessor-based chiller control system that provides complete monitoring and efficiency optimization for the Water-Cooled CenTraVac Chiller. It is a factory-mounted package including a full complement of controls to safely and efficiently operate the CenTraVac chiller, including oil management, purge operation, an interface to the starter or AFD, and comprehensive motor protection including three-phase solid state motor overload.

Features and Capabilities

Some of the features and capabilites available through the AdaptiView display interface include

• Auto/stop commands

• Status (all subsystems)

• Setpoint adjustment (daily user points)

• Ten (10) historic and any active diagnostics

• Graphical trending (up to 16 graphs and 10 variables per graph)

• Mode overrrides

• Reports including ASHRAE

• Operating settings - security password protection

• BACnet and MODBUS direct communications

AdaptiView control receives information from, and communicates commands to the other devices on the chiller’s communication link. It performs the leaving chilled water temperature and limit control algorithms, arbitrating capacity against any operating limit within which the chiller may be operating.

Page 9: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 9

Operator Interfaces

User-selected languages and units

The AdaptiView display contains 24 language options including non-Western languages, such as Arabic, Chinese, Hebrew, Japanese, Korean, and Thai. You can select the appropriate language on the Language screen and click Save to change the language displayed on the screens.

You can select either I-P or SI units of measure as well as presure units on the Display Preferences screen.

Figure 1. A CenTraVac chiller with the AdaptiView display

The AdaptiView display screens provide essential information

about chiller components and overall chiller performance.

Page 10: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

10 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

The Versatile AdaptiView Display Arm

The AdaptiView display is mounted on a flexible “arm” that allows extensive height and viewing angel variations to make your work more comfortable and convenient.

The Tracer AdaptiView display is mounted on the chiller control panel. It is attached to the chiller by an arm that can extend 11 inches. Five pivot points enable full articulation as described in the following specifications and in the illustration:

• Two horizontal pivots points 90º right or left (180º total)

• Two vertical pivots points: 90º degrees up or down (180º total)

• Rotation: 135º clockwise and 135º counterclockwise (270º total)

Figure 2. AdaptiView display mounted on CenTraVac with flexible arm

Figure 3. Pivot Points on the flexible AdaptiView display arm

Page 11: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 11

Operator Interfaces

AdaptiView Display Screens

The AdaptiView display screens provide at a glance information about all main chiller components including the compressor, evaporator, condenser, motor, and purge.

The main or “home” screen

The home screen provides the most frequently needed chiller status information on “touch targets” (the white rectangular areas) for each chiller component. Touching any touch target displays a screen containing more chiller status information related to each component.

Legend

Figure 4. AdaptiView display main or home screen

1 Activates chiller shutdown process.

2 Activates chiller startup process.

3 Displays value of Evap Leaving Water Temp and setpoint source

4 Displays chiller status (Running or Stopped)

5 “Touch targets” linked to component screens and more detailed information.

6 Animated graphics indicate current water flow within the condenser and evaporator

7 Link to Diagnostics and alarm information

8 Link to pre-established and custom reports

9 Link to graphing tool (trends)

10 Link to operator settings

11 Image of chiller unit with animated components.

1

5

6

2

5 5

7 8 9

11

34

10

Page 12: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

12 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Main display area/screen saver

After 30 minutes of inactivity, the screen dims and the screen saver (Figure 5) appears in the main display area. The screen saver also appears if you touch the animated graphic on the home screen. Alternately, if you touch the screen saver, the home screen appears. If the chiller is operating, the screen image includes cut away animations of the compressor and condenser.

Legend

Figure 5. AdaptiView display inactivity screen/screen saver

1 Activates chiller shutdown process.

2 Activates chiller startup process.

3 Highlights current setpoint source.

4 Displays chiller status (Running or Stopped)

5 Link to Diagnostics and alarm information (Red indicates the presence of alarms needing attention.)

6 Link to pre-established and custom reports

7 Link to graphing tool (trends)

8 Link to operator settings

9 Image of chiller unit with animated components.

123

75 6 8

4

9

Page 13: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 13

Operator Interfaces

Compressor screen

The Compressor screen includes several values indicative of compressor status.

Legend

Figure 6. AdaptiView display Compressor screen

1 Activates chiller shutdown process.

2 Activates chiller startup process.

3 Highlights current setpoint source.

4 Displays chiller status (Running or Stopped).

5 Back and Home buttons.

6 Link to graphing tool (trends).

7 Animated image of the compressor.

8 Current state of the compressor.

9 Accumulated compressor running time.

10 Page down for additional data.

123

4

6

8

9

10

4

55

7

Page 14: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

14 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Evaporator screen

The Evaporator screen includes several values indicative of evaporator status.

Legend

Figure 7. AdaptiView display Evaporator screen

1 Links to other component screens.

2 Displays value of Evap Leaving Water Temp and setpoint source

3 Back and Home buttons.

4 Link to graphing tool (trends).

5 Animated image of the evaporator.

6 If the Enhanced Flow Management Package is added as an option, data appears here for flow.

2

13

6

4

5

Page 15: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 15

Operator Interfaces

Condenser screen

The Condenser screen includes several values indicative of condenser status.

Legend

Figure 8. AdaptiView display Condenser screen

1 Links to other component screens.

2 Highlighted setpoint source.

3 Back and Home buttons.

4 Link to graphing tool (trends).

5 Animated image of the condenser.

1

2

3

4

5

Page 16: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

16 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Motor screen

The Motor screen includes several values indicative of motor status

Legend

Figure 9. AdaptiView display Motor screen

1 Links to other component screens.

2 Highlighted setpoint source.

3 Back and Home buttons.

4 Link to graphing tool (trends).

5 Animated image of the motor.

6 Page down for additional data.

1

2

3

5

4

6

Page 17: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 17

Operator Interfaces

Purge screen

The Purge screen includes several values indicative of purge status

Legend

Figure 10. AdaptiView display Purge screen

1 Links to other component screens.

2 Highlighted setpoint source.

3 Back and Home buttons.

4 Link to graphing tool (trends).

5 Animated image of the Purge unit.

6 Page down for additional data.

1

2

3

6

4

5

Page 18: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

18 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Sample graph

You can use the Tracer AdaptiView display to view a variety of default data graphs, such as Chiller Overview (two versions), Approach Temperature, Evaporator, Motor, and so on. In addition, you can create up to six custom data graphs with up to eight data points per graph. The data sample rate is 30 seconds, and the data storage duration is 48 hours. (These rates cannot be adjusted.) You can also include a second Y axis on your graphs.

Legend

Figure 11. AdaptiView display sample graph

1 Color legend for Y axis.

2 Highlighted setpoint source.

3 Back and Home buttons.

4 Link to custom graphing screen.

5 Zoom control to magnify or reduce graph size.

6 Add a second Y (vertical) axis to your graphs.

2

1

3 4

6 5

Page 19: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 19

Operator Interfaces

Alarms screen

The Alarms screens displays both active and historic alarms.

Legend

Figure 12. AdaptiView display Alarms screen

1 Displays total number of active and historic alarms.

2 You can sort active and historic alarms by column (for example, by severity or date/time).

3 Click selection buttons to display only active alarms, only historic alarms, or both.

4 Page indicator and navigation buttons

1

2

3

4

Page 20: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

20 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Report screens

The standard report screens display key data, such as the Log Sheet report shown in Figure 13.

Legend

See “Report Contents,” p. 53 for lists of the contents of available reports. For more detailed information about these reports, see the Tracer AdaptiView™Display for Water-Cooled CenTraVac™ Chillers Operations Guide (CTV-SVU01C-EN).

Figure 13. AdaptiView display Alarms screen

1 Report title.

2 Back and Home buttons.

3 Page down for additional data.

3

2 1

Page 21: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 21

Operator Interfaces

The Tracer™ TU Service Tool (Tracer TU for Chillers)

Tracer TU is a PC application that provides the necessary setup, configuration, and monitoring functions used with AdaptiView™control to service Trane CenTraVac™ chillers (models CVHE, CVHF, and CVHG), CenTraVac Duplex chillers (models CDHF or CDHG), and AdaptiView Panel Upgrades (CVRE).

Tracer TU Capabilities

You can use Tracer TU to perform tasks such as:

• Connecting to and reading the settings from a Tracer AdaptiView controller (UC800)

• Monitoring chiller and controller status

• Making changes to chiller configuration settings

• Saving chiller configurations to your hard drive and then reusing configurations on multiple chiller units

• Saving changed setpoints and configurations to the controller

• Overriding chiller outputs

• Checking for and responding to alarms (Displays up to 100 active and historic alarms.)

• Data logging and graphing controller-generated datapoints

• Managing Low Level Intelligent Device (LLID) binding, sequencing, replacement, and removal

• Generating reports

• Backing up and restoring configuration files and settings

You connect your laptop directly to the UC800 with a Type A/B USB cable and then start a Tracer TU session to view chiller status, configuration settings, diagnostics, LLID operation, and network health. For example, the Unit Summary screen shown in Figure 14 provides at-a-glance information about chiller operation and current status.

Figure 14. The Tracer TU Unit Summary screen

Page 22: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

22 CTV-PRB009-EN, 03 Nov 2010

Operator Interfaces

Laptop Requirements

Your laptop must meet the following hardware and software requirements to successfully run Tracer TU:

Note: Tracer TU is designed and validated for this minimum laptop configuration. Any variation from this configuration may have different results. Therefore, support for Tracer TU is limited to only those laptops with the configuration previously specified.

For more information about the Tracer TU service tool, see the Tracer TU Service Tool Getting Started Guide (TTU-SVN01x-EN).

• 1 GB RAM (minimum) • Ethernet 10/100 LAN card

• 1024 x 768 screen resolution • An available USB 2.0 port

• CD-ROM drive • Windows XP Professional operating system with Service Pack 2

Page 23: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 23

Architecture

Figure 15 presents a graphical overview of general system architecture with the AdaptiView control complex, which includes the UC800, the AdaptiView display, the control panel, and the communications bus.

Tracer AdaptiView control software-based architecture easily accommodates adding or changing features, function, or I/O to the platform. The devices are smaller and easier to replace. In addition, you can use choose from the communication options shown in Figure 17, p. 27 through Figure 22, p. 29.

Figure 15. Chiller System Architecture

Control Enclosure (Chiller Mounted)

Tracer SC

AdaptiView Display

Laptop Running Tracer TU

Tracer ES

Starter Purge TemperatureSensor

PressureSensor

Inlet Guide Vane Actuator

UC800 IMC Bus

Page 24: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

24 CTV-PRB009-EN, 03 Nov 2010

Accuracy of Analog to Digital Conversions

Each device (for example, a sensor) is connected to its own microprocessor, which converts the sensor signal from analog to digital. The calibration of the conversion is specific to the type of sensor, providing better temperature accuracy and eliminating the need for matched sensor pairs.

Distributing logic to the sensors allows the main processor to focus on responding to changing conditions—in the load, the machine, its ancillary equipment, or its power supply.

Table 1. Accuracy of sensor conversions

DescriptionAccuracy (+or-) Units

Accuracy(+or-) Units

Current, (3) Phase3 3% % Amps 3% % Amps

Voltage (3) Phase4 3% Volts 3% Volts

Kilowatt 5% Kw 5% Kw

Motor Winding Temperatures 14.9 F 8.3 C

Water Temperatures1 °F °C

Evaporator 0.45 °F 0.25 °C

Condenser 0.45 °F 0.25 °C

Flow Compensation Option:

Evaporator flow rate2 5% GPM 5% GPM

Condenser flow rate2 5% GPM 5% GPM

Evaporator water pressuredifferential5 1.5% PSID 1.5% PSID

Condenser water pressuredifferential5 1.5% PSID 1.5% PSID

Chiller Capacity 8% Tons 8% Tons

Enhanced Protection Option:

Bearing temperature sensors6 1.80 °F 1.00 °C

Compressor discharge temperature sensor6 1.80 °F 1.00 °C

Notes:

1. -4 to 122 F(-40 to 121C) 2. With calibration 3. Based on single phase 4. 600 Volt AC and less 5. At 77 F (25 C) 6. -40 to 250 F (-40 to 121 C)

Page 25: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 25

Control and Communication Options

The CenTraVac AdaptiView control complex provides several control and communication options. Figure 16 summarizes the available options.

Figure 16. An overview of AdaptiView controls for CenTraVac chillers

Page 26: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

26 CTV-PRB009-EN, 03 Nov 2010

Control and Communication Options

Hardwire Control Points

Standard hardwire interface points include the binary points shown on Figure 16, p. 25. These include evaporator and condenser pump relays, chiller auto/stop and chiller emergency stop. Additional binary points can be hardwired out if the option call Operating Status (OPST) is selected. See Figure 16, p. 25 for a listing of what control boards and terminal points are applicable within AdaptiView control.

Generic BAS (GBAS)

If you are interested in controlling the chiller with an external hardwire analog signal, you can select the option called Generic BAS (GBAS). (See Figure 16, p. 25. ) With the GBAS option an external hardwire signal can be received to allow changes to the chilled water set point and the demand limit of the chiller. In addition, an analog output of % RLA is available. The GBAS option also includes the condenser pressure output signal that can be used for Head Pressure Control if required.

Condenser Pressure Output (CDRP)

If all that is required is a condenser pressure output signal, for Head Pressure Control, select Condenser Pressure Output (CDRP) alone. With this option you also get an analog output of % RLA.

The CDRP signal is an option typically used on chillers that will have cold starts (northern applications, daytime-only operation), or plants where combined free cooling and regular cooling might take place, and so on. It is specifically used in applications that might have trouble maintaining the 3 psid differential pressure between the evaporator and the condenser. It requires field engineering, wiring, and some control work to implement. Today, AdaptiView control, with the CDRP option can supply a signal that goes directly to the variable speed drive or bypass valve on the condenser water circuit. (See Condenser Water Temperature Control (CTV-PRB006-EN) for more detailed information.)

Control Options (EPRO and WFC)

There are two control options that can be chosen on the CenTraVac:

• Enhanced Protection Option EPRO. See “Enhanced Protection (EPRO) Option,” p. 39 for more information.

• Enhanced Flow Management Package (WFC). See “Enhanced Flow Management Package (WFC),” p. 35 for more details on this option.

Some special unit options require a hardwire interface control card. The card option is called Extended Operation (EXOP). See “Extended Operation (EXOP),” p. 34 for more details on these capabilities.

Communication Options

There are a variety of chiller communication options depending on the application requirements. This subsection covers some options that describe the control interface flexibility of AdaptiView control for CenTraVac chillers. Remember, if you choose to use these communication pathways, you may not need the hardwire points described in the previous subsection. However many customers choose to have the hardwire points for back-up external communication.

Page 27: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 27

Control and Communication Options

Total Building Automation by Trane

The following options describe the typical chiller connection options and available communication protocols when building level control is handled by Tracer SC.

Option 1: LonTalk

Figure 17, p. 27 illustrates the use of a LonTalk card/LLID installed on the chiller to enable the AdaptiView chiller to communicate to the Tracer SC. Using a LonTalk card provides you with a comprehensive list of points that can be communicated. (See LonTalk Communication Interface for Trane Chillers with Tracer AdaptiView Control (ACC-SVN100A-EN) for more information.)

Figure 17. Option 1: LonTalk to Tracer SC

Option 2: BACnet MSTP (RS485)

Figure 18 illustrates the use of the direct BACnet connection using MSTP to communicate with the Tracer SC. The list of communicated points are described in the BACnet™ and Modbus™ RTU Communication Interfaces for Trane™ Chillers with AdaptiView™ Control Integration Guide (BAS-SVP01F-EN).

Figure 18. Option 2: BACnet MSTP to Tracer SC

LonTalk

Tracer SC

MBUS Port (IPC3)

LLIDUC800

AdaptiView Control

(Chiller Mounted)

Tracer SC

UC800

BACnet MSTP(RS485)

“Link Port”

AdaptiView Control

(Chiller Mounted)

Page 28: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

28 CTV-PRB009-EN, 03 Nov 2010

Control and Communication Options

Chiller Plant Control by Trane

The following options illustrate the typical chiller connection options and available communication protocols when Trane is responsible for controlling the chiller plant. Tracer SC allows monitoring and control from a third-party building automation system (BAS).

Option 3: LonTalk

Figure 19 illustrates the use of a LonTalk LLID with data being communicated to the Tracer SC. From the Tracer SC, specific data would pass to the external BAS via a BACnet IP link.

Figure 19. Option 3: LonTalk to Tracer SC

Option 4: BACnet MSTP (RS485)

Figure 20 illustrates a direct BACnet link from the chiller controller to the Tracer SC. Then the Tracer SC would communicate to the external BAS through an IP link.

Figure 20. Option 4: BACnet MSTP (RS485) to Tracer SC

Competitive BASBACnet IP(Ethernet)

Tracer SC

LonTalk

MBUS Port (IPC3)

UC800

LLID

AdaptiView Control

(Chiller Mounted)

Competitive BASBACnet IP(Ethernet)

Tracer SC

UC800

“Link Port”

BACnet MSTP(RS485)

AdaptiView Control

(Chiller Mounted)

Page 29: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 29

Control and Communication Options

Chiller by Trane

The following options illustrate the typical chiller connection options and available communication protocols when an AdaptiView control CenTraVac chiller is controlled directly by a third-party building automation system (BAS).

Option 5: BACnet IP

Figure 21 illustrates data communicated through a BACnet IP link. The chiller direct BACnet connection using MSTP can be output to a field provided BACnet router.

Figure 21. Option 5: BACnet IP to third-party BAS

Option 6: BACnet (MSTP) or MODBUS RTU via 485

Figure 22 illustrates the use of BACnet (MSTP) or MODBUS RTU via RS 485 with a third-party BAS that can receive them. With this option, the controller output can communicate directly with the third-party BAS. Another option would be to use the LonTalk card for the chiller controller, and then communicate the specified LonTalk points list.

Figure 22. Option 6: BACnet (MSTP) or MODBUS RTU or LonTalk with LIDD to third-party BAS

Competitive BASBACnet IP(Ethernet)

BACnet Router

UC800

“Link Port”

BACnet MSTP(RS485)

AdaptiView Control

(Chiller Mounted)

Competitive BAS

BACnet MSTP OR (RS485)

UC800

LLID

“MBUS” Port

Modbus RTU(RS485)

ORLonTalk with LLID

AdaptiView Control

(Chiller Mounted)

“Link” port

Page 30: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

30 CTV-PRB009-EN, 03 Nov 2010

Standard Controls

AdaptiView control supports the standard controls described in this section.

Field Connection

The field connected elements listed here are involved in physically turning the chiller on or off. This involves ensuring that the chiller is not in an emergency or external stop condition, starting the pumps, and verifying that flow has been established. The optional, factory-supplied flow switch or a customer-supplied differential pressure switch can be used to prove flow.

• External Auto Stop (Enable/Disable)

• Emergency Stop

• Chilled-Water Flow Contacts

• Condenser-Water Flow Contacts

• Chilled-Water Pump Relay

• Condenser-Water Pump Relay

Heat Exchanger Control

The fundamental internal variables listed here are necessary to control the chiller. They are gathered and acted upon by the heat exchanger control function.

• High-Pressure Cutout

• Evaporator Entering-Water Temperature

• Evaporator Leaving-Water Temperature

• Condenser Entering-Water Temperature

• Condenser Leaving-Water Temperature

• Evaporator Saturated-Refrigerant Temperature

• Condenser Saturated-Refrigerant Temperature

Motor Control

Motor Control includes all functions that start, run, and stop the motor. The starter module provides the interface and control of Y-delta, across-the-line, primary reactor, autotransformer, and solid-state starters. Analog and binary signals are used to interface with the solid state starter.

An AFD output signal, included in the AFD option, controls the Adaptive Frequency Drive. The Motor Control also provides protection to both the motor and the compressor. It includes the following components:

• Starter Module (all starters except AFD)

• Starter Fault (all solid-state starters)

• Power Supply

• Oil Heater Relay

• Oil and Refrigerant Pump Relay With Interlock

• Oil Temperature

• Oil-Sump Pressure

• Oil-Pump Discharge Pressure

• Compressor Motor-Winding Temperatures

Page 31: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 31

Standard Controls

EarthWise Purge Control

The purge control function provides all the inputs and outputs to control the purge, optimizing both purge and chiller efficiency. The purge controller communicates with AdaptiView control over the IPC3 bus communications link, uploading setpoints and downloading data and diagnostics.

Phase Voltage Sensors – 3-Phase

Includes factory-installed potential transformers in the starter for monitoring and displaying phase voltage and provides over/undervoltage protection. The AdaptiView display, Tracer TU, and Tracer SC display the following:

• Compressor phase voltage (a-b, b-c, c-a)

• Kilowatts

• Power factor (uncorrected)

Chilled-Water Reset (Based on Returned Chilled Water Temperature)

Chilled-water reset is often a practical means of reducing energy consumption during periods of the year when heating loads are high but cooling loads are reduced. Resetting the chilled-water temperature reduces the amount of work that the compressor must do by increasing the evaporator refrigerant pressure.

Chilled-water reset is also used in combination with the hot-water control. By resetting the chilled-water temperature upward, the compressor can generate a higher condenser pressure, resulting in higher leaving hot-water temperatures.

Hot-Water Control

In the hot-water mode, the chiller produces hot water as its primary objective, rather than chilled water. As an option, the Extended Operation (EXOP) package allows an external controller to enable, disable, and modulate this mode. It can be performed with or without a secondary condenser. See also “Heat Recovery/Auxiliary Condenser (ACOS),” p. 32 option.

Ice-Making Control

For chillers that have been selected to allow for ice-making operation, the standard control package includes the ice-making mode. As an option, the Extended Operation (EXOP) package allows an external controller to enable, disable, and modulate this mode.

Page 32: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

32 CTV-PRB009-EN, 03 Nov 2010

Optional Controls

AdaptiView control supports the optional controls described in this section.

Heat Recovery/Auxiliary Condenser (ACOS)

Includes a second condenser for the purpose of recovering heat that would normally be rejected to a cooling tower.

Also includes factory-installed sensors for the entering-and leaving water temperatures. These temperatures are shown at the AdaptiView display, Tracer TU, and Tracer SC.

There are two ways to implement heat recovery: in hot water control mode (get whatever incidental cooling is produced) or in cooling mode (get whatever incidental heating is produced.)

In hot-water control mode, the Hot Gas Bypass (HGBP) option is more- likely necessary. The Extended Operation (EXOP) option is relevant to ACOS only for external hot-water control, which includes enabling, disabling, and controlling the hot- water setpoint. These settings and the hot-water control mode are available internally as standard with AdaptiView control.

Hot-Gas Bypass (HGBP)

While the multi-stage CenTraVac design has excellent surge resistance at low load, there are some applications where HGBP may be necessary to avoid excessive surging or extend to lower loads:

• Heat recovery—elevated head pressure combined with low cooling load

• Process or other applications where entering condenser-water temperature (ECWT) is independent of the cooling load

• Customer preference—based on experience with a single-stage centrifugal chiller that is prone to surge without HGBP

HGBP is generally not needed in northern climates when ECWT varies with the load. TOPSS performs a stability check on all standard CenTraVac chillers down to 25% load with constant ECWT. The chiller selection may be able to unload further. Use the part-load, constant-condenser function of TOPSS to find out how far.

HGBP eliminates or reduces compressor cycling during periods of low or no load. It can be used for short or long periods of time, and allows the chiller to respond quickly to a load increase from the minimum capacity condition. It is sometimes used instead of an AFD when the chiller is oversized. HGBP can also be used in concert with the inlet guide vane control to reduce the settling time after a cooling-load adjustment.

The new compressor-discharge, refrigerant temperature-limit control makes HGBP more adaptable to different operating conditions. When a chiller is selected with the HGBP option, the discharge-refrigerant temperature sensor is included and factory-installed. This temperature and the HGBP hours of operation will be shown at the AdaptiView display, Tracer TU, and Tracer SC.

Chilled-Water Reset (CWR)

(CWR is based on ambient temp.)

This option is an alternative to the standard chilled-water reset, which is based on the return chilled-water temperature.

It consists of ambient temperature sensors and related controls. The ambient temperature is displayed in AdaptiView control, Tracer TU, and at Tracer Summit. The temperature sensor is shipped with the chiller for field installation.

Page 33: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 33

Optional Controls

Gas-Powered Chiller (GENR)

In today's climate of turbulent energy prices and availability, building owners look for solutions. The ability to run a chiller on either natural gas or electricity puts the owner in a stonger and more flexible position. Engine-driven chillers have the highest coefficients of performance of any natural-gas cooling system. Installations in many parts of the country demonstrate the engine-driven chiller's lower total operating costs.

There are two ways to couple a centrifugal chiller with a natural-gas engine—electrically and mechanically. By electrically coupling the chiller and the engine, the system designer has the flexibility to place the engine–generator in a remote location and isolate its sound from sound-sensitive areas.

The controls package is a custom control-interface that coordinates and protects the engine and the chiller.

Free Cooling (FRCL)

Free Cooling (also known as Refrigerant Migration) is based on the principle that refrigerant migrates to the coldest area in the system. The CenTraVac’s Free Cooling option converts the basic CenTraVac chiller to a simple heat exchanger by diverting refrigerant around the compressor. It does not provide control of the leaving chilled-water temperature.

If condenser water is available at a temperature lower than the required leaving chilled-water temperature, the operator manually switches to a Free Cooling cycle by enabling the Free Cooling mode in the AdaptiView settings group.

When the chiller operator initiates the Free Cooling mode, the compressor shuts down if running. The shutoff valves in the liquid and gas lines open the compressor bypass and the unit control logic prevents the compressor from energizing. Liquid refrigerant drains by gravity from the storage tank into the evaporator and floods the tube bundle. Since the temperature and pressure of the refrigerant in the evaporator are higher than in the condenser (due to the higher water temperature), the refrigerant vaporizes and travels to the condenser without assistance from the compressor. Cooling-tower water causes the refrigerant to condense and the cycle continues.

This cycle is sustained as long as a temperature differential exists between the condenser water and evaporator water. The actual cooling capacity provided by the Free Cooling cycle is determined by the difference between these temperatures and the consequent rate of refrigerant flow.

Several components must be factory-supplied or field-installed to equip the unit for Free Cooling operation:

• A refrigerant gas line with an electrically-actuated shutoff valve between the evaporator and condenser

• A liquid return line with an electrically-actuated shutoff valve between the condenser sump and the evaporator

• A liquid refrigerant storage vessel

• Additional refrigerant

The Free Cooling option defines the basic chiller type, including factory-installed piping, valves, controls, and additional refrigerant. Free Cooling is not available with Heat Recovery or Auxiliary Condenser units or with the Hot-Gas Bypass option.

Page 34: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

34 CTV-PRB009-EN, 03 Nov 2010

Optional Controls

Extended Operation (EXOP)

Select the Extended Operation package for chillers that require ice-building control, hot water control, and/or base-loading capabilities to be controlled externally. This package uses the following components, including a 4-20 mA or 0-10 Vdc analog input for a refrigerant monitor.

• External Ice Building Control

• External Ice Building Relay

• External Base Loading Control

• External Base Loading Relay

• External Hot Water Control Relay

• Refrigerant Monitor Input

Base-Loading Control

This feature allows an external controller to directly modulate the capacity of the chiller. It is typically used in applications where virtually infinite sources of evaporator load and condenser capacity are available and it is desirable to control the loading of the chiller. Two examples are industrial process applications and cogeneration plants. Industrial process applications might use this feature to impose a specific load on the facility’s electrical system. Cogeneration plants might use this feature to balance the system’s heating, cooling, and electrical generation.

All chiller safeties and Adaptive Control functions are in full effect when Base Loading is enabled. AdaptiView control’s Adaptive Control logic limits the loading of the chiller to prevent the chiller from shutting down on a safety limit should one of the following events occur:

• The chiller approaches full current

• The evaporator temperature drops too low

• The condenser pressure rises too high

These limits may prevent the chiller from reaching the load requested by the Base Loading signal.

An alternative and less radical approach to Base Loading indirectly controls chiller capacity. Artificially load the chiller by setting the Chilled Water Setpoint lower than its normal range. Then, modify the chiller’s load by adjusting the Current Limit Setpoint. This approach provides greater safety and control stability because it leaves the chilled water temperature control logic in effect. The chilled water temperature control responds more quickly to dramatic system changes and limits chiller loading prior to reaching an Adaptive Control limit.

Ice-Making Control

This feature allows an external controller to control the chiller in an ice storage system. Ice storage is typically used in areas where high electrical-demand charges can be offset by shifting building energy use to off-peak (typically nighttime) hours.

While AdaptiView control is capable of running the chiller in Ice-Making mode, installation savings and additional energy savings can be realized by using the Chiller Plant Control module of the Tracer building automation system. Chiller Plant Control anticipates how much ice needs to be made at night and operates the system accordingly. The controls are integrated with the chiller. Two wires and preprogrammed software reduce field-installation cost and complex custom programming.

The CenTraVac chiller is uniquely suited for low-temperature applications like ice storage, because it provides multiple stages of compression. This allows the chiller to produce ice efficiently, while experiencing less stress than a single-stage compression chiller.

Page 35: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 35

Optional Controls

Hot-Water Control

This feature allows an external controller to enable/disable and modulate the Hot Water Control mode. Occasionally, CenTraVac chillers are used to provide heating as a primary mission. In this case the external controller or operator would select a hot water temperature setpoint and the chiller capacity would be modulated to maintain the setpoint. Heating is the primary mission and cooling is a waste product or a secondary mission. This technique provides application flexibility, especially in multiple-chiller plants in conjunction with undersized heating plants.

The chiller uses only one condenser for Hot Water Control, whereas Heat Recovery uses a secondary condenser.

Refrigerant Monitor

The Extended Operation package allows for a refrigerant monitor to send a 4-20 mA signal to the AdaptiView display. It can be calibrated to correspond to either 0-100 ppm or 0-1,000 ppm concentration levels. The concentration level is displayed at the AdaptiView display, but the chiller will not take any action based on the input from the refrigerant monitor.

Alternatively, a refrigerant monitor can be connected to Tracer SC, which has the ability to increase ventilation in the equipment room.

Enhanced Flow Management Package (WFC)

The Enhanced Flow Management Package option includes transducers for the differential evaporator-and condenser- water pressures (psid). Flow switches or some other means to prove flow are still required and must be field connected. One type of sensor handles all pressure ranges up to 300 psig.

The following data will be shown at the AdaptiView display, in Tracer TU displays, and at Tracer Summit.

• Evaporator and condenser differential water pressures (psid)

• Evaporator and condenser gpm

• Evaporator tons (estimate)

Enhanced Flow Management Package

The standard Trane chiller is designed to handle variable flow rates of change between 10% - 30% per minute. At 10% per minute, the leaving chilled water temperature fluctuates very little (less than .5F ±). As you increase the rate of change to 30% per minute, the leaving chilled water temperature fluctuation increases, but the unit remains online.This principle applies to units with and without AFDs. To enhance this capability, you can select the Enhanced Flow Management Package option.

The Enhanced Flow Management Package option uses a patented, variable, water-flow algorithm to maintain stable, precise capacity control with flow rate changes up to 30% per minute. In addition, if the Enhanced Flow Management Package option is installed, the chiller can remain online with flow rate changes up to 50% per minute.

It will automatically adjust capacity control to:

• Maintain control stability at low flow rates.

• Maintain control stability at flow rate changes in excess of 30% per minute.

If the water-pressure transducer fails and the flow switch continues to prove flow, the Enhanced Flow Management Package will be disabled and the design delta T will be used.

For applications designed to operate with Variable Primary Water Flow (VPF) , the Enhanced Flow Management Package allows the chiller to respond quickly to accelerating or decelerating water. By automatically adjusting the control gain, large changes in the water flow rate can be tolerated. Data shown on Figure 24, p. 37 demonstrates water- temperature control with flow compensation

Page 36: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

36 CTV-PRB009-EN, 03 Nov 2010

Optional Controls

enabled. The chilled water temperature remains stable, even when the water flow rate drops 50 percent in 30 seconds.

Another benefit of water flow compensation is disturbance rejection. Figure 25, p. 37 shows the test results from step changes in water flow with increasing magnitudes. The leaving chilled water temperature remains largely unaffected. Even the most severe change—dropping water flow 66 percent in 30 seconds—caused a small 1.5°F variation in chilled water temperature.

It is unlikely that a chiller application would be making water flow changes of this magnitude. The results demonstrate that the chiller is more than capable of supporting variable water flow applications.

Variable Flow Stability

The following figures illustrate the effect of the Enhanced Flow Management Package option.

Figure 23. Capacity Control Without Enhanced Flow Management

Page 37: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 37

Optional Controls

Figure 24. Capacity Control With Enhanced Flow Management

Figure 25. Capacity Control With Flow Changes and Compensation

Page 38: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

38 CTV-PRB009-EN, 03 Nov 2010

Optional Controls

Adaptive Frequency Drive (AFD) Option

The AFD option provides the following benefits.

• Simultaneous Adjustment of Inlet Guide Vanes and SpeedSimultaneously adjusts inlet guide vanes and speed to spend more hours at optimum efficiency. Upon startup, the chiller starts at a frequency that provides additional surge margin. The added surge margin decays gradually over 40 minutes to the optimum speed. The extra surge margin is used to allow the chiller refrigerant pressures to stabilize. AFD speed and IGV position are simultaneously adjusted to meet the dual requirements of water temperature control and efficiency. AdaptiView control adjusts speed unconditionally—it does not have to wait for water temperature control to reach setpoint or for stable cooling load.AdaptiView control adjusts speed as needed to track changing load or water-loop conditions. At the same time, it adjusts the inlet guide vanes to prevent the water temperature from deviating from its setpoint. When the vanes are fully open, the compressor speed is controlling the water temperature. Reducing the chiller load or increasing the head conditions cause the compressor to move toward a surge condition. When conditions are within the surge boundary, vanes and speed modulate to control both surge margin and chiller capacity.

• Mathematical Optimization of Inlet Guide Vanes and SpeedMathematically optimizes inlet guide vanes and speed, which eliminates“hunting” at surge boundary. AdaptiView control reduces speed until the surge pressure coefficient boundary is reached. Every 30 minutes, the AFD speed control evaluates whether the boundary should be optimized. If optimization is required, the pressure-coefficient boundary is raised until surge is detected. Upon surge, the boundary is reset and surge recovery occurs. The decision to optimize is based on whether the vane position has changed by an amount greater than the optimization sensitivity since the last optimization was done. After the boundary is established, speed control makes adjustments to follow the boundary as conditions change.

• Increased Stability and AdaptabilityAdaptiView control includes features that overcome previous Variable Frequency Drive (VFD) limitations and prevent instability.

– Variable water-flow designs—work in conjunction with an AFD, provided the chiller control is AdaptiView control with the Flow Compensation Control option installed. Chiller control with rapid water flow variations and large turndown have been demonstrated with and without variable frequency drives.

– Rapid changes in load—Feedforward control improves chilled water temperature response.

– Short chilled water loop—Feedforward control cancels out the effect of short water loops.

– Parallel chiller with poor control is causing temperature variations—AdaptiView control changes speed and adjusts cooling load at the same time. Even if there is a poorly controlled chiller in parallel, a CenTraVac chiller with AdaptiView control maintains excellent water-temperature control at the best efficiency.

– Waiting for leaving temperature to exceed threshold—AdaptiView control reduces speed to the surge boundary based on the current differential operating pressure, making instantaneous corrections to speed and vane settings as conditions change.

Note: CTV-PRB008-EN “Trane Adaptive Frequency Control for Centrifugal Water Chillers” provides a more detailed discussion of this option.

Page 39: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 39

Optional Controls

Enhanced Protection (EPRO) Option

The Optional Enhanced Protection Package includes sensors and transducers that enable the following protection features:

Table 2. AdaptiView control standard protection features

Option Description

Enhanced condenser - limit control Includes factory-installed condenser pressure transducer and interconnecting piping and wiring. Provides enhanced high-pressure cutout avoidance by energizing a relay to initiate head relief.

Note: This option is in addition to the standard high refrigerant-pressure safety contact.

Compressor Discharge Refrigerant Temperature Protection

Includes a factory-installed sensor and safety cutout on high compressor- discharge temperature. Allows AdaptiView control to monitor compressor discharge temperature, which is displayed at the AdaptiView display, Tracer TU, and Tracer SC.

Note: When the chiller is selected with HGBP, this sensor and its associated protection are included.

Bearing Oil Temperature Leaving Each Bearing

Optional factory-installed sensors allow high-temperature safety cutouts to monitor the leaving bearing-oil temperatures. AdaptiView control and Tracer SC display the temperatures.

The high bearing temperature cutout is fixed at 180°F (82.2°C). If either bearing temperature violates the cutout, a latching diagnostic is generated.

Page 40: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

40 CTV-PRB009-EN, 03 Nov 2010

Standard Protections

AdaptiView control uses proportional-integral-derivative (PID) control for all limits—there is no deadband. This removes oscillation above and below setpoints and extends the capabilities of the chiller.

For a complete listing of

• Motor Protection capabilties See Starters, Drives, and Electrical Components for CenTraVac™ Chillers Engineering Bulletin (CTV-PRB004-EN).

• Chiller Protection capabilities See Diagnostic Descriptions, Troubleshooting Tables, and Control Component Overview for Water-Cooled CenTraVac™ Chillers with Tracer AdaptiView™ Control (CTV-SVD03A-EN).

Page 41: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 41

Monitored Points

The following tables present a partial list of points that are monitored at the AdaptiView display or Tracer TU. Please note that certain points require optional control packages, indicated by a three or four letter code.

Table 3. Monitored points grouped into categories

Temperature Option AdaptiView Tracer TU

Evaporator approach temperature Standard Y Y

Evaporator entering water temperature Standard Y Y

Evaporator leaving water temperature Standard Y Y

Condenser approach temperature Standard Y Y

Condenser entering water temperature Standard Y Y

Condenser leaving water temperature Standard Y Y

Compressor motor winding temperature 1,2,3 Standard Y Y

Oil temperature (tank) Standard Y Y

Saturated evaporator refrigerant temperature Standard Y Y

Saturated condenser refrigerant temperature Standard Y Y

Purge compressor suction temperature Standard Y Y

Auxiliary/Heat Recovery entering temperature Standard with HR Y Y

Auxiliary/Heat Recovery leaving temperature Standard with HR Y Y

Discharge temperature EPRO or HGBP Y Y

Bearing oil temperature 1,2 EPRO Y Y

Outdoor air temperature CWR Y Y

Pressure Option AdaptiView Tracer TU

Evaporator refrigerant press (derived) psig Standard Y Y

Condenser refrigerant press (derived) psig Standard Y Y

Evaporator differential water press psid WFC Y Y

Condenser differential water press psid WFC Y Y

Oil tank press psig Standard Y Y

Oil pump discharge press psig Standard Y Y

Differential oil press (derived) psid Standard Y Y

Condenser refrigerant press (transducer) psig EPRO Y Y

Condenser refrigerant press output (0-10 Vdc) CDRP or GBAS Y Y

Page 42: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

42 CTV-PRB009-EN, 03 Nov 2010

Monitored Points

Control inputs Option AdaptiView Tracer TU

Setpoint source - Tracer (software point) TRMM Y Y

Setpoint source - generic BAS (software point) GBAS Y Y

Setpoint source - front panel Standard Y Y

Chilled water reset based on return water temperature Standard Y Y

Chilled water reset based on outdoor air temperature CWR Y Y

Chilled water setpoint GBAS Y Y

Current limit setpoint (% RLA) GBAS Y Y

External chiller AUTO-STOP Standard Y Y

External chiller emergency STOP Standard Y Y

External free cooling enable/disable FRCL Y Y

External ice building enable/disable EXOP

Chiller associated Option AdaptiView Tracer TU

HGBP hours HGBP Y Y

Evaporator GPM (derived) WFC Y Y

Condenser GPM (derived) WFC Y Y

Tons - evaporator WFC Y Y

Compressor associated Option AdaptiView Tracer TU

Compressor motor starts Standard Y Y

Compressor motor running hours Standard Y Y

Current, phase current Standard Y Y

Voltage, L1, L2, L3 Standard Y Y

Compressor motor kW Standard Y Y

Power factor Standard Y Y

Compressor motor percent RLA by phase Standard Y Y

Compressor motor percent RLA output (0-10 Vdc) GBAS NA Y

Page 43: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 43

Monitored Points

AFD associated Option AdaptiView Tracer TU

% RLA L1, L2, L3 Standard Y Y

AFD bus voltage (Vdc) AFD N Y

Frequency AFD Y Y

AFD last diagnostic code AFD N Y

AFD output power (kW) AFD N Y

AFD (output/load) amps, L1, L2, L3 AFD Y Y

Speed AFD Y Y

AFD transistor temperature AFD Y Y

Variable speed settings and limits AFD N Y

Input line kW Standard Y Y

Input line voltage Standard Y Y

Motor speed (Hz) AFD Y Y

Motor speed (rpm) AFD Y Y

Motor winding temps, 1, 2, 3 Standard Y Y

Refrigerant associated Option AdaptiView Tracer TU

Time until next purge run Standard Y Y

Daily pump-out 24 hours Standard Y Y

Average daily pump-out – 7 days Standard Y Y

Daily pump-out limit/alarm Standard Y Y

Chiller on – 7 days Standard Y Y

Pump-out chiller on – 7 days Standard Y Y

Pump-out chiller off – 7 days Standard Y Y

Pump-out - life Standard Y Y

Purge refrigerant compressor suction temperature Standard Y Y

Purge liquid temperature Standard Y Y

Purge carbon tank temperature Standard Y Y

Purge alarm relay output OPST Y Y

Page 44: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

44 CTV-PRB009-EN, 03 Nov 2010

Monitored Points

Binary outputs Option AdaptiView Tracer TU

Maximum capacity relay OPST Vane Position Y

Evaporator pump relay Standard Operating Mode Y

Condenser pump relay Standard Operating Mode Y

Compressor running relay OPST Operating Mode Y

Limit warning relay OPST Operating Mode Y

Ice-making relay EXOP Operating Mode Y

Head relief request relay OPST Operating Mode Y

Free cooling auxiliary relay FRCL Operating Mode Y

Alarm relay MMR, MAR OPST Alarm Display Y

Purge alarm relay OPST Alarm Display Y

Page 45: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 45

Diagnostics

The following tables list of all the AdaptiView control diagnostics by major category.

• Diagnostic NameThe exact text displayed in AdaptiView display and Tracer TU.

• SeverityImmediate Shutdown means immediate shutdown of the affected portion. Normal Shutdown means normal or friendly shutdown of the affected portion. Warning means an informational note or warning is generated.

• PersistenceLatching means that the diagnostic and its effects must be manually reset. Nonlatching diagnostics can be either manually or automatically reset.

Starter Diagnostics

Table 4. List of starter diagnostics

Diagnostic Name Severity Persistence

Starter Did Not Transition Immediate Shutdown Latching

Starter Did Not Fully Accelerate Immediate Shutdown Latching

Phase Reversal Immediate Shutdown Latching

Starter Dry Run Test Immediate Shutdown Latching

Phase Loss Immediate Shutdown Latching

Power Loss Immediate Shutdown Nonlatching

Momentary Power Loss Immediate Shutdown Nonlatching

Severe Current Unbalance Normal Shutdown Latching

Starter Fault Type I Immediate Shutdown Latching

Starter Fault Type II Immediate Shutdown Latching

Starter Fault Type III Immediate Shutdown Latching

Transition Complete Input Shorted Immediate Shutdown Latching

At Speed Input Shorted Immediate Shutdown Latching

Transition Complete Input Opened Immediate Shutdown Latching

At Speed Input Opened Immediate Shutdown Latching

Motor Current Overload Immediate Shutdown Latching

Compressor Did Not Accelerate: Shutdown Immediate Shutdown Latching

Cprsr Did Not Accelerate: Transition Warning Latching

Starter Contactor Interrupt Failure Immediate Shutdown Latching

Starter Module Memory Error Type 1 Warning Latching

Starter Module Memory Error Type 2 Immediate Shutdown Latching

Starter Comm Loss: Main Processor Immediate Shutdown Latching

Page 46: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

46 CTV-PRB009-EN, 03 Nov 2010

Diagnostics

Adaptive Frequency Drive Diagnostics

Table 5. List of AFD diagnostics

Diagnostic Name Severity Persistence

AFD Power Loss Immediate Shutdown Nonlatching

AFD Start Inhibited Normal Shutdown Nonlatching

AFD Motor Current Overload Immediate Shutdown Latching

AFD Motor Short Immediate Shutdown Latching

AFD Instantaneous Current Overload Immediate ShutdownLatching

AFD High Temperature Immediate Shutdown Latching

AFD Output Phase Loss Immediate Shutdown Latching

AFD Ground Fault Immediate ShutdownLatching

HPC/High AFD Heat Sink Water Pressure Immediate Shutdown Latching

AFD Communication Loss: Main Processor Immediate Shutdown Latching

AFD High Bus Voltage Immediate Shutdown Latching

AFD Control Board Memory Error Type 2 Immediate Shutdown Latching

AFD General Failure Immediate Shutdown Latching

AFD Fatal Software Error Immediate Shutdown Latching

AFD I/O Board Failure Immediate Shutdown Latching

AFD Power Intfc Controller Board Failure Immediate Shutdown Latching

AFD Power Structure Board Failure Immediate Shutdown Latching

AFD DPI Communication Failure Immediate Shutdown Latching

AFD RS485 Board Memory Error Type 2 Immediate Shutdown Latching

Page 47: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 47

Diagnostics

Main Processor Defective Sensor or LLID Diagnostics

Table 6. List of main processor defective sensor or LLID diagnostics

Diagnostic Name Severity Persistence

External Chilled/Hot Water Setpoint Warning Nonlatching

External Current Limit Setpoint Warning Nonlatching

Evaporator Entering Water Temp SensorWarningNormal Shutdown (Ice Building)

LatchingLatching (Ice Building)

Evaporator Leaving Water Temp Sensor Normal Shutdown Latching

Condenser Entering Water Temp Sensor Warning Latching

Condenser Leaving Water Temp SensorWarningNormal Shutdown (Hot Water)

Latching

Evaporator Differential Water Pressure Transducer Warning Latching

Condenser Differential Water Pressure Transducer Warning Latching

Second Cond Entering Water Temp Sensor Warning Latching

Second Cond Leaving Water Temp Sensor Warning Latching

Evap Saturated Refrigerant Temp Sensor Normal Shutdown Latching

Cond Saturated Refrigerant Temp Sensor Normal Shutdown Latching

Purge Liquid Temperature Sensor Normal Shutdown Latching

Condenser Refrigerant Pressure Xdcr Normal Shutdown Latching

Oil Tank Temperature Sensor Normal Shutdown Latching

Oil Pump Discharge Pressure Transducer Immediate Shutdown Latching

Oil Tank Pressure Transducer Immediate Shutdown Latching

Motor Winding Temperature 1 Sensor Normal Shutdown Latching

Motor Winding Temperature 2 Sensor Normal Shutdown Latching

Motor Winding Temperature 3 Sensor Normal Shutdown Latching

Inboard Bearing Temperature Sensor Normal Shutdown Latching

Outboard Bearing Temperature Sensor Normal Shutdown Latching

Compressor Discharge Refrigerant Temperature Sensor

Normal ShutdownWarning (HGBP) Latching

Outdoor Air Temperature Sensor Warning Nonlatching

Purge Cprsr Suction Rfgt Temp Sensor Normal Shutdown Latching

Purge Carbon Tank Temperature Sensor Normal Shutdown Latching

External Base Loading Setpoint Warning Nonlatching

Page 48: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

48 CTV-PRB009-EN, 03 Nov 2010

Diagnostics

Main Processor Purge Diagnostics

Main Processor Unit-Level Diagnostics

Table 7. List of main processor purge diagnostics

Diagnostic Name Severity Persistence

Purge Liquid Level Too High Warning Normal Shutdown Nonlatching

Purge Liquid Level Too High Continuously Normal Shutdown Latching

Purge Carbon Regen Temperature Too Low Normal Shutdown Latching

Purge Carbon Regen Temp Limit Exceeded Normal Shutdown Latching

Purge Regen Cooldown Temp Too High Normal Shutdown Latching

Purge Daily Pump-out Limit Exceeded Normal Shutdown Nonlatching

Purge Carbon Regen Temp Not Satisfied Normal Shutdown Latching

Table 8. List main processor unit-level diagnostics

Diagnostic Name Severity Persistence

Low Evaporator Refrigerant Temperature Immediate Shutdown Latching

High Oil Temperature Immediate Shutdown Latching

Low Evaporator Leaving Water Temp: Unit Off (Unit in auto but not starting or running)

Warning Nonlatching

Low Evaporator Leaving Water Temp: Unit On (Unit Starting or Running)

Immediate Shutdown Nonlatching

Evaporator Water Flow Overdue Normal Shutdown Nonlatching

Evaporator Water Flow Lost Immediate Shutdown Nonlatching

Condenser High Pressure Cutout Immediate Shutdown Latching

Emergency Stop Immediate Shutdown Latching

MP: Invalid Configuration Immediate Shutdown Latching

MP: Non-Volatile Memory Reformat Warning Latching

Check Clock Warning Latching

MP: Could not Store Starts and Hours Warning Latching

MP: Non-Volatile Block Test Error Warning Latching

MP: Reset Has Occurred Warning Latching

Extended Compressor Surge Normal ShutdownLatchingNonlatching (Ice Building)

Over Voltage Normal Shutdown Nonlatching

Under Voltage Normal Shutdown Nonlatching

Low Evaporator Water Flow Warning Nonlatching

Condenser Water Flow Overdue Normal Shutdown Nonlatching

Condenser Water Flow Lost Normal Shutdown Nonlatching

Free Cooling Actuators Not Open Normal Shutdown Latching

Free Cooling Actuators Not Open During FC Normal Shutdown Latching

Page 49: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 49

Diagnostics

Free Cooling Actuators Not Closed Normal Shutdown Latching

Free Cooling Actuators Unexpectedly Open Immediate Shutdown Latching

Unexpected Starter Shutdown Normal Shutdown Nonlatching

Starter Failed to Arm/Start Normal Shutdown Latching

Solid State Starter Fault Immediate Shutdown Latching

Low Differential Oil Pressure Immediate Shutdown Latching

Check Oil Filter Warning Latching

Oil Pressure Sensor Calibration Normal Shutdown Latching

High Vacuum Lockout Immediate Shutdown Latching

Low Oil Temperature Immediate Shutdown Latching

High Inboard Bearing Temperature Immediate Shutdown Latching

High Outboard Bearing Temperature Immediate Shutdown Latching

High Cprsr Discharge Rfgt Temperature Normal Shutdown Nonlatching

High Motor Winding Temperature 1 Immediate Shutdown Latching

High Motor Winding Temperature 2 Immediate Shutdown Latching

High Motor Winding Temperature 3 Immediate Shutdown Latching

Unexpected Differential Oil Pressure Immediate Shutdown Latching

Differential Oil Pressure Overdue Immediate Shutdown Latching

BAS Failed to Begin Comm to Comm4 Board Warning Nonlatching

BAS Comm Lost with Comm4 Board Warning Nonlatching

Hot Gas Bypass Valve Closure Overdue Normal Shutdown Latching

Hot Gas Bypass Valve Unexpectedly Open Normal Shutdown Latching

Hot Gas Bypass Valve Opening Overdue Warning Latching

Refrigerant Monitor Input Warning Nonlatching

Table 8. List main processor unit-level diagnostics (continued)

Diagnostic Name Severity Persistence

Page 50: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

50 CTV-PRB009-EN, 03 Nov 2010

Diagnostics

Main Processor Communication Diagnostics

Table 9. Main processor “Comm Loss” diagnostics

Diagnostic Name Severity Persistence

Excessive Loss of Communication Immediate ShutdownLatching

Comm Loss: External Auto/Stop Normal Shutdown Latching

Comm Loss: Emergency Stop Normal Shutdown Latching

Comm Loss: External Ice Building Command Normal Shutdown Latching

Comm Loss: Outdoor Air Temperature Warning Latching

Comm Loss: Evap Leaving Water Temp Normal Shutdown Latching

Comm Loss: Evap Entering Water TempWarningNormal Shutdown(Ice Building)

LatchingNonlatching (Ice Building)

Comm Loss: Condenser Leaving Water TempWarningNormal Shutdown (Hot Water)

Latching

Comm Loss: Condenser Entering Water Temp Warning Latching

Comm Loss: Sec Cond Leaving Water Temp Warning Nonlatching

Comm Loss: Sec Cond Entering Water Temp Warning Nonlatching

Comm Loss: Oil Tank Temperature Normal Shutdown Latching

Comm Loss: Ext Chilled/Hot Wtr Setpoint Warning Nonlatching

Comm Loss: Ext Current Limit Setpoint Warning Nonlatching

Comm Loss: Cond High Pressure Cutout Normal Shutdown Latching

Comm Loss: Evaporator Water Flow Switch Immediate Shutdown Latching

Comm Loss: Condenser Water Flow Switch Normal Shutdown Latching

Comm Loss: Evap Saturated Rfgt Temp Immediate Shutdown Latching

Comm Loss: Cond Saturated Rfgt Temp Normal Shutdown Latching

Comm Loss: Purge Liquid Temperature Normal Shutdown Latching

Comm Loss: Condenser Refrigerant Pressure Normal Shutdown Latching

Comm Loss: Oil Tank Pressure Immediate Shutdown Latching

Comm Loss: Oil Pump Discharge Pressure Immediate Shutdown Latching

Comm Loss: Evaporator Water Pump Relay Warning Latching

Comm Loss: Condenser Water Pump Relay Warning Latching

Comm Loss: Ice Building Relay Normal Shutdown Latching

Comm Loss: Starter Immediate Shutdown Latching

Comm Loss: Adaptive Frequency Drive Immediate Shutdown Latching

Comm Loss: Local BAS Comm4 Board Warning Nonlatching

Comm Loss: Compressor Running Relay Warning Latching

Comm Loss: Non-Wrn Latching Alarm Relay Warning Latching

Page 51: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 51

Diagnostics

Comm Loss: Non-Wrn Nonlatching Alm Relay Warning Latching

Comm Loss: Unit Purge Alarm Relay Warning Latching

Comm Loss: Limit Warning Relay Warning Latching

Comm Loss: Maximum Capacity Relay Warning Latching

Comm Loss: Head Relief Request Relay Warning Latching

Comm Loss: Evap Diff Water Pressure Warning Latching

Comm Loss: Cond Diff Water Pressure Warning Latching

Comm Loss: Cond Rfgt Pressure Output Warning Latching

Comm Loss: Compressor Motor % RLA Output Warning Latching

Comm Loss: Refrigerant Monitor Input Warning Latching

Comm Loss: External Free Cooling Command Normal Shutdown Latching

Comm Loss: Free Cool Actrs Closed Input Immediate Shutdown Latching

Comm Loss: Free Cool Liq Line Actuator Relay Normal Shutdown Latching

Comm Loss: Free Cool Gas Line Actuator Relay Normal Shutdown Latching

Comm Loss: Free Cooling Auxiliary Relay Warning Nonlatching

Comm Loss: Purge Cprsr Suction Rfgt Temp Normal Shutdown Latching

Comm Loss: Purge Carbon Tank Temperature Normal Shutdown Latching

Comm Loss: Purge Liquid Level Switch Normal Shutdown Latching

Comm Loss: Purge Chiller Cprsr Run Input Normal Shutdown Latching

Comm Loss: Purge Pump-out Relay Normal Shutdown Latching

Comm Loss: Purge Carbon Tank Heater Rly Normal Shutdown Latching

Comm Loss: Purge Regen Solenoid Relay Normal Shutdown Latching

Comm Loss: Purge Alarm Relay Normal Shutdown Latching

Comm Loss: Purge Pump-out Solenoid Output Normal Shutdown Latching

Comm Loss: Purge Exhaust Solenoid Output Normal Shutdown Latching

Comm Loss: Purge Condensing Unit Relay Normal Shutdown Latching

Comm Loss: Solid State Starter Fault Immediate Shutdown Latching

Comm Loss: PFCC Relay Warning Nonlatching

Comm Loss: Oil/Refrigerant Pump Relay Immediate Shutdown Latching

Comm Loss: Oil Tank Heater Relay Warning Nonlatching

Comm Loss: Motor Winding Temperature 1 Normal Shutdown Latching

Comm Loss: Motor Winding Temperature 2 Normal Shutdown Latching

Table 9. Main processor “Comm Loss” diagnostics (continued)

Diagnostic Name Severity Persistence

Page 52: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

52 CTV-PRB009-EN, 03 Nov 2010

Diagnostics

Comm Loss: Motor Winding Temperature 3 Normal Shutdown Latching

Comm Loss: Inboard Bearing Temperature Normal Shutdown Latching

Comm Loss: Outboard Bearing Temperature Normal Shutdown Latching

Comm Loss: Cprsr Discharge Rfgt Temp Normal Shutdown Warning (HGBP) Latching

Comm Loss: IGV First Stage Actuator Normal Shutdown Latching

Comm Loss: IGV Second Stage Actuator Normal Shutdown Latching

Comm Loss: Ext Base Loading Setpoint Warning Nonlatching

Comm Loss: Ext Base Loading Command Warning Nonlatching

Comm Loss: External Hot Water Command Warning Nonlatching

Comm Loss: Hot Gas Bypass Load Relay Normal Shutdown Latching

Comm Loss: Hot Gas Bypass Unload Relay Normal Shutdown Latching

Comm Loss: Hot Gas Bypass Actr Closed In Normal Shutdown Latching

Table 9. Main processor “Comm Loss” diagnostics (continued)

Diagnostic Name Severity Persistence

Page 53: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 53

Report Contents

The following data can be viewed on the Reports screen.

Table 10. Log sheet report

Chiller component Report item Unit

Evaporator

Evaporator Entering Water Temperature XXX.X °F/°C

Evaporator Leaving Water Temp XXX.X °F/°C

Evaporator Sat Rfgt Temp XXX.X °F/°C

Evaporator Rfgt Pressure XXX.X PSI/kPa

Evaporator Approach Temp XXX.X °F/°C

Evaporator Water Flow Switch Status Flow/No Flow

Condenser

Cond Entering Water Temp XXX.X °F/°C

Cond Leaving Water Temp XXX.X °F/°C

Cond Sat Rfgt Temp XXX.X °F/°C

Cond Rfgt Pressure XXX.X PSI/kPa

Cond Approach Temp XXX.X °F/°C

Cond Water Flow Switch Status Flow/No Flow

Compressor

Starts XXXX Starts

Running Time XX:XX Hr:Min

Oil Tank Pressure XXX.X PSI/kPa

Oil Pump Discharge Pressure XXX.X PSI/kPa

Oil Differential Pressure XXX.X PSI/kPa

Oil Tank Temperature XXX.X °F/°C

IGV 1 Position XXX.X %

IGV 1 Position Steps

IGV 2 Position XXX.X %

IGV 2 Position Steps

Page 54: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

54 CTV-PRB009-EN, 03 Nov 2010

Report Contents

Note: The ASHRAE Chiller Log contains those items recommended by ASHRAE Std 147 Standard 147-2002, Reducing Release of Halogenated Refrigerants from Refrigeration and Air-Conditioning Equipment and Systems.

Motor

Starter Current L1 XXX.X %

Starter Current L2 XXX.X %

Starter Current L3 XXX.X %

Starter Current L1 XXXX A

Starter Current L2 XXXX A

Starter Current L3 XXXX A

Starter Voltage AB XXXXX.X V

Starter Voltage BC XXXXX.X V

Starter Voltage CA XXXXX.X V

Starter Power Demand XXXX kW

Starter Load Power Factor XX.X

Motor Winding Temp 1 XXX.X °F/°C

Motor Winding Temp 2 XXX.X °F/°C

Motor Winding Temp 3 XXX.X °F/°C

AFD Frequency XX Hz

Motor (cont.)AFD Speed XXXX RPM

AFD Transistor Temp XXX.X °F/°C

Purge

Time Until Next Purge Run XXX.X min

Daily Pumpout—24 Hours XXX.X min

Average Daily Pumpout—7 Days XXX.X min

Daily Pumpout Limit XXX.X min

Chiller On—7 Days XXX.X min

Pumpout Chiller On—7 Days XXX.X min

Pumpout Chiller Off—7 Days XXX.X min

Pumpout—Life XXX.X min

Purge Rfgt Compressor Suction Temp XXX.X °F/°C

Purge Liquid Temp XXX.X °F/°C

Purge Carbon Tank Temp XXX.X °F/°C

Table 10. Log sheet report (continued)

Chiller component Report item Unit

Page 55: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 55

Report Contents

Table 11. ASHRAE Chiller Log

Data name Value

Current Date/Time User-selected date/time format

Chiller Top Level Mode Dependent on chiller type

Starter Current L1 XXXX A

Starter Current L2 XXXX A

Starter Current L3 XXXX A

Starter Phase Voltage AB XXXX V

Starter Phase Voltage BC XXXX V

Starter Phase Voltage CA XXXX V

Active Chilled Water Setpoint XXX.X F°/C°

Active Current Limit Setpoint XXX.X %

Refrigerant Monitor XXX.X ppm

Purge Daily Pumpout—24 Hrs XXX.X Min:Sec

Purge Daily Pumpout Limit XXX.X Min

Pumpout—Life XXX.XXX Min:Sec

Purge Top Level Mode On/Auto/Adaptive/ Stop

Purge Mode On/Auto/Adaptive/ Stop

Compressor Starts XXXX

Compressor Running Time XX:XX Hr:Min

Compressor Refrigerant Discharge Temperature XXX.X °F/C°

Oil Pump Discharge Pressure XXX.X PSIA/kPa

Oil Tank Pressure XXX.X PSIA/kPa

Oil Differential Pressure XXX.X PSID/kPaD

Oil Tank Temperature XXX.X °F/C°

Inboard Bearing Temp XXX.X °F/C°

Outboard Bearing Temp XXX.X F°/C°

Evaporator Entering Water Temp XXX.X °F/C°

Evaporator Leaving Water Temp XXX.X °F/C°

Evaporator Saturated Rfgt Temp XXX.X °F/C°

Evaporator Refrigerant Pressure XXX.X PSI/kPaA

Evap Approach Temp XXX.X °F/C°

Evap Water Flow Status Flow/No Flow

Evap Differential Wtr Press XXX.X PSID/kPaD

Page 56: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

56 CTV-PRB009-EN, 03 Nov 2010

Report Contents

Approx Evap Water Flow XXX.X gpm/lpm

Calculated Chiller Capacity XXXX tons/kW

Cond Entering Water Temp XXX.X °F/C°

Cond Leaving Water Temp XXX.X °F/C°

Condensor Saturated Rfgt Temp XXX.X °F/C°

Condensor Refrigerant Pressure XXX.X PSIA/kPaA

Condenser Approach Temperature XXX.X °F/C°

Cond Water Flow Status: Flow/No Flow

Cond Differential Wtr Press XXX.X PSID/kPaD

Approx Cond Water Flow XXXX gpm/lpm

Second Condenser Ent Wtr Temp XXX.X °F/C°

Second Condenser Lvg Wtr Temp XXX.X °F/C°

Table 12. Other items available for custom reports

Subsystem Description

Chiller

Active Base Loading Setpoint

Active Base Loading Setpoint Source

Application Part Number

Version

Chiller Heating or Cooling Mode

Chiller Top Level Operating Mode

Compressor

Chiller Control Signal

Compressor Refrigerant Discharge Temperature

Compressor Running

Compressor Running Time

Compressor Starts

Inboard Bearing Temperature

IGV 1 Percent Open

IGV 1 Position Steps

IGV 2 Percent Open

IGV 2 Position Steps

Oil Differential Pressure

Oil Differential Pressure Switch

Oil Heater Command

Oil Pump Control

Table 11. ASHRAE Chiller Log (continued)

Data name Value

Page 57: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

CTV-PRB009-EN, 03 Nov 2010 57

Report Contents

Compressor (cont.)

Oil Pump Discharge Pressure

Oil Pump Override Time Remaining

Oil Tank Pressure

Oil Tank Temperature

Outboard Bearing Temperature

Condenser

Condenser Approach Temperature

Condenser Entering Water Temperature

Condenser Leaving Water Temperature

Condenser Refrigerant Pressure

Condenser Saturated Refrigerant Temperature

Condenser Water Flow Switch Status

Condenser Pump Override Time Remaining

Condenser Pump Override

Evaporator

Active Chilled Water Setpoint

Active Chilled Water Setpoint Source

BAS Chilled Water Setpoint

Evaporator Approach Temperature

Evaporator Entering Water Temperature

Evaporator Leaving Water Temperature

Evaporator Pump Override

Evaporator Pump Override Time Remaining

Evaporator Refrigerant Pressure

Evaporator Saturated Refrigerant Temperature

Evaporator Water Flow Status

Motor

Active Current Limit Setpoint

Active Current Limit Setpoint Source

BAS Current Limit Setpoint

Starter Power Consumption

Starter Load Power Factor

Average Line Current %RLA

Motor Winding Temperature 1

Motor Winding Temperature 2

Motor Winding Temperature 3

Restart Inhibit Time (MP)

Starter Average Phase Voltage

Starter Current L1 %RLA

Table 12. Other items available for custom reports (continued)

Subsystem Description

Page 58: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

58 CTV-PRB009-EN, 03 Nov 2010

Report Contents

Motor (cont.)

Starter Current L1

Starter Current L2 %RLA

Starter Current L2

Starter Current L3 %RLA

Starter Current L3

Starter Energy Consumption Not Resettable

Starter Energy Consumption Resettable

Time of Last Reset

Starter Load Power Factor

Starter Power Consumption

Starter Power Demand

Starter Voltage Phase AB

Starter Voltage Phase BC

Starter Voltage Phase CA

Purge

Purge Top Level Mode

Average Daily Pumpout—7 Days

Carbon Regen Cycle

Chiller On—7 Days

Daily Pumpout—24 Hours

Pumpout Chiller Off—7 Days

Pumpout Chiller On—7 Days

Pumpout—Life

Purge Carbon Tank Temp

Purge Liquid Temperature

Purge Refrigerant Compressor Suction Temp

Time at Last Regeneration

Time Until Next Purge Run

Table 12. Other items available for custom reports (continued)

Subsystem Description

Page 59: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate
Page 60: Tracer AdaptiView™ Control - Heating and Air ... Tracer... · Feedforward adaptive control Feedforward is an open-loop, pred ictive control strategy designed to anticipate and compensate

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.