T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015. 1
Installation Instructions
T/PI/160PRT Immersion Temperature Sensor
Important: Retain these instructions
These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com
2 Requirements
1 Dimensions
2 InSTallaTIon
1 Box ConTenTS
T/PI/160 Installation Instructions (TG100310A)
MANUFACTURED IN EUTREND CONTROL SYSTEMS
LTD UK
T/PI/160
6 mm (0.24”)
155 mm (6.1”) 97 m
m (3
.82”
)
65 mm (2.56”)
8 mm (0.31”)
1 m (3’3”) stainless
steel cable
75 m
m (2
.95”
)
55 mm (2.17”)70 mm (2.76”)
Stainless steel pocket (WS150)
57 mm (2.24”)
Universal Fitting Kit for use in existing pocket (ACC/UF) clip
spring
brass bush
hexagonal socket grub screw
117 mm (4.61”)
MANUFACTURED IN EUTREND CONTROL SYSTEMS
LTD UK
T/PI/160
H O2
-10 °C+14 °F
+160 °C+320 °F
0 %RH 95 %RH
measurement ranges
Protection :IP67, NEMA6
1 m max
-10 °C to +160 °C+14 °F to +320 °F
-40 °C to +50 °C-40 °F to +122 °F
Ensure no stratification (e.g. downstream of mixing valves, junctions)
(minimum distance from junctions =10xd).
d
Cl2Note: WS150 is NOT suitable for use in chlorine rich environments.
135 mm (5.31”)
14 mm (0.53”)
24 mm (0.95”)Ø8 mm
(0.31”)
Ø6.5 mm (0.25”)
R½” (BSPT)143 mm (5.63”)
2 T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015.
T/PI/160 Installation Instructions
3 Mount on Wall
4 Install Pocket
5 Install Sensor into Pocket
6 Remove lid
85 m
m (3
.35”
)
Drill 2 pilot holes
Tighten 2 screws
2 off No 6 screws
(if installing new pocket)
Drill hole for boss
Fix threaded boss
Screw pocket into boss
½” BSPT threaded bossapply sealent to boss thread
use M24 spanner
If using compatible pocket
If using universal adaptor
use 2 mm hexagonal socket key
Push adaptor onto probe
(if using new pocket)
(if using old pocket with grub screws)
Adjust probe length
if pocket has clip retaining groove, push clip over pocket
if pocket has grub screw, discard spring and clip
clip
spring
brass brush
tighten
use 2 mm hexagonal socket key
pocket length
clip engages in groove
tighten screws
probe is forced against end of pocket
tighten screw over bush
spring compession fi tting
Fix to pocket
2 InSTallaTIon (continued)
T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015. 3
Installation Instructions T/PI/160
7 Remove Connector
8 Insert Cable
9 Wire to Controller
10 Replace Connector
Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughtout the operation to prevent damage to the units.
BS EN100015/1 Basic Specifi cation: protection of electrostatic sensitive devices.
either use M20 fl exible conduit or use M16 cable gland
polarity independent
IQ controllerSensor
24 Vdc
IN
Terminate screen at IQ end only
Analogue input channel confi gured for current (I)
IQ system TP/I/22/HF/200-600V(Belden 8761) cable recommended. Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)
Note: If connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V), instead connect to AUX+ (+24V).
2 InSTallaTIon (continued)
4 T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015.
T/PI/160 Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems limitedAlbery House, Springfi eld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
TR CU Certifi cation
11 Replace lid
12 Confi gure Controller
13 Set up IQ Sensor Type
14 Test System 3 DISPoSal
Weee Directive :At the end of their useful life the packaging and product, should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste. Do not burn.
2 InSTallaTIon (continued)
Note: The IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened.
IQ
IQ
or IQ Confi guration Manual (90-1533)IQ3 Confi guration Manual (TE200768)IQ4 Confi guration Manual (TE201263)IQeco Confi guration Manual (TE201089)
It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with fi rmware version 2.1 or greater, or IQ3/4 series controllers, the following SET Unique Sensor Reference should be used:
PRT Sensor -10+160 (°C) PRT Sensor +14+320 (°F)
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defi ned in adjacent table. Note that for IQ3/4 the scaling mode and exponent do not need to be set up.
For all other IQ controllers see Sensor Scaling Reference Card (TB100521A).
Y input type 2 (current)
E Exponent 3
Units °C °F
U Upper 160 320
L Lower -10 14
P Points 2 2
x Ix Ox Ox
1 4 -10 14
2 20 160 320
PRT Sensor (-10 °C +160 °C, +14 °F +320 °F)
IQMANUFACTURED IN EUTREND CONTROL SYSTEMS
LTD UK
T/PI/160
∆ T