TO MEASURE NOT MODEL:Case Study – Purdue University

Center for High Performance Design at the Ray W. Herrick Labs

I2SL Annual ConferenceSan Diego, CaliforniaSeptember 21-23, 2015

2015

Presented by: Dave Sereno, PE, LEED AP / Jeff Cappelle, PE, LEED AP

Page 2: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Learning Objectives

Understand error margins in Energy Modeling and CFDs (Computational Fluid Dynamics)—and how they relate to both sustainable design and lab safety.

Understand Data Acquisition System Architectures—and the importance of ‘right tool for the job’ options/choices to be made early in a project.

Understand the keys to measurement, metering and baseline when predicting building systems performance.

1

2

3

Page 3: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Presenters

Dave Sereno, PE, LEED APPrincipal

[email protected]

Jeff Cappelle, PE, LEED APMechanical Engineer

[email protected]

Page 4: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Purdue UniversityCenter for High Performance Design at the Ray W. Herrick Labs

Photography ©Brad Feinknopf 2013

Page 5: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Living Laboratories

Psychrometric Chambers Laboratory

Thermal Systems Laboratory

Air Quality Chamber

Page 6: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

An in situ HVAC research factory.

Thermal Systems Laboratory• Raw idea• Bench top• Still very much “what if” stage

Psychrometric Chambers Laboratory• Commercially viable• Test in 7,000 ft3 chambers• Precision energy balance is end goal

Living Laboratories• Four 20-person office suites• Highly reconfigurable• Dedicated empirical baseline• Quantifiable-primarily;

qualitative-secondarily

Page 7: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

VerificationLaboratory Program

Page 8: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Site

Geothermal Borefields

Explosion Relief and

Fuel Storage Zone

Southern Quad

Page 9: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Site: GeoExchangeNot Your Basic Bore Field

Informing geothermal model through measurement:

Test Ground Coupled Heat Pump Experimentally

Validate numerical models based on the test results

Develop a robust validated model

Analysis of the numerical models

Page 10: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Suite of Delta T’s & The Carnot Efficiency

• Variable Refrigerant systems

• GeoExchange systems

• Energy recovery chillers

• Absorption chillers

• Stirling engines

• Chilled beams, chilled sails

• Radiant heating and cooling panels

• Compressor test stands

• Gas fired boilers• Heat pumps

Photography ©Brad Feinknopf 2013

ηTH, CARNOT = 1 -TL

TH

The Thermodynamicist’s Playground

Page 11: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Purdue Herrick: BTU/Delta T Navigated Highway

Illustration © Affiliated Engineers, Inc.

Page 12: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Living Laboratories

Concept: Four open-plan, occupied, side-by-side office spaces with reconfigurable envelope, lighting, and HVAC/comfort delivery systems and controls. The facilities allow independent monitoring and environmental control with occupant-environment interaction.

Features:• Two baseline labs. Two experimental

labs: hydronic and air.• Highly reconfigurable, modular construction• Rigorously instrumented• Dedicated baseline (aka “placebo” spaces)• Ease of device and instrumentation accessibility and changeover.

Modular, flexible and reconfigurable – comparison and evaluation of design and control options

Page 13: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Living LaboratoriesHydronic Lab

Measurement and Verification

Page 14: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Living LaboratoriesAir Lab

Measurement and Verification

Page 15: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Displacement Ventilation

1. Fresher Air2. Personalized Cooling3. Quiet4. Energy Savings5. Interior Design

Living Lab (Hydronic) Living Lab (Air)

Page 16: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Photography ©Brad Feinknopf 2013

Photography ©Brad Feinknopf 2013

Reconfigurable Double Skin Façade

Page 17: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Living Laboratory, Airside

Page 18: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

ViabilitySustainability Submitted for LEED Silver; received LEED Gold

Blue is the new greenApproaching 50% annual reduction over ASHRAE 90.1

Energy Efficiency Water Efficiency

Page 19: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Data Acquisition System Architecture

BMS*

*Proprietary: Fire Alarm, Lighting, Security

50% R&D

50%BMS*

CONTROL POINT VOLUME

Typical Physical SciencesR&D Lab

Typical R&D Lab/Office Building

Page 20: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Controls: Languages Spoken

Page 21: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Issues that Drive the Architecture

Page 22: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

BMS• Cost• Creature Comfort• Energy Management• Fault Detection• Maintenance Staff• Predictive Wet Bulb• Preventive Maintenance• Robust/Bulletproof• Trend Logging

PLC

• Integration• Safety

SCADA and/or Network Level• Business/Process Network • Display • Enterprise Network • Historian

U.U.T.• Automation• Creativity• Dexterity given to

Change• FDA• High Accuracy/High

Repeatability• High Sampling Rates 10

Hz, 10,000 Hz• IP/Control/Data Security• Legal/IP• Regulation• Software Maintenance• Synchronization vs Time

Stamping

Page 23: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Purdue Network

Illus

tratio

n ©

Affi

liate

d En

gine

ers,

Inc.

Page 24: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via CFD ModelingOptics Lab – Baseline

Baseline LayoutLaser Table Microenvironment Velocity Streamlines

Page 25: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via CFD ModelingOptics Lab – Option 1

Velocity Section StreamlinesPerimeter

Supply

Central Return

Page 26: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via CFD ModelingOptics Lab – Option 1

Velocity Profile Section

Page 27: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via CFD ModelingOptics Lab – Baseline

Table Perimeter

Overhead Ceiling Supply Diffuser (Typ-2)

HEPA System Wall Return

Baseline Layout – Velocity Profile 9 Inches above Table

Page 28: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via Empirical MeasurementAir Quality Chamber

Particle Image Velocimetry Measurement In PIV measurement, the air is seeded with tracer particles for flow visualization. The particles are sufficiently small to be assumed to completely follow the flow dynamics.

Page 29: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Air Quality Via Empirical Measurement Current Subject Environment ExamplesInfectious disease air side transmission: e.g., Ebola, Measles

Clean Rooms: Biological, Semi-Conductor, Nanofabrication

Aerospace: Thermal comfort, humidification, cabin pressurization, air filtration

Page 30: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

Photography ©Brad Feinknopf 2013

Clean, Bright, Lines of Sight

Page 31: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

“Research in Herrick’s new facilities will attack some of the most daunting and complex problems confronting the world, such as rising energy consumption and environmental pollution, climate change, public health, comfort and security, and issues associated with an aging population.“

- Leah Jamieson, The John A Edwardson

Dean of Engineering/Ransburg Distinguished

Professor of Electrical & Computer Engineering

Page 32: To Measure Not Model: Case Study -- Purdue University Center for High Performance Design at the Ray W. Herrick Labs

TO MEASURE NOT MODEL:Case Study – Purdue University

Center for High Performance Design at the Ray W. Herrick Labs

I2SL Annual ConferenceSan Diego, CaliforniaSeptember 21-23, 2015

2015

Presented by: Dave Sereno, PE, LEED AP / Jeff Cappelle, PE, LEED AP

QUESTIONS