Tmax
MCCBs
16.36 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
AccessoriesElectricalT1-T7
KT3S4
1Forfactoryinstallationaddsuffixgiventoendofcircuitbreakercatalognumberperaccessoryformat.2Mustbeorderedseparatelyforfieldinstallation.3SAT5Discountschedule.
T1withKT3S4
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
T7X1Shunttrip-UVR
Shunt trips -(Standard) 1Forremoteopeningofcircuitbreaker.Guaranteedoperationforavoltageofbetween75-110%oftheratedpowersupplyvoltage.T1-T6mountsinthelefthandcavitycannotbeusedwithUVRon2-3Pbreakers
Factory Installation 1 Field Installation
Frame Size Voltage Catalognumbersuffix
List price adder Catalognumber List
Price
T1-T3
480-500VAC S1
$ 535
KT3S1
$ 490
220-250VAC/DC S2 KT3S2380-440VAC S3 KT3S3
110-125VAC/DC S4 KT3S448-60VAC/DC S7 KT3S724-30VAC/DC S8 KT3S8
12VDC S9 KT3S9
Ts3
480VAC/250VDC S1
535
KTS3S1
490
240 VAC S2 KTS3S2120VAC/125VDC S4 KTS3S4
48VDC S7 KTS3S724VAC/VDC S8 KTS3S8
12VDC S9 KTS3S9
T4,T5,T63
480-500VAC S1
535
KT5S1
490
220/250VAC/DC S2 KT5S2380-440VAC S3 KT5S3
110-125VAC/DC S4 KT5S448-60VAC/DC S7 KT5S724VAC/DC S8 KT5S8
12VDC S9 KT5S9
T7
415-440VAC S1
535
KT7XS1
490
380-400VAC S2 KT7XS2240-250VAC/DC S3 KT7XS3220-240VAC/DC S4 KT7XS4120-127VAC/DC S5 KT7XS5110-120VAC/DC S6 KT7XS6
60VAC/DC S7 KT7XS748VAC/DC S8 KT7XS830VAC/DC S9 KT7XS924VAC/DC S0 KT7XS0
Shunt trip connector (REQUIREDforTs3) 2 Field Kit
Ts3 FixedMount2 Includedwhenshunttripfactoryinstalled KTS3C-SU $ 45Ts3 Draw-out2 Includedwhenshunttripfactoryinstalled KTS3C-SUP
Shunt trips(PermanentSupply) 1Forremoteopeningofcircuitbreaker.Guaranteedoperationforavoltageofbetween75-110%oftheratedpowersupplyvoltage.Theseshunttripshavemuchlowerpowerconsumption.
Factory Installation 1 Field Installation
Frame Size Voltage Catalognumbersuffix
List price adder Catalognumber List
Price
Ts3 24VDC SA $ 535 KTS3SA $ 490120VAC SB KTS3SB
T4,T5,T6324-30VDC SA 535 KT5SA 490110/120/VAC SB KT5SB
Shunt trip connector (REQUIREDforTs3) 2 Field Kit
Ts3 FixedMount2 Includedwhenshunttripfactoryinstalled KTS3C-SU $ 45Draw-out2 Includedwhenshunttripfactoryinstalled KTS3C-SUP
TmaxMCCBs
Low Voltage Products & Systems 16.37ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
AccessoriesElectricalT1-T7
T7X1Shunttrip-UVR
KT3U2
Undervoltage release - UVRWilltripcircuitbreakerwhenconnectedvoltagedropsto35-70%oftheundervoltagereleasevoltagerating.Willallowcircuitbreakertoclosewhenvoltageisapproximately85%oftheratedvoltage.T1-T6mountsinthelefthandcavitycannotbeusedwithshunttripon2-3Pbreakers
Factory Installation 1 Field Installation
Frame Size Voltage Catalognumbersuffix
List price adder Catalognumber List
Price
T1-T3
480-500VAC U1
$ 535
KT3U1
$ 490
220-250VAC/DC U2 KT3U2380-440VAC U3 KT3U3
110-125VAC/DC U4 KT3U460VAC/DC U5 KT3U548VAC/DC U7 KT3U7
24-30VAC/DC U8 KT3U8
Ts3
480VAC U1
535
KTS3U1
490
240VAC U2 KTS3U224VAC U3 KTS3U3
120VAC U4 KTS3U4250VDC U5 KTS3U5125VDC U6 KTS3U648VDC U7 KTS3U724VDC U8 KTS3U8
T4,T5,T63
480-500VAC U1
535
KT5U1
490
220/250VAC/DC U2 KT5U2380-440VAC U3 KT5U3
110-125VAC/DC U4 KT5U460VAC/DC U5 KT5U548VAC/DC U7 KT5U724VAC/DC U8 KT5U8
T7
415-440VAC U1
535
KT7XU1
490
380-400VAC U2 KT7XU2240-250VAC/DC U3 KT7XU3220-240VAC/DC U4 KT7XU4120-127VAC/DC U5 KT7XU5110-120VAC/DC U6 KT7XU6
60VAC/DC U7 KT7XU748VAC/DC U8 KT7XU830VAC/DC U9 KT7XU924VAC/DC U0 KT7XU0
Undervoltage trip connector (REQUIREDforTs3) 2 Field Kit
Ts3 FixedMount2 Includedwhenundervoltagefactoryinstalled KTS3C-SU $ 45Plug-In/Draw-out2 Includedwhenundervoltagefactoryinstalled KTS3C-SUP
1Forfactoryinstallationaddsuffixgiventoendofcircuitbreakercatalognumberperaccessoryformat.2Mustbeorderedseparatelyforfieldinstallation.3SAT5Discountschedule.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
Tmax
MCCBs
16.38 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
AccessoriesElectricalT1-T7
KTS3AS
T1withK3TAS
Auxiliary contacts - AUX 1Auxiliarycontactsareforindicationofthecircuitbreakeropen-closed.Bellalarmcontacts(BA)canbeusedtoindicatecircuitbreakertripped.
Frame SizeFactory Installation 1 Field Installation
Catalognumbersuffix
List price adder Catalognumber List
Price
T1-T321 Form C + 1BA A $ 433 KT3AS $ 3803 Form C + 1BA A3 770 KT3AS3 725
3 Form C + 1BA 24VDC A3AU 770 KT3AS3-AU 725T2 T2 PR221DS 1 Form C + 1BA A 433 KT2AS-E 380
Ts3 2 Form C A 430 KTS3AS 2751 Form C+ 1 BA BA KTS3BA 380
T4,T5,T641FormC+1BA250VAC/VDC A 433 KT5AS 3883FormC+1BA250VAC/VDC A3 770 KT5AS3 725
3 Form C + 1BA 24VDC A3AU 770 KT5AS3-AU 725
T7
1FormC+1BA400VAC/250VDC A
446
KT7AS
3962FormC400VAC/250VDC A2 KT7XAS21 Form C + 1BA 24VDC AAU KT7AS-AU
2 Form C 24VDC A2AU KT7XAS2-AU
Auxiliary contact connector (REQUIREDforTs3) 3 Field Kit
Ts3 FixedMount3 IncludedIncluded
KTS3C-AB $ 45Plug-In/Drawout3 KTS3C-ABP
1Forfactoryinstallationaddsuffixtoendofbreakerpartnumberperaccessoryformat.2NotcompatibleforT2withPR221DStripunit.3Mustbeorderedseparatelyforfieldinstallation.4SAT5Discountschedule.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
TmaxMCCBs
Low Voltage Products & Systems 16.39ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
AccessoriesMotoroperatorsT1-T7
KT3M1
KTS3M2
KT5M2
Electrical operatorsAllowsremoteopeningandclosingofcircuitbreaker
Frame size Voltage Catalognumber
Listprice
Solenoid operator
T1-T3 48-60VDC KT3M1 $ 850110-250VAC/DC KT3M2
Direct action motor operator
Ts3
240VAC/250VDC KTS3M2
1,799120VAC/125VDC KTS3M448VDC KTS3M724VDC KTS3M8
Motor operator connector (REQUIREDforTs3) 1
Ts3 FixedMount1 KTS3C-M 45Plug-In/Draw-out1 KTS3C-MP
Stored energy motor operator
T4,T5
220-250VAC/DC KT5M2
2,385110--125-VAC/DC KT5M448-60VDC KT5M7
24VDC KT5M8
Contact for remote/manual operation (storedenergyoperator)T4,T5,T62 - KT5MA 220
Stored energy motor operator
T6
220-250VAC/DC KT6M2
4,990110--125-VAC/DC KT6M4
48-60VDC KT6M724VDC KT6M8380VAC KT6M3
1Mustbeorderedseparatelyforfieldinstallation2SAT5Discountschedule.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
Tmax
MCCBs
16.40 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
AccessoriesTrip units
1AlwayssuppliedwithPR332/Ptripunit.2MustbeorderedwhenusingPR330/D-M.3DiscountscheduleEDX.
Frame Size Catalognumber
List Price
Rating plugs
T7
400A Rating plug KT7X0400RP
$ 125600A Rating plug KT7X0600RP800Ratingplug KT7X0800RP
1000A Rating plug KT7X1000RP1200 Rating plug KT7X1200RP
Modules for T7 PR332 electronic trip units
T7 Communicationmodule(ModbusRTU) PR330/D-M 4,500Battery power supply unit 1 PR030/B 275
Neutral current transformers (requiredfor4wiregroundfaultsystems)
T4100A KT4NCT-100
300150A KT4NCT-150250A KT4NCT-250
T5 300A KT5NCT-300 300400A KT5NCT-400
T6 600A KT6NCT-600 770800A KT6NCT-800
Test setsTestandconfigurationunit3 PR010/T 12,500
Tripcoiltest-allTmaxelectronictripunitexceptPR33* K7TUT 210ExternalBluetoothcommunicationmodule1
IncludesdiagnosticsoftwareforModbus/BluetoothnetworksBT030 3,335
Actuator moduleT7 Actuator module 2 PR330/R-T7 700
Discount schedule SAT — T6, T7 Accessories Discount schedule SAT5 — T4-T5Accessories
TmaxMCCBs
Low Voltage Products & Systems 16.41ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
Technical dataShunttrips/Undervoltages
Standard shunt trip
VoltageInrushPowerConsumption
T1,T2,T3 Ts3 T4,T5,T6 T7AC(VA) DC(W) AC(VA) DC(W) AC(VA) DC(W) AC(VA) DC(W)
12 VDC - 50 - 120 - 150 - -24VAC/DC - - 100 100 or 4 1 - - 300 300
24…30VAC/DC 50 50 - - 150 150 - -30VAC/DC - - - - - - 300 30048VAC/DC - - - 120 - - 300 300
48…60VAC/DC 60 60 - - 150 150 - -60VAC/DC - - - - - - 300 300
100…120VAC/DC - - 100 or 4 1 - - - 300 300120…127VAC/DC - - - - - - 300 300
110…127VAC110…125VDC 50 50 - 120 150 150 - -220…240VAC/DC - - - - - - 300 300
220…240VAC220…250VDC 50 50 100 120 150 150 - -240…250VAC/DC - - - - - - 300 300380…400VAC - - - - - - 300 -380…440VAC 55 - - - 150 - - -415…440VAC - - - - - - 300 -
480VAC - - 100 - - - - -480…525VAC 55 - - - 150 - - -
OpeningTime(ms) 15 15 ≤15 ≤15 15 15 20 20
Permanent supply shunt trip
Voltage T4,T5,T6AC(VA) DC(W)
24VAC/DC 4 4100…120 VAC 4 -
Undervoltage
VoltagePower consumption during permanent operation
T1,T2,T3 Ts3 T4,T5,T6 T7AC(VA) DC(W) AC(VA) DC(W) AC(VA) DC(W) AC(VA) DC(W)
24VAC/DC - - 6 3 - - 3.5 3.524…30VAC/DC 1.5 1.5 - - 6 3 - -
30VAC/DC - - - - - - 3.5 3.548VAC/DC 1 1 6 3 6 3 - -60VAV/DC 1 1 - - 6 3 - -
110…120VAC/DC - - 6 - - - 3.5 3.5120…127VAC/DC - - - - - - 3.5 3.5
110…127VAC110…125VDC 2 2 - - 6 3 - -220…240VAC/DC - - - - - - 3.5 3.5
220…240VAC220…250VDC 2.5 2.5 - 3 6 3 - -220…250VAC - - 6 - - - - -
240…250VAC/DC - - - - - - 3.5 3.5380…400VAC - - - - - - 3.5 -380…440VAC 3 - - - 6 - - -415-440VAC - - - - - - 3.5 -480…525VAC 4 - - - 6 - - -
480VAC - - 6 - - - - -OpeningTime(ms) 15 15 ≤18 ≤18 ≤25 ≤25 ≤25 ≤25
1Shunttrippermanentsupply
Tmax
MCCBs
16.42 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
Technical dataElectrical operators
Electrical operator, T1-T3Rated Voltage AC DC
- 48…60110...250 110...250
OperatingVoltage 85…110%UnInrushpowerabsorptionduringoperation 1800(VA) 1000(W)
Poweronstandby <100(mW)
Time opening(s) < 0.1closing(s) < 0.1
Minimumcontrolimpulsetimeonopeningandclosing(ms) >100
Thisunitispermanentlysuppliedonstandby,acontrolisappliedbymeansofexternalcontactinalowpowercircuit.Contactcharacteristics:VoltageAC/DC=24VCurrent50mA
Electrical operator, Ts3Rated Voltage AC DC
- 24- 48…60
120 125240 250440 -
OperatingVoltage 85…110%UnInrushpowerabsorption 500(VA) 500(W)Servicepowerabsorption 350(VA) 350(W)
Timeconstant(ms) 18
Duration opening(s) 0.1closing(s) 0.1
Minimumdurationoftheopeningandclosingcommandimpulse(ms) ≥150
Electrical operator, T4-T5Voltage AC DC
- 24- 48…60
110…125 110…125220-250 220-250
380 -OperatingVoltage 85…110%
Inrushpowerconsumption ≤ 300VA ≤ 300WInservicepowerconsumption ≤150VA ≤150W
Durationopening(s) 1.5closing(s) < 0.1resetting(s) 3
Minimumdurationoftheopeningandclosingcommandimpulse(ms) ≥100
Electrical operator, T6Voltage AC DC
- 24- 48…60
110-125 110-125220-250 220-250
380 -OperatingVoltage 85…110%
Inrushpowerconsumption ≤ 400VA ≤ 400WInservicepowerconsumption ≤150VA ≤150W
Durationopening(s) 3closing(s) < 0.1resetting(s) 5
Minimumdurationoftheopeningandclosingcommandimpulse(ms) ≥100
TmaxMCCBs
Low Voltage Products & Systems 16.43ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
AccessoriesMechanicalT1-T7
1 Comesstandardwithhighprofileterminalcovers.2 Usesfrontextendedspreadedterminals...refertotechnicalcatalog.3 DiscountscheduleSA.
Standard cable terminal
Frame Wire Size Catalognumber(setof3)
ListPrice
Catalognumber(setof4)
ListPrice
T1 14AWG-1/0 Integral — Integral —T2 14AWG-1/0 KT2100-3 $ 9 KT2100-4 $ 12
T3 14AWG-1/0 KT3100-3 9 KT3100-4 124AWG-300kcmil KT3225-3 18 KT3225-4 24
Ts3
14-2 K3TA 3 6 K3TA-4 3 814-1/0 K4TB 3 6 K4TB-4 3 82-4/0 K4TC 3 6 K4TC-4 3 84-300kcmil K4TD 3 15 K4TD-4 3 20
T4 14AWG-1/0 KT4100-3 9 KT4100-4 126AWG-350kcmil KT4250-3 30 KT4250-4 40
T5 250kcmil-500kcmil KT5300-3 45 KT5300-4 60T51 (2)3/0-250kcmil KT5400-3 45 KT5400-4 60T52 (2)3/0-500kcmil KT5600-3 225 — —T6 (2)250-500kcmil3 K6TH 3 75 K6TH-4 3 100T6 1 (3)2/0-400kcmil3 K6TJ 3 135 K6TJ-4 3 180T7 1 (4)4/0-500kcmil KT7X1200-3 560 KT7X1200-4 747
Standard cable lug kits with power control taps
Frame Wire Size Catalognumber(setof3)
ListPrice
Catalognumber(setof4)
ListPrice
T3 14AWG-1/0 KT3100-3C $ 16 KT3100-4C $ 194AWG-300kcmil KT3225-3C 18 KT3225-4C 31
Ts314AWG-1/0 K4TBC 12 K4TBC-4 202AWG-4/0 K4TCC 12 K4TCC-4 204AWG-300kcmil K4TDC 21 K4TDC-4 31
T4 14AWG-1/0 KT4100-3C 15 KT4100-4C 206AWG-350kcmil KT4250-3C 36 KT4250-4C 48
T5 250kcmil-500kcmil KT5300-3C 51 KT5300-4C 68T51 (2)3/0-250kcmil KT5400-3C 51 KT5400-4C 68T6 (2)250-500kcmil K6THC 3 81 K6THC-4 3 109T6 2 (3)2/0-400kcmil K6TJC 3 141 K6TJC-4 3 190
Terminal covers for fixed breakers -Lowprofile-kitincludestwopieces
Frame Catalognumber(3pole)
ListPrice
Catalognumber(4pole)
ListPrice
T1 KT1LTC-3 $ 35 KT1LTC-4 $ 47T2 KT2LTC-3 40 KT2LTC-4 54T3 KT3LTC-3 50 KT3LTC-4 68Ts3 KTS3LTC-3 55 KTS3LTC-4 74T4 KT4LTC-3 55 KT4LTC-4 74T5 KT5LTC-3 60 KT5LTC-4 81T6 KT6LTC-3 75 KT6LTC-4 101T7 KT7XLTC-3 80 KT7XLTC-4 108
Terminal covers for fixed breakers -Highprofile-kitincludestwopieces
Frame Catalognumber(3pole)
ListPrice
Catalognumber(4pole)
Listprice
T1 KT1HTC-3 $ 37 KT1HTC-4 $ 50T2 KT2HTC-3 43 KT2HTC-4 58T3 KT3HTC-3 53 KT3HTC-4 72Ts3 KTS3HTC-3 58 KTS3HTC-4 78T4 KT4HTC-3 58 KT4HTC-4 78T5 KT5HTC-3 63 KT5HTC-4 85T6 KT6HTC-3 85 KT6HTC-4 108T7 KT7XHTC-3 90 KT7XHTC-4 115
KT3100-3
KT1HTC-3
KT4LTC-3
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
Tmax
MCCBs
16.44 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
AccessoriesMechanicalT1-T7
KT2EF-3
KT2R-3
KT4EF-_
Phase barriers -Lowprofile100mm-3.93inFrame 4pcs(3p) List
Price 6pcs(4p) ListPrice
T1-T3 KT3PBL-3 $ 28 KT3PBL-4 $ 42T4-T5 KT5PBL-3 28 KT5PBL-4 42T6 KT6PBL-3 42 KT6PBL-4 57T7 KT7PBL-3 50 KT7PBL-4 68
Phase barriers -Highprofile200mm-7.87in
Frame 4pcs(3p) ListPrice 6pcs(4p) List
Price
T1-T3 KT3PBH-3 $ 42 KT3PBH-4 $ 63T4-T5 KT5PBH-3 42 KT5PBH-4 63T7 KT7PBH-3 67 KT7PBH-4 90
Saddle terminals for Copper Cables-IEC
Frame Catalognumber(Setof3)
ListPrice
Catalognumber(Setof4)
ListPrice
T2 KT2100S-3 $ 34 KT2100S-4 $ 46T3 KT3225S-3 52 KT3225S-4 70Ts3 K4TES 3 30 K4TES-4 4 40T4 KT4250S-3 41 KT4250S-4 55T5 KT5300S-3 270 KT5300S-4 365
Extended front terminals
Frame Catalognumber(setof3)
ListPrice
Catalognumber(setof4)
ListPrice
T2 KT2EF-3 $ 26 KT2EF-4 $ 35T3 KT3EF-3 33 KT3EF-4 44Ts3 KTS3EF-3 65 KTS3EF-4 88T4 KT4EF-3 55 KT4EF-4 73T5 KT5EF-3 115 KT5EF-4 155
Rear terminals 1
Frame Catalognumber(setof3)
ListPrice
Catalognumber(setof4)
ListPrice
T2 KT2R-3 $ 78 KT2R-4 $ 105T3 KT3R-3 98 KT3R-4 131T4 KT4R-3 60 KT4R-4 80T5 KT5R-3 122 KT5R-4 163T6 KT6R-3 350 KT6R-4 473T7 KT7R-3 407 KT7R-4 550
1Includeslowprofileterminalcover.2Includeshighprofileterminalcover.3Setofsix,DiscountscheduleSA.4Setofeight,DiscountscheduleSA.
Distribution cable lug kit 2
Frame Wire Size Catalognumber(setof3)
ListPrice
Catalognumber(setof4)
ListPrice
T3 (6)#14-6 KT3TN $ 125 KT3TN-4 $ 167Ts3 (6)#14-6 KTS3TN 125 KTS3TN-4 169T4 (6)#14-6 KT4TN 125 KT4TN-4 167T5 (6)#14-1/0 KT5TGD 240 KT5TGD-4 320
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
TmaxMCCBs
Low Voltage Products & Systems 16.45ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
AccessoriesMechanical,T1-T7Lockingdevicesandhandleoperators
KT3LD
OHB65J6
KT5RH
OHB125J10
Padlock locking deviceFrame Style Locking Position Breaker
Mounting Catalognumber ListPrice
T1,T2,T3 PLL OPEN/CLOSED Fixed KT3LD $ 35OPEN KT3LDO
Ts3 FLD OPEN Fixed,Plug-In KTS3FLD 87Draw-0ut KTS3FLDW 125
T4-T5 FLD OPEN Fixed,Plug-In KT5FLD 40Draw-out KT5FLDW 55
T6 FLD OPEN Fixed,Plug-In KT6FLD 220Draw-out KT6FLDW 240
T7 PLL OPEN Fixed,Drawout KT7LDO 260
Keylocks-rotary handle mechanism
Frame Style Locking Position Keys Catalognumber ListPrice
T1,T2,T3 RHL OPEN/CLOSED Different KT3RHL3 $ 94Ts3 - OPEN Different KTS3KLFD 58T4-T5 KLF-D OPEN Different KT5KLFD 58T6 KLF-D OPEN Different KT6KLFD 68T7 KLF-D OPEN Different KT7KLFD 79
Direct mount rotary operator handle
Frame BreakerMounting Catalognumber List
Price
T1,T2,T3 Fixed,Plug-In KT3RH $ 146Ts3 Fixed,Plug-In KTS3RH 150Ts3 Draw-out KTS3RHW 150T5 Fixed,Plug-In KT5RH 135T5 Draw-0ut KT5RHW 135T6 Fixed,Plug-In KT6RH 450T6 Draw-out KT6RHW 450T7 Fixed,Plug-In KT7RH 450
Variable depth handle operators
Frame NEMArating Mechanismcatalognumber
ListPrice Shaftcatalognumber List
Price Handle catalog
numberList
Price
T1—T3
1,3R,12 — — — — OHB65J6 1OHY65J6 1
$ 80
4, 4X KT3VD-M $ 72 OXP6X430(16.9”)2 $ 28 OHB80L6 1OHY80L6 1
130
1 — — KT3VD-S(11.8”) 35 KT3VD-H 87
Ts3
1,3R,12 — — OXP10X148(5.8")2 24 OHB95J10 1OHY95J10 1
80
4,4X KTS3VD-M 72 OXP10X225(8.9")1 26 OHB95L10 1OHY95L10 1
120
— — — OXP10X500(19.7")1 32 — —1 — — KT3VD-S(20") 35 KTS3VD-H 87
T4-T5
1,3R,12 — — OXP10X148(5.8")1 24 OHB95J10 1OHY95J10
80
4,4X KT5VD-M 65 OXP10X225(8.9")1 26 OHB95L10 1OHY95L10 1
120
— — — OXP10X500(19.7")1 32 — —— — — — — — —1 — — KT5VD-S(19.7") 36 KT5VD-H 87
T6
1,3R,12 — — OXP10X148(5.8")1 24 OHB125J10 1OHY125J10 1
90
4,4X KT6VD-M 370 OXP10X225(8.9")1 26 OHB125L10 1 130
— — — OXP10X500(19.7")1 32 — —1 — — KT5VD-S(19.7) 36 KT6VD-H 210
T7
1,3R,12 — — OXP10X148(5.8")1 24 OHB175J10 1OHY175J10 1
100
— KT7VD-M 370 OXP10X225(8.9")1 26 OHB175L10 1 140
— — — OXP10X500(19.7")1 32 — —1 — — KT7VD-S(19.7") 130 KT7VD-H 231
1DiscountscheduleSH.2DiscountscheduleH6.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
Tmax
MCCBs
16.46 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
KT4PMK(onbackofbreaker)
KT4PFVR
KT2PFF+KT2PMK(onbackofbreaker)+breaker
AccessoriesMechanical,T1-T7
Plug-in kits 1
Frame CatalognumberAdaptermovingpart
ListPrice
Catalognumberfixedpart
List Price
T2-3polewithfrontterminals KT2PMK $ 171 KT2PFF $ 238T3-3polewithfrontterminals KT3PMK 190 KT3PFF 264
T2-T3FixedpartsacceptthesamecableandrearterminalkitsasthecircuitbreakersTs33polewithfrontterminals KTS3PMK 250 KTS3PFF 305Ts33polewithrearterminals KTS3PFRT43polewithextendedfrontterminal KT4PFEF 710T43polewithrearhorizontalterminals KT4PMK 250 KT4PFHR 766T43polewithrearverticalterminals KT4PFVR 766
400AT5400A3polewithextendedfrontterminal KT5PFEF 810T5400A3polewithrearhorizontalterminal KT5PMK 350 KT5PFHR 866T5400A3polewithrearverticalterminal KT5PFVR 866
600AT5600A3polewithextendedfrontterminal KT56PFEF 1,158T5600A3polewithrearhorizontalterminal KT56PMK 501 KT56PFHR 1,238T5600A3polewithrearverticalterminal KT56PFVR 1,238
1Plugconnectors(T2-T3),Adaptors(T4-T5),requiredwhenaddingaccessoriestoplug-inbreakers.2SAT5Discountschedule.
Plug connectors, T1-T3Requiredwhenaddingaccessoriestoplug-inbreakers
Plug Connector Catalognumber
Listprice
ShunttriporUVR KT3PC-3 $ 181formCplus1BA KT3PC-6 213formCplus1BA KT3PC-12 24
Adaptors, T4-T6 2Requiredwhenaddingaccessoriestoplug-inordrawoutbreakers
Adaptors Catalognumber
Listprice
1formCplus1BA KT5ADP-6 $ 24Shunttrip/UVR KT5ADP-6 24Stored energy operator KT5ADP-10 30Storedenergyoperatorplusshunttrip/UVR KT5ADP-10 303formCplus1BA KT5ADP-12 35
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
TmaxMCCBs
Low Voltage Products & Systems 16.47ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
1 Adaptors(T4-T6),Slidingcontactblocks(T7)requiredwhenaddingaccessoriestodraw-outbreakers.2 Comesstandardwithhorizontalterminalsfieldconvertibletovertical3 IEC4SAT5Discountschedule.
KT4WMK(onbackofbreaker)
KT5WFVR
AccessoriesT1-T7
Draw-out kits 1
Item CatalognumberAdaptormovingpart
ListPrice
CatalogNumberFixedpart
ListPrice
Ts33polewithfrontterminals KTS3WMK $ 290 KTS3WFF 3 $ 790Ts33polewithrearterminals KTS3WFR 3T43polewithextendedfrontterminal
KT4WMK 290KT4WFEF 816
T43polewithrearhorizontalterminals KT4WFHR 1,021T43polewithrearverticalterminals KT4WFVR 1,021
400AT53polewithextendedfrontterminal KT5WFEF 931T53polewithrearhorizontalterminal KT5WMK 407 KT5WFHR 1,154T53polewithrearverticalterminal KT5WFVR 1,154
600AT53polewithextendedfrontterminal KT56WFEF 1,331T53polewithrearhorizontalterminal KT56WMK 582 KT56WFHR 1,650T53polewithrearverticalterminal KT56WFVR 1,650T63polewithextendedfrontterminal KT6WFEF 3 1,844T63polewithrearhorizontalterminal KT6WMK 670 KT6WFHR 3 1,844T63polewithrearverticalterminal KT6WFVR 2,144T73polewithhorizontal/verticalterminals KT7XWMK 755 KT7WFHR 2 2,567
Adaptors—T4-T6 4Requiredwhenaddingaccessoriestoplug-inordrawoutbreakers
Adaptors Catalognumber
Listprice
1formCplus1BA KT5ADP-6 $ 24Shunttrip/UVR KT5ADP-6 24Stored energy operator KT5ADP-10 30Storedenergyoperatorplusshunttrip/UVR KT5ADP-10 303formCplus1BA KT5ADP-12 35
Sliding contact blocks—T7-Draw-out
Item MovingPartBreaker
ListPrice
FixedPartCradle
ListPrice
Left Block
KT7XSCMP-L $ 160 KT7SCFP-L $ 185
SpringchargingmotorSpringchargedcontactReady to close contactEarlyauxiliarycontactContactfortripcoilreleasetripTrip rest
Center BlockPR331 KT7XSCMP-C 160 KT7XSCFP-C 310PR332
Right BlockAuxiliarycontacts
KT7XSCMP-R 160 KT7XSCFP-R 310ShunttripClosing CoilUndervoltagerelease
Ifatleastoneoftheaccessoriesintableisinstalledonthebreaker-respectivepairofcontactblocksmustbeinstalledonthefixedpart(cradle)andthemovingpart.(breaker)
Position key lock—T7-T7M-X1
Item Catalognumber
ListPrice
Key#20005 KT7XPL2 $ 202Differentkey KT7XPL1Locksdrawoutbreakerinracked-in/testisolation/racked-outposition.
Position key lock accessory—T7-T7M-X1
Item Catalognumber
ListPrice
Key lock accessory KT7XPLA $ 35Accessoryaddedtopositionkeylockallowsbreakertobelockedinracked-outpositiononly.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories
Tmax
MCCBs
16.48 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
AccessoriesT1-T7
KT3MIF2
DIN rail adaptersItem CatalogNumber List Price
T1/T2(mountson35mmDINrail15mmhigh) KT2DIN $ 33T3(mountson35mmDINrail15mmhigh) KT3DIN 41Ts3(mountson75mmDINrail) KTS3DIN 51
Mechanical interlocksT1-T3 CatalogNumber List Price
Slidingbarinterlock-frontmounted(2Breakers) KT3MIF2 $ 625Slidingbarinterlock-frontmounted(3Breakers) KT3MIF3 844
T3RearInterlock-horizontal KT3MI-H 896RearInterlock-vertical KT3MI-V 985
TS3Horizontal KTS3MI-H 798Vertical KTS3MI-V 798
T4-T5 1Interlockframe
MechanicalInterlockframe-horizontal KT5MIR-HB 490MechanicalInterlockframe-vertical KT5MIR-VB 588
Plate typeAT4(F-P-W)T4(F-P-W) KT5MIR-PABT4(F-P-W)T5400(F-P-W)ORT5600(F) KT5MIR-PBCT4(F-P-W)T5600(P-W) KT5MIR-PC 210DT5(F-P-W)T5400(F-P-W)OR630(F) KT5MIR-PDET4(F-P-W)T5600(P-W) KT5MIR-PEFT4(F-P-W)T5600(P-W) KT5MIR-PF
T6620Horizontal KT6MI-H
Vertical KT6MI-VT7 2
CableT7-X1 KT7XMLC 270Mech.interlockplate-fixed KT7XMLPW 670Mech.interlockplate-draw-out KT7XMLPF 670
1T4-T5Completeassemblyconsistsofoneinterlockframeandoneplate.2Tointerlocktwocircuitbreakers,youhavetoorderacablekitandtwoplates.
Discount schedule SAT —T1-Ts3,T6,T7Accessories Discount schedule SAT5 — T4-T5Accessories