three phase split prepayment meterenergynews-ng.com/wp-content/uploads/2018/08/memmcol... · 2018....
TRANSCRIPT
Three Phase Split Prepayment Meter (MMX310 NGS) No. Name Of Item Momas Specification
1. Meter Type Three-phase Split keypad prepayment meter
2. Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3. Wire Type 3-PHASE, 4-WIRES (Direct Connection)
4. Tariff Structure Single
5. Communication MBUS
RS485
PLC
6. Communication protocol DLMS/COSEM MEMMCOL Proprietary
7. Load Control Have load Control
8. Communication Port Infrared / Optical
9. Installation Outdoor Installation(With meter box)
10. Measurement Three Measuring elements (four measuring elements L1,L2,L3,N)
11. Rated Voltage(Un) 240Volts (P - N), 415Volts(P - P)
12. Variation Of Voltage -40% to +10% Vref
13. Frequency 50Hz
14. Frequency Application Range 50Hz+-2%
15. Number Of Terminal Ph – N, N – Ph (symmetrical) 8
16. Accuracy Class 1 (IEC Standard)
17. Common Current Specification 5(100)A
18. Imax 100A
19. Meter Starting Current 0.4% of Ib
MMX310 NGS THREE PHASE SPLIT PREPAYMENT METER
CONNECTION DIAGRAM
20. Meter Metering Current Range Current limit programmable from 0 to Imax using a code generated
by the management software.
21. Power Consumption Of Voltage Circuit <4VA in Voltage Circuit
22. Power Consumption Of Current Circuit 1VA in Current Circuit
23. Meter Constant 1000imp/kWh
24. Display LCD Display with Backlight
25. LCD (Eight digits)
26. Height: 9mm x 4mm
27. Viewing Angle: 160 degrees minimum
28. No. Of Digits For Credit Storage 20 Digit Credit Token
29. Nameplate Language English
30. Calendar Time Nigeria Time
31. Level Of Protection IP54 for meter, IP55 for meter box
32. Operation Temperature Range Upto 60 Celsius
33. Limit Range Of Operation Upto 60 Celsius
34. Limit Range For Storage And Transport upto 70 Celsius
35. Line Type AA-BB-CC-NN
36. Line Drawing Laser Printing in Terminal Cover
37. Sealing Sealing screw for modular box and terminal cover
38. Keypad Keypad on UIU.
39. Meter Number Momas Standard
40. Meter postal address Momas Standard
41. Load threshold Configurable
42. Battery Non- Rechargeable Battery (replaceable)
43. Button One (Display button)
44. Load Relay 3 Channel Load Relay control
45. STS Key change mode Optical Change
Keypad Change
46. Super capacitance No Super Capacitance
47. Service Life (Minimum) 10 years
48. LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
49. Overvoltage rating 415 V ac for 48 hours
50. Reverse Energy Detects and records reverse energy.
51. Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box.
Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
52. Standards STS System: For every meter model, a compliant certificate from
the STS Association will be supplied
IEC 62055-41, IEC 62055-51 (electricity metering, payment systems)
ISO 9001 SANS 1524-1 (electricity vending system)
53. Influence parameters The meter work satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
54. Tamper events Meter behavior
Meter cover open
Terminal cover open
Reverse connection
55. Relative Humidity 96% at 45oC non-condensing
56. Impulse withstand voltage Not less than 6kV
Single Phase Split Prepayment Meter (MMX110 NGS) No. Name Of Item Momas Specification
1 Meter Type Single Phase Split Keypad prepayment Meter
2 Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3 Wire Type 1- Phase, 2-Wire (Direct Connection)
4 Tariff Structure Single Tariff
5 Communication MBUS RS485
PLC 6 Communication protocol DLMS/COSEM
MEMMCOL Proprietary 7 Main Load Control Have Load Control
8 Model Of Meter 240 Volt 5(80)A Smart Electric Energy Meter
9 Communication Port Infrared / Optical
10 Installation Outdoor Installation (With Meter Box)
11 Measurement 2
12 Rated Voltage(Un) 240Volts (P - N)
23 Power Consumption Of Voltage Circuit
<4VA in Voltage Circuit
24 Power Consumption Of Current Circuit
1VA in Current Circuit
25 Meter Constant 1000imp/kWh
26 Display LCD Display with Backlight
CONNECTION DIAGRAM
MMX110 NGS SINGLE PHASE SPLIT PREPAYMENT METER
LCD (Eight digits)
Height: 9mm x 4mm
Viewing Angle: 160 degrees minimum
27 No. Of Digits For Credit Storage 20 Digit Credit Token
28 Nameplate Language English
29 Calendar Time Nigeria Time
30 Level Of Protection IP54 For the Meter IP55 for the meter box
31 Operation Temperature Range Up to 60 degree Celsius
32 Limit Range Of Operation Up to 70 degree Celsius
33 Limit Range For Storage And Transport
Up to 70 degree Celsius
34 Line Type LNNL
35 Line Drawing Laser Printing in terminal cover
36 Sealing Sealing screw for modular box and terminal cover
37 Meter Number Momas Standard
38 Meter postal address Momas Standard
39 Meter Storage For Out port Factory Configurable
40 Load threshold Configurable
41 Button One (Display Button)
42 Load Relay Channel Load Relay Control
45 STS Key change mode Optical Change
Keypad Change
44 Super capacitance No Super Capacitance
45 Service Life (Minimum) 10 years
46 LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
47 Overvoltage rating 415 V ac for 48 hours
48 Reverse Energy Detects and records reverse energy.
49 Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box. Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
50 Standards STS System: For every meter model, a compliant certificate from the STS Association will be supplied IEC 62055-41, IEC 62055-51 (electricity metering, payment systems) ISO 9001 SANS 1524-1 (electricity vending system)
51
Influence parameters
The meter work satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
52 Tamper events Meter behavior Meter cover open Terminal cover open
Reverse connection
53 Relative Humidity 96% at 45oC non-condensing
54 Impulse withstand voltage Not less than 6kV
Single Phase Compact Prepayment Meter (MMX110 NGC) No. Name Of Item Momas Specification
1. Meter Type Single Phase Compact Keypad Prepayment Meter
2. Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3. Wire Type 1- Phase, 2-Wire (Direct Connection)
4. Tariff Structure Single Tariff
5. Communication Keypad (Compact) 6. Communication protocol DLMS/COSEM
MEMMCOL Proprietary 7. Main Load Control Have Load Control
8. Model Of Meter 240 Volt 5(80)A Smart Electric Energy Meter
9. Communication Port Infrared / Optical
10. Installation Outdoor Installation (With Meter Box)
11. Measurement 2
12. Rated Voltage(Un) 240Volts (P - N)
13. Power Consumption Of Voltage Circuit <4VA in Voltage Circuit
14. Power Consumption Of Current Circuit 1VA in Current Circuit
15. Meter Constant 1000imp/kWh
16. Display LCD Display with Backlight
LCD (Eight digits)
Height: 9mm x 4mm
Viewing Angle: 160 degrees minimum
17. No. Of Digits For Credit Storage 20 Digit Credit Token
MMX110 NGC SINGLE PHASE COMPACT PREPAYMENT METER
CONNECTION DIAGRAM
18. Nameplate Language English
19. Calendar Time Nigeria Time
20. Level Of Protection IP54 For the Meter IP55 for the meter box
21. Operation Temperature Range Up to 60 degree Celsius
22. Limit Range Of Operation Up to 70 degree Celsius
23. Limit Range For Storage And Transport Up to 70 degree Celsius
24. Line Type LNNL
25. Line Drawing Laser Printing in terminal cover
26. Sealing Sealing screw for modular box and terminal cover
27. Meter Number Momas Standard
28. Meter postal address Momas Standard
29. Meter Storage For Out port Factory Configurable
30. Load threshold Configurable
31. Button One (Display Button)
32. Load Relay Channel Load Relay Control
33. STS Key change mode Optical Change
34. Keypad Change
35. Super capacitance No Super Capacitance
36. Service Life (Minimum) 10 years
37. LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
38. Overvoltage rating 415 V ac for 48 hours
39. Reverse Energy Detects and records reverse energy.
40. Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box. Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
41. Standards STS System: For every meter model, a compliant certificate from the STS Association will be supplied IEC 62055-41, IEC 62055-51 (electricity metering, payment systems) ISO 9001 SANS 1524-1 (electricity vending system)
42. Influence parameters The meter works satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
43. Tamper events Meter behavior Meter cover open Terminal cover open
Reverse connection
44. Relative Humidity 96% at 45oC non-condensing
45. Impulse withstand voltage Not less than 6kV
Three-Phase Compact Prepayment Meter (MMX310 NGC) No. Name Of Item MOMAS
1. Meter Type Three-phase compact keypad prepayment meter
2. Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3. Wire Type 3-PHASE, 4-WIRES (Direct Connection)
4. Tariff Structure Single
5. Communication Keypad (compact)
6. Communication protocol DLMS/COSEM MEMMCOL Proprietary
7. Load Control Have load Control
8. Communication Port Infrared / Optical
9. Installation Outdoor Installation(With meter box)
10. Measurement Three Measuring elements (four measuring elements L1,L2,L3,N)
11. Rated Voltage(Un) 240Volts (P - N), 415Volts(P - P)
12. Variation Of Voltage -40% to +10% Vref
13. Frequency 50Hz
14. Frequency Application Range 50Hz+-2%
15. Number Of Terminal Ph – N, N – Ph (symmetrical) 8
16. Accuracy Class 1 (IEC Standard)
17. Common Current Specification 5(100)A
18. Imax 100A
19. Meter Starting Current 0.4% of Ib
20. Meter Metering Current Range Current limit programmable from 0 to Imax using a code generated by the management software.
MMX310 NGC THREE PHASE COMPACT PREPAYMENT METER
CONNECTION DIAGRAM
21. Power Consumption Of Voltage Circuit <4VA in Voltage Circuit
22. Power Consumption Of Current Circuit 1VA in Current Circuit
23. Meter Constant 1000imp/kWh
24. Display LCD Display with Backlight
LCD (Eight digits)
Height: 9mm x 4mm
Viewing Angle: 160 degrees minimum
25. No. Of Digits For Credit Storage 20 Digit Credit Token
26. Nameplate Language English
27. Calendar Time Nigeria Time
28. Level Of Protection IP54 for meter, IP55 for meter box
29. Operation Temperature Range Upto 60 Celsius
30. Limit Range Of Operation Upto 60 Celsius
31. Limit Range For Storage And Transport upto 70 Celsius
32. Line Type AA-BB-CC-NN
33. Line Drawing Laser Printing in Terminal Cover
34. Sealing Sealing screw for modular box and terminal cover
35. Keypad keypad is available
36. Meter Number Momas Standard
37. Meter postal address Momas Standard
38. Load threshold Configurable
39. Battery Non- Rechargeable Battery (replaceable)
40. Button One (Display button)
41. Load Relay 3 Channel Load Relay control
42. STS Key change mode Optical Change
Keypad Change
43. Super capacitance No Super Capacitance
44. Service Life (Minimum) 10 years
45. LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
46. Overvoltage rating 415 V ac for 48 hours
47. Reverse Energy Detects and records reverse energy.
48. Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box.
Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
49. Standards STS System: For every meter model, a compliant certificate from the STS Association will be supplied
IEC 62055-41, IEC 62055-51 (electricity metering, payment systems)
ISO 9001 SANS 1524-1 (electricity vending system)
50. Influence parameters The meter works satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
51. Tamper events Meter behavior
Meter cover open
Terminal cover open
Reverse connection
52. Relative Humidity 96% at 45oC non-condensing
53. Impulse withstand voltage Not less than 6kV
Single Phase Smart Prepayment Meter (MMX110 NGG/NGW) No. Name Of Item Momas Specification
1. Meter Type Single Phase Smart Prepayment Meter
2. Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3. Wire Type 1- Phase, 2-Wire (Direct Connection)
4. Tariff Structure Single Tariff
5. Communication MMX110 NGG Wi-Fi or 2G (GPRS)
MMX110 NGW Smart Bundle (Wi-Fi & 2G)
Mobile App to communicate with Meters
6. Communication protocol DLMS/COSEM MEMMCOL Proprietary
7. Main Load Control Have Load Control
8. Model Of Meter 240 Volt 5(80)A Smart Electric Energy Meter
9. Communication Port Infrared / Optical / Wi-Fi
10. Installation Outdoor Installation (With Meter Box)
11. Measurement 2
12. Rated Voltage(Un) 240Volts (P - N)
13. Power Consumption Of Voltage Circuit <4VA in Voltage Circuit
14. Power Consumption Of Current Circuit 1VA in Current Circuit
15. Meter Constant 1000imp/kWh
MMX110 NGG/NGW SINGLE PHASE SMART PREPAYMENT METER
CONNECTION DIAGRAM
16. Display LCD Display with Backlight
LCD (Eight digits)
Height: 9mm x 4mm
Viewing Angle: 160 degrees minimum
17. No. Of Digits For Credit Storage 20 Digit Credit Token
18. Nameplate Language English
19. Calendar Time Nigeria Time
20. Level Of Protection IP54 For the Meter IP55 for the meter box
21. Operation Temperature Range Up to 60 degree Celsius
22. Limit Range Of Operation Up to 70 degree Celsius
23. Limit Range For Storage And Transport Up to 70 degree Celsius
24. Line Type LNNL
25. Line Drawing Laser Printing in terminal cover
26. Sealing Sealing screw for modular box and terminal cover
27. Meter Number Momas Standard
28. Meter postal address Momas Standard
29. Meter Storage For Out port Factory Configurable
30. Load threshold Configurable
31. Button One (Display Button)
32. Load Relay Channel Load Relay Control
33. STS Key change mode Optical Change
Keypad Change
34. Super capacitance No Super Capacitance
35. Service Life (Minimum) 10 years
36. LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
37. Overvoltage rating 415 V ac for 48 hours
38. Reverse Energy Detects and records reverse energy.
39. Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box. Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
40. Standards STS System: For every meter model, a compliant certificate from the STS Association will be supplied IEC 62055-41, IEC 62055-51 (electricity metering, payment systems)
ISO 9001 SANS 1524-1 (electricity vending system)
41. Influence parameters The meter works satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
42. Tamper events Meter behavior Meter cover open Terminal cover open
Reverse connection
43. Relative Humidity 96% at 45oC non-condensing
44. Impulse withstand voltage Not less than 6kV
Three-Phase Smart Prepayment Meter (MMX310 NGG/NGW) No. Name Of Item MOMAS Specification
1 Meter Type Three-phase Smart prepayment meter
2 Normative references IEC Standard ( IEC62053-21, IEC62056-21)
3 Wire Type 3-PHASE, 4-WIRES (Direct Connection)
4 Tariff Structure Single
5 Communication MMX310 NGG Wi-Fi or 2G (GPRS)
MMX310 NGW Smart Bundle (Wi-Fi & 2G)
Mobile App communicate with meters.
6 Communication protocol DLMS/COSEM MEMMCOL Proprietary
7 Load Control Have load Control
9 Communication Port Infrared / Optical / WI-FI
10 Installation Outdoor Installation(With meter box)
11 Measurement Three Measuring elements (four measuring elements L1,L2,L3,N)
12 Rated Voltage(Un) 240Volts (P - N), 415Volts(P - P)
13 Variation Of Voltage -40% to +10% Vref
15 Frequency 50Hz
16 Frequency Application Range 50Hz+-2%
17 Number Of Terminal Ph – N, N – Ph (symmetrical) 8
MMX310 NGG/NGW THREE PHASE SMART PREPAYMENT METER
CONNECTION DIAGRAM
18 Accuracy Class 1 (IEC Standard)
19 Common Current Specification 5(100)A
20 Imax 100A
21 Meter Starting Current 0.4% of Ib
22 Meter Metering Current Range Current limit programmable from 0 to Imax using a code generated by the management software.
23 Power Consumption Of Voltage Circuit <4VA in Voltage Circuit
24 Power Consumption Of Current Circuit 1VA in Current Circuit
25 Meter Constant 1000imp/kWh
26 Display LCD Display with Backlight
LCD (Eight digits)
Height: 9mm x 4mm
Viewing Angle: 160 degrees minimum
27 No. Of Digits For Credit Storage 20 Digit Credit Token
28 Nameplate Language English
29 Calendar Time Nigeria Time
30 Level Of Protection IP54 for meter, IP55 for meter box
31 Operation Temperature Range Upto 60 Celsius
32 Limit Range Of Operation Upto 60 Celsius
33 Limit Range For Storage And Transport upto 70 Celsius
34 Line Type AA-BB-CC-NN
35 Line Drawing Laser Printing in Terminal Cover
36 Sealing Sealing screw for modular box and terminal cover
37 Keypad keypad is available
38 Meter Number Momas Standard
39 Meter postal address Momas Standard
41 Load threshold Configurable
42 Battery Non- Rechargeable Battery (replaceable)
43 Button One (Display button)
44 Load Relay 3 Channel Load Relay control
45 STS Key change mode Optical Change
Keypad Change
46 Super capacitance No Super Capacitance
47 Service Life (Minimum) 10 years
48 LED Indication Indication of the rate of consumption by flashing of LED (flashing rate: 1000 pulses/kWh)
Indication of fraud symbols
49 Overvoltage rating 415 V ac for 48 hours
50 Reverse Energy Detects and records reverse energy.
51 Antifraud system Mechanical system: Presence of a seals on the meter and on the meter box.
Electronic system: Presence of a system that prevents unscrewing the meter or reaching the electric connection points of the meter. The meter switches off the supply in case of an attempt to open it lid or when connection points are handled The meter will resume the supply only if an appropriate management code is entered
52 Standards STS System: For every meter model, a compliant certificate from the STS Association will be supplied
IEC 62055-41, IEC 62055-51 (electricity metering, payment systems)
ISO 9001 SANS 1524-1 (electricity vending system)
53 Influence parameters The meter works satisfactory with guaranteed accuracy limit under the presence of the listed quantities as contained in IEC62053-21
External magnetic fields
Electromagnetic field induction
Radio frequency interference
Vibration etc
Waveform 10% of 3rd harmonics
Electromagnetic H.F. Fields
DC Immunity test 2
54 Tamper events Meter behavior
Meter cover open
Terminal cover open
Reverse connection
55 Relative Humidity 96% at 45oC non-condensing
56 Impulse withstand voltage Not less than 6kV