Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014LACUSIN11 TG B Laboratory measurements of airborne sound insulation TESTS SPECIMENS: 7 SaintGobain Glazing Partition Systems with tesa ® ACX plus 7058. APPLICANT: PERSON OF CONTACT: Jean Francois Outin. TESTS STANDARD: EN ISO 101402:2010. DATES OF TESTS: 3 rd ,6 th ,7 th ,9 th , 17 th and 21 st October, 2014. 18 th November, 2014. DATE OF THE TESTS REPORT: 17 th December, 2014. The technicalowned of the ENAC Nº4/LE456 accreditation fall to Fundación Tecnalia Research & Innovation, the same way as the technical signature of this report. The installations where are performed the measurements according ENAC Nº4/LE456 accreditation belong to the Acoustics Area of Laboratory for Quality Control in Buildings of the Basque Country Government. Notified Laboratory Nº 1292 for acoustic testing. THIS REPORT CONTAINS: Total number of pages: 26 + (4 of ANNEX A). This document includes only and exclusively the tested specimens and the moment and conditions in which those measurements were made. It is expressly forbidden any total or partial reproduction of this document, except with a written conformity from TECNALIA. The test specimens have been subjected to the test asked by the applicant, following the specified procedures in the used standards. Test results are detailed in the inside pages. Uncertainties of measurements complies the recommendations of EN 201402:1994 and they are available to the applicant. This document is a copy in PDF of the original Report, for request of our client. Signature María José de Rozas López Acoustics Laboratory Manager AKUSTIKA ARLOA kudeatzailea: ACOUSTICS AREA managed by: DEPARTAMENTO DE EMPLEO Y POLÍTICAS SOCIALES Dirección de Vivienda Laboratorio de Control de Calidad de la Edificación EMPLEGU ETA GIZARTE POLITIKETAKO SAILA Etxebizitza, Zuzendaritza Eraikuntzaren Kalitate Kontrolerako Laborategia SAINTGOBAIN GLASSOLUTIONS SAINTGOBAIN GLASS France 18 avenue d´Alsace 92400 Courbevoie France

Upload: others

Post on 18-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

Page 1 of 26 (+ Annex A)

4 / L E 4 5 6

 Tests Report Nº B2014‐LACUS‐IN‐11 TG B 

Laboratory measurements of airborne sound insulation 

 TESTS SPECIMENS: 7 Saint‐Gobain Glazing Partition Systems with tesa® ACXplus 7058.  

  APPLICANT: 

   

PERSON OF CONTACT: Jean Francois Outin. 

TESTS STANDARD: EN ISO 10140‐2:2010.  DATES OF TESTS: 3rd, 6th, 7th, 9th, 17th and 21st October, 2014.  

  18th November, 2014.   DATE OF THE TESTS REPORT: 17th December, 2014. 

 

 

 

 

 

 

The technical‐owned of the ENAC Nº4/LE456 accreditation fall to Fundación Tecnalia Research &  Innovation, the same way as the technical signature of this report. 

The  installations  where  are  performed  the  measurements  according  ENAC  Nº4/LE456  accreditation  belong  to  the Acoustics Area of Laboratory for Quality Control in Buildings of the Basque Country Government. Notified Laboratory Nº 1292 for acoustic testing.  

THIS REPORT CONTAINS: 

Total number of pages: 26 + (4 of ANNEX A). 

 

This document includes only and exclusively the tested specimens and the moment and conditions in which those measurements were made. 

It is expressly forbidden any total or partial reproduction of this document, except with a written conformity from TECNALIA. 

The  test  specimens  have  been  subjected  to  the  test  asked  by  the  applicant,  following  the  specified  procedures  in  the  used standards. 

Test results are detailed  in the  inside pages. Uncertainties of measurements complies the recommendations of EN 20140‐2:1994 and they are available to the applicant. 

This document is a copy in PDF of the original Report, for request of our client. 

Signature 

 

María José de Rozas López 

Acoustics Laboratory Manager 

AKUSTIKA ARLOA kudeatzailea:

ACOUSTICS AREA managed by:

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza, Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

SAINT‐GOBAIN GLASSOLUTIONS SAINT‐GOBAIN GLASS France       18 avenue d´Alsace 92400 Courbevoie ‐ France

Page 2: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 2 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

      INDEX 

 

 

1.‐  AIM .................................................................................................................... Page 2 

2.‐  DESCRIPTION OF TEST SPECIMENS .................................................................... Page 3 

3.‐  RESULTS ........................................................................................................... Page 19 

 

ANNEX A:  Test arrangements and evaluation. 

 

 

1.‐  AIM 

This  report  presents  the  results  of  the  laboratory  measurements  of  airborne  sound insulation of 7 Saint‐Gobain Glazing Partition Systems with tesa® ACXplus 7058. 

 The test specimens were selected and delivered by Tesa SE and Saint Gobain Glassolutions.  The installation and sealing of the specimens into the test opening was made by Cristalería BELAGUA, S.L. under supervision of personnel of TECNALIA. Each test specimen stayed 24 hours in the same temperature conditions than the test rooms.  The  tests were performed by personnel of TECNALIA  (Construction Area  ‐ Technological Services Division) in the acoustics facilities of the Laboratory for Quality Control in Buildings of the Basque Country Government, located at Aguirrelanda, Nº 10, 01013 Vitoria‐Gasteiz (Alava – Spain).   The details of the test arrangements and test evaluation are described in Annex A.        

Page 3: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 3 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

2.‐  DESCRIPTION OF TESTS SPECIMENS 

This report presents the acoustic results of the following tested specimens:  

 Table 1: Test specimens 

 Specimens  were  mounted  into  a  concrete  frame  20  cm  thick,  with  interior  nominal dimensions of 2800 mm of height and 3600 mm of length.  

  TEST SPECIMEN 

Code 

Test Code: 

B2014‐ 11 

Description: 

Saint‐Gobain Glazing Partition Systems with tesa® ACXplus 7058 acrylic core tape. 

Type of Glass/glasses Material between 

glass units 

Framework: Type of profiles and other 

components 

Details in 

Drawing Nº 

I  M150  SGG Stadip 66.1   tesa® ACXplus 7058  Click 25 aluminium profiles 

(Reynaers) 

II  M151  SGG Planilux 12mm toughened  tesa® ACXplus 7058  2 

III  M152  SGG Planilux 10mm toughened  tesa® ACXplus 7058  3 

IV  M153 

Double Skin: 

SGG Stadip 66.1 +                        SGG Stadip 55.1 

tesa® ACXplus 7058 

Double Click 25 aluminium profiles 

(Reynaers) 

V  M161 

Double Skin: 

SGG Stadip Silence 66.1 +                    SGG Stadip Silence 55.2 

tesa® ACXplus 7058 

Double Click 25 aluminium profiles 

(Reynaers) 

VI  M185  SGG Stadip Silence 66.1  tesa® ACXplus 7058 

Click 25 aluminium profiles 

(Reynaers) 

VII  M154 

Double Skin  

SGG Planilux 10mm +                           SGG Stadip Silence 55.2 

tesa® ACXplus 7058 Double profile Clipper (Coramine) 

Page 4: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 4 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

      

 

 

 

 

 

 

 

 

Drawing 1: Test specimen I. Details  

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

F  Click 25 spierubber 12‐17mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 5: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 5 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

     

                          

        

 

 

 

 

Photos 1‐7: Test specimen I in acoustic rooms and details of installation 

Photo 1                                                        Photo 2 

Photo 3 

Photo 5 

Photo 4 

Photo 7 Photo 6 

Page 6: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 6 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

                                 

         

 

Drawing 2:  Test specimen II. Details 

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

F  Click 25 spierubber 12‐17mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 7: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 7 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

               

  

                        

Photos 8‐13: Test specimen II in acoustic rooms and details of installation 

Photo 8                                                                        Photo 9

Photo 10 

Photo 11 

Photo 12  Photo 13 

Page 8: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 8 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

                                

         

 

Drawing 3: Test specimen III. Details 

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

E  Click 25 spierubber 10mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 9: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 9 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

               

 

                         

Photos 14‐19: Test specimen III in acoustic rooms and details of installation 

Photo 14                                                                    Photo 15

Photo 16 

Photo 17 

Photo 18  Photo 19 

Page 10: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 10 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

  

                             

          

 

 

Drawing 4: Test specimen IV. Details 

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

A  Click 25 double 10‐12mm 100mm EV‐1  

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

E  Click 25 spierubber 10mm ZWART  

F  Click 25 spierubber 12‐17mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 11: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 11 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

              

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

Photos 20‐25: Test specimen IV in acoustic rooms and details of installation 

Photo 20                                                                                                          Photo 21 

Photo 22 Photo 23 

Photo 24  Photo 25 

Page 12: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 12 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

 

             

Figure 1: details of materials for test specimens (I to VI) 

Ref. A 

Ref. B 

Ref. C 

Ref. D 

Ref. E 

Ref. F 

Ref. G 

Tesa ® ACXplus 7058 (6mm) 

Page 13: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 13 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                                       

 

 

Drawing 5: Test specimen V. Details 

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

A  Click 25 double 10‐12mm 100mm EV‐1  

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

E  Click 25 spierubber 10mm ZWART  

F  Click 25 spierubber 12‐17mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 14: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 14 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                                          

Photos 26‐31: Test specimen V in acoustic rooms and details of installation 

Photo 36 

Photo 27 

Photo 29 

Photo 28 

Photo 30 Photo 31 

Page 15: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 15 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                                       

Drawing 6: Test specimen VI. Details 

Ref. PROFILE 

Saint‐Gobain Glassolutions Clip‐in Light System 

B  Click 25 contra 4674.17 ALU 

C  Click 25 10‐12mm 4674.17 ALU 

D  Click 25 glasrubber 10‐12‐17mm ZWART 

F  Click 25 spierubber 12‐17mm ZWART 

G  Self‐adhesive tape polyethylene foam(close cell) 25x3mm 

1

2

Page 16: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 16 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                                          

Photos 32‐38: Test specimen VI in acoustic rooms and details of installation 

Photo 32  Photo 33                                     Photo 34 

Photo 35 

Photo 36 

Photo 37 

Photo 38 

Page 17: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 17 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                               

            

 

Drawing 7: Test specimen VII. Details 

       

1  Flat cover strip Ref: 5‐7900  9  Double glazing Ref: 5‐1500 

2  tesa® ACXplus 7058 (6mm)  10  Upright Ref: 5‐1350 

3  Channel Ref: 5‐7100  11  Clips S Ref: 1‐020 

4  Separator Ref: 1‐030  12  Retaining gasket Ref: 9‐840 

5  Acoustic foam for channel Ref: 9‐600  13  Glazing gasket Ref: 9‐980 

6  Acoustic foam for upright Ref: 9‐620  14  Shim 

7  Knock‐in Screw  15  Glass SGG STADIP® 55.2 Silice 

8  Glass SGG Planilux 10 mm     

A

B

3596

A

278

8

B

A-A

B-B

Page 18: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 18 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

                     

                      

Photo 39 

Photo 41 

Photo 40 

Photo 42 

Photo 44 

Photo 43 

Page 19: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

Report Nº B2014‐LACUS‐IN‐11 TG B  Page 19 of 26 (+ Annex A)

EUSKO JAURLARITZAGOBIERNO VASCO

 

 

 

 

 

 

 

 

 

 

  

Photos 39‐45: Test specimen VII in acoustic rooms and details of installation 

  3.‐  RESULTS 

For each test sample, the following airborne sound insulation results are featured: 

 

Sound reduction index, R, in third octave frequency bands from 100 to 5000 Hz, in table 

and graph. 

 

The Weighted sound  reduction  index, Rw, calculated according  to EN  ISO 717‐1,  from 

the sound reduction index, R. 

The  spectrum  adaptation  terms  between  100  and  3150  Hz,  C  and  Ctr,  calculated 

according to EN ISO 717‐1, which are the values, expressed in decibels, to be added to 

the  global  magnitude  value  (Rw,  for  example)  to  consider  the  characteristics  of  a 

particular noise spectrum, such as pink noise (C) and traffic noise (Ctr). 

 

 

 

Photo 45 

Page 20: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                            Test date: October 3rd, 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Stadip 66.1 and tesa® ACXplus 7058.        Receiving room volume: 56,26 m3       Source room volume: 65,50 m

      Estimated superficial mass: 30 kg/m2     Test specimen area: 10,08 m2 (2,8x3,6 m) 

    T rooms: 19,7 ºC       HR rooms: 64 %     P rooms: 964 mbar

     

   

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M150  Signature:  Acoustics Area   Managed by  Date of report: 17th December, 2.014.

f (Hz)  R (dB) 

100  22,8 125  22,0 160  26,3 

200  28,2 250  28,5 315  31,5 

400  33,0 500  33,2 630  34,2 

800  33,9 1000  29,1 1250  28,2 

1600  33,2 2000  37,7 2500  41,3 

3150  45,1 4000  48,0 5000  51,5 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  34 (‐2; ‐3)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

34

10

20

30

40

50

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n i

nd

ex R

(d

B)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                       Page 20 of 26 (+ Annex A)

Page 21: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                             Test date: 6th October, 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Planilux 12mm toughened and    tesa® ACXplus 7058.       Receiving room volume: 56,26 m3       Source room volume: 65,50 m3 

      Estimated superficial mass: 30 kg/m2     Test specimen area: 10,08 m2 (2,8x3,6 m) 

    T rooms: 19,6 ºC       HR rooms: 65 %     P rooms: 953 mbar 

 

 

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M151  Signature:  Acoustics Area   Managed by  Date of report: 17th December, 2.014.

f (Hz)  R (dB) 

100  22,2 125  23,7 160  26,7 

200  28,3 250  28,7 315  30,8 

400  33,3 500  33,8 630  34,6 

800  33,3 1000  26,2 1250  26,4 

1600  31,3 2000  35,6 2500  38,5 

3150  41,6 4000  44,6 5000  45,8 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  33 (‐2; ‐4)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

33

10

20

30

40

50

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n i

nd

ex R

(d

B)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                        Page 21 of 26 (+ Annex A)

Page 22: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                             Test date: 7th October, 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Planilux 10mm toughened and   tesa® ACXplus 7058.       Receiving room volume: 56,26 m3       Source room volume: 65,50 m3 

      Estimated superficial mass: 25 kg/m2     Test specimen area: 10,08 m2 (2,8x3,6 m) 

    T rooms: 19,5 ºC       HR rooms: 64 %     P rooms: 951 mbar 

 

 

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M152  Signature:  Acoustics Area   Managed by Date of report: 17th December, 2.014. 

f (Hz)  R (dB) 

100  21,9 125  21,0 160  24,9 

200  26,4 250  27,7 315  30,1 

400  31,1 500  32,5 630  33,7 

800  34,2 1000  33,5 1250  23,9 

1600  26,7 2000  32,3 2500  35,3 

3150  38,9 4000  42,3 5000  43,6 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  32 (‐3; ‐3)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

32

10

20

30

40

50

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n i

nd

ex R

(d

B)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                               Page 22 of 26 (+ Annex A)

Page 23: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                            Test date: 9th October, 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Stadip 66.1 / SGG Stadip 55.1 and   tesa® ACXplus 7058.  Receiving room volume: 55,50 m3  Estimated superficial mass: 55 kg/m2  T rooms: 19,6 ºC  P rooms: 951 mbar Source room volume: 65,50 m3  Test specimen area: 10,08 m2 (2,8x3,6 m)  HR rooms: 68 %           

       

 

 

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M153  Signature:  Acoustics Area   Managed by  Date of report: 17th December, 2.014.

f (Hz)  R (dB)

100  26,4 125  24,8 160  29,1 

200  31,2 250  30,0 315  33,4 

400  35,9 500  38,5 630  40,5 

800  42,4 1000  40,7 1250  39,5 

1600  45,1 2000  51,9 2500  59,3 

3150  61,4 4000  66,9 5000  74,1 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  41 (‐1; ‐4)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

41

20

30

40

50

60

7010

0

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n in

dex

R (

dB

)R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                           Page 23 of 26 (+ Annex A)

Page 24: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                          Test date: 21st October 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Stadip Silence 66.1 / SGG Stadip Silence 55.2 and tesa® ACXplus 7058. 

    Receiving room volume: 55,50 m3       Source room volume: 65,50 m

      Estimated superficial mass: 55 kg/m2     Test specimen area: 10,08 m2 (2,8x3,6 m) 

    T rooms: 19,7 ºC       HR rooms: 56 %     P rooms: 964 mbar

      

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M161  Signature:  Acoustics Area   Managed  Date of report: 17th December, 2.014. 

f (Hz)  R (dB) 

100  27,1 125  25,5 160  28,2 

200  30,4 250  30,0 315  33,1 

400  36,0 500  38,9 630  41,9 

800  46,3 1000  49,7 1250  52,6 

1600  54,6 2000  57,7 2500  63,5 

3150  66,0 4000  68,2 5000  73,2 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  43 (‐1; ‐5)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

43

20

30

40

50

60

70

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n in

dex

R (

dB

)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                           Page 24 of 26 (+ Annex A)

Page 25: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                      Test date: 18th November, 2.014. 

Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System with SGG Stadip Silence 66.1 and tesa® ACXplus 7058.  Receiving room volume: 56,26 m3  Estimated superficial mass: 30 kg/m2  T rooms: 20,0 ºC  P rooms: 950 mbar Source room volume: 65,50 m3  Test specimen area: 10,08 m2 (2,8x3,6 m)  HR rooms: 43 %           

       

   

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M185  Signature:  Acoustics Area   Managed by  Date of report: 17th December, 2.014. 

f (Hz)  R (dB)

100  23,9 125  23,4 160  27,1 

200  28,5 250  28,9 315  31,6 

400  33,0 500  34,4 630  36,0 

800  36,9 1000  37,9 1250  38,3 

1600  37,8 2000  39,1 2500  43,1 

3150  47,3 4000  50,2 5000  54,0 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  37 (0; ‐3)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method.

37

10

20

30

40

50

60

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

ed

uc

tio

n in

de

x R

(d

B)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                           Page 25 of 26 (+ Annex A)

Page 26: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

EMPLEGU ETA GIZARTE

POLITIKETAKO SAILA

Etxebizitza Zuzendaritza

Eraikuntzaren Kalitate Kontrolerako Laborategia

DEPARTAMENTO DE

EMPLEO Y POLÍTICAS SOCIALES

Dirección de Vivienda

Laboratorio de Control de Calidad de la Edificación

Airborne Sound Insulation according to EN ISO 10140‐2:2010 (*) Laboratory Measurements 

Applicant: SAINT‐GOBAIN GLASSOLUTIONS.                         Test date: 17th October, 2.014. Test specimen: Saint‐Gobain Glass Solution Clip‐in Light System  (Coramine) with SGG Planilux 10mm / SGG Stadip 

Silence 55.2 and tesa® ACXplus 7058.   

      Receiving room volume: 55,60 m3       Source room volume: 65,60 m3 

      Estimated superficial mass: 50 kg/m2     Test specimen area: 10,08 m2 (2,8x3,6 m) 

    T rooms: 19,2 ºC       HR rooms: 62 %     P rooms: 957 mbar 

 

  

(*) It annuls, replaces and complies with cancelled standard norme EN ISO 140‐3:1995

Nº of result: B2014–11–M154  Signature:  Acoustics Area   Managed by  Date of report: 17th December, 2.014. 

f (Hz)  R (dB) 

100  25,4 125  20,9 160  22,3 

200  25,2 250  25,8 315  30,7 

400  33,6 500  35,3 630  37,3 

800  37,7 1000  37,7 1250  35,5 

1600  36,7 2000  40,9 2500  42,9 

3150  47,7 4000  50,0 5000  53,2 

Rating according to EN ISO 717‐1:  Rw (C;Ctr):  37 (‐1; ‐5)  dB   

Evaluation based on laboratory measurement results obtained by an engineering method. 

37

15

25

35

45

55

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

Frequencies (Hz)

So

un

d r

edu

ctio

n i

nd

ex R

(d

B)

R (dB)

Curve of reference values for the evaluation of theweighted sound reduction Index, Rw

4 / L E 4 5 6

Report Nº B2014‐LACUS‐IN‐11 TG B                         Page 26 of 26 (+ Annex A)

A-A

Page 27: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

 

Annex A to Report Nº B2014‐LACUS‐IN‐11 TG B  Page 1 of 4 

EUSKO JAURLARITZAGOBIERNO VASCO

Annex A - Test arrangements and evaluation 

 

 

A.1  Test standards and procedures 

●  EN  ISO  10140‐2:2010:  “Acoustics.  Laboratory  measurement  of  sound  insulation  for building elements. Measurement of airborne insulation”. 

 

●  EN  ISO 717‐1:2013:  “Rating of  sound  insulation  in buildings and of building elements. Airborne sound insulation”. 

 

●  TECNALIA  internal  procedures.  According  to  ENAC  accreditation  No  4/LE456  (ENAC: Spanish National Accreditation Body)”. 

 

Standard  EN  ISO  10140‐2:2010,  together with  the  other  EN  ISO  10140‐1:2010,  EN  ISO 10140‐3:2010,  EN  ISO  10140‐4:2010  and  EN  ISO  10140‐5:2010,  cancels  and  replaces standard EN ISO 140‐3:1994. 

 

 

A.2  Laboratory test facilities 

The  sound  insulation  tests  were  performed  in  the  horizontal  transmission  rooms, composed of a source and a receiving room. The reception room is composed of a double concrete  box  of  twenty  and  ten  centimetres  of  thickness  each  one,  acoustically disconnected.  

 

The horizontal  transmission  rooms comply with  the  requirements of  the EN  ISO 10140‐5:2010. 

 

 

A sketch of each room is included in Drawing 1. 

Page 28: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

 

Annex A to Report Nº B2014‐LACUS‐IN‐11 TG B  Page 2 of 4 

EUSKO JAURLARITZAGOBIERNO VASCO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drawing 1: Sketch of the horizontal transmission rooms 

 

 

A.3  Equipment 

  Source room  Receiving room 

Microphones  Brüel & Kjær 4943; Nº 2534064  Brüel & Kjær 4943; Nº 2534065 

Preamplifiers  Brüel & Kjær 2669; Nº 1948764  Brüel & Kjær 2669; Nº 2025844 

Sound sources  Brüel & Kjær 4296; Nº 2071420  CERWIN VEGA;     Nº 012446 

Booms  Brüel & Kjær 3923; Nº 2036586  Brüel & Kjær 3923; Nº 2036591 

 

  Control room 

Analyser  Brüel & Kjær 2144;        Nº 1893979 

Amplifier  LAB Gruppen;LAB 300; Nº 970‐967 

Equalizer  Sony, SRP‐E100;          Nº 400238 

Calibrator  Brüel & Kjær 4231;        Nº 2061476 

Atmospheric conditions meter  Ahlborn Almemo 2590‐3S;  Nº H09121017 

 

Page 29: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

 

Annex A to Report Nº B2014‐LACUS‐IN‐11 TG B  Page 3 of 4 

EUSKO JAURLARITZAGOBIERNO VASCO

A.4  Test procedures 

 

The sound reduction index (R) for the one‐third‐octave band 100 Hz to 5 KHz is calculated 

according to EN ISO 10140‐2 standard using the following formula: 

 

  R=L1‐L2+10Log S/A    where, 

 

L1:  Average sound pressure level in the source room. 

L2:  Average sound pressure level in the receiving room. 

S:  Test specimen area. 

A:  Equivalent sound absorption area in the receiving room. 

 

The measurement of the average sound pressure levels L1 and L2 is performed emitting an 

equalized white noise  (between 100 Hz and 5 kHz) with a moving omnidirectional sound 

source. 

 

The  sound  field  in  the  source and  receiving  rooms  is  sampled using moving microphone 

with a sweep radius of 1 m and a traverse period of 16 s during 32 s of measure. 

 

Background noise  is measured  in the receiving room  in the one‐third‐octave band 100 Hz 

to 5 kHz according to the same measurement process of sound field in the receiving room.  

 

The equivalent sound absorption area is evaluated from the reverberation time measured 

in the receiving room, using Sabine’s formula: 

 

  A=0.16V/T  where, 

 

A:  Equivalent sound absorption area in the receiving room. 

T:  Reverberation time in the receiving room. 

V:  Receiving room volume. 

 

Reverberation time  in the receiving room  is determined using two positions of the sound 

source  and  three  fixed microphone  positions  for  each  source  position,  at  120º  in  the 

microphone path. 

 

Measuring instruments are verified just before and after the execution of the test. 

Page 30: Tests Report Nº LACUS IN 11 TG B ACOUSTICS AREA …Page 1 of 26 (+ Annex A) 4 / L E 4 5 6 Tests Report Nº B2014‐LACUS‐IN‐11 TG B Laboratory measurements of airborne sound insulation

AKUSTIKA ARLOA/AREA DE ACUSTICA

Eraikuntzaren Kalitate Kontrolerako Laborategia

Laboratorio de Control de Calidad de la Edificación

 

 

Annex A to Report Nº B2014‐LACUS‐IN‐11 TG B  Page 4 of 4 

EUSKO JAURLARITZAGOBIERNO VASCO

The measurement and evaluation process applied  to  the  test specimen described  in  this report  is  according  to  the  standard  in  force  EN  ISO  10140‐2:2010,  and  complies  with cancelled standard EN ISO 140‐3:1994.