3 IN 1 ROOF, INC. TEST REPORT SCOPE OF WORK ASTM B117 - SALT FOG EVALUATION OF THREE (3) 14" X 23" ROOF PANELS - 90 HOUR EVALUATION REPORT NUMBER I0638.01-106-31 R0 TEST DATE 02/12/18
ISSUE DATE 07/31/18 RECORD RETENTION END DATE 02/12/22 PAGES 10 DOCUMENT CONTROL NUMBER ATI 00231 (09/05/17) RT-R-AMER-Test-2827 © 2017 INTERTEK
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Version: 09/05/17 Page 2 of 10 RT-R-AMER-Test-2827
REPORT ISSUED TO 3 IN 1 ROOF, INC. 5041 Kitridge Road Dayton, Ohio 45424 SECTION 1 SCOPE Product: 14" x 23" Roof Panels Intertek Building & Construction (B&C) was contracted by 3 in 1 Roof, Inc. to evaluate Three, (3) 14" x 23" Roof Panels in accordance with ASTM B117 for Salt Fog Corrosion. Results obtained are tested values and were secured by using the designated test method. Testing was conducted at the Intertek B&C test facility in York, Pennsylvania. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. For INTERTEK B&C:
COMPLETED BY: Daryn S. Fassnacht REVIEWED BY: Joseph M. Brickner
TITLE:
Technician Materials Laboratory TITLE:
Laboratory Supervisor Materials Laboratory
SIGNATURE:
SIGNATURE:
DATE: 07/31/18 DATE: 07/31/18 DSF:jmb/mh
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 3 of 10 RT-R-AMER-Test-2827
SECTION 2 TEST METHOD The specimens were evaluated in accordance with the following:
ASTM B117-16, Standard Practice for Operating Salt Spray (Fog) Apparatus SECTION 3 MATERIAL SOURCE The materials were provided by 3 in 1 Roof, Inc. The following were received: Three, (3) 14" X 23" Roof Panels. Representative test specimens will be retained by Intertek B&C for a minimum of four years from the test completion date. SECTION 4 LIST OF OFFICIAL OBSERVERS
NAME COMPANY
Daryn S. Fassnacht Intertek B&C
Joseph M. Brickner Intertek B&C
SECTION 5 TEST PROCEDURE All conditioning of test specimens and test conditions were at standard laboratory conditions unless otherwise reported. Refer to the test related photos in Section 9. ASTM B117 - Salt Fog Corrosion Test specimens will be subjected to a total 500-hour exposure in an QFOG salt fog cabinet (ICN: 005959) utilizing a 5% (by weight) solution of reagent grade Sodium Chloride and laboratory grade water. The cabinet operated with a continuous fog at 35 ±3°C and an atomized solution pH between 6.5-7.2. Specimens were supported at an angle between 15° and 30° from vertical. Prior to exposure the test specimens were photographed upon arrival at the laboratory. The specimens then were covered half way from top to bottom creating a straight edged line for the chemical Acryglaze to be applied. Post exposure, as of 90 hours showed that the specimens had visible darker grey markings on the face side of the specimen.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 4 of 10 RT-R-AMER-Test-2827
SECTION 6 TEST SPECIMEN DESCRIPTION
TEST PROCEDURE
NUMBER OF SPECIMENS
NOMINAL SPECIMEN DIMENSIONS
VISUAL CHARACTERISTICS
ASTM - B117 3 14" x 23" Roof Panels Light-grey, texturized pieces
SECTION 7 TEST RESULTS ASTM B117 - Salt Fog Exposure (90 hours)
SPECIMEN NO.
HOURS IN QFOG-B117 DIMENSIONS OBSERVATIONS
1 90 14" x 23" No Surface Area Compromised
2 90 14" x 23" No Surface Area Compromised
3 90 14" x 23" No Surface Area Compromised
SECTION 8 CONCLUSION The requested test method did not have a specific performance requirement.
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 5 of 10 RT-R-AMER-Test-2827
SECTION 9 PHOTOGRAPHS
Photo No. 1 Received Specimens
Photo No. 2 Acryglaze Chemical
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 6 of 10 RT-R-AMER-Test-2827
Photo No. 3 Prepped Specimen
Photo No. 4 Coated Specimen with Acryglaze
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 7 of 10 RT-R-AMER-Test-2827
Photo No. 5 Specimens 1,2,3 Coated with Acryglaze on Half of Surface Face
Photo No. 6 Specimens in the QFOG B117 (Pre-Exposure)
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 8 of 10 RT-R-AMER-Test-2827
Photo No. 7 Specimen #1
Photo No. 8 Specimen #2
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 9 of 10 RT-R-AMER-Test-2827
Photo No. 9 Specimen #3
130 Derry Court York, Pennsylvania 17406
Telephone: 717-764-7700
Facsimile: 717-764-4129 www.intertek.com/building
TEST REPORT FOR 3 IN 1 ROOF, INC. Report No.: I0638.01-106-31 R0 Date: 07/31/18
Version: 09/05/17 Page 10 of 10 RT-R-AMER-Test-2827
SECTION 9 REVISION LOG
REVISION # DATE PAGES REVISION
0 07/31/18 N/A Initial Report Issue