Page 1: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

TEST REPORT

Page 2: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

CPRl

TEST REPORT

(A Govt. of India Society) P.B.No. 8066, Sadashivanagar Post

Sir C.V. Raman Road, Bangalore - 560 080 (INDIA)

stitute

Office,

Page 3: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

SHORT CIRCUIT LABORATORY CENTRAL POWER RESEARCH INSTIT UTE

P.B,N0.8W, S A M H WANWAR POST OFFICE SIR C.V.RkMAN ROAD, BANGALORE - 5B0 080 (INDIA)

Phone: +91 (0) 80 -23602662 Fax: 491 (0) 8 0 - 1 m 2 1 3

Test Report Number

Name EL Add- of the Customer

Name & Address of the Manufacturer

Particulars of sample te8ted

CondRibn of the sample on ncelpt

TYW Designation W a f number" Number of sahp#kiH@3 Date (8) 9f test (s) GPR1 $ample code no@).

-lam of tests conducted Tssf in accordance with w f & p i d f h t i o n

plsih ~ s ~ -

Sheet 1 of 4 TEST REPORT

dated: 13h February, 2008

Ms. NI E Power & Engineering (P) Ltd., B-40, KSSIE , Industrial Estate, Kumbatagodu, 8angalore - 58Q 074.

Mls. N1E Power & Engineering (P) Ltd., B-40, KSSlDC, Industrial Estate, Kurnbalagodu. Bangalore - 560 074.

AC Mefal Enclosed Switchgear & Conhlgeat- M. V, Switchgear Panel with Vacuum Circui? Break? Hiew

Cubicle Switchgear cubicle 001 One 2"' December 2005 SCOSS274 1

-fibor€-time Hthstand current & f xak wifhshnd tests

.Sub-dauae 6.6 of 1EC 62272~2QQ:2003 Not applicable 26.3kA rn for I .O second 8 6 6 . 7 5 ~ peak on main drcuit * Nil

Page 4: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

SHORT CIRCUIT LABORATORY CENTRAL POWER RESEARCH INSTITUTE

P.B.NO.8066, SADASHIVANAGAR POST OFFICE SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited

CPRl Phone : +91 (0) 80 - 23602662 Fax : +91 (0) 80 - 23601213 Laboratory

Sheet 2 of 4 Report number: SC05514A

J Description of sample tested (rating as assigned by the manufacturer)

'$ Test sample M. V. Switchgear Panel with Vacuum Circuit Breaker (VCB) 1

1 Rated voltage 12 kV

I Rated insulation level 28/75 kV 1 Rated current 1250 A

'$ Rated frequency 50 Hz

I Number of poles

I Details of VCB

Three

12kV, 1250A, Type VD4 12.12.25 SI. No. V8293, ABB make

I Rated short-time withstand current I 8 peak withstand current 26.3kA rms for 1.0 second 8 65.75kA peak f

w

Documents attached to this report

I

I Oscillogram number (s) SC05514A.SOl

t Photo number (s) I 1 Test circuit diagram number (s) C RTLISCISTC-03 I Drawing number (s) I 1

NIEPE/OOI~TIO5, NIEL/OOI/RL/05 SH: 01 & NIEL/001 /RL/05 SH: 02

Test Engine r w

Page 5: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

SHORT CIRCUIT LABORATORY CENTRAL POWER RESEARCH INSTITUTE

P.B.NO.8066, SADASHIVANAGAR POST OFFICE SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA)

NABL Accredited CPRl Phone : +91 (0) 80 - 23602662 Fax : +91 (0) 80 - 23601213 Laboratory

Sheet 3 of 4 Report number: SC05514A

Short-time withstand current & peak withstand current tests (sub-clause 6.6)

Test conditions

-Source Phase Frequency Neutral

Short-circuit generator Three 50 Hz Isolated

Test sample Phase Three; one end of the horizontal bus-bars connected to source. Condition before test In clean & new condition, VCB operable on no-load. Mounting Vertical

Test details Test circuit number Short-circuit applied Short-circuit point

CRTLISCISTC-03 On the outgoing terminals horizontal bus-bars through the VCB Grounded

Test results

Oscillogram Number

SC05514A.SOl

Measurement of resistance of the main circuit

I & peak withstand current tests I

Condition of the sample

Before short-time withstand current & peak withstand current tests As after short-time withstand current

Current (kA) Duration - seconds

1.06

Peak

67.28

Test current (A) d.c.

100

100

Power frequency high voltage withstand test

I connected together and all outgoing terminals connected together I Physical Inspection

Condition of bus-bars No visible damage or deformation Condition of insulators No visible damage Condition of VCB No visible damage

RMS

R - 26.02 Y - 27.93 B - 26.18 Average:

26.71

Power frequency high voltage was applied a) With VCB in close condition, between each phase and all other poles connected to earth b) with VCB in open condition, between all incoming terminals

Remarks: The sample tested complies with sub-clause 6.6 of IEC 62271-200:2003

Ambient Temperature

- "C

26.6

Ambient Temperature "C

26.7

Remarks Withstood 28 kV rms for I .O minute

Withstood 28kV rms for 1.0 minute

Observations

During test: No abnormality.

After test: VCB operable on no-load at the first attempt.

Resistance - pR R-phase Y-Phase B-Phase 104.8 1 92.5 1 98.1

26.6 103 98 105

Page 6: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662

SHORT CIRCUIT LABORATORY CENTRAL POWER RESEARCH INSTITUTE

P.B.NO.8066, SADASHIVANAGAR POST OFFICE SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA)

NABL Accredited CPRl Phone : +91 (0) 80 - 23602662 Fax : +91 (0) 80 - 23601213 Laboratory

Sheet 4 of 4 Report number: SC05514A

NOTE

a) This is not a certificate of rating. A certificate of rating is not issued as only limited tests as requested by the customer were carried out.

b) The test results relate only to the item(s) tested. c) Publication or reproduction of this report in any form other than by complete set of the

whole report and in the language written, is not permitted without the written approval of CPRI.

d) Corrections 1 erasings invalidate the test report. e) Any anomaly 1 discrepancy in the test report should be brought to our notice

within 45 days from the date of issue. 4 # Indicates that for such tests there is no formal NABL accreditation and the tests are

conducted as per the relevant applicable National / International standard or as per the specific customer requirement.

Additional Information: CPRl issues following types of reportslcertificates:

Test Report: The test report contains the record of the values of test parameters as obtained during testing, the physical condition of the sample during I after the test(s) and copy of oscillogram(s). Test report is issued when partial tests are performed as against the complete test requirement for proving specific ratings.

Sealed Certificate: The sealed certificate is issued, on request and payment of the prescribed charges thereof only when the sample of particular type and rating has satisfactorily passed all the specified tests in compliance with the condition stipulated in a published National I International standard.

CPRl issues the following type test certificates based generally on STL Guidelines:

I. Type test certificate of Short Circuit Performance. II. Type test certificate of Switching Performance. Ill. Type test certificate of Temperature Rise Performance. IV. Type test certificate of Dielectric Performance. V. Type test certificate of complete type test.

Page 7: TEST REPORT - img.tradeindia.comimg.tradeindia.com › fm › 1708124 › c4.pdf · SIR C.V.RAMAN ROAD, BANGALORE - 560 080 (INDIA) NABL Accredited CPRl Phone : +91 (0) 80 - 23602662