Government of India Department of Atomic Energy NAME OF WORK : Providing substation and external electrical works for 96 Flats Of TIFR Housing at New Mandala, Anushaktinagar, Mumbai. TENDER NOTICE NO. : DCSEM /CE(E)/TIFR-96 Flats/SS /12/05-2010 dt. 20.05.2010. Number of pages : 22 Tender Papers Sold To : M/s. ( D.K.Jain ) Chief Engineer (Electrical) Directorate of Construction, Services and Estate Management. Financial Bid Page No. 1 of 30

Upload: rsramanujam

Post on 07-Apr-2015

453 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tender Specs-Electrification of Apartments

Government of India

Department of Atomic Energy

NAME OF WORK : Providing substation and external electrical works for 96

Flats Of TIFR Housing at New Mandala, Anushaktinagar,

Mumbai.

TENDER NOTICE NO. : DCSEM /CE(E)/TIFR-96 Flats/SS /12/05-2010 dt. 20.05.2010.

Number of pages : 22

Tender Papers Sold To :

M/s.

( D.K.Jain )

Head P&C(E&M) Chief Engineer (Electrical)

Directorate of Construction, Services and Estate Management.

Financial Bid

Page No. 1 of 30

Page 2: Tender Specs-Electrification of Apartments

Name of work :

Providing substation and external electrical works for 96 Flats Of TIFR Housing at New Mandala,

Anushaktinagar, Mumbai.

Shedule of Quantities

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

1.0 Transformer

1.1 Design, manufacture, supply, installation, testing1 Set

& commisioning of Out door type 1.25 MVA

ONAN, 11/0.433 KV, 3 Phase, 50 Hz, Dyn11,

Vector group copper wound Transformer with

Transformer oil with cable end box on HV side

suitable for 1 No. 3 core x 240 sq. mm, 11 KV

XLPE cable & 2000A Aluminium sandwitch type

bus trunking arrangement on LV side with neutral

brought out seperataly & installation of 1 no.

2000 A / 1 A ratio class P.S. CT as per item No.

6.1 m for restricted earth fault protection of

Transformer with Temp. and oil

indicator.Transformer shall be provided with

OFF Laod tap changer on HV side in

steps of + 5 % to - 5% in steps of 2.5 % with

standard mounting accessories. Epoxy painting at

works and touchup painting at site etc. including

10 % extra Transformer oil,in non returnable

drums.All above conforming to IS 2026/1972

ofcomplete in all respect as required at site.

latest amendments & Complete as per relevent IS

specification & as per instruction of EIC .

NOTE:

1) G.A drawings shall be got

approved

2) Tenderer is advised to seek

guidance of supplier of

transformer for installation,

testing & commissioning.

3) Use of crane for assembly &

installation of transformer is

included in the scope of tender.

4) Co-ordination with electrical

inspector and subsequent

approvals are included in the

scope of the tender.

5) Routine tests, heat run tests

on transformer shall be

performed in presence of

departmental engineers as per

relevant IS/BS/IE specifications

at works before despatch after

clearance. Type test certficate

as indicated in the specification

shall be submitted before

commencement of routine test

of transformers for scrutiny &

approval.

Page No. 2 of 30

Page 3: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

6) The capitalized cost of

transformer, as per formula

given at Sr. No. 9 (Page No.

4) of technical specifications

of transformer, shall be

considered while evaluating

financial bid. Also the

bidders shall note the

formula for penalty for

exceeding guaranteed

transformer losses given at

Sr. No. 9 (Page No. 5) of

technical specification of

transformer & quote for

guaranteed transformer

losses carefully.

1.2 Temp rise test on the above 1

No. transformer as item above

as per IS 2026 at

manufacturers work

1 job

1.3 Filteration of transformer oil of

above referred transformer at

site including testing of break

down value and acidity of oil

and topping of oil after

filteration, all as per relevant IS

specifications & as per

instructions of E.I.C

1 job

2.0 HT Cable:

Supply, Installation, Testing &

Commissioning of11kV(E), 3Cx240 sqmm

aluminium stranded

circular core conductor with

semi conductor

shielding, XLPE insulation with

semi conductor

sheilding copper taped screening, PVC tape

(inner) sheathed, G.I round conductor armoured,

PVC outer sheathed cable conforming to IS 7098

(Part-II) with latest amendments, fixed on

wall/column/slab/false ceiling or in existing hume

pipe/trench/ shaft/pit/ on 5mm thick M.S. flat /GI

spacer/angle/ support fixed with coach

screws/grouted in wall/anchor fasteners 2mm.

thick G.I. Fabricated saddle, all fixing

accessories, etc complete including painting of

M.S spacers/angles and saddles or in ground at a

- depth of 1200 mm below ground level/in all types

of soil/concrete road cutting/foot path cutting

including excavation, sand bedding, laying of

baked bricks on side & RCC tiles on top-,

temporary reinstatement, back filling, dewatering,

consolidation, disposal of excess earth within the

radius of 500 mtrs and making good to the

original finish etc. Providing brass cable

indentification tag as per enclosed detailed

specifications, drawings & as per instructions of

Page No. 3 of 30

Page 4: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

the E-I-C & of the following sizes.

Note: (1) Sealing of hume pipe with wooden bushes,

after cable laying shall be included in the scope

of work.

(2) The hard rock excavation shall be measured

under item N. 27

(3) MS.Support item shall be measured under item

no.31.

2.1 2 nos. of 3Cx240sq.mm. 11kV cable

2.1.1 Laid in existing trench/humepipe /CI pipe etc.# mtr.

2.1.2 In ground upto 1200 mm depth # mtr.

3.0 HT Cable End Joint (Indoor) 5 nos.

Supply,installation and cable termination for

following 11000 volt grade Aluminium

conductor armoured XLPE cable including

Page No. 4 of 30

Page 5: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

heat shrinkable jointing kit complete with

tinned copper lugs,all accessories and

materials required to make complete joint

as required and as per instruction of E-I-C.

3a HT Cable striaght through Joint 3 nos.

Supply,installation and cable termination for

following 11000 volt grade Aluminium conductor

armoured XLPE cable including heat shrinkable

jointing kit complete with ferrules tinned copper,

all accessories and materials required to make

complete joint. Scope also include excavation in

all types of soil refilling temporary reinstatement,

back filling, dewatering, consolidation, disposal of

excess earth within the radius of 500 mtrs etc as

required and as per instruction of E-I-C.

4.0 11 kV SF6 Ring Main Unit (RMU):

4.1 4way extensible type RMU 1 set

Supply, Installation, testing & Commissioning of

12KV,26.2 KA (for 3 sec) short circuit withstand,4

way indoor, double extensible type SF6 ring main

unit comprising of 2 Nos 630A SF6 Isolator one

for incoming & second for close loop & with

double extensible 200 A SF6 circuit breakers for

transformer outgoings. All the circuit breaker shall

be manual operated & shall be provided with

earthingswitches with full making capacity .

Breaker shalll be provided with mechanical

ON/OFF /Earth indication, anti-relfex operated

handle, shunt trip coil (48 V DC ) for external trip

signal,self powerd O/C & E/F relay type similar to

VIP 300 for I/C breaker & VIP 35 of M/S schneider

make or equivalent make for O/G breaker. Cable

testing facality with out disconnecting the cable

terminations, Emergency trip push button, live

cable indicating LED's enerzied through

capacitive voltage dividers with suitable cable

boxes for termination of 3 C X 240 sq. mm, XLPE

cables of 11 KV grade, 3 Nos. class 5 P 10

protection CTs ratio100/5 A for I/C & O/G, right

angle boots equivelent to TP 300 of MECP make

(push button type). 2 Nos. Master trip relay Zelio

of M/s Schneider or equivalent for H.T. breaker

tripping on transformer faults.All accessories of

M.T. relay & additinal control wiring. Relay to be

mounted in seperate box.Control circuit & spring

charging of the panel shall be on 48 V DC supply.

Note: 1) The scope includes the Supply and

installation of M.S. Channel (ISMC 100 ) required

for installation of panel on cable trench.

2) Scope includs the cutting of M.S.chequered

plate trench covers to require size after

installation of Panel.

Page No. 5 of 30

Page 6: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

5.0 BUS DUCT :

Supply, Installation, Testing & Commissioning of

readymade 415 V, 50Hz triple pole & neutral

totally enclosed, IP 55 for outdoor mounting, 1.5

mm GI sheet steel clad, duly painted bus duct

with compact sandwichedtype insulated Al bus

bars having following configuration:

a) Bus bar current rating : 2000 A

b) Bus bar configuration : 3 Phase + neutral

Al bus bar. Neutral shall have 100% capacity.

c) Symetrical short circuit rating : 35 KA at

415 V

d) External earthing : 2 nos 25 x 6 mm tinned

copper strip to be measured under item no.5.11.

The bus duct shall be complete with following

components / accessories inclusive of joint

covers as required,wall crossing unit with

fire barrier, supporting arrangement by

hangers, MS angle 40x40x5mm with 2 nos. of

hanger rods of dia.6mm fixed with ceiling /MS

angle supports on wall with anchor fastener

etc.for indoor product & M.S. angle of size 40 x

40 x 5mm LISMC-75for vertical supports for outdoor

busduct as required & as per instructions of EIC.

Any components/features etc not specifically

mentioned but which are required functionally &

for safety of system shall be inlcuded in scope of

work without extra financial implication.

5.1 Copper braided flexible jumper for transformer and2 no

Panel end connection.

5.2 Main LT Panel end connections. 1 no

5.3 Flange end unit Panel (Indoor) 1 no

5.4 Flange end unit Transformer (Outdoor)1 no

Note: The scope shall include providing flange

end box, if necessary, to match Panel &

transformer end dimensions with flange

dimensions etc.

5.5 Vertical elbow 300mm x 300mm approx (Indoor)1 nos

5.6 Vertical elbow 300mm x 300mm approx (Outdoor)1 nos

5.7 Horizontal Elbow 300mm x 300mm approx.(Indoor)1 nos

5.8 Horizontal Elbow 300mm x 300mm approx.1 nos

(Outdoor)

5.9 Straight length feeder (Indoor) 4 mtr.

5.10 Straight length feeder (Outdoor) 4 mtr.

5.11 25 x 6 mm tinned copper strip fixed on bus # mtr.

duct housing

Page No. 6 of 30

Page 7: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

6.0 LT PANEL:

Supply, installation,testing & commissioning of

floor mounting front operated front access

extensible type cubicle panel totally enclosed,

dust and vermin proof with IP-42 protection with

hinged and lockabale doors. Switchboards

fabricated from 2 mm thick CRCA sheets

including interconnections, tinned copper

crimping lugs, bonding to earth and painting

suitable for use at 415 V, 3 phase 4 wire 50 Hz

system, and to withstand a fault level of 35 KA

symmetrical at 415 V complete as per

specifications, as required and as below :

All switchboards shall have provision for entry

of cables from the top/bottom as required.

All live accessible parts shall be shrouded and

all equipment shall be finger touch proof. The

bus bars shall be insulated with heat

shrinkable sleeves. SMC/DMC shrouds and

busbar supports shall be used.

Note :-

1) All G.A. & fabrication drawings shall be got

approved from the E.I.C. Final painting of panel

to be done with powder coating. Necessary

touch up may be done at site, incase if

required. The scope includes all tests as

specified in department's specification,

relevant I.S. and as required by E.I.C, shall

have to be performed at factory & at

installation site and shall be included in the

quoted rate.

2) The equipment shall be designed to ensure

complete safety during operation inspection,

connection of cables etc.

3) Control wires shall be of 1.1 KV 2.5 sq.mm

FRLS copper wires and neatly bunched

separately and adequately supported so as to

prevent sagging and strain on termination.

4) A minimum of 10% spare terminals shall

be provided on each terminal block.

5) All non current carrying metallic parts of

the equipment shall be earthed with copper

flexible wire / strip of adequate size.

6) All concealed hinged doors and covers

shall be provided with suitable flexible earthing

connections.

7) The size of the earth bus chosen shall be

to withstand full fault current of 35KA

8) Earth bus bar shall be supported at suitable

intervals.

9) All the current transformers are resin cast

type class-I only.

10) Scope includes cable end boxes, reverse

entry boxes as per site conditions and

Page No. 7 of 30

Page 8: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

extension of bus bars as required for

terminating the number of cables as per

schematic diagram.

11) G.A. & detailed fabrication drawing and

short circuit forces and temp rise calculation

for panel including the panel fabricator shall be

submitted for dept. approval.

12) Bimetallic washers to be used for all

aluminium to copper joints wherever required & it

shall be of approved make & quality whereever

required.

13) Indication lamp shall be cluster type LED.

14) All Outgoing feeders shall have 'ON'

indication lamp.

15) All neutral shall be isolatable type.

16) The Incomer sections of the Panel shall

be powder coated in orange shade for easy

identification, as per instructions of EIC.

17) The scope includes the Supply and

installation of M.S. Channel (ISMC 100 ) required

for installation of panel on cable trench.

18) Scope includs the cutting of M.S.chekered

plate trench covers to require size after

installation of Panel.

6.1 Main LT Panel: 1 set

Incomer :-

1 no. 2000 A, 415 volt 35 kA 3Pole EDO

ACB with separate tinned Cu neutral link

complete with :

a Microprocessor release having

inbuilt overload protection with

time delay, short circuit

protection and earth fault

protection.

b 230 V AC spring charging motor

and closing coil c Shunt trip coil 48 V DC and

under voltage coil 230 V AC

d Safety shutter & 6 NO + 6 NC

contacts.

e 1 no.Cast Rasin current

transformer of 2000/5A class I,

15VA, for APFC relay sensing.

f 4 nos cast resin current

transformer of 2000 / 5 ratio

class 1.0 for metering, 15 VA

Burden. (One No. CT for power g Trivector meter, class 1, base

mounting with RS 485 port

similar to Model No. ER 300P of

M/s L&T.

h 96 sqmm 0-2000 amp ammeter

with 3-way & OFF selector

switch

I 96 sqmm 0-500 V voltmeter with

3-way & OFF selector switch

j 1 set of three R Y B indicating

lamps

Page No. 8 of 30

Page 9: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

k Red / green / amber ON / OFF /

Trip indicating lamps / trip circuit

healthy

l Spring charge indication lamp

m Breaker control switch

nStatic Restricted earth fault relay

Page No. 9 of 30

Page 10: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

o 3 nos cast resin current

transformer of 2000 /1 ratio

class P.S for restricted earth

fault relay.

p Terminal to receive 2000A

sandwitch type Aluminium bus

duct.

q All Tinned Copper neutral links

shall be isolable.

r Over voltage relay

Note:

1. All inter connection for

incoming & outgoing should be

with copper busbar.

2. Vertical bus rating shall be

based on outgoing feeders.

3. All MCCBs shall be 415 V, 35

KA.

4.The incomer ACB (2000A) and

400 MCCB, outgoing feeder no.

1 shall have interlock.

5. Cubicle illumination lamp &

space heater in the cable alloy

should be provided

Bus bar

2000 A TPN tinned copper bus bar having

maximum current density of 800 A/sq.inch to

withstand symmetrical fault level of 35 KA at

415 V. The neutral bus bar shall have 100%

capacity

Outgoings :-

I) 2 Nos. 400 A TP MCCB complete with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link

II) 4 No. 200 A TP MCCB complete with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link.

III) 2 No. 100 A TP MCCB complete with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link.

IV) 3 No. 63 A TP MCCB complete with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link.

7 Capacitor Panel

Supply, installation, testing & commissioning

of 415V, 50Hz Capacitor Panel of following

capacity, floor mounting, free standing &

compartmentalized design as per standard

Page No. 10 of 30

Page 11: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

design of approved panel fabricator. The

enclosure shall be fabricated from 2 mm thick

MS CRCA sheet & with IP42 degree of

protection. The Panel shall be powder coated

Air craft with Grey shade 631 as per IS-5

complete as required & as per instructions of

EIC.

7.1 150 KVAR Capacitor Panel 1 sets

Incomer :

Page No. 11 of 30

Page 12: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

1 nos 400 A 415 volt TP Isolator

with separate neutral link

complete with :

Automanual switch for

automanual operation

3 nos cast resin current

transformer of 400 / 5 ratio class

1.0,15 VA Burden,for metering.

96 sqmm 0-400 amp ammeter

with 3-way & OFF selector

switch

RYB indication lamps with fuse

96 sqmm 0-500 V voltmeter with

3-way & OFF selector switch

with fuse

8 step automatic power factor

intelligent monitoring relay

(microprocessor) to sense and

monitor the system power factor

and provide impulses for

operation of sequential

capacitor circuits.

Over voltage relay.

Power factor meter (digital)

Busbar:

400 A TPN Tinned Copper bus bar insulated with

heat shrinkable PVC sleeves & to withstand

symmetrical fault level of 35 KA at 415 V. The

neutral bus bar shall have 50% capacity

Outgoings:

a) i. 125 A TP MCCB 35 KA

complete with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link.-1 no.

ii. 3 pole contactor 110 A (AC- 3)

suitable for automatic switching

of 50 kVAR capacitor bank - 1

no.

iii. ON/OFF indication lamps - 1 set

iv. On/OFF Push button - 1 set

v. Time delay timer - 1 no.

vi. 50 kVAr hermetically sealed

metallized polypropylene

capacitor units MPP-H complete

with fuse protection, discharge

resistors, interconnections etc

complete as required.-1 set

Page No. 12 of 30

Page 13: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

b) i. 63 A TP MCCB 35 KA complete

with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link.- 3 nos.

ii. 3 pole contactor 70 A (AC- 3)

suitable for automatic switching

of 25 kVAR capacitor bank - 3

nos.

iii. ON/OFF indication lamps with

fuse - 3 sets

iv. ON /OFF push buttons.- 3 sets

v. Time delay timer- 3 nos.

Page No. 13 of 30

Page 14: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

vi. 25 kVAr hermetically sealed

metallized polypropylene

capacitor units MPP-H complete

with fuse protection, discharge

resistors, interconnections etc

complete as required.-3 sets

c).i. 40 A TP MCCB 35 KA complete

with thermal

magnetic release having over current and short

circuit relay with adequate size tinned Cu.

Isolatable Neutral link : - 2 nos.

ii. 3 pole contactor 50/40 A (AC -

3) suitable for automatic

switching of 12.5 kVAR

capacitor bank - 2 nos.

iii. ON/OFF indication lamps with

fuses - 2 sets

iv. ON/OFF Push button - 2 sets

v. Time delay timer- 2 nos.

vi. 12.5 kVAr hermetically sealed

metallized polypropylene

capacitor units MPP-H complete

with fuse protection, discharge

resistors, interconnections etc

complete as required.-2sets

8 Battery Charger : 1 set

Supply, Installation, Testing & Commissioning

of 48V 100AH self contained battery charger

cubicle panel, dust & vermin proof, well

ventillated, indoor type fabricated out of 2 mm

thick MS CRCA sheet, floor mounting type

etc. intended to operate on 415 V 50 Hz 3

phase incoming supply. The charger unit shall

be complete with float charger & boost

charger alongwith relays, DC distribution details

board, contactor, switches, Ammeter,

voltmeter etc complete as required and as per

specifications & instructions of E-I-C

DC Distribution board

i) Incoming 63 A DP MCB - 1 No.

ii) Outgoing 16 A DP MCB - 8 Nos.

9 Battery :- 1 set

Supply, installation, testing & commissioning of

lead acid battery set with polypropylene container

comprising of 24 cells of 2 V 100 AH capacity at

10 hr rate of discharge compete with inter cell

connectors, acid level indicating floats etc all as

per IS 1651 1991 and as per instructions of E-I-C

The following accessories shall be included in the

scope of work :

Page No. 14 of 30

Page 15: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

a) Battery Stand constructed out of Teak

wood and coated with anti-acid paint suitable

for accomodating above cells in single row

double tier arrangement

b) Tubular cells

Page No. 15 of 30

Page 16: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

c) Stand insulators

d) Syringe type hydrometer suitable for

specific gravity readings.

e) Cell testing voltmeter (3-0-3) complete with

leads

f) Spanner ( Inter connector bolt wrenches)

g) Inter cell connector with nuts, bolts & washers

h) Vent plugs

i) Acid resisting jugs & funnels.

j) Rubber Gloves

k) Syringes

10 M.V.Cables

Supply, installation, testing & commissioning of

1.1 KV grade aluminium stranded circular/ sector

shape core conductor with semi conductor

shielding, PVC/XLPE insulation with semi

conductor sheilding copper taped screening, PVC

tape (inner) sheathed, G.I with flat strip

armoured, PVC outer sheathed cable conforming

to IS : 1554 Part I / IS 7098 Part-I with latest

amendments, fixed on wall/column/slab/false

ceiling or in existing hume pipe/trench/ shaft/pit/

on 5mm thick M.S. flat /GI spacer/angle/ support

fixed with coach screws/grouted in wall/anchor

fasteners 2mm. thick G.I. fabricated saddle, all

fixing accessories, etc complete including

painting of M.S spacers/angles and saddles or in

ground at a - depth of 900 mm below ground

level/in all types of soil/concrete road cutting/foot

path cutting including excavation, sand bedding,

laying of baked bricks on side & top-, temporary

reinstatement, back filling, dewatering,

consolidation, disposal of excess earth within the

radius of 500 mtrs and making good to the

original finish etc providing brass cable number

tag as per enclosed detailed specifications,

drawings & as per instructions of the E-I-C & of

the following sizes.

MS supports will be measured under item no.31

NOTE:

1) For single cable in route upto 3 1/2 X 70

sq.mm. GI spacer can be used.

2) More than one cable is taken on M.S angle

iron cable supportsmade with 40 x 40 X 5 mm

angle section, duly painted shall be used. M.S

supports shall be measured under item no.31.

Page No. 16 of 30

Page 17: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

3) The length given against quantity of cable

shall be treated as route length.

4) Sealing of hume pipes with wooden bushes after

cable laying shall be included in the scope of

work.

10.1 1 No. of 3.5C X 70 sq.mm Aluminium PVC/

XLPE armoured cable for pump house.

10.1.1 In hume pipe/GI pipe/trench # mtr.

10.1.2 In ground # mtr.

10.2 1 No. of 3.5 C X 35 sq.mm Aluminium PVC/

XLPE armoured cable

10.2.1 In hume pipe/GI pipe/trench # mtr.

10.2.2 In ground # mtr.

10.3 1 No. of 4 C X 25 sq.mm Aluminium PVC/

XLPE cable.

10.3.1 In hume pipe/GI pipe/tench # mtr.

11 End Joints

End jointing of following sizes of cable by

crimping with supply of all jointing materials like

solderless tinned copper cable socket,double

compression brass cable glands, gland earthing,

insulation tape, flux, duplicate interconnection

between gland earthing strip & to the nearest

earthing bus terminals as per the drawings,

specifications and as per the instructions of the

Engineer-in-charge.

11.1 1 No. of 3.5C X 70 sq.mm Aluminium PVC/8 nos.

XLPE cable

11.2 1 No. of 3.5 C X 35 sq.mm Aluminium PVC/2 nos.

XLPE cable

11.3 1 No. of 4 C X 25 sq.mm Aluminium PVC/2 nos.

XLPE cable

12.0 CONTROL CABLES:

Page No. 17 of 30

Page 18: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

Supply, installation, tesing,

commissioning of 1.1 KV grade

multicore PVC insulated, taped

PVC inner sheath G.I wire/strip

armoured , multi stranded

copper conductor overall

extruded PVC sheathed control

cable all as per IS 1554 Part I &

latest ammendments laid in

ground to a depth of 900 mm

below the ground level /in RCC

hume pipe / fixed on trench / on

wall etc on 5 mm thick GI spacer

/2mm thick GI saddle/ MS flats /

angle support fixed with wood

screws / coach screws / anchor

fasteners including painting of

saddle / flat / angle iron etc. The

cables in ground shall be

covered on top & sides with

baked bricks conforming to I.S.

1077 including excavation in all

types of soil, soft rock / hard

rock, dewatering, sand bedding ,

back filling & re- instatement ,

consolidation & removal of

excess earth within a radius of

500 metres, complete & as per

dept. specifications, drawings, &

as per instructions of Engineer-

in-Charge.

Note: Sealing of hume pipe with wooden bushes,

after cable laying shall be included in the scope

of work.

12.1 2 C x 4 sq.mm control cable

12.1.1 In Hume pipe/GI pipe On Wall/Trench# mtr.

12.1.2 In ground # mtr.

12.2 4 C x 1.5 sq.mm control cable

12.2.1 In Hume pipe/GI pipe On Wall/Trench# mtr.

12.2.2 In ground # mtr.

13 End Joints of control cables

End jointing of following sizes of cable by

crimping with supply of all jointing materials like

solderless tinned copper cable socket,double

compression brass cable glands, gland earthing,

insulation tape, flux, duplicate interconnection

between gland earthing strip & to the nearest

earthing bus terminals as per the drawings,

specifications and as per the instructions of the

Engineer-in-charge.

Page No. 18 of 30

Page 19: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

13.1 2 C x 4 sq.mm control cable # nos

13.2 4 C x 1.5 sq.mm control cable # nos

14.0 Cable marker # nos

Supply, installation of

oval/circular shaped G.I cable

Page No. 19 of 30

Page 20: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

marker engraved as "M.V/HV

Cable/HT straight through joint".

complete with 32mm dia NB

medium G.I pipe support

as per IS 1239 with 1:2:4 PCC

base concreting, G.I

nut bolts, including excavation in

all types of soil upto

required depth and refilling etc

all as per drawing,specifications and as per the

instructions of E.I.C

15 EARTHING SYSTEM

Supply,installation,testing & commissioning of

earthing system & asociated accessories,

etc. complete as per specifications & as per

the instructions of E-I-C.

NOTE:

1) Measurement of resistance of each earth

station & resistance of complete scheme of

earthing layout must be measured.

2) Jointing of the earth strip shall be brass bolt

& nuts only also with solder joints.

3) Jointing of the earth wire shall solder joints

only.

15.1 Providing and making earth station with Tinned6 nos

Cu. earth plate electrode 600 X 600 X 3.15 mm

earth station 2.5 mtr. below ground level as per to

IS 3043 & as per drawing No. CED/E&M/STD/12

complete with all required materials like coke

/charcoal, salt, brass nut-bolt & washers,

watering arrangement, G.I. Pipe (B class) , funnel

with wireness, concrete chamber, 12 mm thick

chequered plate hinged cover mounted on

40x40x5 mm thick angle iron frame & excavation

in all types of soil in ground refilling & removal of

excess earth within radius of 500 m. etc.

NOTE

1) The chamber cover & frame shall be hinged

type & it shall be got approved by department.

15.2 Tinned copper earth wire/earth strip fixed on

wall/side of trench/slab /column /beam /shaft

connection to panel/DBs/SFU's etc. with

5mm. Thick G.I. Spacers & 2mm thick G.I.

Saddle in ground at 750 mm. below including

excavation in ground with protective baked

bricks, excavation in ground, refilling & removal

of excess earth within a radius of 500 mtr.

Temporary instatement & back filling of trench,

consolidation, interconnection of earth

strip/wire with brass bolt & nuts & washers &

solder jointing, painting with two coats of black

bituminous paint for earth wire / strip in ground

Page No. 20 of 30

Page 21: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

& green enamel paint for earth wire /strip on

surface etc.

15.2.1 32 x 6 mm tinned copper strip # mtr.

15.2.2 25 X 6 mm. Tinned copper strip # mtr.

15.2.3 8 SWG tinned copper wire # mtr.

16 DISTRIBUTION BOARDS:

Fabrication, inspection at works Supply,

installation, testing & commissioning of

following standard readymade distribution boards,

double door, IP 42 degree protection complete

with necessary, MCB isolators , MCBs, earth

leakage circuit breaker (ELCB) etc including

interconnections with appropriate capacity

size of PVC insulated copper conductor

wires,suitable for concealed mounting /wall

mounting with MS frame work of 40 x 40 x 5

mm MS angle iron, with M.S. enclosure

fabricated out of min 18 SWG thick M.S.

CRCA sheet with concealed hinged door,

locking arrangement etc. including earthing

clamps for both incoming & outgoing circuits,

interconnections, per phase isolation kit as

required,cable end box & wire way box if

required, continuous copper earth wire in the

wire way box with single/duplicate brass

earthing terminals, danger board, name plate,

flexible earthing for the door, metal treatment

& powder coated painting, Phase Distribution

drawing etc. all as per drawings (G.A. &

fabrication drawing to be got approved), etc.

relevant IS & instruction of

Engineer-in-charge.

Note:1. MCB’s shall be minimum 10 KA

breaking capacity (Type –C)

2. Blanking Plates shall be included in

scope of work.

3. DB shall be of standard readymade type as

per catalouge No. from approved

manufacturers as indicated in preferred

makes of material

4. Sample of various DB shall be got approved

by E-I-C including G.A & fabrication drawing.

5. Routine tests will be conducted at factory as

per relevant IS.

16.1 Substation DB 1 no

(12 way / phase TPN DB): similar to MS

legrand or equivalent

a) 63 A, TP MCB type Isolator ( Non -tripping

type) - 1 no

b) 63 A 2 pole ,30 mA ELCB - 3 nos

c) 6A SP MCB - 13 nos

d) 16A SP MCB - 5 nos

Page No. 21 of 30

Page 22: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

e) 10 A SP MCB - 6 nos

f) Brass neutral link - 10 way - 4 nos

g) Blanking plates

17 POINT WIRING IN CONCEALED / SURFACE

PVC CONDUIT SYSTEM:

Point wiring for light/ceiing fan/6A/ 16A/ 6 +

16A socket outlet /16A outlet for exhaust fan ,

bell point etc. with 1.1 KV grade FRLS PVC

insulated multistranded copper conductor

wire(ISI marked), in 25 to 40 mm dia High

Mechanical Stress (HMS) rigid PVC conduit

having ISI marked IS 9537 Part - 3, including

fixing accessories & hardware concealed

/exposed in slab/wall or on 5mm. thick G.I.

spacers fixed with no. 10 nettle fold wood

screws with nylon plug complete with all

conduit accessories 20 SWG G.I. Saddles,

ready made MS switchboxes, socket outlet

boxes of min 18 SWG thickness zinc chromate

passivated, brass earthing stud 1/2 nos,

controlling modular switches, sockets with

moulded front plate and inner plate etc.

including appropriate size of FRLS PVC

insulated copper earth wire , brass/bakelite

(straight / angular) lamp holders, 3 plate ceiling

rose,16 A, connectors, painting etc. as per

specifications and drawings and as per

instructions of E-I-C and as detailed below :

(sample switch Box etc. to be got approved

before fabrication)

NOTE:

1. Connections shall be done with crimped

type tinned copper lugs & washers.

2. All switches & socket outlets shall be as

per preferred makes & ISI marked.

3. All sample boxes with accessories /fixtures

shall be got approved from Department.

4. All 16 A sockets outlets should be with 6

pin & shuttered type

5. MS boxes other than switch boxes &

socket outlet boxes shall be fabricated out of

16 SWG thickness MS sheet duly painted

with red oxide primer & 2 coats of epoxy

paint.

6. Switch plates shall be fixed on M.S box by

means of chromium plated brass screws and

cup washers. Miniumum depth of the switch

box shall be 60 mm

7. Minimum size of the FRLS insulated

copper earth wire continuity shall be 2.5

sq.mm

8. The colour shade of switches & cover

plates shall be white /off white & to be

approved by E-I-C

9. The scope also includes supply of modular

blanking plates whereever required.

Page No. 22 of 30

Page 23: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

17.1 Primary light point with 1.5 sq.mm wires# pts

complete with 6A 240V switch

17.2 Secondary light point lopped to above# pts

primary point (Item No. 4.1 ) with 1.5

sq.mm wire.

17.3 Ceiling fan points with 1.5 sq.mm. wires# Pt.

complete with 6A 240 V SP switches & step

type capacitor regulator and 16 A connector for

ceiling fan of minimum 100 W capacity (There

should not be any radio & T.V. interference)

switch box shall be suitable to accommodate

any fan regulator.

17.4 Point wiring for single phase exhaust fan point4 pts

with 2.5 sq. mm wires with 16A, 240 V, 6 pin

socket near exhasut fan controlling 16 A ,

240 V Switch near entrance door

17.5 Socket outlet point with 2 nos of 6 A, 3 pin# pts

,socket & 2 nos. of 6 A, 250 V SP switch in

one box with 2.5 sq.mm wires (Supply taken

from DB)

17.6 6/16 A, 6 pin socket outlet point with 16 A SP5 pts

switch in one box with 2.5 sq.mm wires

(Supply taken from DB)

17.7

Buzzer point with 1.5 sq.mm

wires complete

3 pt

with 6A 230 V bell push &

luminous indicator

type buzzer with necessary MS

box, etc (to

work without battery).

18 Light Fixtures & Fittings:

Supply, installation, testing & commissioning

of fixtures & fittings & ceiling/exhaust fans, etc

complete with accessories, tube/lamp etc in

false ceiling / on surface of slab/beam by 2

nos (minimum) of 6 mm , anchor fasteners or

on wall by means of 25 x 3 mm G.I strip bend

into shape & with 2 nos of wood screws,

nylon plug etc., suitable supporting frame

fixed with rag bolts grouted on the wall/anchor

fastener on the beam/on the column & other

fixing accessories etc provision & connection

with 1.5 sq.mm multistranded copper

conductor FRLS PVC wires/2.5 sq.mm

copper conductor FRLS PVC insulated earth

wire etc painting with two coats of red oxide &

two coats of enameled paint, all as per

Page No. 23 of 30

Page 24: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

drawing, specifications & as per the

instruction of E.I.C.

Note:

1) Sample fixture/fittings shall be got approved

from Dept with complete technical data.

2) The Cat No. indicated below is only

indicative.

3) Cost of lamps to be included in installation

rate.

4) All fixtures shall be with low loss electronic

ballast

18.1 1 x 11 W PL type fluorescent fixture ceiling / wall mounted FMS 9 nos.

wall mounted FMS 200/111/of M/S Philips Cat .

or equivelent.

18.2 2 x 36 Fixture ceiling mounted TMC 501/236 # sets

HPF with 2 x TLD 36 W Tubes of M/S Philips

or equivelent (M/s. Philips Cat No. TMS 021 236

HF or equivalent approved).

18.3 Industrial Luminair for Fluoresent Lamp 2 nos.

(Corrosion proof)similar to M/S Philips make

TM X 95/236 HPF with 2 x 36 Wattt Tubes

or equivelent.

18.4 1 X 70 W metal halaid lighting fixture of 5 nos.

M/S Philips make Cat No. QVF 135/70 Watt

1 X MHN-TD 70 W Tubes

or equivelent.

18.5 1 X 9 W CFL bulkhead fixture of M/S Philips4 nos.

make Cat No. FXC 101 with 1 X PL S9W

or equivelent.

18.6 Emergency Luminar 2 nos.

Supply, installation, testing & commissioning

of self contained emergency luminiaire

containing 1 x 11 W fluorsecent tube, Ni-cd

batteries for 1 hour backup with suitable

mounting arrangement etc complete as per

M/s. Legrand make Emergency lighting Cat

No. 61734 or equivalent approved make.B1022

19 Ceilings Fans :

Supply, installation, testing & comissioning of

following ceiling fans with double ball bearing

with standard downrod, canopies,

shackles, blades with safety cable

suspension (Secondary support safety cable)

white colour with all accessories including

continous earthing and final connection with

24/0.2 mm dia copper conductor 2/3 core

twisted PVC flexible wire etc but without

speed regulator, suitable for operation on any

type of 100 W noise free capacitor type fan

regulator on 230 V 50 Hz single phase AC

Page No. 24 of 30

Page 25: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

as per specifications enclosed. Test

certificate as per IS 37419 shall be submitted

19.1 1200 mm sweep # nos

20 Exhaust Fan :

Supply, installation, testing & commissioning

of following size of exhaust fans , single

phase complete with blades, motor, scope

includes supply of 3C copper 1.5 sq.mm.

flexible chord of suitable length with 6 A 3 pin

plug top, aluminium louvers shutters, rag

bolt/Anchor fasterner suitable MS angle iron

frame made of 30 x 30 x 5 mm , 4 corners

covered with 2 mm thick MS sheet to form

suitable circular opening with necessary fixing

arrangement painting as per specification,

drawing as directed by E.I.C.

20.1 305 mm dia , 900 rpm 4 nos

21 Fan Hook Boxes # nos.

Supply, installation, testing of concealed fan

hook boxes of size 150 x 150 x 75mm deep

fabricated out of 2mm thick M.S CRCA sheet

with 12.5 mm dia M.S tested rod hook with

brass earthing stud & welded nut from inside

and 2mm thick round M.S cover plate

overlapping by 15 mm, including red oxide and

two coats of white synthetic enamel paints and

brass chromium plated screws for fixing and all

as per conceptional drawing No.: CED/EM

/STD/11 R4 & instruction of Engineer-in-charge

(Sample box with cover to be got approved

before fabrication including the fabricator)

22 Supply, installation, testing & commissiong6 sets

of Security lighting fixture wall mounting

consisting of :

a) Area lighting luminaire QVF-135/70 with 1 X

MHN-TD 70 W lamplamp of M/s. Phlips make or

equivalent control gear, with all accessories as

required, wired with 3C X 2.5 sq. mm PVC

insulated cable from nearest light point , fixture to

be fixed a wall with coach screws / anchor

fastner.

23 TELEPHONE POINT WIRING

Point wiring with 4 pair CAT-6 wires tinned copper

conductor PVC insulated, in 25-40 mm

dia High Mechanical Stress (HMS) rigid

gauge PVC conduit having ISI mark IS 9537

part-III, concealed in slab /wall or surface with

Page No. 25 of 30

Page 26: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

5mm thick G.I.spacer & 20 SWG GI Saddle

fixed with nylon plug, wood screws etc.

complete with all conduit accessories suitable

MS pull boxes of suitable sizes as per site

condition wherever required M.S. telephone

point accessories boxes fabricated out of min

18 SWG thick CRCA sheet zinc chromate

passivated , brass earthing studs 1/ 2 nos.,

RJ-11 telephone socket outlets with shutter

ferrule numbers on both side of the circuits all

terminations with ferrule /lugs if required,

labelling all as per drawing specifications & as

per instructions of E-I-C.

NOTE:

1. Point wiring means 4 pair CAT-6

wires from TTB to assigned point

including end termination of one pair at both

sides and other pairs should be kept spare.

2. G.A drawings & fabrications drawing are to

be got approved from E-I.C.

23.1 Point wiring for telephone point with 4 pair 6 pts

CAT-6 wire with RJ 11 jack type socket

with shutter in a box with connector

(Modular type)

24 Supply, installation, testing & commissioning of

KRONE connector telephone tag block box

fabricated out of 16 SWG M.S. CRCA sheet,

mounted on MS frame of size 40 X 40 X 5mm.

& grouted on the wall/fixed on the column free

standing type with anchor fasteners, cable end /

wire way box with adequate space facility to be

provided in the TTB , with front openable hinged

door, cam type locking arrangement, neoprene

rubber/cork gasket for joints, painting with seven

tank metal treatment process with powder

coated with approved shade (no. 631 of I.S. 5)

name plate, etc. all as per the specification,

drawing & instructions of E.I.C.

NOTE:

1. Point distribution diagram shall put in side the

DB with polythene protective cover.

2. All fabrication drawings shall be got approved.

24.1 20 pair telephone tag blocks 1 no

Page No. 26 of 30

Page 27: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

as required.

25 Safety Equipment

25.1 Providing and fixing carbon di-oxide ( CO1 no

type fire extinguishers conforming to IS

2878-1976 and cylinders fully charged of 4.5 kg

capacity.

25.2 Supply and fixing of foam fire extinguishers,1 no

portable type 9 litres capacity hanged on wall

with brakcet complete as required,

25.3 Supply and fixing safety instruction chart in1 no

word duly frame with 5 mm thick glass as

required ( approx front area 1.20 sq.mt)

25.4 Supply and fixing of electric schematic as1 no

built drawing in frame with 5 mm thick glass

as per instructions of E-I-C

25.5 Providing of set of 4 nos 9.5 litre capacity GI1 set

bucket painted in post office red colour with

prior coat of red-oxide paint with written with

white paint 'FIRE' and mounted on MS angle

iron frame with bracket appropriate size &

capacity including filling

25.6 Providing fire aid box as approved by St. John1 set

Ambulance Brigade/Indian Red Cross

conforming to IS 2217-1963

25.7 Supply & fixing shock treatment chart duly 1 no

mounted on a wooden frame with 5 mm thick

glass as required (approximate front area 1.20

sq.mtr)

25.8 Supply and fixing in position of 'B' class6 mtr.

'ELASTOMER' insulating matt for protection

to operators for working voltages upto 11 KV

as per IS 15652 - 2006 of size 1000 mm (W)

x 2.5 mm (thickness)

25.9 Supply and fixing in position of 'A' class3 mtr.

'ELASTOMER' insulating matt for protection

to operators for working voltages upto 3.3 KV

as per IS 15652 - 2006 of size 1000 mm (W)

x 2 mm (thickness)

25.10 Supply of pedestal type sign

board for substation of size 1530

mm x 900 mm fabricated out of

50 mm x 50 mm x 5 mm angle

including providing and fixing

900 mm x 600 mm x 1.6 mm MS

sheet duly welded , painted and

printing as desired and fixing in

ground complete as required

and as per the instructions of E-I-

C.

1 no

Page No. 27 of 30

Page 28: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

25.11 Supply & fixing of display board

for sub-station of 800 mm x 230

mm x 5 mm perspex sheet

including printing on the sheet

etc and fixing the same on wall

complete as required and as per

the instructions of E-I-C.

3 no

25.12 Supply of artificial respirator as

per Director General of Medical

Supplies , Govt of India ,

required as per IE Rule no 44

1 no

25.13 Supply and fixing of danger plate

of size of 250 X 200 mm as per

approved sample writern in

english and hindi for LV and HV

made out of 2 mm thick M.S

sheet.

4 nos.

26 Excavation below groung level for trenches in# c.m.

hard rock upto depth of 1200 mm including

shroing and dewatering if necessory, dressing

the sides, trimming and refilling watering,

consolidation etc and stacking or disposing of

the excaveted materials with in a distance of

60 mtr. Etc complete as per specifications,

drawing and as directed by EIC.

27 Hume Pipe

Supply, installation of RCC hume pipes of 150mm

dia. (non-pressure type) along with collars,

including excavation below 900mm ground level in

all types of soil/soft rock/asphalt road/concrete

road & jointing of pipes with cement, back filling,

consolidating, reinstatement, removal of excess

earth within a radius of 500mtrs. etc. & making

the road good to its original finish all as per

specification, drawing & instructions of E.I.C.

27.1 150 mm dia RCC hume pipe # mtr.

28 Supply, installation of 38mm dia. GI pipe of B# mtr.

class sleeves in beams/column/slab for passing

electrical cables/conduit as per instruction of

E-I-C

29 Supply, installation, fabrication of cable support # kgs.

by M.S. angle/ channels/ flats etc.

including painting alongwith suitable fixing

hardware/accessories as per instruction of E-I-C

30 Supply & installation of 150 mm dia. Cast iorn# mtr.

pipe to be laid in ground with necessary joints,

concrete supports. Scope includes escavation in

below ground level/in all types of soil/concrete

Page No. 28 of 30

Page 29: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

road cutting/foot path cutting, nallah cutting

including excavation, back filling, dewatering,

consolidation, reinstatement as original,disposal

Page No. 29 of 30

Page 30: Tender Specs-Electrification of Apartments

Sl.No Description of Item Qty Unit Rate (In Rs.) Amount

Supply Install Total (Rs.)

of excess earth within the radius of 500 mtrs and

making good to the original finish etc.

Signature& Seal of Tenderer