tender document for electrical work for … tender... · tender document for electrical work for...

24
BANK OF INDIA ZONAL OFFICE BHUBANESWAR TENDER DOCUMENT FOR ELECTRICAL WORK FOR BRANCH & E-GALLERY OF BANK OF INDIA, KALINGA VIHAR BRANCH Prepared by: Architects Chamber 07,Bivab Estate, Baramunda Bhubaneswar, Ph-0674-2563849 [email protected]

Upload: dokhue

Post on 18-May-2018

221 views

Category:

Documents


1 download

TRANSCRIPT

BANK OF INDIA ZONAL OFFICE

BHUBANESWAR

TENDER DOCUMENT

FOR

ELECTRICAL WORK FOR BRANCH &

E-GALLERY OF BANK OF INDIA,

KALINGA VIHAR BRANCH

Prepared by:

Architects Chamber 07,Bivab Estate, Baramunda

Bhubaneswar, Ph-0674-2563849 [email protected]

2

NOTICE OF INVITATION TO TENDER

Sealed tenders on item rate basis are invited from empanelled electrical contractors

having sound technical and financial capacity for ELECTRICAL WORK FOR

BRANCH & EGALLERY OF BANK OF INDIA, KALINGA VIHAR BRANCH, ..

Tender documents may be collected from the office of Architects Chamber 07,Bivab Estate, Baramunda Bhubaneswar against payment of Rs 500.00

(Rupees Five hundred) only (non-refundable) by A/C payee Demand Draft drawn on

Bhubaneswar.

Estimated cost of the Project : Rs 2.42 Lakh

Earnest money : Rs 3000.00 by A/C demand draft drawn in

favour of Z.M. BANK OF INDIA,

BHUBANESWAR.

Time of completion : 15 days

Tender paper sale date : 09.02.2016 to 17.02.2016

Time and date of : before 14.30 hrs on 17.02.2016 as per

Submission of tender instruction tender documents

Time and date of

Opening of tender : at 15.30 hrs on 17.02.2016

The bank will not be bound to accept the lowest tender and reserve the right to accept or

reject any or all the tenders without assigning any reason whatsoever.

ZONAL MANAGER

BANK OF INDIA,

ZONAL Office

BHUBANESWAR

3

GENERAL RULES AND INSTRUCTIONS

FOR THE GUIDANCE OF TENDERERS

1. Tenders are hereby invited on behalf of BANK OF INDIA, ZONAL OFFICE,

BHUBANESWAR, for ELECTRICAL WORK FOR BRANCH &

EGALLERY OF BANK OF INDIA, KALINGA VIHAR BRANCH, . Contract

documents consisting of the plans complete specifications, the schedule of

quantities of the various class of work to be done, and the set of conditions of

contract to be complied with by the persons whose tenders may be accepted, and

which will also be found in the form of tenders, can be seen at Architects Chamber 07,Bivab Estate, Baramunda Bhubaneswar and BANK OF

INDIA, ZONAL Office, BHUBANESWAR, between the hours of 10.30A.M to

5.30P.M, from 09.01.2016 to 17.01.2016 and every day, except on Sundays and

bank holidays

2. Tenders, which should always be placed in sealed cover with the name of the

project written on the envelopes will be received by Sr. Manager (Premises),

BANK OF INDIA, ZONAL Office, BHUBANESWAR, up to 14.00 hrs on

17.02.2016 and will be opened in his office on the same day at 15.30 hrs.

3. The time allowed for the carrying out of the work will be 15 days from the day

after the date of written orders to commence work.

4. The contractors should quote in figures as well as in words the rate, and

amount tendered by them the amount fore each item should be worked out and the

requisite totals given.

5. When a contractor signs a tender in an Indian language the percentage above or

below and the tendered amount and the total amount tendered should also be

written in the same language in the case of illiterate contractors the rates or the

amounts tendered should be attested by a witness.

6. Earnest money, amounting to Rs. 3000.00 in the form of bank draft drawn in

favour of Z.M. BANK OF INDIA, BHUBANESWAR. must accompany each

tender and each tender is to be in a sealed cover super scribed tender for

ELECTRICAL WORK FOR BANK OF INDIA, KALINGA VIHAR BRANCH, and addressed to the Z.M., BANK OF INDIA, ZONAL Office,

BHUBANESWAR.

4

The contractor, whose tender is accepted, will be required to furnish by way of

security deposit for the due fulfillment of his contract, such sum as will amount to

10.00% of the work order.

The EMD of the contractor, whose tender is accepted, shall be forfeited in full in

case he does not remit the Initial security deposit within the stipulated period or

start in the work by the stipulated date mentioned in the award letter.

7. The acceptance of a tender will rest with the ZONAL MANAGER, BANK OF

INDIA ZONAL Office, BHUBANESWAR which does not bind itself to accept

the lowest tender, and reserves to itself the authority to reject any or all of the

tenders received without the assignment of a reason. All tenders in whom any of

the prescribed conditions are not fulfilled or are incomplete in any respect are

liable to be rejected.

The bank reserves the right to accept the tender in full or in part and the tenderer

shall have no claim for revision of rates or other conditions if his tender is

accepted in parts.

8. Canvassing in connection with tenders is strictly prohibited and the tenders

submitted by the contractors who resort to canvassing will be liable to rejection.

9. All rates shall be quoted on the proper form of the tender alone.

10. An item rate tender containing percentage below/ above all is summarily rejected.

However, where a tender voluntarily offers a rebate for payment within a

stipulated period, this may be considered.

11. On acceptance of the tender, the name of the accredited representative(s) of the

contractor who would be responsible for taking instructions from the

Employer/Architects shall be communicated to the Employer.

12. Special care should be taken to write the rates in figures as well as in words and

the amounts in figures only, in such a way that interpolation is not possible. The

total amount should be written both in figures and in words. In case of figures, the

words “Rs.” Should be written before the figure of rupees and words “P” after the

decimal figures, e.g. Rs. 2.15p and in case of words, the word “Rupees” should

precede and the word “Paise should be written at the end, unless the rate is in

whole rupees and followed by the words, only”, it should invariably be up to two

decimal places. While quoting the rate in schedule of quantities, the word “only”

should be written closely following the amount and it should not be written in the

next line.

13. The bank does not bind itself to accept the lowest or any tender and reserves to

itself the right of accepting the whole or any part of the tender and the tender shall

be bound to perform the same at the rate quoted.

5

14. All taxes including Sales Tax or any other tax on material or on finished works

like works contract tax, Turn over Tax, etc. in respect of this contract shall be

payable by the contractor and the bank will not entertain any claim whatsoever in

this respect.

This particular aspect should be mentioned in the tender

15. The contractor shall give a list of his relatives working with bank along with

their designations and addresses

16. No employee of the bank is allowed to work as a contractor for a period of two

years of his retirement from Bank service, without the previous permission of the

Bank. The contract is liable to be cancelled if either the contractor or any of his

employees is found to be worked as a bank employee within two years of the

contract and he has not taken permission from the bank to do so.

17. The tender for the work shall not be witnessed by a contract or contractors who

himself/themselves has/have tendered or who may and had/have tendered for the

same work Failure to observe this condition would render tenders of the

contractors tendering as well as witnessing the tender liable to summary rejection.

18. It will be obligatory on the part of the tendered to tender and sign and tender

documents for all the components parts and that, after the work is award, he will

have to enter into an agreement for each component with the Competent

Authority in the Bank.

19. The tendered, apart from being a competent contractor must associate himself

with agencies of the appropriate class who are eligible to tender for (1) Electrical

(ii) Sanitary and Water Supply installations and (iii) Horticulture.

20. The quantity of work can be reduced or increased depending upon the

requirement before/during the commencement of the work

Zonal Manager

BANK OF INDIA

ZONAL Office

BHUBANESWAR

6

LIST OF APPROVED MAKE FOR ELECTRICAL WORKS

SlNo Material Description Make of materials

01. M.S.conduit pipe BEC/Supreme/Kalinga/Any other

make with ISI mark

02. M.S.conduit accessories Universal/ Laxmi

03. Switch,socket,holder,ceiling MK India/Legrand/ABB

rose,modular switch box etc SchneiderElectric(ZENCELO)

04. PVC insulated wires Finolex/L & T/ HAGOR/Anchor

05. Bakelite sheets Hylam/Formica

06. PVC insulated cables NICCO/INCAB/Fort Gloster/CCI/

(with ISI mark only) Universal

07. Cable lugs Dowells/Ismal/Clipon

08. Cable jointing kits M Seal

09. Switch gears viz isolator EE/Siemens/L&T/Havells/GEC

switches,SFU,starter,change Alsthom/Indo-Asian

over switch,HRC fuse holder etc

10. MCB, RCCB and associated MDS/L & T/Standard/LEGRAND

distribution board

11. Instrument viz voltmeter etc AE/IMP/Meco

12. Selector switch Kaycee/Saltzer

13. Energy meters GEC/Capital/Jaipur/Havells

14. LT Distribution Board ESS/VeeESS/Technocrat/East

7

(Fabricated) Coast or any other standard

panel manufacturing unit.

15. Kitkats Anchor

16. HRC fuses EE/Siemens/L&T/Indo-Asian

17. CTs & PTs AE/Kappa/Eastern Switchgear

———————————————————————————————-

SlNo Material Description Make of materials

———————————————————————————————-

18. Metal clad plug socket Crompton/Havells/Indo-Asian

19. Trim tubes/ Structurella Decon

20. CFL/Fluorescent fixtures Philips/Crompton/Bajaj/PACE/K-Lite/Indo

Asian

21. Lamps (CFL/Fluorescent) Philips/Bajaj/Crompton/ECE/

Sylvania/Osram

22. Cabin & Pedestal fans Crompton/Khaitan/Usha/Orient

Almonard

23. Exhaust fan Almonard/Crompton

Khaitan

24. Adhesive & Insulating Tapes Steelgrip

25. G.I.Pipes TATA/Jindal/Prakash

26. Clip-in-type modular switches MK(India)/Legrand/ABB

& plug sockets. Schneider Electric(Zencelo)

————————————————————————————————

8

ELECTRICAL WORK OF BRANCH & EGALLERY COUNTER OF BANK OF INDIA,

KALINGA VIHAR BRANCH, BHUBANESWAR

ABSTRACT OF TENDER

SEC NO. DESCRIPTION AMOUNT

1

ELCTRICAL WORK OF BRANCH

2

ELCTRICAL WORK OF EGALLERY

SUMMURY

Section-1 ELECTRICAL WORK OF BRANCH

SL NO. ITEM DESCRIPTION QTY UNIT RATE AMOUNT

A PANELS, DBs, CABLING,

1 MAIN INCOMING PANEL (MIP)

9

Supply, installation, testing and commissioning of

wall /floor mounted indoor type, air insulated, totally

enclosed vermin-proof, dead front, cubicle type, 2

mm thick sheet steel enclosure main incoming (MIP)

Panel suitable for use on 415 V, 3 Ph., 4 wire, 50 Hz.

A.C. system, incoming and outgoing cable

compartment. Each unit shall be accommodated in a

totally separate compartment having gasketted

hinged door with locking arrangement. The Panel

shall be complete with MCCBs/MCB of following

ratings, interconnection, G.I. earth busbar of

adequate size covering the total length of panel board

with drilled holes, G.I. bolts, nuts, washers etc.

The cubicle should be painted with 2 (two) coats of

light grey synthetic enamel paint over two coats of

zinc chromate primer. The complete fabrication,

construction shall be done as per the detailed

specification and conforming to the relevant IS.

Name plate of Panels Danger Board, incoming and

outgoing feeders with Ampere rating of MCCB/MCB

are to be fixed up on front door above or below the

respective switches. Short circuit I.C. of all MCBs

should be of 10 KA (min.) Approval of

Manufacturer’s drawings from Consultant /

Employer is required before commencing

manufacture.

The MIP consists of the following

Incoming- 1No 125 A TPN SDF with HRC switch

125A bus bar- 2 No.

63 A Change over

Phase indicator lamp.

PVC sleeved TPN Tinned Copper Busbar

Out going- 5 Nos 32 A DP MCB for A.C

1Nos 32A DP MCB for LDB/PDB

1Nos 32 A SP MCB for Glow sign Board.

2Nos 40 A FP MCB for UPS

1-500 Amp. Meter with selector switch Volt meter 1.00 Set

Rate in Words :

10

2 MCB DISTRIBUTION BOARD

Supply, installation, testing and commissioning of

following MDS make Legrand Distribution Board in

sheet steel enclosure with double door and suitable

for mounting on wall by chase cutting and flushed

with finished level to the position shown in the

Electrical Layout complete in all respect, mending

good all damages to the original finish, painting,

interconnection, etc. as required. Short circuit I.C. of

all MCBs should be 10 KA (minimum) and RCBOs

should have earth leakage, overload and short circuit

protection. Name plate of DB’s to be fixed / written

on front door alongwith switch board numbers / DB’s

at the outgoing.

a LIGHTING DISTRIBUTION BOARD (LDB)

12 way vertical type DP DB complete with busbar

and the following MCB.

Incoming :

1 No. 32A DP MCB

Outgoing

10 No. 6-10 A SP MCB

02 Nos. Blank plate 1 No

Rate in Words :

b DB WITH 32A SPN MCB

Double pole 1way MCB DB in sheet steel enclosure

with 1 No. 32A SPN MCB complete with

interconnection, etc. as required for operation of

Glow Sign Board. 1 No

Rate in Words :

B WIRING, EARTHING

SUBMAIN WIRING

11

Submain wiring with following sizes 1100 V grade,

single core, PVC insulated flexible FRLS copper

conductor cable (IS:694) through suitable size M.S.

conduit (ISI marked embossed on conduit surface)

complete with junction box, circular box, elbows,

bends and other accessories on surface above false

ceiling or concealed by chase cutting on wall, as per

site condition, mending good all damages to original

finish, interconnection, painting etc. as required to be

completed in all respect. All connections of wires to

be done by means of “Wago” type connectors:

1

A. Recessed wiring with 2x (1x1.5sqmm) + 1x

(1x1.0sqmm) copper wire 40 Mts.

Rate in Words :

2 B. Recessed wiring with 2x(1x2.5sqmm)

+1x(1x1.5sqmm) copper wire. 30 Mts.

Rate in Words :

3 C. Recessed wiring with 2x (1x4sqmm) + 1x

(1x2.5sqmm) copper wire. 40 Mts.

Rate in Words :

4 A.C DB

Supply& fixing of 3ph-4way. Triple pole and neutral,

sheet steel MCB double door distribution box with

9nos of 6to 32amps, 10ka rating, 240volts, single

pole miniature circuit breaker, & and 1no 40a 4p

MCB complite with tinned coper busbar, neutral link,

earthbar, din rail, detachable gland,complite with

connections ,testing, commissioning etc,as required, 1 NO

Rate in Words :

A.C. POWER POINT WIRING :

12

A.C. power point wiring from DB with 1100 volt

grade 2 Nos. single core 4 sq.mm. + 1 No. 2.5sq.mm.

(Green colour for earthing) PVC insulated flexible

FRLS copper conductor cable through suitable size

PVC. conduit (ISI marked embossed on conduit

surface) complete with junction box, circular box,

elbows, bends, couplers and other accessories on

surface above false ceiling or concealed by chase

cutting on wall complete with North-West make AC

power unit having 25A Socket, 20A Starter,

mounting box & front plate, interconnection,

mending good all damages to original finish, painting

etc. as required. All connections of wires to be done

by means of ‘Wago’ type connectors. (INCLUDING

E LOBBY)

5 a) Recessed wiring with 2x (1x4sqmm) + 1x

(1x2.5sqmm) copper wire 50 Mts.

Rate in Words :

6

b)Supply & Installation of Modular type 20 Amp

A/C starter with 25 Amp Socket & Top 6.00 Set

Rate in Words :

6 / 16A SOCKET OUTLET POINT WIRING

7

Wiring for 6 pin 6/16 A shuttered socket outlet with

controlling switch from DB with 1100 volt grade 2

Nos. single core 2.5 sq.mm. + 1 No. 1.5 sq.mm.

(Green colour for earthing) PVC insulated flexible

FRLS copper conductor cable (IS:694) through

suitable size M.S. conduit (ISI marked embossed on

conduit surface) complete with junction box, circular

box, elbows, bends, couplers and other accessories

on surface above false ceiling or concealed by chase

cutting on wall

13

The work includes supply & fixing of non - modular

type 6/16A 6 pin shuttered socket outlet with

controlling switch, indicator, suitable size mounting

box and front plate for socket outlet flushed with

finished wall, mending good all damages to original

finish, interconnection, painting, etc. as required to

be completed in all respect. All connections of wires

to be done by means of ‘Wago’ type connectors. 6 No

Rate in Words :

POINT WIRING

Point wiring with 1100 V grade 3 nos. single core 1.5

sq.mm. (1 for phase, 1 (black colour) for common

neutral by looping method and 1 (green colour) for

common earth by looping method) PVC insulated

flexible FRLS copper conductor cable (IS:694)

through suitable size PVC. conduit (ISI marked

embossed on conduit surface) complete with junction

box, circular box, elbows, bends, couplers and other

accessories on surface above false ceiling or

concealed by chase cutting on wall from light & fan

switch board to light, fan & 6A socket outlet on the

same switch board or separately mounted switch

board.

The work includes supply and fixing of all materials

such as non - modular type 6A switch for each light

and fan point, 6A 2/3 pin shuttered socket outlet with

switch, 3 plate ceiling rose / angle or batten holder

etc. as required. The point wiring also includes

circuit wiring with 1100 V grade 2 nos. single core

2.5 sq.mm. (1 for phase and 1 (Black colour) for

neutral) + 1 no. single core 1.5 sq.mm. (Green colour

for earth) PVC insulated flexible (FRLS) copper

conductor cable (IS:694) through suitable size M.S.

conduit as described above from DB to switch

board, interconnection, mending good all damages to

original finish, painting etc. as required to be

completed in all respect.

14

All connections of wires to be done by means of

“Wago” type connectors. (All wiring in strong room,

locker room, records & stores will be of surface

conduit type.)

Light points

8 a) With one 5Amp switch controling Two nos of

light points 18 No

Rate in Words :

9 b) With one 5Amp switch controling One nos of light

points 22 No

Rate in Words :

10 Wall Bracket fan point with 2/3 pin socket outlet

installed at fan height & switch at the light fan switch

board. 7 No

Rate in Words :

11 Exhaust fan point 3 No

Rate in Words :

12

Ceiling fan point with supply and fixing of electronic

regulator (2 module step, 280 watt ( min.) ) 2 No

Rate in Words :

13 Call bell point with bell push 1 No

Rate in Words :

14 1x6A 2/3 pin shuttered socket with switch on

separate switch board other than light / fan switch

board / on work stations with connection of

maximum 2 Nos. Sockets in one circuit by looping

method 18 No

Rate in Words :

15 1 X 6A 2/3 pin shuttered socket outlet with switch on

light and fan switch board. 7 No

Rate in Words :

15

16 Connecting the Main Incoming panel to existing

earth busbar including supply and fixing of 6 SWG

G.I. wire along the cable with G.I. staples, bolts,

nuts, washers, etc. and mending good all damages to

original finish. 15 Mtr.

Rate in Words :

17 Earthing (General)

Earthing the installation as per I.E rules conforming

to IS : 3043 or its latest ammendment by making

earth station with 600 mm x 600 mm x 6 mm

(minimum) thick G.I plate electrode to be installed

such that its top edge shall be at a minimum depth of

3.0 metre below ground level after preparation of

ground with charcoal and salt and connecting the

25mm x 6mm G.I earth lead-in-strip directly in

ground by bolting and then brazing to the G.I plate

complete with G.I bolts of suitable length double nuts

and washers including supply and fixing of 50mm

dia. partly perforated G.I. pipe with funnel for

watering arrangement.

The earthing installation should be provided with

300mm x 300mm and 300mm depth inside

dimension masonry inspection pit with C.I. hinged

cover having locking arrangement, test link of size

150 mm length x 25mm x6mm G.I flat connected to

G.I earth lead-in-strip and restoring the surfaces duly

rammed. 2 No

Rate in Words :

18

Supply & fixing of fan-hook / clamp by cutting roof

slab and welding 10 mm dia. Fan hook with main re-

inforcement of roof slab complete in all respect. 2 No

Rate in Words :

19

Supply and fixing of 1.5 meter length 3 core 2.5

sq.mm PVC insulated copper wire with 3 pin 6A

plug top at one end and the other end to be fixed with

Switch Board of strong room. 1 No

16

Rate in Words :

C INSTALLATION OF LIGHT FITTINGS & FAN

Installation of following light fittings with lamp and

other electrical fittings including all accessories :

1

Installation, testing and commissioning of 2x18 W

LED light fitting with LED lamps in 1' X 1' Grid

directly on ceiling including supplying and fixing of

2 nos. M.S. clamps or hard wood round block

properly shelac polished suitable for wall / ceiling

mounting including interconnection between light

points and fittings with 3 nos. single core / 3 core

1.5sq.mm. PVC insulated flexible FRLS copper

conductor cable, painting etc. as required. 10 No

Rate in Words :

2

Installation, testing and commissioning of 2 x 18 W

LED light fittings with lamp including supply and

fixing of 10 SWG G.I wire for hanging of fittings

flushed to the false ceiling, 20mm dia. M.S flexible

conduit (800 mm approximately) including

interconnection between light points and fittings with

3 nos. single core / 3 core 1.5sq. mm PVC insulated

flexible FRLS copper conductor cable, painting, etc.

as required. 10 No

Rate in Words :

3 Installation, testing and commissioning of ceilling

mounted LED down light lurninaire recessed in

false ceiling complete with attachment, 1x10 W

lamp, all other accessories, interconnection etc. as

required. 26 No

Rate in Words :

17

4

Installation, testing and commissioning of 1200 mm

sweep capacitor type ceiling fan complete with

blades, down rod and all other accessories to the

position as shown in the drawing, painting the down

rod and interconnection between fan points and fan

with 3 nos. single core/3 core 1.5sq.mm PVC

insulated FRLS flexible copper conductor cable as

required. 2 No

Rate in Words :

5

Installation, testing and commissioning of heavy duty

type ISI marked 400 mm dia. wall bracket fan

suitable for 240V single phase 50 Hz. A.C. supply

complete with all accessories and interconnection

between fan points and fan with 3 core 1.5sq.mm (1

for earth, green colour) PVC insulated flexible FRLS

copper conductor cable, painting, mending good etc.

as required. 7 No

Rate in Words :

6

Installation, testing and commissioning of heavy duty

type ISI marked 300mm dia. Exhaust fan suitable for

240V single phase 50 Hz. A.C. supply complete with

louvre, interconnection between fan points and fan

with 3 nos. single core/3 core 1.5sq.mm PVC

insulated flexible FRLS copper conductor cable,

making suitable size holes on wall to accommodate

the fan, mending good to the original finish, painting

etc. as required. 3 No

Rate in Words :

7 Supplying and fixing on wall call bell buzzer

(approved by Consultant) suitable for 230 volt single

phase A.C. supply including interconnection, etc. as

required. 1 No

Rate in Words :

18

8 Supply and fixing of additional length of down rod

for ceiling fan having 100mm length. (50mm length

or more to be rounded off to the 100 mm and less

than 50 mm length will not be considered for

payment). 2 No

Rate in Words :

D COMPUTER POWER WIRING

1 UPS INPUT DB

Supply,fitting and fixing in position single phase

UPS input DB,(company made with double door

cover to be used ) M.S. Cubical Type duly flushed

with the wall surface

Incoming -63amp, Isolater 2Pole -1no

Out going -40 amp,DP MCB -2nos 1 set

Rate in Words :

2 UPS OUTPUT DB

Supply,fitting and fixing in position single phase

UPS OUTPUT DB,(company made with double door

cover to be used ) M.S. Cubical Type duly flushed

with the wall surface

Incoming -63amp, DP MCB -1nos

Out going -40 amp,DP MCB -2nos 1 set

Rate in Words :

3 COMPUTER DISTRIBUTION BOARD (CDB)

19

Supply and installation of following Legrand make

metallic double door MCB Distribution Board with

MCB having breaking capacity of 10 KA (minimum)

or RCBO of 300 mA sensitivity complete with

busbar, interconnection, painting, mounted on flat

iron frame on wall/flushed with finished wall by

chase cutting, mending good to original finish

painting etc. as required. Name plate & number of

DBs are to be fixed up on front door of DBs for their

identification. RCBOs should have over load, short

circuit & Earth leakage protection.

SPN 8 way consumer unit MCB DB complete with

busbar and the following RCBO/MCBs :

INCOMING :

1 No. 240V 32 A DP MCB

OUTGOING :

8 Nos. 240V 6A/10 A SP MCB. 1 No

Rate in Words :

SUBMAIN WIRING :

Submain wiring with following size 1100 V grade,

single core, PVC insulated flexible FRLS copper

conductor cable conforming to IS : 694 through

suitable size PVC conduit (ISI mark embossed on

conduit surface) and conduit accessories partly on

surface (above false ceiling) with M.S. bar saddles,

partly through partition and partly concealed in wall /

embedded in floor by chase cutting, mending good

all damages, painting, etc. as required to be

completed in all respect.

From MIP to incoming socket DB with 2 nos.6

sq.mm + 1 nos. 4 sq.mm. (green colour for earth)

PVC insulated flexible FRLS copper cable through

suitable size M.S conduit. 20 Mtr.

Rate in Words :

20

4 From outgoing socket DB to CDB with 2 nos. 4

Sq.mm. + 1 no. 2.5 Sq.mm. (Green colour for earth)

PVC insulated flexible FRLS copper conductor cable

in suitable size M.S.conduit.

18 Mtr.

Rate in Words :

5 COMPUTER SOCKET OUTLET CLUSTER

POINT WIRING

Computer socket outlet cluster point wiring with

1100 V grade 3 nos. single core (1 for earth, green

colour) .

1.5 sq.mm. PVC insulated flexible FRLS copper

conductor cable conforming to IS : 694 through

suitable size PVC.conduit (ISI mark embossed on

conduit surface) and conduit accessories partly

through concealed in wall, embedded in floor, partly

on surface above false ceiling and partly through

partition or through flexible conduit from DB to

computer socket outlet cluster as detailed below and

upto connection of 2 nos. socket clusters in 1 (one)

circuit connecting by looping method. The work

includes supply and fixing of non - modular type

socket outlet clusters components as detailed below.

A. Recessed wiring with 2x(1x2.5sqmm) +

1x(1x1.5sqmm) copper wire. 60 Mts.

Rate in Words :

6 Each computer socket outlet cluster comprising the

following :

2 nos. 6A 2/3 pin shuttered socket ;

2 nos.6A controlling switch ;

1 no. Front cover of suitable size ;

1 no. Mounting box of suitable size .

1 no. 16/6A 6 pin shuttered socket

1 no. 16 A controlling switch with indicator 6 Set

Rate in Words :

EARTHING (COMPUTER)

21

7

Providing and fixing of chemical earth elect road

made out of 50mm dia class-B Asahalock or

equivalent 2m length with copper plate made out of

600x600x3.15 mm tinned copper plate along with

one number 40x5mm tinned copper strip grazed with

the plate buried vertically with top edge of the plate

at a depth of 1500 mm with arrangements for

termination of copper strip of earth continuity

conductor including cost of charcoal, salt reign soil,

water pouring arrangements brick missionary enclose

on top with R.C.C cover complete with labour and

material as per direction of Engineer-in- charge. 1.00 Set

Rate in Words :

8 The earth lead by 8sq.mm PVC single core cupper

wire in GI pipe to connect from earth electrodes to

UPS outgoing earth bus & as per direction of

Engineer-in-charge. 15 Mtr

Rate in Words :

E COMPUTER DATA/TELEPHONE SYSTEM

1 TELEPHONE SOCKET

Supply and fixing on wall / furniture / partition

recessed type non - modular telephone socket outlet

(RJ 11) with mounting box & front plate as shown in

the drawing complete with chase cutting, mending

good etc. as required

2 No

Rate in Words :

2 COMPUTER DATA SOCKET

Supply and fixing on wall / furniture / partition

recessed type D - Link make non - modular

Computer data socket (RJ 45) with suitable

mounting box & front plate as shown in the drawing

complete with chase cutting, mending good etc. as

required.

9 No

22

Rate in Words :

3 TELEPHONE JUNCTION BOX

Supply and fixing of 5 pair telephone junction box

“Krone” make on wall /furniture/partiion with

hinged cover and screwed type tag strips complete

with chase cutting, mending good, painting etc. as

required. 1 No

Rate in Words :

4 TELEPHONE WIRING

Supplying and laying of 1 -pair 0.5 mm dia. PVC

insulated telephone cables through pre-laid rigid

PVC conduit as shown in the drawing or otherwise

as directed by the consultant from Telephone

Junction Box to Telephone socket outlet including

interconnection mending good etc. as required to be

completed in all respect.

30 Mtr.

Rate in Words :

5 COMPUTER DATA WIRING

Supplying and laying of CAT – 6 LAN cables

through pre-laid rigid PVC conduit as shown in the

drawing or otherwise as directed by the consultant

from server to HUB, HUB to Computer Data Socket

including interconnection mending good etc. as

required to be completed in all respect.

80 Mtr.

Rate in Words :

6 Supply & Installation of 19” 9U Rack with

cable manager and other assessors of approved brand

and make as per direction of engineer in charge

including all labour 1.00 Nos.

Rate in Words :

7 Supply & Installation of 16 port switch with all

connections and commissioning.

1.00 Nos.

23

Rate in Words :

8 Supply & Installation of 24 port Patch Panel

with all connections and commissioning. 1.00 Nos.

Rate in Words :

9 PATCH CORD

(make- D- LINK/Equivalent)

For 2 mtr. Long 6 No

Rate in Words :

10 Termination & link testing of LAN cable

at both the end. 6 No

Rate in Words :

Section-2 ELCTRICAL WORK OF EGALLERY

1 SITC of 32 amps four pole Change over switch in metal enclosore make- Indo-kopp"c" category for alternate power supply from branch office UPS to EGALLERY UPS. Set 1

Rate in Words :

2 SITC of20 amps 3 pin Single phase 230 volt industrial plug & socket controlled by 25 Amps DP MCB in MS enclosure of MDS make for feeding power to AC unit. No 2

Rate in Words :

3 SITC of5/15 amps universal sockets controlled by 15 amps SP switch in PVC enclosure . Switches shall be modular type of Anchor/ Roma.3 pin Single phase 230 volt industrial plug & socket controlled by 25 Amps DP MCB in MS enclosure of MDS make for feeding power to AC unit. No 2

Rate in Words :

4 Lighing/ UPS/Power Wiring.

a Supplying & wiring two runs of 2.5 sqmm & one run of 1.5 sqmm Cobra/ Finolex/Anchor make PVC insulated flexible multistrand copper wire in 19 mm dia 2mm thick universal make PVC conduit/ casing capping as required for UPS distribution (1 socket in 1 circuit.) mtr 10

Rate in Words :

24

b Supplying & wiring two runs of 4 sqmm & one run of 1.5 sqmm Cobra/ Finolex/Anchor make PVC insulated flexible multistrand copper wire in 25 mm dia 2mm thick universal make PVC conduit/ casing capping as required from UPS DB to UPS source from main DB to AC & UPS.This items should be used for signage wiring. mtr 10

Rate in Words :

c 4x6sqmmcopper conductor PVC insulated wires & 1 R of 8 SWG bare copper wire in 40 mm PVC conduit for providing power to EGALLERY MCB DB from main Power switch board. The pipe should be laid in including termination. mtr 10

Rate in Words :

5 Point Wiring

Supplying & wiring 2 Runs of 2.5 sqmm & 1 Run of 1 sqmm Cobra/ Anchor/ Finolex PVC insulated flexible multistrand copper wire in 19 mm dia 2mm th. Universal make PVC conduit / Casing capping above false ceiling / inside ceiling as required from switch box to individual points only Anchor/ Roma switches plate & boxes shall be used.

a Single Light Point controlled by 6 amp. Switch. No 6

Rate in Words :

b 6 amp socket points (independent ) with switch. No 4

Rate in Words :

6

Installation of lighing fixtures with tubes including all accsesories for fixing complete make should be Philips/Baja/Crompton.

a

Fitting & Testing of ceiling LED Down Light 1x 10 watt lamp. No 6

Rate in Words :

7 Access Lock fixing incoordination with EGALLERY vendors. Job 1

Rate in Words :

GRAND TOTAL RS.