TELECOMMUNICATION DESIGN GUIDELINES
2 | | Guideline || 3 | Guideline |
Main Contents
1) UT Technology Telecommunication
Design Guidelines V 7. 2 5
2) UT Technology Design Guidelines for Smart Home and
Smart Home Ready System V 7.3 59
3) Product Sheets 101
a) Vantage Systems 103
b) e-home Automation 123
c) Eubiq 165
d) Leaf 229
e) Somfy 235
4 | | 5
UT Technology Telecommunications
Design Guidelines V 7.2
UT
Tech
nolo
gy Te
leco
mm
unic
atio
ns D
esig
n G
uide
lines
6 | | Guideline || 7 | Guideline |
Table of Contents
1. UTT design guidelines for fiber to the home requirements in new buildings…….….......…4
1.1. Introduction……………………………………………………………………………….......….....4
1.2. Introduction to FFTH (Fiber To The Home)………………………………………….......…...5
2. Building contractor guidelines............................................................................................7
2.1. General telecommunication requirement…………………………………………...........….7
2.2. Civil requirements applicable for all types of buildings……………………….................7
2.2.1. Entry box…………………………………………………………………….......……....7
2.2.2. Entry ducts (Lead – in ducts)……………………………………………….......……8
2.2.3. Main telecommunication room (MTR)…………………………………….......……9
2.2.4. Secondary telecommunication room (STR) / GSM room………….......………10
2.2.5. Floor telecommunication room (FTR)…………………………………….......……12
2.2.6. Roof top telecommunication room (RTR)…………………………….......……….13
2.2.7. Point of presence room (POP)……………………………………….......…………..14
2.2.8. Pest Control……………………………………………………………….......………..17
2.2.9.Risersfrommaintelecommunicationroomthroughfloor telecommunication rooms…………………………………………….......…………18
2.2.10. Floor distribution box (Pull box)…………………………………….......………..18
2.2.11.Distributioninsidetheflats(fromONUenclosure)…………….......………...19
2.2.12.Distributioninvillas(fromONUenclosure)………………………….......…….20
3. Installation of in building fiber cables...............................................................................20
3.1. High raise buildings……………………....…………………………………………….......…….20
3.2.Office/retailareaswithshellandcore…….......…………………………….......…………23
3.3. Single villas……………………....……………………………………………….......…………….23
4. UTT telecommunication requirement................................................................................24
5. Civil works required by the contractor…….………………………………………........................29
5.1. Back boxes for all telecommunication outlets……….......……………….......……………29
5.2.Horizontalpathways………………………………………....………………….......……………29
5.3. Containment for GSM cables…………………………....………………………….......………30
2
8 | | Guideline || 9 | Guideline |
6. Structured cabling system (SCS)…………………………………………..…………….30
6.1. Cabling and termination…………………………………………………………………30
6.2. Telecommunication socket………………………………………………………………31
6.3. Television cabling, termination and sockets………………………………………..32
6.4. Modular RG 6 jacks……………………………………………………………………...32
6.5. Modular jacks category 6A shielded RJ45………………………………………….32
6.6. Horizontal subsystem (F/FTP cable)……………………….………………............33
6.7. Horizontal cabling…………………………………………….…………………………..33
6.8. Cable capacities in cable trays/conduits…………….………………………………34
6.9. Patching…………………………………………………….……………………………….34
6.10. Labeling………………………………………………….…………………………………34
6.11.Underfloorsystem…………………………………….………………………………..35
6.11.1.Mainelementsofunderfloorracewaysystem…............……………….......35
6.12. Cable trays………………………………………………………….…………………….36
6.13.Indoorcabinetsspecification…………………………………………………………36
7. Protection from electromagnetic interference……………….………………….38
7.1.Separationdistancefrompowersource………................……….…......………38
8. Private branch exchange (PBX)………………………………………………….……39
9. Important notes……………………………........................…………………………41
10. Required documentation for handover (project completion)
NOC/BCC issuance…………………......………….....……………………………...42
11. Examples of related documents and tables………...………………………….43
3
10 | | Guideline || 11 | Guideline |
1.1. INTRODUCTION:
Telecommunications is now an integral part of the social, economic and political issue of the world. Networks
of the future will be digital and intelligent and will offer high transmission capacity and bandwidth
in addition, they will be easily accessed and connected while its services will be personal and tailored to
individual needs. They will allow us to interact in ways previously not possible - available at any time and
any place. In addition to providing entertainment and business services, networks of the future will provide
education, health and other public services.
Major advances in communications technology have substantially widened the range of services carried
by the network. Satellites, microwave radio, optical cable links, digital switching and transmission, offer a
potential for the improvement of quality and for the extension of access to the most remote areas. The pace
of technological change is increasing while the magnitude of demands the future will make on our creativity
and capacity to adapt is great. Customers will demand more than just state-of-the-art technology; they will
want convenience and increased control over their lives that easy and affordable information access can
provide while businesses will look for total telecommunications solutions that will not only enable them to
remain productive and compete globally but will also give them a competitive edge.
Ubiquitous Telecommunication Technology (UTT) can be well-placed to meet these challenges ahead and
meet the varied needs of our local and international customers and pave the way for the region's new
dynamism in the telecommunications industry well into the 21st Century.
As the technology and mode of transport are changing fast, a broad approach to suit all future type of
services will have to be born in mind, while designing the infrastructures for the buildings. A properly
designed building with clear Access path supports the triple play services (viz) telephony, data and Video
services. Also, supports future advanced services, warranting higher speeds and higher bandwidth, planned
to be available in near future, for faster provision of services.
The present booklet is to provide guidelines for consultants, contractors the details on the in-building
facilities required to be considered at the design stage.
The details provided are a general insight and the minimum requirements of UTT for the new buildings,
primarily to develop and deploy FTTH (Fiber to Home).
Utt Design Guidelines For Fiber To The Home Requirements In New Buildings
12 | | Guideline || 13 | Guideline |
1.2. INTRODUCTION TO FTTH (Fiber To The Home)
TheFTTHissimplythe100percentdeploymentofopticalfiberintheaccessnetwork.Itis
commonlydeployedintwospecificconfigurations,asbelow:
• Point-to point. (PTP) network -Fiberisdedicatedtoeachuserintheaccessnetwork.PTPnetworksarecharacterizedbytheuseofonefiberandlaserperuser.Adedicated
fiberisterminatedatthesubscriberandactivedevicesatthecentraloffice(CO)fora
telecommunications provider.
• Passive optical network (PON) -Asinglefiberisshared(viaasplitter)amongaset
numberofusers,typicallythirty-two.
PONsarecharacterizedbythe“splitting”ofthesameopticalfiberalongtheway,resultingin
thesharingoftheopticalfiberamongmultipleusers
ThefiberinaPONisdesignedtosharebetween2to128users,dependinguponthe
availability of splitters.
APONwillhavelessopticalreachthanaPTPnetwork,whichdoesnotusesplitters.Typically
aPONiscapableofreachingsubscribers20kilometers(km)fromtheOLT,whichwillcover
most of the population.
CentralOffice
Fig.1(Pointtopoint(PTP)network)
Feeder FiberDistribution Fiber
Dedicated Fiber to each home
GPONpromises2.5/1.25Gbpsasymmetricaloperation.GPONsupportsATM,Ethernetand
WDMusingasupersetmulti-protocollayer.
GPONrequiressupportingamultipleprotocolsthroughtranslationtothenativeGeneric
Encapsulation Method (GEM) transport layer that through emulation provides support for
ATM, Ethernet and WDM protocols.
TheimportantcharacteristicsofeachPONtechnologyaredefinedbytwoimportantstandards
bodies,theIEEEandtheITU.
2.0 BUILDING CONTRACTIOR GUIDELINES
2.1 GENERAL TELECOMMUNICATION REQUIREMENTS
There are several types of buildings. The infrastructure for each type of building according to the
functionofthebuildingforprovisionofTelecom&Smartservicesi.e.Commercialoffices/buildings,
ResidentialTowers,Warehouses,MediumHighriseinacampus,LaborCamps,Mosque,Petrol
Pump, hotels, private residential villas/multi tenant villas complexes and hospitals, internal
concealedpipesandotherassociatedrequirementswillvaryaccordingly.
The Architects/Consultants and Designers, Building Owners, Builders, Property Developers,
andContractorsmustliaisewithUTTatthedesignstageandobtainUTTapprovalonthefinal
designdrawings.ItisvitalthattheNOCprocessbeadheredtoinorderforUTTtobeableto
providesubscriberswithrobustandreliabletelecommunicationsserviceswithintheirrequired
timeframe.
Fig.2(Principlelayoutofpassiveopticalnetwork)
14 | | Guideline || 15 | Guideline |
2.0 BUILDING CONTRACTIOR GUIDELINES
2.1 GENERAL TELECOMMUNICATION REQUIREMENTS
There are several types of buildings. The infrastructure for each type of building according to the function
of the building for provision of Telecom&Smart services i.e.Commercial offices/buildings,Residential
Towers,Warehouses,MediumHighriseinacampus,LaborCamps,Mosque,PetrolPump,hotels,private
residential villas/multi tenant villas complexes and hospitals, internal concealed pipes and other associated
requirementswillvaryaccordingly.
TheArchitects/ConsultantsandDesigners,BuildingOwners,Builders,PropertyDevelopers,andContractors
mustliaisewithUTTatthedesignstageandobtainUTTapprovalonthefinaldesigndrawings.Itisvitalthat
theNOCprocessbeadheredtoinorderforUTTtobeabletoprovidesubscriberswithrobustandreliable
telecommunicationsserviceswithintheirrequiredtimeframe.
2.2 CIVIL REQUIREMENTS APPLICABLE FOR ALL TYPES OF BUILDINGS 2.2.1. ENTRY BOX:
EntryBox isanunderground jointboxbuilt,exclusively toallow installationofUTTundergroundcable
networktothecustomer‟spremises.
• TheEntryBoxisareinforcedconcretestructure,withaheavydutyDuctileIronFrameandCoverofrating
Grade„A‟.Thecovershallhavemarkingas“Telephones”.
• Thelocationoftheentryboxdependsonthelocationofexisting/ProposedUTTExternalLinePlant.
• The Entry box shall be constructed at a maximum distance of 1 meter from plot line. Within the plot
(customerpremise)ifitisnotpractical,thenoutsidetheplot,touchingwiththeboundarywall.
• Duetothevariablesinvolved,itisessentialtoconsultUTTatthedesignstage,todecidethelocationof the
Entry Box and Entry Pipe. The Consultants/Contractors shall not deviate from the stipulated location
• An earth rod must be provided at the Entry Box. The required earth resistance should not exceed 5 Ohms.
• ForEntryBoxsizedetailspleaserefertoTableNo.1
UTTECHNOLOGYDESIGNGUIDELINESV77
• Entrypipesshouldbelaidatadepthof60cmfromtheproposedfinishedpavinglevel.TheEntry pipe shallbeprotectedwithconcrete,topreventdamages.
• EntrypipeshouldbeextendedtotheentryboxandbeyondtothenearestexistingUTTplantlocation.
• TheEntrypipeshouldbeofuPVCmaterialandofblackcolor.
• The open ends of the entry pipe shall be properly sealed, to prevent entry of sub soil materials and ingressofwater.
• Location of Entry pipes, shall be clearly marked, above ground for easy location
• Building contractors shall be responsible to locate the installed entry pipes on site, if requested by UTT.
• Noright-angledsharp bends shall be installed through out the duct length, except one wide-angle,long radius bend (factory mavided.
• Cable trays may be provided in the basement from location of lead in ducts entering the basement to main telecom room of the building for both main & redundancy route. End of the ducts should be properly sealedtopreventingressofwater.
• Cabletraysshouldbe600mmx50mmwithheavydutyreturnflange(HDRF)type.Minimumclearance of 2.4mshouldbemaintainedfromthefloorlevel.Cabletraysshouldbeprovidedthrough common areas & should not pass through any utility room, pump room, stores and etc…
• Entrypipesshallbeassigned,exclusivelyforUTTTelecommunication&SmartServices.
• Entrypipesshallbeprovidedwithadrawropemadeofnylonofminimum6mmdiameter
• For the number and size of entry pipes, for the various types of buildings, please refer to Table 1.
2.2.2. ENTRY PIPES: (Lead-in ducts)TheentrypipesareuPVCducts.TheseductsaretobeextendedfromtheentryboxtowardsUTTlineplantlocation.Twoleadinductstobeprovidedinseparaterouteformainandredundancy cables.
8UTTECHNOLOGYDESIGNGUIDELINESV7
16 | | Guideline || 17 | Guideline |
2.2.3. MAIN TELECOMMUNICATION ROOM (MTR):Main Telecom room shall be a dedicated room. This is to be provided either on the ground floor
or basementorinthefirstfloororMezzaninefloorofthebuildingforthepurposeofterminating Telecommunication Cables and to house the present & future Telecom/Smart equipments. TheroomshallbeexclusivelyforUTTuse.
• TheroommustbeeasilyaccessibletoUTTPersonnel24Hr/Day,(alldaysincluding
weekends). The room must be clean, dry, and free from dust and secured from unauthorized entry.
• Adequate lighting should be provided.
• Theroommusthaveananti-static“raisedfloor”ofminimum30cm.
• Theroommustbeprovidedwithagoodearthofnotmorethan5Ohms.
• Thedooropeningfortheroomshallswingoutwardshavingthesizeof900mmx2200mmlabeledasUTTMainTelecommunicationRoom
• Thefloor,roofandsurroundingwalloftheTelecomroom,shallbefreeofanyconcealed
water/drainagepipes,highpressurewaterpipes,FCU,BUSbarsandair-conditioningducts
passing through.
• Theroommustbeprovidedwithanemergencylight,asmokedetectorandafirealarm.
• TheroommustbeequippedwithFM200firefighting
• If the Telecom room is proposed in the basement, an automatic sump draining system shall
beprovidedtohandlewaterseepages.
• TheDuctentrytobuildingshallbesealedairandwatertight
• Forthemaintelecomroomsize,pleasereferTableNo.1
• LayoutoftheroomshallbesubmittedtoUTTshowingtheoverhead(laddertypecable
trays)andunderraisedfloorcabletrays.Theinstallationofthecabletraysshallbethe
responsibilityofthecontractoruponobtainingUTT‟sapprovalfortheroomlayout.
UTTECHNOLOGYDESIGNGUIDELINESV79
MEP Requirements:
• 1.2Unitsof6-wayACPowerDistributionBoardhaving160AmpsMCCBIncomerasMainsincomer,
Surfacemounting,TP+N&E,rated415voltsACsupplyfedfromessentialbuildingpower.
• EachDBhaving:
• A) 160 amps, TP incomer MCCB – (Adjustable from 125 to 160A)
• (TP+N+E)–1No.
• Note:ProposedIncomercableshouldbeminimum70sq.mmXLPE4corewithSeparateEarth.
• B)TPoutgoingMCCBrating63Amps–4Nos.(Adjustablefrom63to100A)
• C)SPoutgoingMCCBrating10,20,30Amps–2Nos.each
• (MAKE:SquareD,MerlinGerinorEquivalent)
• (Plug in type MCCB preferred e.g. I Line Square D)
• 2.ElectricPowersocketsfedfromnormalBuildingsupplyonspurswithdedicatedcircuitbreakersrated at 20A.
• TwinelectricACsockets13A–4Nos.
• 3. Grounding earth bar
• DedicatedACcleanearth&DCcleanEarthbar–2Nos.each
• 4.Air-conditioning
• DedicatedAir-conditioningsystemrequiredtomaintainroomtemperatureat21°C±1°Casperthe
room layout/space.
2.2.4. SECONDARY TELECOMMUNICATION ROOMS (STR) / GSM ROOMS:
• Buildings with more than 20 stories must have a Secondary Telecom Room at each 10th floor.This requirement is essential to overcome the distance limitations for the purpose of terminating Telecommunication Cables and to house the Telecom/Smart equipments.
• TheSecondaryTelecommunicationRoomateach10thfloormustbeeasilyaccessibletoUTTPersonnel
24hr/day,(alldaysincludingweekends).Theroommustbeclean,dry,andfreefromdustand secured
from unauthorized entry.
• Adequate should be provided.
• Theroommusthaveananti-static“raisedfloor”ofminimum30cm.
• Theroommustbeprovidedwithagoodearthofnotmorethan5Ohms.
10UTTECHNOLOGYDESIGNGUIDELINESV7
18 | | Guideline || 19 | Guideline |
• Thedooropening for theroomshallswingoutwardshavingthesizeof900mmx2200mm
labeledasUTTSecondaryTelecommunicationRoom
• Thefloor,roofandsurroundingwalloftheTelecomroom,shallbefreeofanyconcealedwater/
drainagepipes,highpressurewaterpipes,FCU,BUSbarsandair-conditioningductspassing
through.
• Theroommustbeprovidedwithanemergencylight,asmokedetectorandafirealarm.
• TheroommustbeequippedwithFM200firefighting
• The size of the room is 3 (L) x 4 (W) x 3 (H) Meters.
• Theroomshouldbeclosetothefloortelecomroomwith2noof(300mmx50mm)ofcable
traystobeprovidedfortheinterconnectionwiththeFloorTelecommunicationRoomandthe
Main Telecommunication Room
MEP Requirements:
• 1.2Unitsof4wayACpowerDistributionBoardhaving63AmpsRCD IncomerasMains
incomer,Surfacemounting,TP+N&E,rated415voltsACsupplyfedfromessentialbuildingpower
• EachDBhaving:
• A)63amps,TPincomerRCD300mA–1No
• B)TPoutgoingMCBrating32Amps–2No
• C)SPOutgoingMCBrating10,20,30Amps–2Noeach
• (MAKE:SquareD,MerlinGerinorEquivalent)
• 2.ElectricPowersockets fed fromnormalBuildingsupplyonspurswithdedicatedcircuitbreakers rated at 20A.
• TwinelectricACsockets13A–4No
• 3. Grounding earth bar
• DedicatedACcleanearth&DCcleanEarthbar–2Noeach
• 4.Air-conditioning
• DedicatedAir-conditioningsystemrequiredtomaintainroomtemperatureat21°C±1°C
UTTECHNOLOGYDESIGNGUIDELINESV711
2.2.5. FLOOR TELECOMMUNICATION ROOM (FTR):
Floor Telecommunication Roomisadedicatedroomandrequiredoneachfloorforthepurposeofaccommodating
internal conduit from every flat termination, routing or terminating Telecommunication Cables and to
accommodate the Telecom equipments, if required. Floor telecommunication room shall be located close to
therisers.ThisroomshouldbeexclusivelyfortheuseofUTT.
• Allfloortelecommunicationroomsshallbeverticallyaligned
• Iffloortelecommunication room cannot be provided directly above the Main telecommunication room,
thenthedistancebetweenthefloortelecommunicationroomandthemaintelecommunicationroom
shall not exceed 10m
• Adequatelightingandminimumoftwo13Amp240voltACMainsoutletshouldbeprovided.
• 1 set of 2x40 W Fluorescent lamps are to be provided.
• The room must readily be accessibletoUTTPersonnelandequipment24hr/day,allthedays,round
the clock and the room, clean dry, and free from dust and secured from unauthorized entry.
• Theroommustbeair-conditioned
• Thefloor,roofandsurroundingwalloftheTelecomroom,shallbefreeofanyconcealedwater/drainage
pipes,highpressurewaterpipes,FCU,BUSbarsandair-conditioningductspassingthrough.
• ThefloorTelecomroomshouldbeprovidedwithgoodearthofnotmorethan5Ohms.
• Thefloortelecomroom,shallnotbelinkedtoorserveanyotherfloorofthebuildingandanyotherELV
cables are prohibited to be in the FTR.
• Ahandheldfirefightingextinguishermustbeavailable24hr/dayintheroom
• A Single conduit of at least 50mm (2 inch)internaldia.,blackandofuPVCmaterialshouldbeprovided
fromeachfloortelecomroomtotheIndoorequipmentcabinetofeachoffice,residence,flatandother
independentareasinthesamefloor.
• The door opening for the roomshallswingoutwardshavingthesizeof900mmx2200mmlabeledas
UTTFloorTelecommunicationRoom
• UTTshouldbeconsultedtoenhancetherequirements,ifthebuildingisdesignedforcommercialuse.
• Forthefloortelecomroomsize,pleasereferTableNo.1
12UTTECHNOLOGYDESIGNGUIDELINESV7
20 | | Guideline || 21 | Guideline |
2.2.6. ROOF TOP TELECOMMUNICATION ROOM (RTR):
Roof Top Telecommunication room is a dedicated room to be provided on the roof top of the proposed
Multi-storiesbuildings,exclusively forUTTuseandsecuredfromunauthorizedentry.Theminimum
Roof Top Telecommunication room size shall be 3(L) x 3(W) x 3(H) Meter.
• The floor loading of this area must be maximum possible, to support future installation of
Telecommunications equipment.
• Anopeningofsize60x40cmtobeprovidedonthewalloftheroom,facingtheTerrace,50cmbelow
the room ceiling.
• ThelocationoftheRoom,shallbewithintheverticalstructureofthebuilding,withdueconsiderations
forloadsafetyprovisionsandtoextendrelatedfacilitiesrequiredsuchasAir-conditioning,3-phase
power(DistributionBoard)D.B,earthlinglessthan5Ohms,adequatelighting,one13Amp240VAC
powersocketandonetelephonesocket.
• Theroommusthaveananti-static“raisedfloor”ofminimum30cm
• Thefloor, roofandsurroundingwall of theTelecomroom,shallbe freeofanyconcealedwater/
drainage pipes, high pressure water pipes, FCU, BUS bars and air-conditioning ducts passing
through.
• TheroommustbeequippedwithFM200firefighting
• Theroommustbeprovidedwithanemergencylight,asmokedetectorandafirealarm.
• TheroommustreadilybeaccessibletoUTTpersonnelandequipment24hr/day,allthedays, round
the clock and the room must be clean, dry and free from dust.
MEP Requirements:
1.2Units of 4wayACpowerDistributionBoardhaving63AmpsRCD IncomerasMains incomer,
Surfacemounting,TP+N&E,rated415voltsACsupplyfedfromessentialbuildingpower
EachDBhaving:
D)63amps,TPincomerRCD300mA–1No
E)TPoutgoingMCBrating32Amps–2No
F)SPOutgoingMCBrating10,20,30Amps–2Noeach
(MAKE:SquareD,MerlinGerinorEquivalent)
UTTECHNOLOGYDESIGNGUIDELINESV713
• 2.ElectricPowersocketsfedfromnormalBuildingsupplyonspurswithdedicatedcircuitbreakers rated at 20A.
• TwinelectricACsockets13A–4No
• 3. Grounding earth bar
• DedicatedACcleanearth&DCcleanEarthbar–2Noeach
• 4.Air-conditioning
• DedicatedAir-conditioningsystemrequiredtomaintainroomtemperatureat21°C±1°C
2.2.7. POINT OF PRESENCE ROOM (POP room):• POP room is to be provided in addition to MTR and shall be required in all the buildings having
more than40floorsintotallocatedpreferablyintheGroundFloorareaor1stbasement.
• POProomshallbeadedicatedroomexclusiveuseofUTT.AllMEPrequirementsmentionedbelow
should be provided. For POP room size refer to table 2.
A) Air Conditioning System :
• BasiccoolingdemandforthePOProomshallnotbelessthan1500watts/sqm,howeverthiswillbe revisited based on the proposed Telecom equipment heat dissipation. The temperature to be
maintainedbetween20°C±1°Candrelativehumidityshallbe50–55%.
• CloseControlAirHandlingunits(couldbechilledwatersystembased(or)DXsplittype),preferably downairdischargetype.
• N+1operationalphilosophyoftheA/Cequipmenttobeconfigured.
• DualsourceofpowersupplytofeedtheA/Cunitsensuringredundancyincaseofmainspower.
• DCorUPSequipmentmustbesegregatedfromTelecomequipmentastheabovecoolingdemandlimited to telecom equipment only.
• AdditionalcoolingforDCandUPSroomtobeprovidedifseparateDCandUPSroomsareconsidered
andtomaintainatemperaturebetween20°C±2°Candrelativehumidityshallbe50–55%with
N+1configuration.
B) Power Requirement :
1. Dedicatedspace/roomshallbeallocatedtoinstallDCplant/UPSequipment.Sizeofroom
shall be decided based on equipment requirement.
2. Floor loading of the above room/space shall not be less than 3000 kg/sq.m.
3. Main AC Input Dist. Board shall be providedwith2x200AmpMCCBasincomersin
case of 1200 Ampere DC plant and 2x400 Amp. MCCB as incomers in case of 2400
Ampere DC plant, as applicable based on Telecom equipment load demand.
14UTTECHNOLOGYDESIGNGUIDELINESV7
22 | | Guideline || 23 | Guideline |
4. Dual sourceofpowersupplytofeedtheaboveDCplantACInputDB,asonefeederfrom
themainspowersectionandotherfeederfromstandbygeneratorboardsectionofthe
MainLVSwitchBoard.
5. DC plant room temperaturetobemaintainedinbetween20to22°Candrelative
humidityshallbe50to55%andthecoolingdemandbasedontheDCplant(Batteries
&Rectifiers)is750watts/m2.IfUPSequipmentistobeinstalledinthesameroomthen
the cooling requirement is 1000watts/m2.
6. 2Nos.earth terminal conductors shall be provided and connected to separate earth
pitswithlessthan1Ωresistance.ThisarrangementisapplicableforbothPOP
room&DCplantroom.Thecopperearthbardimensions:500mmx50mmx
10mm, mounted on standardinsulatorassemblywith10Nos.10mmpre-drilledholes.
7. 5Nos.13Amps.Twinswitchsocketoutlets(withneonindicators)tobeprovidedinthe
DC plant room and POP room combined.
8. One Telephone outlet to be provided in POP room.
9. RequiredcableopeningsshallbeprovidedbetweenDCplantroom&POProomas
mentionedbelowwithfiresealant:
OptionA:450x250mmwall/ceilingopening(OR)
OptionB:6Nos.200mmUPVCductsbetweentherooms.
AllotheropeningsinandoutofthePOP/DCroomsshallbesealedwithapproved
material by civil defense.
10. SuitablehotdippedgalvanizedironcableladdersshallbeprovidedforPowerandfiber
cableentryopening/pointatceilingleveltofloorbottomvertically.Properfloorsealant
“Cableboots/cableseals”shallbeprovidedtopreventairleaktospace.
11. NecessaryG.IheavydutycabletraysshallbeprovidedinPOProombelowtheRaised
floorforDCpowerdistributionanditshallmatchwiththetelecomequipment/
racks layout.
12. The size of the cable tray is 450mm x 50mm.
13. Dedicatedcabletrays(450mmx50mm)shallbeprovidedforFiberOpticcablesbelow
Raisedfloorincoordinationwithtelecomequipment/rackslayout.
DESIGNGUIDELINESV715
C) Mains Power /Distributions :
MainLVSwitchboardofthebuilding/tower/projectwhichisfeedingUTTPOProom&DCplant
roomshouldhavetwosectionswithcommonBusbarandinterlockingfacilityandSection-1
shallbefedfromServiceAuthority(M/s.ADDC,DEWA,SEWA&FEWA,etc.)powersourceand
Section-2byStandbygeneratorrespectively.Incaseofmainspowerfailurestandbygenerator
willbeabletostartautomaticallyandprovidebackuppowertotheconnected“Electricaland
HVAC”loadsoftherelatedtoPOP&DCplantrooms.
D) Fire Detection & Fire Protection System :
POP room&DCplant room should be protected by “Double knock” FireDetection System
interfacedwithAutoFireProtection/SuppressionSystems.
The above fire services control panel shall be interfaced with the Mechanical equipment
controllers/control panels (AirConditioning equipment,Motorized Fire dampers, Ventilation
Fans,etc.)andaswellaswithBuildingManagementSystem/existingfirealarmcontrolpanel,
as applicable.
E) Raised Flooring System :
a) POP room shall be providedwith non combustiblemodular type CaSO4 /CaSi3 Raised
access flooringsystemwithantistatic2mmthickPVCtopcoveringrangesbetween500mmand
1000mmhighdependingonthesizeofPOPwithadequateperforatetilestoallowthecoldair
distribution.Theperforatedtilesshallbearrangedinparalleltothecoldairflowtoachievethe
ColdAisle/HotAisleconfiguration.
b)DCplantroomshallbeprovidedwithantistaticfireretardantPVCflooring.
F) Water Leak Detection System :
POProomshallbeprovidedwithIntelligentWaterLeakDetectionsystemandassociatedcontrol
panel.ThesystemshallbeprovidedbelowRaisedfloor.Alsothewaterleakdetectionsystem
shallbeinterconnectedtoBuildingManagementSystemorremotesounderatwatchmanarea
as applicable for monitoring/ alarming.
16UTTECHNOLOGYDESIGNGUIDELINESV7
24 | | Guideline || 25 | Guideline |
It shall be ensured by all concerned that the POP room & DC plant room shall be properly protected
againstanywaterleakage/seepagepriortoequipmentinstallation.
G) Doors & Floors Loading :
POP room&DCplant roomsentrancedoors shallhavea clear openingof2200mm (width) x
2700mm(height)havingthelabelsasUTTPOPRoom
Floor loading for the POP room shall be 1000 kg/m2 & DC plant room shall be 3000 kg/m2.
H) Door Access Control System:
AccessdoorsforthePOProom&DCplantroomsshallbeprovidedwithSecuritySystems(Access
ControlandCCTV)attheEntrydoors,gates,etc.torestricttheentrytoauthorizedpersonnelonly
andadequateCCTVcamerasshallbeprovidedtomonitortheactivitiesinandaroundtherooms.
TheAccessControl&CCTVsystemsshallbeconnectedtoEtisalatEnterprisesolutionSystem
Platform and shall be dually monitored by central Monitoring Station(s) and local Region Monitoring
Stationand/orBMSinthesamebuilding-ifany-]
AdequateinternalandexternallightingshallbeprovidedtoallowforCCTVsystemtohaveclear
vision of the inside and outside area surrounding the POP Room.
I) Lighting :
Adequate lighting (Minimum 300Lux) shall be provided inside POP & DC plant rooms. Also
sufficient Emergency version fittings (providedwith self contained battery pack suitable for 3
hours duration) shall be provided. Maintained 3 hours Exit lights shall also be provided at the exit
doors of the POP & DC plant rooms.
2.2.8. PEST CONTROLAll Telecommunication rooms and pathwaysmust be pest controlled using the best available
practices to prevent rodents damaging the cables & equipment. Special care should be taken to
preventrodentsfromenteringthetelecommunicationrooms&pathways.Allcableentriesshould
beproperlysealedbefore&afterlayingcables.Cabletraysmaybeprovidedwithremovablecovers
& sealing the ends.
UTTECHNOLOGYDESIGNGUIDELINESV717
2.2.9. RISERS FROM MAIN TELECOM ROOM THROUGH FLOOR TELEPHONE ROOMS
The risers are required in all kinds of buildings for the installation of Telecom Fiber Optic cables from MainTelecomRoomtootherfloors,asdetailedbelow:
• Galvanizedslottedironcabletraysasspecifiedintable-1ofHDRF(heavyduty,returnflange)
shallbeprovidedfromthemaintelephoneroom,toeachfloortelephoneroomandextendedup
to the Roof telephone room.
• TheriserstoeachfloorshallbesymmetricalandverticallyinlinefromtheMainTelecomRoom.
However,wheretheMainTelecomRoom,Floortelephonecloset/Roomandrooftelecomrooms
arenot located onebelow the other in vertical line, a continuous cable trays/conduits to be
providedwithpullboxes/accesspanelsateveryturningpointandatintervalof15meterseach,
up to the Main Telecom Room. Right angle or sharp bends are to be avoided.
• Ifabuildingconsistsofmorethanonetower,alltheabovespecifiedrequirementsarerequired
ineachtower.Thetowersmustbeinter-connectedattheMainTelecomRoom,byseparatecable
traysofminimum1x(600mmx50mm)orthroughfloorracewayspassingthroughacommon
areabetweenthetwobuildings.Thesizeofthefloorracewaystobedecidedatthedesignstage
byUTT.ThesamerequirementsalsoapplytoMezzanineandPenthousefloors.Thetelecomcable
trays should have adequate separation from electrical cable trays. Electrical cable trays should
not cross the Telecom cable trays.
2.2.10. FLOOR DISTRIBUTION BOX (PULL BOX):
PullBoxesaremetallicboxes,concealed,locatedonthewall,wheretheinternalconduitfromevery
Flat is terminated. These empty boxes shall be located close to the risers and the cabinet and can be
morethanone,dependinguponthenumberoffloorsandconduitsproposedtobeterminated.These
distribution boxes facilitate, to route the Fiber Optic cables to the premises direct and the number of
cablescorrespondstothenumberofflats/premises
• The DistributionBoxesshallbeofsizenotlessthan30(L)X30(H)X15(D)cmflushmountedon
wallandshallbefixedinsidetheFloorTelecomroomofeachfloor.Asuitablehingedcovershall
be provided.
• Itshouldbeinstalledataheightof120cmsabovethefinishedfloorlevel.
• The conduitsleadingfromthefloordistributionBoxtowardseachflatshallnotbelessthan50
mm diameter.
• Adequatesafeworkingspaceistobeprovidedaroundeachlocation.
18UTTECHNOLOGYDESIGNGUIDELINESV7
26 | | Guideline || 27 | Guideline |
The Distribution Boxes location should never be near any Electrical Junction Box or bus bars. Adequate safe
workingspaceshouldbeprovidedinfrontofeachBox.
ASingleconduitofatleast50mminternaldia,blackandofuPVCmaterialshouldbeprovidedfromeach
floorDistributionBoxtotheIndoorequipmentcabinetofeachflat/officeandotherindependentareasin
thesamefloor.
Wall-MountableConnectorHousingsprovideinterconnectorcross-connectcapabilitiesbetweentheoutside
plant, riser, distribution cables and the optical cables to the premises.
UTTshouldbeconsultedtoenhancetherequirements,ifthebuildingisdesignedforcommercialuse.
2.2.11. DISTRIBUTION INSIDE THE FLATS: (From ONU enclosure)
AnONUenclosureshallbeofminimumsize24Uandwidth600mmanddepth150mm(fromtheapproved
vendorsofUTT)tohousetheOpticalnetworkunit(ONU),powersocketsandpatchpanel.Thecabinetshall
beflushmountedonwallinaneasilyaccessiblelocationfortechnicians.
Thecabinetshallbededicatedpereachoffice/residentialflatandtobesitedinasecuredplace.
The location of the cabinet shall be at a common point, where all the internal conduitsmeet and the
structuredcablingsystem(SCS)onastartopologycanbeinstalled.However,thefarthestsocketshallnot
exceed 90 M from the Cabinet.
Two13Amppowersocketsarerequired,insideONUenclosure,forpoweringtheOpticalNetworkUnitand
Installed active equipment.
TheONUenclosurelocationshouldnotbeadjacenttoanyelectricaldistributionorbusbarsbutitshould
have an access to it through a duct pipe.
TheONUenclosureshouldbeinstalledataheightof100cmabovethefinishedfloorlevel.
All Internal conduits shall be of diameter not less 2 of 25mm (1 inch) to extend the structured cables from
ONUtoSCSeachdualSocketlocations.
Forduplexflats,ONUenclosurewillbeprovidedat lower level&a junctionboxat theupper levels.All
conduitsoftheupperlevelstobeconnectedwithONUenclosurethroughaminimumof2numbersofPVC
conduits, each of 50mm diameters.
UTTECHNOLOGYDESIGNGUIDELINESV719
2.2.12. DISTRIBUTION IN VILLAS: (From ONU enclosure)
• AnONUenclosureshallbeofminimumsize24Uandwidth600mmanddepth150mm(from
theapprovedvendorsofUTT)tohousetheOpticalnetworkunit(ONU),powersocketsandpatch
panel.Thecabinetshallbeflushmountedonwallinaneasilyaccessiblelocationfortechnicians.
• AsecuredPullBoxofsize30(L)x30(H)x15(W)cmflushmountedonwallisrequiredinevery
floorofthevilla,fordistributingSCS,fromtheONUenclosure.
• The pull box should be kept at a convenient and easily accessible location where the floor
distributionconduitsareterminated.Itshouldbeinstalledataheightbetween40cmand120
cmabovethefinishedfloorlevel.
• Thepullboxesondifferentfloorsofavillashouldbeconnectedthroughaminimum2numbers
ofPVCconduits,each50mmdiameter.
• Thepullboxshouldhaveone50mm(2-inch)conduittotheRooftopofthevilla,fromthecabinet
or from the telephone entry duct location, in order to provide access to cables from the antenna.
• Adequatelightingandminimumoffour20Ampand240VoltA.C.Mainsoutletfromadedicated
circuit breaker should be provided.
• 3.0INSTALLATIONOFINBUILDINGFIBRECABLES
• 3.1HIGHRAISEBUILDINGS:
• Thebuildingowner/Developershallinstallaminimumof2coreSingleMode(SM)Fibercable
G657-B– ITU-Tstandardasspecified inthestructurecablingguideline, fromIndoorCabinet
locationofeachflat/premisestotheFloortelecomroomoneachfloorAndfromFloortelecom
roomon eachfloor toMain telecom in groundfloormulticore indoor singlemodefiber cable
shouldbeprovided.Sizeof thecable frommain telecomroomtofloor telecomroomoneach
floorshouldbeequaltodoublethenumberofflats/premisesonthefloorplus2fibersforsmart
solutionsplus25%extraformaintenance&unforeseendemand.
• Foropenspaceofficesminimumof2Fibersshallbeconsideredper50squaremetersplus2
fibersforsmartsolutionsplus25%extraformaintenance&unforeseendemand.
• 1ONUshallbeinstalledforevery50sqm
• For open space retails minimum of 2 Fibers shall be considered per 100 square meters plus 2
fibersforsmartsolutionsplus25%extraformaintenance&unforeseendemand.
• 1ONUshallbeinstalledforevery100sqm
20UTTECHNOLOGYDESIGNGUIDELINESV7
28 | | Guideline || 29 | Guideline |
AllthefibercablesintheMainTelecommunicationrooms,FloorTelecommunicationroomsandSecondary
telecommunicationroomsshallbeterminatedon19”fiberpatchpanels.
Thesinglemodefibershallhavemaximumattenuationof0.5dB/[email protected]/km@1550nmin
linewithANSI/TIA/EIA-568B1FOattenuationlimits.
Table1(SizeofFiberOpticcablesfromMTRtoeachFTRandSTRaccordingtothenumberofflats)
Number of apartments/ONU on the
floor
2
3
4
5
6
7
8
9
10
11
12
13
14
16
4
6
8
10
12
14
16
18
20
22
24
26
28
32
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
4
4
5
5
6
6
7
7
8
9
8
10
13
15
18
20
23
25
28
30
33
35
38
43
8F
12F
16F
16F
24F
24F
24F
36F
36F
36F
36F
36F
48F
48F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
No. of fibers required in each FTR
Fibers for others
Additional 25%
Total Fibers required
Size of the FO for each FTR
Size of the FO Cable for
each STR
UTTECHNOLOGYDESIGNGUIDELINESV721
TerminationofthesefibersshallbedonebytheInstallerinthewallmountedcabinetsandintheODF
cabinets. The Installer must keep an extra length of 5 M of cable either end for terminations. The cables
shallbesuitablylabeled.ThesuppliermustgettheapprovalfromUTTbeforestartingtheworkandtest
resultsofinstalledcablesshallbesubmittedforfinalapproval.
Additional 8 Fibers cables to be provided from ODF in main telecom room to each Secondary telecom room
and the roof telecom room for GSM. Fiber termination box to be provided in these rooms and cables should
beterminatedatbothendswithpigtails.
Thebuildingowner/developershallprovide42UCabinetswithstandard19”rackandpre-connectedpatch
panelswithSC/APCpigtailsinmaintelecomroomforterminationofmainincomingcablestothebuilding
andterminationofbuildingdistributioncables.TerminationofincomingcablefromPOPshallbebyUTT.
The number of terminations shall be considered the same as the number of cables terminated for the
buildingdistribution.Terminationofallotherfibercablesshallbebyowner/installer
SeparatecabinetsshouldbeprovidedforUTTincomingfibercablesandbuildingriserfibercables.
3.2 OFFICE/RETAIL AREAS WITH SHELL & CORE
Iftheoffice/Retailareaisashellandcore,anundertakingletterfromtheownerisrequiredstatingthat
allnecessaryconduits/cabletrays/ONUenclosures/wallsockets&structuredcablingshallbeprovided
bythetenantasperUTTguidelines.Itwillbetheowner’sresponsibilitytoensurethatthetenantobtains
UTTapprovalpriortoinstallation.
3.3 SINGLE VILLAS
Inthecaseofsinglevillas,UTTshall extend and terminate the F O cable, to the termination box inside the
villaandfromtheterminationboxtotheONUbytheowner.
Inallothercases,thefibercablesshouldbeextendedtotheODFlocationintheTelecomRoom,bythe
owner.
22UTTECHNOLOGYDESIGNGUIDELINESV7
30 | | Guideline || 31 | Guideline |
Thetablesbelow,givesdetailsofthedifferentrequirementsforthevarioustypesofbuildingsandtypes.
4.0 UTT TELECOM REQUIREMENTS
Size:60x60x80cm.
Location:Within the
compound and at Max 1 M
fromcompoundwallline
2X4inches(D54)
pipes/ducttowardsthevilla&2x(2”)inches
pipes/ducts to be extended outside
the plot line towards
UTTNetwork
Notrequired
Notrequired
Notrequired
24U(H)x600mm(W)X150mm(D)flushmounted
Notrequired
24U(H)x600mm(W)X150mm(D)flushmountedonwall
Notrequired
2x4”inches(D54)fromEBtowardvilla2xD54pipes/ductsfromEBtotowardsmain telecom room and
2xD54 be extended outside theplotlinetowardsUTTNetwork.Internal
DistributionwithinplottobeinaccordancetoUTT
advise
42U(H)x800mm(W)X800mm (D) Stand alone
type19”equipme-ntCabinet
2xD54(4”)inches pipes/ductstowards
the building and 2xD54 Primary and Redundant pipes/ductstowardsthe
UTTNetwork
42U(H)x800mm(W)X800mm
(D) Stand alone type19”equipme-nt
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
24U(H)x600mm(W)X150mm(D)flushmountedonwall
4xD54 pipes/ductstowards
the building and 4xD54 Primary and redundant pipes/ductstowardsthe
UTTNetwork
42U(H)x800mm(W)X800mm
(D) Stand alone type19”equipme-nt
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
24U(H)x600mm(W)X150mm(D)flushmountedonwall
Size:JRC-12JointBox(Etisalat standard)
Location:Depends upon the
layout
Size:JRC12JointBox(Etisalat standard)
Primary and redundantLocation:
Within the property, near plot line. Additional
Boxes at all turning pointsoflead-in
Size:JRC 14 Joint Box (Etisalat standard)
Primary and RedundantLocation:
Within the property, near plot line. Additional
Boxes at all turning pointsoflead-in
Entry Box
Entry Pipes / Duct
MainTelecom room
Distribution Cabinet std 19“Rack
FloorTelecom room
Distribution Cabinet 19“Rack
Secondary / GSM / Roof Top Telecom
room Distribution Cabinet 19 “Rack
ONUEnclosure(By approved UTTVendors)
SINGLE VILLA
COMPLEX OF VILLAS
BUILDINGS UP TO (G+20)
BUILDINGS MORE THAN
(G+20 )
UTTECHNOLOGYDESIGNGUIDELINESV723
Size:JRC 14 Joint Box (Etisalat standard)
Location:Depending on the
layout
4xD54pipes/ductsTowardsthe
building and 4x D54 Primary and Redundant pipes/ductstowardsthe
UTTNetwork
42U(H)x800mm(W)X800mm(D)Stand alone type 19”equipment
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
Notrequired
24U(H)x600mm(W)X150mm(D)flush
mountedonwall
12U(H)x600mm(W)X500mm(D)Wallmountedtype19”equipment Cabinet
24U(H)x600mm(W)X150mm(D)flushmountedonwall
12U(H)x600mm(W)X500mm(D)Wallmountedtype19”equipment Cabinet
4xD54 pipes/ductstowardsthe
building and 4xD54 Primary and Redundantpipes/ductstowardsthe
UTTNetwork
42U(H)x800mm(W)X800mm (D) Stand alone type19”equipme-nt
Cabinet
2xD54 pipes/ductstowardsthebuilding and
2xD54 pipes/ducts towardstheUTT
Network
42U(H)x800mm(W)X800mm
(D) Stand alone type19”equipme-nt
Cabinet
12U(H)x600mm(W)X500mm(D)Wallmountedtype19”equipment Cabinet
Norequirement
24U(H)x600mm(W)X150mm(D)flushmountedonwall
Size:JRC 14 Joint Box (Etisalat standard)
Location:Depending on the layout
Size:JRC-12JointBox(Etisalat standard)
Position:WithinLandplotwhere
lead-inbranchingtootherblocks end at turning
points
Entry Box
Entry Pipes / Duct
MainTelecom room Distribution Cabinet std 19“Rack
FloorTelecom
room Distribution
Cabinet 19“Rack
Secondary / GSM / Roof Top
Telecom room Distribution
Cabinet19“Rack
ONUnclosure (By approved
vendorsfromUTT)
SHOPPING MALLS PALACES, HOSPITALS & HOTELS
GROUP OF SHOPS & SHEDS
24UTTECHNOLOGYDESIGNGUIDELINESV7
32 | | Guideline || 33 | Guideline |
Size:One 30 x 30 x
15cm boxRecessed inside the wallforeachfloor.
Convenient locationwith1meterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel.
Size:Per each single
villa.Size:One30x30x15cm box recessed insidethewallfor
eachfloor.Location:
Convenient locationwithonemeterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel.
Size:30 x 30 x 15cm
box recessed inside thewallforeach
floor.Location:
Convenient locationwithone1mfreewallspacearound and at a height 120 cm
abovefinishedfloorlevelwith200mm
cable tray extended to main cable tray
Size:30 x 30 x 15cm
box recessed inside thewallforeach
floor.Location:
Convenient locationwithone1mfreewallspacearound and at a height 120 cm
abovefinishedfloorlevelwith200mm
cable tray extended to main cable tray
BLDGS MORE THAN(G+40)
10x12x4 (LxWxH)In addition to a
battery room along the POP room
withsizeof6x5x4(LxWxH)
Junction Box
(Floor Pull Box size)
POP Room
Main Telecom
Room size
Floor Telecom
Room size
Norequirements
Norequirements
Norequirements Norequirements
Norequirements
Size:3x4x3 (LxWxH) meters
for villas more than 10 numbers
Norequirements
Size:3x4x3 (LxWxH) meters
Location:Inthegroundfloorcommon area. and every10floors
Size:2.3x2.3x3m(LxWxH)Location:Close to the main vertical structural corethemulti-story
Bldg.
Size:2.3x2.3x3m(LxWxH)Location:
Close to the main vertical structural coreofthemulti-
story Bldg.
SizeBLDGSUPTO(G+40)
5x4x3 (LxWxH)BLDGSMORETHAN
(G+40)9X8X3(LxWxH)
Location:Inthegroundfloorcommon area. and every10floors
SINGLE VILLA
COMPLEX OF VILLAS
BUILDINGS MORE THAN
(G+20 )
UTTECHNOLOGYDESIGNGUIDELINESV725
Table1(SizeofFiberOpticcablesfromMTRtoeachFTRandSTRaccordingtothenumberofflats)
Number of apartments/ONU on the
floor
2
3
4
5
6
7
8
9
10
11
12
13
14
16
4
6
8
10
12
14
16
18
20
22
24
26
28
32
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
4
4
5
5
6
6
7
7
8
9
8
10
13
15
18
20
23
25
28
30
33
35
38
43
8F
12F
16F
16F
24F
24F
24F
36F
36F
36F
36F
36F
48F
48F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
8F
No. of fibers required in each FTR
Fibers for others
Additional 25%
Total Fibers required
Size of the FO for each FTR
Size of the FO Cable for
each STR
26UTTECHNOLOGYDESIGNGUIDELINESV7
34 | | Guideline || 35 | Guideline |
TerminationofthesefibersshallbedonebytheInstallerinthewallmountedcabinetsandintheODF
cabinets. The Installer must keep an extra length of 5 M of cable either end for terminations. The cables
shallbesuitablylabeled.ThesuppliermustgettheapprovalfromUTTbeforestartingtheworkandtest
resultsofinstalledcablesshallbesubmittedforfinalapproval.
Additional 8 Fibers cables to be provided from ODF in main telecom room to each Secondary telecom room
and the roof telecom room for GSM. Fiber termination box to be provided in these rooms and cables should
beterminatedatbothendswithpigtails.
The building owner/developer shall provide 42U Cabinets with standard 19” rack and pre-connected
patch panelswithSC/APCpigtailsinmaintelecomroomforterminationofmainincomingcablestothe
building and termination of building distribution cables. Termination of incoming cable from POP shall be
byUTT.Thenumberofterminationsshallbeconsideredthesameasthenumberofcablesterminatedfor
thebuildingdistribution.Terminationofallotherfibercablesshallbebyowner/installer
SeparatecabinetsshouldbeprovidedforUTTincomingfibercablesandbuildingriserfibercables.
3.2 OFFICE/RETAIL AREAS WITH SHELL & CORE
Iftheoffice/Retailareaisashellandcore,anundertakingletterfromtheownerisrequiredstatingthat
all necessaryconduits/cabletrays/ONUenclosures/wallsockets&structuredcablingshallbeprovided
bythetenantasperUTTguidelines.Itwillbetheowner’sresponsibilitytoensurethatthetenantobtains
UTTapprovalpriortoinstallation.
3.3 SINGLE VILLAS
Inthecaseofsinglevillas,UTTshallextendandterminatetheFOcable,totheterminationboxinsidethe
villa andfromtheterminationboxtotheONUbytheowner.
Inallothercases,thefibercablesshouldbeextendedtotheODFlocationintheTelecomRoom,bythe
owner.
UTTECHNOLOGYDESIGNGUIDELINESV727
Thetablesbelow,givesdetailsofthedifferentrequirementsforthevarioustypesofbuildingsandtypes.
4.0 UTT TELECOM REQUIREMENTS
Size:60x60x80cm.
Location:Within the
compound and at Max 1 M from
compoundwallline
Size:JRC-12JointBox(Etisalat standard)
Location:Depends upon the
layout
Size:JRC 12 Joint Box (Etisalat standard)
Primary and redundant
Location:Within the roperty,
near plot line. Additional Boxes at all turning points
oflead-in
Size:JRC 14 Joint Box (Etisalat standard)
Primary and Redundant
Location:Within the roperty,
near plot line. Additional Boxes at all turning points
oflead-in
4xD54 pipes/ductstowards
the building and 4xD54 Primary and redundant pipes/ductstowardsthe
UTTNetwork
Entry Box
Entry Pipes / Duct
MainTelecom room Distribution Cabinet std 19“Rack
Secondary / GSM / Roof Top
Telecom room Distribution Cabinet19“
Rack
ONUEnclosure (By approvedUTT
Vendors)
2X4inches(D54)pipes/ducttowardsthevilla&2x(2”)
inches pipes/ducts to be extended outside the plot linetowardsUTT
Network
Norequirements
Norequirements
24U(H)x600mm(W)X150mm(D)flush
mounted
24U(H)x600mm(W)X150mm(D)flushmountedonwall
24U(H)x600mm(W)X150mm(D)flushmountedonwall
24U(H)x600mm(W)X150mm(D)flushmountedonwall
Norequirements
2x4”inches(D54)fromEBtowardvilla2xD54 pipes/ducts fromEBtotowardsmain telecom room
and 2xD54 be extended outside
theplotlinetowardsUTTNetwork.
Internal Distribution withinplottobeinaccordancetoUTT
advise
42U(H)x800mm(W)X800mm
(D) Stand alone type19”equipme-nt
Cabinet
2xD54(4”)inchespipes/ductstowards
the building and 2xD54 Primary and Redundant pipes/ductstowardsthe
UTTNetwork
42U(H)x800mm(W)X800mm
(D) Stand alone type19”equipme-nt
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
42U(H)x800mm(W)X800mm(D)Stand
alonetype19”equipme-ntCabinet
SINGLE VILLA
COMPLEX OF VILLAS
BUILDINGS UP TO (G+20)
BUILDINGS MORE THAN
(G+20 )
28UTTECHNOLOGYDESIGNGUIDELINESV7
36 | | Guideline || 37 | Guideline |
Size:JRC14JointBox (Etisalat standard)
Location:Depending on the layout
Size:JRC14JointBox (Etisalat standard)
Location:Depending on the layout
Size:JRC-12JointBox(Etisalat standard)
Position:WithinLandplotwherelead-inbranchingtoother blocks end at
turning points
2xD54 pipes/ductstowardstheuildingand 2xD54 pipes/ductstowardsthe
UTTNetwork
Entry Box
Entry Pipes / Duct
MainTelecom room Distribution Cabinet std 19“Rack
FloorTelecom room Distribution
Cabinet19“Rack
Secondary / GSM / Roof Top
Telecom room Distribution
Cabinet19“Rack
ONUEnclosure (By approved
vendorsfromUTT)
4xD54pipes/ductsTowardsthebuildingand
4x D54 Primary and Redundant pipes/ducts towardstheUTTNetwork
4xD54 pipes/ductstowardsthebuilding
and 4xD54 Primary and Redundant pipes/ducts towardstheUTTNetwork
42U(H)x800mm(W)X800mm (D) Stand alone type
19”equipmentCabinet
42U(H)x800mm(W)X800mm (D) Stand alone
type19”equipme-ntCabinet
42U(H)x800mm(W)X800mm (D) Stand alone
type19”equipme-ntCabinet
12U(H)x600mm(W)X500 mm (D) Wall mounted
type19”equipmentCabinet
Norequirement
12U(H)x600mm(W)X500 mm (D) Wall mounted
type19”equipmentCabinet
12U(H)x600mm(W)X500 mm (D) Wall mounted
type19”equipmentCabinet
24U(H)x600mm(W)X150mm(D)flushmountedonwall
24U(H)x600mm(W)X150mm(D)flushmountedonwall
24U(H)x600mm(W)X150mm(D)flushmountedonwall
12U(H)x600mm(W)X500mm(D)Wall mounted type 19”equipment
Cabinet
Norequirement
SHOPPING MALLSPALACES,
HOSPITALS & HOTELS
GROUP OF SHOPS & HEDS
UTTECHNOLOGYDESIGNGUIDELINESV729
Size:One30x30x15cm box Recessed insidethewallfor
eachfloor.Convenient location with1meterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel.
Size:Per each single
villa.Size:One30x30x15cm box recessed insidethewallfor
eachfloor.Location:
Convenient locationwithonemeterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel.
Size:30 x 30 x 15cm
box recessed inside thewallforeach
floor.Location:
Convenient locationwithone1mfreewallspacearound and at a height 120 cm
abovefinishedfloorlevelwith200mm
cable tray extended to main cable tray
Size:30 x 30 x 15cm
box recessed inside thewallforeach
floor.Location:
Convenient locationwithone1mfreewallspacearound and at a height 120 cm
abovefinishedfloorlevelwith200mm
cable tray extended to main cable tray
BLDGS MORE THAN(G+40)
10x12x4 (LxWxH)In addition to a
battery room along the POP room
withsizeof6x5x4(LxWxH)
Junction Box
(Floor Pull Box size)
POP Room Norequirements Norequirements Norequirements
Main Telecom Room size
Floor Telecom Room size
Norequirements
Norequirements Norequirements
Size:3x4x3 (LxWxH) meters
for villas more than 10 numbers
Size:3x4x3 (LxWxH) meters
Location:Inthegroundfloorcommon area. and every10floors
Size:2.3 x 2.3 x 3m
(LxWxH)Location:
Close to the main vertical structural corethemulti-story
Bldg.
Size:2.3 x 2.3 x 3m
(LxWxH) Location:
Close to the main vertical structural
coreofthemulti-storyBldg.
SizeBLDGSUPTO(G+40)
5x4x3 (LxWxH)BLDGSMORETHAN
(G+40)9X8X3(LxWxH)
Location:Inthegroundfloorcommon area. and every10floors
SINGLE VILLA
COMPLEX OF VILLAS
BUILDINGS UP TO (G+20)
BUILDINGS MORE THAN
(G+20 )
30UTTECHNOLOGYDESIGNGUIDELINESV7
38 | | Guideline || 39 | Guideline |
Norequirements
Size:3x4x3m (LxWxH)
Location:Close to the main
vertical structural core themulti-storyBldg.
Entry Pipes / Duct
Secondary /GSM
Telecom room Size
Riser Cable trays
Size:3x4x3m (LxWxH)
Location:Close to the main vertical structuralcorethemulti-
story Bldg.
(1x) 60x5 cm + (1x) 150x5 cm cable trays
(2x) 60x5 cm + (1x) 300x5 cm cable trays
Size:3x4x3m (LxWxH)
Location:Close to FTR
Norequirements
Norequirements
Norequirements
UTTECHNOLOGYDESIGNGUIDELINESV731
Floor Pull Box size
Size:One 30 x 30 x
15cm boxRecessed inside the wallforeachfloor.
Convenient locationwith1meterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel
Size:One 30 x 30 x
15cm boxRecessed inside the wallforeachfloor.
Convenient locationwith1meterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel
BLDGS MORE THAN(G+40)
10x12x4 (LxWxH)In addition to a
battery room along the POP room
withsizeof6x5x4(LxWxH)
Size:One 30 x 30 x
15cm boxRecessed inside the wallforeachfloor.
Convenient locationwith1meterfreewall
space around and ataheightbetween40-120cmabovefinishedfloorlevel
POP Room
Main Telecom Room size
Floor Telecom Room size
Secondary /GSM Telecom room Size
Size:4x5x3 (LxWxH) metersLocation:Inthegroundfloor
common area
Size:2.3x2.3x3(LxWxH)Location:Close to the main vertical structural
core of the shopping mall.
Size:(2.3 x 2.3 x 3
(LxWxH)Location:Incommon areas
Size:3x4x3m(LxWxH)Location:
Close to FTR if more than10floors
Size:3x4x3m(LxWxH)Location:
Close to FTR if more than10floors
(1x) 60x5 cm + (1x) 150x5 cm cable trays
Size:(2.3 x 2.3 x 3
(LxWxH)Location:Incommon areas
Size:4x5x3 LxWxH) metersLocation:Inthegroundfloor
common area.
Size:4x5x3 (LxWxH) metersLocation:Inthegroundfloor
common area.
Norequirements Norequirements
Roof TopTelecom room
Riser Cable trays
Norequirements
Norequirements
Norequirements
Norequirements
Norequirements
(2x) 60x5 cm + (1x) 300x5 cm cable trays
SHOPPING MALLS
PALACES, HOSPITALS & HOTELS
GROUP OF SHOPS & SHEDS
Table 2 (UTT Telecommunication Requirements)
32UTTECHNOLOGYDESIGNGUIDELINESV7
40 | | Guideline || 41 | Guideline |
5.0 CIVIL WORKS REQUIRED BY THE CONTRACTOR
5.1 BACK BOXES FOR ALL TELCOMUNICATION OUTLETS
AllbackboxesfortheTelecommunicationsocketsmusthaveaminof50mmdepthwiththeentranceofthecablefromthetopbacksideoftheboxasinthepicturebelow.
5.2 HORIZANTAL PATHWAYS:
• HorizontalPathways(conduits,Sleeves,Cabletraysetc)areusedfortakingthecablesfromtheONU
cabinet to the Telecommunications outlets in the apartment.
• A variety of methods are available and the choice of selection of method shall depend on the purpose of thefloorareatobeserved(i.e.generalofficespaces,apartmentdwellings,etc.)
CONDUITS:
• Allconduitswithintheflatshallbeinstalledinastartopologymethod(pointtopoint)fromONUenclosureto each individual outlet.
• Theuseofconduitsasahorizontalracewaysystemshouldonlybeconsideredwhentheoutletlocations
arepermanent,thedevicedensitiesarelowandflexibilityisnotrequired.
• The minimum size of a conduit pipe used as a horizontal pathway from the ONU cabinet to the
Telecommunications Outlet should 2 x 25mm (1 inch).
• Eachconduitinstalledshallnothavemorethat2bendsof90°
• Fortheconduits,theinsidebendingradiusshouldalwaysbeatleast10timestheinternaldiameter.
• Minimumofonenylondrawwire6mmatleastmustbeinstalledinaconduit.
• Pull boxes should be located such that they are readily accessible at all times. Pull boxes to be spaced
at a maximum of 15 M apart to minimize cable stress during installation and to provide serviceability in
the future.
• Conduits must be free from sharp edges, to prevent cable damage during and subsequent to pulling.
• Conduits protruding through a floor should be terminated aminimum of 50mm from the floor topreventwaterorotherliquidsfromflowingintotheconduits.
UTTECHNOLOGYDESIGNGUIDELINESV733
5.3 CONTAINMENT FOR GSM CABLES:
All necessarycontainments/cabletrays(width30cm)shallbeprovidedtofacilitateantennacableroutingincludingbasementandpodiums.UTTwillprovideGSMdesigndrawingsshowingthelocationofAntennas& cable routing.
6.0 STRUCTURED CABLING SYSTEM (SCS)
• To deliver state of the art services from the ONU, a SCS System on star topology is required. The
minimumrequirementisstandardCAT6AF/FTPcablewithShieldedRJ45connectivitythatsupports
10GbEincompliancewiththeTIA/EIA-568-B.2-10orISO11801:2002/Amd2:2010standards.
• In addition one RG6 socket shall be provided for the television purposes in every room for the TV
connectivity.
• TheSCSdesignshallbediscussedandapprovedbyUTTengineeringteam.
• However, the following are the general minimum requirements of structured cabling Systems, for
provision of service.
6.1 CABLING & TERMINATION:
• TheCablesusedforthesewiringmustcomplywithminimumCAT6AforBroadbandservices&for
telephone standards.
• HorizontalcablingsystemshallbebasedonCat6AFTPLSZHShieldedasperthedesigndrawingsand
UTTstructurecablingguidelines.
• Allthecomponentsinthelink(Cable,Connectorsandcableassemblies)mustbeshieldedinlinewiththis
document.
• TheSCScableplannedshallmeet thedesignedservice requirementswithin theparticularflat leveland
shouldhavebuilt-inflexibility,tomeetgrowingneedsofthetenants.
• All SCS cables shall be properly labeled and terminated, in the RJ45 sockets and in Patch panel or in CAT
6A by the system integrator appointed by the developer.
• BuildingOwnerisresponsibleforreplacementofin-buildingcablesandotherfixtures,ifthesebecomefaulty.
• Cable diagramsmust be submitted toUTT for approval at the design stage and as-built is required on
completion
• ThewholeSCScabling(endtoendFiberandCopper)shouldbepurchasedfromoneofthevendorsapproved
byUTT.Mixandmatchofdifferentbrandsofcablesisprohibited.
• CompletedSCSshallbesubjecttoacceptancebyUTT.However,thedesignandperformanceoftheSCSsystem shall be the responsibility oftheinstaller/Owner
• Any upgrading required in the in–building facility, Telecommunication cables, due to either enhanced demand, change in building statusordamageshallbeprovidedbybuildingOwner.
• The supply and termination of F/FTP cables on Patch panel and sockets locations shall be the responsibility of the system integrator appointed by the developer.
42 | | Guideline || 43 | Guideline |
• Allthecomponentsinthelink(Cable,Connectorsandcableassemblies)mustbeshieldedinlinewiththis document.
• TheSCScableplannedshallmeetthedesignedservicerequirementswithintheparticularflatlevelandshouldhavebuilt-inflexibility,tomeetgrowingneedsofthetenants.
• All SCS cables shall be properly labeled and terminated, in the RJ45 sockets and in Patch panel or in CAT 6A by the system integrator appointed by the developer.
• BuildingOwnerisresponsibleforreplacementofin-buildingcablesandotherfixtures,ifthesebecome
faulty.
• CablediagramsmustbesubmittedtoUTTforapprovalatthedesignstageandas-builtisrequiredoncompletion
• ThewholeSCScabling (endtoendFiberandCopper)shouldbepurchasedfromoneof thevendors
approvedbyUTT.Mixandmatchofdifferentbrandsofcablesisprohibited.
• CompletedSCSshallbesubjecttoacceptancebyUTT.However,thedesignandperformanceoftheSCS
systemshallbetheresponsibilityoftheinstaller/Owner
• Any upgrading required in the in–building facility, Telecommunication cables, due to either enhanced
demand,changeinbuildingstatusordamageshallbeprovidedbybuildingOwner.
• The supply and termination of F/FTP cables on Patch panel and sockets locations shall be the
responsibility of the system integrator appointed by the developer.
6.2 TELECOMMUNICATION SOCKET:
• AlloutletsshouldbeCategory6Aperformance,inadoublegangwhitefaceplate.AllRJ45outletsshouldbefittedwithshutterstopreventtheingressofdirtanddust.
• ProvisionoftwodualSocketsforTelecommunicationservicesshouldbeinstalledineveryroomandonedualforthekitchenandmaidsroom.Conduitwithnotlessthan2x25mm(1inch)shallbeconnectedbetweeneachsocketlocationsandtheONUenclosure.
• All sockets should have 2 x angled CAT 6A shielded connectors
• Everysocketmustbeconnectedwithaminimumof2xfourpairSCSCat6Acable,followingstartopologywithRJ45allkindsofbuildings,theprovisionofTelecommunicationsocketshouldalsobeextendedtothe bathrooms in case of hotels.
Telecommunicationsockets,cablesandassociatedfacilitieswithinthevariousroomsandpremisesaretobe providedbythebuildingOwner.
6.3 TELEVISION CABLING, TERMINATION & SOCKETS:
• TheCablesusedforthesewiringmustcomplywithminimumRG6coaxialcableforBroadbandservices&Television standards.
• SinglecoaxialcableshallbelaidfromtheONUenclosuretoeachSocketineachroomoftheflat.
• TheconnectorofthesocketshallbeF-connector.
• Any upgrading required in the in–building facility, Television cables, due to either enhanced demand, change
inbuildingstatusordamageshallbeprovidedbybuildingOwner.
• Themodules forcoaxial cableshallbe individualsnap-instyle female-to-femalebulkheadadapters,and
shallfitallotherinstalledtelecommunicationswallplates,Outletsandfield-configurablepatchpanelsand
patch blocks. Bulkhead modules shall be available in multiple colors to match the housings or provide
uniquecolor-codingforportI.D.ModulesshallbeULlisted.Allplasticsusedinconstructionofthemodule
bodiesshallbefire-retardantwithaULflammabilityratingof94V-0.
• Minimumcoaxialcableswithan18AWGcenterconductorand75ohmcharacteristicimpedance,thecenter
conductorisordinarilysolidcopper,theshieldingshallbemuchheavier(typicallyaluminumfoil/95%copper
braid), and tolerances are more tightly controlled, to improve impedance stability.
6.4 MODULAR RG6 JACKS
• ModularjacksshallbeF-connectormeetingtheminimumrequirementsforT.Vconnection.
• Theoutletsshallbedistributedassingleoutletsineachroomintheflatincludingthemaid’sroom.
6.5 MODULAR JACKS CATEGORY 6A SHIELDED RJ45
• ModularjacksshallbeCategory6ARJ45meetingtheminimumrequirementsofTIA/EIA568B-2.10andISO
11801:2002/Amd2:2010.ModularjacksshallbewiredtotheT568Bwiringpattern.
• Category6AmodularJacksFTPShieldedshallbethirdpartycomponentverifiedforcompliancewithANSI/
TIA/EIA568-B.2-10orISO11801:2002/Amd2:2010category6AtransmissionperformanceStandard.
• AllaccessoryplatesshouldbeDual.Theuseofanyspecialfaceplate,whichmaybespecifictoanyothermanufacturer’sproductrange,suchasbrassfinishetcshouldbereviewed.
34UTTECHNOLOGYDESIGNGUIDELINESV7
44 | | Guideline || 45 | Guideline |
• ThebackboxesdedicatedfortheCAT6Asocketsshallbe50mmdeepasperthedrawingshowninthe
civil requirement.
6.6 HORIZONTALSUBSYSTEM (FF/FTP CABLE):
• AllconductorsineachcableshouldbeconnectedtoasingleRJ45connectorattheworkareaoutlets
andpatchpanel.Eachcableshouldbeterminatedtomaintainthetwistsineachpairwithin5mmofthe
termination. Proper strain relief should be provided for the cable at the outlets and patch panel, avoiding
strain on the conductors.
Colorcodingfortheterminationshouldbeasperthefollowingtable.
6.7 HORIZANTAL CABLING:
• The physical topology of the horizontal cabling shall be configured as a star topologywith each outlet
connecteddirectlytoaflat/ApartmentDistributionBoxinsidetheFlatorApartment.Noloopingofcablesfrom outlet to outlet is permitted.
• The horizontal cabling is to be provided to single, dual, triple and quad outlets throughout.
• The lengthofcablebetween the farthestTelecommunicationsOutletand theDistributionBoxshallnotexceed 90m (295 ft.)
• AminimumoftwoTelecommunicationsOutletsshallbeprovidedforeachindividualroom/workarea.
White
White
White
White
1
2
3
4
Blue
Orange
Green
Brown
Pair Tip Ring
UTTECHNOLOGYDESIGNGUIDELINESV735
6..88 CABLE CAPACITIES IN CABLE TRAYS / CONDUITS
• When the internal cable trays, risers and Ladders etc, are designed, supplied and installed by others, the
maximumnumberofF/FTPcablesshallnotexceed75%ofthetray,Howeverthisneedtobereducedinthe
case of bends and crossovers.
• WhereanFOCableblockwiringisconsidered,averycarefulconsiderationmustbetaken,whiledesigning
thesystem.Theownershallberesponsibleforthedesign,supplyandmaintenanceofallrelateditems.
6.9 PATCHING:
• Thedesignofpatchframelayoutsiscriticaltocreateahighlevelofmanageabilitywithinacompactcabinet,
whilstmaintainingeffectiveoperationswhenusedbythecustomer.
• We recommend all horizontal FTP cabling should be terminated in 24 port Patch panel, placed inside the
cabinet.
• SCSCONTRACTORshallprovideCategory6ALSZHcableassembliesattheONTandattheWallOutlets.
• SCSCONTRACTORshallprovide50%ofthetotalnumberofHorizontalOutletsasperthebelowlength
• -ForWallOutlet,thecableassemblyshallbe3m
• -FortheONTthecableassemblyshallbe1m
• Category6A cable assemblies shall be4-pairRJ45/RJ45FTPShieldedhorizontal cabling, andmustbe
factory terminated.
• Fielded Terminated Cable assemblies are not accepted.
• SCSCONTRACTORshall providedetailed ofFOpatching schedule asper the table attached in the last
section of the guidelines.
6.10 LABELING:
LABELE LEMENTS
Allflooroutlets,patchframesandhorizontalcablesshouldbelabeled.Atypewrittenstandardlabelingsystemis
recommended.ThelabelingschemeshallsubmittedbythecontractorforUTTapproval.
36UTTECHNOLOGYDESIGNGUIDELINESV7
46 | | Guideline || 47 | Guideline |
Horizontal Cable Labels
Labelallhorizontalcablesatbothendsusingaself-laminating,wraparoundlabel.
UserOutletLabelsEachRJ45useroutletshouldbelabeledwithauniqueidentifier,typicallyusingtheagreed
scheme.
6.11 UNDER FLOOR SYSTEMSForgeneralofficespaces,anunderfloorracewaysystemshouldbeusedformaximumflexibility
Inmulti-channellayouts,separateracewaysmustbeusedfortelecommunicationsandelectricalpowertoreduce
electromagneticinterference.Thedividersforseparationofcompartmentsintheracewayshouldbebondedto
ground.
6.11.1 MAIN ELEMENTS OF UNDER FLOOR RACE WAY SYSTEMS:
1. DISTRIBUTION RACEWAY:
Distributionracewayprovidesapathwayforthecablesfromthefeederracewaytotheworkareas.Theminimum
sizeoftheDistributionracewayshouldbe30mmheight.
60mmwidthofcrosssectionalarea.Thesamesizemustbeusedforevery(multi-channel)layout.
2. FEEDER RACE WAY:
FeederracewayprovidesapathwayforthecablesfromtheDistributionBoxintheFloorTelecommunications
RoomtotheDistributionraceways.TheminimumsizeoftheFeederracewayshouldbe40mmheightx200mm
widthofcross-sectionalarea.Thesamesizemustbeusedforevery(multi-channel)layout.
ThefeederracewaysstartingpointintheFloorTelecommunicationsRoommustbeadjacenttotheDistribution
Box.TheFeederracewayshouldendatthelastdistributionracewayitisserving.
3. ACCESS UNIT:
TheaccessunitprovidesaccessatthepointofintersectionoftheFeederandtheDistributionraceways.
UTTECHNOLOGYDESIGNGUIDELINESV737
6.12 CABLE TRAYS:
• Cabletraysaremostlyusedforfloorswithraisedtilesorraisefloorings.
• Asageneralguideline,Cabletraysthatintersectmustbeprovidedwithatransitionalbendradiusof150mm
in all directions.
• Exposedsheetmetaledgesmustbeprovidedwithbushingsorothermeansofprotectionsuchthatcableswillnotbedamagedduringorafterinstallation.SinceCabletraysareusuallymetallic,allsharpedges,burrs
andscrewtipsthatmaycomeintocontactwithcablingshouldberemoved.
• Theminimumaccess spacebetween the sub-floor and theunderside of thefloor tile shall beminimum150mm (6 in).
• UTTshouldbeconsultedintheinitialdesignstagetodecideontherequirementsifthebuildingisdesigned
forofficeuse.
6.13 INDOOR CABINETS SPECIFICATION
Depending upon the termination and Patch panel requirement, and to accommodate other active and passive
equipments,aCabinetwithstandard19”rackisrequired,generallycomplyingwiththefollowing:-
A) FREE STANDING TYPES
The free standing types are used in high rise buildings, shopping malls, Hospitals, Airports, Large commercial
establishments in Main Telecommunication Rooms.
42U800mmwidex800mmdeep19”equipmentcabinet
• Glass front door
• Steel doors
• Air Circulation inside the cabinet
• Openings for cable entry on the top and bottom of the cabinet
• Jacking Feet
• Horizontal cable management
• Verticalcablemanagement
• Bonded to a local earth point
B) WALLMOUNTED TYPECABINETS
ThewallmountedcabinetsshallbeinstalledintheFloorTelecommunicationRoomsandtheSecondary/GSM
Telecommunication Rooms
12U(H)x600mmwidex500mmdeep19”equipmentCabinet
38UTTECHNOLOGYDESIGNGUIDELINESV7
220 | | Product Sheets || 221 | Product Sheets || Product Sheets |
222 | | Product Sheets || 223 | Product Sheets || Product Sheets |
224 | | Product Sheets || 225 | Product Sheets || Product Sheets |
226 | | Product Sheets || 227 | Product Sheets || Product Sheets |
228 | | 229| 229
AV Proposal
Prod
uct S
heet
s/LE
AF
230 | | Product Sheets || 231 | Product Sheets || Product Sheets |
232 | | Product Sheets || 233 | Product Sheets || Product Sheets |
wiring
234 | | 235
Prod
uct S
heet
s/SO
MFY
SOMFY
236 | | Product Sheets || 237
100 UT TECHNOLOGY DESIGN GUIDELINES V7
238 | | Product Sheets || 239
UT TECHNOLOGY DESIGN GUIDELINES V7 101
102 UT TECHNOLOGY DESIGN GUIDELINES V7
240 | | Product Sheets || 241
UT TECHNOLOGY DESIGN GUIDELINES V7 103
242 | | Notes || 243 | Notes |
244 | | Notes || 245 | Notes |
246 | | Notes || 247 | Notes |
248 | | Notes || 249 | Notes |
250 | | Notes || 251 | Notes |