LOKSEAM®
Technical/insTallaTion informaTion
IMPORTANT NOTICEREAD THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE LOkSEAM® ROOFING SYSTEM. METL-SPAN DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE WARRANTIES WILL BE ISSUED.
ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY METL-SPAN IMMEDIATELY IF ANY PRODUCT IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT.
IF THERE IS A CONFLICT BETWEEN PROJECT ERECTION DRAWINGS PROVIDED OR APPROVED BY METL-SPAN AND DETAILS IN THIS MANUAL, PROJECT ERECTION DRAWINGS WILL TAkE PRECEDENCE.
Ice Dam DisclaimerMetl-Span designs its standing seam roofs to meet the load requirements dictated by governing codes and project specifications, including applicable snow loads. However, Metl-Span expressly disclaims responsibilty for weathertightness or roof point loading issues or other hazards resulting from ice dam situations. Any time ice and snow can melt on the main body of the roof and refreeze at the eave or in the shadow of an adjacent wall, an ice dam situation may develop. In addition to local climate, ice dam formation is affected by many other factors, including but not limited to, roof insulation R value, roof panel color, interior temperature of building, heater location in building, eave overhangs, parapet walls, shading of building roof areas from adjacent trees, parapets, buildings, etc. These factors are design and maintenance issues and are outside the control of Metl-Span. Metl-Span specifically disclaims any liability for damage due to ice dam formation, although the following issues should be taken into consideration concerning standing seam roofs installed in freezing climates:
• Alwaysusefieldseamedpanels.Thesemachine-foldedseamsaremoredurablewhensubjectedtooccasionalicing.
• Eliminate "cold" eave overhangs and parapet walls from the building design. Roof overhangs outside the heatedenvelope of the building will tend to be colder than the roof areas over the heated envelope. Simple roof designs arepreferred. Parapet walls at the eave allow ice and snow to collect due to shading effects and the lower roof temperaturescaused thereby.
• Make sure the interior of the building is adequately insulated and the heating is properly distributed. Inadequateinsulation in the roof and/or improper heat distribution causes heat flow though the main body of the roof. On days whenthe temperature is below freezing, this heat gain can cause ice and snow to melt and refreeze at the eave where theroof is colder.
• Layoutthebuildingtopreventtheeavesandotherroofareasfrombeingshadedduringthewinter.Thismaymeaneliminating adjacent trees or reconsidering roof geometries.
• Considerusingself-regulatingheatingcablesattheeavestomitigatetheeffectsoficedams.
• Onbuildingdesignsusingattics, over-insulate theattic floor andprovideadequate ventilation in theattic.Thiswillreduce heat transfer through the roof resulting in more consistent roof temperatures between eave and field of roof.
• Increasethedegreeofdiligencewithrespecttounderlaymentmaterialsatroofareaspronetoicing.Thismayincludevalleys, eaves, dormers and roof areas near dormers, parapets and the like where shading may occur.
Formoreinformationonthissubject,pleaserefertotheMCA'sMetalRoofDesignForColdClimatesmanual.
TheEngineeringdatacontainedhereinisfortheexpresseduseofcustomersanddesignprofessionals.Alongwiththisdata,itisrecommendedthatthedesignprofessionalhaveacopyofthemostcurrentversionoftheNorthAmericanSpecificationfortheDesignofCold-FormedSteelStructuralMemberspublishedbytheAmerican Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer.
Descriptionsandspecificationscontainedhereinwereineffectatthetimethispublicationwasapprovedforprinting.Inacontinuingeffort to refine and improve products, Metl-Span reserves the right to discontinue products at any time or change specifications and/or designs without incurring obligation. To ensure you have the latest information available, please inquire or visit our website at metlspan.com. Application details are for illustration purposes only and may not be appropriate for all environmental conditions, building designs or panel profiles. Projects should be designed to conform to applicable building codes, regulations and accepted industry practices. If there is a conflict between this manual and project erection drawings, the erection drawings will take precedence.
© 2019 Metl-Span, part of the Cornerstone Building Brands family. All Rights Reserved.Metl-Span’sSingleSkinproductlineismanufacturedbyMBCI.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-3
LokSeam®
TABLE OF CONTENTSLokSeam®
ROOFING SYSTEMGeneralDescription ......................................................................................................................................................LS-5Architect/EngineeringInformation .................................................................................................................................LS-6
ENGINEERINGUL90Requirements .....................................................................................................................................................LS-718”Properties/LoadTables ............................................................................................................................... LS-8-LS-916”Properties/LoadTables ............................................................................................................................LS-10-LS-1112”Properties/LoadTables ........................................................................................................................... LS-12-LS-13
SPECIFICATIONSSpecifications For Metal Roofing .................................................................................................................. LS-14-LS-20
GENERAL INFORMATIONProductChecklist .......................................................................................................................................... LS-21-LS-25Ordering Information .................................................................................................................................................. LS-26Preparatory Requirements ......................................................................................................................................... LS-27Unloading .............................................................................................................................................................. LS-28-29Handling/Panel Storage ............................................................................................................................................. LS-30
DETAILSSpecialErectionTechniques
RoofCurbInstallation ....................................................................................................................... LS-31-LS-34FieldHemmingPanelEnd ............................................................................................................................. LS-35Panel .............................................................................................................................................................. LS-36
DetailsOverPurlinsEndlap ............................................................................................................................................................ LS-37Hip .................................................................................................................................................................. LS-38Ridge .............................................................................................................................................................. LS-39VentedRidge ................................................................................................................................................. LS-40FloatingValley ................................................................................................................................................ LS-41FixedValley .................................................................................................................................................... LS-42HighEave ...................................................................................................................................................... LS-43FloatingEavewithEaveTrim ........................................................................................................................ LS-44FixedEavewithEaveTrim ............................................................................................................................ LS-45FloatingEavewithGutter .............................................................................................................................. LS-46FixedEavewithGutter .................................................................................................................................. LS-47SnowGutter ................................................................................................................................................... LS-48Floating Rake ................................................................................................................................................. LS-49ParapetHighEave ......................................................................................................................................... LS-50Floating Parapet Rake ................................................................................................................................... LS-51Roof Transition ............................................................................................................................................... LS-52
DetailsOverWoodDeckEndlap ............................................................................................................................................................ LS-53Hip .................................................................................................................................................................. LS-54Fixed Ridge .................................................................................................................................................... LS-55Floating Ridge ................................................................................................................................................ LS-56VentedRidge ................................................................................................................................................. LS-57FloatingValley ................................................................................................................................................ LS-58FixedValley .................................................................................................................................................... LS-59HighEave ...................................................................................................................................................... LS-60FloatingEavewithEaveTrim ........................................................................................................................ LS-61FixedEavewithEaveTrim ............................................................................................................................ LS-62FloatingEavewithGutter .............................................................................................................................. LS-63FixedEavewithGutter .................................................................................................................................. LS-64Floating Rake ................................................................................................................................................. LS-65Fixed Rake ..................................................................................................................................................... LS-66FloatingParapetHighEave ........................................................................................................................... LS-67FixedParapetHighEave ............................................................................................................................... LS-68Floating Parapet Rake ................................................................................................................................... LS-69Fixed Parapet Rake ....................................................................................................................................... LS-70Roof Transition ............................................................................................................................................... LS-71
LS-4REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
TABLE OF CONTENTSLokSeam®
DETAILS CONTINUEDDetailsOverMetalDeck
RigidBoardInsulationOverMetalDeck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-72Endlap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-73Fixed Ridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-74VentedRidge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-75FloatingValley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-76FixedHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-77FloatingEavewithEaveTrim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-78FloatingEavewithGutter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-79Floating Rake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-80FixedParapetHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-81FloatingParapetHighEave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LS-82
SUBJECTTOCHANGEWITHOUTNOTICE SEEmetlspan.comFORCURRENTINFORMATION REV00.02LS-5
LokSeam®
ROOFING SYSTEM
18", 16'', or 12''
1¾"
⅜"
CoverageWidths-18",16"or12"
MinimumSlope-3:12
PanelAttachment-StandardandUL90Clips(concealedfasteningsystems)
PanelSubstrate-Galvalume®(standard)
Gauge-Standard:24(18",16",12"widths);Optional:22(18",16",12"widths),26(12"widthonly)
Finishes-Striated(standard)*orEmbossedStriated
Coatings-Signature®200,Signature®300,Signature®300Metallic
Signature®isaregisteredtrademarkofCornerstone Building Brands family.GalvalumePlus®isaregisteredtrademark
ofBIECInternational. — Available in any quantity.
— Minimum quantity may be required.
Othercolors,finishes,gauges,andmaterialsavailable;pleaseinquire.* Striatedpanelsarestandardtoreduce“oilcanning”.
PRODUCTSignature®300Metallic Signature®300 Signature®200 GalvalumePlus®
26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga. 26-Ga. 24Ga. 22-Ga.LokSeam®
12"Wide
16"Wide
18"Wide
PRODUCT SELECTION CHART
GENERAL DESCRIPTION
LS-6REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
ROOFING SYSTEMARCHITECT/ENGINEER INFORMATION
1. LokSeam®isasnap-together,integralbattenroofsystem,availableinthreewidths:18",16",and12".Factoryappliedmastic inside of female leg of panel is standard.
2.Theminimumrecommendedslopeis3:12.Forslopeslessthan3:12,callMetl-Span.3. LokSeam®isaUL90rated,structuralroofingpanel.Thispanelcanbeinstalleddirectlyoverpurlinsorbarjoists.Itdoes
notrequireasolidsubstructureforsupport(Caution:SeeNote14).4.Watertightandaestheticallypleasingendlapsmaybeaccomplishedthroughtheuseofswagedandprepunchedpanels
(16"panelscanbeswagedbutnotpunched).Metl-Spanrecommendstheuseofprepunchedback-upplatesattheendlapfor weathertightness. Prepunching of the panels is available for the endlap condition only. (Swaged endlaps require the roof erection to proceed from left to right as viewed from the eave looking toward the ridge.) Roofs with no endlaps maybeerectedfromeitherdirection.Forpanellengthsover40’,pleaseinquire.Whenusinganalternateendlapdetailasshown on Pages LS-37 and LS-53 do not order panels with prepunched endlaps.
5.PanelscanbeinstalledonroofswithatransitionbyusingMetl-Span’sdie-formedribcovers.6.Narrowerwidths,heaviergauges,striationsandembossingminimizeoilcanning.Industrystandardis18”wide,24-gauge.
Oil canning is not a cause for rejection.7.Thesubstructure(eavetoridge)mustbeonplanewithatoleranceof¼"in20’and⅜"in40'.8.Allpanelsrequireendsealantateaveandvalleyconditions;however,forillustrationpurposes,thissealantisnotshownon
all drawings. See Page LS-36 for panel end sealant detail.9.Forproperfastenerapplication,seePages LS-24 and LS-25.10.Alldrawingsandtrimdimensionsinthismanualarebasedona1¼"wallthickness(“R”Panel)andaslopeof3:12.
Other wall panel thicknesses as well as roof slopes may affect various dimensions on drawings and trim. If you have any questions, call Metl-Span.
11. The information in this manual is believed to be correct and accurate. It should not be used for any specific application without being reviewed by a registered professional engineer. All metal roofs should be designed by a registered, professonal engineer for loads specified by the governing code, including the higher pressures encountered at the edge zones of the roof.
12. Avoid restricting the thermal expansion and contraction of the LokSeam® panels. (ie: Do not attach panels to the substructure at both the eave and ridge.)
13. LokSeam® panels are not designed to be work platforms. Avoid any unnecessary foot traffic on LokSeam® panels. If foot traffic is required, protect the roof panels by using some type of roof pad, temporary deck, or walkway.
14. When installing LokSeam® panels over open framing with blanket insulation: (A) install insulation parallel to purlins or joists, or (B) install insulation across purlins or joists and compress it with pinch bars. (¼" thick radiant barrier insulation may be used as an alternative to blanket insulation.)
CAUTIONDiaphragmcapabilitiesandpurlinstabilityarenotprovidedbyMetl-Span’sLokSeam® roof system.
Therefore,otherbracingmayberequiredtoconformtoA.I.S.C.orA.I.S.I.specifications.
WARNINGAswithallstandingseamroofsystems,soundattenuation(example:blanketinsulation)shouldbeinstalledbetweenthepanelsandopenframing,suchaspurlinsorjoists,toprevent“roofrumble”duringwindyconditions.
Applications over solid deck such as rigid insulation over a metal deck or a wood deck may require additional acoustical consideration to ensure that thermal vibration noises are isolated from the building interior. This is especially important if the bottom of the deck is left open to the interior, in cathedral ceiling applications or when the attic space is used as a return air plenum.
A vapor retarder may be necessary to protect roofing components when high humidity is a factor. The need for a vapor retarder, as well as the type, placement and location should be determined by an architect or engineer. The following areexamplesofconditionsthatmayrequireavaporretarder:(A)aprojectwhereoutsidewintertemperaturesbelow40degreesF.areanticipatedandwhereaveragewinterinteriorrelativehumidityof45%orgreaterisexpected.(B)building usages with high humidity interiors such as indoor swimming pools, textile manufacturing operations, food, paperorotherwet-processindustrialplants.(C)Constructionelementsthatmayreleasemoistureaftertheroofisinstalled, such as interior concrete, masonry or plaster work and fuel burning heaters.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-7
LokSeam®
ENGINEERINGUNDERWRITERS LABORATORIES APPROVAL
Construction Number
Panel Width (in.)
Gauge Clip Type Clip Spacing Substrate
UL-2218 Impact
Resistance
UL-263 Fire
Rating
UL-580 Rating
254 12" 22min. UL90 5'-0" Open Framing Class4 ClassA Class90
254 12" 24min. UL90 4'-0" Open Framing Class4 ClassA Class90
255 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90
303 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90
342 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90
343 18"max. 24min. UL90 3'-0" Plywood Class4 ClassA Class90
414 18"max. 24min. UL90 3'-0" Plywood Class4 ClassA Class90
436 18"max. 24min. UL90 4'-0" Plywood Class4 ClassA Class90
445 12" 22min. UL90 5'-0" Open Framing Class4 ClassA Class90
445 12" 24min. UL90 4'-0" Open Framing Class4 ClassA Class90
446 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90
448 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90
486 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90
508A 18"max 24min. UL90 3'-0" CompositeSystem Class4 ClassA Class90
543 12"max. 22min. UL90 5'-0" Open Framing Class4 ClassA Class90
543 18"max. 24min. UL90 4'-0" Open Framing Class4 ClassA Class90
544 18"max. 24min. UL90 4'-0" CompositeSystem Class4 ClassA Class90
NOTES1. WinduplifttestproceduresareinaccordancewithUnderwritersLaboratoriesStandardUL-580under“TestsFor
UpliftResistanceofRoofAssemblies”.2. AdetailedinstallationmethodisavailableforeachConstructionNumberaboveandcanbefoundintheUL
RoofingMaterialsandSystemsDirectory.Thepanelsmustbeinstalledinacertainmannertoachievethepublished results.
3. ThepanelqualifiesforaClassAfireratingincompliancewithUnderwritersLaboratoriesStandardUL-263.4. ThepanelsystemislistedunderfollowingFireResistanceDesignNumbers:P225,P227,P230,P237,P265,
P268,P508,P510,P512,P701,P711,P720,P722,P726,P731,P734,P801,P815,andP819.RefertotheULFireResistanceDirectoryforspecificconstructionmethodsandhourlyratings.
5. LokSeam®panelscarryaClass4ratingunderUL-2218“TestStandardForImpactResistance”.
FLORIDA BUILDING CODE PRODUCT APPROVALLokSeam® Roofing System details and engineering load tables have been examined by the State of Florida and comply with the 5thEdition(2014)FloridaBuildingCodeProductApprovalNumber(FL#11819.3).
LS-8REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
ENGINEERINGLokSeam® PANEL
18"
1¾"
SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING
PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)
24 50 1.25 0.0321 0.0403 1.2066 0.0682 0.0465 1.391222 50 1.60 0.0446 0.0594 1.7795 0.0957 0.0655 1.9620
NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof
theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project job site in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-9
LokSeam®
ENGINEERINGLokSeam® PANEL
ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT
24- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 148.4 103.1 75.7 58.0 45.8 37.1 30.7
2-SPAN LIVELOAD 128.7 89.4 65.7 50.3 39.7 32.2 26.6
3-SPAN LIVELOAD 160.9 111.7 82.1 62.8 49.7 40.2 33.2
4-SPAN LIVELOAD 150.2 104.3 76.6 58.7 46.4 37.6 31.0
22- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 200.0 145.3 106.8 81.8 64.6 52.3 43.2
2-SPAN LIVELOAD 189.8 131.8 96.8 74.1 58.6 47.5 39.2
3-SPAN LIVELOAD 200.0 164.8 121.1 92.7 73.2 59.3 49.0
4-SPAN LIVELOAD 200.0 153.8 113.0 86.5 68.4 55.4 45.8
NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.
18"
1¾"
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.
LS-10REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
ENGINEERINGLokSeam® PANEL
SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING
PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)
24 50 1.34 0.0361 0.0452 1.3527 0.0758 0.0520 1.557022 50 1.71 0.0500 0.0666 1.9938 0.1052 0.0731 2.1921
NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof
theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.
16"
1¾"
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-11
LokSeam®
ENGINEERINGLokSeam® PANEL
ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT
24- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 166.1 115.3 84.7 64.9 51.3 41.5 34.4
2-SPAN LIVELOAD 144.8 100.5 73.9 56.6 44.7 36.2 29.8
3-SPAN LIVELOAD 181.0 125.7 92.3 70.7 55.9 45.2 37.4
4-SPAN LIVELOAD 169.0 117.3 86.2 66.0 52.1 42.2 34.9
22- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 200.0 162.4 119.3 91.3 72.2 58.5 48.3
2-SPAN LIVELOAD 200.0 147.7 108.5 83.1 65.6 53.2 43.9
3-SPAN LIVELOAD 200.0 184.6 135.6 103.8 82.0 66.5 54.9
4-SPAN LIVELOAD 200.0 172.4 126.6 97.0 76.6 62.1 51.3
NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.
16"
1¾"
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.
LS-12REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
ENGINEERINGLokSeam® PANEL
SECTION PROPERTIESNEGATIVE BENDING POSITIVE BENDING
PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe MaxoGAUGE (KSI) (PSF) (IN.4/FT) (IN.3/FT) (KIP-IN) (IN.4/FT) (IN.3/FT) (KIP-IN)
24 50 1.41 0.0472 0.0597 1.7888 0.0953 0.0682 2.042922 50 1.81 0.0663 0.0878 2.6292 0.1313 0.0954 2.8577
NOTES1. All calculations for the properties of LokSeam®panelsarecalculatedinaccordancewiththe2012editionof
theNorthAmericanSpecificationforDesignofCold-FormedSteelStructuralMembers.2. Ixe is for deflection determination.3. Sxe is for bending.4. Maxo is allowable bending moment.5. All values are for one foot of panel width.
12"
1¾"
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-13
LokSeam®
ENGINEERINGLokSeam® PANEL
ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT
24- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 200.0 151.3 111.2 85.1 67.3 54.5 45.0
2-SPAN LIVELOAD 190.8 132.5 97.3 74.5 58.9 47.7 39.4
3-SPAN LIVELOAD 200.0 165.5 121.7 93.2 73.6 59.6 49.3
4-SPAN LIVELOAD 200.0 154.6 113.6 87.0 68.7 55.7 46.0
22- Gauge (Fy = 50 kSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET2.5 3.0 3.5 4.0 4.5 5.0 5.5
SINGLE LIVELOAD 200.0 200.0 155.5 119.1 94.1 76.2 63.0
2-SPAN LIVELOAD 200.0 194.8 143.1 109.6 86.6 70.1 57.9
3-SPAN LIVELOAD 200.0 200.0 178.9 136.9 108.2 87.6 72.4
4-SPAN LIVELOAD 200.0 200.0 167.0 127.9 101.0 81.8 67.6
NOTES:1.THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.2.Strenghtcalculationsbasedonthe2012AISIStandardNorth American Specification for the Design of Cold-Formed Steel Structural Members.3.Allowableloadsareapplicableforuniformloadingandspanswithoutoverhangs.4.LIVEloadcapacitiesareforthoseloadsthatpushthepanelagainstitssupports.Theapplicablelimitstatesareflexure, shear,combinedshearandflexure,webcripplingatendandinteriorsupports,andadeflectionlimitofL/180under strenght-level loads.5.Panelpulloverandscrewpulloutcapacitymustbecheckedseparatelyusingthescrewsemployedforeachparticular application when utilizing this load chart.6.Theuseofanyfieldseamingequipmentoraccessoriesincludingbutnotlimitedtoclips,fasteners,andsupportplates (eave,backup,rake,etc.)otherthanthatprovidedbythemanufacturermaydamagepanels,voidallwarrantiesandwill void all engineering data.7.Thismaterialissubjecttochangewithoutnotice.PleasecontactMetl-Spanforthemostcurrentdata.
12"
1¾"
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommendedthat the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed SteelStructural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria forcold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to theproject jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired,please contact the manufacturer.
LS-14REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
SPECIFICATIONS
PART 1 - GENERAL1.1 SECTION INCLUDES
A. Snap joint-seamed, standing seam metal roof panels, with related metal trim and accessories.
1.2 RELATED REQUIREMENTSSpecifier: If retaining this optional article, edit list below to correspond to Project.
A. Division01Section"SustainableDesignRequirements"forrelatedLEEDgeneralrequirements.
B. Division05Section"StructuralSteelFraming"forstructural steel framing supporting metal panels.
C. Division05Section"SteelDecking"forcontinuousmetal decking supporting metal panels.
D. Division05Section"Cold-FormedMetalFraming"forcold-formed metal framing supporting metal panels.
E. Division05Section"Cold-FormedMetalTrusses"forcold-formed metal trusses supporting metal panels.
F. Division06Section"Sheathing"forsheathingsubstrate for metal roof panels.
G.Division07Section["ThermalInsulation"]["RoofInsulation"]forthermalinsulationinstalledundermetalpanels.
H. Division07Section"AirBarriers"forairbarrierswithinroof assembly and adjacent to roof assembly.
I. Division07Section"MetalWallPanels"forfactory-formedmetalwall[andsoffit]panels.
J. Division07Section"SheetMetalFlashingandTrim"for formed sheet metal copings, flashings, reglets, and roof drainage items in addition to items specified in this Section.
K. Division07Section"ManufacturedRoofSpecialties"for manufactured copings, reglets, and roof drainage items in addition to items specified in this Section.
L. Division07Section"JointSealants"forfield-appliedjoint sealants.
M.Division13Section"MetalBuildingSystems"forsteelframing supporting metal panels.
1.3 REFERENCESSpecifier: If retaining this optional article, edit list below to correspond to Project.
A. AmericanArchitecturalManufacturer'sAssociation(AAMA):www.aamanet.org:1. AAMA621-VoluntarySpecificationsforHigh
PerformanceOrganicCoatingsonCoilCoatedArchitecturalHotDippedGalvanized(HDG)&Zinc-AluminumCoatedSteelSubstrates.
2. AAMA809.2-VoluntarySpecificationNon-DryingSealants.
B. AmericanSocietyofCivilEngineers(ASCE):www.asce.org/codes-standards: 1. ASCE7-MinimumDesignLoadsforBuildingsand
Other Structures.C. ASTMInternational(ASTM):www.astm.org:
1. ASTMA653-SpecificationforSteelSheet,Zinc-Coated(Galvanized)orZinc-IronAlloy-Coated(Galvannealed)bytheHot-DipProcess.
2. ASTMA755-SpecificationforSteelSheet,MetallicCoatedbytheHot-DipProcessandPrepaintedbytheCoil-CoatingProcessforExteriorExposedBuildingProducts.
3. ASTMA792/A792M-StandardSpecificationforSteelSheet,55%Aluminum-ZincAlloy-CoatedbytheHot-DipProcess.
4. ASTMA980-StandardSpecificationforSteel,Sheet,Carbon,UltraHighStrengthColdRolled.
5. ASTMC645-SpecificationforNonstructuralSteelFraming Members.
6. ASTMC920-SpecificationforElastomericJointSealants.
7. ASTMD226-StandardSpecificationforAsphalt-Saturated Organic Felt Used in Roofing and Waterproofing.
8. ASTMD2244-TestMethodforCalculationofColorDifferencesfromInstrumentallyMeasuredColorCoordinates.
9. ASTMD4214-TestMethodsforEvaluatingDegreeofChalkingofExteriorPaintFilms.
10. ASTME1592-StandardTestMethodforStructural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference.
11. ASTME1980-PracticeforCalculatingSolarReflectanceIndexofHorizontalandLow-SlopedOpaque Surfaces.
D. CoolRoofRatingCouncil(CRRC):www.coolroofs.org/productratingprogram.html: 1.CRRC-1-2008-CRRCProductRatingProgram.
E. InternationalAccreditationService(IAS):1. IASAC472-AccreditationCriteriaforInspection
ProgramsforManufacturersofMetalBuildingSystems,PartB.
F.UnderwritersLaboratories,Inc.(UL):www.ul.com:1. UL580-TestsforUpliftResistanceofRoof
AssembliesG.USEnvironmentalProtectionAgency:www.
energystar.gov/index.cfm: 1. EnergyStarReflectiveRoofProducts.
H. USGreenBuildingCouncil(USGBC):www.usgbc.org:1. LEED-LeadershipinEnergyandEnvironmental
Design(LEED)GreenBuildingRatingSystems.
SECTION 07 41 13Metal Roofing
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-15
LokSeam®
SPECIFICATIONS1.4 ADMINISTRATIVE REQUIREMENTS
A. Preinstallation Meeting: Prior to erection of framing, conduct preinstallation meeting at site attended byOwner,Architect,manufacturer'stechnicalrepresentative, inspection agency and related trade contractors.1. Coordinatebuildingframinginrelationtometal
panel system. 2. Coordinateopeningsandpenetrationsofmetal
panel system.3. CoordinateworkofDivision07Sections"Roof
Specialties"and"RoofAccessories"andopeningsandpenetrationsandmanufacturer'saccessorieswith installation of metal panels.
1.5 QUALITY ASSURANCEA. Manufacturer/Source: Provide metal roof panel
assembly and accessories from a single manufacturer providing fixed-base roll forming, and accredited under IASAC472PartB.
B. ManufacturerQualifications:Approvedmanufacturerlisted in this Section with minimum five years experience in manufacture of similar products in successful use in similar applications.
Specifier: Retain paragraph below if Owner allows substitutions but requires strict control over qualifying of substituted manufacturers.
1. ApprovalofComparableProducts:Submitthefollowing in accordance with project substitution requirements, within time allowed for substitution review:a. Product data, including certified independent
test data indicating compliance with requirements.
b. Samples of each component.c. Sample submittal from similar project.d. Project references: Minimum of five
installations not less than five years old, with Owner and Architect contact information.
e. Sample warranty.f. IASAC472certificate.
2. SubstitutionsfollowingawardofcontractarenotallowedexceptasstipulatedinDivision01GeneralRequirements.
3. Approvedmanufacturersmustmeetseparaterequirements of Submittals Article.
Specifier:Reviewofmanufacturers'qualifyingofinstallersisrecommended for larger projects. Metl-Span requires Installer and supervisor certification when project requirements include extended warranty.
C. InstallerQualifications:ExperiencedInstaller[certifiedbymetalpanelmanufacturer]withminimumoffiveyears experience with successfully completed projects of a similar nature and scope.
1. Installer'sFieldSupervisor:Experiencedmechanic[certifiedbymetalpanelmanufacturer]supervisingwork on site whenever work is underway.
Specifier: Retain paragraph below and edit as appropriate for Federal projects and for public works projects utilizing Federal funds;consultwithprojectContractingOfficer.CoordinatewithSubmittals Article.
D. BuyAmericanCompliance:Materialsprovidedunderwork of this Section shall comply with the following requirements:1. BuyAmericanActof1933BAA-41U.S.C§§10a–10d.2. BuyAmericanprovisionsofSection1605ofthe
AmericanRecoveryandReinvestmentActof2009(ARRA).
1.6 ACTION SUBMITTALSA. ProductData:Manufacturer’sdatasheetsfor
specified products.Specifier: Retain and edit below to comply with Project requirementsforLEEDorothersustainabledesignrequirements.
B. LEEDSubmittals:1. CreditSS7.2HeatIslandEffect-Roof:Product
data indicating compliance with solar reflectance index requirement.
2. CreditMR4RecycledContent:Productdataindicating the following:a. Material costs for each product having recycled
content.b. Percentages by weight of post-consumer and
pre-consumer recycled content for each item.c. Total weight of products provided.
C. ShopDrawings:Showlayoutsofmetalpanels.Include details of each condition of installation, panel profiles, and attachment to building. Provide details ataminimumscale1-1/2-inchperfootshowingedgeconditions, joints, fastener and sealant placement, flashings, openings, penetrations, roof accessories, lightning arresting equipment, and special details. Make distinctions between factory and field assembled work.1. Indicatepointsofsupportingstructurethatmust
coordinate with metal panel system installation.2. Includedataindicatingcompliancewith
performance requirements.3. Includestructuraldataindicatingcompliancewith
requirements of authorities having jurisdiction.D. SamplesforInitialSelection:Foreachexposed
product specified including sealants. Provide representativecolorchartsofmanufacturer'sfullrangeof colors.
E. SamplesforVerification:Provide12-inch-(305mm-)long section of each metal panel profile. Provide color chip verifying color selection.
LS-16REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
SPECIFICATIONS1.7 INFORMATIONAL SUBMITTALS
A. Product Test Reports: Indicating compliance of products with requirements, witnessed by a professional engineer.
B. QualificationInformation:ForInstallerfirmandInstaller’sfieldsupervisor.
C. IASAccreditationCertificate:Indicatingthatmanufacturer is accredited under provisions of IAS AC472.
Specifier: Retain one or more of three paragraphs below when required for project.
D. BuyAmericanCertification:Manufacturers'lettersof compliance acceptable to authorities having jurisdiction, indicating that products comply with requirements.
Specifier:FSBCcertificationbelowisavailablefor12and16inch wide panels.
E. FloridaStateBuildingCodeCertificate.F. Manufacturer'sWarranty:Samplecopyof
manufacturer'sstandardwarranty.
1.8 CLOSEOUT SUBMITTALSA. Maintenance data.B. Manufacturer'sWarranty:Executedcopyof
manufacturer'sstandardwarranty.
1.9 DELIVERY, STORAGE, AND HANDLINGA. Protect products of metal panel system during
shipping, handling, and storage to prevent staining, denting, deterioration of components or other damage. Protect panels and trim bundles during shipping.1. Deliver,unload,store,anderectmetalpanel
system and accessory items without misshaping panels or exposing panels to surface damage from weather or construction operations.
2. StoreinaccordancewithManufacturer'swritteninstructions. Provide wood collars for stacking and handling in the field.
1.10 COORDINATIONA. Coordinatesizes,profiles,andlocationsofroof
curbs and other roof-mounted equipment and roof penetrations, based upon sizes of actual selected equipment.
1.11 WARRANTYSpecifier:WarrantytermsbelowareavailablefromMetl-Span.Verifythatotherallowablemanufacturersfurnishwarrantymeeting requirements.
A. SpecialManufacturer’sWarranty:Onmanufacturer’sstandard form, in which manufacturer agrees to repair or replace metal panel assemblies that fail in materials and workmanship within one year from date ofSubstantialCompletion.
Specifier:Metl-Span'soptionalsinglesourceweathertightnesswarranties below are available for projects installed by an Metl-Span-certified installer under inspection by an Metl-Span field technical representative. Metl-Span representative can provide warranty cost estimate for desired combination of cost limitation and period of warranty desired by owner.
B. SpecialWeathertightnessWarranty:Onmanufacturer’sstandardform,inwhichmanufactureragrees to repair or replace metal panel assemblies that fail to remain weathertight, including leaks, [withoutmonetarylimitation][uptocostlimitationofsevendollars($7.00)persquarefootofcoveredarea][uptocostlimitationoffourteendollars($14.00)persquarefootofcoveredarea]within[5][10][15][20]yearsfromdateofSubstantialCompletion.
C. SpecialPanelFinishWarranty:OnManufacturer’sstandard form, in which Manufacturer agrees to repair or replace metal panels that evidence deterioration offactory-appliedfinishwithin[25]yearsfromdateofSubstantialCompletion,including:1. FluoropolymerTwo-CoatSystem:
Specifier:Confirmwarrantedperformancevaluesbelowforcustom colors. Second options in subparagraphs below are for Metl-SpanBrite-Red.
a. Colorfadinginexcessof[5][10]HunterunitsperASTMD2244.
b. ChalkinginexcessofNo.[8][6]ratingperASTMD4214.
c. Failure of adhesion, peeling, checking, or cracking.
2. ModifiedSilicone-PolyesterTwo-CoatSystem:Specifier:Confirmwarrantedperformancevaluesbelowforcustom colors. Second options in subparagraphs below are for Metl-SpanBrite-Red.Metl-SpanPolarWhitePolyesterdoesnot carry a warranty against chalking.
a. Colorfadinginexcessof[5][7]HunterunitsperASTMD2244,forverticalapplications.
b. Colorfadinginexcessof[7][10]HunterunitsperASTMD2244,fornon-verticalapplications.
c. ChalkinginexcessofNo.[8][7]ratingperASTMD4214,forverticalapplications.
d. ChalkinginexcessofNo.[6][5]ratingperASTMD4214,fornon-verticalapplications.
e. Failure of adhesion, peeling, checking, or cracking.
PART 2 - PRODUCTS2.1 MANUFACTURERSpecifier: Retain basis of design manufacturer and products listed in this Article where allowed. If inserting comparable manufacturers, carefully review products and engineering capabilities in relation to requirements of this Section, to ensure that other approved manufacturers offer products meeting Metl-Span'sstandards.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-17
LokSeam®
SPECIFICATIONSA. BasisofDesignManufacturer:Metl-SpanMetalRoof
andWallSystems,Metl-Span;Lewisville,TX.Tel:(972)221-6656;Email:[email protected]; Web:www.metlspan.com.1. Providebasisofdesignproduct[,orcomparable
productapprovedbyArchitectpriortobid].
2.2 PERFORMANCE REQUIREMENTSA. General:Providemetalroofpanelsystemmeeting
performance requirements as determined by application of specified tests by a qualified testing facilityonmanufacturer'sstandardassemblies.
Specifier:RecycledContentparagraphbelowdescribescalculationutilizedforLEED-NCCreditMR4.Modifyasrequired to meet project recycled content requirements, or delete if recycled content requirements are stipulated solely in Division01Section"SustainableDesignRequirements."
B. RecycledContent:ForSteelProducts:Postconsumer recycled content plus one-half of preconsumerrecycledcontentnotlessthan[25]percent.
Specifier: Retain one or more radiative property performance subparagraphs below based on project requirements. Retain SolarReflectanceIndexforLEEDprojects.RetainEnergyStarreferenceforprojectsseekingEnergyStarrating;productsmustbelistedonEPAEnergyStarwebsite.RetainCRRCcomplianceforprojectsrequiredtocomplywithCECrequirements.Verifyvalueswithmanufacturerforselectedpanelfinishes.ConfirmthatEnergyCoderequirementsarealso met by below.
C. RadiativePropertyPerformance:1. SolarReflectanceIndex:Minimum78forroof
slopesof2:12orlessand29forroofslopesgreaterthan2:12undermediumwindconditions,perASTME1980.
2. EnergyStarQualified:ListedonUSDoEENERGYSTARRoofProductsQualifiedProductList.
3. EnergyPerformance:ListedinCRRCRatedProductDirectory,withminimumpropertiesasrequiredbyapplicableEnergyefficiencyorHigh-PerformanceGreenBuildingstandard.
D. StructuralPerformance:Providemetalpanelassemblies capable of withstanding the effects of indicated loads and stresses within limits and under conditions indicated:
Specifier:Consultstructuralengineerandeditbelowasrequired by local codes. Insert structural data below if not indicated on drawings. Select applicable deflection limit.
1. WindLoads:Determineloadsbasedonuniformpressure, importance factor, exposure category, and basic wind speed indicated on drawings.a. WindUpliftTesting:Certifycapacityofmetal
panels by actual testing of proposed assembly perASTME1592.
2. SnowLoads:[___lbf/sq.ft.(___Pa)][Asindicated].
3. DeflectionLimits:Withstandinwardandoutwardwind-load design pressures in accordance with applicable building code with maximum deflection of[1/120][1/180][1/240]ofthespanwithnoevidence of failure.
4. SeismicPerformance:ComplywithASCE7,Section9,"EarthquakeLoads."
E. WindUpliftResistance:ComplywithUL580forwind-upliftclass[UL-30][UL-60][UL-90].
F. FloridaStateBuildingCodeCompliance:ComplywithrequirementsofFloridaStateBuildingCode.www.floridabuilding.org/pr/pr_app_srch.aspx
G. ThermalMovements:Allowforthermalmovementsfrom variations in both ambient and internal temperatures. Accommodate movement of support structure caused by thermal expansion and contraction. Allow for deflection and design for thermal stresses caused by temperature differences from one side of the panel to the other.
Specifier: Retain underlayment materials required for project.H. Self-Adhering, High-Temperature Underlayment:
Cold-appliedsheetunderlaymentminimum30mils(0.76mm)thick,consistingofslip-resistant,polyethylene-film top surface laminated to a layer of butylorSBS-modifiedasphaltadhesive,withrelease-paper backing. Provide primer when recommended by underlayment manufacturer for substrate.
I. FeltUnderlayment:Laminatedpolypropyleneandpolyethylenesheet,tear-resistant,UVresistant,manufactured with textured surface for slip resistance, meetingperformancerequirementsofASTMD226.
2.3 METAL ROOF PANELSA. Mechanically-seamed,ConcealedFastener,Metal
Roof Panels: Structural metal roof panel consisting of formed metal sheet with vertical ribs at panel edges, installed by lapping and mechanically interlocking edges of adjacent panels, and attaching panels to supports using concealed clips and fasteners in a weathertight installation.1. BasisofDesign:Metl-Span, LokSeam,
www.metlspan.com/lokseam.html.Specifier:MaterialdescriptionbelowcorrespondstoBIECInternational,Inc.http://galvalume.com/Galvalumesubstrate,available Prepainted from Metl-Span. Second paragraph belowdescribesGalvalumePluswithclearacryliccoatingforuse as exposed metallic finish.
2. Aluminum-ZincAlloy-CoatedSteelSheet:ASTMA792/A792M,structuralquality,Grade50,CoatingClassAZ50(Grade340,CoatingClassAZM150),prepainted by the coil-coating process per ASTM A 755/A755M.
3. Aluminum-ZincAlloy-CoatedSteelSheet:ASTMA792/A792M,structuralquality,Grade50,Coating
LS-18REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
SPECIFICATIONSClassAZ55(Grade340,CoatingClassAZM165)unpaintedGalvalumePluscoating.
Specifier: Prior to selecting metal thickness and panel thicknessbelow,consultmanufacturer’sspantablesandreview selection against panel thickness requirements and span condition. Select appropriate panel configuration to meet requirementsofdesignwindpressure.Important:Consultthisdocument when specifying gauge with the intent that it meet a prescriptive decimal thickness requirement in addition to strengthperformancerequirements.(ClickHeretoView)
a. NominalCoatedThickness:[26gage][24gage][22gage].
b. PanelSurface:[Smoothwithstriationsinpan][Stuccoembossedwithstriationsinpan].
c. ExteriorFinish:[Modifiedsilicone-polyestertwo-coatsystem][Fluoropolymertwo-coatsystem][Fluoropolymertwo-coatmetalliccolorsystem][ExposedGalvalumePluscoating].
d. Color:[Asindicated][AsselectedbyArchitectfrommanufacturer'sstandardcolors][MatchArchitect'scustomcolor].
4. PanelWidth:[12inches(305mm)][16inches(406mm)][18inches(457mm)].
5. PanelSeamHeight:1.75inch(44.4mm).6. JointType:Snapjoint-seamed.
Specifier: Add underlayment materials if required for project. Metl-SpanLokSeamisawatertighttestedpanelthatdoesnotrely upon underlayment materials for waterproofing. Retain slip sheet when recommended by manufacturer for separating metal panels from underlayment or substrate materials.
2.4 METAL ROOF PANEL ACCESSORIESA. General:Providecompletemetalroofpanel
assembly incorporating trim, copings, fasciae, gutters and downspouts, and miscellaneous flashings, in[manufacturer'sstandardprofiles][profilesasindicated].Providerequiredfasteners,closurestrips,thermal spacers, splice plates, support plates, and sealantsasindicatedinmanufacturer'swritteninstructions.
B. FlashingandTrim:Matchmaterial,thickness,andfinish of metal panel face sheet.
C. PanelClips:ASTMC645,withASTMA653/A653M,G90(Z180)hot-dipgalvanizedzinccoating,configured for concealment in panel joints, and identical to clips utilized in tests demonstrating compliance with performance requirements.
D. PanelFasteners:Self-tappingscrewsandother acceptable corrosion-resistant fasteners recommendedbyroofpanelmanufacturer.Whereexposed fasteners cannot be avoided, supply fastenerswithEPDMorneoprenegaskets,withheadsmatching color of metal panels by means of factory-applied coating.
E. JointSealers:Manufacturer'sstandardorrecommended liquid and preformed sealers and
tapes, and as follows:1. Factory-AppliedSeamSealant:Manufacturer's
standard hot-melt type.2. TapeSealers:Manufacturer'sstandardnon-curing
butyltape,AAMA809.2.3. ConcealedJointSealant:Non-curingbutyl,AAMA
809.2.Specifier: Retain one or more of the following four optional paragraphs as required by Project.
F. SteelSheetMiscellaneousFramingComponents:ASTMC645,withASTMA653/A653M,G60(Z180)hot-dip galvanized zinc coating.
G.RoofAccessories:Approvedbymetalroofpanelmanufacturer.RefertoSection077200"RoofAccessories"forrequirementsforcurbs,equipmentsupports, roof hatches, heat and smoke vents, ventilators, and preformed flashing sleeves.
H. SnowGuards:Approvedbymetalroofpanelmanufacturer.RefertoSection077253"SnowGuards"forrequirementsforsnowguardsattachedtometal roof panels.
2.5 FABRICATIONA. General:Providefactoryfabricatedandfinished
metal panels and accessories meeting performance requirements, indicated profiles, and structural requirements.
B. Fabricatemetalpaneljointsconfiguredtoacceptfactory-applied sealant providing weathertight seal and preventing metal-to-metal contact and minimizing noise resulting from thermal movement.
C. Formpanelsincontinuouslengthsforfulllengthofdetailed runs, except where otherwise indicated on approved shop drawings.
D. SheetMetalFlashingandTrim:Fabricateflashingandtrimtocomplywithmanufacturer'swritteninstructions, approved shop drawings, and project drawings. Form from materials matching metal panel substrate and finish.
2.6 FINISHESA. Finishes,General:Prepare,pretreat,andapply
coating to exposed metal surfaces to comply with coatingandresinmanufacturers'writteninstructions.
Specifier: Retain one or more of the following three finish paragraphsasapplicabletotheproject.CoordinatewithWarrantyarticleinPart1.
B. ModifiedSilicone-PolyesterTwo-CoatSystem:0.20–0.25milprimerwith0.7–0.8milcolorcoat[,meetingsolarreflectanceindexrequirements].1.BasisofDesign:Metl-Span,Signature200.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-19
LokSeam®
SPECIFICATIONSSpecifier:Metl-Span'sfluoropolymercoatingsarebasedonArkema,Inc.Kynar500andSolvaySolexisHylar500PVF2resins. Retain optional requirement for solar reflectance index whenrequiredforproject;coordinatewithselectedcolor.
A. FluoropolymerTwo-CoatSystem:0.2–0.3milprimerwith0.7-0.8mil70percentPVDFfluoropolymercolorcoat,AAMA621[,meetingsolarreflectanceindexrequirements].1. BasisofDesign:Metl-Span,Signature300.
B. FluoropolymerTwo-CoatMetallicSystem:0.2–0.3milprimerwith0.7-0.8mil70percentPVDFmetallicfluoropolymercolorcoat,AAMA621[,meetingsolarreflectanceindexrequirements].1. BasisofDesign:Metl-Span,Signature300
Metallic.C. InteriorFinish:0.5miltotaldryfilmthickness
consisting of primer coat and wash coat of manufacturer'sstandardlight-coloredacrylicorpolyester backer finish.
PART 3 - EXECUTION3.1 EXAMINATION
A. Examinemetalpanelsystemsubstrateandsupportswith Installer present. Inspect for erection tolerances and other conditions that would adversely affect installation of metal panel installation. 1. Inspectmetalpanelsupportsubstratetodetermine
if support components are installed as indicated onapprovedshopdrawings.Confirmpresenceofacceptable supports at recommended spacing to match installation requirements of metal panels.
2. PanelSupportTolerances:Confirmthatpanelsupports are within tolerances acceptable to metal panel system manufacturer but not greater than the following:a. 1/4inch(6mm)in20foot(6.1m)inany
direction.b. 3/8inch(9mm)overanysingleroofplane.
B. Correctout-of-toleranceworkandotherdeficientconditions prior to proceeding with insulated metal roof panel system installation.
3.2 PREPARATIONA. Miscellaneous Supports: Install subframing,
girts, furring, and other miscellaneous panel supportmembersaccordingtoASTMC754andmanufacturer'swritteninstructions.
Specifier:Retainparagraph(s)belowformetalroofpanelsappliedoversolidroofsheathing.Retain"Self-AdheringSheetUnderlayment"or"FeltUnderlayment"Paragraphbeloworretain both if required.
B. Self-AdheringSheetUnderlayment:Applyinaccordancewithunderlaymentmanufacturer'swritteninstructions;applyprimerifrequired.Applyatlocations indicated below. Roll laps with roller. Retain
one of two subparagraphs below.1. Applyovertheentireroofsurface.2. Applyovertheroofareaindicatedbelow:
a. Roof perimeter for a distance up from eaves of 24inches(610mm)beyondinteriorwallline.
b. Valleys,fromlowestpointtohighestpoint,foradistanceoneachsideof18inches(460mm).
c. Rakeedgesforadistanceof18inches(460mm).
d. Hips and ridges for a distance on each side of 18inches(460mm).
e. Roof-to-wall intersections for a distance from wallof18inches(460mm).
f. Around roof penetrating elements for a distance fromelementof18inches(460mm).
C. FeltUnderlayment:Applyatlocationsindicatedbelow,inaccordancewithunderlaymentmanufacturer'swritten instructions.
Specifier: Retain one of two subparagraphs below or delete bothifindicatedonDrawings.
1. Applyovertheentireroofsurface.2. Applyonareaofroofnotcoveredbyself-adhering
sheetunderlayment.Lapoveredgesofself-adheringsheetunderlaymentnotlessthan6inches(150mm).
Specifier:Retain"SlipSheet"Paragraphbelowifrequired.D. Flashings:Provideflashingsasrequiredtocomplete
metal roof panel system. Install in accordance with Section076200"SheetMetalFlashingandTrim"andapproved shop drawings.
3.3 METAL PANEL INSTALLATIONA. Snap-Joint-Seamed,StandingSeamMetalRoof
Panels: Install weathertight metal panel system in accordancewithmanufacturer'swritteninstructions,approved shop drawings, and project drawings. Install metal roof panels in orientation, sizes, and locations indicated, free of waves, warps, buckles, fastening stresses, and distortions. Anchor panels and other components securely in place. Provide for thermal and structural movement.
B. Attachpanelstosupportsusingclips,screws,fasteners, and sealants recommended by manufacturer and indicated on approved shop drawings.1. Fastenmetalpanelstosupportswithconcealed
clips at each location indicated on approved shop drawings, with spacing and fasteners recommended by manufacturer.
2. SnapJoint:Neststandingseamsandfastentogether by interlocking and completely engaging factory-applied sealant.
3. Provideweatherproofjacksforpipeandconduitpenetrating metal panels of types recommended by manufacturer.
4. DissimilarMaterials:Whereelementsofmetal
LS-20REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
SPECIFICATIONSpanel system will come into contact with dissimilar materials, treat faces and edges in contact with dissimilar materials as recommended by manufacturer.
3.4 ACCESSORY INSTALLATIONA. General:Installmetalpaneltrim,flashing,and
accessories using recommended fasteners and joint sealers, with positive anchorage to building, and with weather tight mounting. Provide for thermal expansion.Coordinateinstallationwithflashingsandother components.1. Installcomponentsrequiredforacompletemetal
panel assembly, including trim, copings, flashings, sealants, closure strips, and similar items.
2. Complywithdetailsofassembliesutilizedto establish compliance with performance requirementsandmanufacturer'swritteninstallation instructions.
3. Provideconcealedfastenersexceptwherenotedon approved shop drawings.
4. Setunitstruetolineandlevelasindicated.Installwork with laps, joints, and seams that will be permanently weather resistant.
B. JointSealers:Installjointsealerswhereindicatedandwhere required for weathertight performance of metal panelassemblies,inaccordancewithmanufacturer'swritten instructions.1. Preparejointsandapplysealantsperrequirements
ofDivision07Section"JointSealants."
3.5 FIELD QUALITY CONTROLSpecifier: Retain paragraph below when scope and complexity of metal roof panel installation justifies independent inspection and testing provisions.
A.TestingAgency:[Ownerwillengage][Engage]anindependent testing and inspecting agency acceptable to Architect to perform field tests and inspections and to prepare test reports.
3.6 CLEANING AND PROTECTIONA. Remove temporary protective films immediately in
accordancewithmetalroofpanelmanufacturer'sinstructions.Cleanfinishedsurfacesasrecommended by metal roof panel manufacturer.
B. Replacedamagedpanelsandaccessoriesthatcannotbe repaired to the satisfaction of the Architect.
END OF SECTION
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-21
LokSeam®
GENERAL INFORMATION
18"
16"
12"
COLOR
SPECIFY ANGLE
95°120°
5¹⁄₂"
1¹⁄₄"
1" 2¹⁄₂"
¹⁄₂"
¹⁄₄"
³⁄₈" ¹⁄₂"
Ridge Flash for Vent
Ridge Flash for Vent
• For use with vent material
• For use with vent material
T-5089 q FL-540 q
5"3⅞"
1¾"
2¼"
PRODUCT CHECkLISTLokSeam® Panel
Clips Bearing PlateStandard
Back-Up Plate Floating Rake Support
• 16-gaugeredoxide• For use with rigid-
board insulation
• 20'Length• 14-gaugeredoxide• Factory slots
• For use at ridge and endlaps
• Prepunched• 16-gaugeredoxide
P-140 q
P-141 q
HW-7500 q
HW-4680 q
UL90-HW-6400 q
Standard-HW-6200 q
HW-776218" qHW-776616" qHW-776412" q
q q q
NOTE:Alltrimtobe24-gaugematerialunlessnoted
6½"
SPECIFY ANGLE
COLOR
Specify Roof Pitch
Ridge/Hip Flash, Fixed
Support Plates
Floating Ridge/Hip
Fixed Ridge
T-5075 q
2½"4"
SPECIFY ANGLE
120°120°
1¹⁄₄"
Ridge Flash, Floating
T-5087 q
SPECIFY ANGLE
COLOR10¼"
⅝"
5" 135°
Specify Roof Pitch
Peak Cap
T-5085 q
5"
COLOR
90°
135°
⅝"
4"Box Rake
T-5235 q
SPECIFY ANGLE
10¹¹⁄₁₆”
1”
SPECIFY ANGLE
11 ¹¹⁄₁₆ "
LS-22REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
GENERAL INFORMATIONPRODUCT CHECkLIST
NOTE:Alltrimtobe24-gaugematerialunlessnoted
T-5151 q
SPECIFYANGLE
3"
⅝"
4"1 ¼"
COLOR
COLOR
SPECIFYANGLE
1" OPEN HEM
⅝"3"
1 ½"
2 ½
Eave Trimw Drip Edge
1"
6"
3" ⁵⁄₈"
⁵⁄₈" ¹⁄₂" ¹⁄₂"
4¹⁄₂"
5¹⁄₂"
SPECIFYANGLE
TO BE DETERMINEDBASED ON SLOPE
Snow Gutter
(PleaseInquire)
8"
2"
Gutter Strap
T-5281 q
4"SPECIFYANGLE
"A"
COLOR
T-5213q
Parapet High Side Eave Flash-Fixed
T-5211q
4"
2 ½"
1¼"
SPECIFYANGLE
4 ¾"
COLOR
Parapet High Side Eave Flash-Floating
T-5215q
COLOR
3½"
1"
OPENHEM
4¼"
90°
Parapet Rake Flash
T-5217 q
Parapet Rake Cleat
1"
1"COLOR
90°
T-5219 q
FILE:EAVE TRIM
3 ½"
"A"
⅝"
SPECIFYANGLE
COLOR
Eave Trim
T-5141q
5½" 4½"
1"⅝"
5¼"
6"
SPECIFYANGLE
COLOR
Box Gutter
T-5261 q
Specify Roof Pitch Specify Roof Pitch
Box Gutter w/Drip Edge
5½" 4½"
1"⅝"
5½"
6"
SPECIFYANGLE
COLOR
1½"
T-5271q
Gutter End
T-5291q
T-5093 q
SPECIFY ANGLE
45°
2"
11" 11"
COLOR
Standard30' or less
SPECIFY ANGL E
45°
2"
22" min. 22" min.
COLOR
ExtendedMore than 30'
Valley Trim - Standard Valley Trim - Extended
T-5097 q
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-23
LokSeam®
GENERAL INFORMATIONPRODUCT CHECkLIST
Rib Cover
Tape Sealer Tape Sealer
Perforated Vent Drip
Panel Hemming ToolMetal Vent Material
Continuous Cleat
Tube Sealant
Triple Bead
Tri-Bead Triple Bead
Tri-Bead
1"
3¼" 1"
½"
1 "
PERFORATED 135°
2½" ½"
• For use at eave, ridge, and endlaps
• Paintable• Urethane
• For use at valleys with through fasteners
HW-540—WHITE q HW-541—GRAY q
HW-544—ALMOND q HW-542—MED.BRONZE q
FL-254 q
HW-525 q
HW-502 q
T-5121 q
HW-602 qFL-565 q
HW-504 q
90°
1"
30°
COLOR
2½"
½"
Counterflash
T-5255 q
1½"
⅛"1½"
½"
Offset Cleat
T-5131 q
1"
1¾"
1"
COLOR
Zee Closure
T-5014 q
1"
⅝"
150°
½"
¾"
COLOR⅝"
120°
150°
Alternate Counterflash
T-5221q
LS-24REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
GENERAL INFORMATION
NOTE:Alltrimtobe24-gaugematerialunlessnoted
PRODUCT CHECkLISTFastener #1E
¼"-14x1¼"LongLifeDriller5⁄16"HexWasherHeadwith sealing washer
¼"-14x⅞"LapTek5⁄16"HexWasherHeadwith⅝"O.D.washer
¼"-14x1¼"ShoulderTek25⁄16"HexWasherHeadnowasher ¼"x1¼"NailDriveMasonryAnchor
12-11x1"PancakeHeadwith#3DrillPoint#2QuadrexDrive
12-11x1"PancakeHeadTypeA#2QuadrexDrive
Fastener #4
Fastener #12A
Fastener #5 Fastener #11
Fastener #13A
• Panel to eave strut• Standard endlap• Panel to valley plate (fixed)
• Floating Rake or Parapet Rake
• Rake support to purlin
• zee closure to panel atridge(withoutback-upplate)
q q
q
q
q
q
• Parapet rake flash to masonry parapet wall
• Cliptoplywood• zee closure to plywood• Offset cleat to plywood
• Cliptopurlin• Offset cleat/panel
starter to eave strut or valley plate
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-25
LokSeam®
GENERAL INFORMATION
NOTE:Alltrimtobe24-gaugematerialunlessnoted
PRODUCT CHECkLISTFastener #14
⅛"x0.337"PopRivetstainless steel
⅛"x0.525"PopRivetstainless steel
14x4"DeckScrewDriller#3PhillipsTrussHead
12x24x1¼"#2QuadrexDrive
Fastener #211
Fastener #16
Fastener #14A
Fastener #210
Fastener #15D
• zeeClosuretoangleat floating hip
• Trim to trim• Trim to panel
• For clip attachment in a composite roof assembly
• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications
• Lengthtobedeterminedby insulation thickness and metal deck depth
• For clip attachment in a composite roof assembly
• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications
• Lengthtobedeterminedby insulation thickness and metal deck depth
• For clip attachment in a composite roof assembly
• Fastens clip and bearing plate to metal deck in rigid board insulation over metal deck applications
• Lengthtobedeterminedby insulation thickness and metal deck depth
• Cliptojoist• Offset cleat/panel
starter to joist
q
q
q
q
q
q
14x3"DeckScrew#3PhillipsTrussHead
14x6"DeckScrew#3PhillipsTrussHead
LS-26REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
GENERAL INFORMATION
WhenorderingLokSeam® panels without technical assistance from Metl-Span, the following must be provided:
1. PanelLength-Thelengthofeachpanelshouldincludetheproperoverhangattheeave,endlap,andpeakasrequired. Refer to specific details in this manual for the proper overhang at these locations. Add 1½" to the panel length for all panels to be hemmed as shown on page LS-35.
2. PanelDesignations-Eachpanelmusthaveadesignationtobeproperlymanufactured. Thesedesignationsare:Blank,Peak,MidandEave.
3. Panelsmaybespecifiedas:“Notched”forfoldinghemateave.Add3”topanellength.Iffactorynotchingisrequested,
panelswillbenotched1½"atbothends.Note: Notching is only available for Blank Panels.
4. 16"widepanelscanbeswagedbutnotprepunched.
5. If you are using an endlap with an offset cleat as shown on pages LS-37 and LS-53, you must also specify that the panels not be prepunched. Panels will still be swaged as normal. If your specific detail is not in this manual or if you have questions concerning panel length, designation, or product application, call your Metl-Span sales representative.
INSTALLATION GUIDELINES I. Pre-Order
A. Prior to ordering panels, all dimensions should be confirmed by field measurement.
II.JobsiteStorageandHandlingA.Checktheshipmentagainsttheshippinglist.B.DamagedmaterialmustbenotedonBillofLading. C.Panelcratesshouldbehandledcarefully.Aspreaderbarofappropriatelengthisrecommendedforhoisting.D.Checktoseethatmoisturehasnotformedinsidethebundlesduringshipment.Ifmoistureispresent,panels
should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels.
III.ApplicationChecklistA.Checksubstructureforproperalignmentanduniformitytoavoidpaneldistortion.B.Periodiccheckofpanelalignmentiscrucialtoproperpanelalignment. C.Ifthereisaconflictbetweenthismanualandtheerectiondrawings,theerectiondrawingswilltakeprecedence.
ORDERING INFORMATION
BLANK
FEMALE
MALE
FEMALE
MALEEAVE
4½"
MID
1½"
PEAK
THREE OR MORE PANELS FROM EAVE TO PEAK
ONE PANEL FROM EAVE TO PEAK
MORE THAN ONE PANEL FROM EAVE TO PEAKMORE THAN ONE PANEL FROM EAVE TO PEAK
DOWN SLOPE 1½"
FEMALE
MALE
DOWN SLOPE
FEMALE
MALE
DOWN SLOPE
SWA
GED
EN
D
SWA
GED
EN
D
4½"
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-27
LokSeam®
GENERAL INFORMATION
1. A single pitch eave strut must be used with the LokSeam® Roof System.
2. Make sure a rake angle or an alternate structural flat surface has been installed on top of the purlins to accept the“RakeSupport”.
3. The walls do not have to be erected before the roof is installed. However, for the purpose of this manual, we have assumed that the wall panels have been installed.
4. Thesubstructure(eavetoridge)mustbeonplanetoleranceof¼"in20'and⅜"in40'.
5. It is critical that the purlins or bar joists at the ridge and endlaps be located exactly as detailed and that they are straight from rafter to rafter. Any mislocation or bowing of these members can cause the fasteners at the ridge or endlaps to foul as the panels expand and contract.
6. PeakPurlinSpacing-FloatingRidge:18"(9"fromcenterlineofridgetowebofpurlin).-FixedRidge:10"(5"fromcenterlineofridgetowebofpurlin).
7. Metl-Span can furnish LokSeam®roofpanelsin18",16"and12"widths.However,forthepurposeofthismanual,wehaveassumedthattheroofpanelswillbe18"wide.
PREPARATORY REQUIREMENTS
CAUTIONApplication and design details are for illustration purposes only, and may not be appropriate for all environmental conditions or building designs. Projects should be engineered to conform to applicable building codes, regulations, and accepted industry practices.
CAUTIONDiaphragmcapabilitiesandpurlinstabilityarenotprovidedbyMetl-Span’sLokSeam® roof system. Therefore, other bracing may berequiredtoconformtoA.I.S.C.orA.I.S.I.specifications.
LS-28REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
GENERAL INFORMATION
CAUTIONImproper unloading and handling of bundles and crates may cause bodily injury or material damage. The manufacturer is not responsible for bodily injuries or material damages during unloading and storage.
5' Minimum
RIGHT WAY
RIGHT WAY
WRONG WAY
WRONG WAYX
X
UNLOADING
Upon receiving material, check shipment against shipping list for shortages and damages. Metl-Span will not be responsible for shortages or damages unless they are noted on the shipping list.
Each bundle should be lifted at its center ofgravity.Wherepossible,bundlesshouldremainbanded until final placement on roof. If bundles must be opened, they should be retied before lifting.
When liftingbundleswithacrane,aspreaderbar and nylon straps should be used. NEVER USE WIRE, ROPE OR CHAIN SLINGS, THEY WILL DAMAGE THE PANELS.
When liftingbundleswitha forklift, forksmustbeaminimumoffivefeetapart.Donottransportopen bundles. Drive slowly when crossingrough terrain to prevent panel buckling.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-29
LokSeam®
GENERAL INFORMATIONUNLOADING(continued)
BLOCk AND BAND WITH CARDBOARD CARTON
This method of bundling is used for orders that are to be picked up by the customer or shipped bycommoncarrier.2x4’sarestrappedunderthe cartons to allow access for straps or a forklift. Bundles less than 25' long may behandled by a forklift. The forklift should have at least5'between forks.Cartons longer than25'shouldbeliftedutilizingaspreaderbarwithnylon straps.
FULL CRATE
This method is used on all overseas shipments orbycustomer’sorder.Handlingrequirementsare the same as block and band.
LS-30REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
GENERAL INFORMATION
NOTEProtective gloves should always be used while handling panels. OSHA safety regulations must be followed at all times.
10' to 12'
10' to 12'
5'
RIGHT WAY
WRONG WAY
HANDLING/ PANEL STORAGE
Standing on one side of the panel, lift it by the seam. If the panel is over 10' long, lift it withtwo or more people on one side of the panel to prevent buckling.
Donotpickpanelsupbytheends.
Store bundled sheets off the ground sufficiently high to allow air circulation beneath bundle and to prevent rising water from entering bundle. Slightly elevate one end of bundle. Prevent rain from entering bundle by covering with tarpaulin, making provision for air circulation between draped edges of tarpaulin and the ground.
PROLONGED STORAGE OF SHEETS IN A BUNDLE IS NOT RECOMMENDED. If conditions do not permit immediate erection, extra care should be taken to protect sheets from white rust or water marks.
Check to see that moisture has not formedinside the bundles during shipment. If moisture is present, panels should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-31
LokSeam®
DETAILS
Metl-Span recommends that only one-piece .080 Aluminum (Min.) roof curbs be used with the LokSeam® roof system. The roof curb will be installed under the roof panels on the upslope end and over the panels at the downslope end. To accomplish this, the roof panels must be endlapped at the upslope and downslope end of the curb. This allows both ends of the curb to shed water and places the heavier gauge metal of the curb under the roof panels for better resistance to foot traffic. The exception is at the downslope end where the curb is on top of the roof panels. Since there are endlaps at this area, back-up plates provide support.
Outsidecapcells(forbottom)areusedtosealthe panel to the roof curb. If the curb must be located in a precise location, order the cap cells loose for field installation.
For the purpose of these instructions, a curb with a factory attached cap cell is illustrated. Panels are assumed to be blank and installed right to left.
ROOF CURB INSTALLATION INSTRUCTIONS
CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.
DECKSCREW(2)PERCLIP(MIN. ³⁄₄"PENETRATION
INTOMETALDECK)
VAPORBARRIER(NOT BYMetl-Span)
FIELDNOTCHANDREMOVERIGIDINSULATION
RIGIDINSULATION(NOT BYMetl-Span)
BEARINGPLATE
METALDECK(NOT BYMetl-Span)
1½"
4½"
TRI-BEAD TAPESEALER
LOWERSWAGEDLokSeam® PANEL
UL90CLIP
BACK-UPPLATE
FASTENER#1E6 "
UPPERLokSeam®
PANEL
LS-32REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
Full length panels may be installed up to the curb location. All panel runs affected by a roof curb must have field endlaps at the upslope and downslope end of the curb. Provision must be made for this condition by ordering two panels12" longer than thepanels immediatelyadjacent to the curb. The panels do not need to be ordered with pre-punched holes. Install all bottom panels, engaging backup plates and apply triple bead tape sealer to each panel as it is being installed. It is critical that the tape sealer be installed across the full panel width. Failure to follow this procedure will cause the curb to leak during rains coupled with high winds.
The first downslope panel immediately adjacent to the last full length panel will require field notchingof the female leg foradistanceof6".Notch the panel just above the lock in the female leg. The remaining portion of the female leg will needtobecrimpedwith“duckbill”visegrips.
The last downslope panel immediately adjacent to the first full length panel after the curb will require field notching of the male leg for a distance of 6". Notch the panel by removingthe male “lock” leg only. Apply two beads ofurethane sealant vertically to the downslope end of the notch.
ROOF CURB INSTALLATION INSTRUCTIONS (continued)
DIRECTION OFPANEL INSTALLATION
R OOF SLOPE
BACK-UP PLATE TRIPLE BEADTAPE SEALER
FRAMING OMITTED FOR CLARITY
FULL LENGTH PANEL
FRAMINGOMITTED FORCLARITY
URETHANE SEALANT
6"
FIELD NOTCH PANEL
FIELD NOTCH AND CRIMP WITH "DUCKBILL" VISE GRIPS
6”
ROOF SLOPE
TRIPLE BEADTAPE SEALER
TRIPLE BEADTAPE SEALER
TRIPLE BEADTAPE SEALER
DIRECTION OF PANELINSTALLATION
FASTENER #1E
CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-33
LokSeam®
DETAILS
Install curb on top of bottom panels and curb support framing.Whenusinga loose cap cell,the curb flange must be notched out to accept the panel rib. Apply triple bead tape sealer to the sides and upslope end of curb. Fasten the downslope end of curb to the bottom roof panels andback-upplateswithFastener#1Eat3"o.c.Fasteners must go through the tape sealer.
Install the top run of panels cutting the panels at each side of the curb to fit. Apply urethane sealant to seams of all panels on the upslope end of the curb.Endoftoppanelsshouldbeaminimumof12"fromthepointofthewaterdiverter.Thetoppanelshouldlapontothecurb6".
Install cinch straps at sides of curb to form a compression seal (cinch straps not by Metl-Span)FastencinchstrapsandtoppanelswithFastener#1Eat3"o.c.Fastenersmustgothrough the triple bead tape sealer.
Full length panels may now once again be used.
ROOF CURB INSTALLATION INSTRUCTIONS (continued)
ROOF SLOPE
12" MIN
DIRECTION OFPANELINSTALLATION
FIELD CUT PANELTO FIT CURB
FIELD CUTPANEL TOFIT CURB
FLAT CINCHSTRAP
FRAMINGOMITTED FORCLARITY
URETHANE SEALANT
6"
FIELD NOTCH PANEL
FIELD NOTCH AND CRIMP WITH "DUCKBILL" VISE GRIPS
6”
ROOF SLOPE
TRIPLE BEADTAPE SEALER
TRIPLE BEADTAPE SEALER
TRIPLE BEADTAPE SEALER
DIRECTION OF PANELINSTALLATION
FASTENER #1E
½"
SLOPE
DIRECTION OF INSTALLATION TRIPLE BEAD
TAPE SEALER
ROOF CURB
CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.
LS-34REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
1. LokSeam® Panel2. Urethane Sealant3. Outside Cap Cell4. Back-up Plate5. Fastener #1E6. Tri-bead Tape Sealer7. Roof Curb Made From Structural
Aluminum (Min. .080 Thickness)8. Water Diverter9. Panel Fins (to be cut from panel length
equal to length of curb).
Whenorderingcurbs,specifyone-piececurbsas shown on this page.
ROOF CURB INSTALLATION INSTRUCTIONS (continued)
87
6
5
4
3
2
1
56
6"12" MIN.
18" MIN.
3
97
8
1
5
ROOF SLOPE
DIRECTION OFPANEL INSTALLATION
REMOVE 6" OF MALELEG (LOCK ONLY)
NOTCH FEMALE LEGOF LOWER PANEL
CAUTIONIt is the user’s responsibility to ensure that openingscut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-35
LokSeam®
DETAILS
NOTES:1.Fieldnotchmaleandfemalelegsofpanel1½".(Factorynotchingisavailable,callMetl-Span)2.Engagepanelhemmingtoolontoprotrudingpanel.3.Bendpaneldowntoformanopenhem.4.Hemmaybetightenedwithapairofvisegrip“duckbills.”5.Panel engagement shown above is for panel runs up to 100' long. For panel runs over 100' long, please call Metl-Span.
1½"
FIELD NOTCH
PANEL HEMMINGTOOL
PANELHEMMING TOOL
PANELHEMMING TOOL
1½"
1½"
½"
½"
1"
FORMINGOPEN HEM
ENGAGINGHEMMING TOOL
NOTCHINGPANEL END
PANELENGAGEMENT
LokSeam® PANEL
LokSeam® PANEL
LokSeam® PANEL
FIELD HEMMING PANEL END
LS-36REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
PANEL CLIP
FACTORY MASTIC
PANEL CLIP
FILL ENDWITH URETHANE
SEALANT
FACTORY MASTIC
LokSeam® PANEL
INSTALLED PANELCROSS SECTION
PANEL CLIPINSTALLATION
PANEL END SEALANT DETAIL
PANEL
NOTES:1.Fillendofpanelseamateaveandvalleyswithurethanesealant.2.ForUL90rating,UL90clipswithtwofastenersmustbeused.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-37
LokSeam®
DETAILS
2 4 53 1
1½"
4½"
1 0 "
TRI-BEAD TAPE SEALER
LOWER SWAGED LokSeam® PANEL
UL 90 CLIP
PURLIN
BACK-UP PLATE
FASTENER #12
OFFSET CLEAT
LOWER SWAGED LokSeam® PANEL
BA CK-UP PLA TE
PRE-PUNCHED PANEL HOLES
LOWER SWAGED LokSeam® PANEL
FASTENER #12 4" O. C.
UPPER LokSeam® PANEL
6"
"
FASTENER #1E
6 "
FASTENER #1E
3
UPPER LokSeam®
PANEL
UPPER LokSeam®
PANEL
CROSS SECTIONOF STANDARDENDLAP
ENDLAPINSTALLATIONSEQUENCE
CROSS SECTIONOF ALTERNATE ENDLAP
FASTENER SEQUENCE(FOR STANDARD ENDLAP ONLY)
ENDLAPOVER PURLINS
NOTES:1.A UL 90 rating is not available on roofs over open framing with endlaps.2.Installbottompanelsothattheeavehastheproperoverhang(refertoeavedetails).Theswaged,upslopeendofthepanelshould
be10"fromthewebofthepurlin.3.Slideaprepunchedback-upplateontotheendofthepanel;makesuretheteethontopoftheback-upplateareontopofthepanel.
Visuallychecktoseethattheholesintheback-upplatealignwiththeprepunchedholesinthepanel4.PlaceTri-Beadtapesealerovertheentirewidthofthepanel.Itmustbecentereddirectlyovertheprepunchedholes.5.Usinganawltoaligntheholes,installtoppanelbylappingitovertheswagedportionofthebottompanel.InstallFastener#1Ein
the prepunched holes in the proper sequence.6.Endlapsrequirerooferectiontoproceedfromlefttorightasviewedfromtheeavelookingtowardtheridge.7. When using the alternate endlap method, LokSeam® panels should be ordered without the prepunched endlap holes.
Panels will be swaged as normal. Order the upper endlap panel 1½" longer than normal for the panel hem. See Page LS-26 for ordering information.
8. When using the alternate endlap detail, use the offset cleat method of attachment at the eave or valley and the fixed detail at the ridge or hip.
LS-38REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
4"FIXED RIDGE/HIPFLASH
2" 9"
TRI-BEADTAPE SEALER
FLOATING RIDGE/HIPFLASH
ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)
MIN 16-GA.SUPPORT PLATE
URETHANE SEALANT
2" x 2" x 16-GA.ANGLE (CONT.)
4" 9"
FASTENER#12
UL 90 CLIP
CROSS SECTIONOF FIXED HIP
CROSS SECTIONOF FLOATING HIP
TRI-BEADTAPE SEALER
ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)
UL 90 CLIP
MIN 16- GA.SUPPORT PLATE
URETHANE SEALANTIMPORTANT NOTE:TEMPORARILY SECUREPANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED LokSeam®
PANEL
LokSeam®
PANEL
FASTENER #14A4" O.C.
FASTENER #12
FASTENER #176" O.C.
FASTENER #14A4" O.C.
FASTENER #14A4" O.C.
2"
HIPOVER PURLINS
NOTES:Fixed Hip
1.Do not use this detail with the fixed eave or valley details.2.Installhipsupportplate,notchingdownturnedlegatpurlinlocations.3.Bevelcutandinstallpanelstofollowslopeofhip.4.InstallTri-Beadtapesealertopansofpanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromthecenterofthehip.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe4"fromcenterofhip.
Floating Hip1.Do not use this detail with the floating eave or valley details.2.Installhipsupportplate,notchingdownturnedlegatpurlinlocations.3.Bevelcutandinstallpanelstofollowslopeofhip.4.InstallTri-Beadtapesealertopanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromcenterofhip.5.Slidealengthof2"x2"x16-gaugeangleunderthepanels.Do not fasten 2" x 2" angle to hip support plate. This will restrain
the panels from floating.6.Bevelcutandinstallzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"
from center of hip. Seal sides and top of zee closures to panel seams with urethane sealant.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-39
LokSeam®
DETAILS
9 " 2"
2"
URETHANE SEALANT
FLOATING RIDGE FLASH
UL 90 CLIP
PURLIN ZEE CLOSURE
BACK-UP PLATE
LokSeam®
PANEL TRI-BEADTAPE SEALER
FASTENER #14 6" O. C.
FASTENER #12 FASTENER #17 6" O. C.
FLOATING RIDGE
RIDGEOVER PURLINS
NOTES:Floating Ridge
1.Do not use this detail with a floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.7.AttachridgeflashtozeeclosurewithFastener#4at6"o.c.
Fixed Ridge1.Use this detail with a fixed eave or valley detail.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.6.AttachridgeflashtozeeclosurewithFastener#4at6"o.c.
12"
2" 2"
RIDGE TRIM
PURLIN ZEE CLOSURE
RIDGE PLATE
LokSeam®PANEL
TRI-BEADTAPE SEALER
FASTENER #4 6" O. C.
FASTENER #12A FASTENER #1E 6" O. C.
URETHANE SEALANT
FIXED RIDGE
LS-40REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
9"2"
2"
TRI-BEADTAPE SEALER
FASTENER #12
RIDGE FLASH
UL 90 CLIP
PURLIN
ZEE CLOSURE
BACK-UPPLATE
RIDGE WITH METALVENT
RIDGE WITHPERFORATED VENT DRIP
LokSeam®
PANEL
FASTENER #4
FASTENER #17 6" O.C.
WEATHER FILTER
FASTENER #4 6" O. C.
9"
2"
PERFORATEDVENT DRIP
RIDGE FLASH FOR VENT
TRI-BEADTAPE SEALER
FASTENER #12 PURLINUL 90 CLIP
ZEE CLOSURE
FASTENER #4 6" O. C.
BACK-UP PLATE
2"
LokSeam®
PANEL
FASTENER #4 12" O. C.
FASTENER #17 6" O.C.
VENTED RIDGEOVER PURLINS
NOTES:Ridge With Metal Vent
1. Do not use this detail with floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosure.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Balance vent exhaust at ridge with vent intake at eave or soffit.
Ridge With Perforated Vent Drip1.Do not use this detail with floating eave or valley details.2.Ventedridgedetailshouldbeusedinconjunctionwithsoffitand/oreaveventstoprovidepropercirculationandtopreventweather
infiltration during high winds.3.Installback-upplateandzeeclosureasinNotes2-6above.4.AttachventdriptozeeclosureswithFastener#4at6"o.c.Seallapsinventdripwithurethanesealant.5.AttachridgeflashtoventdripwithFastener#4at6"o.c.
Metal vent material must have urethane sealant at all lap conditions.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-41
LokSeam®
DETAILS
NOTES:VALLEY WITH OFFSET CLEAT
1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panels must be attached to substructure at the ridge, high eave or hip to prevent them from sliding downslope.3.OffsetcleatisinstalledcontinuousalongslopeofvalleyoverTri-beadtapesealerwithFastener#12Aat1'-0"o.c.Fasteners must
go through tape sealer.4.Add 1½" to panel length for the panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.
CROSS SECTION OFFLOATING OVER PURLINS
OFFSET CLEAT
VALLEYTRIM
TRI-BEADTAPE SEALER
WOOD DECK
MOISTUREBARRIER
FASTENER #12 1'-0" O. C.
(FASTENER MUST GOTHROUGH TAPE SEALER)
LokSeam®
PANEL
WOOD DECK MOISTUREBARRIER
ISOMETRIC VIEW OF VALLEY
BEVEL CUT PANEL TO MATCH SLOPEOF VALLEY TRIM
VALLEY TRIM
6" OVERLAP
VALLEY TRIM
FASTENER #12
URETHANESEALANT
SUPPORT PLATE
TRI-BEADTAPE SEALER
LokSeam®
PANEL
FASTENER #12 1'-0" O. C.(FASTENER MUST GO THROUGTHTAPE SEALER)
OFFSET CLEAT
4½" or 9"9" Valley dimension must be used in valleys longer than 30'-0".
MOISTUREBARRIER
MIN 16- GASUPPORT PLATE
FLOATING VALLEYOVER PURLINS
LS-42REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:FIXED VALLEY
1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Do not use this detail with the fixed ridge or hip details.3.Endsofpanelsshouldbe4½"minimumfromtheverticallegofvalleytrim.4.InstallTripleBeadtapesealercontinuouslyunderLokSeam® panel.5.AttachpaneltosupportplatewithFastener#1Eat3"o.c.Fasteners must go through tape sealer under panel.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.
Valley must be designed to support the panels between the purlins.(ie: channel, angle or plate)
PURLIN
BEVEL CUT PANEL TO MATCH SLOPE OF VALLEY TRIM
VALLEY TRIM
FASTENER #1E
ISOMETRIC VIEW OF VALLEY
6" OVERLAP
VALLEY TRIM
FASTENER #12
URETHANESEALANT
SUPPORTPLATE
TRIPLE BEAD TAPE SEALER
FIXED VALLEY
TRIPLE BEAD TAPE SEALER
MIN 16-GA.SUPPORT PLATE
VALLEY TRIM
LokSeam®
PANEL
FASTENER #1E 4" O.C.(FASTENER MUSTGO THROUGH TAPE SEALER)
LokSeam®
PANEL
4½" or 9" 9" Valley dimension must be usedin valleys longer than 30'-0".
FIXED VALLEYOVER PURLINS
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-43
LokSeam®
DETAILS
NOTES:Floating High Eave
1.Do not use this detail with the floating eave or valley details.2.Installpanelandclips.3,Installbackupplateontoendofpanel.4.Fieldcutzeeclosurestofitpanelwidth.5.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe6"fromtheendofthepanel.6.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe6½"fromendofpanel.7.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.8.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.
Fixed High Eave1.Use this detail with a floating eave or valley detail.2.Installpanelandclips.3,Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1½"fromtheendofthepanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.7.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.
CROSS SECTIONOF FIXED EAVE
TRI-BEADTAPE SEALER
PEAK CAP ZEE CLOSURE
URETHANE SEALANT
HIGH SIDE EAVE STRUT
TRI-BEADTAPE SEALER WALL PANEL
EPDM CLOSURE
OPTIONAL CONTINUOUS CLEAT
FASTENER #14A 6" O.C.
FASTENER #14
FASTENER #1E@ 6” O.C.
2"
CROSS SECTION OFFLOATING HIGH EAVE
TRI-BEADTAPE SEALER
PEAK CAP
UL 90 CLIP
ZEE CLOSURE
URETHANE SEALANT
FASTENER #12
WALL PANEL
6½"
EPDM CLOSURE
FASTENER #14A 6" O.C.
FASTENER #14 FASTENER #17@ 6” O.C.
BACK-UP PLATE
HIGH EAVEOVER PURLINS
LS-44REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Eave with Offset Cleat
1.The offset cleat method of attachment should be used when ridge, high side eave or endlap is fixed to the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.
2.AttachoffsetcleattoeavestrutwithFastener#12Aat1'-0"o.c.3.Tofieldhempanel,seepageLS-31.4.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.
Eave with Drip Edge1.The eave with extended drip edge method of attachment should be used when ridge, high side eave or endlap is fixed to
the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.AttacheavetrimtoeavestrutwithFastener#14Aat2'-0"o.c.3.Tofieldhempanel,seepageLS-31.4.See “Panel End Sealant Detail” on page LS-32.
CROSS SECTION OF EAVE TRIM WITH OFFSET CLEAT
CROSS SECTION OF EAVE TRIMWITH EXTENDED DRIP EDGE
PANEL END DETAIL
OFFSET CLEAT
EAVE TRIM
EAVE STRUT
UL 90 CLIP
WALL PANEL
EPDM CLOSURE
UL 90 CLIP
EAVE STRUT EAVE TRIM
W/DRIP EDGE
EPDM CLOSURE
SEE PAGE LS-36 FOR PANEL ENGAGEMENT
PANEL END DETAIL SEE PAGE LS-36 FOR PANEL ENGAGEMENT
CONTINUOUSCLEAT
LokSeam® PANEL
FASTENER #14
FASTENER #14A
FASTENER #14
WALL PANEL
LokSeam® PANEL
FASTENER #12 1'-0" O. C.
FASTENER #12
FASTENER #14A
FASTENER #12
TRI-BEADTAPE SEALER
FLOATING EAVE WITH EAVE TRIMOVER PURLINS
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-45
LokSeam®
DETAILS
NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttacheavetrimtoeavestrutwithFastener#14A(3fastenersper10'piece).3.ApplyTri-Beadtapesealertoslopelegofeavetrim.Edgeoftapesealershouldalignwithedgeofeavestrut.4.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.5.See"PanelEndSealantDetail"onpageLS-32tosealpanelends.
PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT
EAVE TRIM
WALL PANEL
EAVE STRUT
OUTSIDE CLOSURE
OPTIONAL CONTINUOUSCLEAT
LokSeam® PANEL
FASTENER #14
FASTENER #14A
FASTENER #1E
TRI-BEADTAPE SEALER
FIXED EAVE WITH EAVE TRIMOVER PURLINS
FASTENER SPACING @ EAVE
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
LS-46REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Offset Cleat
1.The offset cleat method of attachment should be used when ridge, high eave or endlap is fixed to the substructure. 2.Panels must be attached at one of these points to prevent them from sliding downslope.3.AttachoffsetcleattoeavestrutwithFastener#12Aat1'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.6.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail
for these areas.
Gutter with Drip Edge1.The gutter with drip edge method of attachment should be used when ridge, high eave or endlap is fixed to the
substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.InstallguttertoeavestrutwithFastener#14Aat2'-0"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Thisdetailmaybeusedonroofswithpitchesof4:12orless.Forroofswithpitchesgreaterthan4:12,callMetl-Span.8.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail
for these areas.
CROSS SECTION OF GUTTER WITHDRIP EDGE
FASTENER #12 1'-0" O. C.
UL 90 CLIP
GUTTER STRAP
BOX GUTTER
OFFSET CLEAT
EAVE STRUT
WALL PANEL
UL 90 CLIP
GUTTER STRAP
BOX GUTTER W/DRIP EDGE EAVE STRUT
CROSS SECTION OF GUTTER WITHOFFSET CLEAT
PANEL END DETAIL SEE PAGE LS-35 FOR PANEL ENGAGEMENT
PANEL END DETAIL SEE PAGE LS-35 FOR PANEL ENGAGEMENT
LokSeam® PANEL
LokSeam® PANEL
WALL PANEL
FASTENER #14
FASTENER #14A FASTENER #14
FASTENER #12
FASTENER #12
TRI-BEADTAPE SEALER
FLOATING EAVE WITH GUTTEROVER PURLINS
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-47
LokSeam®
DETAILS
NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertoeavestrutwithFastener#14A(3fastenersper10'piece).3.Installgutterstrapsevery3'-0"ofgutterlength.AttachtooutsidelegofgutterandtoeavestrutwithFastener#14A.4.ApplyTri-Beadtapesealertoslopelegofgutter.Edgeoftapesealershouldalignwithoutsideedgeofeavestrut.5.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.6. See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.
FASTENER #1E (4 PER PANEL)
GUTTER STRAP
BOX GUTTER
TRI-BEAD TAPE SEALER
EAVESTRUT
EAVE STRUT
TRI-BEAD TAPE SEALER
GUTTER STRAP
BOX GUTTER
LokSeam® PANEL
LokSeam® PANEL
FASTENER #14
FASTENER #14A
CROSS SECTION OFFIXED EAVE WITH GUTTER
ISOMETRIC VIEW OFFIXED EAVE WITH GUTTER
FIXED EAVE WITH GUTTEROVER PURLINS
FASTENER SPACING @ EAVE
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
LS-48REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
CROSS SECTION OF SNOW GUTTER WITH OFFSET CLEAT
UL 90 CLIP
GUTTER STRAP 3'-0" O. C.
OFFSET CLEAT
EAVESTRUT
WALL PANEL
FASTENER #12 (TWO PER CLIP)
SNOWGUTTER
TRI-BEADTAPE SEALER
CROSS SECTIONOF SNOW GUTTER THROUGH FASTENER
GUTTER STRAP 3'-0" O. C.
EAVESTRUT SNOW
GUTTER
TRI-BEADTAPE SEALER
FASTENER #1E
FASTENER #14
¹⁄₂”
½"
LokSeam® PANEL
LokSeam® PANEL
FASTENER #14
WALL PANEL
FASTENER #121'-0" O. C.
FASTENER #14A
FASTENER #14A
FASTENER #14A
FASTENER #14A
FASTENER SPACING @ EAVE
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
SNOW GUTTEROVER PURLINS
NOTES:Through Fastened
1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertoeavestrutwithFastener#14A(3fastenersper10'piece).3.AttachgutterstrapstogutterwithFastener#14at3'-0"o.c.4.ApplyTri-Beadtapesealertoslopelegofgutter.5.InstallpanelandfastentoeavestrutwithFastener#1Eatthespacingshownintheabovediagram.6.See “Panel End Sealant Detail at Eave” on page LS-32 to seal panel ends.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-49
LokSeam®
DETAILS
NOTES:1. The top dimension of the rake trim will be affected by the wall panel thickness.2. InstallfloatingrakesupportwithFastener#5at2'-0"o.c.3. Engagefemalelegofpaneloverrakesupport.4. ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.
FASTENERS MUST GO THROUGH RAkE SUPPORT.5. ApplyTri-BeadtapesealertotopofparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6. Use continuous cleat to hold bottom of rake trim in place. Fasten continuous cleat to each high rib of wall panel.7. If roof finishes on module, finishing detail will be similar to starting detail. If roof finishes off module, field cut and bend last panel run to fit
against floating rake support. Install parapet rake cleat, tape sealer and rake trim as previously described.8. If rake trim is not to be immediately installed, temporarily fasten panels to rake support to prevent wind damage.
TRI-BEADTAPE SEALER
FASTENER #14(@ 6" O.C.)
BOX RAKE
FLOATINGRAKESUPPORT
FASTENER #1E
RAKEANGLE
PURLIN
PARAPETRAKE CLEAT
PURLIN
RAKEANGLE
TRI-BEAD TAPE SEALER
BOX RAKE
WALL PANEL
FLOATINGRAKESUPPORT
EPDMCLOSURE
PARAPET RAKE CLEAT
5"
CONTINUOUSCLEAT
EPDMCLOSURE
CONTINUOUSCLEAT
CONTINUOUSCLEAT
FINISHING OFFMODULE
BEGINNINGON MODULE
FASTENER #5 @ 2" O.C.
FASTENER #14(@ 6" O.C.)
LokSeam®
PANEL
CONTINUOUSCLEAT
ISOMETRICVIEW OFBEGINNING ONMODULE
FLOATING RAkEOVER PURLINS
LS-50REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Floating Parapet High Eave
1.Do not use this detail with the floating eave or valley details.2.Installback-upplateontoendofpanel.3.Fieldcutzeeclosurestofitpanelwidth.4.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosuresshouldbezeefromendofpanels.6.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.7.AttachparapethighsideeavetrimtozeeclosurewithFastener#4Aat6"o.c.8.Sealcounterflashtoparapetwallwithurethanesealant.
Fixed Parapet High Eave1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1½"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.6.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.7.AttachparapethighsideeavetrimtozeeclosurewithFastener#4Aat6"o.c.
PARAPET HIGH EAVE OVER PURLINS
LokSeam® PANEL
ZEEPURLIN
BUILDINGDIM.
FIELDSAWCUT
FLEXIBLEMEMBRANE
TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE
TRI-BEAD TAPESEALER(HW-504) @TOP OFCLOSURE& TOP OF
FLEXIBLEMEMBRANE
TRI-BEAD TAPESEALER(HW-504)
MASONRYWALL(NOTBYMetl-Span)
PARAPETHIGHEAVETRIM
COUNTERFLASH(T-5225)
URETHANETUBESEALANTCONTINUOUS
14-10x2"DECKSCREW (FASTENER#209)@24"O.C.(PRE-DRILLHOLE)
UL90CLIP (HW-6400)
¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)(1)PERRIB
¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)
URETHANETUBESEALANT@CLOSUREENDS2"
2"7"
BACKUPPLATE(HW-7762)@18"PANEL(HW-7766)@16"PANEL(HW-7764)@12"PANEL
ZEECLOSURE(T-5014)(FIELDCUT TO FIT PANEL)
12-14x1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)
(2PERCLIP)
¹⁄₄"-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOT INSTALL THRU PANELRIB)
HIGHSIDE EAVEFLASH
TRI-BEADTAPESEALER
TRI-BEADTAPESEALER
ZEECLOSURE
PURLIN
PARAPETWALL
COUNTERFLASH
URETHANESEALANT
URETHANESEALANT
BACK-UPPLATE
ISOMETRIC VIEWOF HIGH SIDE EAVE
FASTENER#11
LokSeam®
PANEL
FASTENER#146"O.C.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-51
LokSeam®
DETAILS
NOTES:1.InstallfloatingrakesupportwithFastener#5at2'-0"o.c.Fastenersmustbeinstalledincenterofslot.2.Engagefemalelegofpaneloverrakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneandparapetrakecleattopanellegwithFastener#1Eat
2'-0"o.c.FASTENERS MUST GO THROUGH RAkE SUPPORT.4.EngageopenhemofparapetrakeflashontoparapetrakecleatandfastentoplegtoparapetwallwithFastener#11.5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun
to fit against floating rake support. Install parapet rake cleat, tape sealer, and parapet rake flash as previously described.6.Ifparapetrakeflashisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.
FLOATING PARAPET RAkEOVER PURLINS
BUILDINGDIM.
FEILDSAWCUT
FEILDSAWCUT
FEILDCUT&BENDUP1³⁄₄"LEG
TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE
TRI-BEAD TAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALER(HW-504)EA.SIDEOFFLEXIBLEMEMBRANE
¹⁄₈ x ³⁄₈ POPRIVET(FASTENER14A)
¹⁄₈ x ³⁄₈ POPRIVET(FASTENER14A)
TRI-BEADTAPESEALER(HW-504)
TRI-BEADTAPESEALER(HW-504)
FLEXIBLEMEMBRANE
FLEXIBLEMEMBRANE
MASONRYWALL(NOTBYMetl-Span)
2x4x16GA.ANGLE
2x4x16GA.ANGLE
14-10x2"DECKSCREW (FASTENER#209)
@24"O.C.(PRE-DRILLHOLE)
14-10x2"DECKSCREW(FASTENER#209) @24"O.C.(PRE-DRILLHOLE)
ZEEPURLIN
LokSeam® PANEL
LokSeam® PANEL
UL90CLIP(HW-6400)
¹⁄₄"-14x1¹⁄₄"LONGLIFES.D.W/WASHER(FASTENER#1E)@12"O.C.
¹⁄₄"-14x1¹⁄₄"LONGLIFES.D.W/WASHER(FASTENER#1E)@12"O.C.
ZEECLOSURE(T-5014)
PARAPETRAKETRIM(T-5218)
PARAPETRAKETRIM(T-5218)
COUNTERFLASH(T-5225)
COUNTERFLASH(T-5225)
URETHANETUBESEALANTCONTINUOUS
URETHANETUBESEALANTCONTINUOUS
12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)(1)PERCONN.@EACHPURLIN
12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)(1)PERCONN.@EACHPURLIN
FINISHING OFF MODULE
LS-52REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.Donotusethisdetailwiththefixedridgeorhipdetails.2.Fieldcutlegsofpanelsandbendtorequiredangle.3.Fillbothexposedendsofpanelwithurethanesealant.4.Fieldnotchribcovertoallowittobendtotheproperangle.5.Fieldapplyabeadofurethanesealantoverribbeforeapplyingribcover.6.Do not use this detail inside the building envelope.
RIB COVER
F ASTENER #12
EAVE STRUT
EAVE STRUT
URETHANE SEALANT BEND RIB COVER AND INSTALL ON PANEL
SEAL BOTH PANEL ENDS WITHURETHANE SEALANT
URETHANE SEALANT
FIELD NOTCH RIB COVER TO MATCH ROOF SLOPE
LokSeam® PANEL
LokSeam® PANEL
FASTENER #14
FASTENER #14
INSTALLATION DIRECTION
CROSS SECTIONOF ROOFTRANSITION
ISOMETRIC VIEWOF ROOF TRANSITION
UL 90 CLIP
UL 90 CLIP
ROOF TRANSITIONOVER PURLINS
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-53
LokSeam®
DETAILS
NOTES:1.The above endlap detail must be used with the floating eave or valley details. The fixed detail must be used at the ridge
or hip. The above detail also requires that the LokSeam® panels be ordered without prepunched endlaps. Panels will be swaged as normal. Order the upper endlap panel 1½" longer than normal for the panel hem. See Page LS-26 for ordering information.
2.Installbottompanelsothateavehasproperoverhang(refertoEaveDetails).3.Atupslopeendofbottompanel,placeTri-Beadtapesealeroverentirewidthofpanel.Centeroftapesealershouldbe4½"fromend
of panel.4.Installoffsetcleatacrosswidthofpanel(overtapesealer)withFastener#13Aat4"o.c.Fasteners must go through tape sealer.5.Fieldnotchmaleandfemalelegsofpanel1½"andbendpaneltoformanopenhem.6.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels
ENDLAPOVER WOOD DECk
TRI-BEAD TAPE SEALER
OFFSET CLEAT
UL 90 CLIP
LOWER SWAGED LokSeam® PANEL
UPPER LokSeam®
PANEL
LOWER SWAGED LokSeam® PANEL
FASTENER #13 4" O.C.
MOISTURE BARRIER
TRI-BEAD TAPE SEALER
WOOD DECK
OFFSET CLEAT
3"UPPER LokSeam®
PANEL
FASTENER #13 4" O.C. CROSS SECTION
ENDLAP OVER WOOD DECK
ENDLAPSEQUENCEINSTALLATION
LS-54REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Fixed Hip
1.Do not use this detail with the fixed eave or valley details.2.Bevelcutandinstallpanelstofollowslopeofhip.3.InstallTri-Beadtapesealertopanels,runningparalleltothehip.Centeroftapesealershouldbe3½"fromthecenterofthehip.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe4"fromcenterofhip.
Floating Hip1.Do not use this detail with the floating eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.Slidealengthof2"x2"x16-gaugeangleunderthepanels.5.Installzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"fromcenterof
ridge. Seal sides of zee closures to panel seams with urethane sealant.
HIPOVER WOOD DECk
4"FIXED RIDGE/HIP FLASH
2" 9"
TRI-BEADTAPE SEALER FLOATING RIDGE
FLASH
ZEE CLOSURE(FIELD CUT TOLENGTH AND BEVELCUT TO FIT PANEL)
URETHANE SEALANT
2"x2"x16-GA.ANGLE (CONT.)
4"9"
FASTENER #13
2"
UL 90 CLIP
STANDARD FIXED HIP OVER WOOD DECK
TRI-BEADTAPE SEALER
ZEE CLOSURE(FIELD CUT TO LENGTH AND BEVEL CUTTO FIT PANEL)
UL 90 CLIP
URETHANE SEALANT IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED LokSeam®
PANEL
LokSeam®
PANEL
FASTENER #144" O.C.
FASTENER #13
FASTENER #136" O.C.
FASTENER #144" O.C.
MOISTUREBARRIER
WOOD DECK
WOOD DECK
MOISTUREBARRIER
STANDARD FLOATING RIDGE/HIP OVER WOOD DECK
FASTENER #14A4" O.C.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-55
LokSeam®
DETAILS
NOTES:1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners
must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.6.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels.
FIXED RIDGEOVER WOOD DECk
2"URETHANESEALANT
FIXED RIDGE FLASH
ZEE CLOSURE WOOD DECK
MOISTUREBARRIER
ZEE CLOSURE
URETHANESEALANT
MOISTUREBARRIER
FIXED RIDGE FLASH
2"
UL 90 CLIP
WOOD DECK
STANDARD RIDGE OVER WOOD DECK
ISOMETRICVIEW OF RIDGEOVER WOOD DECK
IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED
FASTENER #144" O.C.
TRI-BEADTAPE SEALER
TRI-BEADTAPE SEALER
FASTENER #144" O.C.
FASTENER #136" O.C.
FASTENER #13
FASTENER #136" O.C.
LokSeam®
PANEL
LokSeam®
PANEL
LS-56REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1. Do not use this detail with floating eave or valley details.2. Field cut zee closures to fit panel width.3. InstallTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromendofpanel.4. Slidealengthof2"x2"x16gaugeangleunderthepanels.5. Installzeeclosurestopanelsand2"x2"anglewithFastener#14Aat4"o.c.Verticallegofzeeclosureshouldbe4"fromcenterof
ridge. Seal sides of zee closures to panel seams with urethane sealant.
FLOATING RIDGEOVER WOOD DECk
TRI-BEAD(HW-504)TAPESEALER
RIDGETRIM(T-5088)
ZEECLOSURE(T-5014)(FIELDCUTTOLENGTHANDBEVELCUTTOFITPANEL)
MOISTUREBARRIER(NOTBYMetl-Span) ⁵⁄₈"PLYWOODMIN.
(NOTBYMetl-Span)
URETHANETUBESEALANT @CLOSUREENDS
2"x2"x16-GA.BACKUPANGLE
9"
FASTENER#13A
2"
UL90CLIP(HW-6400)
LokSeam® PANEL
FASTENER#4@6"O.C.(DONOTINSTALLTHRUPANELRIB)
FASTENER#14A@4"O.C.
2"
ZEECLOSURE
URETHANESEALANT
MOISTUREBARRIER
FLOATINGRIDGEFLASH
WOODDECK
ISOMETRIC VIEW OF FLOATING RIDGEOVER WOOD DECk
TRI-BEADTAPESEALER
FASTENER#14A6"O.C.
Lok-Seam®
PANEL
FASTENER#4@6"O.C.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-57
LokSeam®
DETAILS
NOTES:Ridge With Perforated Vent Drip
1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners
must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Metalventmaterialmusthaveurethanesealantatalllapconditions.
Ridge With Metal Vent1.Do not use this detail with the fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.Fasteners
must go through tape sealer.5.Sealendofzeeclosuretopanelseamswithurethanesealant.7.InstallventedmetaltooutsideclosureswithFastener#4at6"o.c.8.AttachridgeflashwithFastener#4at6"o.c.toventedmetal.9.Balance vent exhaust at ridge with vent intake at eave or soffit. Metal vent material must have urethane sealant at all trim
lap conditions.
VENTED RIDGEOVER WOOD DECk
TRI-BEADTAPE SEALER
ZEE CLOSURE
URETHANESEALANT
MOISTUREBARRIER
RIDGE FLASHFOR VENT
WOOD DECK
IMPORTANT NOTE:TEMPORARILY SECURE PANELS AT RIDGE UNTILZEE CLOSUREIS INSTALLED
LokSeam®
PANEL
PERFORATEDVENT DRIP
RIDGE FLASHFOR VENT
TRI-BEADTAPE SEALER
FASTENER #13 UL 90 CLIP
ZEE CLOSURE
FASTENER #46" O.C.
STANDARD RIDGE WITHPERFORATED VENT DRIP
LokSeam®
PANEL
FASTENER #412" O.C.
FASTENER #13 6" O.C.
MOISTUREBARRIER
URETHANESEALANT
2"2"
ISOMETRICVIEW OF METALVENT DRIP
LS-58REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panels must be attached to substructure at the ridge or hip to prevent them from sliding downslope.3.OffsetcleatisinstalledcontinuousalongslopeofvalleyoverTri-BeadtapesealerwithFastener#13Aat1'-0"o.c.
FASTENERS MUST GO THROUGH TAPE SEALER.4.Add 1½" to the panel length for panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.
FLOATING VALLEYOVER WOOD DECk
OFFSET CLEAT
VALLEYTRIM
TRI-BEADTAPE SEALER
WOOD DECK
MOISTURE BARRIER
FASTENER #131'-0" O.C. (FASTENER MUST GOTHROUGH TAPE SEALER)
LokSeam®
PANEL
WOOD DECK MOISTURE BARRIER
BEVEL CUT PANEL TO MATCHSLOPE OF VALLEY TRIM
VALLEY TRIM
6" OVERLAP
VALLEY TRIM
FASTENER #13
URETHANESEALANT
WOOD DECK
TRI-BEADTAPE SEALER
LokSeam®
PANEL
FASTENER #131'-0" O.C.(FASTENER MUSTGO THROUGTHTAPE SEALER)
OFFSET CLEAT
4½" or 9"9" Valley dimension must be usedin valleys longer than 30'-0".
MOISTURE BARRIER
CROSS SECTION OFVALLEY OVER WOOD DECK
ISOMETRIC VIEW OFVALLEY OVER WOOD DECK
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-59
LokSeam®
DETAILS
NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Do not use this detail with fixed ridge or hip details.3.ApplyTriple-BeadtapesealercontinuouslyunderLokSeam®panel.4.AttachpanelstowooddeckwithFastener#2Bat3"oncenter.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.
FIXED VALLEYOVER WOOD DECk
VALLEYTRIM
FILLENDOFRIBW/URETHANSEALANT
TRIPLE-BEADTAPESEALER MOISTUREBARRIER
(NOTBYMetl-Span)12-11xPANCAKEHEAD
SELF-TAPPER(FASTENER#13A)
@5'-0"O.C.
LokSeam® PANEL
WOODDECK MOISTURE BARRIER
BEVELCUT PANELTOMATCHSLOPEOFVALLEYTRIM
VALLEYTRIM
6"OVERLAP
VALLEYTRIM
FASTENER#13A
URETHANESEALANT
WOODDECK
TRIPLE-BEADTAPESEALER
LokSeam®
PANEL
OFFSETCLEAT
4½"or9"9"Valleydimensionmustbeusedinvalleyslongerthan30'-0".
MOISTURE BARRIER
CROSS SECTION OFVALLEY OVER WOOD DECk
ISOMETRIC VIEW OFVALLEY OVER WOOD DECk
¹⁄₄-14 x 1 LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)@3"O.C.(FASTENERMUSTGOTHROUGHTAPESEALER)
⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)
LS-60REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Fixed High Eave
1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromtheendofthepanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.6.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.
Floating High Eave1.Do not use this detail with floating eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Thecenteroftapesealershouldbe1ZZZ"fromtheendofthepanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendsofzeeclosurestopanelseamswithurethanesealant.InstallTri-Beadtapesealertotoplegofzeeclosure.6.AttachpeakcaptozeeclosurewithFastener#14Aat6"o.c.
HIGH EAVEOVER WOOD DECk
CROSS SECTION OF PEAk
FIXED HIGH EAVE
FLOATING HIGH EAVE
TRI-BEADTAPESEALER
TRI-BEADTAPESEALER
12-11X1"PANCAKEHEADSELF-TAPPER(FASTENER#13A)@6"O.C.
ZEECLOSURE
URETHANETUBESEALANT
PEAKCAP
WALLPANEL
2"
OUTSIDECLOSURE
CONTINUOUSCLEAT
¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.
¹⁄₄-14 x 1LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)
¹⁄₈X ³⁄₆POPRIVET(FASTENER#14A)
@6"O.C.(DONOT INSTALLTHRUPANELRIB)
MOISTURE BARRIER
(NOTBYMetl-Span)
⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)
LokSeam® PANEL
TRI-BEADTAPESEALER
TRI-BEADTAPESEALER
ZEECLOSURE
URETHANETUBESEALANT
PEAKCAP
UL90CLIP
WALLPANEL
2"
OUTSIDECLOSURE
¹⁄₈ x ³⁄₆POPRIVET(FASTENER#14)@12"O.C.
¹⁄₄-14 x 1LONG-LIFE‘TYPEAB’SELF-TAPPERW/WASHER(FASTENER#2B)
1³⁄₄ x 2¹⁄₄x16GA.BACK-UPANGLE
¹⁄₈X ³⁄₆POPRIVET(FASTENER#14A)
@6"O.C.(DONOT INSTALLTHRUPANELRIB)
¹⁄₈X ³⁄₆POPRIVET(FASTENER#13A)
@6"O.C.12-11 x 1"PANCAKEHEADSELF-TAPPER(FASTENER#14A)
(2)PERCLIP
MOISTURE BARRIER(NOTBYMetl-Span)
⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)
IMPORTANTNOTE:TEMPORARILYSECUREPANELSATPEAKUNTILZEECLOSUREIS INSTALLED.
2"
LokSeam® PANEL
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-61
LokSeam®
DETAILS
NOTES:EavewithOffsetCleat
1.Panels must be attached to substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.OffsetcleatisinstalledcontinuousalongeaveoverTri-BeadtapesealerwithFastener#13Aat1'-0"o.c.
FASTENERS MUST GO THROUGH TAPE SEALER.3.Clipspacingshouldnotexceed4'-0"o.c.for24-gaugepanelsor5'-0"o.c.for22-gaugepanels.4.Add 1½" to the panel length for the panel hem.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends at valley.
EavewithExtendedDripEdge1.Panels must be attached to substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.AttacheavetrimtothewooddeckwithFastener#13Aat2'-0"o.c.
FASTENERS MUST GO THROUGH TAPE SEALER.3.Tofieldhempanel,seepageLS-31.4.See "Panel End Sealant Detail" on page LS-32.
FLOATING EAVE WITH EAVE TRIMOVER WOOD DECk
PANEL END DETAIL
ISOMETRIC VIEW OF EAVE OVER WOOD DECK
CROSS SECTION OF EAVE OVERWOOD DECK
FASTENER #13
OFFSET CLEAT
EAVE TRIM
SEE PAGE LS-40 FOR PANEL ENGAGEMENT
EAVE TRIM
OFFSET CLEAT
UL 90 CLIP
WOOD DECK
TRI-BEADTAPE SEALER
CONTINUOUSCLEAT
CONTINUOUSCLEAT
WALL PANEL
WALL PANEL
FASTENER #13 1'-0" O.C.
EPDMCLOSURE
MOISTUREBARRIER
MOISTUREBARRIER
TRI-BEADTAPE SEALER
WOOD DECK
LokSeam® PANEL
LokSeam® PANEL
FASTENER #13
FASTENER #131'-0" O.C.
LS-62REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.Do not use this detail with the fixed ridge or hip details.2.AttacheavetrimtowooddeckwithFastener#13A(3fastenersper10'piece).3.ApplyTri-Beadtapesealertoslopelegofeavetrim.Edgeoftapesealershouldalignwithedgeofwooddeck.4.INstallpanelandfastentowooddeckwithFastener#2B.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.
FIXED EAVE WITH EAVE TRIMOVER WOOD DECk
PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT
OPTIONAL CONTINUOUSCLEAT
WOOD BLOCKING
WOOD DECK
WALL PANEL
MOISTUREBARRIER
LokSeam® PANEL
EAVE TRIMW/DRIP EDGE
EPDM CLOSURE
FASTENER #14
FASTENER #13A(2) PER CLIP
¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)
¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)
FASTENER SPACING @ EAVE
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-63
LokSeam®
DETAILS
NOTES:Offset Cleat
1.The offset cleat method of attachment should be used when ridge, peak or endlap is fixed to the substructure. Panels must be attached at one of these points to prevent them from sliding downslope.
2.AttachoffsetcleattowooddeckwithFastener#13Aat1'-0"o.c.3.Tofieldhempanel,seepageLS-314.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.5.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail
for these areas.
Gutter with Drip Edge1.The gutter with drip edge method of attachment should be used when ridge, high eave or endlap is fixed to the
substructure. Panels must be attached at one of these points to prevent them from sliding downslope.2.InstallguttertowooddeckwithFastener#13Aat2'-0"o.c.3.AttachgutterstrapstogutterwithFastener#14at3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Thisdetailmaybeusedonroofswithpitchesof4:12orless.Forroofswithpitchesgreaterthan4:12,callMetl-Span.8.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail
for these areas.
FLOATING EAVE WITH GUTTEROVER WOOD DECk
CROSS SECTIONOF GUTTER WITHDRIP EDGE
FASTENER #131'-0" O.C.
UL 90 CLIP
GUTTER STRAP
BOX GUTTER
OFFSET CLEA T
WALL PANEL
UL 90 CLIP
GUTTER STRAP
BOX GUTTERW/DRIP EDGE
CROSS SECTIONOF GUTTER WITHOFFSET CLEAT
PANEL ENDDETAIL SEE PAGE LS-39 FOR PANEL ENGAGEMENT
PANEL ENDDETAIL SEE PAGE LS-39 FOR PANEL ENGAGEMENT
LokSeam® PANEL
LokSeam® PANEL
WALL PANEL
FASTENER #14
FASTENER #14 FASTENER #13
FASTENER #13
TRI-BEADTAPE SEALER
FASTENER #14 MOISTURE BARRIER
WOOD DECK
MOISTUREBARRIER
WOOD DECK
LS-64REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:Fixed Eave with Gutter
1.Do not use this detail with the fixed ridge or hip details.2.AttachguttertowooddeckwithFastener#13A(3fastenersper10'piece)3.Installgutterstrapsevery3'-0"ofgutterlength.AttachtooutsidelegofgutterandslopelegofgutterwithFastener#14.4.ApplyTri-Beadtapesealertoslopelegofgutter.Edgeoftapesealershouldalignwithedgeofwooddeck.5.Installpanelandfastentowooddeckwithfastener#2Batthespacingshownintheabovediagram.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForgreater.
FIXED EAVE WITH GUTTEROVER WOOD DECk
GUTTER STRAP
BOX GUTTERW/DRIP EDGE
LokSeam® PANEL
WALL PANEL
¹⁄₈ x ³⁄₁₆ POP RIVETFASTENER #14
WOOD BLOCKING
MOISTURE BARRIER
WOOD DECK
¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPERW/WASHER (FASTENER #2B)
¹⁄₄-14 x 1 LONG-LIFE‘TYPE AB’ SELF-TAPPER
W/WASHER (FASTENER #2B)
TRI-BEAD TAPE SEALER
FILL END OF RIB WITHURETHANE SEALANT
12-11 X 1" PANCAKE HEADSELF-TAPPER (FASTENER #13A)
@ 6" O.C.
PANEL END DETAIL FILL END OF RIB WITHURETHANE SEALANT
FASTENER SPACING @ EAVE
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-65
LokSeam®
DETAILS
NOTES:1.Thetopdimensionoftherakewillbeaffectedbythewallpanelthickness.2.InstallfloatingrakesupportwithFastener#13Aat2'-0"o.c.(InstallFastener#13Asoasnottorestrictthemovementoftherake
support).3.Engagefemalelegofpaneloverrakesupport.4.ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.
FASTENERS MUST GO THROUGH RAkE SUPPORT.5.ApplyTri-BeadtapesealertotopofparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6.Usecontinuouscleattoholdbottomofraketriminplace.Fastencontinuouscleattoeachhighribofwallpanel.Thebottomhemof
theraketrimis“open”.7.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun
to fit against floating rake support. Install parapet rake cleat, tape sealer and rake trim as previously described.8.Ifraketrimisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.
FLOATING RAkEOVER WOOD DECk
TRI-BEADTAPE SEALER
FASTENER #14
BOX RAKE
FLOATING RAKESUPPORT
FASTENER #1E
PARAPETRAKE CLEAT
WALL PANEL
WALL PANEL
EPDMCLOSURE
5"
CONTINUOUSCLEAT
EPDMCLOSURE
CONTINUOUSCLEAT
FINISHING OFFMODULE
BEGINNINGON MODULE
FASTENER #132" O.C.
WOOD DECK
MOISTUREBARRIER
TRI-BEADTAPE SEALER
BOX RAKE
FLOATING RAKE SUPPORT
PARAPET RAKE CLEAT
CONTINUOUSCLEAT
FASTENER #14
LokSeam® PANEL
FASTENER #132" O.C.
FASTENER #132" O.C.
OPEN HEMWALL PANEL
MOISTUREBARRIER
WOOD DECK CONTINUOUSCLEAT
ISOMETRICVIEW OFBEGINNINGON MODULE
LS-66REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.ApplyTri-Beadtapesealertobottomlegofzeeclosure.2.InstallzeeclosuretopanelwithFastener#13Aat12"oncenter.3.ApplyTri-BeadtapesealertotoplegofzeeclosureandattachraketrimtozeeclosurewithFastener#14Aat12"oncenter.4.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutpanelandbenda1/3/4"
leg before installing zee closure.
FIXED RAkEOVER WOOD DECk
TRI-BEADTAPESEALER
ZEECLOSURE
WALLPANEL
OUTSIDECLOSURE
CONTINUOUSCLEAT
FINISHING OFFMODULE
BEGINNINGON MODULE
MOISTUREBARRIER
TRI-BEADTAPESEALERBOXRAKE
ZEECLOSURE
CONTINUOUSCLEAT
LokSeam® PANEL
12-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER
(FASTENER#3)
12-11x1"PANCAKEHEADSELF-TAPPER(FASTENER#13A)@24"O.C.
¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)
@12"O.C.
¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)
@12"O.C.
¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14A)@12"O.C.
FIELDCUTANDBENDUP1³⁄₄"LEG
¹⁄₄-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@12"O.C.
WALLPANEL
MOISTUREBARRIER
WOODDECK
CONTINUOUSCLEAT
ISOMETRICVIEW OFBEGINNINGON MODULE
BOXRAKETRIM
⁵⁄₈" PLYWOODMIN.(NOTBYMetl-Span)WOODBLOCKING(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-67
LokSeam®
DETAILS
NOTES:1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.5.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.6.AttachparapethighsideeavetrimtozeeclosurewithFastener#4at6"o.c.7.Sealcounterflashtoparapetwallwithurethanesealant.
FIXED PARAPET HIGH EAVEOVER WOOD DECk
URETHANE SEALANT
COUNTERFLASH
URETHANE SEALANT
TRI-BEADTAPE SEALER
2"
2"
HIGH SIDE EAVE FLASH
UL 90 CLIP
ZEE CLOSURE
CROSS SECTIONOF HIGH SIDEEAVE
TRI-BEADTAPE SEALER
FASTENER #14
FASTENER #11
LokSeam®
PANEL
FASTENER #136" O.C.
FASTENER #13
WOOD DECK
MOISTUREBARRIER
TRI-BEADTAPE SEALER
ZEE CLOSURE
HIGH SIDEEAVE FLASH
TRI-BEADTAPE SEALER
PARAPET WALL
COUNTERFLASH
URETHANE SEALANT
URETHANE SEALANT
ISOMETRIC VIEWOF HIGH SIDE EAVE
FASTENER #11
LokSeam®
PANEL
FASTENER #14 6" O.C.
WOOD DECK MOISTUREBARRIER
LS-68REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.Do not use this detail with fixed eave or valley details.2.Fieldcutzeeclosurestofitpanelwidth.3.ApplyTri-Beadtapesealertopanels.Centeroftapesealershouldbe1½"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#13Aat6"o.c.Verticallegofzeeclosuresshouldbe2"fromendofpanels.5.Sealendsofzeeclosurestothepanelseamswithurethanesealant.ApplyTri-Beadtapesealertothetoplegofzeeclosures.6.AttachparapethighsideeavetrimtozeeclosurewithFastener#4at6"o.c.7.Sealcounterflashtoparapetwallwithurethanesealant.
FLOATING PARAPET HIGH EAVEOVER WOOD DECk
URETHANETUBESEALANTCONTINUOUS
COUNTERFLASH
URETHANESEALANT@CLOSUREENDS
TRI-BEADTAPESEALER@TOPOFCLOSURE&TOPOFFLEXIBLEMEMBRANE
2"2"
MASONARYWALL(NOTBYMetl-Span)
FLEXIBLEMEMBRANE
PARAPETHIGHEAVETRIM
PARAPETHIGHEAVETRIM
UL90CLIP
ZEECLOSURE(FIELD CUTTOFITPANEL
CROSS SECTIONOF HIGH SIDEEAVE
TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALER
¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL
THROUGHPANELRIB)
¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL
THROUGHPANELRIB)
14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)
14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)
FIELDSAWCUT
LokSeam® PANEL
12-11x1"PANCAKEHEADFASTENER#13A6"O.C.
12-11x1"PANCAKEHEADSELF-TAPPER
(FASTENER#13A) (2)PERCLIP
⁵⁄₈"PLYWOOD(NOTBYMetl-Span)
MOISTUREBARRIER(NOTBYMetl-Span)
TRI-BEADTAPESEALER
ZEECLOSURE
TRI-BEADTAPESEALER
PARAPETWALL
COUNTERFLASH
URETHANESEALANT
URETHANESEALANT
ISOMETRIC VIEWOF HIGH SIDE EAVE
LokSeam®
PANEL
WOODDECK MOISTUREBARRIER
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-69
LokSeam®
DETAILS
NOTES:1.InstallfloatingrakesupportwithFastener#13Aat2'-0"o.c.(InstallFastener#13Asoasnottorestrictthemovementoftherake
support).2.Engagefemalelegofpaneloverrakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneandparapetrakecleattopanellegwithFastener#1Eat
2'-0"o.c. FASTENERS MUST GO THROUGH RAkE SUPPORT.
4.EngageopenhemofparapetrakeflashontoparapetrakecleatandfastentoplegtoparapetwallwithFastener#11.5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun
to fit against floating rake support. Install parapet rake cleat, tape sealer and parapet rake flash as previously described.6.Ifparapetrakeflashisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.
FLOATING PARAPET RAkEOVER WOOD DECk
URETHANE SEALANT URETHANE SEALANT COUNTERFLASH
PARAPET RAKEFLASH
TRI-BEADTAPE SEALER
ALTERNATECOUNTERFLASH
FASTENER #13A
FLOATING RAKESUPPORT
PARAPETWALL
PARAPET RAKECLEAT
BEGINNINGON MODULE
FASTENER #1E
FINISHINGOFF MODULE
FASTENER #11
LokSeam®
PANEL
WOOD DECK MOISTUREBARRIER
URETHANESEALANT
PARAPET RAKE FLASH
TRI-BEADTAPE SEALER
FLOATING RAKE SUPPORT
COUNTERFLASH
LokSeam®
PANEL FASTENER #11
ISOMETRIC VIEWOF STARTINGOFF MODULE
WOOD DECK
MOISTUREBARRIER
SAWCUT DETAIL(RECOMMENDED)
SURFACE MOUNTDETAIL
TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE
LS-70REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFIXED PARAPET RAkE
OVER WOOD DECk
NOTES:1.ApplyTRi-Beadtapesealertobottomlegofzeeclosure.2.Installzeeclosuretopanelwithfastener#13Aat12"oncenter.3.ApplyTri-Beadtapesealertotoplegofzeeclosure.4.AttachflexiblemembranetoTri-BeadtapesealerontopofzeeclosureandaddasecondrunofTri-Beadtapesealerontopofthe
flexible membrane.5.AttachparapetraketrimtozeeclosurewithFastener#14Aat12"oncenter.6.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutpanelandbenda1ZZZ"
leg before installing zee closure.
URETHANE SEALANT URETHANE SEALANT COUNTERFLASH
PARAPET RAKE FLASH
TRI-BEADTAPE SEALER
PARAPETWALL
ZEE CLOSURE
ZEE CLOSURE
BEGINNINGON MODULE
FINISHINGOFF MODULE
14-10 x 2 DECK SCREW(FASTENER #209)@ 24” O.C. (PRE-DRILL HOLE)
14-10 x 2 DECK SCREW(FASTENER #209) @ 24” O.C.
(PRE-DRILL HOLE)
LokSeam®
PANEL
WOOD DECK
MOISTUREBARRIER
URETHANESEALANT PARAPET RAKE
FLASH
TRI-BEAD TAPE SEALER
COUNTER FLASH
LokSeam®
PANEL
ISOMETRIC VIEWOF STARTINGOFF MODULE
WOOD DECK
MOISTUREBARRIER
SAWCUT DETAIL(RECOMMENDED) SURFACE MOUNT
DETAIL
TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE
TRI-BEAD TAPE SEALER(HW-504) EA. SIDE OFFLEXIBLE MEMBRANE
TRI-BEAD TAPE SEALER (HW-504)
FIELD CUT & BENDUP 1³⁄₄” LEG
FLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE¹⁄₈" x ³⁄₁₆" POP RIVET(FASTENER #14A) @ 6" O.C.
¹⁄₈" x ³⁄₁₆" POP RIVET(FASTENER #14A) @ 6" O.C.
12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A)@ 24" O.C.
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-71
LokSeam®
DETAILS
NOTES:1.Donotusethisdetailwiththefixedridgeorhipdetails.2.Fieldcutlegsofpanelsandbendtorequiredangle.3.Fillbothexposedendsofpanelwithurethanesealant.4.Fieldnotchribcovertoallowittobendtotheproperangle.5.Fieldapplyabeadofurethanesealantoverribbeforeapplyingribcover.6.Amoisturebarriermustbeinstalledandextendedaminimumof12"upslopeandbehindthefasciatothebottom.7. Do not use this detail inside the building envelope.
ROOF TRANSITIONOVER WOOD DECk
UL 90 CLIPRIB COVER
UL 90 CLIPFASTENER #13
URETHANESEALANT BEND RIB
COVER ANDINSTALL ONPANEL
SEAL BOTH PANELENDS WITHURETHANE SEALANT
URETHANE SEALANT
FIELD NOTCHRIB COVER TO MATCH ROOF SLOPE
LokSeam® PANEL
LokSeam® PANEL
FASTENER #14
FASTENER #14
WOOD DECK
MOISTUREBARRIER
WOOD DECK
MOISTUREBARRIER
CROSS SECTIONOF ROOFTRANSITION
ISOMETRIC VIEWOF ROOF TRANSITION
INSTALLATIONDIRECTION
LS-72REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILS
NOTES:1.Metaldecktobe1½"deep,22-gauge.2.Rigidboardinsulationtobe1"-4"thick.3.ClipsandbearingplatestobeinstalledsimultaneouslywithtwoDeckFastenersintothemetaldeck.Lengthoffastenerstobe
determinedbythicknessofinsulationplusdepthofmetaldeck.Fastenersshouldextend¾"belowmetaldeck.4.Somecompositesystemsrequireadditionalacousticalconsideration.Contactyourarchitectand/orengineerforproperacoustical
design.
RIGID BOARD INSULATIONOVER METAL DECk
RIGID BOARD INSULATION
22-GAUGE1½" METAL DECK
BEARIN G PLA TE
UL 90 CLIP
PURLIN
PURLIN
RIGID BOARDINSULATION
22-GAUGE1½" METAL DECK
UL 90 CLIP
BEARING PLATE
VAPORBARRIER
VAPORBARRIER
LokSeam® PANEL
LokSeam® PANEL
FASTENER #15
ISOMETRIC VIEW OFRIGID BOARD INSULATIONOVER METAL DECK
CROSS SECTION OFRIGID BOARDINSULATION OVERMETAL DECK
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-73
LokSeam®
DETAILSENDLAP
OVER METAL DECk
FASTENER SPACING AT ENDLAP
16"
12"1" 1"3⁵⁄₁₆" 3⁵⁄₁₆" 3⁵⁄₁₆"
1" 1"3¹⁄₂"3¹⁄₂"3¹⁄₂"3¹⁄₂"
18"
1" 1"4" 4" 4" 4"
NOTES:1.Installbottompanelsothattheeavehastheproperoverhang(refertoeavedetails).2.Slideaprepunchedback-upplateontotheupperendofthepanel;makesuretheteethoftheback-upplateareontopofthepanel.
Visuallychecktoseethattheholesintheback-upplatealignwiththeprepunchedholesinthepanel.3.PlaceTri-Beadtapesealerovertheentirewidthofthepanel.Itmustbecentereddirectlyovertheprepunchedholes.4.Usinganawltoaligntheholes,installtoppanelbylappingitovertheswagedportionofthebottompanel.InstallFastener#1Ein
the prepunched holes in the proper sequence.5.Endlapsrequirerooferectiontoproceedfromlefttorightasviewedfromtheeavelookingtowrdtheridge.
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION
INTOMETALDECK)
VAPORBARRIER(NOTBYMetl-Span)
FIELDNOTCHANDREMOVERIGIDINSULATION
RIGIDINSULATION(NOTBYMetl-Span)
BEARINGPLATE
METALDECK(NOTBYMetl-Span)
1½"
4½"
TRI-BEAD TAPESEALER
LOWERSWAGEDLokSeam® PANEL
UL90CLIP
BACK-UPPLATE
FASTENER#1E
6 " UPPERLokSeam®
PANEL
MOISTUREBARRIER(NOTBYMetl-Span)
LS-74REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFIXED RIDGE
OVER METAL DECk
NOTES:1.Use this detail with a floating eave or valley detail.2.Fieldcutzeeclosurestofitpanelwidth.3.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.4.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.Verticallegofzeeclosureshouldbe2"fromendofpanel.5.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosures.6.AttachridgeflashtozeeclosurewithFastener#4at6"oncenter.
12"
2" 2"
URETHANESEALANT
RIDGETRIM ZEECLOSURE
RIDGEPLATE
LokSeam®PANEL
TRI-BEADTAPESEALERTOPANDBOTTOMOFCLOSURE
FASTENER#4 6"O.C.
FASTENER#1E 6"O.C.
DECKSCREW@12”O.C.(MIN.3/4”PENETRATIONINTOMETALDECK)
MOISTUREBARRIER(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-75
LokSeam®
DETAILSVENTED RIDGE
OVER METAL DECk
NOTES:1.Do not use this detail with the offset cleat method of attachment at the eave or valley.2.Ventedridgedetailshouldbeusedinconjunctionwithsoffitand/oreaveventstoprovidepropercirculationandtopreventweather
infiltration during high winds.3.Installback-upplateandzeeclosureasinNotes2-6above.4.AttachventdriptozeeclosureswithFastener#4at6"o.c.Seallapsinventdripwithurethanesealant.5.AttachridgeflashtoventdripwithFastener#4at6"o.c.
12"
2"
PERFORATEDVENTDRIP
RIDGEFLASHFORVENTTRI-BEAD
TAPESEALER
ZEECLOSURE
FASTENER#4@6"O.C.
2"
URETHANETUBESEALANT@CLOSUREENDS
LokSeam®PANEL
FASTENER#4 @6"O.C.
DECKSCREW@12”O.C.(MIN.3/4”PENETRATION INTOMETALDECK
FASTENER#1E @6”O.C.
2x4x16GA.ANGLE
RIGIDINSULATION(NOTBYMetl-Span)METALDECK
(NOTBYMetl-Span)
VAPORBARRIER(NOTBYMetl-Span)
MOISTUREBARRIER(NOTBYMetl-Span)
LS-76REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFLOATING VALLEYOVER METAL DECk
NOTES:1.Forvalleyslongerthan30',useextendedvalleytrim(seepageLS-22).2.Panelsmustbeattachedtothesubstructueattheridge,higheaveorhiptopreventthemfromsildingdownslope.3.OffsetcleatisinstalledcontinuouslyalongslopeofvalleyoverTri-BeadtapesealerwithFastener#12Aat1'-0"o.c.FASTENERS
MUST GO THROUGH TAPE SEALER.4.Add 1-1/2" to panel length for panel hem.5.See"PanelEndsealantDetail"onpageLS-32tosealpanelendsatvalley.
PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT
OFFSETCLEAT(T-5131)
FIELDNOTCHPANELLEGSANDBENDPANTOFORMOPENHEM
1¹⁄₂"
1¹⁄₂"
1¹⁄₂"
1" ¹⁄₂"¹⁄₂"
4 ¹⁄₂" TRI-BEADTAPESEALER(HW-504)
2"
¹⁄₂"
1'-0" MAX.UL90CLIP(HW-6400)
BEARINGPLATE(HW-7500)
VALLEYTRIM(T-5093)
OFFSETCLEAT(T-5131)
³⁄₈"
VALLEYSUPPORTPLATE(P-140)
LokSeam® PANEL
12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)@12"O.C.(FASTENERMUSTGOTHROUGHTAPESEALER)
VAPORBARRIER(NOTBYMetl-Span)
RIGIDINSULATION(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION
INTOMETALDECK)
DECKSCREW@12"O.C.(MIN.³⁄₄"PENETRATION
INTOMETALDECK)
12-14X1"PANCAKEHEADSELF-DRILLER(FASTENER#12A)
@5”O.C.
MOISTUREBARRIER(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-77
LokSeam®
DETAILSFIXED HIGH EAVE
OVER METAL DECk
NOTES:1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealaertotopofzeeclosures.7.AttachpeakcaptozeeclosurewithFastener#4at6"oncenter.
3"x5"x14GA.BENTPLATE
STRUCTURALANGLE(NOTBYMetl-Span)
FASTENER#16@12"O.C.
LONG-LIFETEK4.5FASTENER#78
VAPORBARRIER(NOTBYMetl-Span)
RIGIDINSULATION(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
TRI-BEADTAPESEALER
TRI-BEADTAPESEALER
ZEECLOSURE
URETHANETUBESEALANT
PEAKCAP
WALLPANEL
2"
OUTSIDECLOSURE
¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.
¹⁄₈X³⁄₆POPRIVET(FASTENER#14A)
@6"O.C.(DONOTINSTALLTHRUPANELRIB)
LokSeam® PANEL
FASTENER#1E
PEAKCAP
CONTINUOUSCLEAT
OPTIONALCONTINUOUS CLEAT
¹⁄₈ x ³⁄₁₆POPRIVET(FASTENER#14)@12"O.C.
LS-78REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFLOATING EAVE WITH EAVE TRIM
OVER METAL DECk
NOTES:1.Panels must be attached to the substructure at the ridge, high eave, endlap or hip to prevent them from sliding downslope.2.AttacheavetrimtobentplateateavewithFastener#12Aat12"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.
UL90CLIP
3"x5"x14GA.BENTPLATE
FILLENDOFRIBW/URETHANESEALANT
EAVETRIMW/EXTENDEDDRIPEDGE
WALLPANEL
STRUCTURALANGLE(NOTBYMetl-Span)
FASTENER#16@12"O.C.
FASTENER#14@12"O.C.
LONG-LIFETEK4.5FASTENER#78
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION
INTOMETALDECK)
VAPORBARRIER(NOTBYMetl-Span)
BEARINGPLATE
RIGIDINSULATION(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
LokSeam® PANEL
FASTENER#12A12"O.C.
PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT
OUTSIDECLOSURE
MOISTUREBARRIER(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-79
LokSeam®
DETAILSFLOATING EAVE WITH GUTTER
OVER METAL DECk
NOTES:1.The floating gutter detail should be used when ridge, high eave or endlap is fixed to the substructure. Panels must be
attached at one of these points to prevent them from sliding downslope.2.InstallguttertobentplateateavewithFastener#12Aat12"o.c.3.AttachgutterstrapstogutterwithFastener#14Aat3'-0"o.c.4.Tofieldhempanel,seepageLS-31.5.Notchpanelhemforgutterstrap.6.See “Panel End Sealant Detail” on page LS-32 to seal panel ends.7.Theaboveguttershouldnotbeusedinareasthatexperiencesnowloadsof10PSForhigher.SeepageLS-44forthegutterdetail
for these areas.
UL90CLIP
GUTTERSTRAP
BOXGUTTERW/DRIPEDGE
3"x5"x14GA.BENTPLATE
FILLENDOFRIBW/URETHANESEALANT
WALLPANEL
STRUCTURALANGLE(NOTBYMetl-Span)
FASTENER#16@12"O.C.
LONG-LIFETEK4.5FASTENER#78
FASTENER#14
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATION
INTOMETALDECK)
VAPORBARRIER(NOTBYMetl-Span)
BEARINGPLATE
RIGIDINSULATION(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
LokSeam® PANEL
FASTENER#12A12"O.C.
PANEL END DETAIL FILLENDOFRIBWITHURETHANESEALANT
MOISTUREBARRIER(NOTBYMetl-Span)
LS-80REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFLOATING RAkE
OVER METAL DECk
NOTES:1.Thetopdimensionoftheraketrimwillbeaffectedbythewallpanelthickness.2.InstallfloatingrakesupportwithFastener#12A,2'0"o.c.Installfastenersinthecenteroftheslotsintherakesupport(donotover
tightentoallowtherakesupporttofloat).3.Engagethefemalelegofthepanelovertherakesupport.4.ApplyTri-Beadtapesealertoverticallegofpanel.InstallparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.
FASTENERS MUST GO THROUGH THE RAkE SUPPORT.5.ApplyTri-BeadtapesealertothetopoftheparapetrakecleatandattachraketrimtoparapetrakecleatwithFastener#14Aat6"o.c.6.Useacontinuouscleattoholdbottomofraketriminplace.Fastencontinuouscleatateachhighribofwallpanel.7.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifrooffinishesoffmodule,fieldcutandbendlastpanelrun
to fit against floating rake support. Install parapet rake cleat and rake trim as previously described.8.Ifraketrimisnottobeimmediatelyinstalled,temporarilyfastenpanelstorakesupporttopreventwinddamage.
TRI-BEADTAPESEALER(HW-504)
12x14x1PANCAKEHEADSELF-DRILLER(FASTENER#12A)@24"O.C(DONOTOVER-TIGHTEN)
CONTINUOUSCLEAT(T-5121)
WALL PANEL
0/ODIMENSION(SEEPLAN)
DECKSCREW(2)PERCLIP (MIN. ³⁄₄"PENETRATIONINTOMETALDECK)
VAPORBARRIER(NOTBYMetl-Span)
RIGIDINSULATION(NOTBYMetl-Span)
STRUCTURAL ANGLE(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
2x4x16GA.ANGLEOUTSIDECLOSURE
BOXRAKETRIM
RAKESUPPORT ANGLE(HW-4680)
12-24x1¹⁄₄"PANHEADTEK4.5SELF-DRILLER
(FASTENER#16)@12"O.C.
12-24x1¹⁄₄"LONG-LIFETEK4.5W/WASHER
(FASTENER#78)
¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14)
@12"O.C.
¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.
PARAPETRAKECLEAT (T-5219)
¹⁄₈"x³⁄₈"POPRIVET(FASTENER#14A)@6"O.C.
LokSeam® PANEL
UL90CLIP(HW-6400)
BEARINGPLATE(HW-7500)
TRI-BEADTAPESEALER(HW-504)
CONTINUOUSCLEAT(T-5121)
0/ODIMENSION(SEEPLAN)
BOXRAKETRIM
RAKESUPPORT ANGLE(HW-4680)
¹⁄₈"x³⁄₁₆"POPRIVET(FASTENER#14)@12"O.C.
FIELDCUT&BENDUP1³⁄₄"LEGTO FIT AGAINST RAKESUPPORT ANGLE
¹⁄₄"-14x1¹⁄₄"LONG-LIFESELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.
PARAPETRAKECLEAT (T-5219)
¹⁄₈"x ³⁄₈"POPRIVET(FASTENER#14A)@6"O.C.
LokSeam® PANEL
MOISTUREBARRIER(NOTBYMetl-Span)
MOISTUREBARRIER(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-81
LokSeam®
DETAILSFIXED PARAPET HIGH EAVE
OVER METAL DECk
NOTES:1.Use this detail with a floating eave or valley detail.2.Installpanelsandclips.3.Fieldcutzeeclosurestofitpanelwidth.4.InstallTri-Beadtapesealertopanels.Thecenterofthetapesealershouldbe1-1/2"fromendofpanel.5.InstallzeeclosurestopanelswithFastener#1Eat6"oncenter.Verticallegofzeeclosureshouldbe2"fromendofpanel.6.Sealendofzeeclosuretopanelseamwithurethanesealant.InstallTri-Beadtapesealertotopofzeeclosures.7.InstallFlexiblemembraneoverTri-Beadtapesealer.ApplyasecondlayerofTri-Beadtapesealerontopoftheflexiblemembrane.8.AttachparapethigheavetrimtozeeclosurewithFastener#4at6"oncenter.
URETHANETUBESEALANTCONTINUOUS
COUNTERFLASH
URETHANESEALANT@CLOSUREENDS
TRI-BEADTAPESEALER@TOPOFCLOSURE&TOPOFFLEXIBLEMEMBRANE
2"2"
MASONARYWALL(NOTBYMetl-Span)
FLEXIBLEMEMBRANE
PARAPETHIGHEAVETRIM
UL90CLIP
ZEECLOSURE(FIELD CUTTOFITPANEL
TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALER
¹⁄₄-14x⁷⁄₈"LONG-LIFELAPTEKW/WASHER(FASTENER#4)@6"O.C.(DONOTINSTALL
THROUGHPANELRIB)
14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)
FIELDSAWCUT
LokSeam® PANEL
¹⁄₄-14x1¹⁄₄"LONG-LIFE SELF-DRILLERW/WASHER(FASTENER#1E)@6"O.C.
2"x4"x16GA.ANGLE
RIGIDINSULATION(NOTBYMetl-Span)
VAPORBARRIER(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
STRUCTURAL ANGLE(NOTBYMetl-Span)
VAPORBARRIER(NOTBYMetl-Span)
LS-82REV00.02SEEmetlspan.com FORCURRENTINFORMATIONSUBJECTTOCHANGEWITHOUTNOTICE
LokSeam®
DETAILSFLOATING PARAPET HIGH EAVE
OVER METAL DECk
NOTES:1.InstallfloatingrakesupportwithFastener#5,2'-0"o.c.Installfastenersinthecenteroftheslotsintherakesupport.2.Engagethefemalelefofthepanelovertherakesupport.3.ApplyTri-Beadtapesealertoverticallegofpanel.InstallflexiblemembraneovertheTri-Beadtapesealerandapplyasecondlayer
ofTri-Beadtapesealerovertheflexilemembrane.InstalparapetrakecleattopanellegwithFastener#1Eat2'-0"o.c.FASTENERS MUST GO THRUGH THE RAkE SUPPORT.
4.Engageopenhemofparapetraketrimontoparapetrakecleat.Attachflexiblemembraneandtoplegofparapetraketrimtoparapetwall with an appropriate fastener, depending upon wall substrate.
5.Ifrooffinishesonmodule,finishingdetailwillbesimilartostartingdetail.Ifroodfinishesoffmodule,fieldcutandbendlastpanelrunto fit against floating rake support. Install flexible membrane, parapet rake cleat and parapet rake trim as previously described.
¹⁄₄"-14x1¹⁄₄SHOULDERTEK2SELF-DRILLER
(FASTENER#5)@24"O.C
0/ODIMENSION(SEEPLAN)
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATIONINTOMETALDECK)
DECKSCREW(2)PERCLIP(MIN.³⁄₄"PENETRATIONINTOMETALDECK)
VAPORBARRIER(NOTBYMetl-Span)
RIGIDINSULATION(NOTBYMetl-Span)
STRUCTURAL ANGLE(NOTBYMetl-Span)
METALDECK(NOTBYMetl-Span)
PARAPETRAKETRIM
PARAPETRAKECLEAT
PARAPETRAKECLEAT
2”x4x16GA.ANGLE
RAKESUPPORTANGLE
TRI-BEADTAPESEALER(HW-504)EACHSIDEOFFLEXIBLEMEMBRANE ¹⁄₄"-14x1¹⁄₄"LONG-LIFE
SELF-DRILLERW/WASHER(FASTENER#1E)@24"O.C.
PARAPETRAKETRIM(T-5218)
MASONRYWALL(NOTBYMetl-Span)
URETHANETUBESEALANTCONTINUOUS
COUNTERFLASHFLEXIBLEMEMBRANE
LokSeam® PANEL
UL90CLIP(HW-6400)
BEARINGPLATE(HW-7500)
LokSeam® PANEL
URETHANETUBESEALANTCONTINUOUS
COUNTERFLASH
FLEXIBLEMEMBRANE
TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE
TRI-BEADTAPESEALEREACHSIDEOFFLEXIBLEMEMBRANE
FIELDCUT&BENDUP1³⁄₄"LEGTOFITAGAINSTRAKESUPPORTANGLE
14-10x2"DECKSCREW(FASTENER#209)@24"O.C.(PRE-DRILLHOLE)
14-10x2"DECKSCREW(FASTENER#209)@24"O.C.
(PRE-DRILLHOLE)
FIELDSAWCUT
FIELDSAWCUT
MOISTUREBARRIER(NOTBYMetl-Span)
MOISTUREBARRIER(NOTBYMetl-Span)
SUBJECTTOCHANGEWITHOUTNOTICESEEmetlspan.comFORCURRENTINFORMATIONREV00.02LS-83
LokSeam®
NOTES
1720 lakepointe Drive suite #101 lewisville, Texas 75057
Toll-free: 877.585.9969 | Email: [email protected] Web: metlspan.com
© 2019 Metl-Span, part of the Cornerstone Building Brands family. All Rights Reserved. Printed in the U.S.A. | January 31, 2019 / Rev 01.01