.7 TEST ~EPO s EZ TRADE 290 cc All: Mr C Paqe 5 Hyde Park Platinum Cresent Marconi Beam Milnerton 7447 Your Ref: SAB 001 Our ref: 19/3/21/1 Enquiries: ASW van Rensburg Tel No: 012- 428-6315 Project. FPE/84935/08 Date: 18 November 2008 TECHNICAL INFORMATION ON FIREoBAllS 1. The-fife extingballcontains a non toxic Furex Powder named Mono J.l.monium Phosphate (91.0%MAPf .:7 2. The ball has been tested at thermal temperatures of 85 degrees for 24 hours to prove the fire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only be activated by open flames ( 85 degrees or more) and not by heat. This was conducted in point 5.3 of the test report. 3. In point 5.4 of the test report it is proved that the burts effect of the fire extinguisher ball cannot cause harm to humans, animals or property upon activation. 4. The sound level test on activation was measured to be 121 dB and thus is safe for use and cannot be harmfull to human and for animal eardrums as it is below the recommended 140 dB. This is substantiated in Point 5.5 of the test report. 5. The fire extinguishing ball has been subjected to compression test in Point 5.6 of this report and complies to 150 kg compression. 6. Drop test on Point 5.7 of this test report proves that the ball can be dropped from a height of 2.5 m with no damages caused. 7. Fire ball complies with class 1A, 5B and C fire rating. These are Thailand fire ratings and could be comparable with 3A, 21 Band C according to SANS 6172:2003( South Afican National Standards). Y oU/iaithf,JY ./t ~~uU E Seeger / MANAGER: BUILDING & CONSTRUCTION ~- ASW van Rensburg: SENIOR TEST OFFICER FIRE PROTECTION ENGINEERING:SABS 1 Or Lategan Road, Groenkloof, Private Bag x191, Pretoria, 0001, Tel: +27 (012) 428 7911, Fax: +27 (012) 3441568 This test was performed by SABS Commercial (Pty) Ltd. This report and the test results relate only to the specific sample(s) identified herein. They do not imply SABS approval of the quality and/or performance of the item(s) in question and the test results do not apply to any similar item that has not been tested. (Refer also to the complete conditions printed on the back of this page.)

Upload: others

Post on 02-Jun-2020

20 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: TECHNICAL INFORMATION ON FIREoBAllS - Fire Extinguishing Ball · fire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only be activated by open flames

.7

TEST ~EPO s

EZ TRADE 290 cc

All: Mr C Paqe5 Hyde ParkPlatinum CresentMarconi BeamMilnerton7447

Your Ref: SAB 001Our ref: 19/3/21/1Enquiries: ASW van RensburgTel No: 012- 428-6315Project. FPE/84935/08Date: 18 November 2008

TECHNICAL INFORMATION ON FIREoBAllS

1. The-fife extingballcontains a non toxic Furex Powder named Mono J.l.monium Phosphate(91.0%MAPf .:7

2. The ball has been tested at thermal temperatures of 85 degrees for 24 hours to prove thefire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only beactivated by open flames ( 85 degrees or more) and not by heat. This was conducted inpoint 5.3 of the test report.

3. In point 5.4 of the test report it is proved that the burts effect of the fire extinguisher ballcannot cause harm to humans, animals or property upon activation.

4. The sound level test on activation was measured to be 121 dB and thus is safe for useand cannot be harmfull to human and for animal eardrums as it is below therecommended 140 dB. This is substantiated in Point 5.5 of the test report.

5. The fire extinguishing ball has been subjected to compression test in Point 5.6 of thisreport and complies to 150 kg compression.

6. Drop test on Point 5.7 of this test report proves that the ball can be dropped from a heightof 2.5 m with no damages caused.

7. Fire ball complies with class 1A, 5B and C fire rating. These are Thailand fire ratings andcould be comparable with 3A, 21 Band C according to SANS 6172:2003( South AficanNational Standards).

YoU/iaithf,JY./t ~~uUE Seeger /MANAGER: BUILDING & CONSTRUCTION

~-ASW van Rensburg:

SENIOR TEST OFFICERFIRE PROTECTION ENGINEERING:SABS

1 Or Lategan Road, Groenkloof, Private Bag x191, Pretoria, 0001, Tel: +27 (012) 428 7911, Fax: +27 (012) 3441568This test was performed by SABS Commercial (Pty) Ltd. This report and the test results relate only to the specific sample(s) identified herein. They do not

imply SABS approval of the quality and/or performance of the item(s) in question and the test results do not apply to any similar item that has not been tested.

(Refer also to the complete conditions printed on the back of this page.)

Page 2: TECHNICAL INFORMATION ON FIREoBAllS - Fire Extinguishing Ball · fire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only be activated by open flames

TEST REPORT Si:;J~ • 8

EZ TRADE 290 CC

Attention: Mr. C Page5 Hyde ParkPlatinum CresentMarconi BeamMilnerton7447

DRY POWDER TYPE FIRE EXTINGUISHING BALLS

o Significance of test results contained in this report.

Your ref: SAB 001Our ref: 15/25/9/1

Enquiries: ASW v RensburgTel: (012) 428-6315No.: FPE/84935/08

, Page: 1 01'3Date: 2008-11-10

0.1 Refer to the print on the back of this page.0.2 The sample described was tested for all the requirements of the clients own testing manual for Fire

Extinguishing Balls.0.3 The sample tested complies with the requirements of the testing manual for Fire Extinguishing Balls.

1 DESCRIPTION OF SAMPLE

Twenty four 1,2 kg dry powder type fire extinguishing balls marked "Elide Fire"were

submitted by the sponsor to the Fire Protection Engineering Laboratory of the SABS on 25

Apri1200S.

The specimens were accompanied by drawings and specifications of which copies are attached

to this report.

2. The extinguishing balls were labelled as follows:

Capacity:

Class:

Trade mark:

1,2 kg

ABC

Elide Fire

3. NATURE AND METHOD OF TEST

The extinguishing balls were evaluated for compliance to the "Testing manual for Fire

Extinguishing". At the request of the sponsor all the tests specified in the Testing manual were

conducted and reported under section 5 of this report.

1 Dr Lategan Road, Groenkloof, Private Bag x191, Pretoria, 0001, Tel: +27 (012) 428 7911, Fax: +27 (012) 3441568This test was performed by SABS Commercial (Ply) Ltd. This report and the test results relate only to the specific sample(s) identified herein. They do not

imply SABS approval of the qualily and/or performance of the item(s) in question and the test results do not apply to any similar item that has not been tested.(Refer also to the complete conditions printed on the back of this page.)

Page 3: TECHNICAL INFORMATION ON FIREoBAllS - Fire Extinguishing Ball · fire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only be activated by open flames

SABS Commercial (Pty) Ltd

REPORT No. FPE/84935/08 Page 2 of 3

I

- Complied - 121 dB

4 OBSERVATIONS AND FINDINGS

Note:- The sections that follow reflect observations and findings. The numbering of these sections isconsistent with the numbering of the relevant paragraphs in the testing manual. This numbering system isutilized with the objective to ease cross reference.

5 GENERAL REQUIREMENTS

5.1 General Appearance

The extinguishing balls shall not show any cracks, tears or leakage of the extinguishing agent, when

inspected visually.

5.2 Extinguishing agent contained inside the fire extinguishing balls,-;

The agent must be dry chemical powder, which is not in a hardened or agglomerative form. The test for the

agent depends on the age of the ball. The ball with the age of one year or more must be tested according to

clause 5.2.1 and with the age less than one year must be tested according to clause 5.2.2.

5.2.] By removing the soft shell ofthe fire extinguishing ball, the chemical powder can be examined. rt must not

agglomerated.

5.2.2 To determine moisture aging of the chemical powder, a desiccator or similar equipment may be used. This

may be conducted by filling the device with water to cover the bottom and then hanging the ball above the

water, and keeping the device at room temperature for 14 days. Remove the ball out of the device, and

test in accordance with sub clause 5.2.1.

5.3 Thermal resistance test

When the fire extinguishing balls are tested according to clause 8, for thermal resistance they should not

show any cracks, tears or leakage of the extinguisher agent. - Complied

5.4 Bursting effect

When the fire extinguisher balls are rested for resistance to bursting according to clause 9, the glass panels

used in the test should not crack or break. - Complied

5.5 Sound level test

When the sound pressure level of the explosion, as measured in accordance with clause 10, it should

not be more than 140dB.

5.6 Test for resistance to compression

When the fire extinguishing balls are tested for the resistance to the compression, according to clause 11,

they should not show any cracks, tears or leakage. - Complied

5.7 Drop test

When the fire extinguishing balls are dropped to the ground according to clause 12, they shall

show no cracks, tears or leakage of the extinguishing agent. - Complied

This report relates only to the specific sample(s) tested as identified herein. It does not imply SABS approval of the qualityand/or performance of the item(s) in question and the test results do not apply to any similar item that has not been tested.. . . ... ~""'-" "

Page 4: TECHNICAL INFORMATION ON FIREoBAllS - Fire Extinguishing Ball · fire extinguishing ball cannot be activated by heat. The fire extinguishing ball can only be activated by open flames

SABS Commercial (Pty) Ltd

REPORT No. FPE/84935/08

5.8 Performance of the extinguisher

In addition the fire extinguishing balls shall meet the criteria of acceptance as described in

table 1. (See clause 13)

Page 3 of 3

NO Performance rating CriteriaTest methodResults

]

Class ] A extinguishersMust extingui:;h fire]3.1Complied

2

Class 5 B extinguishersMust extinguish fire13.2Complied'.,73

Class C extinguishersMust extinguish fire13.3Complied

6 Results

The sample of dry powder extinguishing balls as described under section one of this report complies

to requirements ofthe properties listed under section 5 ofthis report.

j(') hDQ/E Seeger . J

MANAGER: BUILDING AND CONSTRUCTION

ASW v Rensburg

TEST OFFICER: FIRE PROTECTION ENGINEERING TEST OFFICER