Serial No
CUSTOMER REQUIREMENTS
MESC CLARIFICATION
FINAL DECISION BY
PURCHASER1
As per BOQ Item. 10 & 11 refers insulation color of Green/Yellow but Doc. No. KOC-E-023 Rev.2 refers to Yellow/Green for earth cables.MESC follows as per Doc. No. KOC-E-023 Rev.2 Yellow/Green for earth cables.2KOC-E-023 Rev.2 Cl. 6.2.1.D refers inner sheath of lead alloy sheath to EEMUA 133.
MESC offer lead sheath as per IEC 60502-1.