synco living train the trainer service & maintenance august 2007

13
Page 1/13 Train the Trainer - August 2007 Batteries Binding Test Faults Removing / Deleting Devices Synco living Train the Trainer Service & Maintenance August 2007

Upload: dexter-neal

Post on 03-Jan-2016

35 views

Category:

Documents


1 download

DESCRIPTION

Synco living Train the Trainer Service & Maintenance August 2007. Service & Maintenance Batteries. Battery life Battery-powered Synco 900 devices require 2 or 3 batteries type AA (LR6). Typical battery life is 3 years . - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Synco living Train the Trainer Service & Maintenance August 2007

Page 1/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Synco living

Train the Trainer

Service & Maintenance

August 2007

Page 2: Synco living Train the Trainer Service & Maintenance August 2007

Page 2/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBatteries

Battery lifeBattery-powered Synco 900 devices require 2 or 3 batteries type AA (LR6).Typical battery life is 3 years.Typically 3 years for alkaline / manganese batteries under the following conditions:

Capacity: >= 2,500 mAh Typical HVAC application New batteries (all) Used within the permissible operating temperature

range SSA955: No silent mode (silent mode about 2 years)2707Z22

When changing batteries, always replace all exhausted batteries by new ones!!

Rechargeable batteries should not be used, since self-discharge is excessive and – when nearly fully exhausted – the voltage delivered drops completely and very rapidly ( Bat Low display appears much too late).

Page 3: Synco living Train the Trainer Service & Maintenance August 2007

Page 3/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBatteries

If voltage drops to a level where correct operation is no longer possible, the central apartment unit indicates breakdown of communication since radio communication with the unit is no longer possible.

Low batteryWhen battery voltage is low (life ≤ about 3 months), the respective signal is sent to the central apartment unit via radio and a fault status message will appear on the display.

Device state

Battery capacity lowQAW910 3Room 1 24.04.2006 10:10

Device state

Radio communication errorQAW910 3Room 1 24.04.2006 10:10

Page 4: Synco living Train the Trainer Service & Maintenance August 2007

Page 4/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBatteries

If battery voltage is too low (life ≤ about 3 months), this is also indicated on the battery-powered devices:

Room unitQAW910

Room temperature sensorQAA910

Meteo sensor QAC910

Radiator control actuatorSSA955

+

270

7Z01

9

F

LED

Continuous symbol on the LCD

Red LED after startup and after pressing multifunction button F

Red LED after startup and after pressing multifunction button F

Page 5: Synco living Train the Trainer Service & Maintenance August 2007

Page 5/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBatteries

GAMMA wave devices indicate low battery capacity as follows:

Short flashes of LEDevery 10 s

Door / window contactwave AP 260

DELTA reflex smoke detector3 short flashes of LCD every 48 s anda short acoustic signal

Page 6: Synco living Train the Trainer Service & Maintenance August 2007

Page 6/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBatteries

Full batteryIf exhausted batteries have been replaced by new ones, the fault display on the central apartment unit will disappear as soon as the radio link is reestablished. The Synco devices indicate full batteries as follows:

Room unitQAW910

Room temperature sensor QAA910

Meteo sensor QAC910

Radiator control actuatorSSA955

+

270

7Z01

9

F

LED

Symbol when pressing the multifunction button, no symbol in operation

Green LED after startup and after pressing multi-function button F

Green LED after startup and after pressing multi-function button F

Page 7: Synco living Train the Trainer Service & Maintenance August 2007

Page 7/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBinding Test

To check the radio control link to the central apartment unit, Synco 900 devices can be used to make a binding test.

On the central apartment unit, each successful binding test is confirmed in the form of 3 short acoustic signals. Also, an additional window appears, displaying information about the device just tested.

The additional window continues to be displayed until it is acknowledged with the ok or the Esc button, or until it is replaced by the new additional window the next time a binding test is made.

Binding tests cannot be made with Gamma wave and Hager products!

Device info / number 03

Room 1Room unit QAW9100x00FDFF000833 V0.6

Page 8: Synco living Train the Trainer Service & Maintenance August 2007

Page 8/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceBinding Test

+

270

7Z01

9

F

LED

F

LED

2707

Z18

The binding test with the heating circuit controllers is made per channel. Use the Channel selection button to select the channel whose radio control link shall be tested. The LED of the selected channel blinks. Then, press briefly the multifunctionbutton.

RRV912

CH

NC 3P NO B U Q1 Q2 Y1 Y2LED

CH

F

270

7Z21

The binding test also displays the device number on the central apartment unit. With the help of that number, the device can be unambiguously identified device list.

Page 9: Synco living Train the Trainer Service & Maintenance August 2007

Page 9/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceRemoving / Deleting Devices

A device can be removed from the system in 2 different ways:

1. Disconnect the device.

2. Delete the device.

“Disconnect the device“ should be used whenever possible!

“Disconnect the device“ is used when the device to be disconnected still functions and when it is within the radio control range.

Use: A device was binded to a wrong room by mistakeA room sensor shall be replaced by a room unitIn a room, some other radiator control actuator shall

assume the function of lead controller

. . .

Page 10: Synco living Train the Trainer Service & Maintenance August 2007

Page 10/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceRemoving / Deleting Devices

What happens in the case of “Disconnect device“?The device will be removed from the central apartment unit‘s device listBidirectional devices will be reset to their supply state

Procedure:1. Select the respective menu on the central apartment unit:

Commissioning > RF connections > Rooms > Room x > Disconnect device

2. On the device to be disconnected, press the multifunction button until the LED starts blinking.

3. The central apartment unit confirms successful disconnection by displaying “Process finished“ and a bleep.

1. 2. 3.

Page 11: Synco living Train the Trainer Service & Maintenance August 2007

Page 11/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceRemoving / Deleting Devices

“Delete the device“ is used when the device to be disconnected is either faulty or no longer within the radio control range.

Use: A device in the plant is faulty and must be replacedAn extra device was binded by mistake and is no longer

present in the plant

Page 12: Synco living Train the Trainer Service & Maintenance August 2007

Page 12/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceRemoving / Deleting Devices

What happens in the case of “Delete device“?The device will only be deleted on the central apartment unit‘s device list.

The devices are not reset to their supply state, which means that they are still binded and try to make a connection to the “old“ central apartment unit! Battery.If the central apartment unit receives RF telegrams from deleted Synco 900 devices, a fault status message “Unknown device“ is displayed. Procedure:

1. Select the Device list menu on the central apartment unit:Main menu > Commissioning > Device list > Device x > Delete device

2. Select the device and dialog Delete device the dialog verifies one more time if the device shall really be deleted ok.

1. & 2

Page 13: Synco living Train the Trainer Service & Maintenance August 2007

Page 13/13 Train the Trainer - August 2007

BatteriesBinding Test FaultsRemoving / Deleting Devices

Service & MaintenanceFaults

Function “Faults“ is structured the same way as it is with the Synco 700 controllers:

Main menu > Faults > . . .

Faults current Display of the current faults (1…10)

Acknowledge faultsAcknowledgement of all faults Fault historyDisplay of the last 10 faultsFault status message busDisplay of the fault status message on the bus (only the most severe

fault is on the bus)

Delete faultsDeletion of the fault history