symmetrical faults 1
TRANSCRIPT
-
8/11/2019 Symmetrical Faults 1
1/31
1
EE 340EE 340Symmetrical FaultsSymmetrical Faults
-
8/11/2019 Symmetrical Faults 1
2/31
2
IntroductionIntroduction
AA faultfault in a circuit is any failure thatin a circuit is any failure thatinterferes with the normal systeminterferes with the normal systemoperation.operation.
Lighting strokes cause most faults onLighting strokes cause most faults on
highhigh--voltage transmission linesvoltage transmission linesproducing a very high transient thatproducing a very high transient thatgreatly exceeds the rated voltage ofgreatly exceeds the rated voltage ofthe line.the line.
This voltage usually causes flashoverThis voltage usually causes flashoverbetween the phases and/or the groundbetween the phases and/or the groundcreating an arc.creating an arc.
Since the impedance of this new pathSince the impedance of this new path
is usually low, an excessive currentis usually low, an excessive currentmay flow.may flow.
Faults involving ionized current pathsFaults involving ionized current pathsare also called transient faults. Theyare also called transient faults. Theyusually clear if power is removed fromusually clear if power is removed fromthe line for a short time and thenthe line for a short time and thenrestored.restored.
-
8/11/2019 Symmetrical Faults 1
3/31
3
IntroductionIntroduction
If one, or two, or all three phases break or
if insulators break due to fatigue or
inclement weather This fault is called a
permanent fault since it will remain after aquick power removing.
Approximately 75% of all faults in power
systems are transient in nature.
Selecting an appropriate circuit breaker(type, size, etc.) is important
-
8/11/2019 Symmetrical Faults 1
4/31
4
33--Phase fault current transients inPhase fault current transients in
synchronous generatorssynchronous generators
When a symmetrical 3-phase fault
occurs at the terminals of a
synchronous generator, the resultingcurrent flow in the phases of the
generator can appear as shown.
The current can be represented as atransient DC component added on top
of a symmetrical AC component.
Therefore, while before the fault, onlyAC voltages and currents were present
within the generator, immediately after
the fault, both AC and DC currents are
present.
-
8/11/2019 Symmetrical Faults 1
5/31
-
8/11/2019 Symmetrical Faults 1
6/31
6
Symmetrical AC component of the fault current:Symmetrical AC component of the fault current:
There are three periods of time:There are three periods of time: SubSub--transient period: first cycle or so after the faulttransient period: first cycle or so after the faultAC current is veryAC current is very
large and falls rapidly;large and falls rapidly;
Transient period: current falls at a slower rate;Transient period: current falls at a slower rate;
SteadySteady--state period: current reaches its steady value.state period: current reaches its steady value. It is possible to determine the time constants for the subIt is possible to determine the time constants for the sub--transienttransient
and transient periods .and transient periods .
7
-
8/11/2019 Symmetrical Faults 1
7/31
7
Fault current transients in machinesFault current transients in machines
The AC current flowing in the generator during the subThe AC current flowing in the generator during the sub--transient period is called the subtransient period is called the sub--transient current and istransient current and isdenoted bydenoted by II.. The time constantThe time constant of the subof the sub--transient current istransient current isdenoted bydenoted by TT and it can be determined from the slope. Thisand it can be determined from the slope. This
current may be 10 times the steadycurrent may be 10 times the steady--state fault current.state fault current. The AC current flowing in the generator during the transientThe AC current flowing in the generator during the transient
period is called the transient current and is denoted byperiod is called the transient current and is denoted by II. The. Thetime constanttime constant of the transient current is denoted byof the transient current is denoted by TT. This. Thiscurrent is often as much as 5 times the steadycurrent is often as much as 5 times the steady--state faultstate faultcurrent.current.
After the transient period, the fault current reaches a steadyAfter the transient period, the fault current reaches a steady--
state conditionstate condition IIssss.. This current is obtained by dividing theThis current is obtained by dividing theinduced voltage by the synchronous reactance:induced voltage by the synchronous reactance:
A
ss
s
E
I X=
-
8/11/2019 Symmetrical Faults 1
8/31
9
-
8/11/2019 Symmetrical Faults 1
9/31
9
Fault current transientsFault current transients
Example 12-1:A 100 MVA, 13.8 kV, Y-connected, 3 phase 60 Hz synchronous
generator is operating at the rated voltage and no load when a 3 phase fault occurs
at its terminals. Its reactances per unit to the machines own base are
1.00 ' 0.25 " 0.12sX X X= = =
and the time constants are
' 1.10 " 0.04T s T s= =The initial DC component in this machine averages 50 percent of the initial AC
component.
a)What is the AC component of current in this generator the instant after the fault?
b)What is the total current (AC + DC) in the generator right after the fault occurs?
c)What will the AC component of the current be after 2 cycles? After 5 s?
-
8/11/2019 Symmetrical Faults 1
10/31
11
-
8/11/2019 Symmetrical Faults 1
11/31
11
Fault current transientsFault current transients
a) The initial AC component of current is I = 34,900 A.
b) The total current (AC and DC) at the beginning of the fault is
1.5 " 52,350totI I A= =c) The AC component of current as a function of time is
( ) ( ) ( ) 0.04 1.1" '" ' ' 18,200 12,516 4,184t tt t
T Tss ssI t I I e I I e I e e A
= + + = + +
After 2 cycles t = 1/30 s and the total AC current is
17,910 12,142 4,184 24, 236
30I A
= + + =
At 5 s, the current reduces to
( )5 0 133 4,184 4, 317I A= + + =
12
-
8/11/2019 Symmetrical Faults 1
12/31
12
Fault current transientsFault current transients
Example 12-2: Two generators are
connected in parallel to the low-
voltage side of a transformer.Generators G1 and G2 are each rated
at 50 MVA, 13.8 kV, with a
subtransient resistance of 0.2 pu.
Transformer T1 is rated at 100 MVA,
13.8/115 kV with a series reactance of0.08 pu and negligible resistance.
Assume that initially the voltage on the high side of the transformer is 120 kV, that
the transformer is unloaded, and that there are no circulating currents between thegenerators.
Calculate the subtransient fault current that will flow if a 3 phase fault occurs at the
high-voltage side of transformer.
13
-
8/11/2019 Symmetrical Faults 1
13/31
13
Fault current transientsFault current transients
Let choose the per-unit base values for this power system to be 100 MVA and 115
kV at the high-voltage side and 13.8 kV at the low-voltage side of the transformer.
The subtransient reactance of the two generators to the system base is2
given newnew given
new given
V SZ Z
V S
=
The reactance of the transformer is already given on the system base, it will not
change
2
" "
1 2
13,800 100, 0000.2 0.4
13, 800 50, 000X X pu
= = =
0.08T
X pu=
Therefore:
14
-
8/11/2019 Symmetrical Faults 1
14/31
Fault current transientsFault current transients
The per-unit voltage on the high-voltage side of the transformer is
120,000
1.044115,000pu
actual valueV pubase value
= = =
Since there is no load on the system,
the voltage at the terminals of each
generator, and the internal generated
voltage of each generator must also
be 1.044 pu. The per-phase per-unit
equivalent circuit of the system is
We observe that the phases of
internal generated voltages are
arbitrarily chosen as 00. The phase
angles of both voltages must be the
same since the generators wereworking in parallel.
15
-
8/11/2019 Symmetrical Faults 1
15/31
Fault current transientsFault current transients
To find the subtransient fault current, we need to solve for the voltage at the
bus 1 of the system. To find this voltage, we must convert first the per-unit
impedances to admittances, and the voltage sources to equivalent current
sources. The Thevenin impedance of each generator is ZTh = j0.4, so theshort-circuit current of each generator is
1.044 02.61 90
04
oc
sc
th
VI
Z j
= = =
The
equivalent
circuit
-
8/11/2019 Symmetrical Faults 1
16/31
17
-
8/11/2019 Symmetrical Faults 1
17/31
Fault current calculations using the busFault current calculations using the bus
impedance matriximpedance matrix
So far, we considered simple circuits. ToSo far, we considered simple circuits. Todetermine the fault current in a system:determine the fault current in a system:
Create a perCreate a per--phase perphase per--unit equivalent circuit of the powerunit equivalent circuit of the power
system using either subsystem using either sub--transienttransient reactancesreactances (if(if subtransientsubtransientcurrents are needed) or transientcurrents are needed) or transient reactancesreactances (if transient(if transientcurrents are needed).currents are needed).
Add a short circuit between one node of the equivalent circuitAdd a short circuit between one node of the equivalent circuitand the neutral and calculate the current flow through that shorand the neutral and calculate the current flow through that shorttby standard analysis.by standard analysis.
This approach always works but can getThis approach always works but can getcomplex while dealing with complexcomplex while dealing with complexsystems. Therefore, a nodal analysissystems. Therefore, a nodal analysistechnique will be used.technique will be used.
We introduce a new voltage sourceWe introduce a new voltage source in thein thesystem to represent the effects of a faultsystem to represent the effects of a faultat a bus. By solving for the currentsat a bus. By solving for the currents
18
-
8/11/2019 Symmetrical Faults 1
18/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrix
Let us consider a power system
shown.
Assuming that we need to find the
sub-transient fault current at some
node in the system, we need to create
a per-phase, per-unit equivalentcircuit using sub-transient reactances
X. Additionally, we assume that the
system is initially unloaded, making
the voltages behind sub-transientreactances
1
2
"
"
1 0
1 0
A
A
E pu
E pu
=
=
19
-
8/11/2019 Symmetrical Faults 1
19/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrixThe resulting equivalent circuit is shown.
Suppose that we need to determine thesub-transient fault current at bus 2 when
a symmetrical 3 phase fault occurs on
that bus.
20
-
8/11/2019 Symmetrical Faults 1
20/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrixBefore the fault, the voltage on bus 2
was Vf. If we introduce a voltage source
of value Vfbetween bus 2 and theneutral, nothing will change in the
system.
Since the system operates normallybefore the fault, there will be no current
If through that source.
21
-
8/11/2019 Symmetrical Faults 1
21/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrixAssume that we create a short circuit on
bus 2, which forces the voltage on bus 2 to
0. This is the same as inserting anadditional voltage source of value -Vf in
series with the existing voltage source. This
make the total voltage at bus 2 equal to 0.
With this additional voltage source, there
will be a fault current If, which is entirely
due to the insertion of the new voltage
source to the system. Therefore, we can
use superposition to analyze the effects of
the new voltage source on the system.
The resulting current If will be the current
for the entire power system, since the othersources in the system produced a net zero
current.
22
Fault current calculations using theFault current calculations using the
-
8/11/2019 Symmetrical Faults 1
22/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrix
If all voltage sources except Vf are
set to zero and the impedances are
converted to admittances, the power
system appears as shown.
For this system, we can construct
the bus admittance matrix as
discussed previously:
16.212 5.0 0 6.667
5.0 12.5 5.0 2.5
0 5.0 13.333 5.0
6.667 2.5 5.0 14.167
bus
j j j
j j j jY
j j j
j j j j
=
The nodal equation describing this power system is
busY V = I
23
F lt t l l ti i thF lt t l l ti i th
-
8/11/2019 Symmetrical Faults 1
23/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrix
With all other voltage sources set to zero, the voltage at bus 2 is Vf,
and the current entering the bus 2 is If. Therefore, the nodal
equation becomes
11 12 13 14 1
"
21 22 23 24
31 32 33 34 3
41 42 43 44 4
0
0
0
f f
Y Y Y Y V
Y Y Y Y V I
Y Y Y Y V
Y Y Y Y V
=
where V1, V3, and V4 are the changes in the voltages at thosebusses due to the current If injected at bus 2 by the fault.
The solution to is found as
-1
bus busV = Y I = Z I
24
F lt t l l ti i thF lt t l l ti i th
-
8/11/2019 Symmetrical Faults 1
24/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrix
11 12 13 141
"
21 22 23 24
31 32 33 343
41 42 43 444
0
0
0
f f
Z Z Z ZV
Z Z Z ZV I
Z Z Z ZV
Z Z Z ZV
=
where Zbus = Ybus-1. Since only bus 2 has current injected at it, the
system reduces to
"
"
1 12
"
3 32
"
2
4
2
42
Which, in the case considered, is
f
f
f
f f
V Z I
V Z I
V
I
Z I
V Z
=
=
=
=
25
-
8/11/2019 Symmetrical Faults 1
25/31
Fault current calculations using theFault current calculations using the
impedance matriximpedance matrixTherefore, the fault current at bus 2 is just the prefault voltage Vfat
bus 2 divided by Z22, the driving point impedance at bus 2.
"
22
f
fVI
Z=
The voltage differences at each of the nodes due to the fault current
can be calculated by" 12
1 12
22
2
" 32
3 32
22
" 424 42
22
f f
f f
f f
f f
ZV Z I V
Z
V V VZ
V Z I V Z
ZV Z I V Z
= =
= =
= =
= =
26
-
8/11/2019 Symmetrical Faults 1
26/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
Assuming that the power system was running at no load conditionsbefore the fault, it is easy to calculate the voltages at every bus
during the fault. At no load, the voltage will be the same on every
bus in the power system, so the voltage on every bus in the system
is Vf. The change in voltage on every bus caused by the fault current
If is specified , so the total voltage during the fault is
12
22
12
22
1
2
32
3
22
4
1
2
32
3
22
4
4 42
22
2
22
1
0
1
1
f
f f
f
f f
ff f
f f
f
f
ZV
ZV VVV
V VVZ
VV VVZ
V
Z
ZV
VVZ
VZ
V Z
Z
VV ZV
Z
=
=
+ = +
Therefore, we can calculate the voltage at every bus in the
power system during the fault from a knowledge of the pre-fault
voltage at the faulted bus and the bus impedance matrix!
27
F lt t l l ti i th ZF lt t l l ti i th Z b t ib t i
-
8/11/2019 Symmetrical Faults 1
27/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
Once these bus voltages are known, we can calculate the faultOnce these bus voltages are known, we can calculate the faultcurrent flowing in the transmission line using bus voltages andcurrent flowing in the transmission line using bus voltages andthe bus admittance matrix.the bus admittance matrix.
The general procedure for finding the bus voltages and lineThe general procedure for finding the bus voltages and linecurrents during a symmetrical 3 phase fault is as follows:currents during a symmetrical 3 phase fault is as follows:
Create a perCreate a per--unit equivalent circuit of the power system. Includeunit equivalent circuit of the power system. Includesubtransientsubtransient reactancesreactances of each synchronous and inductionof each synchronous and inductionmachine when looking formachine when looking for subtransientsubtransient fault currents; includefault currents; includetransienttransient reactancesreactances of each synchronous machine when lookingof each synchronous machine when lookingfor transient fault currents.for transient fault currents.
Calculate the bus admittance matrix. Include the admittances ofCalculate the bus admittance matrix. Include the admittances ofall transmission lines, transformers, etc. between busses includall transmission lines, transformers, etc. between busses includingingthe admittances of the loads or generators themselves at eachthe admittances of the loads or generators themselves at eachbus.bus.
Calculate the bus impedance matrixCalculate the bus impedance matrix ZbusZbus as inverse of the busas inverse of the busadmittance matrix.admittance matrix.
Assume that the power system is at no load and determine theAssume that the power system is at no load and determine thevoltage at every bus, which will be the same for every bus and tvoltage at every bus, which will be the same for every bus and thehesame as the internal voltage of the generators in the system. Thsame as the internal voltage of the generators in the system. Thisisis the preis the pre--fault voltagefault voltage VfVf..
28
-
8/11/2019 Symmetrical Faults 1
28/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
5. Calculate the current at the faulted bus i as
"
,
f
f iii
V
I Z=6. Calculate the voltages at each bus during the fault. The voltage at
busj during a symmetrical 3 phase fault at the bus i is found as
1 ji
j f
ii
ZV V
Z
=
7. Calculate the currents in any desired transmission line during thefault. The current through a line between bus i and busj is found as
( )ij ij i jI Y V V=
29
-
8/11/2019 Symmetrical Faults 1
29/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
Example 12-4: The previous power system is working at no load
when a symmetrical 3 phase fault is developed on bus 2. a)
Calculate the per-unit subtransient fault current If at bus 2. b)
Calculate the per-unit voltage at every bus in the system during thesubtransient period. c) Calculate the per-unit current I1 flowing in line
1 during the subtransient period of the fault.
Following the 7 steps discussed before, we write:1.The per-phase per-unit equivalent circuit was shown earlier.
2.The bus admittance matrix was previously calculated as
16.212 5.0 0 6.667
5.0 12.5 5.0 2.5
0 5.0 13.333 5.0
6.667 2.5 5.0 14.167
bus
j j j
j j j jY
j j j
j j j j
=
30
F l l l i i h Z b i
-
8/11/2019 Symmetrical Faults 1
30/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
3. The bus impedance matrix calculated using Matlab as the inverse
of Ybus is0 0.1515 0 0.1232 0 0.0934 0 0.1260
0 0.1232 0 0.2104 0 0.1321 0 0.14170 0.0934 0 0.1321 0 0.1726 0 0.1282
0 0.1260 0 0.1417 0 0.1282 0 0.2001
bus
j j j j
j j j jZj j j j
j j j j
+ + + +
+ + + + = + + + +
+ + + +
4. For the given power system, the no-load voltage at every bus isequal to the pre-fault voltage at the bus that is
1.00 0fV pu=
5. The current at the faulted bus is computed as
"
,222
1.00 04.753 90
0.2104
f
f
VI pu
Z j
= = =
31
F lt t l l ti i th ZF lt t l l ti i th Z b t ib t i
-
8/11/2019 Symmetrical Faults 1
31/31
Fault current calculations using the ZFault current calculations using the Z--bus matrixbus matrix
6. The voltage at busj during a symmetrical 3 phase fault at bus I
can be found as
12
1
22
2
32
3
22
42
4
22
0.1232
1 1 1.0 0 0.414 00.2104
0.0 0
0.1321
1 1 1.0 0 0.372 00.2104
0.14171 1 1.0 0 0.327 0
0.2104
f
f
f
Z j
V V puZ j
V pu
Z j
V V puZ j
Z jV V pu
Z j
= = =
=
= = =
= = =
7. The current through the transmission line 1 is computed as
( ) )12 12 1 2 0.414 0 0.0 0 5.0 2.07 90I Y V V j pu= = =
Thats it!