1
Swiss fire regulations
according to VKF
Possibilities of
timber constructions
Reinhard Wiederkehr
Makiol + Wiederkehr, Dipl. Holzbau-Ingenieure HTL/SISH, CH-Beinwil am SeeMember of the project team „fire safety for timber constructions“, Lignum, holz 21
Fire safety for timber constructions
13. September 05, Tallinn, Estonia
![Page 2: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/2.jpg)
2
Content
• Swiss fire regulations according to VKF
• Structures – fire compartments
• Facades
• Summary
![Page 3: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/3.jpg)
3
Swiss fire regulations according to VKFSwiss fire regulations according to VKFSwiss fire regulations according to VKFSwiss fire regulations according to VKF
www.vkf.chEdition 2003
![Page 4: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/4.jpg)
4
Fire resistance:
Load bearing capacity = R
Integrity = E
Thermal insulation = I
Classification according to EN codes
Demand for non-combustible building materials must be stated.
nbb ���� non-combustible (nicht brennbar)
REI 60 ���� timber constructions are possible
REI 60 (nbb) ���� no timber constructions are allowed
![Page 5: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/5.jpg)
5
• Timber constructions
• Non-combustible outercladdings with a fireresistance for 30 minutes (K30)
• Non-comubustibleinsulation layers
REI60/EI30 (nbb)
• Timber constructions
• Combustible insulationslayers covered withboard for 30 minutes fireresistance
REI 60
Verkleidung EI 60 Verkleidung EI 30 (nbb)
Verkleidung EI 30 (nbb)Verkleidung EI 60
R 60/EI 30 (nbb)
EI 60/EI 30 (nbb)
REI 60/EI 30 (nbb)
R 60
REI 60
EI 60
Verkleidung EI 30
Verkleidung EI 30
EI 60
REI 60
R 60
Timber constructions with a 60 minutes fire resistance
REI 60
REI 60 / EI 30 (nbb)
REI 60
![Page 6: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/6.jpg)
6
R 60 (nbb)
EI 60 (nbb)
REI 60 (nbb)
REI 60 (nbb)
R 60 (nbb)
EI 60 (nbb)
Constructions with a 60 minutes fire resistance
• Without anycombustiblebuilding materialsonly:
• Reinforcedconcrete
• Brick
• Steel
• Non-combustibleinsulation
REI 60 (nbb)
REI 60 (nbb)
REI 60 (nbb)
![Page 7: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/7.jpg)
7
Specially applied concept
of fire safety
Standard concepts of fire safety
ExceptionTechnical(Sprinkler)
Constructional
Regulations for fire safety
Building fullfills the fire safety concept
Construc-tional
Technical
Constructional
Organi-zational
Technical
Construc-tional
Technical
Fire safety concepts
Organi-zational
Organi-zational
![Page 8: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/8.jpg)
8
One-familiy houses
![Page 9: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/9.jpg)
9
Single storey buildings
![Page 10: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/10.jpg)
10
Attic / top floor
![Page 11: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/11.jpg)
11
2 storey buildings
![Page 12: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/12.jpg)
12
3 storey buildings
Constructional concept of apartments, offices and schoolsStructure R30 timber constructionFire compartment EI30 timber constructionStaircase REI60/EI30(nbb) timber construction with a
non-combustible cladding
![Page 13: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/13.jpg)
13
3 storey buildings
Constructional concept of apartments, offices and schoolsStructure R60 timber constructionFire compartment EI60 timber constructionStaircase REI60 (nbb) no timber construction
![Page 14: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/14.jpg)
14
4 storey buildings
Concept with sprinkler of apartments, offices and schools
Structure R30 timber constructionFire compartment EI30 timber constructionStaircase REI60 (nbb) no timber construction
![Page 15: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/15.jpg)
15
5 and 6 storey buildings
Constructional concept of apartments, offices and schools
Structure R60/EI30 (nbb) timber construction with a non-combustible claddingFire compartment EI60/EI30 (nbb) timber construction with a non-combustible claddingStaircase REI60 (nbb) no timber constructionQuality management system
![Page 16: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/16.jpg)
16
5 and 6 storey buildings
Concept with sprinkler of apartments, offices and schools
Structure R60 timber constructionFire compartment EI60 timber constructionStaircase REI60 (nbb) no timber constructionQuality management system
![Page 17: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/17.jpg)
17
Facades / external walls
Fire safety on facades
Testing of singlebuilding
components (SBI ornational tests)
testing the externalwall system
6.35.2 (7)4.2 (1) (7)Lichtbänder
6.34.1 (5) oder
5 (200˚C).1 (6)4.1 (1) (4)Wärmedämmschicht /
Zwischenschicht
6.34.3 (1) (2) oder
6.3 (3)4.2 (1)Aussenschicht
Hoch-häuser
4 Geschosse
bis Hoch-
hausgrenze
≤ 3
Geschosse
Anforderungen an das Brandverhalten bei Aussenwänden
Large scale tests
![Page 18: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/18.jpg)
18
Large scale test V4 (MFPA Leipzig)
5th minute
of the test
10th minute
of the test
15th minute
of the test
20th minute
of the test
![Page 19: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/19.jpg)
19
� October 2003
� 4 ½ storey reinforcedconcrete boardconstruction
� Full scale test
� Several timber claddingsand constructional firesafety measures
Full scale test in Merkers (Germany)
40.1
m
10.1 m
13.8
m
Total of 700 m2 facade in timber construction
![Page 20: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/20.jpg)
20
Full scale test V2 in Merkers (Germany)
7th minute of the testFlashover
11th minute of the testInflaming facade
(Simulation of the cross-ventilation)
32th minute of the testTimber facade is not burning
anylonger on ist own
![Page 21: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/21.jpg)
21
Timber on facades
� Combustion aloneisn‘t substantial
� Overall construction isessential
� Well constructedfacades achievefull protection
![Page 22: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/22.jpg)
22
Project example
� Timber facade of a 6-storey building
� variance
� Steel sheet sticks out the facade by 200 mm
Housing estate Herti 6, Zug (Switzerland)
![Page 23: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/23.jpg)
23
![Page 24: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/24.jpg)
24
Multi-storey timber constructions
![Page 25: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/25.jpg)
25
REI 60 / EI 30 (nbb)timber construction
with non-combustiblecladding
REI 60timber construction
F 30bbtimber construction
Up to 2004
Structures and fire compartements
REI 30timber construction
since 2005
Application: multy storey appartment, office or school
Constructional standard fire safety concepts
![Page 26: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/26.jpg)
26
Since 2005 standard fire safety concepts
Timber constructions in Switzerland
![Page 27: Swiss fire regulations according to VKF](https://reader030.vdocuments.mx/reader030/viewer/2022032817/623f29b554902f216515eabc/html5/thumbnails/27.jpg)
27