Surge Protection- General Recommendations Written by: Chris Quillen, MSEE, P.E. (TN)- Principal Engineer- TVA Customer Service
Installing Surge Protection Devices (SPDs) can help prevent the electrical equipment damage associated with lightning activity. SPDs operate by diverting surge energy to ground before the energy can pass to sensitive equipment. SPDs must have a reliable, low impedance path to ground in order to function effectively. Proper electrical system grounding and bonding is essential for operation of sensitive equipment and is also necessary to allow surge protective devices to function properly. The National Electrical Code (NEC) article 250 contains the requirements for proper grounding and bonding.
Grounding and Bonding All SPDs require a good connection to ground (the earth). A minimum of one Ground rod should be installed at all buildings with electric power. Depending on soil conditions, it may be necessary to install a second ground rod to supplement the first ground rod. Concrete footer grounds (using rebar or buried copper wires) can serve as one ground rod. All utilities that enter a facility should be electrically connected (bonded) together. This includes:
– Metal gas piping – Metal water piping – Telephone service – Cable TV service – Satellite TV service – TV antenna service
Telecommunication Equipment NEC articles 800, 810, and 820 list the requirements for grounding and lightning protection on telecommunications services. Any telecommunications service must have a primary lightning protector or grounding block installed where the service enters the house. The protectors and grounding blocks should be connected to the electrical ground. If communication equipment such as TV Antennas, Satellite Dishes, or Telephone services enter the house more than 25 feet away from the electric service, the communication equipment must have its own nearby ground rod and a #6 AWG copper conductor to connect the telecommunication ground rod to the electrical ground.
Surge Protection for Electrical Equipment TVA recommends a multi-level approach to applying electrical system SPDs:
1) Main Service Entrance- at meter base, main panel, or closest main panel to service entrance.
2) Distribution sub-Panel (if present)- at all sub-panels that supply sensitive equipment such as electronics, computers, televisions, or air conditioning equipment.
3) Point-of-use- Surge protected multi-outlet strips where sensitive equipment (such as a computer) connects to wall outlet.
Applying surge protection in this fashion provides three barriers between the electrical system and the end-use equipment. These barriers offer three distinct points to stop a surge before it can damage sensitive equipment. Be sure to follow all manufacturers’ instructions regarding the installation of permanently mounted SPDs. Improper installation techniques can degrade or negate the performance of SPDs. The units should be installed so that the wires between the SPD and the circuit breaker connections are kept as short and straight as possible. Do not install the SPD wires with sharp bends or kinks. Specifications to look for when purchasing SPDs for electrical systems:
• UL 1449 (3rd Edition) listing- this is the latest UL safety standard for SPDs • For Line Voltage Models, the SPD should provide multi-mode protection against Line
to Line, Line to Neutral, and Line to Ground transients • Line Voltage Models should also have indicator lights that display the operational status
of the SPD. These lights should be checked on a regular basis and especially after a thunderstorm.
• Point-of-use surge protectors (plug strips) should be chosen which provide connections for all utilities that connect to a particular device. Example: A point-of-use protector for a television should also have provisions to connect the cable TV service. A point-of-use protector for a computer should also have provisions to connect the telephone/DSL/internet line.
The installation of all SPDs should comply with NEC article 285. All permanently mounted SPDs should be connected to a circuit breaker. Reference the manufacturer’s specific instructions for circuit breaker ratings.
BackUp Power It is often convenient to provide uninterruptible power for computers so that work in progress is not lost when the power unexpectedly goes out. Some newer flat screen televisions also require a cool-down time after they are turned off. When the power goes out, the TVs are not able to cool down as needed and damage can result. TVA recommends that you consider installing uninterruptible power supplies (UPS) for equipment such as computers and televisions (especially if cool down time is necessary). UPSs typically incorporate built-in SPDs and are available with telephone and cable surge protection connections.
AppendixInformation Included in the appendix is information on the following:
– Brochure for Eaton Electrical Corporation’s brand of permanently mounted electrical system surge suppressors for 120/240 volt applications at main panels.
– A brochure for a Citel coax (cable TV) surge protector. – Brochures for some plug-strip type SPDs for use at sensitive electronic equipment. – Brochure for Tripp-Lite Uninterruptible Power Supply
TVA does not endorse one manufacturer over another, the information is only provided as an example of equipment that meets the recommended specifications. Many vendors make equipment meeting these recommendations, TVA recommends obtaining multiple quotes for surge protection equipment.
Introduction
Since 1980, Eaton's Innovative Technology has provided Surge Protective Devices (SPDs) to power quality equipment users around the world. Whatever your electrical surge protection need may be, Eaton’s Innovative Technology has a Surge Protective Device to fill it!
General Features
Parallel configured, hard wire connected, Surge •Protective Device
Peak Surge Current — • XT50: 50 kA XT100: 100 kA
Application — Medium and low exposure level AC power •service entrances, branch panels and/or individual equipment disconnects feeding all types of loads
Warranty — 5 Year free replacement•
Unit Listings — UL• ®1449 Third Edition; permanently connected; Type 1 and 2
Nominal discharge current — 20 kA•
SCCR — 100 kA•
CE Compliant to IEC 61643-1 Test Classification I & II•
Vibration Tested to IEC 60255-21-1 & -2•
Manufacturer Qualifications — ISO• ® 9001:1994 Quality System Certification BSI FM 30833
Mechanical and Electrical Features
Enclosure — NEMA• ® 4X (IP56) polycarbonate weatherproof enclosure (meets or exceeds NEMA 1, 2, 4, 4X, 12, 13)
Mounting — Threaded conduit fitting and multi-point case •mounting holes (external mounting feet available separately)
Connection — #10 (6 mm• 2) stranded wire
Weight — • ≈2.0 lbs (1.0 kg)
Operating Temperature — –13 to 140°F (–25 to 60°C)•
Protection — All Modes•
Input Power Frequency — 47–420 Hz (50/60 Hz typical)•
Diagnostics — LED indicators, 1 per phase, normally ON •
Optional Features and Equipment
External Mounting Feet•
Standard Dimensions
Submittal Spec SheetEaton Innovative Technology® XT50/100 Models Surge Protective Device
SECTION A-A
A A1.12 [28.5]
3.53 [89.7]
4.17 [106.0]
4.72 [119.9]
5.60 [142.3]
Ø 0.17 [4.3]
0.75 [19.0] InternallyThreaded Conduit Fitting
Mounting HolesUnder Lid (4)
Mounting HoleShafts
Dimensions are in inches [mm]
4.72
[11
9.9]
3.39
[86
.0]
2.36
[59
.9]
XT50/100
Performance Data
XT50 System Configuration
Nominal System Voltage
MCOV UL 1449-3 VPR *
L-L L-N L-G N-G L-L L-N L-G N-G
1P201 Single-Phase 2w + grnd
200, 208, 220, 230, 240, 277
-- 320 640 320 -- 1200 2000 1200
1S101 Split-Phase 3w + grnd
100/200, 110/220, 120/240
300 150 300 150 1200 700 1200 800
3Y101 3-Phase Y/Star 4w + grnd
100/175, 110/190, 120/208, 127/220
300 150 300 150 1200 700 1200 800
3Y201 3-Phase Y/Star 4w + grnd
220/380, 230/400, 240/415, 277/480
640 320 640 320 2500 1200 2000 1200
NN201 3-Phase Δ 3w + grnd
200, 208, 220, 230, 240
640 -- 320 -- 2000 -- 1200 --
NN400 3-Phase Δ 3w + grnd
380, 400, 415, 440, 480
1100 -- 550 -- 3000 -- 1800 --
XT100
1P201 Single-Phase 2w + grnd
200, 208, 220, 230, 240, 277
-- 320 320 320 -- 1200 1200 1200
1S101 Split-Phase 3w + grnd
100/200, 110/220, 120/240
300 150 150 150 1200 700 800 700
3Y101 3-Phase Y/Star 4w + grnd
100/175, 110/190, 120/208, 127/220
300 150 150 150 1000 600 700 700
3Y201 3-Phase Y/Star 4w + grnd
220/380, 230/400, 240/415, 277/480
640 320 320 320 1800 1200 1200 1200
NN201 3-Phase Δ 3w + grnd
200, 208, 220, 230, 240
640 -- 320 -- 1800 -- 1200 --
NN400 3-Phase Δ 3w + grnd
380, 400, 415, 440, 480
1100 -- 550 -- 3000 -- 1800 --
* UL 1449 3rd Edition VPR (Voltage Protection Rating) Test environment: All tests performed with 6” lead length, positive polarity.
Innovative Technology is a registered service mark of Eaton Corporation.UL is a federally registered trademark of Underwriters Laboratories Inc.ISO is the registered trademark and sole property of the International Organization for Standardization.NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association.
XT –
Per Phase Peak Surge Current (kA)
50 100
Configuration & Voltage Ranges (Vac)
1P201 = Single-Phase – 200, 208, 220, 230, 240, 2771S101 = Split-Phase – 100/200, 110/220, 120/2403Y101 = Three-Phase WYE (Star) – 100/175, 110/190, 120/208, 127/2203Y201 = Three-Phase WYE (Star) – 220/380, 230/400, 240/415, 277/480NN201 = Three-Phase Delta – 200, 208, 220, 230, 240NN400 = Three-Phase Delta – 380, 400, 415, 440, 480
© 2007–2008 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. PS01006046EMarch 2008
Eaton CorporationInnovative Technology SPD Products1000 Cherrington ParkwayMoon Township, PA 15108-4312USAPhone: 1-800-525-2000Web: www.Eaton.com
Cutler-Hammer
Ordering Guidelines
3Pjj
5kA transient amps protection (10/350μs) DC Pass to +/-48V VSWR < 1.2
Insertion Loss < 0.1dB Bi-directional, series installed Waterproof Removable GDT
Ordering information
Max RF Power
25 = 190W 50 = 780W
Connecto r Type
Gender Type P8AX __- __- ___
20kA transient amps protection (8/20μs)
09 = 25W N, TNC, SMA, F, BNC, 7/16 (Din)
MF = Male/Bulkhead Female
FF = Female/Bulkhead Female
High-Frequency Surge Protection
P8AX SeriesUniversal Gas Tube Coaxial Surge Protectors
CITEL INC | 11381 Interchange Circle South | Miramar, FL 33025 USAToll Free: 800.248.3548 | Tel: 954.430.6310 | Fax: 954.430.7785 | www.citel.us | [email protected]
The P8AX series coaxial surge protectors have been designed to protect antennas, microwaves, broadband applications, two-way radios, cellular, GPS and CATV equipment against lightning surges and electrical transients. They are a first line of defense for your sensitive equipment.
The P8AX series employs a patented gas tube, are waterproof (IP65) and available with three grounding options: M6 ground screw, bulkhead or optional mounting bracket.
Tower Mounted Amplifiers (TMA)Global Positioning Systems (GPS)Antenna SystemsTower Top Electronics (TTE)Transmitters and RecieversWiFiBroadband WirelessWiMax Broadband wireless
1 Impedance for F-Type Connector is 75 Ohms.
CITEL Part Number P8AX09 P8AX25 P8AX50
DC-5GHz DC-5GHz DC-5GHz
90-130V 200-300V 400-600V
Gas Discharge Tube Gas Discharge Tube Gas Discharge Tube
Frequency Range
DC Turn-On (Breakdown)
Technology
≤0.1db ≤0.1db ≤0.1db
≥20db ≥20db ≥20db
lnsertion Loss
Return Loss
<1.2:1 <1.2:1 <1.2:1
20kA 20kA 20kA
VSWR
lpeak (8/20 μs)
25W 190W 780W
10A 10A 10A
Max Power
Max current
50 omhs 50 omhs 50 omhs
Series (bi-directional) Series (bi-directional) Series (bi-directional)
lmpedance
Connection Method
N, TNC, SMA,F, BNC, 7/16
N, TNC, SMA,F, BNC, 7/16
N, TNC, SMA,F, BNC, 7/16
M6 Screw, Bulkhead, Bracket
M6 Screw, Bulkhead, Bracket
M6 Screw, Bulkhead, Bracket
Connectors
Grounding
IP65 IP65 IP65
-50 C to +85 C -50 C to +85 C -50 C to +85 C
Enviromental Rating
Operating Temp
13,000 ft (4,000m) 13,000 ft (4,000m) 13,000 ft (4,000m)up to 5 to 95%non-condensing, up to 100%
up to 5 to 95%non-condensing, up to 100%
up to 5 to 95%non-condensing, up to 100%
Operating Altitude
4.4 oz 4.4 oz 4.4 ozWeight
Relative Humidity
Characteristics
1 1 1
◦ ◦ ◦ ◦◦ ◦
Part# L632 REV.A
Applications for:• Computers• Printers• Copiers• Appliances• TV’s
Front cover can easily be removed & painted to match any wall color.
Measurements Weights Qty. UPCProduct: 1.625” x 3.25” x 5.25” .65 lb. 1 -Individual Box: 3” x 4.75” x 6.25“ .75 lb. 1 050616008754 Inner Pack: 6.125” x 15’ x 6.375” 5 lbs. 6 30050616008755 Master Pack: 15” x 10” x 13” 21 lbs. 24 50050616008759
TYPICAL INSTALLATION
Multi-Use AC SurgeProtection
• EMI/RFI Filtration Circuitry for Clean, Unimpeded Power.
• Protect or DisconnectTM
Circuitry
• Two Diagnostic Lights (LED) Power On/Protection OK and Line Fault
• Thin Profile - Only 1.5 inches deep. • Two AC Outlets
• Removable, Paintable Cover
Surge Protect
Noise Filter
Connected Equipment Longevity
Lifetme Warranty
Panamax MD2
800-472-5555 • www.panamax.com
VersatileOutlet
Orientation
MEASUREMENTS, WEIGHTS, QTYS & UPC FOR ORDERING & SHIPPING
PROPERLY GROUNDED AC OUTLET
MD2
AC LINE
AC LINE
TYPICAL INSTALLATION
AC POWERProtect or Disconnect™ Circuitry___________________YesLine Voltage_______________________120VAC, 50/60HzInitial Clamping Level_________________________ 200VVoltage Protection Rating (UL1449 3rd Edition, 3,000A) L-N 400V, L-G 500V, N-G 400 V
Nominal Discharge Current____________________3,000A Protection Modes_____________________ L-N, L-G, N-G
Maximum Current Rating_________________ 15A (1800W)
EMI/RFI Noise Filtration__________ 50dB (100kHz – 1 MHz)
Response Time_____________________ < 1 nanosecond
Single Pulse Energy Dissipation_____________1350 Joules
Peak Impulse Current______________________ 60,000 A
Catastrophic Surge Circuit______________________ Yes
Thermal Fusing______________________________ Yes
SPECIFICATIONS
Design and specifications subject to change without notice due to product improvement.
PM
8-A
V AC power, telephone and coax lines can provide direct pathways for surges
and spikes to enter and damage expensive audio/video equipment.
PM8-AV eliminates voltage irregularities & protects your AV system.
PM8-AV
The PM8-AV’s Power Cleaning and Filtration
eliminate common symptoms of
contaminated power (including loss
of detail, pops, hisses, hums and visual
artifacts) and allows your A/V
equipment to perform up to its
full capability.
L628-A 10/09
Exclusive Protect or Disconnect™ circuitry. In the
event of a catastophic surge such as lightning,
it completely disconnects AC power to
connected equipment.
SURGE PROTECTION
IMPROVES PICTURE & SOUND QUALITY
1
2
www.panamax.com
Lifetime Product Warranty*
Product Upgrade Policy*
$100,000 Limited Connected Equipment
Protection Policy*
*See actual warranty documentation.
HD Flat Panel
Display Systems
(Plasma, LCD, CRT’s
and Receivers)
SPECIFICALLY DESIGNED AND ENGINEERED TO PROTECT:
MODEL NO.
PM8-AV
HOME THEATER POWER MANAGEMENT
Protects equipment from electrical surges that travel over telephonelines.
Protects equipment from electrical surges that travel over cable, satellite and antenna lines.
Exclusive Protect or Disconnect™ circuitry.
Hi-Def Designed to work with your High Definition system.
More outlets for all of your power needs.
Cable/Sat Protection
Telephone line protection
Surge Protection
Eight Outlets
Hi Def Ready
8
© 2009 Panamax Inc. Panamax and the Panamax logo are registered US trademarks of Panamax.
PM8-AV
L628-A 10/09
FEATURES
www.panamax.com
HOME THEATER POWER MANAGEMENT
Power ON/Protection OK LED(green) Normally ON; indicatesthat the surge protector isfunctioning properly and that allconnected equipment is protected.
Ground OK LED(green) Normally ON; indicatesthat the wall outlet is properlywired and grounded.
IN / OUT Telco Connectors
CATV / Satellite Connectors2 sets of IN /OUT, universal coaxialconnectors
6 ft, Power Cord with Right Angle45 degree Offset Plug
8 AC Outlets with transformer spacing between outlets
ON / OFF Power Switch and Circuit Breaker Combination
1
2
Accepts Panamax add on data line protection modules, (modules sold separately).
AC Specifications:Protect or Disconnect™ Circuitry___________________ YesThermal Fusing_______________________________ YesLine Voltage________________________120VAC, 50/60HzInitial Clamping Level______________200V Peak, 141V RMSVoltage Protection Rating (UL1449 3rd Edition, 3,000A)__500VProtection Modes______________________ L-N, L-G, N-GMaximum Current Rating__________________15A (1800W)EMI/RFI Noise Filtration___________ 45dB (100kHz – 1 MHz)Response Time______________________________ < 1nsSingle Pulse Energy Dissipation______________1125 JoulesPeak Impulse Current_______________________ 52,000 A
Universal Cable / Satellite Protection: HD Ready___________________________________ YesBi-Directional________________________________ YesShielded____________________________________YesClamping Level ______________________________75VFrequency Range_____________________0MHz – 2.2 GHz Insertion Loss_____________________________ <0.5dBConnections___________________Female "F", Gold Plated
Telco Protection: Fuseless/Auto-Resettable ________________________YesClamping Level______________________________260VCapacitance _________________________ 30 pf (approx.)Suppression Modes______________ Metallic & LongitudinalWires Protected_____________________2 wire, 1 pair (3,4)Connectors________________________________ RJ-11
SPECIFICATIONS
Design and specifications subject to change without notice due to product upgrades and improvements.
UPC’S, QUANTITIES, WEIGHTS & MEASUREMENTS FOR ORDERING & SHIPPING
Dimensions Weight Dimensions Weight UPC Qty. Dimensions Weight UPC
12” x 5” x 1.75” 3.5 lbs 13.25” x 9.5” x 2.5” 4 Lbs 0 50616 00872 3 6 17.25” x 8.5” x 14” 25 Lbs 50 050616 00872 8
MODEL PM8-AV SINGLE UNIT CARTON MASTER CARTON
1690 Corporate Circle, Petaluma, CA. 94954 • 800-472-5555 or 707-283-5900 • Fax 707-283-5901
(12.5 in. L Including brackets)
Accessory Included:3 ft. Coax Cable
Tripp Lite1111 West 35th Street
Chicago, IL 60609 USATelephone: +(773) 869 1234
E-mail: [email protected]
Model #: HT850UPSHome Theater Ultra-compact Line-Interactive 120V UPS with USB port
Highlights
750VA ultra-compact 120V line interactive UPS for home theater
Corrects brownouts and overvoltages from 83V to 147V
6 UPS battery supported outlets, 6 surge-only outlets
USB port, TEL/DSL/Coax protection, Wall mountable, 98% efficient
NEMA 5-15P input plug and 12 NEMA 5-15R outlets
DescriptionTripp Lite's HT850UPS line-interactive UPS offers complete protection for PCs, workstations and other sensitive electronics in an ultra-compact,
mountable housing. Internal UPS circuits support individual VCR/DVR components as long as 3 hours during power failures. Prevents data loss and
system downtime by providing battery-supported AC output during blackouts and automatic voltage regulation (AVR) during brownouts and
overvoltages. Includes 12 output receptacles, 4 of which are widely spaced to accommodate large transformer blocks without obscuring adjacent
outlets. 6 outlets offer full battery support and surge suppression, protecting computers, monitors and other vital system components from power
loss. 6 additional outlets with surge suppression only are ideal for printers and other peripherals not requiring battery support. Single-line telephone
suppression jacks protect modems, fax machines, cordless phones or other equipment with a DSL or standard dialup RJ-11 phone line connection.
Set of gold coaxial line surge suppression jacks protect CATV, satellite or broadcast antenna connections. USB port with included cable and
PowerAlert monitoring software enables safe unattended system shutdown in case of extended power failure. HID-compliant USB interface enables
integration with built-in power management and auto-shutdown features of Windows and Mac OS X. Audible alarm and front panel LEDs offer
status information regarding line and battery power operation. 450W power-handling ability supports entry-level PCs for up to 35 min. during power
failures. $100,000 Ultimate Lifetime Insurance (USA and Canada only).
Package Includes
HT850UPS UPS SystemPowerAlert Software CD-ROM, USB cable, RJ-11 phone cable, 6-foot gold coax cableInstruction manual with warranty information
Features
HT850UPS line-interactive UPS offers protection from blackouts, brownouts and surges on AC, tel/DSL and coaxial line connectionsBuilt-in automatic voltage regulation (AVR) boosts brownouts as low as 83V and reduces overvoltages up to 147V back to usable 120Vnominal levels12 AC outlets, 4 of which are widely spaced to accommodate large transformer blocks without obscuring adjacent outlets6 UPS battery-supported outlets protect computers, monitors and vital system peripherals; 6 additional surge suppression-only outletsprotect system accessories not requiring battery supportProvides battery-derived AC output during blackouts, voltage boost during brownouts and voltage reduction during overvoltages750VA/450W power-handling ability supports a variety of home theater equipment, workstations and other sensitive electronicsSupports individual VCR/DVR components as long as 3 hours during power failures
Built-in single-line tel/DSL surge suppression protects modems, fax machines or cordless phones. Built-in coaxial line surge suppressionprotects CATV, satellite or broadcast antenna connectionsUSB port, included USB cable and PowerAlert Software offer safe, unattended shutdown without data loss during extended outagesHID-compliant USB interface enables integration with built-in power management and auto-shutdown features of Windows and Mac OS X. Supports Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application/OS or hardpower off/on reboot of connected equipment; ideal for unattended kiosk applicationsHot-swappable user battery replacement supported via battery access doorSpace-saving, ultra-compact housing fits almost anywhereKeyhole mounting flanges enable secure wallmount installation
Specifications
OUTPUT
Output Volt Amp Capacity(VA)
750
Output Watt Capacity (watts) 450
Nominal Output Voltage(s)Supported
115V; 120V
Frequency compatibility 60 Hz
Output voltage regulation(line mode)
+8%, -21%
Output voltage regulation(Battery mode)
115V (+/- 5%)
Built-in UPS outputreceptacles
12 5-15R outlet(s)
Surge suppression onlyoutlets
6 UPS outlets, 6 surge-only outlets
Output AC waveform (ACmode)
Sine wave
Output AC waveform(battery mode)
PWM sine wave
INPUT
Rated input current (atmaximum load)
12A
Nominal Input Voltage(s)Supported
120V AC
UPS input connection type 5-15P
UPS Input cord length (ft.) 6
UPS Input cord length (m) 1.8
Recommended ElectricalService
15A 120V
BATTERY
Full load runtime (minutes) 4 min. (450w)
Half load runtime (minutes) 10 min. (225w)
DC system voltage (VDC) 12