Surge protection for
POWER SUPPLY SYSTEMSSPDs for low-voltage installations and equipment
-
8/18/2019 Surge protection for power systems
2/117www.dehn.de14
-
8/18/2019 Surge protection for power systems
3/117
Easy cho ice 16
Com bined SPDs – Type 1 25
Light ning current arresters – Type 1 39
N-PE Lightning current arresters – Type 1 5 7
Surge arresters – Type 2 63
Surge arresters – Type 3 97
Accessories 123
POWER SUPPLY SYSTEM S
www.dehn.de 15
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
CONTENTS
Accessories
Surge Arresters –Type 3
Lightning CurrentArresters – Type 1
N-PE Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
Surge Arresters –Type 2
-
8/18/2019 Surge protection for power systems
4/117
POWER SUPPLY SYSTEM S
www.dehn.de
Easy Choice
16
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
L1 L2 L3 N PE
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3
D E H N
g u a r
d
D G M
O D 2
7 5
N
9
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3
D E H N
g u a r
d
D G M
O D 2
7 5
N
9
L1 L1 ' L2 L2 ' L3 L3'
N /́ PE N N /P EN
DEHNbloc DB 3 255 H
L1 L1 ´ L2 L2 ´
PEN
L3 L3´
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
9
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
ÜS-Schutz
DEHNf lex
C a b l e l e n g t h ≥ 5 m
16 A
S o c k e t O u t l e t
i n d i c a t i o n
o f
i n t e r f e r e n c e
1 x DSA 2 3 0 LA Part N o. 92 4 3 7 0for cable ducts
1 x STC 2 3 0 Part No. 92 4 3 50for existing socket out lets
with remote signall ing contact:1 x D G M T NS 2 7 5 FM Pa rt N o. 95 2 40 5
1 x D V M TN C 2 55 Pa rt N o. 95 1 30 0a l t .1 x DV M TNC 255 FM Part No. 951 3 05also available as
1 x D V M TN S 2 55 Pa rt No . 9 5 1 4 0 0a l t .1 x DV M TNS 255 FM Part No. 951 4 05
1125 A
SPD Type 2(Surge arrester)
1125 A
SPD Type 2(Surge arrester)
1 x DG M TN S 2 75 Part N o. 95 2 4 0 0
Cable length ≥ 1 5 m
SPD Type 1(Lightning current arrester)
1 x DB 3 2 55 H Part No. 90 0 1 20
a l t .3 x DB 1 2 55 H Part No. 90 0 2 221 x M VS 1 6 Part No. 90 0 8 15
1315 A
SPD Type 1(Coordinated lightning
current arrester)
DEHNbloc ® MCoordinated to DEHNguard ®
without additional cable length.
3 x D B M 1 2 5 5 FM Pa rt N o. 96 1 1 251 x M VS 1 6 Part N o. 90 0 8 15
a l t .3 x DB M 1 2 55 Part N o. 96 1 1 201 x M VS 1 6 Part N o. 90 0 8 15
1315 A
M
a i n
D i s t r i b u t i o n
B o a r d
S u b d i s t r i b u t i o n
B o a r d
SPD Type 1(Combined lightning current
and surge arrester)
DEHNvent il ®
Directly coordinated toRed/Line SPDs Type 2 and 3
without additional cable length.
For serial connection please see also page 19
1315 A
SPD Type 3(Surge arrester)
1 x DFL M 2 55 Part No. 9 24 39 6for flush-mount ed systems
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
EBB
1) Only requi red, i f a fuse of the same or a lower nominal value is not a l ready prov ided in the upstream power supply .
i n d i c a t i o n
o f
i n t e r f e r e n c e
TN systems: Example: Off ice Bui ld ing – Separat ion of the PEN in the main distr ibution board
-
8/18/2019 Surge protection for power systems
5/117
POWER SUPPLY SYSTEM S
www.dehn.de
P R O
T E C T O
R
Überspannungsschutz
0 1
SFL-Protector
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PEN
D E H N
g u a r
d
D G M
O D 2
7 5
L3
9
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PEN
D E H N
g u a r
d
D G M
O D 2
7 5
L3
9
L1 L1' L2 L2 ' L3 L3 '
N /́ PE N N /P EN
DEHNbloc DB 3 255 H
L1 L1 ´ L2 L2 ´
PEN
L3 L3´
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
9
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
L1 L2 L3 N PE
C a b l e l e n g t h ≥ 5 m
16 A
S o c k e t O
u t l e t
M
a i n
D i s t r i b u t i o n
B o a r d
S u b d i s t r i b u t i o n
B o a r d
SPD Type 2(Surge arrester)
Cable length ≥ 1 5 m
SPD Type 1(Lightning current arrester)
SPD Type 1(Coordinated lightning
current arrester)
SPD Type 1(Combined lightning current
and surge arrester)
DEHNbloc ® MCoordinated to DEHNguard ®
without additional cable length.
i n d i c a t i o n
o f
i n t e r f e r e n c e
1 x N SM PRO EW Part N o. 92 4 3 4 2 1 x DPRO 2 3 0 F Part No. 9 09 24 01 x DPRO 2 3 0 Part No. 9 09 23 0
1 x SFL PRO Part No. 91 2 2 60
1 x DG M TNC 2 75 Part N o. 95 2 3 0 0with remote signall ing contact:1 x D G M T N C 2 7 5 FM Pa rt N o. 95 2 30 5
1 x DB 3 25 5 H Part No. 9 00 12 0
a l t .3 x DB 1 25 5 H Part No. 9 00 22 21 x M VS 1 6 Part No. 9 00 81 5
3 x D B M 1 2 5 5 FM Pa rt N o. 96 1 1 2 51 x M VS 1 6 Part N o. 90 0 8 1 5
a l t .3 x DB M 1 2 5 5 Part N o. 96 1 1 2 01 x M VS 1 6 Part N o. 90 0 8 1 5
1 x D V M TN C 2 55 Pa rt N o. 95 1 30 0
a l t .1 x DV M TNC 255 FM Part No. 951 3 05
1) Only requi red, i f a fuse of the same or a lower nominal value is not a l ready prov ided in the upstream power supply .
DEHNvent il ®
Directly coordinated toRed/Line SPDs Type 2 and 3
without additional cable length.
For serial connection please see also page 19
1125 A 1125 A
SPD Type 2(Surge arrester)
1315 A 1315 A 1315 A
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
EBB
i n d i c a t i o n
o f
i n t e r f e r e n c e
Easy Choice
17
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
TN systems: Example: Off ice Bui ld ing – Separat ion of the PEN in the subdistr ibution board
-
8/18/2019 Surge protection for power systems
6/117
POWER SUPPLY SYSTEM S
www.dehn.de
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PEN
D E H N
g u a r
d
D G M
O D 2
7 5
L3
9
DE HNbloc NHDB NH00 255 H
DE HNbloc NHDB NH00 255 H
DE HNbloc NHDB NH00 255 H
V NHV NH00 280
V NHV NH00 280
V NHV NH00 280
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
DEHN SPDSPSPRO
funct ion
OUT/ FM
99 / IN
D E H N
r a i l
D R M 4
P 2 5 5 F M
L1 L2 L3 N 9
L1 L2 L3 N 9
L1 L1 ´ L2 L2 ´
PEN
L3 L3´
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
9
D E H
N r a i l
D R
M
2 P
2 5 5 F M
4 3
2 1
9
9
NETZFILTER
L' L' N' N'OUT
L L N NIN
9 9
9 9
3 x V N H0 0 28 0 Part No. 9 0 0 2 61
3 x D B N H0 0 2 5 5 H Pa rt N o . 9 0 0 2 7 3
a l t .3 x DB 1 2 55 H Part No. 9 0 0 2 221 x M VS 1 6 Part No. 9 0 0 8 15
1315 A
3 x D B M 1 2 5 5 FM Pa rt N o. 96 1 1 251 x M VS 1 6 Part No. 9 0 0 8 15
a l t .3 x DB M 1 2 55 Part No. 9 6 1 1 201 x M VS 1 6 Part No. 9 0 0 8 15
1315 A
i n d i c a t i o n
o f
i n t e r f e r e n c e
1 x DV M TNC 255 FM Part No. 951 30 5
a l t .1 x DV M TN C 2 55 Pa rt N o. 95 1 30 0
1315 A
i n d i c a t i o n
o f
i n t e r f e r e n c e
1 x DG M TN C 27 5 Part No. 9 5 2 3 00or with remote signall ing contact:1 x D G M TN C 2 7 5 FM Pa rt N o. 95 2 3 05
1125 A
13 A
1 x SPS PRO Part No. 9 12 25 3
125 A
electronicequipment
1 x DR M 2 P 2 55 FM Pa rt No. 95 3 2 051 x NF 10 Part No. 91 2 2 54
110 A
L1 L2 L3 N PE
C a b l e l e n g t h ≥ 5 m
32 A
S w
i t c h g e a r / M
a c h i n e
SPD Type 2(Surge arrester)
SPD Type 2(Surge arrester)
Cable length ≥ 1 5 m
SPD Type 1(Lightning current arrester)
SPD Type 1(Coordinated lightning
current arrester)
DEHNbloc ® MCoordinated to DEHNguard ®
without additional cable length.
M
a i n
D i s t r i b u t i o n
B o a r d
S u b d i s t r i b u t i o n
B o a r d
SPD Type 1(Combined lightning current
and surge arrester)
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
DEHNvent il ®
Directly coordinated toRed/Line SPDs Type 2 and 3
without additional cable length.
For serial connection please see also page 19
2
EBB
PLC PLC
1) Only requi red, i f a fuse of the same or a lower nominal value is not a l ready prov ided in the upstream power supply .
2) Withou t separate backup fuse in case of earth-fault- and short-circuit-proof installation.
25 A alsopermissiblewithou t NF 10
1 x D R M 4 P 25 5 FM P ar t N o . 9 5 3 4 0 5a l t .1 x DR M 4P 25 5 Part No. 9 53 40 0
i n d i c a t i o n
o f
i n t e r f e r e n c e
TN systems: Example: Industry – Separat ion of the PEN in the subdistr ibution board
Easy Choice
18
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
-
8/18/2019 Surge protection for power systems
7/117
POWER SUPPLY SYSTEM S
www.dehn.de
P R O
T E C T O
R
D E H N
r a
i l
D R M 2
P 2 5 5 F M
21 9
DEHNventi l ZP
DV ZPTNC 255
PEN9
PEN
L3
L2
L1
L1 L2 L3 N PE
16 A
S o c k e t
O u t l e t
EBB
H e a t i n g
C o n t r o l
SPD Type 1(Combined lightning current
and surge arrester)
1 x D V Z P T N C 2 5 5 Pa r t N o . 9 0 0 3 9 0
also available for 5-w ire systems1 x DV ZP TT 2 55 Part N o. 90 0 3 9 1
C e n t r a i l
M
a i n
a n d
S u b d i s t r i b u t i o n
B o a r d
1 x DPRO 2 3 0 Part No. 9 09 23 01 x DPRO 2 3 0 F Part No. 9 09 24 01 x SFL PRO Part No. 9 12 26 0
SPD Type 3(Surge arrester)
1 x DR M 2P 25 5 Part No. 9 5 3 2 00
SPD Type 3(Surge arrester)
KW h
L1L2L3
PEN
heat ing
315 A gL/gG
Not e :As an alternative, surge arresters can also beused downstream of meter panels(e.g. D G M TN C 2 75 Pa rt No . 9 52 30 0),i f no
– li gh tn in g p ro te cti on syst em , – elect rical p ow er suppl y by th e service entry m ast, – an te nn a o n th e r oo fis available.
C a b l e l e n g t h ≥ 5 m
TT systems: Example: Single-fami ly house
Easy Choice
19
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
TN systems: Example: Single-fami ly house
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D N
P E
5 0
L1 L2
PE
L3 N
9
D E H N
r a
i l
D R M 2
P 2 5 5 F M
21 9
RCD
L1 L2 L3 N PE
16 A
S o c k e t O u t l e t
H e a t i n g
C o n t r o l
SPD Type 1(Combined lightning current
and surge arrester)
1 x DV M TT 2 5 5 Part No. 9 51 31 0 C e n t r a i l M
a i n
a n d
S u b d i s t r i b u t i o n
B o a r d
1 x DR M 2P 2 5 5 Part No. 9 5 3 20 0
SPD Type 3(Surge arrester)
125 A
1 x DFL M 2 5 5 Part No. 9 2 4 3 96
SPD Type 3(Surge arrester)
heat ing
EBB
Not e :As an alternative, surge arresters can also beused downstream of meter panels(e.g. DG M TT 2 75 Part No. 9 52 310 ),i f no
– li gh tn in g p ro te cti on syst em , – elect rical p ow er suppl y by th e service entry m ast, – an te nn a o n th e r oo fis available.
C a b l e l e n g t h ≥ 5 m
DEHNf lex
-
8/18/2019 Surge protection for power systems
8/117
POWER SUPPLY SYSTEM S
www.dehn.de
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3 N
D E H N
g u a r
d
D G M
O D N
P E
9
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3 N
D E H N
g u a r
d
D G M
O D N
P E
9
DEHNf lex
ÜS-Schutz
D E H N
v e n
t i l
D V M O D 2
5 5
L1 L1 ´ L2 L2´
PE
L3 L3 ´ N N´
9
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D N
P E 5 0
L1 L1 ' L2 L2' L3 L3 '
N /́ PE N N /P EN
DEHNbloc DB 3 255 HD u rch g an g sklemme
DK 35
DEHNgap B/nDGPBN 255
N
PE
D E H N
g a p
D G P M 2
5 5
9
D E H N b l o
c
D B M 1
2 5 5
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5
N/PE(N)
L/N
1 x DB 3 2 55 H Part No. 90 0 1 20a l t .3 x DB 1 2 55 H Part No. 90 0 2 22
1 x DGP BN 2 55 Pa rt N o. 9 00 1 321 x DK 35 Part No. 90 0 6 991 x M VS 1 2 Part No. 90 0 6 17
1315 A 1315 A
1 x D V M T T 2 5 5 FM Pa r t N o. 9 5 1 3 1 5
a l t .1 x DV M TT 255 Part No. 9 51 31 0
1315 A
indication ofinterference
L1 L2 L3 N PE
C a b l e l e n g t h ≥ 5 m
16 A
S o c k e t O
u t l e t
i n d i c a t i o n
o f
i n t e r f e r e n c e
1 x DSA 2 30 LA Part No. 92 4 3 70for cable ducts
1 x STC 2 30 Part No. 9 24 35 0for existing socket out lets
with remote signall ing contact:1 x D G M TT 2 75 FM Part No. 95 2 3 15
1125 A
SPD Type 2(Surge arrester)
1125 A
SPD Type 2(Surge arrester)
1 x DG M TT 27 5 Part No. 95 2 3 10
Cable length ≥ 1 5 m
SPD Type 1(Lightning current arrester)
SPD Type 1(Coordinated lightning
current arrester)
DEHNbloc ® MCoordinated to DEHNguard ®
without additional cable length.
M
a i n
D i s t r i b u t i o n
B o a r d
S u b d i s t r i b u t i o n
B o a r d
SPD Type 1(Combined lightning current
and surge arrester)
SPD Type 3(Surge arrester)
1 x DFL M 25 5 Part N o. 92 4 3 9 6for flush-mount ed systems
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
DEHNvent il ®
Directly coordinated toRed/Line SPDs Type 2 and 3
without additional cable length.
For serial connection please see also page 19
RCD
EBB
1) Only requi red, i f a fuse of the same or a lower nominal value is not a l ready prov ided in the upstream power supply .
3 x DB M 1 2 5 5 Part N o. 96 1 1 201 x DGP M 25 5 Part N o. 96 1 1 011 x M VS 1 8 Part N o. 90 0 6 11
TT systems: Example: Off ice Bui ld ing
Easy Choice
20
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
-
8/18/2019 Surge protection for power systems
9/117
POWER SUPPLY SYSTEM S
www.dehn.de
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3 N
D E H N
g u a r
d
D G M
O D N
P E
9
D E H N
g u a r
d
D G M
O D 2
7 5
D E H N
g u a r
d
D G M
O D 2
7 5
L1 L2
PE
D E H N
g u a r
d
D G M
O D 2
7 5
L3 N
D E H N
g u a r
d
D G M
O D N
P E
9
DE HNbloc NHDB NH00 255 H
DE HNbloc NHDB NH00 255 H
DE HNbloc NHDB NH00 255 H
DEHNgap BNHDGPB NH00 N 255
D E H N
v e n
t i l
D V M O D 2
5 5
L1 L1 ´ L2 L2 ´
PE
L3 L3 ´ N N´
9
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D 2
5 5
D E H N
v e n
t i l
D V M O D N
P E 5 0
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
D E H N b l o
c
D B M 1
2 5 5 F M
N/PE(N)
L/N
N
PE
D E H N
g a p
D G P M 2
5 5 F M
9
D E H N
r a i l
D R
M
2 P 2 5 5
F M
4 3
2 1
9
9
NETZFILTER
L' L' N' N'OUT
L L N NIN
9 9
9 9
DEHN SPDSPSPRO
funct ion
OUT/ FM
99 / IN
D E H N
r a
i l
D R M 4
P 2 5 5 F M
L1 L2 L3 N 9
L1 L2 L3 N 9
13 A
1 x SPS PRO Part N o. 91 2 2 53
3 x DB NH00 25 5 H Part No. 90 0 2 731 x D GP B N H0 0 N 2 55 Pa r t N o. 9 00 2 6 9
1315 A
1 x D V M T T 2 5 5 FM Pa r t N o. 9 5 1 3 1 5
a l t .1 x DV M TT 255 Pa rt No. 9 51 31 0
1315 A
125 A
elect ronicequipment
1315 A
1 x DR M 2 P 2 55 FM Part No. 95 3 2 051 x NF 1 0 Part No. 9 12 25 4
110 A
L1 L2 L3 N PE
C a b l e l e n g t h ≥ 5 m
32 A
S w
i t c h g e a r / M
a c h i n e
i n d i c a t i o n
o f
i n t e r f e r e n c e
with remote signall ing contact:1 x DG M TT 2 75 FM Pa rt No. 9 52 31 5
1125 A
SPD Type 2(Surge arrester)
1125 A
SPD Type 2(Surge arrester)
1 x DG M TT 27 5 Part N o. 95 2 3 1 0
Cable length ≥ 1 5 m
SPD Type 1(Lightning current arrester)
SPD Type 1(Coordinated lightning
current arrester)
DEHNbloc ® MCoordinated to DEHNguard ®
without additional cable length.
M
a i n
D i s t r i b u t i o n
B o a r d
S u b d i s t r i b u t i o n
B o a r d
SPD Type 1(Combined lightning current
and surge arrester)
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
SPD Type 3(Surge arrester)
DEHNvent il ®
Directly coordinated toRed/Line SPDs Type 2 and 3
without additional cable length.
For serial connection please see also page 19
EBB
PLC PLC
1) Only requi red, i f a fuse of the same or a lower nominal value is not a l ready prov ided in the upstream power supply .
1 x D R M 4 P 2 5 5 FM P ar t N o . 9 5 3 4 0 5a l t .1 x DR M 4 P 2 55 Pa rt No . 9 53 40 0
25 A alsopermissiblewithou t NF 10
i n d i c a t i o n
o f
i n t e r f e r e n c e
i n d i c a t i o n
o f
i n t e r f e r e n c e
indication of int erference
3 x DB M 1 2 55 FM Part No. 96 1 1 251 x DGP M 2 55 FM Part No. 96 1 1051 x M VS 1 8 Part No. 90 0 6 11
RCD
TT systems: Example: Industry
Easy Choice
21
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
-
8/18/2019 Surge protection for power systems
10/117
POWER SUPPLY SYSTEM S
www.dehn.de22
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
Easy Choice
D E H N
g u a r
d
D G S
4 4 0 F M
D E H N
g u a r
d
D G S
4 4 0 F M
D E H N
g u a r
d
D G S
4 4 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
4 4 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
4 4 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
4 4 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
7 6 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
7 6 0 F M
N/PEN
L
D E H N b l o
c
M
a x
i
D B M 1
7 6 0 F M
DEHNguardDG 1000 FM
DEHNguardDG 1000 FM
DEHNguardDG 1000 FM
L
D E H N b l o
c
M
a x
i
D B M 1
7 6 0 F M
L1 L2 L3 PEN
SPD Type 1
(Coordinated lightningcurrent arrester)
3 x DG S 4 40 FM Part No. 95 2 0 951 x M VS 1 3 Part No. 90 0 6 15
SPD Type 2(Surge arrester)
125 A
EBB
250 A
L1 L2 L3 PE
SPD Type 1
(Coordinated lightningcurrent arrester)
3 x D BM 1 7 6 0 FM P ar t N o . 9 6 1 1 7 51 x EB DG 1000 1 3 Part No. 900 411
3 x DG 1 0 00 FM Part No. 9 5 0 1 121 x EB DG 1 00 0 1 3 Pa rt No . 9 00 41 1
SPD Type 2(Surge arrester)
125 A
EBB
250 A
3 x D BM 1 4 4 0 FM Pa rt N o. 96 1 14 5
a l t .3 x DBM 1 4 4 0 Part N o. 96 1 1 401 x E B D G 1 0 0 0 1 3 P ar t N o. 9 0 0 4 1 1
i n d i c a t i o n
o f
i n t e r f e r e n c e
i n d i c a t i o
n
o f
i n t e r f e r e n c e
i n d i c a t i o
n
o f
i n t e r f e r e n c e
i n d i c a t i o
n
o f
i n t e r f e r e n c e
TN systems: Industry TN-C 400/690 V IT systems: Industry IT 690 V, w ithout in tegrated neutra lconductor
-
8/18/2019 Surge protection for power systems
11/117
POWER SUPPLY SYSTEM S
www.dehn.de 23
Pow er Supply Syst em s Worldw ide
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
L1
L2
L3
PEN
RB
L1
L2
L3
N
RB
PE
L1
L2
L3
NPE
RB
TN-C system TN-S system
L1
L2
L3
N
RB RA
PE
L1
L2
L3
RA
PE
TN-C system 230 / 400 V
TN-S system 230 / 400 V
TN-C-S syste m 230 / 400 V
TT system 230 / 400 V IT syste m 230 V
L
N
G
L1
N
G
L2
L1
G
L2
L3
L1
G
L2
L3
N
L1
G
L2
L3
N
L1
G
L2
L3
L1
G
L2
L3
single-phase; 3 conductors
(1 Ph, 2 W + G)
110 V120 V220 V24 0 V
single-phase; 4 conductorsSplit Phase or Edison
(1 Ph, 3 W + G)
120 V / 240 V
3-phase; 4 conductors
(3 Ph Y, 3 W + G)
480 V
3-phase; 5 conductors
(3 Ph Y, 4 W + G)
120 V / 208 V277 V / 480 V
3-phase; 5 conductorsDel ta ” Highleg“
(3 Ph ∆, 4 W + G )
120 V / 240 V
3-phase; 4 conductorsDel ta ”Ungrounded“
(3 Ph ∆, 3 W + G )
240 V480 V
3-phase; 4 conductorsDelta ”Grounded Corner“
(3 Ph ∆, 3 W + G )
240 V480 V
R
N
100 V
R
T
200 V
R
N
100 V
100 V
200 V
T
single-phase; 2 conductors
(1 Ph, 2 W)
200 V
single-phase; 3 conductors
(1 Ph, 3 W)
100 V / 200 V
single-phase; 2 conductors
(1 Ph, 2 W)
100 V
R
S
200 V
200 V
200 V
T
R
S
100 V
100 V200 V
T
N200 V
200 V
3-phase; + single-phase;3 conduct ors 3 conductors
100 V / 200 V; 200 V
3-phase; 3 conductors
(3 Ph, 3 W)
200 V
International system configurations* according to IEC 603 64-1 (DIN VDE 010 0-30 0)
Further system configurations* used w orldwide
* System according t o earth connection (according to DIN VDE 0100-300)
-
8/18/2019 Surge protection for power systems
12/117
POWER SUPPLY SYSTEM S
www.dehn.de24
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
Cross-reference
Combined SPDs – Type 1
900 370 DV 2P TT 255 951 110 DV M TT 2P 255 or951 115 DV M TT 2P 255 FM
900 371 DV 2P TN 255 951 200 DV M TN 255 or951 205 DV M TN 255 FM
900 373 DV TNC 255 951 300 DV M TNC 255 or951 305 DV M TNC 255 FM
900 374 DV TNS 255 951 400 DV M TNS 255 or951 405 DV M TNS 255 FM
900 375 DV TT 255 951 310 DV M TT 255 or951 315 DV M TT 255 FM
Coordinated Lightning Current Arresters – Type 1
900 044 DBM 440 961 140 DBM 1 440 or961 145 DBM 1 440 FM
Lightning Current Arresters – Type 1
900 100 DP 255 900 222 DB 1 255 H
900 101 DP 440 961 140 DBM 1 440 or900 159 DB 1 440
900 110 DB 3 255 900 120 DB 3 255 H
900 111 DB 1 255 900 222 DB 1 255 H
900 260 DB NH00 255 900 273 DB NH00 255 H
Surge Arresters – Type 2
900 133 DGP C T 255 952 030 DGP C S or952 035 DGP C S FM
900 265 V NH1 3 900 270 V NH1 280
900 266 VA NH1 3 900 271 VA NH1 280
900 506 DG TN 230 952 200 DG M TN 275
900 507 DG TN 230 FM 952 205 DG M TN 275 FM
900 508 DG TT 230 952 110 DG M TT 2P 275
900 509 DG TT 230 FM 952 115 DG M TT 2P 275 FM
900 510 DG TNC 230 400 952 300 DG M TNC 275
900 516 DG IT 500 952 302 DG M WE 600
900 520 DG TT 230 400 952 310 DG M TT 275
900 530 DG TNS 230 400 952 400 DG M TNS 275
900 540 DG TNC 230 400 FM 952 305 DG M TNC 275 FM
900 546 DG IT 500 FM 952 307 DG M WE 600 FM
900 550 DG TT 230 400 FM 952 315 DG M TT 275 FM
900 560 DG TNS 230 400 FM 952 405 DG M TNS 275 FM
900 600 DG 275 952 070 DG S 275
900 601 DG 600 952 076 DG S 600
900 602 DG 385 952 074 DG S 385
900 603 DG 150 952 072 DG S 150900 604 DG 75 952 071 DG S 75
900 605 DG 320 952 073 DG S 320
900 607 DG 440 952 075 DG S 440
900 620 DG 275 FM 952 090 DG S 275 FM
900 621 DG 600 FM 952 096 DG S 600 FM
900 622 DG 385 FM 952 094 DG S 385 FM
900 623 DG 150 FM 952 092 DG S 150 FM
900 624 DG 75 FM 952 091 DG S 75 FM
900 625 DG 320 FM 952 093 DG S 320 FM
900 627 DG 440 FM 952 095 DG S 440 FM
900 641 DG T 385 952 074 DG S 385
900 650 DG T 275 952 070 DG S 275
900 651 DG T 600 952 076 DG S 600
900 652 DG T 320 952 073 DG S 320
900 653 DG T 150 952 072 DG S 150
900 654 DG T 75 952 071 DG S 75
900 655 DG T 440 952 075 DG S 440
900 680 DG T 275 FM 952 090 DG S 275 FM
900 681 DG T 600 FM 952 096 DG S 600 FM
900 682 DG T 320 FM 952 093 DG S 320 FM
900 683 DG T 150 FM 952 092 DG S 150 FM
900 684 DG T 75 FM 952 091 DG S 75 FM
900 685 DG T 440 FM 952 095 DG S 440 FM
900 691 DG T 385 FM 952 094 DG S 385 FM
901 000 VAV 1000 950 102 DG 1000 or950 112 DG 1000 FM
902 375 VA NH00 280 3 IG FM –
902 376 VA NH00 280 4 IG FM –
902 385 VA NH00 280 3 IG –
902 386 VA NH00 280 4 IG –
Surge Arresters – Type 3
901 100 DR 230 FM L 953 205 DR M 2P 255 FM or953 200 DR M 2P 255
901 101 DR 120 FM L 953 209 DR M 2P 150 FM or953 204 DR M 2P 150
901 102 DR 60 FM L 953 208 DR M 2P 75 FM or953 203 DR M 2P 75
901 103 DR 48 FM L 953 207 DR M 2P 60 FM or953 202 DR M 2P 60
901 104 DR 24 FM L 953 206 DR M 2P 30 FM or953 201 DR M 2P 30
909 820 SF PRO 909 240 DPRO 230 F
909 821 S PRO 909 230 DPRO 230
M ains Connection Boxes
900 964 NAK 63A 4 951 400 DV M TNS 255
900 965 NAK 63A 3 951 300 DV M TNC 255
900 966 NAK 35A 4 951 400 DV M TNS 255
900 967 NAK 35A 3+ 1 951 310 DV M TT 255
900 968 NAK 35A 3 951 300 DV M TNC 255
900 969 NAK 63A 3+ 1 951 310 DV M TT 255
902 492 NAK TAB 3 900 390 DV ZP TNC 255
902 493 NAK TAB 3+ 1 900 391 DV ZP TT 255
902 494 NAK TAB 4 900 391 DV ZP TT 255
Accessories
900 309 IGA 10 IP54 902 480 IGA 10 IP55
900 121 DBR 35 –
900 122 DBR 63 –
Isolating Spark Ga ps
923 070 EXFS C1 923 100 EXFS 100
923 071 EXFS C1 KU 923 101 EXFS 100 KU
Discont inued Products Alternat ivesPart N o. Type Part No. Type
Discont inued Products Alternat ivesPart No. Type Part N o. Type
-
8/18/2019 Surge protection for power systems
13/11725www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
Mult ipole m odular comb ined lightning current
and surge a rrest erSPD Type 1 according to EN 61643-11SPD Class I according t o IEC 61643-1
• Prewired spark-gap-based combinedlightning current and surge arreste r,
consisting o f a b ase pa rt a nd plug-inprotection modules• M aximum system ava i lab il ity due to
RADAX Flow fol low current l imitation• No tr ipping of 20 A gL/gG fuses up to
short -circuit currents of 5 0 kA rm s• Discharge capaci ty up to 100 kA
(10/350 µs)• Allow s for protection of terminal devices
• Operat ing state/ faul t indicat ion by markin the inspection window
• Al low s for easy replacing of protect ionmodules due to module locking systemw ith releasing button
• Tested for v ibrat ion- and shock-proof-ness according to EN 60068-2
For protecting low -voltage consumer´s installations against surges, even
in case of direct l ight ning strokes. For use according t o the lig htning pro-
tection zones concept at bo undaries 0A – 2.
Wit h the function al design of t he new Red/Line series, the devices of the
modular DEHNventil family combine safety and innovation in an impres-
sive way. Being an ” a l l - in-one device” they assume l ightn ing equipoten-
tial bond ing and surge protection in only on e stage. Especially for use in
compact electr ical installations, this function is of advantage. The design
of t he surge arresters according to energy-coordination criteria allow s forprotect ion of even terminal devices at shor t d istances between
DEHNventil and t he consumers ( 5 m). Considering the lightning current
discharge capacity up to 100 00 0 A, this is a safe basis for high availabil-
ity of the electr ical installation t o be protected. Even for expanded electr i-
cal installations, the mo dular DEHNventil devices provide various applica-
tion possibil it ies. Red/Line surge arresters installed at th e boundaries of
the individual l ightning protection zones are already energy-coordinated
w ith DEHNventil devices. Encapsulated creepage discharge spark gaps
and the small space required by the combined light ning current and surge
arresters allow fo r easy integration int o swit chgear installation s or distr i-
bution b oards. A special feature of the new m odular Red/Line product
fami ly is the funct ional design. An important component is the module
releasing butt on. It f ixes the protection mod ule reliably to keep the safe
connection to the base part even in case of maximu m loads. If protectionmodu les have to be replaced, it releases the module w ithout requir ing
tools and allow s to remove it easily. By using the doub le terminals avail-
able for all conductor connections, the surge arresters can be connected
in series in a space-saving and cost-effective w ay up t o nom inal currents
of 125 A, as preferred by IEC 60364-5-53. For connecting further DINrail
mountable devices, busbars type
MVS 3 8 6 and MVS 4 11 8 can be
used. The right DEHNventil d evices
can be easily chosen according to
the system configuration of the
exist ing low-vol tage consumer´sinstallation and type designation of
the device.
Using the patented RADAX Flow
technology for follow current l imi-
tation and extinction achieves high
availabil ity of the electr ical installation t o be protected. Even for high
short-circuit currents up to 50 kA rm s, upcoming mains fo l low currents are
reduced in such a w ay that there is a selectivity to small fuse values, i.e.
upstream fuses cannot tr ip due t o arising mains follow currents.
The operating state/fault indicator of each protective circuit, w hich is not
supplied by operating currents, inform s imm ediately about the operating
state of the surge arrester. Apart from the standard visual indicator wit hgreen and red marks, types DEHNventil M ... FM h ave a 3-pole terminal
for remote signall ing. With t he remot e signall ing contact being a f loating
changeover contact, the remot e signal can be used as a break or make
contact, according to circuit concept.
DEHNventi l M TNC 255: M odular combined l ightning current and surge arrester for use in TN-C systems
DEHNventi l M TNS 255: M odular combined l ightning current and surge arrester for use in TN-S systems
DEHNvent il M TT 255: M odular combined l igh tn ing current and surge ar rester fo r use in TT and TN-S systems(”3+ 1” ci rcu i t )
DEHNvent il M TN 255: M odular combined l igh tn ing current and surge ar rester fo r use in s ing le-phase TN systems
DEHNvent il M TT 2P 25 5: M odular combined lightning current and surge arrester for use in single-phase TT and TN system s(”1+ 1” ci rcu i t )
D EH N ven t il M . .. FM : Wi t h remo t e si g na l li ng co nt act f o r mo n i t or in g d ev ice ( f lo a t in g ch ang eo ver co n t act )
-
8/18/2019 Surge protection for power systems
14/11726 www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
DEHNvent il M TNC (FM )95 1 30 0 DV MTNC 25595 1 30 5 DV MTNC 255 FM
D V M TN C 2 5 59 5 1 3 0 0DV M TNC 255 FM9 5 1 3 0 5
12
1114
L2 L2´
PEN
L1 L1´ L3 L3´
Basic circuit diagram DV M TNC 255 FM Dim ension draw ing DV M TN C 255 (FM )
DV M TNC 255 (FM ): M odular combined light ning current and surge arrester for use in
TN-C system s
DV M TNC 255 DV M TNC 255 FM
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN 230 / 400 V 230 / 400 V
Ma x. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10 /350 µs) [L1+ L2+L3-PEN] Itotal 75 kA 75 kA
Lightning impulse current (1 0/35 0 µs) [L-PEN] I im p 25 kA 25 kA
Nominal discharge current (8/20 µs) I n 25 / 75 kA 25 / 75 kA
Voltage protection level UP 1.5 kV 1.5 kV
Follow current e xtinguishing capability a.c. I fi 50 kA rms 50 kA rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Response tim e t A 100 ns 100 ns
Ma x. backup fuse (L) up to IK = 50 kA rm s 315 A gL/gG 315 A gL/gG
Ma x. backup fuse (L) for I K > 50 kA rm s 200 A gL/gG 200 A gL/gG
M ax. backup fuse (L-L )́ 125 A gL/gG 125 A gL/gG
Tempora ry overvolta ge (TOV) UT 440 V / 5 sec. 440 V / 5 sec.Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional a rea (L1, L1´, L2, L2´, L3, L3´, PEN,9) min. 10 mm 2 solid/flexible 10 mm 2 solid/flexible
Cross-sectional a rea (L1, L2, L3, PEN) max. 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm2 flexible
Cross-sectional a rea (L1´, L2 ,́ L3 ,́9) max. 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure mat erial red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 6 mods., DIN 43880 6 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE, UL,VdS
Type of re mote signalling contact — cha ng eov er con ta ctSwitching capacity a .c. — 25 0 V/ 0.5 A
Switching capacity d.c. — 25 0 V/ 0.1 A ; 12 5 V/ 0.2 A ; 75 V/0 .5 A
Cross-sectional area for rem ote signalling term inals — ma x. 1.5 mm 2 solid/flexible
Ordering information
Type DV M TNC 255 DV M TNC 255 FM
Part N o. 951 300 951 305
Packing unit 1 pc(s). 1 pc(s).
Accessory Part for DEHNventil ® modular
Spark-gap-based protection moduleDV MOD 255: Spark-gap-based protection module
PU PartType pc(s) No.
DV M OD 255 1 9 5 1 0 0 1
9 5 1 0 0 1 D V M OD255
D V M OD 25 5 Ko mb i -A blei te r-Sch u tzmo d ul 9 51 0 01
-
8/18/2019 Surge protection for power systems
15/11727www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
DEHNvent il M TNS (FM )DV M TNS
DV M TNS
12
1114
L2 L2´ N N´
PE
L1 L1´ L3 L3´
Basic circuit d iagram DV M TNS 255 FMDimension drawing DV M TNS 255 (FM)
DV M TNS 255 (FM ): M odular combin ed lightnin g current and surge arrester for TN-S systems
DV M TNS 255 DV M TNS 255 FM
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN 230 / 400 V 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] I total 100 kA 100 kA
Lightning impulse current (1 0/35 0 µs) [L,N-PE] I imp 25 kA 25 kA
Nominal discharge current (8/20 µs) I n 25 / 100 kA 25 / 100 kA
Voltage prot ection level [L-PE] UP 1.5 kV 1.5 kV
Voltage protection level [N-PE] UP 1.5 kV 1.5 kV
Follow current e xtinguishing capability a.c. I fi 50 kA rms 50 kA rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Response time t A 100 ns 100 ns
Max. backup fuse (L) up to IK = 50 kA rm s 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kA rm s 200 A gL/gG 200 A gL/gG
M ax. backup fuse (L-L )́ 125 A gL/gG 125 A gL/gGTempora ry overvolt age (TOV) [L-N] U T 440 V / 5 sec. 440 V / 5 sec.
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE,9) min. 10 mm 2 solid/flexible 10 mm 2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm 2 flexible
Cross-sectional area (L1 ,́ L2 ,́ L3 ,́ N´,9) max. 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm 2 flexible
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure mat erial red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 8 mods., DIN 43880 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE, UL,VdSType of re mote signalling contact — cha ng eov er con ta ct
Switching capacity a .c. — 25 0 V/ 0.5 A
Switching capacity d.c. — 25 0 V/ 0.1 A; 12 5 V/ 0.2 A ; 75 V/0 .5 A
Cross-sectional area for rem ote signalling term inals — ma x. 1.5 mm 2 solid/flexible
Ordering information
Type DV M TNS 255 DV M TNS 255 FM
Part N o. 951 400 951 405
Packing unit 1 pc(s). 1 pc(s).
Accessory Part for DEHNventil ® modular9 51 00 1 DV M OD255
DV M OD 2 5 5 Kom bi -Ab lei ter -Sch ut zmo du l 95 1 0 01
Spark-gap-based protection moduleDV MOD 255: Spark-gap-based protection module
PU PartType pc(s) No.
DV M OD 255 1 9 5 1 0 0 1
-
8/18/2019 Surge protection for power systems
16/11728 www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
DEHNvent il M TT (FM )95 1 31 0 DV M TT25595 1 31 5 DV M TT2 5 5 FM
D V M TT2 5 59 5 1 3 1 0D V M TT2 5 5 FM9 5 1 3 1 5
12
1114
L2 L2´ N N´
PE
L1 L1´ L3 L3´
NPE
Basic circuit diagram DV M TT 255 FM Dim ension draw ing DV M TT 255 (FM )
DV M TT 255 (FM ): M odular combined l ightn ing current and surge arrester for TT and
TN-S systems (” 3+ 1“ circuit)
DV M TT 255 DV M TT 255 FM
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN
230 / 400 V 230 / 400 V
Ma x. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] I total 100 kA 100 kA
Lightning impulse current (10 /350 µs) [L-N] I imp 25 kA 25 kA
Lightning impulse current (10 /350 µs) [N-PE] I im p 100 kA 100 kA
Nominal discharge current (8/20 µs) I n 25 / 100 kA 25 / 100 kA
Voltage protection level [L-N] U P 1.5 kV 1.5 kV
Voltage protection level [N-PE] UP 1.5 kV 1.5 kV
Follow current e xtinguishing capability [L-N] a.c. I fi 50 kA rms 50 kA rmsFollow current extinguishing capability [N-PE] a.c. I fi 100 A rms 100 A rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Response tim e t A 100 ns 100 ns
Ma x. backup fuse (L) up to IK = 50 kA rm s 315 A gL/gG 315 A gL/gG
Ma x. backup fuse (L) for I K > 50 kA rm s 200 A gL/gG 200 A gL/gGM ax. backup fuse (L-L )́ 125 A gL/gG 125 A gL/gG
Tempora ry overvolt age (TOV) [L-N] U T 440 V / 5 sec. 440 V / 5 sec.
Tempora ry overvolt age (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE,9) min. 10 mm 2 solid/flexible 10 mm 2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm2 flexible
Cross-sectional area (L1 ,́ L2 ,́ L3 ,́ N´,9) max. 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure mat erial red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20Dimension 8 mods., DIN 43880 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE, UL,VdS
Type of re mote signalling contact — cha ng eov er con ta ct
Switching capacity a .c. — 25 0 V/ 0.5 A
Switching capacity d.c. — 25 0 V/ 0.1 A ; 12 5 V/ 0.2 A ; 75 V/0 .5 A
Cross-sectional area for rem ote signalling term inals — ma x. 1.5 mm 2 solid/flexible
Ordering information
Type DV M TT 255 DV M TT 255 FM
Part N o. 951 310 951 315
Packing unit 1 pc(s). 1 pc(s).
Spark-gap-based protection moduleDV MOD 255: Spark-gap-based protection module
PU PartType pc(s) No.
DV M OD 255 1 9 5 1 0 0 1
9 5 1 0 0 1 D V M OD255
D V M OD 25 5 Ko mb i -A blei te r-Sch u tzmo d ul 9 51 0 01
N-PE Spark-gap-based prot ection mod uleDV MOD NPE 100: 100 kA N-PE Spark-gap-based protection m odule
PU PartType pc(s) No.
DV M OD NPE 100 1 951 100
9 5 1 1 0 0D V M OD N P E 1 0 0
D V M OD N P E 1 0 0Kombi-Ableiter-Schutzmodul N-PE100 kA9 5 1 1 0 0
Accessory Part for DEHNventil ® m odular Accessory Part for DEHN vent il ® modular
-
8/18/2019 Surge protection for power systems
17/11729www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
DEHNvent il M TN (FM )DV M TN
DV M TN
12
1114
L L´ N N´
PE
Basic circuit diagram DV M TN 255 FMDimension drawing DV M TN 255 (FM)
DV M TN 255 (FM ): M odular combined lightni ng current and surge arrester for single-phase
TN systems
DV M TN 255 DV M TN 255 FM
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN
230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10 /350 µs) [L+ N-PE] Itotal 50 kA 50 kA
Lightning impulse current (1 0/35 0 µs) [L,N-PE] I imp 25 kA 25 kA
Nominal discharge current (8/20 µs) I n 25 / 50 kA 25 / 50 kA
Voltage prot ection level [L-PE] UP 1.5 kV 1.5 kV
Voltage protection level [N-PE] UP 1.5 kV 1.5 kV
Follow current e xtinguishing capability a.c. I fi 50 kA rms 50 kA rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Response time t A 100 ns 100 ns
Max. backup fuse (L) up to IK = 50 kA rm s 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kA rm s 200 A gL/gG 200 A gL/gG
M ax. backup fuse (L-L )́ 125 A gL/gG 125 A gL/gG
Tempora ry overvolt age (TOV) [L-N] U T 440 V / 5 sec. 440 V / 5 sec.Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L, L ,́ N, N´, PE,9) min. 10 mm 2 solid/flexible 10 mm 2 solid/flexible
Cross-sectional area (L, N, PE) max. 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm 2 flexible
Cross-sectional a rea (L´, N´,9) max. 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm 2 flexible
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure mat erial red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE, UL,VdS
Type of re mote signalling contact — cha ng eov er con ta ctSwitching capacity a .c. — 25 0 V/ 0.5 A
Switching capacity d.c. — 25 0 V/ 0.1 A; 12 5 V/ 0.2 A ; 75 V/0 .5 A
Cross-sectional area for rem ote signalling term inals — ma x. 1.5 mm 2 solid/flexible
Ordering information
Type DV M TN 255 DV M TN 255 FM
Part N o. 951 200 951 205
Packing unit 1 pc(s). 1 pc(s).
Accessory Part for DEHNventil ® modular9 51 00 1 DV M OD255
DV M OD 2 5 5 Kom bi -Ab lei ter -Sch ut zmo du l 95 1 0 01
Spark-gap-based protection moduleDV MOD 255: Spark-gap-based protection module
PU PartType pc(s) No.
DV M OD 255 1 9 5 1 0 0 1
-
8/18/2019 Surge protection for power systems
18/11730 www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® modular
DEHNvent il M TT 2P (FM )95 1 11 0 DV M TT2 P 2 5 595 1 11 5 DV M TT2 P 2 5 5 FM
D V M TT2 P 2 5 59 5 1 1 1 0D V M TT2 P 2 5 5 FM9 5 1 1 1 5
12
1114
N N´
PE
L L´
NPE
Basic circu it diagram DV M TT 2P 255 FM Dim en sion draw ing DV M TT 2P 255 (FM )
DV M TT 2P 255 (FM ): M odular combined ligh tning current and surge arrester for single-phase
TT and TN systems (” 1+ 1“ circuit)
DV M TT 2P 255 DV M TT 2P 255 FM
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN 230 V 230 VMa x. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10 /350 µs) [L+ N-PE] Itotal 50 kA 50 kA
Lightning impulse current (10 /350 µs) [L-N] I imp 25 kA 25 kA
Lightning impulse current (10 /350 µs) [N-PE] I im p 50 kA 50 kA
Nominal discharge current (8/20 µs) I n 25 / 50 kA 25 / 50 kA
Voltage protection level [L-N] U P 1.5 kV 1.5 kV
Voltage protection level [N-PE] UP 1.5 kV 1.5 kV
Follow current e xtinguishing capability [L-N] a.c. I fi 50 kA rms 50 kA rmsFollow current extinguishing capability [N-PE] a.c. I fi 100 A rms 100 A rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Response tim e t A 100 ns 100 ns
Ma x. backup fuse (L) up to IK = 50 kA rm s 315 A gL/gG 315 A gL/gGMa x. backup fuse (L) for I K > 50 kA rm s 200 A gL/gG 200 A gL/gG
M ax. backup fuse (L-L )́ 125 A gL/gG 125 A gL/gG
Tempora ry overvolt age (TOV) [L-N] U T 440 V / 5 sec. 440 V / 5 sec.
Tempora ry overvolt age (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L, L ,́ N, N´, PE,9) min. 10 mm 2 solid/flexible 10 mm 2 solid/flexible
Cross-sectional area (L, N, PE) max. 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm2 flexible
Cross-sectional area (L´, N´,9) max. 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure mat erial red thermoplastic, UL 94-V-0 red thermoplastic, UL 94-V-0
Degree of protection IP 20 IP 20
Dimension 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE, UL,VdS
Type of re mote signalling contact — cha ng eov er con ta ct
Switching capacity a .c. — 25 0 V/ 0.5 A
Switching capacity d.c. — 25 0 V/ 0.1 A ; 12 5 V/ 0.2 A ; 75 V/0 .5 A
Cross-sectional area for rem ote signalling term inals — ma x. 1.5 mm 2 solid/flexible
Ordering information
Type DV M TT 2P 255 DV M TT 2P 255 FM
Part N o. 951 110 951 115
Packing unit 1 pc(s). 1 pc(s).
Spark-gap-based protection moduleDV MOD 255: Spark-gap-based protection module
PU PartType pc(s) No.
DV M OD 255 1 9 5 1 0 0 1
9 5 1 0 0 1 D V M OD255
D V M OD 2 5 59 5 1 0 0 1
N-PE Spark-gap-based prot ection mod uleDV MOD NPE 50: 50 kA N-PE Spark-gap-based protection m odule
PU PartType pc(s) No.
DV M OD NPE 50 1 951 050
9 5 1 0 5 0D V M OD
D V M OD N P E 5 0
Accessory Part for DEHNventil ® m odular Accessory Part for DEHN vent il ® modular
-
8/18/2019 Surge protection for power systems
19/11731www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
Protect ion M odule for D EHNvent il ® modular
SPD Type 1 according to EN 61643-11SPD Class I according t o IEC 61643-1
• High discharge capaci ty due to pow er-ful creep age discharge spark ga p
• M aximum system ava i lab il ity due toRADAX Flow fol low current l imitation
• Wi th module re leasing but ton forreplacing protection m odules w ithouttools
• Operat ing state/ faul t indicat ion bygreen and red mark in the inspectionwindow
D V M O D 2 5 5: Sp ark -g ap -b ase d p ro te ct io n m od ule
D V M O D N P E 50 : 50 kA N - PE Sp ark - g ap - based p ro t ect i on mo d u le
DV MOD NPE 100: 100 kA N-PE Spark-gap-based pro tect ion module
For prot ecting low -voltage consumer ś installations against surges even
in case of direct l ight ning strokes. For use according t o the lig htning pro-
tection zones concept at bo undaries 0A – 2.
The spark-gap-based protection modules of the modular DEHNventil
series combin e safety and innovat ion in an im pressive way. Apart from the
encapsulated RADAX Flow spark gap technology, the compact protection
components include the complete monitoring circuit for controll ing the
energy flow of t he spark gap, as well as the monit oring device and oper-
ating state/fault indication.
The mechanical coding of the protection module prevents any unintend-
ed confusing of the N-PE protection modules with the spark-gap-based
modu le for the phase conductors.
The modu le locking device ensures a safe f ixing of t he protection m odules
in the base part. The module releasing butt on allow s to remove the pro-
tection modules easily without tools.
-
8/18/2019 Surge protection for power systems
20/11732 www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
Protect ion M odule for D EHNvent il ® modular
Spark -gap-based prot ect ion module95 1 00 1 DV M OD255
DV MOD 2559 5 1 0 0 1
Basic circu it diagram DV M OD 255 Dimension draw ing DV M OD 255
DV MOD 255: Spark-gap-based protection module
DV MOD 255Ma x. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 µs) I im p 25 kA
Follow current e xtinguishing capability [L-N] a.c. I fi 50 kA rmsFollow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)
Ordering information
Type DV MOD 255
Part N o. 951 001
Packing unit 1 pc(s).
N-PE Spark-gap-based protect ion module95 1 05 0 DV M ODN P E 5 095 1 10 0 DV M ODN P E 1 0 0
D V M OD N P E 5 09 5 1 0 5 0D V M OD N P E 1 0 09 5 1 1 0 0
NPE
Basic circuit diagram DV M OD NPE ... Dim ension draw ing DV M OD NPE ...
DV M OD NPE 50: 50 kA N -PE Spark-gap-based protection module
DV MOD NPE 100: 100 kA N -PE Spark-gap-based protection m odule
DV M OD NPE 50 DV M OD NPE 100
Ma x. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 µs) I im p 50 kA 100 kA
Follow current extinguishing capability [N-PE] a.c. I fi 100 A rms 100 A rms
Ordering information
Type DV M OD NPE 50 DV M OD NPE 100
Part N o. 951 050 951 100
Packing unit 1 pc(s). 1 pc(s).
-
8/18/2019 Surge protection for power systems
21/11733www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® ZP
Mult ipole com bined lightning current and
surge arre st er f or pr ima ry pow er supply syst em sSPD Type 1 according to EN 61643-11SPD Class I according t o IEC 61643-1
• Combined l ightning current and surgearrester w ith RADAX Flow spark g ap
technology• Fulf ils ent i re ly the requirements of thenational VDN* Directive on useupstream of supply met ers
• Allow s for quick and easy instal lation bysnapping onto 40 mm busbar system s
• Test for correct functioning can be per-formed by pressing the according but-ton w ith l ight indicator
• No tr ipping of fuses from 32 A gL/gG upto short- circuit currents of 2 5 k A rm s• Discharge capaci ty up to 100 kA
(10/350 µs)• Al low s for protect ion of terminal equip-
ment• Provides maximum system avai labi li ty
For prot ecting low -voltage consumer ś installations against surges even
in case of direct l ight ning strokes. For use according t o the lig htning pro-
tection zones concept at bo undaries 0A – 2.
The DEHNventil ZP combined lightning current and surge arrester is an
SPD especially designed for busbar panels of supply meters. It can be
snapped directly onto busbar systems witho ut to ols.The small installation
width leaves enough space for connecting cables from the service
entrance box (SEB), even if three selective main circuit breakers are
installed.
The operating state of the SPD is reported by a l ight indicator which is
contro l led by a but ton. Both w ith th is k ind of operat ing state contro l and
due to its design as an on ly spark-gap-based SPD, DEHNventil ZP is free
of leakage and op erating currents.
The RADAX Flow spark gap technology applied allows for the requiredselectivity on follow currents even for small-sized fuses in the SEB.
Unwanted interruptions of the power supply due to tr ipping mains fuses
are thus avoided.
The rating of the parameters as well as the complete concept of the
device fulf i l entirely the require-
ments of the new German VDN*
Directive on use of surge protective
devices in prim ary pow er supply sys-
tems.
* VDN .. . Ver b an d d er Net z b e-
treiber VDN e. V. at VDEW
[Association of German networkoperators]
DEHNventi l ZP TNC 255 : 3-pole combined l ightning current and surge arrester f or TN-C system s for use in p rimary pow er
supply system sDEHNventi l ZP TT 255: 4-pole combined l ightning current and surge arrester for TT and TN-S system s for use in primarypower supply systems
-
8/18/2019 Surge protection for power systems
22/11734 www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® ZP
DEHNvent il ZP TNC90 0 39 0 DV ZPTNC 255
D V ZP TN C 2 5 59 0 0 3 9 0
L1
L2
L3
&
PEN
PEN
Basic circuit diagram DV ZP TNC 255 Dim ension draw ing DV ZP TNC 255
DV ZP TNC 255: Combined ligh tning current and surge arrester for TN-C systems for use in
primary pow er supply systems (” 3-0“ circuit)
DV ZP TNC 255SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Nominal a.c. voltage UN 230 / 400 V
Ma x. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10 /350 µs) [L1+ L2+L3-PEN] Itotal 75 kA
Lightning impulse current (1 0/35 0 µs) [L-PEN] I im p 25 kA
Nominal discharge current (8/20 µs) I n 25 / 75 kA
Voltage protection level UP 1.5 kV
Follow current e xtinguishing capability a.c. I fi 25 kA rmsFollow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kA rms (prosp.)
Response tim e t A 100 ns
Ma x. backup fuse up to I = 25 kA rm s 315 A gL/gG
Ma x. backup fuse for IK > 25 kA rm s 200 A gL/gG
Tempora ry overvolta ge (TOV) UT 335 V / 5 sec.
Operating te mperature range TU -40°C...+80°C
Function control button w ith l ight indicator
Cross-sectional area (PEN,9) 10-35 mm2 flexible/50 mm 2 stranded
For mounting on 40 mm busbar system
Enclosure mat erial red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 3 mods., DIN 43880
Certifications, Approvals VDE
Ordering information
Type DV ZP TNC 255Part N o. 900 390
Packing unit 1 pc(s).
-
8/18/2019 Surge protection for power systems
23/11735www.dehn.de
AccessoriesSurge Arresters –
Type 3Surge Arresters –
Type 2N-PE Lightning Current
Arresters – Type 1Lightning CurrentArresters – Type 1
Combined SPDs –Type 1
POWER SUPPLY SYSTEM S
COM BINED SPDs – TYPE 1
DEHNvent il ® ZP
DEHNvent il ZP TTDV ZP TT
&
* in case o f ex is t ing PE busba r
L1
L2
L3
N
PE*
PE
Basic circuit diagram DV ZP TT 255Dimension drawing DV ZP TT 255
DV ZP TT 255: Combined light ning current and surge arrester for TT and TN-S systems for use in
pr imary power supply systems ( ” 3+ 1“ c ircui t )
DV ZP TT 255SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Nominal a.c. voltage UN 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] I total 100 kA
Lightning impulse current (10 /350 µs) [L-N] I imp 25 kA
Lightning impulse current (10 /350 µs) [N-PE] I im p 100 kA
Nominal discharge current (8/20 µs) I n 25 / 100 kA
Voltage protection level [L-N] U P 1.5 kV
Voltage protection level [N-PE] UP 1.5 kV
Follow current extinguishing capability [L-N] a.c. I fi 25 kA rmsFollow current extinguishing capability [N-PE] a.c. I fi 100 A rmsFollow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kA rms (prosp.)
Response time t A 100 ns
Max. backup fuse up to I = 25 kA rm s 315 A gL/gG
Max. backup fuse for IK > 25 kA rm s 200 A gL/gG
Tempora ry overvolt age (TOV) [L-N] U T 335 V / 5 sec.
Tempora ry overvolt age (TOV) [N-PE] UT 1200 V / 200 ms
Operating te mperature range TU -40°C...+80°C
Function control button w ith l ight indicator
Cross-sectional area (PE,9) 10-35 mm 2 flexible/50 mm 2 stranded
For mounting on 40 mm busbar system
Enclosure mat erial red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 3 mods., DIN 43880Certifications, Approvals VDE
Ordering information
Type DV ZP TT 255
Part N o. 900 391
Packing unit 1 pc(s).
-