surge arrester - type 1 flp50gr › ... · surge arrester - type 1 flp50gr 255 v ac npe no 1025511...

7
1 AC Surge Protection Devices Type 1 (T1, Class I, Class B) SPDaccording to EN 61643-11 / IEC 61643-11 Maximum continuous operational voltage U c from 150 V up to 600 V AC Versions with 1P, 1P+N, 2P, 2P+N, 3P, 3P+N and 4P connection Without remote indication contact FLP Product family FLP Type Key Surge Arrester - Type 1 FLP50GR www.lsp-international.com 4 Type of connection 1: 1P 2: 2P 3: 3P 4: 4P 1+1: 1P+N 3+1: 3P+N NPE 50 Current I imp (10/350 µs) 50 kA (L-N) 100 kA (N-PE) GR Spark Gap Graphite 275 Max. oper. voltage 275 V AC 320 V AC 385 V AC 440 V AC 150 V AC 600 V AC © 2018 Wenzhou Arrester Electric Co., Ltd. Specifications are subject to change without notice. Revised: 01/01/19 The FLP50GR line is a group of Class I Surge Protective Devices. They are intended as a protection against direct hit of lightning strokes of high intensities or in installation with often occurrence of lightning strokes. In standard three phase TN-C grid, they provides protection over LPL I requirements given in EN 62305 with total lightning current introduced into electrical installation over 100 kA and total lightning stroke current 210 or 280 kA based on physical configuration and mutual position of grounding point of lightning rod, grounding point of the electrical installation and place of SPD installation. The design of FLP50GR is fully based on Spark Gap solution. It brings very high capability and life time and full insulation in case of no overvoltage is present. Thus, these SPDs can be used also upstream to energy meters and can be intended for IT grids (with respective special tests). The high value of Iimp makes these SPDs suitable also for single phase outlets which are wired out of LPZ 0-1 and thus can be hit with direct lightning stroke. Due to the single phase cable, the total lightning current is split to 3 conductors only and intensity per conductor is thus higher than in the case of ingoing three phase cable.

Upload: others

Post on 29-Jun-2020

25 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

1

AC Surge Protection Devices

Type 1 (T1, Class I, Class B)

SPD�according to EN 61643-11 / IEC 61643-11

Maximum continuous operational voltage U c

from 150 V up to 600 V AC

Versions with 1P, 1P+N, 2P, 2P+N, 3P,

3P+N and 4P connection

Without remote indication contact

FLP

Product family

FLP

Type Key

Surge Arrester - Type 1 FLP50GR

www.lsp-international.com

4

Type of connection

1: 1P2: 2P3: 3P4: 4P

1+1: 1P+N3+1: 3P+N

NPE

50

Current

Iimp (10/350 µs)

50 kA (L-N)

100 kA (N-PE)

GR

Spark Gap

Graphite

275

Max. oper. voltage

275 V AC320 V AC385 V AC440 V AC

150 V AC

600 V AC

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

The FLP50GR line is a group of Class I Surge Protective Devices. They are intended as a protection

against direct hit of lightning strokes of high intensities or in installation with often occurrence of

lightning strokes. In standard three phase TN-C grid, they provides protection over LPL I requirements

given in EN 62305 with total lightning current introduced into electrical installation over 100 kA and total

lightning stroke current 210 or 280 kA based on physical configuration and mutual position of grounding

point of lightning rod, grounding point of the electrical installation and place of SPD installation.

The design of FLP50GR is fully based on Spark Gap solution. It brings very high capability and life time

and full insulation in case of no overvoltage is present. Thus, these SPDs can be used also upstream to

energy meters and can be intended for IT grids (with respective special tests).

The high value of Iimp makes these SPDs suitable also for single phase outlets which are wired out of LPZ

0-1 and thus can be hit with direct lightning stroke. Due to the single phase cable, the total lightning current

is split to 3 conductors only and intensity per conductor is thus higher than in the case of ingoing three

phase cable.

Page 2: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

Type 1 SPD (T1, Class I, B) complete devices, I = 50 kA (10/350 µs) imp

Max. oper. Connection Signaling Article No. Type Packing voltage U

c contact

2www.lsp-international.com

150 V AC 1P no 5015011 1/42FLP50GR-150/1 150 V AC 1P+N no 5015013 1/24FLP50GR-150/1+1 150 V AC 2P no 5015021 1/24FLP50GR-150/2 150 V AC 2P+N no 5015023 1/12FLP50GR-150/2+1 150 V AC 3P no 5015031 1/12FLP50GR-150/3 150 V AC 3P+N no 5015033 1/12FLP50GR-150/3+1 150 V AC 4P no 5015041 1/12FLP50GR-150/4

Surge Arrester - Type 1 FLP50GR

• Maximum impulse current I imp 50 kA (10/350 μs) per module and 100 kA (10/350 μs) for moduleFLP100GRD-NPE• Nominal discharge current In 50 kA (8/20 μs) per module and 100 kA (8/20 μs) for NPE (+1) module• Maximum continuous operating voltage U 385 V AC per FLP50GR module and 260 V AC for modulec FLP100GRD-NPE• Maximum continuous operational voltage Uc 150 V AC up to 600 V AC per module and 505 V AC for NPE (+1) module• Due to I imp 50 kA per module suitable for LPL I - LPL IV according to EN 62305 in standard 3-phase TN-C and TN-S installations

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

275 V AC 1P no 5027511 1/42FLP50GR-275/1 275 V AC 1P+N no 5027513 1/24FLP50GR-275/1+1 275 V AC 2P no 5027521 1/24FLP50GR-275/2 275 V AC 2P+N no 5027523 1/12FLP50GR-275/2+1 275 V AC 3P no 5027531 1/12FLP50GR-275/3 275 V AC 3P+N no 5027533 1/12FLP50GR-275/3+1 275 V AC 4P no 5027541 1/12FLP50GR-275/4

320 V AC 1P no 5032011 1/42FLP50GR-320/1 320 V AC 1P+N no 5032013 1/24FLP50GR-320/1+1 320 V AC 2P no 5032021 1/24FLP50GR-320/2 320 V AC 2P+N no 5032023 1/12FLP50GR-320/2+1 320 V AC 3P no 5032031 1/12FLP50GR-320/3 320 V AC 3P+N no 5032033 1/12FLP50GR-320/3+1 320 V AC 4P no 5032041 1/12FLP50GR-320/4

• Coordination with class II SPDs: SLP40-440/xxx – direct coordination SLP40-275/xxx – coordination with cable of minimum length of 10 m in between FLP50GR and SLP40-275/xxx

Page 3: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

Max. oper. Connection Signaling Article No. Type Packing voltage U

c contact

3www.lsp-international.com

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

385 V AC 1P no 5038511 1/42FLP50GR-385/1 385 V AC 1P+N no 5038513 1/24FLP50GR-385/1+1 385 V AC 2P no 5038521 1/24FLP50GR-385/2 385 V AC 2P+N no 5038523 1/12FLP50GR-385/2+1 385 V AC 3P no 5038531 1/12FLP50GR-385/3 385 V AC 3P+N no 5038533 1/12FLP50GR-385/3+1 385 V AC 4P no 5038541 1/12FLP50GR-385/4

440 V AC 1P no 5044011 1/42FLP50GR-440/1 440 V AC 1P+N no 5044013 1/24FLP50GR-440/1+1 440 V AC 2P no 5044021 1/24FLP50GR-440/2 440 V AC 2P+N no 5044023 1/12FLP50GR-440/2+1 440 V AC 3P no 5044031 1/12FLP50GR-440/3 440 V AC 3P+N no 5044033 1/12FLP50GR-440/3+1 440 V AC 4P no 5044041 1/12FLP50GR-440/4

600 V AC 1P no 5060011 1/42FLP50GR-600/1 600 V AC 1P+N no 5060013 1/24FLP50GR-600/1+1 600 V AC 2P no 5060021 1/24FLP50GR-600/2 600 V AC 2P+N no 5060023 1/12FLP50GR-600/2+1 600 V AC 3P no 5060031 1/12FLP50GR-600/3 600 V AC 3P+N no 5060033 1/12FLP50GR-600/3+1 600 V AC 4P no 5060041 1/12FLP50GR-600/4

Type 1 SPD (T1, Class I, B) complete devices, I = 50 kA (10/350 µs) imp

Surge Arrester - Type 1 FLP50GR

255 V AC NPE no 1025511 1/42FLP100GRD-NPE

Page 4: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

4www.lsp-international.com

Technical Data FLP50GR

Surge Protection Devices Type 1, I = 50 kA (10/350 µs)imp

General parameters

Suitable for protection of electrical installation against the effects of atmospheric overvoltage when a direct lightning strike to the building equipped with a lightning rod or lightning to the outdoor power line

Due to I imp 50 kA per module suitable for LPL I - IV according to EN 62305 in standard 3-phase TN-C and TN-S installations

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

1P, 2P, 3P, 4P, 1P+N, 2P+N, 3P+N(L-N/PE/PEN connection)

1P+N, 2P+N, 3P+N(N-PE connection)

Type 1

Technology Graphite

Nominal a.c. voltage Un

Max. continuous operational voltage Uc

255 V AC

Nominal frequency f 50 / 60 Hz

Nominal discharge current I (8/20 µs)n

50 kA

Max. impulse current I (10/350 µs)imp

100 kA

Voltage protection�level U 1.5 kVp

150 V AC 275 V AC 320 V AC

385 V AC 440 V AC 600 V AC

Follow current limitation / Selectivity no tripping of a 20 A gL/gG fuse up to 50 k (prosp.)Arms

fiFollow current extinguishing capability I 50 A �/ 100 Arms rms

1200 V / 200 ms

230 V / 120 min 530 V / 120 min

530 V / 120 min

530 V / 120 min

765 V / 120 min 915 V / 120 minTemporary overvoltage (TOV) (U )T

- Characteristic (withstand)

Response time ta ≤ 100 ns

315 A gL/gGMax. backup fuse (L) up to I = 50 kArms

Max. backup fuse (L-L')

Number of ports 1

Type of LV system TN-C, TN-S, TT (1P+N, 3P+N)

SPD according toEN 61643-11 / IEC 61643-11

120 V AC 230 V AC 230 V AC

230 V AC 400 V AC 480 V AC 230 V AC

1 2 3

4 5 6

1 2 3

4 5 6

1 2 3

4 5 6

Electrical parameters

50 kA

100 kA

Max discharge current I (8/20 µs)max

-

Impulse current specific energy W/R 156,50 kJ/ohms 2,5 MJ/ohms

125 A gL/gG

Protection fuction Overcurrent

2.0 kV

Page 5: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

144

90

L2 L3

PE

L1 L1′ L3′L2′ N′N

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

144

90

L2 L3

N

L1 L1′ L3′L2′ PE′PE

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

108

90

L1

PEN

L1′ L2 L2′ L3 L3′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

108

90

LL1 L2L1 ′ L2′

N

PE′PE

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

72

90

L

PE

L′ N N′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

72

90

L L′ PE

N

PE′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60 Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

Acessibility Inaccessible

Device length 90 mm

Device width 36, 72, 108, 144 mm

Device height 65 mm

Method of mounting fixed

Mechanical parameters

Degree of protection IP 20

Enclosure material thermoplastic

installation indoor

Range of operating temperatures TU -40 °C +70 °C...

Atmospheric pressure and altitude 80k Pa ... 106k Pa, -500 m ... 2000 m

Humidity range 5% ... 95%

Place of installation

For mounting on 35 mm DIN rail acc. to EN 60715

Cross-sectional area (min.)

Cross-sectional area (max.)

210 mm solid /flexible2 235 mm stranded / 50 mm flexible

5www.lsp-international.com

Technical Data FLP50GR

Surge Protection Devices Type 1, I = 50 kA (10/350 µs)imp

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

Dimensions

6550

5

1P 1P+N 2P

3P+N 4P

3P2P+N

36

90

L

PE

L′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

Page 6: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

Basic circuit diagram

6www.lsp-international.com

Technical Data FLP50GR

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

Surge Protection Devices Type 1, I = 50 kA (10/350 µs)imp

1P

PE

L L ′

1P+N

N

PE L L ′ PE ′

2P

PE

N N ′L L ′

2P+N

N

PE L2 L2 ′L1 L1 ′ PE′

3P

PEN

L3 L3 ′L2 L2 ′L1 L1 ′

3P+N

N

PE L3 L3 ′L2 L2 ′L1 L1 ′ PE ′

4P

PE

N N′L3 L3 ′L2 L2 ′L1 L1 ′

SPD coordination

Class I Class II

SLP40-440/xxx 0

SLP40-275/xxx ≥ 10 m

Imin

FLP50GR SLP40

FLP50GR

Min. cable length lmin

FLP50GR

SLP40

T2

L

PE

Green-ok / Red-defect

L

PE

L′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

Page 7: Surge Arrester - Type 1 FLP50GR › ... · Surge Arrester - Type 1 FLP50GR 255 V AC NPE no 1025511 FLP100GRD-NPE 1/42. 4 Technical Data FLP50GR Surge Protection Devices Type 1, I

www.lsp-international.com

Technical Data FLP50GR

© 2018 Wenzhou Arrester Electric Co., Ltd.Specifications are subject to change without notice.

Revised: 01/01/19

Surge Protection Devices Type 1, I = 50 kA (10/350 µs)imp

Connection diagrams, protection mode

TN-C (3P)

F1L1

L2

L3

F2

L2'

L3'

PEN

L1'

TN-S, TT (3P+N)

F1L1

L2

L3

F2

L1'

L2'

L3'

N

PE'PE

TN-S (4P)F1

L1'L2'L3'N'PE'

L1L2L3N

PE

F2

F1L1

L2

F2

L2'

N

L1'

TN-S, TT (2P+N)

PE'PE

F1

PE

LN

L'N'

TN-S (2P)

F2

(1P)F1

PE

L L'

F2

N

L L'

F1

F2

TN-S, TT (1P+N)

PE'PE

L1

PEN

L1′ L2 L2′ L3 L3′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

L2 L3

N

L1 L1′ L3′L2′ PE′PE

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

L2 L3

PE

L1 L1′ L3′L2′ N′N

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

LL1 L2L1 ′ L2′

N

PE′PE

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

L

PE

L′ N N′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

L L′ PE

N

PE′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

FLP100GRD-NPESurge Protector

IP20

Up 1,5 kV

255 VUc (50/60 Hz)

T2100 kAIn (8/20 ) μs

T1100 kAIimp (10/350 ) μs

L

PE

L′

FLP50GR-275

Surge Protector

IP20

T1

275 VUc (50/60Hz)

50 kAIimp (10/350 ) μs

Up 2,0 kV

315 A

7