Page 1: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

Fire Protection Systems

Super Firetemp®T Board

Grease & VentilationDuct Systems

Product Manual

Page 2: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

2FPS-199- 7-01 (new)

Table of Contents

Product Information 3

Listings 4

Product Properties 5

Board/Wrap Transition 7

Architects Specification 8

Installation Guide 10

Materials Estimating Guide 17

Suggested Installation Details 19

Page 3: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

FPS-199- 7-01 (new

Super Firetemp ® T

The structural gradfor preventing a firebuilding.

T board provides aor ventilation duct.

T board is faster, e

Check out these fe

���� No steel stud ½” air gap vs

� One Layer vs���� Requires few���� Butt joints���� No taping���� 1/3” installat

G

Super Firetemp® T board

3)

Board from Johns Manville was made for grease and Ventilation ducts.

e calcium silicate material tested to 2000 F is the best of all alternatives in a kitchen grease or ventilation duct fire from spreading throughout a

1 and 2 hour fire rated enclosure around any kitchen exhaust hood, duct

asier and more economical to install than traditional drywall.

atures and benefits of T-board compared to drywall:

framing 4”-6” 3-5er screws

ion time

���� One Inspection���� Easily cut to fit���� Zero clearance to combustibles���� Simple clean out doors���� Compliance to UL 1978 Grease duct ISO-6944 ventilation duct

Designed to Protectrease and Ventilation ducts

Page 4: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

4FPS-199- 7-01 (new)

Listings System Testing & ApprovalsGrease DuctUL YYET MH 19893OPL 16053-1 GD 503 R

GD 505 C GD 515 RSBCCI PST & ESI 2134Air DuctOPL VAD 521 RULC FRD-11Firestop ApprovalsUL W-L-7055

C-AJ-7060 C-AJ-7061OPL FS546 W FS547 W FS 551 W

UL 1978 – Standard for grease ducts – internal fire testNormal Temperature test (soaking heat) 500 FAbnormal Temperature test (grease duct fire) 2000 F

ASTM E119 –External Fire Test2 hour full engulfment test

ASTM E814 –Firestop penetration2 hour engulfment with hose stream test

ISO-6944- Ventilation duct standard1 or 2 hour full engulfment

NFPA 96 – Standard for ventilation control and fire protection ofcommercial cooking operations

Field fabrication criteria for zero clearance to combustible

System Testing and Listing

The enclosure meets the following requirements:

Agency ListingOPL 16053-1

#07820 Classification - 48" ductsISO-6944 - 1985 for Ventilation Ducts

UL UL Classification YYET - 24" ductsNFPA 96 Standard for Ventilation Control and Fire

Protection of Commercial Cooking OperationSBCCI Southern Building Code Congress International

When installed according to the directions stated herein

Page 5: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

5FPS-199- 7-01 (new)

DescriptionSuper Firetemp® T board is an inorganic,incombustible material. Chemically, Super Firetemp®T board features a tobermorite crystal structure thatresults in exceptional strength and controlled waterof hydration. Super Firetemp® T board is composedprimarily of lime, silica, and reinforcing fibers. Theproduct is white, essentially dust-free, and containsno asbestos. It has been fire tested up to 2000°F(1093°C).

ApplicationsUses include 1 & 2 hour fire-rated enclosures aroundkitchen exhaust hoods and ventilation ducts. SuperFiretemp® T board meets the requirements definedby Underwriters Laboratories (UL), the National FireProtection Association (NFPA 96), and SBCCI. It isan alternative method of providing duct fireprotection instead of the traditional shaft wallenclosure construction around a duct. For designflexibility, JM also has the first approved grease ductenclosure that combines Super Firetemp® T boardwith Firetemp® Wrap.

AdvantagesSystem Design. Super Firetemp® T board is anOmega Point Laboratories and UnderwritersLaboratories (UL) classified board. The product isnon combustible and complies with 25/50 flame andsmoke requirements per ASTM E84.

Simplified Installation. Super Firetemp® T board islightweight. Cutting and fabrication of the boardaround ducts is easily accomplished, therebyminimizing labor cost.

Space Saving. Super Firetemp® T board is a singlelayer system with zero clearance to combustiblewhich makes it ideal for tight installations.

Tough Board. The board is self supporting and doesnot depend on the strength of the duct to supportthe weight of the fire protection system.

Attractive. The product’s sanded surface readilyaccepts oil-based paints, wall coverings and curedveneers.

Fire Rated Doors. Super Firetemp® T board beingstrong and rigid will allow for the installation oftypical fire rated inspection doors used in shaft wallenclosures (check local codes for applicability andapproval for use).

System Testing and ApprovalsASTM C 656, Type II, Grade 5ASTM C 795: PassesASTM E 84: Flame Spread: 0, Smoke Development:0ASTM E 136: PassesASTM E 119; UL 263; NFPA 251:1 to 2 hour rating for fire rated enclosureUL 1978: Internal Grease Duct and Air Duct FireTestASTM E 814; UL 1479: Through penetration, 2-hour“F” and “T” ratings using Firetemp® CI & SIfirestopping products.Underwriters Laboratories Inc. YYETOmega Point Laboratories

Available FormsSuper Firetemp® T board is manufactured in 4' x 8'(1.22 m x 2.44 m) panels with a sanded finish onone or both sides. The standard thickness forSuper Firetemp® T board is 2" (51 mm).

Technical ServicesFor technical information and assistance regardingapplication information, code approvals andperformance specifications, call 1-800-872-0338. Ifthis piece is more than one year old, please contactJohns Manville for the current information.

Order PlacementRefer to the maps on the back page to find theappropriate location for placing orders.

Super Firetemp® T BoardDuct Insulation

Page 6: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

6FPS-199- 7-01 (new)

SpecificationsPhysical PropertiesDensity (Average) . . . . . . . . . . . . . . ……….. 18 pcf (288 kg/m3)Maximum Recommended Continuous Service Temperature . . . . . . . . . . . . . . . . . ……1200°F (649°C)Flexural Strength . . . . . . . . . . . . . . . . . . . . …. 140 psi (965 kPa) Compressive Strength@ 10% Deformation. . . . . . . . . . . . . . . . ……400 psi (2,758 kPa)Moisture Content, NormalPercentage of Dry weight. . . . . . . . . . . . . .. ……….. . . . . . . . . . 4

Standard SizesThickness* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2" (51 mm)Sheet Size . . . . . . . . . . . . . . . . . . . . . . .. 4' x 8' (1.22 m x 2.44 m)Dimensional TolerancesLength and Width . . . . . . . . . . . . . . . . . . . . . . . . + 1/8" (3 mm)Thickness (sanded one side) . ……. . – 1/8" (3 mm) +1/4" (6 mm)* Other thickness' available upon request

Linear Shrinkage After 24 Hours at Temperatures, % Weight

Temp °F (°C) Length Width Thickness Loss1200 (649) <1% <1% <1-1/2% <9%

Thermal Conductivity (“k”)Mean Temp “k”°F °C Btu in/(hr sqft°F) W/m °K200 93 .54 0.078400 204 .61 0.088600 316 .67 0.097800 427 .73 0.105

Super Calstik AdhesiveColor: whiteAvailable in 1-5 gallon pails

Firestop Barrier

Firetemp CI, SI or SEReady to use water based sealant offered as caulk or spray masticColors: CI (Red), SI (Blue), SE (Grey)

Firetemp® Wrap is a high temperature insulation blanket specificallydesigned to provide one and two hour fire ratings around manycommercial applications.

Super Firetemp® T BoardDuct Insulation

Page 7: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

7FPS-199- 7-01 (new)

AdvantagesSimplified Installation. This transition provides flexibilityto the installer to utilize the installation benefits of theboard and wrap, while providing an approved greaseduct fire protection system. Use of this transition willallow for time or labor saving by maximizing installationefficiency and by providing flexibility for installation indifficult spaces. Before and after any transition followthe installation recommendations described for the boardand wrap products.

System Testing and ApprovalsThis transition using Super Firetemp T board andFiretemp Wrap has been fully tested against internalgrease duct fires (UL 1978), external fires (ASTM E119/UL 263), through penetration, insulated duct fires (ASTME814/ UL 1479), and surface burning (ASTM E84/UL723). Omega Point Laboratories (OPL) fire endurancetesting agency accredited by ICBO, BOCA and SBCCI(National Evaluation Services) in the United Statesperformed these tests and have provided referencelistings.

InstallationInstall board and wrap as described in installation guides before or after transition area.

At transition, install board, then butt inner layer of wrap next to board. Hold first layer of blanket in place by attaching ½”stainless steel band (0.0015” thick) 1 ½” from edge of blanket. Coat a 5-inch width of board, with Super Calstik™adhesive, adjacent to butt joint of wrap. Overlap the second layer of wrap a minimum of 5 inches over the board and incontact with the Super Calstik® adhesive. Overlap the blanket a minimum of 3 inches over itself. Attached 2 ½” longcoarse dry wall screws with washers (1 1/2” speed clips) every 8” OC and from 3-4 inches from the edge of each corner.Attach additional stainless steel bands over wrap as described in wrap installation guide. See Figure 1 for visual depictionof board/wrap transition.

Super Firetemp® T board and Firetemp® WrapTransition - Installation Guide

Super Firetemp T Board and WrapTransition - Joint System

Metal BandsSuper Calstik Adhesive

Firetemp WrapSuper FiretempBoard

5" Blanket overlapover Board

2 1/2" coarse drywall-screws & 3/4" washers

Figure 1

Inner Layer

Exterior Layer

T BoardWrap

Page 8: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

8FPS 199 - 7-01 (new)

Architects Specification - Super Firetemp® T Board

Johns Manville Super Firetemp T board Commercial Kitchen Grease and Air Ventilation Duct System

Part 1 - General

1.01 Description of System

A. Work in this section includes labor, material, and equipment to provided a 1 and 2-hour fire-resistiveenclosure with zero clearance to combustibles for commercial kitchen grease and ventilation ductsystems.

B. Related Sections:1. Section 04200 – Unit Masonry2. Section 05500 - Metal Fabrication3. Section 07270 - Firestopping4. Section 09260 - Gypsum Wallboard Systems5. Section 15890 - Ductwork

1.02 References

A. Test Standards for evaluating and rating performance of fire resistive duct wrap systems.1. Underwriters Laboratories, Inc. (UL)

a. UL 723, surface burning characteristics per ASTM E-84b. UL 1978, Standard for Grease ducts, Clearance to Combustiblesc. UL 1479, Through-Penetration 2 hour Firestop Test.d. Fire Protection Equipment Directory, Grease Duct Enclosures, YYET

2. Underwriters Laboratory of Canada (ULC)a. Underwriters Laboratory of Canada, ISO-6944-1985 2 hour large Ventilation Duct fire resistive

enclosure test.b. Underwriters Laboratory of Canada, CAN4S115-M85/UL1479 2 hour Through Penetration

Firestop Tests3. Omega Point Laboratories (OPL)

a. UL 1978 Interior fire testb. ASTM E-119 2 hour external total engulfment testc. ASTM E814 standard method of fire test of through penetration firestops – 2-hour firestop testd. ASTM E136 Combustibilitye. OPL Grease Duct Enclosures, GDf. OPL Ventilation Duct Enclosures, VAD

4. American Society for Testing and Materials (ASTM)a. E119 Standard Method of Fire tests of building construction and material; 2-hour external total

engulfment test.b. E814, Standard Method of Fire Tests of Through-Penetration Fire stops; 2-hour firestop tests.c. E136, Combustibility Testd. E84, Surface Burning Characteristicse. C518 thermal Transmission Properties

5. ISO Standarda. ISO-6944-1985 Part24 Fire Resistance Tests – Ventilation ducts

6. International Mechanical Code, Section 506.6 - compliance7. Southern Building Code Congress (SBCCI) compliance8. NFPA 96, 1994 Edition, Ventilation Control & Fire Protection of Commercial Cooking Operations

Page 9: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

9FPS 199 - 7-01 (new)

1.03 System Description

A. A light weight, non-asbestos, calcium-silicate, fire-resistive board. This fire-resistive board is a two-hourenclosure system, with zero clearance to combustibles, when used with a listed and approved through-penetration firestop system.

B. Performance Requirements:1. Two hour fire resistive enclosure assembly, ASTM E119: Total Engulfment test2. Zero clearance to combustible, UL 1978 Standard for Grease Ducts3. Class Interior Finish materials, ASTM E-8144. Through Penetration protection systems for commercial kitchen grease and air ventilation ducts,

ASTM E814.5. Non-Combustibility, ASTM E136.6. ISO-6944-1985, Fire Resistance Tests – Ventilation ducts

1.04 Submittals

A. Submit independent third listings or test reports substantiating performance requirements and codecompliance along with manufacturer’s installation instructions.

1.05 Delivery, Storage, Handling

A. Deliver materials in original sealed containers or unopened packages, clearly labeled with manufacturer’sname, product identification, and lot numbers.

B. Store materials out of weather and in an enclosed shelter.

Part 2 Products

2.01 Manufacturer

A. Fire Resistive materials as supplied by Johns Manville Intl, Super Firetemp® T board, Super CalstikAdhesive, and Firetemp Firestop products (CI, SI, or SE).

2.02 Materials

A. Fire Resistive Super Firetemp T Board – 2” thickB. Super Calstik AdhesiveC. Type S drywall screws – 3-41/2” in lengthD. Through Penetration Firestop Materials

1. Firetemp firestop (CI, SI or SE) ¼ to ½” in thickness2. Soluble Amorphous Wool Blanket or Mineral wool batt – 8 or 4 pcf density – packed in annular

space.

Part 3 Execution

3.01 Preparation

A. Remove dirt and dust, and clean surfaces for openings and items penetrating rated floors and walls.

3.02 Installation

A. Install Super Firetemp T board in accordance with Manufacturer’s instructions and referenced standards.

3.03 Warning Labels

A. Provide warning label on duct1. Once every 20 feet2. On each clean-out door

To discourage contractors or workers from disturbing fire resistive system.

B. Wording - “Fire resistive Enclosure- Do Not Remove”

3.04 Repair Procedure

A. Repair damaged surface in accordance with manufacturer’s instructions.

Page 10: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

10FPS 199 - 7-01 (new)

Installation InstructionsPart 1 - General

1.01 Description of SystemA. This fireproofing system shall be a

complete system of Fireproofing materialssupplied as specified by Johns Manville.

B. This system is designed for application ongrease ducts as shown on the drawings.

1.02 Quality AssuranceA. Supplier Qualifications: The Super Firetemp

system as supplied by Johns Manville isapproved for use on this project.

B. Applicator Qualifications: Applicatorsbidding on this work represent that theyare fully apprised of Super Firetempproducts and application procedures.

1.03 Submittals A. Product Data: Submit copies of Super

Firetemp data and these applicationinstructions and drawings.

B. Samples: Submit samples of SuperFiretemp board, Super Calstik and othermaterials as requested.

1.04 Product Delivery, Storage and Handling A. Materials shall be delivered in packaged

lots, clearly marked with Johns Manville'sname, brand and type of material with ULor other labels as required.

B. Materials shall be stored in a clean, drywarehouse with careful handling to avoiddamage.

1.05 Job ConditionsA. Environmental conditions: while a warm

environment is desirable, Super Firetempboard may be applied in subfreezing or wetweather, if necessary. The only restrictionin subfreezing conditions is to provideenough heat to prevent the Super Calstikfrom freezing before it cures.

B. Ventilation: When Johns Manville SuperFiretemp is saw-cut in the field, workersmust follow personal protection asindicated in the product warning label orMaterial Safety Data Sheet (MSDS).

C. Coordination: Fireproofing must becoordinated with other construction toavoid retrofits that would interfere with theintegrity of the finished fireproofing job.At the same time, the fireproofing shouldbe applied last to minimize the possibilityof incidental damage to the finishedsystem.

1.06 CodesA. Install all Super Firetemp board in strict

accordance with all published, applicableregulations by local, state or federalagencies that may have jurisdiction.

B. The Grease Duct Enclosure and throughfirestop penetration is listed underUnderwriters Laboratories under YYET andOmega Point Laboratories Classification16053-1in the OPL Fire ProtectionEquipment Directory.

C. The Grease Duct Insulation andFireproofing System complies with SBCCI.

D. For 1 & 2 hour rated assemblies, use 2"(51mm) thick Super Firetemp T.

E. The Ventilation duct Enclosure and throughfirestop penetration is listed under OmegaPoint Laboratories Classification 15053-1.

Part 2 - Product Information

2.01 Super FiretempA. Description: Super Firetemp is press-

molded tobermorite calcium silicate boardpossessing such strength and resiliencythat it can be installed without damage.

B. Typical Average Properties:Super Firetemp T BoardDensity, pcf (kg/m3) 18 (288)Flexural Strength, psi (kPa) 140 (965)Compressive Strength @ 10% deformation, psi (kPa) 400 (2760)

C. Easy Application 1 May be field-installed using ordinary tools

such as drywall screws and a powerscrewdriver or nails and a power nail gun.

2 May be field-cut using a circular sawequipped with a carbide-tipped blade or areciprocating saw equipped with a metalcutting blade. Precut in a shop forminimum on-site effort. Field cuts, with acircular saw, should be made using astraightedge for the saw to follow.

3 Miscellaneous materials such as drywallscrews and Super Calstik Glue as approvedby Johns Manville.

D. Hazardous Warning 1 For the latest health and safety information

for this product, please refer to the JohnsManville Material Safety Data Sheet(MSDS) No. 2005-1.0, or contact theJohns Manville Product Information Centerat 1-800-654-3103.

2 Contains no asbestos.

Part 3 - Installation

3.01 InspectionA. Verify that the ducts to be fireproofed are

as represented in the design criteria.

3.02 Job PreparationA. The metal duct must comply with the code

The enclosure is constructed of minimum2 " (51 mm) thick Super Firetemp T for a1-hour or 2-hour enclosure. The exterior of

Page 11: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

11FPS 199 - 7-01 (new)

the enclosure is permitted to be in directcontact with combustibles.

B. The installation of Super Firetemp boardmust be coordinated with otherconstruction work to avoid retrofits ordamage to the enclosure. Plan the worksuch that the enclosure will not have to beopened or taken apart after it has beeninstalled.

C. The enclosure must be located so that theinstaller does not have to cut into theSuper Firetemp to make room for adjacentequipment, pipe fittings, electrical fittings,etc. Verify there is sufficient room for theaccess doors to be removed so the ductcan be inspected and cleaned.

D. Super Firetemp board can be installed inany weather condition. In subfreezingtemperatures, provide enough heat toallow the adhesive to set before it freezes.The Super Calstik adhesive must be keptabove the freezing point to preventseparation.

E. It is important to have the proper tools.Super Firetemp board can be cut withordinary handsaws or power tools,however the blades will dull quickly. Usecarbide-tipped blades for maximum life.

3.03 InstallationA. Support the duct enclosure using a

conventional trapeze arrangement or simplyrest it on the ceiling support structures(Figure 1 & 2). The structures must becapable of supporting the weight of theSuper Firetemp boards and the weight ofthe duct assembly (Figure 4). Supportsmust be no further apart than 4' (1.22 m)O.C. When stiffeners are used on the metalduct, place the supports under theassembly so that the metal stiffenermembers are within 6" (152 mm) of thesupports (Figure 3).

B. For horizontal ducts the minimum clearancebetween the duct and the enclosure shallbe zero inches on the bottom, 1/4" (6 mm)(1/2" - 12mm for duct >24") on each sideand 1/2" (12 mm) (1"- 24mm for duct>24") on the top (Figure 4). Ifreinforcements are used for the particularduct, the spacing must be maintainedbetween the reinforcement and the SuperFiretemp board.

C. For vertical ducts, provide 1/4" (6 mm)(1/2" - 12mm for ducts >24") clearancebetween the duct and enclosure on all foursides for expansion clearance. Observethese clearances at all locations along thelength of the duct. If reinforcements areused for the particular duct, the spacingmust be maintained between thereinforcement and the Super Firetempboard.

D. Provide adequate clearance at the end ofall straight runs to allow for expansion ofthe metal duct inside the enclosure. Allow2" (51 mm) of expansion for every 100'(30.5 m) of straight run length.

E. Completely cover the duct with SuperFiretemp board. Use 2 " (50mm) SuperFiretemp T for 1-hour and 2-hour ratedassemblies. Butt joints should be staggereda minimum of 12 inches from other buttjoints (Figure 2). No more than 2 adjacentbutt joints should be placed in a commonplane surrounding a duct.

F. Cement all joints together with SuperCalstik by buttering both mating surfaceswith cement before joining. Use enoughSuper Calstik so that it squeezes out wherethe boards are mated together. Usageshould be about 50' (15.3 m) of joint (1/8"[3 mm] thick) per gallon (3.8 liters) ofSuper Calstik.

G. Fasten Super Firetemp sections togetherwith drywall screws or nails (8"[203 mm]O.C.) at joints where sections meet at rightangles. Screws or nails should be at least5" long (Screws or nails for ducts at orbelow cross-sectional dimensions of 24"(310 mm) by 24" (610 mm) 24" should beat least 3 1/2" long).

H. Provide adequate support at the bottom oflong vertical runs. On multiple-storyvertical runs, the Super Firetemp enclosureshall be supported at every floor level(Figure 5).

I. In multistory buildings product can beinstalled deck to deck or as a continuousenclosure. For deck to deck run the metalduct up through the penetrations in aconcrete floor system with metal supportsfor the metal duct resting on the floor ateach level. For continuous enclosuresthrough fire rated walls or floors followfirestop recommendations shown in Figures6A or 6B.

J. Whenever clean-out covers are required,use a rated access door or fabricate anaccess clean-out cover as shown in Figure7. Use a 1/8" (3 mm) thick gasket madefrom glass, mineral wool or ceramic fiberpaper around the outer 3" (76 mm) of theaccess opening to seal the door cover.Hold the fabricated access door in placewith two metal or wooden bars, usingwing nuts as shown in Figure 7.

K. Spackle all joints with Super Calstik.

L. Super Firetemp L and or M can becombined with Super Firetemp T usingSuper Calstik adhesive to form a fire ratedenclosure.

Page 12: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

Notes:1. Where required, duct shall be sloped by shimmingunder the duct and/or the Super Firetemp enclosure.

2. Duct Hangers and support for horizontal and vertical

Figure 1Super Firetemp Grease Duct EnclosureSystem for 1 & 2 Hour Fire Protection

12FPS 199 - 7-01 (new)

LegendA. Approved exhaust hoodB. Building wallC. Duct clean-out doorD. Support flange attached to enclosureE. Ceiling system

runs shall be designed to provide adequate support forthe duct and the building and mechanical codes.

3. Labels shall be placed adjacent to all clean-outopenings, which state that cover must be replaced afteruse.

4. Duct and Super Firetemp shall be supported byhangers from roof or by laying directly on ceiling joists.Maximum distance between supports is 4'.

5. Lateral support for vertical runs shall be providedevery 10' or at every floor level in multistory structures.

6. Lateral support for vertical portion of the enclosuremust be capable of supporting the weight of the ductand the enclosure.

7. Calculations for the supporting members andconnection shall be submitted to the building official forapproval.

Figure 2Typical Installation

Legend

A. 2" Thick Super Firetemp T BoardB. Drywall screws min 5" (3 1/2" screws or nails for ducts equal to or less then 2' in cross sectional dimensions) 8" on centerC. Seal all joints with Super Calstik glue Stagger seamsD. Maintain clearance as required

Page 13: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

13FPS 199 - 7-01 (new)

Figure 4Typical Cross Section

Legend

A. Spacing between duct and enclosure Vertical runs spacing nominal 1/4" (1/2" for ducts > 24" in size) Horizontal runs duct permitted to rest on board (note 1) 1/2” spacing (ducts > 24" use 1" air gap for top of duct)B. Trapeze support sized for weight 1/2" threaded rod for 24" duct 5/8" threaded rod for 48" duct 2 by 2 by 1/4" angle Iron

LegendA. Duct Stiffener when required due to size

B. Weight Support

Note Maintain 1/4" air space (1/2" for ducts>24") on all sides –bottom of duct may be indirect contact with insulation

Figure 3Typical Elbow

Page 14: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

14FPS 199 - 7-01 (new)

Figure 6Multi-story Grease duct Enclosure Construction

LegendA. Super Firetemp EnclosureB. 22 msg galvanized steel floortrackC. 1/8" thick angle ironD. Mineral fiber safingE. Concrete deckF. Angle iron support clips

Note: Support clips must not sealpenetration and restrict airmovement

Figure 5External Support

LegendA. Super Firetemp enclosureB. Weight support collarC. Metal support bracket

Note:Weight support required every10' of vertical travel.

Page 15: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

15FPS 199 - 7-01 (new)

Mastic 1/4" thickFiretemp SI

Firetemp Wrap or 8 pcf soluble amorphourswool blanket wedged between fire rated floor

or wall and Super Firetemp Board

Concrete

Mastic 1/16" thickFiretemp SI

5" screw

Calstik Adhesive

Figure 6AFirestop PenetrationFor Ducts > 24" to 48"

Super Firetemp Board

Steel grease duct

Mastic 1/2" thickFiretemp CI orFiretemp SI

Firetemp Wrap or 8 pcf soluble amorphourswool blanket wedged between fire rated floor

or wall and Super Firetemp Board

Concrete or two hour fire ratedgypsum for wall

Figure 6BFirestop PenetrationFor Duct ≤ 24"

Super Firetemp Board

Steel grease duct

Page 16: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

16FPS 199 - 7-01 (new)

Figure 7Clean-out Door for Kitchen Grease Duct Enclosure System

LegendA. Two layers of Super Firetemp board secured togetherB. Super Firetemp Support BlockC. Metal BarsD. Wing nutsE. Gasket

Notes:1. Maintain 3" overlap around all sides ofopening.2. Support Blocks may be on sides.3. Use 1/8" thick gasket between door andenclosure (acceptable gasket can be madefrom fiberglass, ceramic fiber, mineral fiber).4. Spacer bar to be 2 1/2" by 2 1/2" barattached to enclosure with adhesive andscrews.

Page 17: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

17FPS 199 - 7-01 (new)

Super Firetemp® T boardMaterial Estimating Guide

Circular Ducts

Estimates include the following:Air gap on all sides of duct (1/4” or ½” depending upon duct sizeTypical flange and reforcement ribs (per SMANCA) included and added to duct size

Actual usage may vary depending upon exact job requirements.

Duct sizeDiameter Air Gap Estimated Diameter Air Gap Estimated

Usage Usage (In) (In) (sf/lf of duct) (In) (In) (sf/lf of duct)

4 0.25 2.3 34 0.5 13.06 0.25 3.0 36 0.5 13.78 0.25 3.7 40 0.5 15.110 0.25 4.4 44 0.5 16.512 0.25 5.1 48 0.5 17.914 0.25 5.8 52 0.5 19.316 0.25 6.5 56 0.5 20.718 0.25 7.2 60 0.5 22.120 0.25 7.9 64 0.5 23.522 0.25 8.6 68 0.5 24.924 0.25 9.3 72 0.5 26.326 0.5 10.2 76 0.5 27.728 0.5 10.9 80 0.5 29.130 0.5 11.6 84 0.5 30.532 0.5 12.3

Page 18: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

18FPS 199 - 7-01 (new)

Super Firetemp® T boardMaterial Estimating Guide

Square or Rectangular Ducts

Estimates include the following:Air gap on all sides of duct (1/4” or ½” depending upon duct sizeTypical flange and reforcement ribs (per SMANCA) included and added to duct size

Actual usage may vary depending upon exact job requirements.

Semi-Perimeter = duct width + duct height

Duct sizeSemi-Perimeter Air Gap Estimated Semi-Perimeter Air Gap Estimated

Usage Usage (In) (In) (sf/lf of duct) (In) (In) (sf/lf of duct)

18 0.25 4.0 100 0.5 19.620 0.25 4.4 104 0.5 20.322 0.25 4.7 108 0.5 21.024 0.25 5.1 112 0.5 21.726 0.25 5.4 116 0.5 22.428 0.25 5.8 120 0.5 23.130 0.25 6.1 124 0.5 23.832 0.25 6.5 128 0.5 24.534 0.25 6.8 132 0.5 25.236 0.25 7.2 136 0.5 25.938 0.25 7.5 140 0.5 26.640 0.25 7.9 144 0.5 27.344 0.25 8.6 148 0.5 28.048 0.25 9.3 152 0.5 28.752 0.5 10.7 156 0.5 29.456 0.5 11.4 160 0.5 30.160 0.5 12.4 164 0.5 30.864 0.5 13.1 168 0.5 31.568 0.5 13.8 172 0.5 32.272 0.5 14.5 176 0.5 32.976 0.5 15.2 180 0.5 33.680 0.5 15.9 184 0.5 34.384 0.5 16.6 188 0.5 35.088 0.5 17.4 192 0.5 35.792 0.5 18.196 0.5 18.8

Page 19: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

19FPS 199 - 7-01 (new)

Legend

1. Duct2. Super Firetemp Board3. Angle Iron Duct Support4. Drywall Screws5. Calstik Adhesive6. Threaded Rod7. Threaded Rod Coupler8. Anchor Support9. Nut and Washer10 SFT Board Supports

Suggested Installation MethodExtended Duct Support for Long Vertical Runs

Super FiretempR Board

1

34

6

5

2 7

8

9

10

Angle Iron Supports locatedevery 10 to 15 feet depend-ing upon duct size andweight. Super Firetempboard compression proper-ties designed to withstandcompressive loads of up to30 feet in length.

Note:Angle Iron, threaded rod, and anchorsupports should be sized for weight ofduct being installed.Follow UMC or SMACA Guidelines.

SuperFiretemp Board Supports for AngleIron Attached to Grease Duct Insulationusing drywall screws (3" from edge and12" OC) and Super Calstik Adhesive.

Page 20: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

20FPS 199 - 7-01 (new)

2

4

Super Firetemp BoardLocation Within Slab

Note BoardButts Up to Angle Ironand Coated withCalstik Adhesive

Legend

1. Duct2. Super Firetemp Board3. Angle Iron Duct Support4. Drywall Screws5. Calstik Adhesive6. Concrete Slab7. Firestop as Required

Super FiretempR BoardChase Wall with Multiple Ducts

Suggested Installation Method forInstalling Board Over Standard Duct

Support1

3

6

5Board Knotched Around Angle Ironto Allow for Air Gap and Tight FitBetween Boards

5

LEGEND

1 SUPER FIRETEMP BOARD2 SHAFT ENCLOSURE (X TYPE)3 DRYWALL SCREWS (8" O.C.)4 CALSTIKTM ADHESIVE (COVER JOINT)5 STEEL GREASE DUCT6 SHAFT CLEARANCE MIN. 3"7 AIR GAP8 1/8" THICK ANGLE IRON SHOOT NAILS OR BOLTS INTO CONCRETE TO HOLD ANGLE IRON9 FIRE RATED FLOOR

Page 21: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

21FPS 199 - 7-01 (new)

D R Y WALL SC R EW S

SU P ER FI R ET EM P B OAR D

34

2

1

L E G E N D

5

MINI MUM 1/4" AIR GAP (1/ 2" F OR D UCTS > 24"

S UPER C A LS TI K AD H ESIVE

SH AF T WAL L LI NE R O R X RAT ED D R Y WALL

SUGGESTED INSTALLATIONFOR 900 SHAFT WALL TRANSISTION

BETWEEN SUPER FIRETEMP BOARD AND SHAFT WALL LINER

NOTE: DUCTS AND INSULATION MUST BE SUPPORTED USINGSTANDARD ROD AND TRAPEZE.FOLLOW UMC OR SMACA GUIDELINES.

1

2

2

3

3

4

DUCT

5

1

2

4

1

2

3

3

Page 22: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

22FPS 199 - 7-01 (new)

5

6

1 2

3

4

7

6-8"12-16"

8

5

12

3

4

7

6-8"

6

Legend

1 Super Firetemp Board2 Shaft Enclosure ( X type)3 Drywall screws (8" O.C.)4 Calstik adhesive5 steel grease duct6 Shaft clearance Min. 3"7 Air Gap8 Steel Stud

Horizontal or Vertical Shaft Transition

Super FiretempR Board and Fire Rated Drywall Joint

5

1 2

3

47

12 -16"

6

3"3"

Page 23: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

23FPS 199 - 7-01 (new)

1

2

5 DUCT

AIRGAP*

5

6

7

6

6

8

8

1

5 DUCT

5

6

8

8

9

9

9

1

2

4

56

DUCT

53

AIRGAP*

6

7

a-a b-b c-c

4

4

ORDuctThisside

DuctThisside

9

8

5DuctThisside

OR

9

5

3

AIR GAP*

1

2

5

6

DUCT

47

5

5

2

3 5

8

5

a-a b-b

a-a b-b c-c

c-c

1 CO NC R ET E SL AB2 SU PER FI RETE MP BOA RD3 CO N CR ET E FAST EN ER SY STE M4 C CH ANNEL- NOMI NAL 2" BY 1 1/2 " BY 2" - 22 MSG GA LVINIZED ST EEL OR ANGLE IRO N 2" BY 2 " - 22 MSG OR METAL STU D5 D R YWA LL SC RE WS6 SUPER C ALSTI K A DH ESIVE7 MI NIMUM 1/4" AIR GAP ( 1/2" FOR D UCTS> 24")8 SHA FT W AL L LI NE R FO R X R AT ED D RY W AL L9 META L ST UD

L E G E N D

SUGGESTED INSTALLATIONFOR 3 SIDED HORIZONTAL SHAFT TRANSITION

SUPER FIRETEMP BOARD AND FIRE RATED DRYWALL

NOTE: DUCTS AND INSULATION MUST BE SUPPORTED USINGSTANDARD ROD AND TRAPEZE (TRAPEZE ATTACHED TO WALL)FOLLOW UMC OR SMACA GUIDELINES.

* AIR GAP FROM DUCT TO CEILING OR TO WALL MAY BEEQUAL TO OR GREATER THAN MINIMUM AIR GAP PERLISTING.

OR

Page 24: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

24FPS 199 - 7-01 (new)

3 1 /2 " DR Y WALL S CR EWS & SU PE R CA LS TI K AD HESI VE

SU PER FI R ETE M P B OAR D

CO N C R ET E SLAB

CO N C RET E F ASTE N ER S YST EM34

2

1

L E G E N D

5

6 MINI MUM 1/4" AIR GAP (1/ 2" FOR D UCTS > 2 4"

C CHANNEL - NO MIN AL 2" BY 1 1/ 2"- 25 MSG GALVI NIZ ED S TEEL

OR A NGLE I RON 2 " BY 2 " - 2 2 M SG O R M ETAL S TUD S

DUCT

2

5

6

1

4

OR

45

3

ORDuctThisside

DuctThisside

AIRGAP *

NOTE: DUCTS AND INSULATION MUST BE SUPPORTED USING STAN-DARD ROD AND TRAPEZE (TRAPEZE ATTACHED TO WALL) FOLLOWUMC OR SMACA GUIDELINES.

4

* AIR GAP FROM DUCT TO CEILING OR TO WALL MAY BEEQUAL TO OR GREATER THAN MINIMUM AIR GAP PERLISTING.

SUPER FIRETEMPR BOARD

SUGGESTED INSTALLATIONWHEN ATTACHED TO A WALL OR CEILING

2 SIDED DETAIL

3 1 /2 " DR Y WA LL SCR EWS & SU PE R CA LS TI K AD HESI VE

SU PER FI R ET EM P BOA R D

CO N C R E TE SL AB

CO N C RE T E F AS TEN E R SY STE M34

2

1

L E G E N D

5

6 MINI MUM 1/4" AIR GAP (1/ 2" F OR D UCTS > 24"

C CH ANNEL - NO MIN AL 2 " BY 1 1/ 2"- 25 MS G GALVI NIZED STEE L

OR ANGLE I RON 2 " BY 2 " - 22 M SG O R M ETAL S TUD S

1

2

4

5

6

4OR

DUCT

4

5

3

ORDuctThisside

DuctThisside

AIRGAP*

NOTE: DUCTS AND INSULATION MUST BE SUPPORTED USINGSTANDARD ROD AND TRAPEZEFOLLOW UMC OR SMACA GUIDELINES. * AIR GAP FROM DUCT TO CEILING OR TO WALL MAY BEEQUAL TO OR GREATER THAN MINIMUM AIR GAP PERLISTING.

1

2

4

5

6DUCT

5

3

AIRGAP*

SUGGESTED INSTALLATIONWHEN ATTACHED TO A WALL OR CEILING

3 SIDED DETAILSUPER FIRETEMPR BOARD

Page 25: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

25FPS 199 - 7-01 (new)

LEGEND

1 SUPER FIRETEMP BOARD2 1/4" AIR GAP OR 1/2" FOR DUCTS > 24"3 DRYWALL SCREWS4 ALL JOINTS GLUED WITH CALSTIK ADHESIVE* SEE INSTALLATION GUIDE FOR ADDITIONAL DETAILS

SUGGESTED INSTALLATIONFOR NON-RATED HOOD

FOR SUPER FIRETEMP BOARD

1

2

3

4

4*

Rated Ceiling

Page 26: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

26FPS 199 - 7-01 (new)

LEGEND

1 SUPER FIRETEMP BOARD2 1/4" AIR GAP OR 1/2" FOR DUCTS > 24"3 DRYWALL SCREWS 4"4 ALL JOINTS GLUED WITH CALSTIK ADHESIVE* SEE INSTALLATION GUIDE FOR ADDITIONAL DETAILS

SUGGESTED INSTALLATIONFOR GREASE HOOD DETAIL

FOR SUPER FIRETEMP BOARD1 OR 2 HR SYSTEM

1

2

3

4

4*

Rated Ceiling

Page 27: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

27FPS 199 - 7-01 (new)

LEGEND

1 ROOF2 SUPER FIRETEMP BOARD3 DUCT4 FLASHING5 VENT EXTERIOR - FLASHING6 MINIMIUM 1/4" AIR GAP (1/2" FOR DUCTS > 24"

SUGGESTED INSTALLATIONFOR DUCT EXITING ROOF

SUPER FIRETEMP BOARD

NOTE: DUCTS AND INSULATION MUST BESUPPORTED USING STANDARD ROD AND TRAPEZE .FOLLOW UMC OR SMACA GUIDELINES.

1

2

4

6

5

3

Page 28: Super Firetemp® T Board - coupe-feu · 5 FPS-199- 7-01 (new) Description Super Firetemp® T board is an inorganic, incombustible material. Chemically, Super Firetemp® T board features

28FPS 199 - 7-01 (new)

Product Information(800) 654-3103

International(303) 978-3310Fax: (303) 978-2627

Building Insulations Mechanical Insulations

WesternRegion

EasternRegion

United States – (800) 644-4013 Eastern Region – (800) 426-2433Canada – (800) 272-9067 Western Region – (800) 293-3393