summary of price schedule - construction of 33/11 …cable of 1.1 kv grade of following size on...

31
SL NO. ANNEXURE DESCRIPTION TOTAL AMOUNT ( In Rs.) 1 Abstract-1 Schedule of Quantities for Electrical Works 2 Abstract-2 Schedule of Quantities for Civil Works 3 Abstract-3 Schedule of Quantities for HVAC & Ventilation System 4 Abstract-4 Schedule of Quantities for Fire Detection and Alram System GRAND TOTAL SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 KV GIS SUBSTATION & ITS RELATED DISTRIBUTION NETWORK Tender for Construction of 33/11 KV GIS Substation its related Distribution Network 1 of 1

Upload: others

Post on 07-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO. ANNEXURE DESCRIPTION TOTAL AMOUNT ( In Rs.)

1 Abstract-1 Schedule of Quantities for Electrical Works

2 Abstract-2 Schedule of Quantities for Civil Works

3 Abstract-3 Schedule of Quantities for HVAC & Ventilation System

4 Abstract-4 Schedule of Quantities for Fire Detection and Alram System

GRAND TOTAL

SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 KV GIS SUBSTATION & ITS RELATED DISTRIBUTION NETWORK

Tender for Construction of 33/11 KV GIS Substation its related Distribution Network 1 of 1

Page 2: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total Qty

A POINT WIRING AND SUBMAINS1 Wiring for light/fan point/ exhaust fan point/ call bell point with 1.5sqmm FRLS

PVC insulated copper conductor single core cable in surface/ recessed steelconduit, with modular switch, modular plate, suitable GI box and earthing thepoint with 1.5sqmm FRLS PVC insulated copper conductor single core cable etcas required.

1.1 Group C Pts. 80 0 802 Wiring for light /power plug with 2X4 sq. mm FRLS PVC insulated copper

conductor single core cable in surface/ recessed steel conduit along with 1 No 4sq. mm FRLS PVC insulated copper conductor single core cable for loop earthingas required.

Meter 350 0 350

3 Wiring for light/power plug with 4X4 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed steel conduit alongwith 2 Nos 4sq. mm FRLS PVC insulated copper conductor single core cable for loop earthingas required.

Meter 100 0 100

4 Supplying and fixing following modular switch/ socket on the existing modularplate & switch box including connections but excluding modular plate etc. asrequired.

a 5/6 amps switch Each 2 0 2b 15/16 amps switch Each 26 0 26c 3 Pin 5/6 amps socket outlet Each 2 0 2d 6 pin 15/16 amp socket outlet Each 26 0 265 S/F Modular Type Electronic Fan Regulator : Supplying and fixing two module

stepped type electronic fan regulator on the existing modular plate & switch boxincluding connections but excluding modular plate etc. as required.

Nos 2 0 2

6 Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required. (GI box thicknessshall be 1.6mm)

a 1 or 2 Module (75mmX75mm) Each 14 0 14b 3 Module (100mmX75mm) Each 14 0 14c 4 Module (125mmX75mm) Each 3 0 3d 6 module ( 200mmX75mm) Each 4 0 4e 8 Module (125mmX125mm) Each 1 0 1f 12 Module ( 200 mm X 150 mm) Each 1 0 17 Supplying and fixing modular blanking plate on the existing modular plate &

switch box excluding modular plate as required.Each 4 0 4

8 Supply and fixing 3pin, 5 amp ceiling rose on the existing junction box/ woodenblock including connection etc. as required.

Each 2 0 2

9 Supplying and fixing 30amps, 415 volts, TPN industrial type, socket outlet, with 4pole and earth, metal enclosed plug top alongwith 32amps "C" curve, TPMCB, insheet steel enclosure , on surface or in recess, with chained metal cover for thesocket outlet and complete with connections, testing and commissioning etc. asrequired.

Each 2 0 2

B CABLES & CABLE TRAYS 1 HT CABLES

Supply, testing and commissioning of XLPE insulated, Aluminum conductor E

Abstract-1 Schedule of Quantities for Electrical WorksSL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

METL 1 of 15

Page 3: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

a 33kV, 3C X 300sq. mm. XLPE insulated, Aluminum conductor meter 3200 2630 5830b 33kV, 3C X 185sq. mm. XLPE insulated, Aluminum conductor meter 100 0 100c 11kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor meter 0 6850 6850d 11kV, 3C X 240 sq. mm. XLPE insulated, Aluminum conductor meter 600 800 1400e 11kV, 3C X 95 sq. mm. XLPE insulated, Aluminum conductor meter 200 0 200

2 INDOOR HT CABLE TRMINATIONSSupply, Installation, testing and commissioning of Indoor REYCHEM RPG pushon type termination kits suitable for following sizes of 33 & 11 kV, XLPE insulatedAluminum conductor E grade, strip/round wire armoured cable including lugs.

a 33kV, 3C X 300sq. mm. XLPE insulated, Aluminum conductor each 4 6 10b 33kV, 3C X 185sq. mm. XLPE insulated, Aluminum conductor each 2 0 2c 11kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor each 0 6 6d 11kV, 3C X 240 sq. mm. XLPE insulated, Aluminum conductor each 6 16 22e 11kV, 3C X 95 sq. mm. XLPE insulated, Aluminum conductor each 4 0 4

3 OUTDOOR HT CABLE TERMINATIONSSupply, Installation, testing and commissioning of Outdoor REYCHEM RPGpush on type termination kits suitable for following sizes of 33 & 11 kV, XLPEinsulated Aluminum conductor E grade, strip/round wire armoured cableincluding lugs.

a 33kV, 3C X 300sq. mm. XLPE insulated, Aluminum conductor each 4 6 10b 33kV, 3C X 185sq. mm. XLPE insulated, Aluminum conductor each 2 0 2c 11kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor each 38 38d 11kV, 3C X 240 sq. mm. XLPE insulated, Aluminum conductor each 6 16 22

4 STRAIGHT THROUGH JOINTSS/F of straight through 11 kV jointing kit Heat Shrinkable type for 11 kV,240sqmm, 3 core cable complete in all respect as per direction of /E I.

a 33kV, 3C X 300sq. mm. XLPE insulated, Aluminum conductor each 13 12 25b 11kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor each 0 28 28c 11kV, 3C X 240 sq. mm. XLPE insulated, Aluminum conductor each 3 4 7

grade, stranded, Aluminium conductor, screened by extruded semi-conductingcompound for the conductor, cross-linked poly ethylene (XLPE) insulated,screened by extruded semi-conducting compound for the insulation followed withcopper tape and inner and outer extruded PVC sheath compound Type-ST2,FRLS and galvanised steel flat wire armouring of following sizes to be buried inground / laid in trays, installation of cable markers. Civil work such as excavation,backfilling, sand, brick/tile/semi-circle hume pipe protection etc. Miscellaneousitems such as clamp, cleat cable tags etc. are included in the scope. Removal ofempty drums, cartoons & making the site normal as instructed by Client isincluded in the scope and complete in all respects as per direction of E/I.

METL 2 of 15

Page 4: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

5 HT CABLE LAYING5.1 Laying of one number PVC insulated and PVC sheathed / XLPE

power cable of 11 kV grade of following size in the existingmasonry open duct as required.

a Upto 120 sq. mm Mtrs. 200 0 200b Above 120 sq. mm and upto 400 sq. mm Mtrs. 600 7650 8250

5.2 Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 33 kV grade of following size in the existingmasonry open duct as required.

b Above 120 sq. mm and upto 400 sq. mm Mtrs. 3300 2630 5930

6 LT CABLESSupply, loading, transportation unloading at site, storages at site ,shifting fromstorage place to site of following sizes of XLPE insulated PVC sheathed, outersheath FRLS, Aluminium conductor flat strip armoured power cable of1.1 KV grade conforming to IS amended upto date and as per specifications.

a 3.5C x 300 Sqmm Metre 508 508b 3.5C x 240 Sqmm Metre 268 268c 3.5C x 120 Sqmm Metre 60 0 60d 3.5 C x 70 Sqmm Metre 1038 1038e 3.5C x 50 Sqmm Metre 2354 2354f 3.5C x 35 Sqmm Metre 3359 3359g 4C x 25 Sqmm Metre 2521 2521h 4C x 16 Sqmm Metre 313 313i 4 C x 10 Sqmm Metre 20 0 20j 4 C x 6 Sqmm Metre 20 0 20k 2C x 150 Sqmm Metre 20 20

7 MV CABLE LAYINGLaying and fixing of one number PVC insulated and PVC sheathed / XLPE powercable of 1.1 KV grade of following size on cable tray as required.

a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193 6618b Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) Mtrs. 0 3392 3392

c Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) Mtrs. 80 0 80

d Above 185 sq. mm and upto 400 sq. mm (clamped with 25/40x3mm MS flatclamp)

Mtrs. 776 776

METL 3 of 15

Page 5: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

8 Supplying and making indoor end termination with brass compression gland andaluminium lugs for following size of XLPE insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required.

a 3.5C x 300 Sqmm Each 48 48b 3.5C x 240 Sqmm Each 24 24c 3.5C x 120 Sqmm Each 4 0 4d 3.5 C x 70 Sqmm Each 8 8e 3.5C x 50 Sqmm Each 24 24f 3.5C x 35 Sqmm Each 64 64g 4C x 25 Sqmm Each 16 16h 4C x 16 Sqmm Each 8 8i 4 C x 10 Sqmm Each 4 0 4j 4 C x 6 Sqmm Each 4 0 4k 2 C x 150 Sqmm Each 4 4

9 Supply, loading, transportation unloading at site, storages at site ,shifting fromstorage place to site of following sizes of XLPE insulated PVC tapeinnersheathed, outersheath FRLS, Copper conductor flat strip armoured power cable of 1.1 KV grade conforming to IS:7098 (part-1) 1988 or amended upto dateand as per specifications.

a 3C x 4 Sqmm Metre 100 0 100b 4C x 4 Sqmm Metre 45 0 45c 2C x 6 Sqmm Metre 200 200

10 Supplying and making indoor end termination with brass compression gland andCopper lugs for following size of XLPE insulated and PVC sheathed / XLPEinsulated copper conductor cable of 1.1 KV grade as required.

a 3 C x4 Sqmm Nos. 14 0 14b 4 C x4 Sqmm Nos. 4 0 4c 2 C x 6 Sqmm Nos. 16 16

11 Supplying of following 1100 volts grade PVC insulated sheathed copperconductor armoured control cables in existing trenches cables trays, clamped onwall with suitable saddles, fixing bolts, including testing and commissioning.

a 2 core 2.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10b 4 core 2.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10c 7 core 2.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10d 10 core 2.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10e 12 core 2.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10f 2 core 1.5 sq mm PVC insulated copper conductor armoured control cables RM 10 0 10

METL 4 of 15

Page 6: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

12 Cable end termination of the following PVC insulated sheathed copperconductor control cables of 1100 volt grade including supplying and fixing ofCOPPER lugs. Double compression glands with earthing

a 7 core 2.5 sq.mm Control cable No. 2 0 2b 10 core 2.5 sq.mm Control cable No. 2 0 2c 12 core 2.5 sq mm control cables No. 2 0 2d 4 core 2.5 sq mm control cables No. 2 0 2e 2 core 2.5 sq mm PVC insulated copper conductor armoured control cables No. 2 0 2f 2 core 1.5 sq mm PVC insulated copper conductor armoured control cables No. 2 0 2

13 Providing and fixing of fire retardant sealant on wall / floor crossings/Manholes. Sqmtr 200 0 200

CABLE TRAYS 14 Supplying and installing following size of perforated Hot Dipped Galvanised Iron

cable tray (galvanisation thickness not less than 70 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspendedfrom the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

a 150 mm width X 50 mm depth X 1.6 mm thickness Metre 30 0 30b 300 mm width X 50 mm depth X 1.6 mm thickness Metre 20 0 20c 750 mm width X 75 mm depth X 2.0 mm thickness Metre 385 0 385

15 Supplying and installing following size of perforated Hot Dipped Galvanised Ironcable tray “bends” (galvanisation not less than 70 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspendedfrom the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

a 750 mm width X 75 mm depth X 2.0 mm thickness Each 10 0 1016 Supplying and installing following size of perforated Hot Dipped Galvanised Iron

cable tray “Tee” (galvanisation not less than 70 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspendedfrom the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

b 750 mm width X 75 mm depth X 2.0 mm thickness Each 4 0 417 Supplying and installing following size of perforated Hot Dipped Galvanised Iron

cable tray “Cross member” (galvanisation not less than 50 microns) withperforation not more than 17.5%, in convenient sections, joined with connectors,suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required.

a 150 mm width X 50 mm depth X 1.6 mm thickness Each 2 2 4b 300 mm width X 50 mm depth X 1.6 mm thickness Each 2 2 4c 750 mm width X 75 mm depth X 2.0 mm thickness Each 2 2 4

METL 5 of 15

Page 7: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

18 Supplying and installing following size of perforated Hot Dipped Galvanised Ironcable tray “Reducer” (galvanisation not less than 70 microns) with perforation notmore than 17.5%, in convenient sections, joined with connectors, suspendedfrom the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

a 150 mm width X 50 mm depth X 1.6 mm thickness Each 4 0 4

C DISTRIBUTION BOARDS1 Supplying and fixing following way,horizontal type three pole and neutral,sheet

steel,MCB distribution board, 415 Volts, on surface/recess,complete with tinnedcopper busbar,neutral busbar,earth bar,din bar,interconnections, powder paintedincluding earthing , numbering etc. as required. (But without MCB/RCCB/Isolator)

a 12way (4+36), Double door ( for LPDB) Each 1 12 Supplying and fixing 5 amps to 32 amps, rating, 240/415 volts, 'C' Curve ,

miniature circuit breaker suitable for inductive load of following poles in theexisting MCB DB complete with connections, testing and commissioning etc. asrequired.

a Single Pole ( for LPDB) Each 36 36b Single Pole ( for ELDB) Each 4 43 Supplying and fixing following rating, double pole, (single phase and neutral), 240

V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA inthe existing MCB DB complete with connections, testing and commissioning etc.as required.

a 40 amps ( for LPDB) Each 3 3b 25 amps ( for ELDB) Each 1 1

4 Supplying and fixing following way, single pole and neutral,sheet steel,MCBdistribution board, 415 Volts, on surface/recess,complete with tinned copperbusbar,neutral busbar,earth bar,din bar,interconnections, powder paintedincluding earthing , numbering etc. as required. (But without MCB/RCCB/Isolator)

a 4 way ( for ELDB) Each 1 1

5 Supplying and fixing of following rating, four pole , 415 volts, MCB, C curve in theexisting MCB DB complete with connections, testing and commissioning etc. asrequired.

a 63 amps Each 1 1

6 Supplying and fixing of following rating, four pole , 415 volts, MCB, C curve in theexisting MCB DB complete with connections, testing and commissioning etc. asrequired.

a 25 amps Each 1 1

METL 6 of 15

Page 8: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

D LIGHTING FIXTURES AND FANS1 Supply, loading, unloading at site, complete in all respects such as all clamps,

internal wiring between accessories and earthing terminal etc. All lighting fixturessuch as T5/ CFL/ LED shall be provided with Electronic ballast/ drivers and shallbe a part of the lighting fixtures.

1.1 40W Surface mounted Batten Type LED fixture of Philips BN108C LED 40SPSU CDL WH Diffused or equivalent

Nos. 66 0 66

1.2 70W Flood type LED fixture for transformer yard of PHILIPS BVP120 LED70CWNB FG S1 PSU GR Narrow Beam or equivalent

Nos. 3 0 3

1.3 20W BattenType LED fixture of Philips BN108C LED 20S PSU CDL WH OREQUIVALENT

Nos. 2 0 2

1.4 35W green line LED fixture of PHILIPS BRP409 LED CW 036MR FG S1 PSUGR OR EQUIVALENT at substation boundary with clamps etc. complete in allrespects.

Nos. 6 0 6

2 Ceiling Fan : Supplying of capacitor type 1200 mm sweep ceiling fan completewith blades, shakle etc. with high breeze, high speed for operation on 230V, 50Cy. Single phase A.C. supply confirming to IS 374-1979 and with double ballbearing system The fan shall be green rated with 5 star as per BEE norms.

Nos. 2 0 2

3 INSTALLATION OF LIGHTING FIXTURES a Installation, testing and commissioning of wall bracket /ceiling fittings of all sizes

and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with allaccessories including connections etc. as required.

Each 77 77

b Installation, testing & commissioning of ceiling fan , including wiring the down rodof standard lengths (30cm) with 1.5sqmm FRLS PVC insulated, copperconductor, single core cable, including providing and fixing phenolic laminatedsheet cover on the fan box etc. as required.

Each 2 2

c Erection of steel tubular or rail pole strut in cement concrete 1:3:6 (1 cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) foundationincluding excavation and refilling and secured with holding clamps, bolts, nuts,etc. as required.

Each 6 6

3.1 Supply, receiving, installation, testing and commissioning of the following lightingfixtures and poles including excavation and back filling as required

a Street lights-35W LED Street light lumaries and with the lumen level of 3500 lm.Philips Fixture Model no BRP409 LED CW 035 NR FG S1 or equivalent forStreet lighting

Nos. 6 0 6

b 5 meter Octagonal Pole with 1 meter bracket, Junction Box with hinges andlocking arrangement ,MS clamp made of 50x6 mm flat, complete in all respectincluding 2 nos. GI pipe 50mm dia having 1 mtr. length each and chuck nut forcable connection etc.

Nos. 6 0 6

METL 7 of 15

Page 9: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

3.2 Supply, laying, testing and commissioning of following size XLPE insulated, PVCinner sheathed, outer sheath FRLS, copper conductor 1100 V grade armouredcable, confirming to IS-7098 (Part-I), 1988 including excavation of earth,sand/brick protection refilling, watering & ramming complete.

a 3C x 2.5 Sqmm Cu FRLS wire from Junction box to street light Mtrs 30 30

3.3 Supply and making end termination & jointing of following size XLPE insulatedcopper conductor 1100 V grade armored cable including cost of crimped copperlugs, sockets, insulation tapes, double compression glands etc. complete.

a 3C x 2.5 Sqmm cable terminations, copper lugs etc. from Junction box to streetlight

No. 12 0 12

E EARTHING SYSTEM

a Earthing with GI earth pipe 3 Mtr long , 40 mm dia including accessories andproviding masonary enclosure with cover plate having locking arrangement andwatering pipe etc without charcoal/coke & salt as required.

Set 16 44 60

b Earthing with Copper earth plate 600mm X 600mm X 3 mm thick includingaccessories and providing masonary enclosure with cover plate having lockingarrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and saltas required.

Set 9 8 17

c Supplying and laying 40mm x 6 mm GI strip at 0.50 m below ground as strip earth electrocde, including connection/terminating with G.I. nut, bolt, spring, washeretc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I nutbolt & spring washer sapced at 50mm).

Metre 0 40 40

d Supply, installation, testing & commissioning of following sizes of G.I./Custrip/wire clamped to walls, cable trays, bus ducts, cables in recess or surface etcfor equipment /system earthing complete as required including inter connectionbetween length at joints, all fixing accessories saddles clamps etc, and otherfixing hardware material as required for proper installation.

i 40 x 10 mm strip GI RM 360 440 800e 50 X 6 mm MS Strip ( for earthing of RCC cable trench ( S/S as well as

distribution Network )RM 50 3850 3900

f Earthing with MS Rod Electrode 3 Mtr long , 40 mm dia including accessorieswithout masonary work & charcoal/coke & salt etc - For Cable trench earthing fordistribution network

Set 120 120

F LIGHTENING PROTECTION SYSTEM

METL 8 of 15

Page 10: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

a Providing and fixing G.I. tape 25 mm X 3 mm thick on parapet or surface of wallfor lightning conductor complete as required.(For horizontal run)

metre 190 190

b Providing and fixing G.I. tape 25 mm X 3 mm thick on parapet or surface of wallfor lightning conductor complete as required.(For vertical run)

metre 50 50

c Providing and fixing testing joint, made of 25 mm X 3 mm thick G.I. strip, 125 mmlong, with 4 nos. of G.I. bolts, nuts, chuck,nuts and spring washers etc. completeas required.

Each 6 6

d Earthing with GI earth pipe 3Mtr long , 40 mm dia including accessories andproviding masonary enclosure with cover plate having locking arrangement andwatering pipe etc with charcoal/coke & salt as required.

Set 6 6

G DISTRIBUTION BOARDS & PANELSMain Distribution Board PanelIncoming2 Nos. 200 amps 4 pole MCCB (20KA)2 Nos. Digital Multi-function meter with RS 485 communication port of accuracyclass-1Real TimeTotal active energy (KWH/MWH)Maximum demand (KVA/MVA) (KW/MW)Instantaneous power factorCurrentVoltageFrequency2 sets of Breaker ON / OFF / TRIP indicating lights with control MCB’s.2 sets of 0-500 Volt digital voltmeter with selector switch protected by 2 amp TPMCB’s 2 sets of 0-200 Amps digital electronic ammeter with selector switch with 1 no.200/1A, 15VA, CL-1.0 Current Transformer2 sets of R,Y,B Phase indicating lamps with control MCB’s.Bus Bars200 amps TPN aluminium bus bars (10 kA/sec) with coloured heat shrinkableinsulation sleeve.Outgoing63 amp TPN MCB (10KA) 8 Nos.32 amp TPN MCB (10KA) 2 Nos.25 amp DP MCB ( 10 kA) 1 Nos.Bus Coupler1 Nos. 200 amps 4 pole MCCB (20KA)MDB as described above Set 1 1

DC Distribution Board PanelIncoming2 Nos. 250 amps DP MCCB (20KA)2 sets of Breaker ON / OFF / TRIP indicating lights with control MCB’s.

a

b

METL 9 of 15

Page 11: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

2 sets of 0-500 Volt digital voltmeter with selector switch protected by 2 ampTP MCB’s 2 sets of 0-250 Amps digital electronic ammeter with selector switch with 1nos.250/1A, 15VA, CL-1.0 Current Transformer2 sets of R,Y,B Phase indicating lamps with control MCB’s.Bus Bars250 amps TPN, 110Volt, copper bus bars with coloured heat shrinkable insulationsleeve.Outgoing32 amp DP MCB(20KA) 8 Nos.Bus Coupler1 Nos. 250 amps DP MCCB (20KA)DC DB as described above Set 1 1

H HT PANELS, POWER AND DISTRIBUTION TRANSFORMERS, RMU, CSSi 33 kV HT Switchgear Set 1 0 1

Supply, Erection testing & commissioning of Indoor type SF6 breaker 33 kV,1250Amp, 1500 MVA, 25 KA for 1 sec Motorized complete with structure in allrespect and with all necessary protection, metering and other accessories asrequired.

33kV Centralized switchgear (SF6) with following configuration:2 nos.1250A incomer with PT.1 no.1250A of buscoupler10 nos of outgoings 630A, (6 nos.for 33 kV rings+2 nos. 33/11kV TR. +2 Spares)

Indoor type 2 panel board Bus PT, 33 KV, 3 phase, 25 KA for 1 sec with allnecessary protection, metering and other accessories as required

ii Power Transformers Nos. 2 0 212.5 MVA, 33/11 KV, Oil type, two winding, 3 Phase, Dyn11, 50Hz, ONANTransformer with 8% impedance on base MVA without negative tolerance withOLTC (+5% to -15% @1.25%) including HV & LV cable box & cable terminations.

cable terminating box with disconnecting facility for 33 kV, 300 sqmm XLPE cableoutdoor arrangement with 33KV bushings at 33kv side.

cable terminating box with disconnecting facility with 11 kv bushing for 3 nos. 11KV, 240sqmm XLPE cable at 11 side. ON load tap changer +5% to -15%Bi directional roller Conservator with drain valve & sump value Earthing terminals (two) Double diaphragm explosion vent Radiator with top & bottom shut of valve First filling of oil including makeup fill Silica gel breather with oil seal Rating and diagram plate

METL 10 of 15

Page 12: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

Air release plugBuchhoiz relay with shut off valves on poth sides.Winding temperature indicator (WTI)Oil temperature indicator (OTI )Magnetic oil level gauge pressure relief device Marshalling BOX Tap position indicatorMarking plate for OLTC Terminal marking plate Drain valve with plug &locking arrangement Filter valve Oil sampling valves (03 Nos.)

iii CONTROL RELAY PANEL FOR 33/11KV TRANSFORMERSiv Supply, installation, supervision, testing & commisioning of 33kV C& R panel

suitable for controlling single transformer complete in all respectsNos. 2 0 2

v Supply, installation, testing & commisioning of Nitrogen injection fire preventionsystem for 12.5 MVA 33/11 KV Power transformer, complete including 100 mmdia class 'C' pipe between transformer and F.E cubicle and oil pit, 12 core X 2.5sqmm FRLS armoured cable with all accessories for connections betweentransformer - circuit breaker - F.E cubicle , 2.5 sqmm X 4 core FRLS copperarmoured cable for connection between relay panel to control box etc complete inall respects

Nos. 2 0 2

Control PanelLinear Heat Sensing Cable AssemblyExtinguishing Cubical Consist of :N2 Cylinder assy. 50 ltrs with pressure gauge and required assemblyAutomatic Actuation Device : Electro mechanical Solenoid valve assembly withpilot cylinder for automatic operation of nitrogen injection and opening of oil drainvalveManual Operation of the systemOil drain Valveoil pressure Rupture Disklimit switches for indication in control panelConservator Isolation ValvePipe for oil drainage and pressure release 3''Supply of FRLS Armoured Copper cable 2.5 sqmm X 10/12 core along withaccessoriesSupply of FRLS Armoured Copper cable 2.5 sqmm X 4 core along withaccessoriesInstallation

vi 11 kV HT Panel EACH 1 0 1Indoor type Vacuum circuit breaker 11 KV, 3 phase, 20 KA for 1 sec. HT switchgear VCB breaker with all necessary protection, metering and other accessoriesas required. 2 nos. 1250A, incomer with PT.

METL 11 of 15

Page 13: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

1 no.1250A buscoupler12 nos of 630A outgoings (6 nos. for 11 kV rings+ 2 nos. for 11/.433kV StationTR.+2nos. Spares+2 nos. capacitor panel)Indoor type 2 panel board Bus PT, 11 KV, 3 phase, 20 KA for 1 sec with allnecessary protection, metering and other accessories as required

vii1.0 SITC of Compact substation (CSS)-1,1A,2,2A EACH 0 4 4

11kV, HT Panel with 1no. self powered VCB incomer.11/ 0.433kV, 1000kVA, dry type, two winding, 3 phase, Dyn11, 50Hz, AN,Transformer with off circuit tapchanger and losses as per CBIP.FRTU (Field remote terminal unit) for SCADA integrationMetering compartment and LT isolator of one 1600A 4P ACB Breaker

2.0 SITC of Compact substation (CSS)-3,3A,4,4A EACH 0 4 411kV, HT Panel with 1no. self powered VCB incomer.11/ 0.433kV, 500kVA, dry type, two winding, 3 phase, Dyn11, 50Hz, AN,Transformer with off circuit tapchanger and losses as per CBIP.FRTU (Field remote terminal unit) for SCADA integrationMetering compartment and LT isolator of one 1000A 4P ACB Breaker

viii Outdoor LT Panel-1 & 2 EACH 0 2 2Incoming2 No. 1600 amps 4P ACB (50KA) with in built earth fault protection Buscoupler1 No. 1600 amps 4P ACB (50KA) with in built earth fault protection Measuring instruments for each incomer0-500 volts digital electronic volt meter with selector switch protected by 2 ampsTP MCB's.0-1600 Amps digital electronic ammeter with selector switch with 3 nos. 1000/5A,10VA, CL-1.0 Current TransformerDigital Multi-function meter with RS 485 communication port of accuracy class-1

1 set of Phase indicating lights Breaker ON / OFF / TRIP indicating lights with control MCB’s.Bus Bars2nos. 1600 amps TPN aluminium bus bars (25 kA) with coloured heat shrinkableinsulation sleeve.Outgoing100 amp TPN MCCB 26Nos.16 amp TPN MCCB 1Nos.

ix Outdoor LT Panel for 500kVA CSS-3,3A EACH 0 1 1Incoming2 No. 1000 amps 4P ACB (50KA) with in built earth fault protection Buscoupler1 No. 1000 amps 4P ACB (50KA) with in built earth fault protection Measuring instruments for each incomer

11/0.433KV COMPACT SUBSTATIONS

METL 12 of 15

Page 14: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

0-500 volts digital electronic volt meter with selector switch protected by 2 ampsTP MCB's.0-1000 Amps digital electronic ammeter with selector switch with 3 nos. 1000/5A,10VA, CL-1.0 Current TransformerDigital Multi-function meter with RS 485 communication port of accuracy class-1

1 set of Phase indicating lights Breaker ON / OFF / TRIP indicating lights with control MCB’s.Bus Bars2nos. 1000 amps TPN aluminium bus bars (25 kA) with coloured heat shrinkableinsulation sleeve.Outgoing100 amp TPN MCCB 13Nos.16 amp TPN MCCB 1Nos.

x Outdoor LT Panel for 500kVA CSS-4,4A EACH 0 1 1Incoming2 No. 1000 amps 4P ACB (50KA) with in built earth fault protection Buscoupler1 No. 1000 amps 4P ACB (50KA) with in built earth fault protection Measuring instruments for each incomer0-500 volts digital electronic volt meter with selector switch protected by 2 ampsTP MCB's.0-1000 Amps digital electronic ammeter with selector switch with 3 nos. 1000/5A,10VA, CL-1.0 Current TransformerDigital Multi-function meter with RS 485 communication port of accuracy class-1

1 set of Phase indicating lights Breaker ON / OFF / TRIP indicating lights with control MCB’s.Bus Bars2nos. 1000 amps TPN aluminium bus bars (25 kA) with coloured heat shrinkableinsulation sleeve.Outgoing100 amp TPN MCCB 15Nos.32 amp TPN MCCB 9Nos.16 amp TPN MCCB 1Nos.

xi Suppy , installation, testing & commissioning of 100 kVA, 11/0.433KV, 3-ph ,50Hz, Class F insulation, impedance 4%, AN cooled , cast resin ,dry typetransformer, IP-23 for indoor, with OFF load tap changer for voltage variationfrom + 5% to - 5 % in steps of 2.5% each.

Nos. 2 0 2

xii RMU WITH TWO OUTGOING FEEDERS

METL 13 of 15

Page 15: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

1.0 Supply, testing & commissioning of GIS type outdoor RMU (Ring main unit).comprising 2 Nos. 33 KV , 630 A, 25 KA incoming Load break switches and 2nos. 630 A VCB 25 KA as outgoings and earth switch bus bars, interlocking andearth bar complete with snap action mechanism for manual & motorizedoperation, F.PI (Fault position Indication), bushing for 630A, arc proof cable covercomplete with interlocking FRTU (IEC 61850) for SCADA.

No. 0 3 3

2.0 Supply, testing & commissioning of GIS type outdoor RMU (Ring main unit).comprising 2 Nos. 11 KV , 630 A, 20 KA incoming Load break switches and 2nos. 630 A VCB 20 KA as outgoings and earth switch bus bars, interlocking andearth bar complete with snap action mechanism for manual & motorizedoperation, F.PI (Fault position Indication), bushing for 630A, arc proof cable covercomplete with interlocking FRTU (IEC 61850) for SCADA.

No. 0 12 12

3.0 Supply, testing & commissioning of GIS type outdoor RMU (Ring main unit).comprising 2 Nos. 11 KV , 630 A, 20 KA incoming Load break switches and 3nos. 630 A VCB 20 KA as outgoings and earth switch bus bars, interlocking andearth bar complete with snap action mechanism for manual & motorizedoperation, F.PI (Fault position Indication), bushing for 630A, arc proof cable covercomplete with interlocking FRTU (IEC 61850) for SCADA.

No. 0 3 3

I Battery and Battery Charger

- J SCADA SYSTEM

1.0 Design, manufacture, supply ,installing and testing for SCADA System of 33/11kVsubstation including 33&11KV RMU, Network switch etc complete in all respects.SCADA System will have redundant server (Main + Back up server).

Lot 1 1

K SAFETY AND FIRE PROTECTION EQUIPMENTS1.0 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild

steel,atleast 2mm thick,and vitreous enamelled white on both sides,and withinscription in single red colour on front side as required.

Each 2 2

2.0 Providing and fixing HT danger notice plate of 250 mm X 200 mm, made of mildsteel,atleast 2mm thick,and vitreous enamelled white on both sides,and withinscription in single red colour on front side as required.

Each 6 6

3.0 Supply and fixing wooden framed covered with glass shock treatment chartprinted on cloth in English ,Hindi & Local language.

Each 1 1

4.0 Supply and fixing suitable size wooden framed covered with glass for MainPanel SLD in electrical room as per IE rules fixed to wall as required.

Each 1 1

2Supplying, assembling, installation, commissioning of Ni-cd 110V D.C., 250 AHbatteries. The batteries shall rest on treated wooden planks fabricated from MSangle and free standing floor mounted rack with acid resistant finish andcomplete with series connecting electrical leads and charging of batteries. Thebatteries shall be accompanied with tester. This shall have incoming leads aswell as outgoing leads and of suitable battery charger for 8 hrs charge of 216AH

set 2 0

METL 14 of 15

Page 16: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

33/11 KV S/S Distribution Network

Total QtySL NO DESCRIPTION OF IEM UNIT QUANTITY UNIT RATE

( In Rs.)TOTAL AMOUNT

( IN Rs.)

5.0 Supply and providing ISI marked electrical 1.1 kV grade 3 mm thick anti-skidrubber mat, 2 x 1 mtr as per IS:15652-2006 with up to date ammendment.

Each 1 1

6.0 Supply, installation, testing and commissioning of Standard First aid boxcomplete with all accessories as required.

Each 1 1

7.0 Supply and fixing in position 1000 mm wide rubber matting of 33 KV grade as perelectricity rules. Thickness of rubber mat shall be as per latest IS Code.

RM 12 12

8.0 Co2 type duly refilled 4.5 Kg & ready to use Each 3 35kg DCP type Fire extinguisher Each 3 3

10.0 Providing & fixing 50kg trolley mounted foam type Fire Extinguishers for powertransformers.

Each 2 2

10.0 Providing & fixing 4 nos. fire buckets with stand. Each 2 29.0 Supply of 33kV pair of hand gloves Set 1 1

11.0 Providing & fixing of 'No Smoking' and 'No Unauthorized Entry' signboards inEnglish and Hindi, as per IPR- 1970.

Each 3 3

L MISCELLANEOUS ITEMS1.0 Providing, laying and fixing following dia G.I. pipe (medium class) in ground

complete with G.I. fittings including trenching (75 cm deep) and re-filling etc asrequired

a 100 mm dia metre 10 10

2.0 Providing, laying and fixing following dia RCC pipe NP3 class (medium duty) inground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2fine sand) including trenching (75 cm deep) and refilling etc as required.

a 100 mm dia metre 130 130

M UPS FOR EMERGENCY LIGHTS1.0 Supply and installation of 1kVA UPS for 30mins back up with single phase input

and 1 phase output.No. 1 1

N 11KV CAPACITOR BANKS1.0 Supply and installation of 4.8 MVAR 11 kV AUTOMATICALLY SWITCHED

CAPACITOR BANKS AT 33/11kV SUB-STATIONS.No. 2 2

TOTAL

METL 15 of 15

Page 17: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

1.0 EARTHWORK1.1 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not

exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, includinggetting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.0-1.5m depth cum 670

1.2 Clearing grass and removal of the rubbish up to a distance of 50 m outside the periphery of the area cleared Sq m 2,178

1.3 Filling available excavated earth (excluding rock) in trenches, plinth,sides of foundations etc. in layers not exceeding 20cm in depth,consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

cum 782

1.4 Filling in foundation with soling under raft slab including watering, ramming, consoilidation and dressingetc. complete. cum 59

2.0 CONCERTE AND ALLIED WORK2.1 PCC

Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work upto plinth level.1:2:4 (1 Cement : 2 coarse sand (zone-III) : 4 graded stoneaggregate 40 mm nominal size).

cum 70

2.2 Damp-Proof courseProviding and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand(zone-III) : 4 gradedstone aggregate 20mm nominal size).

Cum 64

2.3 Cast in SituProviding and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement contentas per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for allleads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concretework, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing andreinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting ofconcrete,improve workability without impairing strength and durability as per direction of the Engineer-in-charge.

cum 743

2.4 Formwork2.4.1 Foundations, footings, bases of columns, etc. for mass concrete sqm 394

2.4.2 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. sqm 538

2.4.3 Lintels, beams, plinth beams, girders, bressumers and cantilevers sqm 1,603

2.4.4 Columns, Pillars, Piers, Abutments, Posts and Struts sqm 420

3.0 Reinforcement

Abstract-2 Schedule of Quantities for Civil Works

METL 1 of 13

Page 18: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level.

MT 86

Thermo-Mechanically Treated bars of grade Fe-500 D or more.

4.0 GENERAL BUILDING WORK4.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up

to floor V level in all shapes and sizes in :Cement mortar 1:4 (1 cement : 4 coarse sand)230 thk cum 138 150 thk sqm 26

4.2 Cement Plaster with a floating coat of neat cement

a) External 20mm thick cement plaster in single coat (double coat where cladding is not provided) finished even, smooth andcurring including cost of complete work in CM 1:3

Sqm 411

b) Internal 12mm thick cement plaster in single coat finished even, smooth and curring including cost of complete work in CM1:3

Sqm 1,300

4.3 Flooringa Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption

less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cementand matching pigments etc., complete.Size of Tile 500x500 mm SqmAdmin Room & Conference Room 70 Automation Room 25 Panel Room Area 205 Store Room & Kitchen 27

b Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by themanufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved byEngineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand)and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shadecomplete

Sqm

SR Item No 11.37A of Dehli SR, Pg No 196 under Sub Head 11.0 Flooring for the Year of 2016-17 74

c Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resistingmortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction ofEngineer-in- Charge.In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)-Acid and alkali resistant tile Sqm 12 In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)-Acid and alkali resistant tile Sqm 56

Stone aggregate below 40 mm nominal size Cum 66

4.4 Paint

METL 2 of 13

Page 19: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specificationsincluding appropriate priming coat, preparation of surface, etc. complete.On concrete work sqm 1,711

5.0 Rolling ShutterSupplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through theirentire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guidesand arrangements for inside and outside locking with push and pull operation complete, including the cost of providing andfixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS:4454 - part 1 and M.S. top cover of required thickness for rolling shutters.

sqm 12

80x1.25 mm M.S. laths with 1.25 mm thick top cover

7.0 Miscellaneous7.1 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm

nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted withfine sand, including necessary excavation, levelling & dressing & finishing the top smooth.

sqm 104

7.2 Fencing with R.C.C. post placed at required distance, embedded in cement concrete blocks, every 15th post, last but one endpost and corner post shall be strutted on both sides and end post one side only, provided with horizontal lines and twodiagonals of barbed wire weighing 9.38 kg per 100 metres (minimum), between the two posts fitted and fixed with G.I. stapleson wooden plugs or G.I. binding wire tied to 6 mm bar nibs fixed while casting the post (cost of R.C.C. posts, struts, earth workand concrete to be paid for separately) :- Payment to be made per metre cost of total length of barbed wire used.

With G.I. barbed wire mt 53

7.3 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer using structural steel etc. as required.n stringers, treads, landings etc. of stair cases, including useof chequered plate wherever required, all complete

kg 7,941

8.00 Compound Wall allround the Site Boundary (Quote per running meter all the sub divisions are for reference only)

Rmtr 200

8.1 Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out theexcavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. Ordinary rock

Cum 300

8.2 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up

to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)Cum 39

8.3 Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement :

6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand)

Cum 50

8.4 Coursed rubble masonry (first sort) with hard stone in foundation and plinth with : Cement mortar 1:6 (1 cement : 6 coarse

sand)Cum 31

METL 3 of 13

Page 20: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

8.5 Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) : Flush/ Ruled pointing Sqm 34

8.6 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)

Cum 59

8.7 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering,

finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stoneaggregate 20 mm nominal size).

Cum 32

8.8 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses,

fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost ofcentering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stoneaggregate 20 mm nominal size).

Cum 10

8.9 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto

plinth level. 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more.Kg 1,934

8.10 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above

plinth level. Thermo-Mechanically Treated bars of grade Fe-500 D or more.Kg 617

8.11 Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of

columns, etc. for mass concreteSqm 361

8.12 Centering and shuttering including strutting, propping etc. and removal of form for all heights :Columns, Pillars, Piers,

Abutments, Posts and StrutsSqm 294

8.13 20 mm cement plaster of mix : 1:4 (1 cement: 4 fine sand) Sqm

8.14 Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm) Sqm 688

8.15 Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm) Sqm 688

8.16 Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one

end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines andtwo diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two postsfitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid forseparately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire

Rmtr 200

8.17 Supplying at site Angle iron post & strut of required size including bottom to be split and bent at right angle in opposite directionfor 10 cm length and drilling holes upto 10 mm dia. etc. complete.

kg 300

9.0 Road Estimate(Quote per running meter all the sub divisions are for reference only)

RMT 70

METL 4 of 13

Page 21: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

9.1 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at aheight of 1m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared.

Sqm 420

9.2 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an averageof 22.5cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rollingthe sub grade and disposal of surplus earth with lead upto 50 metres. compacting to meet requirement of table 300-1, 300-2and as per relevant clauses of section-300

Sqm 420

9.3 Construction of embankment/SubgradeFilling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm indepth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. as per table 300-1,300-2 and as per relevant clauses of section-300

Cum 256

9.4 Construction of granular sub-base by providing well graded material like natural sand crushed gravel or crushed stone havingCBR >30, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator orplant mix method at OMC, and compacting with vibratory rollers of 80 to 100 kN static weight to achieve the desired density,complete as per Clause 401 of Specification.

Cum 66

9.5 Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing theMaterial with water at OMC in mechanical mixplant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well preparedsurface and compacting with vibratory roller to achieve the desired density in accordance to Table No. 400-12, 400-13 and asper clause of section 406 of specifications.

Cum 54

9.6 "Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as perdesign mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved& specified design criteria, providing dowel bars with sleeve/ tie bars wherever required,laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision forcontraction/ expansion, construction & longitudinal joints ( 10 mm wide x 50 mm deep) by groove cutting machine, providingand filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers,sealants, dowel bars with sleeve/ tie bars to be paid separately). Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately.16.43.1 Cement concrete prepared with batch mixing machine

Cum 56

9.7 Road Marking with Hot Applied Thermoplastic Compound with Reflectorising Glass Beads on Bituminous Surface Providingand laying of hot applied thermoplastic compound 2.5 mm thick including reflectorising glass beads @ 250 gms per sqm area,thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform andfree from streaks and holes all complete as per clause 803 of specifications.

Sqm 562

9.8 Cast in Situ Cement Concrete M 20 Kerb with Channel Construction of cement concrete kerb with channel with top and bottomwidth 115 and 165 mm respectively, 250 mm high in M 20 grade PCC on M10 grade foundation 150 mm thick, kerb channel300 mm wide, 50 mm thick in PCC M20 grade, sloped towards the kerb, kerb stone with channel laid with kerb laying machine,foundation concrete laid manually, all complete as per clause 409B-Using Concrete Batching and Mixing Plant

RMT 70

9.9 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two ormore coats on new work over an under coat ofsuitable shade with ordinary paint of approved brand and manufacture

Sqm 22

METL 5 of 13

Page 22: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

10.0 Plumbing Cost(Quote as Lumsum, all the sub Heads are for reference only)SUB HEAD-I SANITARY WARE INSTALLATION :

a Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre lowlevel white P.V.C.flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231,with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :

W.C. pan with ISI marked white solid plastic seat and lid. each 2

b Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern,including painting of fittings and brackets, cutting and making good the walls wherever require :

White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps each 1 c Providing and fixing Below counter white colour vitrous china wash basin with C.P. chrome, pair of pillar taps, mixer without

pop-up waste .Make: Hindware, Model:Monalisa-ZEN(56x45), CAT No. 10049, pillar cock-Model: Essence cat no.130001,Waste coupling full thread model no.F850002.including painting of fittings, cutting and making good the counter/wall whereverrequired ,all complete:

each 1

d Providing and fixing PTMT Bottle Trap for Wash basin and sink.

d.1 Bottle trap 31mm single piece moulded with height of 270 mm,effective length of tail pipe 260 mm from the centre of the wastecoupling, 77 mm breadth with 25 mm minimum water seal,weighing not less than 260 gms.

each 2

d.2 Bottle trap 38mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the wastecoupling, 77 mm breadth with 25 mm minimum water seal,weighing not less than 263 gms.

each 1

e Providing and fixing white vitreous china battery based infra red sensor operated urinal of approx 610 x 390x 370mm having

pre and post flushing with water (250ml &500ml consumption), having water inlet from back side including fixing to wall withsuitable brackets all as per manufacturers specification and direction of engineer in charge.

each 2

f Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40

mm including painting of fittings and brackets, cutting and making good the walls wherever required :

f.1 Kitchen sink with drain board f.2 510x1040 mm bowl depth 250 mm each 1 g Providing and fixing CP brass long body Bib cock of approved quality confirming to I.S. Standards and weighing not less than

690 gms.

15 mm nominal bore each 1

h Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15 mm nominal bore each 6

i Providing and fixing toilet paper holder.

METL 6 of 13

Page 23: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

C.P Brass each 2

j Providing and fixing health faucet (ABS body) with 8mm dia. With 1m flxible tube and wall hook etc. complete in all respects asper manufacturers specifications and direction of Engineer-in-Charge. (Make : Jaquar, Model :ALD-IVC-593)

each 2

k Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape

with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gmseach 1

l Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :

15 mm nominal bore each 2

SUB HEAD II DRAINAGE INSTALLATION a Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete,

including cost of cutting and making good the walls and floors :

100 mm inlet and 100 mm outlet Sand cast iron S&S as per IS: 3989 each 4

b Providing and fixing PTMT grating of approved quality and colour.

Rectangular type with openable circular lid 150 mm nominal size square 100 mm diameter of the inner hinged round grating each 6

c Providng & fixing 100 x 50 G.I. elbow for floor drain in toilets to be connected to floor trap with bitumastic paint etc. over a coat

of primer (of approved quality)each 6

d Providing and fixing soil, waste and vent pipes :

100 mm dia Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989 meter 15 75mm diameter : Centrifugally cast (spun) iron socketed pipe as per IS: 3989 meter 12

e Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and

including cement concrete blocks 10x10x10cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mmnominal size) including cost of cutting holes and making good the walls etc. :

For 100mm dia. Pipe each 2 For 75mm dia. Pipe each 2

f Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.

100 mm dia Sand cast iron S&S as per IS - 3989 each 4

g Providing and fixing plain bend of required degree

METL 7 of 13

Page 24: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

100 mm dia Sand cast iron S&S as per IS : 3989 each 6 75 mm diameter Sand cast iron S&S as per IS : 3989 each 4

h Providing and fixing heel rest sanitary bend

100 mm dia Sand cast iron S&S as per IS : 3989 each 3 75 mm diameter Sand cast iron S&S as per IS : 3989 each 2

i Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts

and nuts complete.

100x100x100 mm Sand cast iron S&S as per IS : 3989 each 4 75x75x75 mm Sand cast iron S&S as per IS : 3989 each 2

j Providing and fixing single equal plain junction of required degree :

100x100x100 mm Sand cast iron S&S as per IS : 3989 each 2 75x75x75 mm Sand cast iron S&S as per IS - 3989 each 2

k Providing and fixing door piece, insertion rubber washer 3mm thick, bolts & nuts complete :

100 mm Sand cast iron S&S as per IS : 3989 each 4 75 mm Sand cast iron S&S as per IS : 3989 each 2

l Providing and fixing terminal guard :

100 mm Sand cast iron S&S as per IS : 3989 each 3 75 mm Sand cast iron S&S as per IS : 3989 each 2

m Providing and fixing collar :

100 mm Sand cast iron S&S as per IS : 3989 each 2 75 mm Sand cast iron S&S as per IS : 3989 each 2

n Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter:

100 mm diameter pipe each 12 75 mm diametre pipe each 6

METL 8 of 13

Page 25: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

o Providing and fixing M.S. stays and clamps for sand cast iron/ centrifugally cast (spun) iron pipes of diameter :

100 mm diameter pipe each 6 75 mm diametre pipe each 4

p Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent pipes and fittings with two coats of synthetic enamel paint

of any colour such as chocolate grey, or buff etc. over a coat of primer (of approved quality) for new work :

100 mm diameter pipe metre 15 75 mm diameter pipe metre 12

q Providing and fixing G.I. Inlet connection fitting of suitable size with 2 & 3 Nos. G.I. Socket 32 & 40 welded to G.I. pipe and

dipped in hot bitumen complete in all respect.

100 mm diameter pipe (Hopper) each 6

r Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/ccutting and making good the walls etc.

Internal work - Exposed on wall 40 mm nominal bore meter 10 50 mm nominal bore meter 25

SUB HEAD-III WATER SUPPLY INSTALLATION

a Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply includingall CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes &fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of jointscomplete as per direction of Engineer in Charge

Concealed work, including cutting chases and making good the walls etc. 15 mm nominal outer dia .Pipes meter 15 20 mm nominal outer dia .Pipes meter 8

b Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including

all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.

Internal work - Exposed on wall 25 mm nominal outer dia .Pipes meter 10 32 mm nominal outer dia .Pipes meter 5

c Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply includingall CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching,refilling & testing of joints complete as per direction of Engineer in Charge.

External Work 40 mm nominal outer dia Pipes meter 56

METL 9 of 13

Page 26: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

d Provide and fixing of motorised control float valve made of cast iron body, consisting motorised butterlfy / ball valve, heavy

duty float,mechanism for roating floats, electrical control, float with control and accessories complte as per manufacturersstandard.

40 mm dia nominal bore. set 1

f Providing and fixing brass stop cock of approved quality : 15 mm nominal bore each 2 20 mm nominal bore each 4

g Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :

32 mm nominal bore each 1

h Providing & fixing brass mesh in elbow with necessary G.I. Vent pipe with fittings. 100 mm dia Each 2

i Providing & fixing mosquito proof brass overflow grating for tanks.

100 mm dia Each 2

j Providing & fixing of 1000 Liter three layered Plastic water tanks. Each 1

k Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stopcock, with C. I.surface box 100x100 x75 mm (inside) with hinged cover fixed in cement surface box 100x100 x75 mm (inside)with hinged cover fixed in cement surface box 100x100 x75 mm (inside) with hinged cover fixed in cement surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 gradedstone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1cement : 3 coarse sand) 12mm thick,finished with a floating coat of neat cement complete as per standard design :

With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 Each 1

Providing & Fixing of washing hydrant outlet consisting 1 No. 20mm dia. Ball valve & Brass Nozzle for connecting rubber hoseincluding pipes, fittings and accesssories complete.

Each 1

SUB HEAD IV EXTERNAL DRAINAGE INSTALLATION

a Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in

the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete

150 mm dia. R.C.C. pipe metre 75

b Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design:

150 mm diameter metre 75

METL 10 of 13

Page 27: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

c Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tightC.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than2.70 kg as per standard design :

100x100 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 each 2

d Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1

cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarsesand : 8 graded stone aggregate 40mm nominal size), inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarsesand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standarddesign :

Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weightof cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :

With common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5

each 4

e Excavating trenches of required width for pipes, cables, etc. including excavation for sockets and dressing of sides, ramming of

bottoms,, depth upto 1.5m including getting out the excavated soil and then returning the soil as required in layers notexceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplusexcavated soil as directed, within a lead of 50m.for excavation in all kind of soil.

All kinds of soil Pipes, cables etc, not exceeding 80 mm dia. metre - For pipes cables etc exceeding 80mm dia but not exceeding 300 mm dia. metre 75

f Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steel bar

conforming to IS: 1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequeringbesides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to withstand the bend test and chemical resistance test as per specification and having manufacture's permanent identification markto be visible even after fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 ( 1 cement : 3 coarsesand :6 graded stone aggregate 20 mm nominal size) complete as per design.

each 10

g Constructing brick masonry circular type manhole 0.91m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1

cement: 4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with afloating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mmnominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S.12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12mmthick cement plaster at the external surface shall be paid for separately) :

METL 11 of 13

Page 28: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

With Sewer bricks conforming to IS : 4885 Each 1

SUB HEAD V EXTERNAL STORM WATER DRAINAGE INSTALLATIONCollection Chambers

a Excavation for strom water collection Chamber : Excavation work by mechanical means (Hydraulic excavator)/ manual meansin foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming ofbottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within alead of 50 m.

a) In all sort of soils and soft murrum Upto 1.5 m Cum 3

b Providing and laying in position plain cement concrete of specified grade(M-15) excluding the cost of centering and shuttering -All work up to plinth level 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)

Cum 1

c Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforcedcement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying butexcluding the cost of centering, shuttering, finishing and reinforcement,including admixtures inrecommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairingstrength and durability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately).1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate 20 mm nominal size)

Cum 1

d Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete uptoplinth level.Thermo Mechanically Treated bars of grade Fe-500D or more.

Quintal 1

e Centering and shuttering including strutting, propping etc. and removalof form for all heights:Walls (any thickness) including attached pilasters, butteresses,plinth and string courses etc.

Sqm 14

f Precast perforated slab of 600mm X 400mm X 50mm No. 8 Strom Water Drain

g Excavation for strom water collection drain: Excavation work by mechanical means (Hydraulic excavator)/ manual means infoundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming ofbottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within alead of 50 m.

a) In all sort of soils and soft murrum Cum 59 Upto 1.5 m

h Providing and laying in position plain cement concrete of specified grade(M-15) excluding the cost of centering and shuttering -All work up to plinth level :1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)

Cum 9

i Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforcedcement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying butexcluding the cost of centering, shuttering, finishing and reinforcement, including admixtures inrecommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairingstrength and durability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately).1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate 20 mm nominal size)

Cum 18

j Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete uptoplinth level.Thermo Mechanically Treated bars of grade Fe-500D or more.

Quintal 17

k Centering and shuttering including strutting, propping etc. and removalof form for all heights:Walls (any thickness) including attached pilasters, butteresses,plinth and string courses etc.

Sqm 358

l Precast perforated slab of 600mm X 400mm X 50mm No. 315 Pipe Laying

METL 12 of 13

Page 29: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO

DESCRIPTION OF ITEM UNIT QTY UNIT RATE

( In Rs.)

TOTAL AMOUNT ( In Rs.)

m Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming ofbottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers notexceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering,etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :

Cum 3

n Providing and laying in position plain cement concrete of specified grade(M-15) excluding the cost of centering and shuttering -All work up to plinth level :1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)

Cum 1

o Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar inthe proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete: 100 mm dia. R.C.C. pipe

Rmt 40

p Pipe Encasing :Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concretefor reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to siteof laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommendedproportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength anddurability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330 kg/cum.“Excess/ lesscement used as per design mix is payable/recoverable separately). 1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate20 mm nominal size)

Cum 1

q Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete uptoplinth level.Thermo Mechanically Treated bars of grade Fe-500D or more.

Quintal 1

r Centering and shuttering including strutting, propping etc. and removal of form for all heights:Walls (any thickness) includingattached pilasters, butteresses,plinth and string courses etc.

Sqm 6

Above mentioned S.no 8 ,9 &10 are inclusive of all items for the smooth Operational after construction of those systems andshould be approved by Client. Item mention in discription are only major items

Total

METL 13 of 13

Page 30: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO DESCRIPTION OF ITEM UNIT QTY UNIT RATE ( In Rs.)

TOTAL AMOUNT ( In Rs.)

A Ventilation System1.0 Tube Axial Fans

Supply, installing, testing and commissioning of Tube Axial fan complete with tube casing, impeller , bird screen, necessary nut bolts,necessary transition piece and canvas connection for proper Installing, silencers on inlet and outlet and directly coupled TEFC Sq.cage,EFF-1 High efficiency induction motor mounted on vibration isolators suitable for 415V±10%, 50 Hz. 3 phase electric supply andcomplete as per technical specification.

The speed of the motor shall be less than 1450 RPM and the impellar speed shall be less than 1000 RPM and capacities based onminimum 1.0 inch (25mm WC) static pressure or to suit the system, shall be as follows:

For Pump Room Exhaust1.1 14,000 cmh @ 25 mm of wg total static for Exhaust Air Nos. 21.2 14,000 cmh @ 15 mm of wg total static for Fresh Air Supply Nos. 22.0 Rectangular GSS Sheet Metal Duct

Supply, fabrication, Installing, testing and commissioning of Rectangular GSS Ducting in complete with all fittings such as tee, bends,special off chutes, turning vanes, spilitter, dampers inspection doors,transformation pieces etc. as required and as per IS Standardsincluding suspension and supporting arrangement plenum, duct as per technical conforming to specifications and as required with theapproved shop drawings .

2.1 24 Gauge GSS Ducting (0.63 mm thk) Sqm. 402.2 22 Gauge GSS Ducting (0.8 mm thk) Sqm. 203.0 Exhaust Air Grilles

Supply, Installing, testing and balancing of powder coated extruded aluminum Grills of non-flammable material frames etc asspecification The grilles shall be complete with flanges as required In accordance with the approved shop drawings

3.1 Air grilles with extruded aluminium VCD Sqm. 1.8

4.0 Volume Control Duct DampersSupply, Installing, testing and commissioning of opposed blade box type 18 G GSS construction damper for ducts, to be provided withsuitable links and quadrants for control of volume of air. and complete as per technical specificaton.

Sqm. 0.8

5.0 LOUVERS Supply, Installing, testing and comissioning of Powder coated extruded aluminium construction fresh air louvers with min. 60 % freearea, bird screen and 20 mircon Filter efficiency down to 90 % as per as per specifications. Louvers need to be suitable in order avoidrain water entry in to basement @ 15 degree deflection

Sqm. 2.6

6.0 Propeller FansProviding, fixing, testing and commissioning of propeller type fan for exhaust/fresh air complete with gravity louvers and cabling uptopower point complete as per specifications and drawings.

6.1 500 cfm No 26.2 300 cfm No 37.0 Back Draft Dampers

Supplying, fixing , testing & commissioning of Back Draft damper having 18 gauge G.I. frame and 20 gauge louvers at exhaust air fans. Sq.mt. 1

B Air Conditioning SystemHi Wall Split Unit

1.0 Supply, installation, testing and commissoning of high wall mounted split unit airconditioners with evaporator with fan with motor,cooling coil, filter, all enclosed in decorative plastic casing, condenser with hermatically sealed rotary compressor, condenser coil,propeller fan with motor, inter connecting refrigerant piping, wiring, earthing, cordless remote control, M.S. frame for mountingcondensing unit.

1.1 1.5 Tons No 21.2 2 Tons No 3

Total

Abstract-3 Schedule of Quantities for HVAC & Ventilation System

METL 1 of 1

Page 31: SUMMARY OF PRICE SCHEDULE - CONSTRUCTION OF 33/11 …cable of 1.1 KV grade of following size on cable tray as required. a Upto 35 sq. mm (clamped with 1mm thick saddle) Mtrs. 425 6193

SL NO DESCRIPTION OF ITEM UNIT QTY UNIT RATE ( In Rs.)

TOTAL AMOUNT ( In Rs.)

FIRE Detection And ALARM SYSTEMSupply, Installation,Testing & Commissioning of following equipment for FDAS as per technical specification.

A FACP,detectors and modules1 Microprocessor based Analog Addressable Fire Alarm with audio message generator (pre-recorded), 1 loop per panel having 99

detectors and 99 devices per loop. Panel shall have 80/160 character LCD to display emergency information. SMF Battery withbackup for 48 Hrs under normal condition and 120 Min under alarm condition. Panel shall have required interface to transmitdata to Graphical User Software. Panel shall be UL & CE approved. Panel shall be LAN Compatible with Bacnet/Modbussoftware or open protocol, network adaptor,etc., complete in all respects as per Technical Specification and Tender drawings.

1.1 1 Loop Panel of above specification Nos. 12 Analog addressable Photoelectric smoke detector with electronic mounting base,junction box and other accessories as per

specifications.Detectors shall be UL Listed.Nos. 12

3 Analog addressable rate of rise and fixed temperature heat detectors with electronic mounting base, junction box and otheraccessories as per specifications.Detectors shall be UL Listed.

Nos. 2

4 Addressable type manual call point(break glass unit) as per specifications. Nos. 35 Addressable Sounder cum Strobe rated at 90 dBA at 3m for Audible annunciation and 110cd flashing at 1 Hz for visual indication

with control modules for Sounders as per specification Nos. 3

6 Addressable Monitor Module to connect NO/NC contacts such as hydrogen gas detector as per specification. Nos. 17 Auto Dialer unit as per specifications with minimum 6 emergency nos dialing capcity Nos. 18 Conventional 2.5%-10% LEL commercial Hydrogen gas detector, Output: PFC relay / Rs-485 optional, Dustproof & Water

Splash proof – IP65 Enclosure including necessary mounting accessories.Nos. 1

B FAS CABLES & ACCESSORIESSupply & Laying of following cables/conduits as per technical specification.

1 2 core 1.5 sq.mm, multi strand, copper conductor, FRLS (Fire Retardent Low Smoke)-PVC insulated GI Screened Armouredcable with saddle and required accessories.

Mtr 130

2 20mm Dia heavy duty PVC FRST Conduits conealed in ceiling,wall,floor etc., mtr 20TOTAL - FDAS ITEMS

Abstract-4 Schedule of Quantities for Fire Detection and Alram System

METL 1 of 1