stronger than steel · 2017-10-30 · astm e-814 standard method of fire tests of fire stop systems...
TRANSCRIPT
BlazeFrame®
I N T E G R AT E D F I R E S T O P S Y S T E M S
S T R O N G E R
T H A N S T E E LSM
.
clarkdietrich.com/BlazeFrame
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
What is BlazeFrame? BlazeFrame products are innovative steel framing proile/intumescent composites, that combine ease of installation, inspection, life safety and joint protection dependability into one unique product.
How does it work? Using a cured factory metered dosage intumescent material, BlazeFrame proiles provide ire stopping, smoke and sound dampening that is efective immediately after framing components are installed. When exposed to heat above 375° F, the intumescent material expands up to 35 times its size. This provides additional protection from heat and lame passage during a ire event.
What does it replace? BlazeFrame's factory metered dosage intumescent material eliminates elastomeric ire prooing caulks and spray. The cured intumescent tape eliminates VOC's and of gases associated with caulked spray ire prooing. With the intumescent tape factory applied it eliminates both overage and underage often associated with the messy caulks and sprays.
BlazeFrame Advantages:
• Installed & inspected as " joint framing" (before obstructions)
• Unafected by dirty, oily, wet or freezing conditions
• Cured intumescent efective immediately (no VOC)
• No fatigue to joint or substrate materials for life of assembly
BlazeFrame Design Advantages
One to three hour assembly
BLAZEFRAME FIRE STOP
DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERS
FOR 1, 2, 3 HR RATING
5/8” TYPE X
GYPSUM WALLBOARD
CONCRETE DECK
2
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
Fire Stopping
• UL 2079 Classiied and listed for up to 3 hr assemblies
• Protection for up to 3" overall movement capability (1-1/2" up and 1-1/2" down)
• Eliminates ire prooing caulks and sprays
• Shaftwall Assemblies certiied for use with all UL listed "liner" boards and inish side gypsum products
Sound Dampening
• NVLAP certiied to provide up to STC 62 (based on wall assembly)
• Open unencumbered joints (no caulk required)
• Fluted deck exposed with only BlazeFrame Deck Plug or Flute Cover STC = 50+
Smoke barrier-air leakage - IBC 2009 BlazeFrame assemblies have been UL Classiied
with the lowest possible L-Rating (less than 1 CFM/lft).
Seismic Requirements BlazeFrame is UL 2079 Classiied for Class III Cycling of 500 cycles at 30 cycles per minute of vertical movement which may be capable of meeting seismic design and building code requirements.
Code Compliance BlazeFrame joint protection complies with up to date building codes and is listed by Underwriters Laboratories Inc.
UL 2079 Tests for Fire Resistance of Building Joint SystemsASTM E-1966 Standard Test Method for Fire Resistive Joint SystemsASTM E-814 Standard Method of Fire Tests of Fire Stop SystemsULC S115-M95 Standard Method of Fire Tests of Fire Stop SystemsASTM E-119 Evaluation of a Non-Load Bearing Wall Assembly with FAS-093X Control JointASTM E-2837 Rated Wall Assemblies Installed to Non-Rated Assemblies (pending)
Expanded intumescent strip after ire test
BlazeFrame delection track & deck plugs in sound test
3
C O N C R E T E D E C K C O N D I T I O N
M E T A L D E C K C O N D I T I O N
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
• Head of Wall assembly complete before studs are installed.
• Mineral wool only needed for lute ill.
• Earlier, easier, and accurate inspection.
• Clean transition from wall sheathing to substrate.
• Exposed and inished joints are ire and sound rated.
BLAZEFRAME FIRE STOP
DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERS
FOR 1, 2, 3 HR RATING
5/8” TYPE X
GYPSUM WALLBOARD
CONCRETE DECK
MINERAL WOOL
FLUTE FILL
BLAZEFRAME FIRE
STOP DEEP LEG
DEFLECTION TRACK
(DL2, DSL2)
1, 2, 3, LAYERS
FOR 1, 2, 3, HR
RATING
ATTACH GYPSUM PER UL
DESIGN REQUIREMENT
STEEL STUD
BlazeFrame Design Advantages
4
B E A M P E N E T R A T I O N C O N D I T I O N
P A R A L L E L O F F S E T C O N D I T I O N
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
• Eliminates contour cutting of wall sheathing, caulks/sprays.
• Spray ire prooing or mineral wool are the easy option for beam cavity ill.
METAL PAN DECK
BLAZEFRAME FIRE STOP
DEEP LEG DEFLECTION
TRACK (DL2)
STEEL STUD
ANGLE OR Z-CLIPCENTERED
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOFINGor MINERAL WOOL
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME OFFSET DEEP
LEG DEFLECTION TRACK (ODL2, ODSL2)
14GA STRAP / ANGLEOUTRIGGER
STEEL STUD
• Eliminates z-clips, lath basket, voids in ire prooing.
• 14 ga angle outrigger/proile preassembled prior to installation.
5
BlazeFrame Sample Profiles
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
* 4" leg length is not available for 2-1/2" wide system
DSL 2 (DEEP LEG - SLOT TED BOTH SIDES)
SL 1 (DEEP LEG - SLOT TED ONE SIDE)
Proile with two slotted legs w/ ire stop on both sides
Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Legs with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.
Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) DSLE 30mils
Proile Leg Length (L)
Tape Width (I)
Slot Height (S)
Joint Protection
DSLE 2 2.50" 0.75" 1.50" 0.50"
DSL 2 3.00" 1.00" 1.50" 0.75"
DSLW 2 3.00" 1.25" 1.50" 1.00"
DSLX 2 4.00" * 1.75" 2.00" 1.50"
Proile with one slotted leg and one solid leg w/ ire stop on slotted side
Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. One leg with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.
Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga)
Proile Slotted Leg Length (L1)
Solid Leg Length (L2)
Tape Width (I)
Slot Height (S)
Joint Protection
SL 1 3.00" 2.00" 1.00" 1.50" 0.75"
SLW 1 3.00" 2.00" 1.25" 1.50" 1.00"
SLX 1 4.00" * 2.50" 1.75" 2.00" 1.50"
(L)
Width
(L)
(S)
(I)
(L)
.22”1.00”
Fastener mid-height of exposed slot
(L2)
Width
(L1)(I)
(I)
* 4" leg length is not available for 2-1/2” wide system
6
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
(DL 1 Series)
(DL 2 Series)
* 4" leg length is not available for 2-1/2" wide system
* Additional sizes available.
DL (DEEP LEG - SOLID)
JR (J-RUNNER)
Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 3" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two solid legs supporting "free loating" studs per listed assemblies in UL Fire Resistance Directory.
Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) DLE 30mils
(DL 1 Series) Proile with two solid legs w/ ire stop on one side (DL 2 Series) Proile with two solid legs w/ ire stop on both sides
Proile Leg Length (L)
Tape Width (I)
Joint Protection
DLE 2.00" 0.75" 0.50"
DL 2.00" 1.00" 0.75"
DLW 2.00" 1.25" 1.00"
DLX 2.50" 1.75" 1.50"
DLZ 3.00" 2.25" 2.00"
DLY 4.00" * 3.25" 3.00"
Proile with two solid legs w/ ire stop on one side
Composite Fire Stop/Framing for use in up to 3 hr ire rated shaft wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. One leg (front) having intumescent per listed assemblies in UL Fire Resistance Directory.
Widths: 2-1/2", 4" and 6" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga)
Proile Front Leg Length (FL)
Back Leg Length (BL)
Tape Width (I)
Joint Protection
JR 1 2.00" 3.00" 1.00" 0.75"
JRW 1 2.00" 3.00" 1.25" 1.00"
JRX 1 2.00" 3.00" 1.75" 1.50"
(L) (L)
(I)(I)
(BL)(FL)
(I)
Width
Width
7
BlazeFrame Sample Profiles
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
ODL 2 (OFFSET DEEP LEG)
ODSL 2 (OFFSET DEEP SLOT TED LEG)
Proile with two solid legs w/ ire stop on both sides
Composite Fire Stop/Framing with "ofset step" accommodates various depths of ireprooing in head of wall and wall to wall (column) assemblies. (Other ofset depths available to accommodate other sprayed thicknesses). Provides 100% unencumbered joint protection. Accommodates up to 2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two solid legs per listed assemblies in UL Fire Resistance Directory.
Widths: 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) "D" Dimension: Varies with depth of ire stop material required.
Proile Lower Leg Length (L)
Tape Width (I)
Joint Protection
ODL 2 2.00" 1.00" 0.75"
ODLW 2 2.00" 1.25" 1.00"
ODLX 2 2.50" 1.75" 1.50"
ODLZ 2 3.00" 2.25" 2.00"
Proile with two slotted lower legs w/ ire stop on both sides
Composite Fire Stop/Framing with "ofset step" accommodates various depths of ireprooing in head of wall and wall to wall (column) assemblies. (Other ofset depths available to accommodate other sprayed thicknesses). Provides 100% unencumbered joint protection. Accommodates up to 1-1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two legs with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.
Widths: 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) "D" Dimension: Varies with depth of ire stop material required.
Proile Lower Leg Length (L)
Tape Width (I)
Slot Height (S)
Joint Protection
ODSL 2 3.00" 1.00" 1.50" 0.75"
ODSLW 2 3.00" 1.25" 1.50" 1.00"
ODSLX 2 4.00" 1.75" 2.00" 1.50"
Width
(L)
0.75”0.75”
D
Width
(L)
0.75” 0.75”
D
(I)
(I)
8
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
FAS-093X FIRE RATED CONTROL JOINT
Proile for protection of control joints A composite control joint with intumescent tape factory applied to the back side of the control joint. The FAS-093X has been tested according to UL-2079 “Test For Fire Resistance of Building Joint Systems” and is used to relieve stresses of expansion and contraction of drywall interior partitions or ceilings running in a horizontal or vertical direction. The opening is protected by an orange plastic tape to indicate the ire rating this tape is removed after joint compound has been applied and the inish is completed. The section is fabricated from hot-dipped galvanized steel complying with ASTM A653, and ASTM A1003. Width: 2" Length: 10'-0" Thicknesses: 13mils Packaging: 20 Pcs./Ctn. - 24 Ctn. per pallet
FC (FLUTE COVER)
Proile strap for under luted decks Corrugated strap for horizontal use to span luted areas of unprotected or protected metal decks in up to 2 hr rated assemblies. Proile attached to deck "valley" surfaces a max 16" o.c. on both sides. Proiles provide a surface area for attachment of head of wall partition track proiles centered or ofset underneath and parallel to deck luted areas per listed assemblies in UL Fire Resistance Directory.
Sizes: 675 (6-3/4") or 700 (7") Length: 10'-0" Thicknesses: 33mils (20ga)
1.50” 1.50”0.875” 0.875”
Width varies to match
lute opening0.5
63”
BLAZEFRAME COMPOSITE(DL2, DSL2)
(FC) FLUTE COVER(continuous)
5/8” TYPE XGYPSUM WALLBOARD STEEL STUD
FLUTED DECK
9
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL1, SL1)
5/8” TYPE XGYPSUM WALLBOARD
CONCRETE DECK
STEEL STUD
BLAZEFRAME FIRE STOP
DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERS
FOR 1, 2, 3 HR RATING
5/8” TYPE X
GYPSUM WALLBOARD
CONCRETE DECK
Post Tension or Structural Concrete Overhead
PT-1
HW-D-0498
Chase Wall Post Tension or Structural Flat Concrete
PT-2
HW-D-0505
METAL PAN DECK
BLAZEFRAME FIRE STOP
DEEP LEG DEFLECTION
TRACK (DL2)
STEEL STUD
ANGLE OR Z-CLIPCENTERED
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOFINGor MINERAL WOOL
MINERAL WOOL
FLUTE FILL
BLAZEFRAME FIRE
STOP DEEP LEG
DEFLECTION TRACK
(DL2, DSL2)
1, 2, 3, LAYERS
FOR 1, 2, 3, HR
RATING
ATTACH GYPSUM PER UL
DESIGN REQUIREMENT
STEEL STUD
Perpendicular Unprotected Deck (UD) – Mineral Wool Fill
UD-1
HW-D-0513
Head of Wall Beam Penetration
SS-1
HW-D-0495
BlazeFrame Sample Details
10
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
BLAZEFRAME COMPOSITE(DL2, DSL2)
(FC) FLUTE COVER(continuous)
5/8” TYPE XGYPSUM WALLBOARD STEEL STUD
FLUTED DECK
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL2, DSL2)
FIRE PROOFING
5/8” TYPE XGYPSUM WALLBOARD
MINERAL WOOL
STEEL STUD
Centered Under Flute Unprotected Deck (UD) – Flute Cover
UD-6
HW-D-0544
Perpendicular Protected Deck (PD) – Mineral Wool Flute Fill
PD-12
HW-D-0513
Parallel Under Structural Support (Z-Clips)
SS-16
HW-D-0502
Wall to Wall Gypsum to Protected Steel (I-Beam)
VM-3
Design Based on
WW-S-0055
HW-D-0558
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL2, DSL2)
5/8” TYPE XGYPSUM WALLBOARD
Z-CLIPS
STEEL STUD
STEEL COLUMN
BLAZEFRAME “OL” PROFILE(ODL2)
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOF COATING
11
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
CONCRETE COLUMN / WALL
5/8” TYPE XGYPSUM WALLBOARD
STEEL STUD
BLAZEFRAME COMPOSITE TRACK / FIRESTOP
(DL2)
Wall to Wall Gypsum to Concrete Column/Wall
VM-1
WW-S-0055
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME COMPOSITETRACK / FIRE STOP
“OL” - SERIES(ODL2, ODSL2)
STEEL STUD 5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME OFFSET DEEP
LEG DEFLECTION TRACK (ODL2, ODSL2)
14GA STRAP / ANGLEOUTRIGGER
STEEL STUD
5/8” TYPE X
GYPSUM WALLBOARD
093 CONTROL JOINT
(optional)
SHAFT LINER BOARD
BLAZEFRAME COMPOSITE
TRACK / FIRE STOP
(JR1)
CH, CT, OR I STUD
Parallel Under Structural Support (Ofset Leg Proile)
SS-2
HW-D-0502
Edge of Structural Support with Angle (Ofset Leg Proile)
SS-28
HW-D-0631
Hollow Steel Shape - Non RatedSS-21
Design Based on
HW-D-0543
HW-D-0559
BlazeFrame Sample Details
12
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
Under UL G500 Series DesignVM-6
HW-D-0503
BLAZEFRAME COMPOSITE
TRACK / FIRE STOP
(DL2, DSL2)
5/8” TYPE X
GYPSUM WALLBOARD
FURRING CHANNEL
STEEL STUD
5/8” TYPE X
GYPSUM WALLBOARD
Bottom of WallVM-12
BW-S-0021
5/8” TYPE X
GYPSUM WALLBOARD
BLAZEFRAME COMPOSITE
TRACK / FIRE STOP
(DL2) CONCRETE FLOOR
STEEL STUD
Flat Strap PatchVertical Cavity Obstructions
ECA - End Cap AngleExterior Corner Application
FIELD MODIFIED - VERTICAL OBSTRUCTION
TOP VIEW SIDE VIEW
FASTEN FSP TO OUTERSURFACE OF TRACK LEG
FSP (Flatstrap Patch)
TOP VIEW TOP VIEWINSERT ECA
SIDE VIEW INSERT ECA
ECA ATTACHED WITH FASTENER
INTERSECTING WALL BLAZEFRAME “BUTTED”
13
The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com
CONCRETE DECK
BLAZEFRAME COMPOSITE
TRACK / FIRE STOP
(JR1)
3 LAYERS FOR
3 HOUR RATING
CH, CT, OR I STUD
LINER BOARD
MINERAL WOOL
5/8” TYPE X
GYPSUM WALLBOARD
BLAZEFRAMECOMPOSITE
TRACK / FIRE STOP(JR1)
FASTENER AT BOTTOMOF OBSTRUCTION
(when exists)CT, CH, OR I STUD
LINER BOARD
MINERAL WOOL
MINERAL WOOL orFIRE PROOFING
5/8” TYPE XGYPSUM WALLBOARD
5/8” TYPE X
GYPSUM WALLBOARD
FAS-093X
CONTROL JOINT
STEEL STUDS
5/8” TYPE X
GYPSUM WALLBOARD
FAS-093X
CONTROL JOINT
STEEL STUDS
Shaft Wall Post Tension or Structural Concrete
PT-3
HW-D-0496
FAS-093X Control Joint one layer each side (1-hour)
UL-2079
Shaft Wall Perpendicular to Unprotected Deck
UD-10
HW-D-0504
FAS-093X Control Joint two layers each side (2-hour)
UL-2079
BlazeFrame Sample Details
14
The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com
UL Approvals
UL Control - R25833 (US)- 1, 2 and 3 hr designs - UL 2079 standard compliant
UL Listings
HW-D-0495 Protected Beam Penetration HW-D-0496 Under Flat Concrete (shaft wall) HW-D-0497 Parallel to Protected Beam (shaft wall) HW-D-0498 Under PT or Structural Concrete HW-D-0499 Parallel to Unprotected Fluted Metal Deck HW-D-0500 Perpendicular Unprotected Fluted Metal Deck HW-D-0501 Parallel to Beam (standard wall) HW-D-0502 Parallel & Edge Overlap Under Structural Support HW-D-0503 Under Layer "Type C" UL 500 Series Designs HW-D-0504 Under Unprotected Fluted Metal Deck (shaft wall) HW-D-0505 Under PT or Structural Concrete (chase wall) HW-D-0506 Under Fluted Metal Deck (chase wall) HW-D-0512 Perpendicular Protected Deck w/Fire Prooing Flute Fill HW-D-0513 Perpendicular Unprotected Deck w/Mineral Wool only Flute Fill HW-D-0543 Stair Shaft (093 Control Joint Optional) HW-D-0544 Parallel under Flute (Flute Cover Plate) HW-D-0558 Ofset Leg Standard Wall Protected Roof Deck/Substrate HW-D-0559 Ofset Leg Shaft Wall Protected Roof Deck/Substrate HW-D-0597 Parallel to Beam (Z-clip & Drywall Rip) HW-D-0631 Shaft Wall Parallel & Edge Overlap Under Structural Support HW-D-0632 PT or Structural Concrete Bare Slotted with Caulks HW-D-0633 Fluted Metal Deck Bare Slotted with Flute Plate/Caulks WW-S-0055 Vertical Wall to Wall Joint BW-S-0021 Bottom of Wall
Details shown are a limited sample of assemblies based on UL certified and listed assemblies. Additional assembly details, submittal sheets, and constructability designs are periodically added upon design and approval. Information can be viewed, downloaded, and printed from www.clarkdietrich.com/BlazeFrame.
Project Information
Name:
Address:
City/ST/ZIP:
Contractor Information
Name:
Contact:
Phone:
Fax:
Architect Information
Name:
Contact:
Phone:
Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
® (CJB)
“CJB” (Control Joint Backer)
Composite Fire Stop/Control Joint Backer for use to protect Architectural
design joints (optional control joint over gap) for up to 2 hr rated assemblies.
between opposing drywall edge at control joint locations. Also eliminates the
need for a second stud in the gypsum assembly.
Material:
Yield Strength: Grade 33ksi
Coating:
G40
18mils: 25 Gauge, 0.0188” Design Thickness, 0.0179“ Min. Thickness
Dimensions:
Width:
3-1/4”
Length:
10’-0”
Packaging:
14 Pieces/Carton
Intumescent
Width
Width
Gap
Width
Flange
Width
CJB-181.25”
3.25”
.75”
1.25”
ASTM A1003, C955
WFCI 12033
is available @ www.clarkdietrich.com
CD-BlazeFrame-CJB © 08/12 ClarkDietrich Building Systems
Wallboard
Eliminates the need
for a second stud in
the gypsum assembly
Steel Stud
093 Control Joint
CJB - Control Joint Backer
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206
Sales: 800-543-7140
clarkdietrich.com
FAS-093X Fire Rated Control Joint
A
Product Data & Ordering Information:
ASTM & Code Standards:
� � �
� No Drywall Rips Required
� No Sealant Required
� No Mineral Wool Required
� UL Listed Joint System
� US Patent 8,671,632
Fir
e R
ate
d C
on
tro
l Jo
int
2.00”
.478”.693”
8
1 Hour Fire Rating
2 Hour Fire Rating
09.22.16 (Non-Structural Metal Framing)
Project Information
Name:
Address:
City/ST/ZIP:
Contractor Information
Name:
Contact:
Phone:
Fax:
Architect Information
Name:
Contact:
Phone:
Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
Material:
Yield Strength: Grade 33ksi for 33mils & 43mils, 50ksi for 54mils
Coating: CP60 (G90 available)
33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness
43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness
54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness
Dimensions:
Inside width: Equal to the outside width of the stud
Widths (W): 3-5/8”, 4”, 6” and 8”
Track length: 10’-0”
Lower Leg
Length (L)
Tape
Width (I)
Slot
Height (S)
Joint
Protection
ODSL 2 3.00” 1.00” 1.50” 0.75”
ODSLW 2 3.00” 1.25” 1.50” 1.00”
ODSLX 2 4.00” * 1.75” 2.00” 1.50”
ASTM A1003, C955
UL2079, E814, E1966, E119
is available @ www.clarkdietrich.com
CD-BlazeFrame-ODSL2 © 08/12 ClarkDietrich Building Systems
Width (W)
(L)0.75” 0.75”
(1-1/4”) **
®
“ODSL 2” (Offset Slotted Leg)
Two offset slotted lower legs
Composite F
up to 1-1/2” thick in head of wall and wall to wall (column) assemblies. Pro-
vides 100% unencumbered joint protection. Accommodates up to 3” overall
legs with slots spaced 1”o.c. for positive attachment of studs per listed
assemblies in UL Fire Resistance Directory.
provides air, smoke and sound seals. When exposed to heat above 325
degrees Fahrenheit, the intumescent material expands up to 35 times its size.
* 4” leg length is not available for 2-1/2” wide system** Other offset step depths available
(I)
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206
Sales: 800-543-7140
clarkdietrich.com
Project InformationName: Address: City/ST/ZIP: Contractor Information
Name: Contact: Phone: Fax:
Architect InformationName: Contact: Phone: Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
®
Composite Fire Stop/Framing for
100% unencumbered joint protection. Accommodates up to 1 1/2” overall
with slots spaced 1”o.c. for positive attachment of studs per listed assemblies
in UL Fire Resistance Directory.
provides air, smoke and sound seals. When exposed to heat above 325
degrees Fahrenheit, the intumescent material expands up to 35 times its size.
Material: Yield Strength: Grade 33ksi for 33mils & 43mils
Grade 50ksi for 54mils
Coating:
CP60 (G90 available)
33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness
43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness
54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness
Dimensions: Inside width: Equal to the outside width of the stud
Widths (W):
2-1/2”, 3-5/8”, 4”, 6” and 8”
Vertical slots: 0.22” wide & spaced every 1”o.c.
Track length: 10’-0”
Leg Length (L)
Tape Width (I) Slot
Height (S) Joint Protection
DSL 23.00”
1.00”1.50”
0.75”
DSLW 23.00”
1.25”1.50”
1.00”
DSLX 24.00” *
1.75”2.00”
1.50”
ASTM A1003, C955UL2079, E814, E1966, E119
is available @ www.clarkdietrich.com
CD-BlazeFrame-DSL2 © 08/12 ClarkDietrich Building Systems
(L)
(W)
(L)
(S)
(I)
(L)
.22”
1.00”
Fastener mid-height of exposed slot
* 4” leg length is not available for 2-1/2” wide system
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206 Sales: 800-543-7140clarkdietrich.com
NEED TO SEND PRODUCT SUBMIT TALS?
Build BlazeFrame Product Submittals for your next project. Use ClarkDietrich's SubmittalPro® Product Submittal System to create and send a PDF package of BlazeFrame's product information and technical submittals based on your project's layout conditions.
Launch SubmittalPro® from clarkdietrich.com
Code Approvals
15
CD-BlazeFrame 5/16 © ClarkDietrich Building Systems. The technical content of this literature is effective 5/12/16 and supersedes all previous information.
Turn to ClarkDietrich for a complete lineup of steel construction products and services nationwide:
Interior Framing∙Exterior Framing∙Interior Finishing∙Clips/Connectors∙Metal Lath/Accessories∙Engineering
9100 Centre Pointe Dr. Suite 210 West Chester, OH 45069
P 513.870.1100 F 513.870.1300
clarkdietrich.comClarkwestern Dietrich Building Systems LLC