sto poren panel cladding system drawing · pdf filestoporen panel cladding system inter-storey...

185
Drawing Description Drawing No. Drawing Register PP 001 - 006 Introduction Series 000 StoPoren Panel Cladding System StoPoren Plaster System PP 007 StoPoren Panel Cladding System StoPoren Plaster System PP 008 StoPoren Panel Cladding System StoPoren Panel Information PP 009 StoPoren Panel Cladding System StoPoren Panel layout PP 010 Panel Layout Series 100 StoPoren Panel Cladding System Cavity Batten Setout (600 ctrs) - Isometric PP 100 StoPoren Panel Cladding System Cavity Batten Setout (400 ctrs) - Isometric PP 101 StoPoren Panel Cladding System Cavity Batten Setout Steel Frame/Thermal Break (600 ctrs) PP 102 StoPoren Panel Cladding System Cavity Batten Setout (300 & 600 ctrs) Elevation PP 103 Foundation Series 200 StoPoren Panel Cladding System Foundation Slab-on-ground PP 200 StoPoren Panel Cladding System Insulated Slab-on-Ground PP 201 StoPoren Panel Cladding System Rebated Slab-on-Ground - Plaster Finish PP 202 StoPoren Panel Cladding System ESP Block Foundation Detail PP 203 StoPoren Panel Cladding System Conc.Block Foundation Edge Detail PP 204 StoPoren Panel Cladding System Solid Conc.Foundation Edge Detail PP 205 StoPoren Panel Cladding System Conc.Continuous Perimeter Found.Wall PP 206 StoPoren Panel Cladding System Timber Pile/Subfloor Ventilation (Parallel Wall) PP 207 StoPoren Panel Cladding System Timber Pile/Subfloor Ventilation (Right Angled Wall) PP 208 StoPoren Panel Cladding System Timber Subfloor with Jack Studs PP 209 StoPoren Panel Cladding System Masonry Conc.Block in-ground Wall PP 210 StoPoren Panel Cladding System Masonry Conc.Block Inter-Storey Drained Junction PP 211 StoPoren Panel Cladding System Ribraft Floor System / Edge Detail PP 212 StoPoren Panel Cladding System Maxraft Floor System / Edge Detail PP 213 Walls Series 300 StoPoren Panel Cladding System Poren Panel layout PP 300 StoPoren Panel Cladding System Cross Section PP 301 StoPoren Panel Cladding System External Corner PP 302 StoPoren Panel Cladding System Internal Corner PP 303 StoPoren Panel Cladding System Vertical Control Joint PP 304 StoPoren Panel Cladding System Horizontal inter-storey Control Joint - Opt 1 PP 305 StoPoren Panel Cladding System Horizontal inter-storey Control Joint - Opt 2 PP 306 StoPoren Panel Cladding System Drained Joint at Third Storey PP 307 StoPoren Panel Cladding System Boxed Beam PP 308 StoPoren Panel Cladding System Post Detail PP 309 THESE DETAILS ARE ISSUED AS A GUIDE INCORPORATING STANDARD BUILDING PRACTICES. ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS. THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE. STO DRAWING REGISTER PAGE 1 OF 6 The information contained in this detail is based on our experience and testing and represents the latest information available at the date of issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications. STO POREN SYSTEM STO POREN PANEL CLADDING SYSTEM DRAWING REGISTER PP 001 2014

Upload: vuongtuyen

Post on 06-Mar-2018

238 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

Drawing Register PP 001 - 006

Introduction Series 000StoPoren Panel Cladding System StoPoren Plaster System PP 007

StoPoren Panel Cladding System StoPoren Plaster System PP 008

StoPoren Panel Cladding System StoPoren Panel Information PP 009

StoPoren Panel Cladding System StoPoren Panel layout PP 010

Panel Layout Series 100StoPoren Panel Cladding System Cavity Batten Setout (600 ctrs) - Isometric PP 100

StoPoren Panel Cladding System Cavity Batten Setout (400 ctrs) - Isometric PP 101

StoPoren Panel Cladding System Cavity Batten Setout Steel Frame/Thermal Break (600 ctrs) PP 102

StoPoren Panel Cladding System Cavity Batten Setout (300 & 600 ctrs) Elevation PP 103

Foundation Series 200StoPoren Panel Cladding System Foundation Slab-on-ground PP 200

StoPoren Panel Cladding System Insulated Slab-on-Ground PP 201

StoPoren Panel Cladding System Rebated Slab-on-Ground - Plaster Finish PP 202

StoPoren Panel Cladding System ESP Block Foundation Detail PP 203

StoPoren Panel Cladding System Conc.Block Foundation Edge Detail PP 204

StoPoren Panel Cladding System Solid Conc.Foundation Edge Detail PP 205

StoPoren Panel Cladding System Conc.Continuous Perimeter Found.Wall PP 206

StoPoren Panel Cladding System Timber Pile/Subfloor Ventilation (Parallel Wall) PP 207

StoPoren Panel Cladding System Timber Pile/Subfloor Ventilation (Right Angled Wall) PP 208

StoPoren Panel Cladding System Timber Subfloor with Jack Studs PP 209

StoPoren Panel Cladding System Masonry Conc.Block in-ground Wall PP 210

StoPoren Panel Cladding System Masonry Conc.Block Inter-Storey Drained Junction PP 211

StoPoren Panel Cladding System Ribraft Floor System / Edge Detail PP 212

StoPoren Panel Cladding System Maxraft Floor System / Edge Detail PP 213

Walls Series 300StoPoren Panel Cladding System Poren Panel layout PP 300

StoPoren Panel Cladding System Cross Section PP 301

StoPoren Panel Cladding System External Corner PP 302

StoPoren Panel Cladding System Internal Corner PP 303

StoPoren Panel Cladding System Vertical Control Joint PP 304

StoPoren Panel Cladding System Horizontal inter-storey Control Joint - Opt 1 PP 305

StoPoren Panel Cladding System Horizontal inter-storey Control Joint - Opt 2 PP 306

StoPoren Panel Cladding System Drained Joint at Third Storey PP 307

StoPoren Panel Cladding System Boxed Beam PP 308

StoPoren Panel Cladding System Post Detail PP 309

THESE DETAILS ARE ISSUED AS A GUIDE INCORPORATING STANDARD BUILDING PRACTICES.

ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.

THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS

RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL

WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

STO DRAWING REGISTER

PAGE 1 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 001

2014

Page 2: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

Wall Penetrations & Fittings Series 350StoPoren Panel Cladding System Pipe Penetration Detail PP 350

StoPoren Panel Cladding System Light Fitting/Fixing Detail PP 351

StoPoren Panel Cladding System Tap Fiting/Fixing Detail PP 352

StoPoren Panel Cladding System Handrail Bracket/Fixing Detail PP 353

StoPoren Panel Cladding System Meterbox - Isometric PP 354

StoPoren Panel Cladding System Meterbox - Cross Section PP 355

StoPoren Panel Cladding System Downpipe Saddle Fixing & Wiring Details PP 356

StoPoren Panel Cladding System Fan Vent Detail PP 357

StoPoren Panel Cladding System Inter-Storey Junction with Poly Profile PP 358

StoPoren Panel Cladding System Joint at Third Storey with Poly profile PP 359

Joinery Series 400StoPoren Panel Cladding System Alu.Joinery - Head Detail - Stick on Jamb PP 400

StoPoren Panel Cladding System Alu.Joinery - Head Detail - Cavity Jamb PP 401

StoPoren Panel Cladding System Alu.Joinery - Sill Detail - Sto uPVC Stick on Sill PP 402

StoPoren Panel Cladding System Alu.Joinery - Sill Detail - Sto Cavity Sill PP 403

StoPoren Panel Cladding System Alu.Joinery - Jamb Detail - Sto uPVC Cavity Jamb PP 404

StoPoren Panel Cladding System Alu.Joinery - Jamb Detail - Sto uPVC Stick on Jamb PP 405

StoPoren Panel Cladding System Int.Cnr Alu.Window/Door Joinery - Jamb Detail PP 406

StoPoren Panel Cladding System Entry Door Threshold Detail PP 407

StoPoren Panel Cladding System Entry Door/Deck Threshold Detail PP 408

StoPoren Panel Cladding System Bifold Door/Threshold Detail PP 409

StoPoren Panel Cladding System Level Entry Threshold Detail PP 410

StoPoren Panel Cladding System Garage Door - Timber Head Detail PP 411

StoPoren Panel Cladding System Garage Door - Timber Jamb Detail PP 412

StoPoren Panel Cladding System Garage Door - Plastered Head Detail PP 413

StoPoren Panel Cladding System Garage Door - Plastered Jamb Detail PP 414

Parapets, Balustrades, Decks Series 500StoPoren Panel Cladding System Parapet/Metal Flashing Detail PP 500

StoPoren Panel Cladding System Plastered Parapet/Balustrade Detail PP 501

StoPoren Panel Cladding System Parapet and/or Encl.Balustrade Wall Junction - Plan View PP 502

StoPoren Panel Cladding System Flexible Flashing Install - Isometric PP 503

StoPoren Panel Cladding System Metal Saddle Flashing & Cap Install - Isometric PP 504

StoPoren Panel Cladding System StoFlexyl Meshed Saddle Flashing Install - Isometric PP 505

StoPoren Panel Cladding System StoFlexyl Meshed Waterproofing Cap - Isometric PP 506

StoPoren Panel Cladding System Balustrade/Encl.Deck Detail PP 507

StoPoren Panel Cladding System Enclosed Deck Detail PP 508

StoPoren Panel Cladding System Cantilevered Slatted Deck PP 509

StoPoren Panel Cladding System Non Cantilevered Slatted Deck PP 510

StoPoren Panel Cladding System Timber Beam/Pergola Detail PP 511

StoPoren Panel Cladding System Parallel Deck Joist Bracket PP 512

StoPoren Panel Cladding System RWH/Scupper Opening PP 513

STO DRAWING REGISTER

THESE DETAILS ARE ISSUED AS A GUIDE INCORPORATING STANDARD BUILDING PRACTICES.

ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.

THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS

RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL

WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

PAGE 2 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 002

2014

Page 3: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

Soffit Series 600StoPoren Panel Cladding System Flat Soffit/Wall Junction PP 600

StoPoren Panel Cladding System Raking Soffit/Wall Junction PP 601

StoPoren Panel Cladding System Face Fixed Fascia PP 602

StoPoren Panel Cladding System Raking Soffit PP 603

StoPoren Panel Cladding System Raking Soffit - Sto uPVC Control Joint PP 604

StoPoren Panel Cladding System Soffit to Cladding Detail PP 605

StoPoren Panel Cladding System Gutter/Wall Junction PP 606

StoPoren Panel Cladding System Soffit at Window/Door Head PP 607

Roof Series 700StoPoren Panel Cladding System Apron Flashing PP 700

StoPoren Panel Cladding System Parallel Apron Flashing PP 701

StoPoren Panel Cladding System Inter-storey Transverse (Apron) Roof/Stopend PP 702

StoPoren Panel Cladding System Inter-storey Deck or Roof/Stopend Flashing PP 703

StoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704

StoPoren Panel Cladding System Roof Penetration/Gutter (Masonry Tile) PP 705

StoPoren Panel Cladding System Roof Parallel/Hidden Gutter PP 706

StoPoren Panel Cladding System Face Fixed Fascia/Barge PP 707

StoPoren Panel Cladding System Face Fixed Fascia/Membrane Roof PP 708

StoPoren Panel Cladding System Roof/Wall Ridge PP 709

StoPoren Panel Cladding System Framed Chimney PP 710

Dissimilar Material

Weatherboard Series 800StoPoren Panel Cladding System Ext.Corner Weatherboard/Sto Poren - Opt 1 PP 800

StoPoren Panel Cladding System Ext.Corner Weatherboard/Sto Poren - Opt 2 PP 800-1

StoPoren Panel Cladding System Ext.Corner Weatherboard/Sto Poren - Direct Fix PP 801

StoPoren Panel Cladding System Int.Corner Weatherboard/Sto Poren - Opt 1 PP 802

StoPoren Panel Cladding System Int.Corner Weatherboard/Sto Poren - Opt 2 PP 802-1

StoPoren Panel Cladding System Int.Corner Weatherboard/Sto Poren - Direct Fix PP 803

StoPoren Panel Cladding System Vertical Joint Weatherboard/Sto Poren - Opt 1 PP 804

StoPoren Panel Cladding System Vertical Joint Weatherboard/Sto Poren - Opt 2 PP 804-1

StoPoren Panel Cladding System Vertical Joint Weatherboard/Sto Poren - Opt 3 PP 804-2

StoPoren Panel Cladding System Horizontal Junction Weatherboard/Sto Poren PP 805

StoPoren Panel Cladding System Gable End Weatherboard/Sto Poren PP 806

STO DRAWING REGISTER

THESE DETAILS ARE ISSUED AS A GUIDE INCORPORATING STANDARD BUILDING PRACTICES.

ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.

THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS

RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL

WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

PAGE 3 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 003

2014

Page 4: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

Continuation Dissimilar Material

Brick Series 810StoPoren Panel Cladding System External Corner Brick Veneer/Sto Poren PP 810

StoPoren Panel Cladding System Internal Corner Brick Veneer/Sto Poren - Opt 1 PP 811

StoPoren Panel Cladding System Internal Corner Brick Veneer/Sto Poren - Opt 2 PP 812

StoPoren Panel Cladding System Vertical Junction Brick Veneer/Sto Poren PP 813

StoPoren Panel Cladding System Horizontal Junction Brick Veneer/Sto Poren PP 814

Fibre Cement Sheet Series 820StoPoren Panel Cladding System External Corner FC Sheet/ Sto Poren PP 820

StoPoren Panel Cladding System Internal Corner FC Sheet/ Sto Poren - Opt 1 PP 821

StoPoren Panel Cladding System Internal Corner FC Sheet/ Sto Poren - Opt 2 PP 822

StoPoren Panel Cladding System FC Sheet - Framed Sub Floor Cladding PP 823

StoPoren Panel Cladding System FC Sheet Gable End PP 824

Concrete Block Series 830StoPoren Panel Cladding System External Corner Concrete Block/Sto Poren PP 830

StoPoren Panel Cladding System Internal Corner Concrete Block/Sto Poren PP 831

StoPoren Panel Cladding System Vertical Joint Concrete Block/Sto Poren PP 832

StoPoren Panel Cladding System Horizontal Junction Concrete Block/Sto Poren PP 833

Manufactured Stone - Schist & Natural Stone Series 840StoPoren Panel Cladding System Ext.Cnr Manuf.Stone/Sto Poren - Opt 1 PP 840

StoPoren Panel Cladding System Ext.Cnr Manuf.Stone/Sto Poren - Opt 2 PP 841

StoPoren Panel Cladding System Ext.Cnr Schist or Stone Veneer/Sto Poren PP 842

StoPoren Panel Cladding System Boxed Ext.Cnr Stone Veneer/Sto Poren PP 843

StoPoren Panel Cladding System Internal Cnr. Manuf.Stone/Sto Poren PP 844

StoPoren Panel Cladding System Internal Cnr. Schist or Stone Veneer/Sto Poren PP 845

StoPoren Panel Cladding System Vertical Junction Manuf.Stone/Sto Poren PP 846

StoPoren Panel Cladding System Vertical Junction Schist or StoneVeneer/Sto Poren PP 847

StoPoren Panel Cladding System Horiz.Junction Manuf.Stone/Sto Poren PP 848

StoPoren Panel Cladding System Horiz.Junction Schist or StoneVeneer/Sto Poren PP 849

STO DRAWING REGISTER

THESE DETAILS ARE ISSUED AS A GUIDE INCORPORATING STANDARD BUILDING PRACTICES.

ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.

THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS

RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL

WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

PAGE 4 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 004

2014

Page 5: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

Continuation Dissimilar Material

Profile Metal Series 850StoPoren Panel Cladding System Ext.Cnr Horiz.Profiled Metal/Sto Poren PP 850StoPoren Panel Cladding System Int.Cnr Horiz.Profiled Metal/Sto Poren PP 851StoPoren Panel Cladding System Vertical Junction Horiz.Profiled Metal/Sto Poren PP 852StoPoren Panel Cladding System Horizontal Junction Horiz.Profiled Metal/Sto Poren PP 853StoPoren Panel Cladding System External Corner Vertical Profiled Metal/Sto Poren PP 854StoPoren Panel Cladding System Internal Corner Vertical Profiled Metal/Sto Poren PP 855StoPoren Panel Cladding System Horiz.Junction Vertical Profiled Metal/Sto Poren PP 856

StoTherm Panel EIFS Series 860StoPoren Panel Cladding System Ext.Cnr StoTherm/Sto Poren PP 860StoPoren Panel Cladding System Int.Cnr StoTherm/Sto Poren PP 861StoPoren Panel Cladding System Vertical Joint 50mm StoTherm/Sto Poren PP 862StoPoren Panel Cladding System Vertical Joint 80mm StoTherm/Sto Poren PP 863StoPoren Panel Cladding System Inter-Storey Junction StoTherm/Sto Poren PP 864StoPoren Panel Cladding System Inter-Storey Third Storey Inter-storey Junction PP 865

DISSIMILAR JOINERY Series 870TIMBER JOINERYStoPoren Panel Cladding System Timber Window Joinery - Head Detail PP 870StoPoren Panel Cladding System Timber Window Joinery - Sill Detail PP 871StoPoren Panel Cladding System Timber Window Joinery - Jamb Detail PP 872StoPoren Panel Cladding System Timber Door Joinery - Timber Floor/Threshold Detail PP 873StoPoren Panel Cladding System Timber Door Joinery - Concrete Floor/Threshold Detail PP 874NK PVCu JOINERYStoPoren Panel Cladding System NK PVCu - Head Detail PP 875StoPoren Panel Cladding System NK PVCu - Sill Detail PP 876StoPoren Panel Cladding System NK PVCu - Jamb Detail PP 877FLASHMAN JOINERY FLASHING SYSTEMStoPoren Panel Cladding System Flashman Head Flashing PP 878StoPoren Panel Cladding System Flashman Sill Flashing PP 879StoPoren Panel Cladding System Flashman Jamb Flashing PP 880HOMERIT PVC JOINERYStoPoren Panel Cladding System Homerit PVC Joinery - Head Detail PP 881StoPoren Panel Cladding System Homerit PVC Joinery - Sill Detail PP 882StoPoren Panel Cladding System Homerit PVC Joinery - Jamb Detail PP 883

MOULDINGS & SHAPESRefer to - www.accumen.co.nzLightweight exterior decorative moldings and shapes, including columns, architraves,cornices, window sills, fence caps, quoins that can be finished in Stolit K or MP spongecoloured finishing render.Note: Decorative mouldings require min. 10° PPope to top surface and a drip edge.

STO DRAWING REGISTER

THESE DETAILS ARE ISSUED AS A GUIDE TO INCORPORATE STANDARD BUILDING PRACTICES.ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE ISRESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALLWATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

PAGE 5 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 005

2014

Page 6: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Drawing Description Drawing No.

StoPoren Panel(40mm Cavity)Series 1000

StoPoren Panel Cladding System Introduction (40mm Cavity) PP 1000

StoPoren Panel Cladding System Information (40mm Cavity) PP 1001

StoPoren Panel Cladding System Cavity Spacer Setout (600 Ctrs) PP 1002

StoPoren Panel Cladding System Cavity Batten Setout (600 Ctrs) PP 1003

StoPoren Panel Cladding System Cavity Batten Setout (400 Ctrs) PP 1004

StoPoren Panel Cladding System Cavity Batten Setout (400 Ctrs) - Elevation PP 1005

StoPoren Panel Cladding System Rebated Slab-on-Ground - Cavity Spacer PP 1006

StoPoren Panel Cladding System Foundation Slab-on-Ground - Cavity Spacer PP 1007

StoPoren Panel Cladding System External Corner PP 1008

StoPoren Panel Cladding System Internal Corner PP 1009

StoPoren Panel Cladding System Vertical Control Joint PP 1010

StoPoren Panel Cladding System Horizontal Inter-Storey Joint PP 1011

StoPoren Panel Cladding System Horizontal Inter-Storey Control Joint PP 1012

StoPoren Panel Cladding System Drained Joint at Third Storey PP 1013

StoPoren Panel Cladding System Meterbox Detail PP 1014

StoPoren Panel Cladding System Alu.Window Joinery - Head Detail PP 1015

StoPoren Panel Cladding System Alu.Window Joinery - Sill Detail PP 1016

StoPoren Panel Cladding System Alu.Window Joinery - Jamb Detail PP 1017

StoPoren Panel Cladding System Parapet Detail - Metal Cap PP 1018

StoPoren Panel Cladding System Parapet Detail - Plastered Finish PP 1019

StoPoren Panel Cladding System Parapet and/or Encl.Balustrade to Wall - Plan PP 1020

StoPoren Panel Cladding System Balustrade/Enclosed Deck Detail PP 1021

StoPoren Panel Cladding System Flexible Flashing Install PP 1022

StoPoren Panel Cladding System Metal Saddle Flashing PP 1023

StoPoren Panel Cladding System StoFlexyl Meshed Saddle Flashing PP 1024

StoPoren Panel Cladding System Raking Soffit/Wall Junction PP 1025

StoPoren Panel Cladding System Flat Soffit/Wall Junction PP 1026

STO DRAWING REGISTER

THESE DETAILS ARE ISSUED AS A GUIDE TO INCORPORATE STANDARD BUILDING PRACTICES.

ALWAYS REFER TO MANUFACTURERS CURRENT DETAILS AND SPECIFICATIONS.

THE SEQUENCE OF WORK COVERS VARIOUS BUILDING COMPONENTS, EACH TRADE IS

RESPONSIBLE TO ENSURE THEIR ELEMENTS ARE FULLY INSTALLED INCLUDING ALL

WATERPROOFING/SEALANT/ FLASHINGS AS IS APPLICABLE.

PAGE 6 OF 6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAWING REGISTER

PP 006

2014

Page 7: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

STOPOREN PANEL CLADDING SYSTEM with Stoarmat Miral Plaster System

THE STOPOREN PANEL CLADDING SYSTEM HAS BEEN APPRAISED AS AN EXTERNAL WALL CLADDING SYSTEM FORBUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER FRAMING COMPLYING WITH THE NZBC; AND,• WITH A RISK SCORE OF 0-20, CALCULATED IN ACCORDANCE WITH NZBC ACCEPTABLE SOLUTION E2/AS1, TABLE 2;

AND,• SITUATED IN NZS 3604 WIND ZONES UP TO, AND INCLUDING ‘EXTRA HIGH’.

THE STOPOREN PANEL CLADDING SYSTEM HAS ALSO BEEN APPRAISED FOR WEATHERTIGHTNESS AND STRUCTURALWIND LOADING WHEN USED AS AN EXTERNAL WALL CLADDING SYSTEM FOR BUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER OR STEEL FRAMING COMPLYING WITH THE NZBC; AND,• SITUATED IN SPECIFIC DESIGN WIND PRESSURES UP TO A MAXIMUM DESIGN DIFFERENTIAL ULTIMATE LIMIT STATE

(ULS) OF 2.5 KPA.

STOARMAT MIRAL PLASTER SYSTEM Can also be used for additional strength & reinforcement

INCORPORATING:1. S-PROTECT WS 205 SEALER TO SEAL POREN PANELS2. STOPOREN PLASTER 25kg BAG3. STOARMAT MESHED REINFORCEMENT COAT4. STOLIT K : 1.0mm, 1.5mm, 2.0mm & 3.0mm COLOURED FINISHING RENDER MP : MP COLOURED FINE SPONGE FINISHING RENDER MP NATURAL COLOURED FINE SAND FINISHING RENDER MILANO SMOOTH COLOURED FINISHING RENDER5. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL

: LASTIC SATIN FACADE PAINT 15lt PAIL : LOTUSAN MINERAL RESIN PAINT 15lt PAIL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

STOPOREN PLASTER SYSTEM

PP 007

2014

Page 8: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

STOPOREN PANEL CLADDING SYSTEM with Stoarmat Miral Plaster System

THE STOPOREN PANEL CLADDING SYSTEM HAS BEEN APPRAISED AS AN EXTERNAL WALL CLADDING SYSTEM FORBUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER FRAMING COMPLYING WITH THE NZBC; AND,• WITH A RISK SCORE OF 0-20, CALCULATED IN ACCORDANCE WITH NZBC ACCEPTABLE SOLUTION E2/AS1, TABLE 2;

AND,• SITUATED IN NZS 3604 WIND ZONES UP TO, AND INCLUDING ‘EXTRA HIGH’.

THE STOPOREN PANEL CLADDING SYSTEM HAS ALSO BEEN APPRAISED FOR WEATHERTIGHTNESS AND STRUCTURALWIND LOADING WHEN USED AS AN EXTERNAL WALL CLADDING SYSTEM FOR BUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER OR STEEL FRAMING COMPLYING WITH THE NZBC; AND,• SITUATED IN SPECIFIC DESIGN WIND PRESSURES UP TO A MAXIMUM DESIGN DIFFERENTIAL ULTIMATE LIMIT STATE

(ULS) OF 2.5 KPA.

STOPOREN PLASTER SYSTEM

INCORPORATING:1. S-PROTECT WS 205 SEALER TO SEAL POREN PANELS2. STOPOREN PLASTER 25kg BAG3. STOPLEX W SEALER 10lt CONTAINER4. STOLIT K : 1.0mm, 1.5mm, 2.0mm & 3.0mm COLOURED FINISHING RENDER 25kg PAIL5. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL

: LASTIC SATIN FACADE PAINT 15lt PAIL : LOTUSAN MINERAL RESIN PAINT 15lt PAIL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

STOPOREN PLASTER SYSTEM

PP 008

2014

Page 9: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

2200

2020

0mm

STE

EL

RE

INFO

RC

ING

CE

NTR

ES

25 55 SCALE NTS

POREN PANELAUTOCLAVED AERATED CONCRETEDENSITY 600kg/m³THERMAL RESISTANCE RV 0.30ON CAVITY CONSTRUCTION

POREN PANEL DIMENSIONS2200 x 600 x 50mmFREIGHT20 PANELS PER DOUBLE PALLET1.3m³ PER PALLET + PALLETAREA 1.32sqm EACHWEIGHT 42kg EACH

POREN 100mm FIXINGSCOUNTERSUNK MAX. 12mm

MAX 300mm FIXING CENTRES

FIXINGS MINIMUM 40mm FROMTHE HORIZONTAL EDGE

STO CAVITY BATTENVH POLYSTYRENE1200 x 50 x 20mm250 PER PACKET

600

150

300

150

600

BEVELED EDGE OF PANELFACES FRAMING

50

FIXINGS

FIXINGS

170 155165

200

200

200

200

200

160

200

200

200

200

200

STEEL REINFORCING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

POREN PANEL INFORMATION

PP 009

2014

Page 10: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:50

600

50

50

STAGGER

CORNERS

CUT TO SPAN

MINIMUM OF

TWO STUDS

FILL IN JOINERY SILL

AND HEAD PANELS

AFTER JAMB PANELS

FITTED

MEASURE VERTICAL HEIGHT AND CUT

FROM TWO PANEL ROWS TO AVOID

NARROW PANEL WIDTHS

POREN PANEL INSTALLATION

1. LEAVE PANEL IN PLASTIC WRAP AND COVER TO KEEP DRY BEFORE USING.

2. READ SPECIFICATIONS AND CHECK DRAWINGS, DETAILS, FRAMING, UNDERLAY, FLASHING TAPES, AND BLOCKING

IS SATISFACTORY.

3. INSTALL STO PVC FOOT TRAY AND JOINERY FLASHINGS AS PER STO DETAILS (BUILDER TO SUPPLY

ALUMINUM HEAD FLASHINGS

4. CHECK PANEL LAYOUT AND INSTALL PANEL HORIZONTALLY STARTING FROM FOUNDATION.

5. STAGGER VERTICAL PANEL JOINTS GENERALLY OFF STUDS IN STRETCHER BOND PATTERN.

PANELS SHOULD BRIDGE TWO (2) STUDS TO ENSURE THEY ARE SECURELY FIXED

6. GLUE OR MORTAR ALL VERTICAL AND HORIZONTAL JOINTS AND SECURE PANELS WITH

POREN FIXINGS AS PER STO DETAILS.

7. STAGGER EXTERNAL CORNERS PANELS AND BUTT OR STAGGER INTERNAL CORNERS.

8. MEASURE VERTICAL DISTANCES AND CUT FROM LAST TWO ROWS OF PANEL TO AVOID NARROW WIDTHS.

9. PRIME EXPOSED REINFORCING ON CUT PANEL AND BUTT TO ADJACENT PANEL WHERE POSSIBLE.

10. SEAL PANELS WITH S-PROTECT WS 205 AS WORK PROCEEDS TO KEEP PANELS DRY.

2200

GENERALLY BUTT JOIN

PANELS OFF STUDS

SAFE WORKING PRACTICE

1. HAVE SUFFICIENT PEOPLE TO LIFT OR POSITION PANEL ON SITE (MINIMUM TWO MAN LIFT)

2. WEAR PROTECTIVE CLOTHING, EYE AND EAR PROTECTION AND DUST MASK OR RESPIRATOR

WHEN CUTTING OR SANDING.

3. USE A CIRCULAR SAW FITTED WITH A DIAMOND BLADE AND HEPA VACUUM WHEN CUTTING PANEL.

4. CONTAIN CUTTING AREA TO MINIMIZE DUST AND WARN OTHER IN IMMEDIATE VICINITY- HEPA VACUUM UP RESIDUE.

5. PROVIDE SUITABLE ACCESS PLATFORMS, EQUIPMENT AND TOOLS TO CARRY OUT THE WORK.

6. MAINTAIN HEALTH AND SAFETY REGULATIONS AND FIRST AID EQUIPMENT IN ACCORDANCE WITH LEGISLATION.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

POREN PANEL LAYOUT

PP 010

2014

Page 11: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

TIMBER FRAMING

TO NZS 3604

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- POREN PLASTER

- MESH REINFORCEMENT

PLASTER

- STOPLEX W SEALER

- STOLIT COLOURED

FINISHING RENDER

- STOCOLOR PAINT

EXTRA CAVITY BATTENS

BETWEEN 600mm CTR FRAMING

FOR FLEXIBLE UNDERLAY TO

STOP INSULATION ENCROACHING

INTO CAVITY

50m

m m

in.

WALL UNDERLAY MEETING

REQUIREMENTS OF E2/AS1

DPC

NOTE: 600mm FRAMING

FIXINGS AT 300mm CENTRES GENERALLY ON FRAMING 150mm

FROM PANEL EDGE WITH ONE FIXING BETWEEN STUDS ON THE

BOTTOM PLATE ON FRAMING @ 600mm CTRS max.

REFER TO FOUNDATION DETAILS FOR SPECIFIC FIXING LAYOUT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CAVITY BATTEN SETOUT (600ctrs) - ISOMETRIC

PP 100

2014

Page 12: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

NOTE: 400mm FRAMINGFIXINGS AT 300mm CENTRES GENERALLY ON STUDS 150mm

FROM PANEL EDGE AND 400mm CTRS ALONG BOTTOM PLATE

ON FRAMING @ 400mm CTRS max.

REFER TO FOUNDATION DETAILS FOR SPECIFIC FIXING LAYOUT

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- POREN PLASTER

MESH COAT

- STOPLEX W SEALER

- STOLIT K COLOURED

FINISHING RENDER

- STOCOLOR PAINT

50

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CAVITY BATTEN SETOUT (400ctrs) - ISOMETRIC

PP 101

2014

Page 13: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

NOTE: 600mm FRAMINGFIXINGS AT 300mm CENTRES ON FRAMING 150mm FROM PANEL EDGE WITH ONE

FIXING BETWEEN STUDS ON THE BOTTOM PLATE OVER FRAMING @ 600mm CTRS max.

REFER TO FOUNDATION DETAILS FOR SPECIFIC FIXING LAYOUT

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- POREN PLASTER

MESH COAT

- STOPLEX W SEALER

- STOLIT K COLOURED

FINISHING RENDER

- STOCOLOR PAINT

STEEL FRAME CONSTRUCTION MUST BE SPECIFIC DESIGN MEETING

REQUIREMENTS OF NZBC.

FOR STEEL FRAMED BUILDINGS SITUATED IN NZS 3604 WIND ZONES UP TO

VERY HIGH STUDS ARE AT 600mm MAX.CTRS. FOR ALL OTHER DWELLINGS

STUDS ARE AT 400mm MAX.CTRS, DWANGS ARE REQUIRED AT 800mm

CTRS

PROVIDE THERMAL BREAK TO ALL STEEL MEMBERS OR BRANZ APPRAISED

PROPRIETARY RIGID AIR BARRIER/THERMAL BREAK

STO ADJUSTABLE FOOT TRAY

MIN. 50mm PAST BOTTOM PLATE

OR SUBFRAME. VENTILATION MIN

1000sq mm PER LINEAL METRE

POREN PANEL ADHESIVE

ON PANEL JOINTS

POREN PANEL

10mm THICK THERMAL BREAK

BATTENS ON STUDS &

DWANGS - UNDER WALL

UNDERLAY

STEEL STUD

EXTRA CAVITY BATTEN

BETWEEN FRAMING @ 600mm

ctrs FOR FLEXIBLE UNDERLAY.

WALL UNDERLAY MEETING

REQUIREMENTS OF E2/AS1

MIN. R VALUE 0.3 THERMAL

BREAK TO ALL STEEL FRAMING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CAVITY BATTEN SETOUT STEEL FRAME/THERMAL BREAK (600CTRS)

PP 102

2014

Page 14: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

DOOR

WINDOW

FOUNDATION

FRAMING STUDS 400mm CENTERS

N.T.S

SOFFIT PLATE

DOOR WINDOW

FOUNDATION

FRAMING STUDS 600mm CENTERS - WITH BATTENS @

300mm CTRS

NOTE: EXTRA CAVITY BATTEN REQUIRED BETWEEN STUDS

FOR FLEXIBLE UNDERLAY CONSTRUCTION on 600 FRAMING

SOFFIT PLATE

300

600

400

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CAVITY BATTEN LAYOUT (400 & 600ctrs) ELEVATION

PP 103

2014

Page 15: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

6mm OVERHANG

RECOMMENDED TO

AVOID VARIANCES IN

FOUNDATION

TIMBER FRAMING

TO NZS 3604

DPC

INTERIOR LINING

50m

m

clad.

AS PER NZS 3604

6

STO PLASTER SYSTEM

ON FOUNDATION

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWNFOR CLARITY

DPM

INSULATION

AS PER NZBC

H1/AS1

100m

m M

IN

.

Sto P

laster

50m

m

Flexyl

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FOUNDATION SLAB-ON-GROUND

PP 200

2014

Page 16: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

TIMBER FRAMING

TO NZS 3604

DPC

225m

m M

IN

.

TO

U

NP

AV

ED

G

RO

UN

D LE

VE

L

150m

m M

IN

.

TO

P

AV

ED

G

L

AS PER NZS 3604

DPM

INSULATION AS

PER NZBC -

Clause H1

100m

m M

IN

.

Sto P

laster

50m

m

Clad.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INSULATED SLAB-ON-GROUND

PP 201

2014

Page 17: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

TIMBER FRAMING

TO NZS 3604

DPC

STO PLASTER SYSTEM

INTERNAL LINING

DPM

AS PER NZS 3604

75mm

rebate

10

INSULATION TO EXTERIOR

WALLS

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWNFOR CLARITY

INSULATION AS

NZBC H1/AS1

100m

m M

IN

.

Sto P

laster

50m

m

flexyl

50m

m

Clad.

100m

m

to paving

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

REBATED SLAB-ON-GROUND - PLASTERED FINISH

PP 202

2014

Page 18: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

CONCRETE FOOTING AS

PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

DPM REQUIRED ON FOUNDATION

FOR POORLY DRAINED SITES

OTHERWISE TERMINATE AT

BOTTOM EXTERNAL CORNER OF

FOUNDATION

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

DPC

NOTE:INSTALL STOFLEXYL UNDER DPM AT TRANSITION IF REQUIRED FOR POORLY

DRAINED SITES.

STO uPVC VENTED BASE CAP -

5mm MIN.GAP

WALL UNDERLAY

STO 20mm VH CAVITY

BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

CAVITY SPACERS TO

SUIT FIXINGS

DPM

INSULATION AS PER

NZBC - Clause H1

STOFLEXYL WATERPROOFING

TO REBATE, CONTINUE TO 50mm

PAST STO PLASTER

TERMINATION POINT

100m

m

Sto P

laster

50m

m

Flexyl

50m

m

cladding

150m

m

TO

P

AV

ED

G

L

225m

m

TO

U

NP

AV

ED

G

RO

UN

D LE

VE

L

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EPS BLOCK FOUNDATION DETAIL

PP 203

2014

Page 19: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

225m

m unpaved G

L

SCALE 1:5

CONCRETE FOOTING AS

PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN

NOTE:SHELL OF BLOCK CAN SUPPORT

BOTTOM PLATE WHEN SLAB IS

TIED TO FOUNDATION

50m

m

cladding

150m

m to paved

GL

INSULATION AS PER

NZBC - Clause H1

DPM

STO uPVC VENTED

BASE CAP

WALL UNDERLAY

STO 20mm VH CAVITY

BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

CAVITY SPACERS TO

SUIT FIXINGS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CONC.BLOCK FOUNDATION EDGE DETAIL

PP 204

2014

Page 20: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

50m

m

cladding

150m

m to paved

225m

m unpaved G

L

INSULATION AS PER

NZBC - Clause H1

DPM

DPC

10mm INSULATION

IF REQUIRED

GL

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR SPECIFIC

ENGINEER DESIGN (SED)

Varies

refer to N

ZS

3604 or S

ED

WALL UNDERLAY

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED

BASE CAP

STO 20mm VH CAVITY

BATTENS

STOPOREN PLASTER

SYSTEM

CAVITY SPACERS TO

SUIT FIXINGS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

SOLID CONC.FOUNDATION EDGE DETAIL

PP 205

2014

Page 21: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

50

NOTE:1. CONTINUOUS PERIMETER FOUNDATION

WALL WITH VENTILATION OPENINGS

2. CLEARANCE BETWEEN CLADDING AND

ADJACENT GROUND - REFER NZS3604

SED - Specific Engineer Design

as per N

ZS

3604

or S

ED

as per N

ZS

3604

or S

ED

FGL

as per NZS3604

MA

X.H

EIG

HT

- N

ZS

3604 6.11.2

MIN

.H

EIG

HT

6.11.2

WALL UNDERLAY

STO 20mm VH CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CONC.CONTINOUS PERIMETER FOUND.WALL

PP 206

2014

Page 22: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

MIN. H1.2 TREATED

FLOOR JOISTS

20

20

50

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

2/NAIL LAMINATED FLOOR JOISTS

UNDER LOAD BEARING WALLS

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

WALL UNDERLAY

STO 20mm VH CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

H4 TREATED BASEBOARDS WITH

20mm CONTINUOUS SUB FLOOR

VENTILATION GAP BETWEEN

H3.2 TREATED BEARER, H5

TREATED PILE - REFER NZS 3604

FOR TIMBER & PILE SETOUT

POREN PANEL FIXING

NOTE:FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT GROUND

- REFER NZS3604

SCALE 1:5

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER PILE/SUBFLOOR VENTILATION (Parallel Wall)

PP 207

2014

Page 23: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

50

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

MIN. H1.2 TREATED

FLOOR JOISTS

FLOOR JOISTS UNDER LOAD

BEARING WALLS

20

20

H4 TREATED BASEBOARDS WITH

20mm CONTINUOUS SUB FLOOR

VENTILATION GAP BETWEEN

SELECTED FLOORING

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY

STO 20mm VH CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

SCALE 1:5

POREN PANEL FIXING

NOTE:FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER PILE/SUBFLOOR VENTILATION (Right Angled Wall)

PP 208

2014

Page 24: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

OVERHANG BOUNDARY JOIST

TO ALLOW CLADDING TO LAP

SUBFLOOR CLADDING

100mm DRAPE TO

DOUBLE-SIDED PERFORATED

FOIL INSULATION R = 0.9 -

REFER NZBC - Clause H1

JACK FRAMING IN AS PER

NZS3604 6.10.2

DPC

WALL UNDERLAY

STO 20mm VH CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

NOTE:FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER SUBFLOOR WITH JACK STUDS

PP 209

2014

Page 25: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:10

SLAB-ON-GROUND FLOOR & CONC.MASONRY WALLS AS PER NZS

4210/4229/4230 & AND ENGINEERS DRAWINGS

ALLOW ADEQUATE TIME FOR BLOCK TO DRY/STABALISE BEFORE

PLASTERING NORMALLY FROM 4-8 WEEKS IN AVERAGE DRYING

CONDITIONS.

50m

m

SELECTED

INTERIOR LINING

CONCRETE FLOOR SLAB, FOOTING

& WALL TO SPECIFIC DESIGN

SELECTED INTERIOR

PLASTER/FINISH

FILTER FABRIC

SLOTTED DRAIN LAID

TO A FALL

WALL UNDERLAY

NOMINAL 20x45mm H3.1 TIMBER

CAVITY BATTENS

POREN PANEL FIXING

POREN PANEL

POREN PLASTER SYSTEM

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

NZBC COMPLIANT WATERPROOF

TANKING MEMBRANE

NOTE:FOR CLEARANCE BETWEEN

CLADDING AND ADJACENT

GROUND - REFER NZS3604:2011

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

MASONRY CONC.BLOCK IN-GROUND WALL

PP 210

2014

Page 26: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO FLEXYL WATERPROOF TOCONCRETE REBATE SURFACES ANDPLASTER INTO REBATE

STOARMAT MIRALPLASTER SYSTEM

TIMBER FRAMINGTO NZS 3604

DPC

NOTE:CUT SLOPE AT 15° OR CUTREBATE AND PLASTER 15°SLOPE IN.

WALL UNDERLAY

STO 20mm VH CAVITYBATTENS

STOPOREN PLASTERSYSTEM

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED BASECAP

5

REINFORCED CONCRETE BLOCKWALLS IN ACCORDANCE WITH NZS4230, 4229, 4218 & 4210

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PLANEL CLADDING SYSTEM

CONCRETE BLOCK INTER-STOREY DRAINED JUNCTION

PP 211

2014

Page 27: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

50m

m

cladding

150m

m to paved

225m

m unpaved G

L

DPC

GL

WALL UNDERLAY

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED

BASE CAP

STO 20mm VH CAVITY

BATTENS

STOPOREN PLASTER

SYSTEM

CAVITY SPACERS TO

SUIT FIXINGS

RIBRAFT POLYSTYRENE POD

INSTALLATION IN ACCORDANCE TO FIRTH

RIBRAFT CONSTRUCTION DETAILS

85

220

CONCRETE SLAB/REINFORCING

AS PER NZS 3604, SPECIFIC

DESIGN OR ENGINEER (SED)

Reinforcing not shown for clarity

300

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

RIBRAFT FLOOR SYSTEM / EDGE DETAIL

PP 212

2014

Page 28: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

DPC

WALL UNDERLAY

POREN PANEL FIXING

POREN PANEL

STO uPVC VENTED BASE CAP

20mm DRAINED CAVITY

STOPOREN

PLASTER SYSTEM

CAVITY SPACERS TO

SUIT FIXINGS

1. CONCRETE SLAB/REINFORCING AS PER NZS 3604,

SPECIFIC DESIGN OR ENGINEER (SED)

Reinforcing not shown for clarity2. WHERE INSULATION OS BELOW GROUND, APPLY TWO

(2) COATS OF STOFLEXYL TO MAXRAFT INSULATION

BEFORE COMMENCING

3. 150mm MIN. CLEARANCE FROM SLAB LEVEL TO

EXTERIOR PAVING, 225mm MIN. CLEARANCE FROM

SLAB LEVEL TO UNPAVED GROUND TO E2/AS1

SOLID COMPACTION

800mm MIN.PAST EDGE

OF FOUNDATION100

100

50

250

50

10

450

STOMULTI SCREED MESHED

BASECOAT FINISHED IN 1.0mm FLOAT

or STOLIT K FINISHING RENDER,

PAINTED IN STOCOLOR MAXICRYL

SCALE 1:10

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

MAXRAFT FLOOR SYSTEM / EDGE DETAIL

PP 213

2014

Page 29: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE: USE FULL PANELS WHERE POSSIBLE.

ALL PANELS CUTS SHALL BE CAREFULLY MADE TO ACHIEVE A TIGHT BUTT FIT.

ALL PANEL JOINTS MUST BE BONDED WITH POREN ADHESIVE MORTAR OR AAC 2 HOUR

CONSTRUCTION GLUE.

MECHANICALLY FIX ALL PANELS WITH POREN SCREW FIXINGS AT MAXIMUM 300mm CENTRES.

PRIME ANY EXPOSED STEEL REINFORCING ENDS AND BUTT JOIN WHERE POSSIBLE.

PANELS TO BE SUPPORTED BY MINIMUM TWO STUDS OR BLOCKING.

VERTICAL CONTROL JOINTS REQUIRED AT MAXIMUM 8m CENTERS, SEE STO DETAILS.

HORIZONTAL CONTROL JOINTS AT INTERSTOREY JUNCTION IF UNSEASONED JOISTS USED.

HORIZONTAL DRAINED JUNCTION REQUIRED AT THIRD STOREY OR 7 METERS

N.T.S

600

50

50

STAGGER

CORNERS

CUT TO SPAN

MINIMUM OF

TWO STUDS

FILL IN JOINERY SILL

AND HEAD PANELS

AFTER JAMB PANELS

FITTED

MEASURE VERTICAL HEIGHT AND CUT

FROM TWO PANEL ROWS TO AVOID

NARROW PANEL WIDTHS

2200

GENERALLY BUTT JOIN

PANELS OFF STUDS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

POREN PANEL LAYOUT

PP 300

2014

Page 30: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE: STO POREN FIXINGS AT 300mm MAX.CTRS

ENSURE FIXINGS ARE COUNTERSUNK 5mm MIN.WHERE A RIGID UNDERLAY OR

BRACING IS USED.

COUNTERSINK STO POREN FIXINGS TO ACHIEVE 30mm MIN.FRAME PENETRATION UP

TO A MAX.DEPTH OF 12mm

SCALE 1:5

TIMBER FRAMING

AS PER NZS 3604

FLEXIBLE OR RIGID

UNDERLAY

STOTHERM 20mm

VH CAVITY BATTEN

STO POREN FIXING

STO POREN PANEL

STO POREN

PLASTER SYSTEM

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CROSS SECTION

PP 301

2014

Page 31: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

POREN MINERAL PANEL

ADHESIVE OR AAC 2 HR

CONSTRUCTION GLUE ON ALL

PANEL JOINTS

SCALE 1:2

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY

CONTINUOUS AROUND

CORNERS

STO PREMESHED

CORNER ANGLE

STOTHERM 20mm VH

CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXTERNAL CORNER

PP 302

2014

Page 32: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

POREN MINERAL PANEL

ADHESIVE OR AAC 2 HR

CONSTRUCTION GLUE ON ALL

PANEL JOINTS

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

INTERNAL CORNERS ARE

DOUBLE LAPPED MESHED

STOTHERM 20mm VH

CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL CORNER

PP 303

2014

Page 33: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

10mm GAP IN PANEL

NOTE:ENSURE POREN PANELS ARE SUPPORTED BY A MIN.OF 2/STUDS. VERTICAL JOINTS

ARE REQUIRED AT 8.0M MAX.CTRS. SET STO CONTROL JOINT AND REMOVE TAB

CAREFULLY AS SOON AS THE JOINT IS SET TO AVOID CRACKS

INSTALL STO uPVC CONTROL JOINT WITH

MS SEALANT IN MESH COAT

300mm MAX.CTRS

STOTHERM 20mm VH

CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL FIXING

POREN PANEL

BETWEEN STUDS AT

CONTROL JOINT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL CONTROL JOINT

PP 304

2014

Page 34: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

A

NOTE: SEASONED (dry) TIMBER FLOOR JOIST DETAIL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO POREN

SYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZONTAL INTER-STOREY (on dry joists) CONTROL JOINT

PP 305

2014

Page 35: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

A

INSTALL STO uPVC 12mm

CONTROL JOINT WITH MS

SEALANT IN MESH COAT

15

10m

m G

AP

POREN PANEL

STO THERM 20mm VH CAVITY

BATTENS

STOPOREN PLASTER

SYSTEM

WALL UNDERLAY - ENSURE

UNDERLAY RUNS CONTINUOUS

OVER JOINT

POREN PANEL

STO THERM 20mm VH CAVITY

BATTENS

STO POREN PLASTER

SYSTEM

NOTE: UNSEASONED TIMBER FLOOR JOIST DETAIL.

STO POREN FIXING

STO POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZONTAL INTER-STOREY CONTROL JOINT

PP 306

2014

Page 36: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

STO THERM 20mm VH CAVITY

BATTEN

FLASHING TAPE OVER

STO uPVC VENTED

BASE CAP

ALLOW TO PLASTER BEHIND

THEN SEAL WITH MS SEALANT

or STO SEAL TAPE

1. AS REQUIRED TO LIMIT

CONTINUOUS CAVITY

CONSTRUCTION TO TWO

STOREYS OR MAX.7

METERS FLASHING BACK

AND FRONT COVER TO BE A

MINIMUM 35mm EXCLUDING

DRIP EDGES.

2. IN EXTRA HIGH WIND ZONE

INCREASE FLASHING

COVER TO 60mm MIN. AND

USE A RIGID UNDERLAY

SCALE: 1:2

MIN

.C

OV

ER

MIN

.C

OV

ER

35m

m

STO POREN PLASTER SYSTEM

POREN PANEL

WALL UNDERLAY - ENSURE

UNDERLAY RUNS CONTINUOUS

OVER JOINT

WALL UNDERLAY - ENSURE

UNDERLAY RUNS CONTINUOUS

OVER JOINT

5

35m

m

STO POREN FIXING

STO POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DRAINED JOINT AT THIRD STOREY

PP 307

2014

Page 37: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

MIN. 35mm HIGH BACK

FLASHING

FIBRE CEMENT SOFFIT.

STOARMAT PLASTER FC SOFFIT

& uPVC STO CLIP ON TRAYS

STO THERM 20mm

VH CAVITY BATTEN

WALL UNDERLAY

FLASHING TAPE

ONTO WALL

UNDERLAY

5mm GAP 5mm GAP

STO uPVC VENTED

BASE CAP

STO PLASTER

SYSTEM

POREN PANEL

STO POREN FIXING

MIN. 35mm HIGH BACK FLASHING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

BOXED BEAM

PP 308

2014

Page 38: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

POREN PANEL

10

25

POST ANCHOR

BRACKET

STO PLASTER

SYSTEM

STO THERM 20mm VH

CAVITY BATTEN

POREN FIXING

SCALE 1:5

STO PREMESHED

CORNER

STO PLASTER SYSTEM

POREN PANEL FIXING

H3.2 TIMBER POST

STO THERM 20mm VH

CAVITY BATTENS

POREN PANEL - 2 HOUR AAC

CONSTRUCTION GLUE AT ALL

PANEL JOINS

25mm HIGH CONCRETE

PLINTH

10mm GAP BETWEEN PANEL

AND CONCRETE - SLOPE

CONCRETE OUT

STO uPVC

VENTED BASE

CAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

POST DETAIL

PP 309

2014

Page 39: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

100mm min.

SCALE 1:5

FLASHING TAPE

STAR CUT

CUT LINES

8/10mm SEALANT BEAD ON PEF ROD

BETWEEN PIPE AND PLASTER

PIPE OR OTHER PENETRATION

SLOPED DOWNWARDS

TIMBER

FRAMING TO

NZS3604

POREN PANEL

STO PLASTER

SYSTEM

STO THERM 20mm VH

CAVITY BATTEN

WALL UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PIPE PENETRATION DETAIL

PP 350

2014

Page 40: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

NOTE: LIGHTS AND LIGHT WEIGHT FITTINGS CAN BE FIXED

USING MASONRY FIXINGS WITH 40mm MIN. EMBEDMENT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

LIGHT FITTING/FIXING DETAIL

PP 351

2014

Page 41: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TAP FITTING ON EPDM

RUBBER WASHER

PROVIDE TIMBER

BLOCKING AT TAP

WALL UNDERLAY

STOTHERM 20mm VH

CAVITY BATTENS

STOPOREN PLASTER

SYSTEM

POREN PANEL

FLASHING TAPE

100mm ONTO UNDERLAY

25mm ONTO TAP CONNECTION

MS SEALANT

AROUND TAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TAP FITTING/FIXING DETAIL

PP 352

2014

Page 42: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER PACKER AT FIXINGS

POINTS - SLOPED AT 5

DEGREES min. 50mm

CLEARANCE FROM CAVITY

BATTENS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HANDRAIL BRACKET/FIXING DETAIL

PP 353

2014

Page 43: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

POLY WEDGE OR BATTENFULL WIDTH OF METER BOX

AT min. 10° SLOPE WITHFLASHING TAPE OVER.

EXTEND WEDGE 100mmPAST SIDE OF METER BOX

LEAVE min. 50mm GAP IN CAVITYBATTEN FOR DRAINAGE

STO JOINT SEALTAPE OR PEF ROD

STO THERM 20mm VH CAVITYBATTENS TO BE 8mm FROM

SIDES OF METERBOX

POREN PANEL

SCALE 1:10

FLEXIBLE FLASHING TAPE 50mmOUT OVER THE METERBOX

PERIMETER ALL AROUND AND100mm ONTO UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

METERBOX - ISOMETRIC

PP 354

2014

Page 44: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

WEDGE OR BATTENSLOPED AT 10° MIN.WITH

BOTTOM EDGEEXTENDING INTO CAVITY

88

INTERNAL LINING

TIMBER FRAMINGTO NZS3604

INTERNAL LINING

TIMBER FRAMINGTO NZS3604

MS SEALANT OVER STO JOINT SEALTAPE TO PERIMETER OF METERBOX

STO POREN PLASTERSYSTEM

STO THERM 20mm VH CAVITYBATTEN WITH 50mm GAP FROMHORIZONTAL SLOPED BATTEN

AT JUNCTION

8mm AIRSEAL ONPEF ROD BYBUILDER

8mm AIRSEAL ONPEF ROD BYBUILDER

FLASHING TAPE OVER SLOPEDPOLY WEDGE OR BATTEN ONTO

WALL UNDERLAY

PRIME PANEL EDGESSTOPLEX W SEALER

METERBOX FLASHING TAPED 50mmONTO BOX AND 100mm ONTO WALLUNDERLAY ALL ROUND

STO 6mm PRE MESHEDFINISHING EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

METERBOX - CROSS SECTION

PP 355

2014

Page 45: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

uPVC OR OTHER

DOWNPIPE -

SIZE REFER

NZBC E1 Table 5

STO THERM 20mm VH

CAVITY BATTENS

DOWNPIPE/CLIP -

SADDLE @ 1.2M

CTRS MAX.

MS SEALANT ALL AROUND

CABLE/WIRING

PVC CONDUIT SLEEVE INSTALLED

AT 5 DEGREES DOWNWARD

SLOPE TO MESH COAT

1. DOWNPIPE/CLIP - SADDLE DETAIL

2. WIRING PENETRATION DETAIL

NOTE: ENSURE THE AMOUNT OF PENETRATIONS THROUGH THE

SYSTEM IS KEPT TO A MINIMUM. THE WEATHERSEALING OF ALL WIRING,

ETC AS SHOWN, IS THE RESPONSIBILITY OF THE APPLICABLE TRADE

STOPOREN PLASTER

SYSTEM

STO THERM 20mm VH

CAVITY BATTENS

STO POREN PANEL

STOPOREN PLASTER

SYSTEM

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

DOWNPIPE SADDLE FIXING & WIRING DETAILS

PP 356

2014

Page 46: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

EXTRACTION PIPE SLOPEDOWNWARDS AT MINIMUM 5°

FAN

CO

VE

R

TIMBER BLOCKING ASREQUIRED

NOTE:LEAVE 40mm DRAINAGE GAP IN SEALANT AT BOTTOM OF FAN COVER.INSTALL FLASHING TAPE 100mm AROUND PIPE ONTO WALL UNDERLAY AND WRAP25mm ROUND PIPE.FOR FLEXIBLE PIPES, TAPE PIPE TO FAN COVER, APPLY STO JOINT SEAL, TAPEAROUND TAPE BEFORE PLACING IN HOLE. ALWAYS FINISH PLASTER BEFOREINSTALLING FAN COVER

TIMBER FRAMING ASPER NZS 3604

STO THERM 20mm VHCAVITY BATTENS

STO POREN PANEL

STOPOREN PLASTERSYSTEM

TIMBER BLOCKING ASREQUIRED

FLEXIBLE FLASHINGTAPE

MS SEALANT TO HEAD &SIDES

MS SEALANT/PEF RODAT PIPE JUNCTION (STOSEAL TAPE ON FLEXIBLEPIPES)

FLEXIBLE FLASHINGTAPE

STO uPVC 6mmFINISHING EDGE

STO uPVC 6mmFINISHING EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FAN VENT DETAIL

PP 357

2014

Page 47: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

PREMESHEDARCHITECTURAL PROFILEOVER INTERSTOREY JOINTFIXED OVER MESH COAT

STOPOREN PLASTERSYSTEM

SCALE 1:2

TIMBER FRAMINGTO NZS 3604

A: INTERSTOREYPANEL JOINT

CENTRED 1/3 WAYDOWN FROM TOP

OF JOIST

NOTE:1. VERTICAL CAVITY BATTENS AREINSTALLED WITH A 15mm GAP ATINTER-STOREY JOINT2. INSTALL STO uPVC 12mm CONTROL JOINT3. ONLY SUITABLE FOR 2 STOREY - REFERDRAWING SHEET PP359 FOR THIRD STOREY4. ENSURE THERE ARE NO FIXINGS INTOFLOOR JOIST

A15

WALL UNDERLAY - ENSUREUNDERLAY RUNSCONTINUOUS OVER JOINT

min.10°FALL

STO POREN PLASTERSYSTEM

5mm GAP

10°

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENPLASTER SYSTEM

STO POREN PANEL CLADDING SYSTEM

INTER-STOREY JUNCTION WITH POLY PROFILE

PP 358

2014

Page 48: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

STO POREN PLASTERSYSTEM

SCALE 1:2

TIMBER FRAMINGTO NZS 3604

WALL UNDERLAY -ENSURE UNDERLAY RUNSCONTINUOUS OVER JOINT

STOPOREN PLASTERSYSTEM

1. AS REQUIRED TO LIMITCONTINUOUS CAVITYCONSTRUCTION TO TWOSTOREYS or 7 METERS.FLASHING BACK ANDFRONT COVER TO BE AMINIMUM 35mmEXCLUDING DRIP EDGES

2. IN EXTRA HIGH WINDZONES INCREASEFLASHING COVER TO60mm AND USE A RIGIDUNDERLAY

STO THERM 20mm VHDRAINED CAVITYSTO POREN PANEL

INTER-STOREYFLASHING15°MIN.SLOPEAND 5mmMIN.GAP

ADDITIONAL WALLUNDERLAY DRESSED

OVER FLASHING5

STO VENTED BASE CAP

ATTACH WITH EPSSUITABLE ADHESIVE -TOPSIDE ONLY

STO POREN PLASTERMESHED BASECOATBEHIND PROFILE

PREMESHEDARCHITECTURALPROFILE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

JOINT AT THIRD STOREY WITH POLY PROFILE

PP 359

2014

Page 49: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

1. FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERYOPENINGS AS PER E2/AS1 DETAILS

2. STO UPVC CAVITY VENTED HEAD FLASHING CAN BE USEDWHERE A PLASTERED HEAD IS DETAILED - REFER DWG PP 401

3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO60mm MIN.AND USE A RIGID UNDERLAY

SCALE 1:2

TIMBER LINTEL ASPER NZS 3604

STO POREN PLASTERSYSTEM

STO THERM 20mm VHCAVITY BATTEN

WALL UNDERLAY

FLASHING TAPE ONTOWALL UNDERLAY

STO POREN PANEL

ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES

35m

m M

IN.

50m

m

ALUMINIUM WINDOWJOINERY

INTERIOR LINING

AIRSEAL ON PEFROD GAP

7.5-8mm APPROX

5

STO uPVC VENTEDBASE CAP

STO POREN PANELFIXING

HEAD FLASHING WITH 10mmSTOPENDS POSITIONED10mm PAST WINDOW JAMBS

STO STICK ON JAMBFLASHING FINISH AT HEADFLASHING WITH PUNCHEDPLASTER LEG CONTINUING30mm ABOVE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALU.JOINERY - HEAD DETAIL - STICK ON JAMB

PP 400

2014

Page 50: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER LINTEL ASPER NZS 3604

STO POREN PLASTERSYSTEM

STO THERM 20mm VHCAVITY BATTEN

WALL UNDERLAY

FLASHING TAPE ONTOWALL UNDERLAY

STO POREN PANEL

ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES

35m

m M

IN.

50m

m

ALUMINIUM WINDOWJOINERY

INTERIOR LINING

AIRSEAL ON PEFROD GAP

7.5-8mm APPROX

1. FLASHING TAPE SYSTEM TO BEINSTALLED AROUND JOINERYOPENINGS AS PER E2/AS1 DETAILS.

2. THE ALUMINUM WINDOW HEADFLASHING BUTTS INTO THE STOCAVITY JAMB TO PROVIDE STOPENDAFTER REMOVING THE JAMB TAB ANDFITTING TO JOINERY BEFORE FITTINGWINDOW HEAD FLASHING TIGHT ANDMS SEALANT THE JUNCTIONS - SEEDETAIL PP402

3. IN EXTRA HIGH WIND ZONESINCREASE FLASHING COVER TO 60mmMIN.AND USE A RIGID UNDERLAY

STO uPVC MESHEDDRIP EDGE

STO POREN PANELFIXING

5

STO uPVC VENTEDHEAD FLASHING

STO CAVITY JAMBFLASHING 30mm ABOVEHEAD FLASHING FLASHINGTO FORM STOPENDS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALU.JOINERY - HEAD DETAIL - CAVITY JAMB

PP 401

2014

Page 51: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

NOTE: OPENINGS OVER 600mm REQUIRE JOINERY SUPPORT BAR USE STO uPVC STICK ON JOINERY FLASHING WITH WANZ JOINERY SUPPORT BAR

JOINERY SUPPORT MUST BE CUT 15mm SHORT OF JOINERY JAMBS TO ALLOW FOR STO uPVC FLASHINGS1. SEALANT IS APPLIED TO THE SILL AND JAMB FLASHINGS2. WINDOW HEADS ARE LEFT OPEN3. FLEXIBLE FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1 DETAILS

WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.

JOINERY SUPPORT BARREQUIRE FOROPENINGS OVER 600mm

PROPRIETARYALUM.WINDOWJOINERY

MS SEALANT

STOPOREN PLASTERSYSTEM

STO POREN PANEL

TIMBER FRAMINGTO NZS 3604

AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

WALL UNDERLAY RETURNED INTOOPENINGS & FLASHING TAPE

CONTINUOUS ALONG SILL MIN 100mm UPJAMBS & 50mm ONTO FACE OF WALL

UNDERLAY

STOPOREN FIXING

STO THERM 20mm VHCAVITY BATTEN

STO uPVC STICK ON JOINERYFLASHING FLASHING ADHESIVE FIXTO PANEL AT min.15° SLOPE

STO PRE-MESHEDADJUSTABLE CORNER

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALUMINIUM JOINERY - SILL DETAIL - OPT 1

PP 402

2014

Page 52: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE: JOINERY SUPPORT BAR REQUIRED ON OPENINGS OVER 600mm.1.SEALANT IS APPLIED TO THE SILL AND JAMBS2.WINDOW HEADS ARE LEFT OPEN3.FLEXIBLE FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1 DETAILS

WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.

SCALE 1:2

PROPRIETARYALUM.WINDOWJOINERY

MS SEALANT

STOPOREN PLASTERSYSTEM

STO POREN PANEL

TIMBER FRAMINGTO NZS 3604

AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

WALL UNDERLAY RETURNED INTOOPENINGS & FLASHING TAPE

CONTINUOUS ALONG SILL MIN 100mm UPJAMBS & 50mm ONTO FACE OF WALL

UNDERLAY

STOPOREN FIXING

STO THERM 20mm VHCAVITY BATTEN

STO uPVC FACE FIXED JAMB ANDSILL FLASHING ADHESIVE FIX TOPANEL AT 15° SLOPE

STO PRE-MESHEDANGLE

NOTE: ONLY SUITABLE FOR OPENINGS UNDER 600mmOR JOINERY WITHOUT JOINERY SUPPORT BARS

10 10mm MIN.COVER

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALU.JOINERY - SILL DETAIL - STO CAVITY SILL

PP 403

2014

Page 53: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

23 - 25m

m G

AP

10mm

20m

m C

AV

IT

Y B

AT

TE

N

+/- 3-5m

m T

O A

LLO

W

FO

R F

LA

SH

IN

G T

AP

ES

AT

JO

IN

ER

Y

ALUMINIUM

WINDOW JOINERY

MS SEALANT TO JAMBS

6

H1.2 PACKER TO

SUPPORT JOINERY

LINE OF HEAD FLASHING

OVER WITH STOPEND

WALL UNDERLAY RETURNED INTO

RECESS WITH FLASHING TAPE

SYSTEM. FLASHING TAPE RETURNED

min 100mm UP JAMBS AS PER E2/AS1

STOPOREN PLASTER

SYSTEM

STO POREN PANEL

STOPOREN FIXING

STO THERM 20mm VH

CAVITY BATTEN

STO uPVC CAVITY JAMB

AND SILL FLASHING

STO PRE-MESHED

ANGLE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALU.JOINERY - JAMB DETAIL - STO uPVC CAVITY JAMB

PP 404

2014

Page 54: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE: INSTALL STOPOREN JOINERY FLASHING DURING POREN PANEL CONSTRUCTION

SCALE 1:2

23 - 25m

m G

AP

10mm

20m

m C

AV

IT

Y B

AT

TE

N

+/- 3-5m

m T

O A

LLO

W

FO

R F

LA

SH

IN

G T

AP

ES

AT

JO

IN

ER

Y

ALUMINIUM

WINDOW JOINERY

MS SEALANT TO JAMBS

6

H1.2 PACKER TO

SUPPORT JOINERY

LINE OF HEAD FLASHING

OVER WITH STOPEND

WALL UNDERLAY RETURNED INTO

RECESS WITH FLASHING TAPE

SYSTEM. FLASHING TAPE RETURNED

min 100mm UP JAMBS AS PER E2/AS1

STOPOREN PLASTER

SYSTEM

STO POREN PANEL

STOPOREN FIXING

STO THERM 20mm VH

CAVITY BATTEN

STO uPVC STICK ON JOINERY

FLASHING

STO PRE-MESHED

ANGLE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ALU.JOINERY - JAMB DETAIL - STO uPVC STICK ON JAMB

PP 405

2014

Page 55: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

MS SEALANT TO JAMBS

SCALE 1:2

TIMBER FRAMING

TO NZS 3604

20

STO UPVC CAVITY JAMB AND

SILL FLASHING

APPLY WS 205 SEALER

BEFORE PLASTERING

STO POREN FIXING

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

POREN PLASTER SYSTEM

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CNR ALU.WINDOW/DOOR JOINERY - JAMB DETAIL

PP 406

2014

Page 56: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

SILL SUPPORT BAR

REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .

GROUND LEVELS 150mm MIN.FROM TOP OF FINISHED FLOOR COVERING TO

PAVED GROUND

100

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ENTRY DOOR THRESHOLD DETAIL

PP 407

2014

Page 57: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10

MIN.THRESHOLD 100mm FROM FLOOR TO FINISHED DECK

NOTE: ADJUST 35mm TO ALLOW FOR SELECTED TILES AS REQUIRED, UNDER

DOOR TRIM BY BUILDER

100

35

SELECTED FLOORING

TURN-UP FLASHING

TAPE 100mm MIN. AT

TRIMMER STUDS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ENTRY DOOR/DECK THRESHOLD DETAIL

PP408

2014

Page 58: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

WANZ SUPPORT BAR COMPLETE WITH

VENTILATION/DRAINAGE HOLES,

INSTALLED TO MANUFACTURERS

RECOMENDATIONS

100

8

REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .

150mm MIN. FROM TOP OF FFL COVERING TO PAVED GROUND

LINE OF STO POREN

CLADDING SYSTEM BEYOND

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

BIFOLD DOOR/THRESHOLD DETAIL

PP 409

2014

Page 59: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

DRAINAGE CHANNEL

FALL ALONG LENGTH

TO OUTLET

100

NOTE

REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10

150

12

12m

m M

AX

.

200mm MIN.

WANZ SUPPORT BAR WITH

VENTILATION/DRAINAGE HOLES

INSTALLED TO MANUFACTURERS

RECOMMENDATIONS

UNDER DOOR TRIM BY BUILDER

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

LEVEL ENTRY THRESHOLD DETAIL

PP 410

2014

Page 60: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

1. CHECK GARAGE DOOR SPECIFICATIONS FOR INTERNAL CORNER REQUIREMENTS\2. SEAL FLASHING FOR VERY HIGH or EXTRA HIGH

WIND ZONES3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING

COVER TO 60mm MIN.AND USE A RIGID UNDERLAY

TIMBER LINTEL ASPER NZS 3604

10

5

WALL UNDERLAY

ADDITIONAL LAYER OFFLASHING TAPE LAPPED

OVER HEAD FLASHING

20mm DRAINED CAVITY

STO uPVC VENTED BASECAP

ALUMINIUM HEADFLASHING WITH 15°

SLOPE AND 10mm COVER

MIN. 5mm GAP REQUIRED

POREN PANEL

STO POREN PLASTERSYSTEM

STO POREN PANELFIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GARAGE DOOR - TIMBER HEAD

PP 411

2014

Page 61: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

WALL UNDERLAY

CONTINUOUS

AROUND CORNERS

TIMBER FRAMING

TO NZS 3604

STO POREN PLASTER

SYSTEM

6

MS SEALANT ON

STO JOINT SEAL

TAPE OR PEF ROD

POREN PANEL

SELECTED GARAGE DOOR

GARAGE DOOR TRIM

10

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GARAGE DOOR TIMBER JAMB

PP 412

2014

Page 62: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

5mm MIN.GAP

STO uPVC ADJUSTABLE

FOOT TRAY - BASE

STO uPVC ADJUSTABLE

FOOT TRAY - FRONT ORSTO VENTED BASED CAP

POREN PANEL

STOPOREN

PLASTER SYSTEM

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GARAGE DOOR - PLASTER HEAD DETAIL

PP 413

2014

Page 63: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO POREN PLASTER

SYSTEM

STOTHERM 20mm VH

CAVITY BATTEN

POREN PANEL

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GARAGE DOOR - PLASTER JAMB DETAIL

PP 414

2014

Page 64: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

CARRY MESH/PLASTERUP TO TOP EDGEWALL UNDERLAY CONTINUOUSOVER TOP OF WALL FRAME

POREN PANEL

STO POREN PLASTERSYSTEM

20mm DRAINEDCAVITY

PROVIDE SEPARATION (ROOFUNDERLAY) UNDER METAL

CAPPING AND 9mm MIN.H3 PLY -PACKED TO A FALL

PRE FINISHED METAL CAPPINGTO PARAPET WITH 5° MIN.FALL

Z Z

REFER TABLE 7- E2/AS1

POREN FIXING

1. INSTALL METAL SADDLE FLASHING AT WALL JUNCTION2. ENSURE TOP IS TEMPORARILY WATERPROOFED BEFORE COMMENCING PLASTERING3. METAL CAPPING EXCLUDING DRIP EDGE MUST OVERLAP SHEET BY

50mm MIN.IN LOW, MED or HIGH WIND ZONE,70mm MIN.IN VERY HIGH,90mm MIN.IN EXTRA HIGH WIND ZONES

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PARAPET/METAL FLASHING DETAIL

PP 500

2014

Page 65: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

WALL UNDERLAY CONTINUOUSOVER TOP OF WALL FRAME

POREN PANEL

STO POREN PLASTERSYSTEM

20mm DRAINEDCAVITY

POREN FIXING

NOTE:STO FLEXYL MESHED WATERPROOFING MEMBRANE HAS BEENTESTED BY BRANZ TO MEET THE REQUIREMENTS OF AS/NZS4858

WATERPROOF MEMBRANE AS REQUIRED BY E2/AS1

EXTRA HIGH WIND ZONES REQUIRE A RIGID UNDERLAY. FLASHINGMUST BE TAPED TO RIGID UNDERLAY

OVERLAY OF STO FLEXYL MEMBRANEUNDER MESH COAT TO TOP & SIDES,75mm MIN.DOWNTURN OVERLEVELITE BASE COAT

STO PREMESHED uPVC ADJUSTABLECORNERS

75

POREN CAP AT 10°OVERSEATS WALLS, GLUE TO

POREN WALL CLADDING

75

10°

H3.1 CAPPING PLATE CUT TO10° SLOPE WITH FLASHING

TAPE OR ROOFING UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PLASTERED PARAPET/BALUSTRADE DETAIL

PP 501

2014

Page 66: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

100mm MIN.

BALUSTRADE WALL UNDERLAY

LAPPED AROUND CORNER

FLASHING TAPE IN CORNERS

100x50mm MIN.

DRAIN FORMED IN

CORNER

100mm MIN.

STO POREN PLASTER

SYSTEM

STOTHERM 20mm VH

CAVITY BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PARAPET and/or ENCL.BALUSTRADE WALL JUNCTION - PLAN

PP 502

2014

Page 67: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

WALL UNDERLAYWALL FRAMING

DRAIN FORMED INCORNERCAVITY BATTENS

H3.1 CAPPINGPLATE CUT AT 10°SLOPE

FLEXIBLE FLASHING TAPE DRESSEDUP AND SECURELY ADHERED TO WALLUNDERLAY AT REAR OF CAVITYCONTINUE FLASHING TAPE OR ROOFUNDERLAY OVER H3.1 CAPPING PLATE

NOTE: POREN PANEL CAP TO BE POSITIONEDUNDER WALL 10mm OFF FRAMING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FLEXIBLE FLASHING INSTALL - ISOMETRIC

PP 503

2014

Page 68: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

2 LINES OF

SEALANT

1

0

0

m

m

M

I

N

.

5

0

m

m

M

I

N

.

50

mm

M

IN

.

A. SADDLE FLASHING B. PARAPET CAP

METAL PARAPET CAP

FLASHING

RIVET THROUGH TOP OF CAP TO

SADDLE FLASHING. MS SEALANT

TO RIVETS

EXTENT OF SADDLE FLASHING

8mm EXPANSION GAP BETWEEN

PARAPET CAP AND SADDLE

FLASHING - USE MS SEALANT

NOTE: SADDLE FLASHING INSTALLED AFTER CAVITY

SYSTEM. 50x50mm INTERNAL CNR FLASHING FROM

BEHIND SADDLE EXTENDED TO BOTTOM OF WALL

PANELS ON EACH BUILDING FACE

STO 20mm VH CAVITY

BATTENS

PLACE CAP FLASHING OVER

SADDLE FLASHING - REFER TO

E2/AS1 FIGURE 12 FOR CAP FIXING

DETAILS.

H3.1 CAPPING PLATE CUT TO A

FALL WITH FLASHING TAPE OR

ROOFING UNDERLAY

WALL UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENPANEL

STO POREN PANEL CLADDING SYSTEM

METAL SADDLE FLASHING & CAP INSTALL

PP 504

2014

Page 69: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

NOTE:APPLY STOFLEXYL MESHED WATERPROOFING OVER BASECOATSTOFLEXYL MESHED WATERPROOFING HAS BEEN TESTED BY BRANZ TO MEET THEREQUIREMENTS OF AS/NZS4858 FOR A WATERPROOFING MEMBRANE AS REQUIREDBY E2/AS1

OVERLAY OF STOFLEXYLMEMBRANE UNDER MESH COAT TOTOP & SIDES 75mm MIN.DOWNTURNOVER LEVELITE BASE COATLEVELLITE BASECOATPLASTER

STO 20mm VH CAVITYBATTEN

FLASHING TAPE ORROOF UNDERLAY OVERH3.1 CAPPING PLATEH3.1 TIMBER CAPPING PLATECUT TO A FALL - MIN.10°

75

WALL UNDERLAYWALL FRAMING

POREN PANEL CAP

WALL UNDERLAY

STO 20mm VH CAVITYBATTENS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

STOFLEXYL MESHED SADDLE FLASHING - ISOMETRIC

PP 505

2014

Page 70: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

NOTE:APPLY STOFLEXYL MESHED WATERPROOFING OVERBASECOATSTOFLEXYL MESHED WATERPROOFING HAS BEEN TESTED BYBRANZ TO MEET THE REQUIREMENTS OF AS/NZS4858 FOR AWATERPROOFING MEMBRANE AS REQUIRED BY E2/AS1

75E2/AS1 REQUIRES BALCONY &PARAPET WALLS TO BE OFFSETFROM MAIN WALL PLAIN TOALLOW FOR SADDLE FLASHINGS

BASECOAT PLASTER,STOPOREN CAP OVER H3.1TIMBER CAPPING PLATE

10° FALL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

STO FLEXYL MESHED WATERPROOFING CAP

PP 506

2014

Page 71: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

POREN PANELSTO POREN PLASTERSYSTEM

20mm DRAINEDCAVITY

10°

NOTE:

HANDRAIL REQUIRED WHERE BALUSTRADE IS UNDER 1000mm

10150

35

STO uPVC VENTEDBASE CAP

20mm MIN.ANGLE FILLET

FULLY SUPPORTEDMEMBRANE UPSTAND

10° MIN.FALL TO TOP OFPARAPET

POREN PANELSTO POREN PLASTER

SYSTEM

WALL UNDERLAY CONTINUOUSOVER TOP OF WALL FRAME

STOTHERM 20mm VHCAVITY BATTEN

H3.1 TIMBER CAPPING PLATE -CUT TO 10° SLOPE WITH

FLASHING TAPE OR ROOFINGUNDERLAY OVER

STO PREMESHED PVCADJUSTABLE CORNER ANGLESOVERLAY OF STO FLEXYLMEMBRANE UNDER MESHCOAT TO TOP & SIDES, 75mmMIN.DOWNTURN OVER BASECOAT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO POREN SYSTEM

STO POREN PANEL CLADDING SYSTEM

BALUSTRADE ENCLOSED DECK DETAIL

PP 507

2014

Page 72: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

NOTE: - 100mm MIN. FROM FLOOR LEVEL FOR ENCLOSED DECKS

- MIN.FALLS: 1:40 FOR DECKS, 1:30 FOR ROOFS & 1:100 FOR

GUTTERS

- ALLOW FOR TILES IF REQUIRED

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ENCLOSED DECK DETAIL

PP 508

2014

Page 73: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

35

STOPOREN PLASTER SYSTEM

6mm STO uPVC FINISHING

EDGE, SEAL END PANEL WITH

S PROTECT WS 205

20mm DRAINED CAVITY

STO JOINT SEAL TAPE & MS

SEALANT TO TOP AND SIDES

LINE OF CANTILEVER JOIST -

SHOWN DASHED

SOLID BLOCKING

BETWEEN JOISTS

5mm MIN. GAP BETWEEN

STOPOREN PLASTER SYSTEM

AND SADDLE FLASHING

5

35

MIN

.C

OV

ER

12mm MAX.DRAINAGE

CONTINUOUS INTER-STOREY

FLASHING

LINE OF CLADDING BETWEEN

JOISTS - SHOWN DASHED,

CUT AROUND JOIST

NOTE:REFER E2/AS1 Fig.16 FOR FLASHING REQUIREMENTS. PROVIDE 6-8mm

WIDE SEALANT JOINT AT CLADDING/SADDLE FLASHING JUNCTION.

50mm MIN. SET DOWN FROM FLOOR OR THRESHOLD FOR

CANTILEVERED SLATTED DECKS

12

5

STOPOREN PLASTER SYSTEM

6mm STO uPVC FINISHING

EDGE, SEAL END PANEL WITH

S PROTECT WS 205

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

CANTILEVERED SLATTED DECK

PP 509

2014

Page 74: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

CAVITY SPACERS TO SUIT

12

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

50

DECKING

DECK JOIST

FLOORING

FLOOR JOIST

WALL UNDERLAY

STO 20mm VH CAVITY

BATTEN

POREN PANEL FIXING

STO POREN PANEL

STO POREN PLASTER

SYSTEM

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

NON CANTILEVERED SLATTED DECK

PP 510

2014

Page 75: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

WALL UNDERLAY

20mm DRAINED CAVITY

STO POREN PLASTER SYSTEM

FLASHING TAPE 100mm ONTO WALL

UNDERLAY 25mm ONTO BRACKET

MS SEALANT ON STO

JOINT SEAL TAPE

GALVANIZED OR STAINLESS

STEEL L BRACKET ENGINEERED

FOR LOAD

LINE OF STO JOINT SEAL TAPE -

SHOWN DASHED

TIM

BE

R B

EA

M

NOTE: 'L' BRACKET ENGINEERED FOR LOAD. FLASHING TAPE TO

BUILDING UNDERLAY IN ACCORDANCE WITH E2/AS1 FIG. 68

POREN FIXING

12mm MIN.GAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER BEAM / PERGOLA DETAIL

PP 511

2014

Page 76: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

ENGINEERED TO SPECIFIC

STRUCTURAL REQUIREMENTS

GALVANIZED OR STAINLESS STEEL

'H' or 'U' BRACKET, SEAL BRACKET

WITH MS SEALANT OVER PEF ROD

TIMBER BEAM TO BE FIXED AFTER

PLASTERING COMPLETE

40

40mm GAP RECOMMENDED

(12mm MIN. GAP)

STO POREN PLASTER

SYSTEM

POREN PANEL

MS SEALANT OVER STO JOINT

SEAL TAPE BETWEEN POREN

PANEL AND BRACKET

FIXING CAPACITY AS PER

ENGINEER

POREN FIXING

STO POREN PLASTER

SYSTEM

POREN PANEL

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PARALLEL DECK JOIST BRACKET

PP 512

2014

Page 77: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

EPDM WASHERS REQUIRED AROUND

FIXINGS AND PLATE TO PROVIDE

WATERTIGHTNESS

RWH HEAD FIXED DIRECTLY ABOVE &

BELOW SCUPPER PENETRATION

PRE FINISHED 0.55MM BMT

STEEL CUSTOM FOLDED AND

RIVETED RAIN WATER HEAD

STOPLEX W SEALER & MS

SEALANT AROUND

OPENING/RHW

MEMBRANE DRESSED OVER 50x50mm

ALU.ANGLE REBATED INTO SUBSTRATE

50mm LIP

SECTION A - A

SELECTED MEMBRANE FINISH

OVER H3 "C" FACED PLYWOOD

LAID TO 1:60MIN.FALL. GLUE &

SCREW TO TIMBER JOISTS, ALL

EDGES SUPPORTED ON TIMBER

20mm MIN.ANGLE FILLET

OUTLET THROUGH WALL

LINE OF MEMBRANE

LAPPED 50mm MIN.BEHIND

WRAP UNDER CLADDING

DEBRIS SCREEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

RWH/SCUPPER OPENING

PP 513

2014

Page 78: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:10

VARIES

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FLAT SOFFIT/WALL JUNCTION

PP 600

2014

Page 79: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:10

H3.1 PRE PRIMED &

PAINTED FASCIA BOARD

VARIES

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

RAKING SOFFIT/WALL JUNCTION

PP 601

2014

Page 80: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:10

NOTE:

REFER TO E2/AS1 TABLE 1 FOR RISK LEVELS. EAVE FLASHINGSARE REQUIRED WHEN FASCIA IS 100mm OR LESS FROM WALLCLADDING AND ROOF PITCH IS LESS THAN 10°

H3.1 PRE PRIMED &PAINTED FASCIA BOARD

PREFINISHED METALROOFING OVER ROOFUNDERLAY

PREFABRICATED TRUSSTOP CHORD

50mm COVER TO CLADDINGWITH STO JOINT SEAL TAPE ORMS SEALANT ON PEF ROD

PRE FINISHED METAL E2 EAVES FLASHING,LAP 1300-200mm MAX. UNDER ROOFCLADDING, TURN DOWN INTO GUTTER

50

BLOCKING TO CLOSE OFF CAVITYFROM ROOF SPACE

WALL UNDERLAY20mm DRAINED CAVITYPOREN PANELSTO POREN PLASTERSYSTEM

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FACE FIXED FASCIA

PP 602

2014

Page 81: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

SELECTED FIBRECEMENT SOFFIT LINING

35

PREFINISHED METALROOFING OVER ROOF

UNDERLAY

STO POREN PLASTERSYSTEM

WALL UNDERLAY

POREN PANEL20mm DRAINED CAVITY

50x35mm MIN.METALFLASHING6mm MAX.GAP WITH MSSEALANT

NOTE:

MAX.ANGLE OF SOFFIT RESTRICTEDTO BETWEEN 91°-115°

50

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

RAKING SOFFIT

PP 603

2014

Page 82: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

SELECTED FIBRECEMENT SOFFIT LINING

5035

PREFINISHED METAL ROOFINGOVER ROOF UNDERLAY

STOPOREN PLASTERSYSTEM

WALL UNDERLAY

POREN PANEL20mm DRAINED CAVITY

STO uPVC JONERYCONNECTORFINISH WITH MS SEALANT

NOTE:

MAX.ANGLE OF SOFFIT RESTRICTEDTO BETWEEN 91°-115°

6

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

RAKING SOFFIT - STO uPVC CONTROL JOINT

PP 604

2014

Page 83: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO uPVC VENTED

BASE CAP

5mm MIN.GAP

FLASHING TAPE OVER

35mm MIN.HIGH BACK

FLASHING

STO uPVC CLIP ON TRAY

POREN PANEL

STOPOREN

PLASTER SYSTEM

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

SOFFIT TO CLADDING DETAIL

PP 605

2014

Page 84: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

FASCIA

BUILDING UNDERLAY/RAB

STO POREN PANEL SYSTEM

WITH STO uPVC FOOT TRAY

OR STO uPVC BASECAP

STO 20mm VH CAVITY

BATTEN

FLASHING TAPE OR

BUILDING UNDERLAY

OVER FLASHING

APRON FLASHING WITH TAPERED

STOPEND TO DIVERT WATER INTO

GUTTER. PANEL TO BE CAREFULLY

CUT OVER STOPEND, SEALED & MS

SEALANT JOINTED

APPLY MS SEALANT JOINT TO

FASCIA BOARD ON COMPLETION

STOP SPOUTING MIN.10mm

CLEAR OF FINISHED WALL

CLADDING

NOTE:BACK FLASHING IS REQUIRED BEHIND FACISA AND

PANEL JUNCTION 50mm MIN.COVER

SCALE 1:10

SOFFIT

50x50mm BACK FLASHING

BEHIND FASCIA & CLADDING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GUTTER/WALL JUNCTION

PP 606

2014

Page 85: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

SELECTED ALUMINIUM

WINDOW/DOOR JOINERY

TIMBER LINTEL AS

PER NZS 3604

100mm MIN.TO FACE OF CLADDING

SELECTED FIBRE CEMENT

SOFFIT LINING

18x18mm TIMBER BEAD AT

SOFFIT, PAINTED

LINE OF POREN PANEL CLADDING

BEYOND - SHOWN DASHED

PROVIDE AIRSEAL ON PEF

ROD GAP 7.5-8mm APPROX.

WALL UNDERLAY DRESSED

INTO OPENING AS PER

E2/AS1 DETAIL

varies

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

SOFFIT AT WINDOW/DOOR HEAD

PP 607

2014

Page 86: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

ROOF

STRUCTURE

20mm DRAINED CAVITY

POREN PANEL

75

35

R

E

F

E

R

E

2

/A

S

1

T

A

B

L

E

7

5

m

m

G

A

P

M

A

X

.

F

O

R

N

O

T

C

H

E

D

T

U

R

N

-D

O

W

N

STO POREN PLASTER SYSTEM

STO VENTED ADJUSTABLE

FOOT TRAY

POREN FIXING

ROOF UNDERLAY

CONTINUOUS TO TOP OF

FLASHING

STOPEND TO RUN 10mm

MIN.PAST CLADDING

PRE FINISHED METAL

APRON FLASHING

PREFINISHED METAL

ROOFING OVER UNDERLAY

SELECTED ROOF WRAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

APRON FLASHING

PP 700

2014

Page 87: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

75

35

ROOF STRUCTURE

20mm DRAINED CAVITY

POREN PANEL

STO POREN PLASTER SYSTEM

WALL UNDERLAY LAPPED

OVER APRON FLASHING

UPSTAND

REFER E2/AS1 TABLE 7

PORENFIXING

STO uPVC VENTED

ADJUSTABLE FOOT TRAY

APRON FLASHING WITH TAPERED

STOPEND TO DIVERT WATER IN

GUTTER. CLADDING TO BE CAREFULLY

CUT OVER STOPEND & SEALED

NOTE: PROVIDE FLASHING STOPEND AT ROOF TO

GUTTER JUNCTION TO DIVERT WATER INTO THE

GUTTER - Refer Drawing PP606

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PARALLEL APRON FLASHING

PP 701

2014

Page 88: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

20mm DRAINED CAVITY

POREN PANEL

75

35

R

E

F

E

R

E

2

/A

S

1

T

A

B

L

E

7

5

m

m

G

A

P

M

A

X

.

F

O

R

N

O

T

C

H

E

D

T

U

R

N

-D

O

W

N

STO POREN PLASTER SYSTEM

STO VENTED ADJUSTABLE

FOOT TRAY

CAVITY CLOSER

PRE FINISHED METAL

APRON FLASHING

PREFINISHED METAL ROOFING

OVER UNDERLAY

SELECTED ROOF WRAP

POREN FIXING

ROOF UNDERLAY

CONTINUOUS TO TOP OF

FLASHING

NOTE: CONTRACTOR TO FIT STOPEND FLASHING & HEMMED

FLASHING FOR FASCIAS 50mm BEHIND CLADDING, 50mm BEHIND

FASCIA. STO CONTRACTOR TO APPLY FINISHED SEALANT JOINT

BETWEEN FASCIA & PLASTER. UNDERLAY or FLASHING TAPE OVER

FLASHING UPSTAND.

PARAPETS - REFER 500 SERIES - PARAPET DETAILS

50mm MIN.FASCIA BACK

FLASHING - SHOWN DASHED

STOPEND

FLASHING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERSTOREY TRANSVERSE (APRON) ROOF STOPEND

PP 702

2014

Page 89: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

STOP END 10mm PAST

FINISHED CLADDING

FASCIA 10mm SHORT OF

FINISHED CLADDING WITH MS

SEALANT JOINT

POREN PANEL

20mm DRAINED

CAVITY

STOPOREN PLASTER

SYSTEM

POREN FIXING

10

10

BACK FLASHING 50mm BEHIND

FASCIA & CLADDING

35

75

110

150

STO STICK ON CONNECTOR or MS

SEALANT JOINT ON PEF ROD

BETWEEN STOPEND AND CLADDING

ROOFING MEMBRANE OVER METAL

STOPEND. STOPEND TO EXTEND 10mm

MIN.PAST FINISHED WALL

ROOFING MEMBRANE 150mm

MIN.UPSTAND, 75mm

CLADDING COVER, CLADDING

35mm MIN. ROOF/DECK

110

35

75

150

1

0

I

F

M

E

M

B

R

A

N

E

I

F

R

O

O

F

F

L

A

S

H

I

N

G

C

L

A

D

D

I

N

G

R

O

O

F

/

D

E

C

K

NOTE: MEMBRANE ROOF NOT SHOWN ON

STOP END FOR CLARITY. STOP END

UNDER MEMBRANE OR IN CONJUNCTION

WITH ROOF APRON FLASHING

A = CAVITY & FINISHED CLADDING + 10mm

PRE FINISHED FABRICATED

STOP END

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO POREN SYSTEM

STO POREN PANEL CLADDING SYSTEM

INTER-STOREY DECK OR ROOF/STOPEND FLASHING

PP 703

2014

Page 90: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

10

FASCIA 10mm SHORT OF

CLADDING - MS SEALANT JOINT

FINISHED CLADDING & FASCIA

MS SEALANT ON PEF RODS

H3.1 PRE PRIMED & PAINTED

FASCIA/BARGE BOARD

PRE FINISHED METAL

FLASHING

FASCIA / CLADDING BACK

FLASHING 50mm MIN.COVER

0.55mm BMT PREFINISHED

METAL APRON FLASHING

STOPEND

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTER-STOREY ROOF STOPEND - PLAN VIEW

PP 704

2014

Page 91: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

100mm MIN.

75m

m50

mm

20mm DRAINED CAVITYSTO POREN PANELSTO POREN PLASTERSYSTEM

STO POREN FIXING

DRESS WALLUNDERLAY OVER

GUTTER LINING

SELECTED GUTTER LINING CARRIEDOVER ANTI-PONDING BOARD AND UPABUTMENT FRAME ON NOG TO SUIT

GUTTER BOARD AT ABUTMENTON NOGS TO SUIT

ANTI-PONDING BOARDLAID TO A 5° MIN.FALL

ROOF UNDERLAY CARRIEDDOWN OVER GUTTER LINING

MASONRY ROOFING TILE

SCALE 1:5

STO uPVC ADJUSTABLEFOOT TRAY

MIN. LAP

MIN.DEEP

STOTHERM LAPOVER UPSTAND.

FINISH 50mmMIN.ABOVE

GUTTER LINING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO POREN SYSTEM

STO POREN PANEL CLADDING SYSTEM

ROOF PENETRATION/GUTTER (Masonry Tile) DETAIL

PP 705

2014

Page 92: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

80mm MIN.80mm MIN.

20m

m M

IN

.

110m

m

NOTE: WHERE GUTTER FINISHES WITHIN THE LENGTH OF THE WALL, STEP LOWER PART OF

GUTTER OUT TO 10mm PAST THE CLADDING LINE, WHILE MAINTAINING REQ.CLEARANCES, TO

ALLOW THE GUTTER TO FEED INTO THE LOWER EAVES GUTTER.

- REFER NZBC E2/AS1 Fig: 50 Incl.Section 8.1.6.2

35m

m G

AP

75m

m M

IN

.C

OV

ER

MIN

.T

OT

AL

20mm DRAINED CAVITY

POREN PANEL

STO POREN PLASTER

SYSTEM

ADDITIONAL LAYER OF

FLASHING TAPE LAPPED

OVER GUTTER UP STAND

PORENFIXING

PRE FINISHED METAL GUTTER

STO uPVC VENTED BASE CAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

PARALLEL ROOF/HIDDEN GUTTER

PP 706

2014

Page 93: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

50/90mm LAP REFER NZBC,

TABLE 7 E2/AS1

H3.1 PRE PRIMED & PAINTED

FASCIA/BARGE BOARD

PRE FINISHED METAL

FLASHING

WALL UNDERLAY

20mm DRAINED CAVITY

POREN PANEL

STO POREN

PLASTER SYSTEM

6mm

MAX.GAP

MS SEALANT ON PEF ROD

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FACE FIXED FASCIA/BARGE

PP 707

2014

Page 94: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

SELECTED MEMBRANE FINISH OVER H3 "C" FACED

PLYWOOD LAID TO 1:60MIN.FALL. GLUE & SCREW TO

TIMBER JOISTS, ALL EDGES SUPPORTED ON TIMBER

MIN.5mm RADIUS

TO PLYWOOD

TAKE BOTH LAYERS 6mm PAST

S/S ANGLE TO FORM DRIP EDGE

PREFINISHED METAL SPOUTING

AND BRACKETS

50/90mm LAP REFER NZBC,

TABLE 7 E2/AS1

H3.1 PRE PRIMED & PAINTED

FASCIA/BARGE BOARD

MS SEALANT ON PEF ROD

WALL UNDERLAY

20mm DRAINED CAVITY

TIMBER FRAMING

TO NZS3604

CONTINOUS BATTEN TO

CLOSE OFF CAVITY

FROM ROOF SPACE

POREN PANEL

STO POREN PLASTER

SYSTEM

POREN FIXING

50m

m

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FACE FIXED FASCIA/MEMBRANE ROOF

PP 708

2014

Page 95: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

ROOF

STRUCTURE

PRE FINISHED METAL

FLASHING, TURN DOWN TO

SUIT PROFILE

PRE FINISHED METAL

ROOFING OVER

SELECTED ROOF UNDERLAY

50/90mm LAP REFER NZBC,

TABLE 7 E2/AS1

PRE FINISHED METAL

FLASHING, FIXED AT SIDE

ONLY

WALL UNDERLAY

20mm DRAINED CAVITY

POREN PANEL

STO POREN PLASTER SUSTEM

MS SEALANT ON PEF ROD

R

E

F

E

R

E

2

/A

S

1

T

A

B

L

E

7

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

ROOF/WALL RIDGE

PP 709

2014

Page 96: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

PENETRATION APRON FLASHINGHEM FOLD UNDER ROOFING

SEPARATE ROOFING SHEETOVER

MIN. UPSTAND 110mm

SIDE COVER= 2 CRESTS

SCALE 1:20FRAMED CHIMNEY

STOARMAT PLASTER SYSTEMWITH PREMESHED EXTERNAL CORNERS

H3.1 TIMBER CAVITY BATTENS

WALL UNDERLAY

FIBRE CEMENT SHEETWALL CLADDING

35mm GAP BETWEENCLADDING AND FLASHING

SET ONE CORNER OF UPSTANDHIGHER UP ROOF PLANE

TO PROVIDE CROSS FALL

250mm MIN.

110

35

130 - 200

130 - 200

COVER 130 - 200mm MAX.REFER TO E2/AS1 Table 7

110

NOTE:SUITABLE FOR RECTANGULAR PENETRATIONSUP TO 1200mm WIDE.ROOF PITCH MUST BE 10° or HIGHER - REFERTO E2/AS1 TABLE 9 or 17 FOR MAX.ROOFLENGTH ABOVE PENETRATIONS. BLOCKINGREQUIRED FOR PENETRATIONS OVER 200mm

UNDERLAY SEPARATORBETWEEN FLASHINGAND FRAMING. FRAMETO SUPPORT FLASHING

CAVITY CLOSER POSITIONEDTO GIVE 15mm MIN.DRIPEDGE TO CLADDING

7535

ROOF STRUCTURENZS 3604

Table 7 NZBC

LAP 250mm MIN.

PREFINISHED METAL ROOFINGOVER UNDERLAY

SELECTED ROOF WRAP

0.55mm BMT PREFINISHEDMETAL APRON FLASHING

STOARMAT PLASTER SYSTEMOVER 7.5 - 9mm FIBRE

CEMENT SHEET CLADDINGSTO CAVITY BATTEN

WALL UNDERLAY LAPSOVER FLASHING

CAVITY CLOSER POSITIONEDTO GIVE 15mm MIN.DRIP

EDGE TO CLADDING

STOARMAT PLASTER SYSTEMOVER 7.5 - 9mm FIBRECEMENT SHEET CLADDINGSTO CAVITY BATTEN

STO CLIP ON FINISHING EDGE

WALL UNDERLAY LAPSOVER FLASHING

STO uPVC CLIP ON FINISHINGEDGE

SCALE 1:10

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FRAMED CHIMNEY

PP 710

2014

Page 97: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

E2/AS1 COMPLIANT

FLASHING

5mm

50mm COVER

50m

m

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOTHERM 20mm VH

CAVITY BATTEN

STO uPVC END CAP TO

PANEL/MS SEALANT OVER

PEF ROD

NOTE: IF A TIMBER SCRIBER REQUIRED

EXTEND FLASHING ACCORDINGLY

POREN FIXING

SELECTED HORIZONTAL

TIMBER WEATHERBOARDS

OVER 20mm DRAINED CAVITY

STO uPVC 6mm

FINISHING EDGE

WALL UNDERLAY CONTINUOUS

AROUND CORNER

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER W'BOARD/STO POREN - OPT 1

PP 800

2014

Page 98: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

H3.1 SCRIBER TO SUIT

WEATHERBOARD PROFILE

SELECTED HORIZONTAL TIMBER

WEATHERBOARDS OVER 20mm

DRAINED CAVITY

FLASHING TAPE APPLIED TO

UNDERLAY MIN. 75mm WIDE

WALL UNDERLAY CONTINUOUS

AROUND CORNER

CNR BOARDS TO SUIT. ON

PANEL USE 2hr AAC

CONSTRUCTION GLUE, FIX

50mm S/S POZI DRIVE SCREWS

SCALE 1:5

STOPOREN PLASTER

SYSTEM

STOTHERM 20mm VH

CAVITY BATTEN

STO POREN PANEL

POREN FIXING

MS SEALANT

STO uPVC

FINISHING EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER WEATHERBOARD/STO POREN - OPT 2

PP 800-1

2014

Page 99: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

E2/AS1 COMPLIANT

FLASHING

5mm

50mm COVER

50m

m

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOTHERM 20mm VH

CAVITY BATTEN

STO uPVC END CAP TO

PANEL - MS SEALANT

NOTE: IF A TIMBER SCRIBER REQUIRED

EXTEND FLASHING ACCORDINGLY

POREN FIXING

BUILDING UNDERLAY

CONTINUOUS AROUND CORNER

STO uPVC 6mm FINISHING

EDGE

SELECTED HORIZONTAL

TIMBER WEATHERBOARDS -

DIRECT FIXED

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER WEATHERBOARD/STO POREN - DIRECT FIX

PP 801

2014

Page 100: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm MIN.

COVER

50m

m M

IN

.

CO

VE

R

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CORNER WEATHERBOARD/STO POREN - OPT 1

PP 802

2014

Page 101: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

NOTE: IF A TIMBER SCRIBER REQUIRED

EXTEND FLASHING ACCORDINGLY

E2/AS1 COMPLIANT

FLASHING

STOPOREN PLASTER SYSTEM

POREN PANEL

STOTHERM 20mm VH CAVITY BATTEN

S PROTECT WS 205 SEAL TO

END OF PANEL - MS SEALANT

POREN FIXING

SELECTED HORIZONTAL

TIMBER WEATHERBOARDS

OVER 20mm DRAINED CAVITY

STO uPVC 6mm FINISHING

EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CORNER WEATHERBOARD/STO POREN - OPT 2

PP 802-1

2014

Page 102: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

NOTE: IF A TIMBER SCRIBER REQUIRED

EXTEND FLASHING ACCORDINGLY

FLASHING TAPE APPLIED TO

UNDERLAY MIN. 75mm WIDE

WALL UNDERLAY CONTINUOUS

AROUND CORNER

MS SEALANT ON STO JOINT SEAL

TAPE or PEF ROD 6mm GAP MIN.

SELECTED HORIZONTAL TIMBER

WEATHERBOARDS - DIRECT FIXED

E2/AS1 COMPLIANT FOLDED

METAL FLASHING

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOTHERM 20mm VH

CAVITY BATTEN

S PROTECT WS 205 SEAL TO

END OF PANEL - MS SEALANT

POREN FIXING

STO uPVC 6mm FINISHING

EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CORNER WEATHERBOARD/STO POREN - DIRECT FIX

PP 803

2014

Page 103: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm MIN. 50mm MIN.

WALL UNDERLAY

SELECTED HORIZONTAL TIMBER

WEATHERBOARDS OVER 20mm

DRAINED CAVITY

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROD 6mm MIN.GAP

40x40mm PC ALUMINUM ANGLE

WITH MS SEALANT AT

WEATHERBOARD SEALANT

STOTHERM 20mm VH

CAVITY BATTEN

POREN PANEL

STOPOREN PLASTER SYSTEM

- STO uPVC END CAP

STO 6mm FINISHING EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT - WEATHERBOARD/STO POREN - OPT 1

PP 804

2014

Page 104: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

COVER

WALL UNDERLAY

SELECTED HORIZONTAL TIMBER

WEATHERBOARDS OVER 20mm DRAINED

CAVITY, SCRIBER TO SUIT PROFILE

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROAD 6mm MIN.GAP

E2/AS1 COMPLIANT TOP HAT

METAL FLASHING

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

STO POREN PLASTER SYSTEM WITH

6mm FINISHING EDGE. S PROTECT

WS 205 TO SEAL END PANEL

A

NOTE:A = CHECK WITH SHEET METAL FOLDER A

NARROW NECK MAY REQUIRE A WELDED

JOINT OR WIDER TOP HAT

COVER

50mm MIN. 50mm MIN.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT - WEATHERBOARD/STO POREN - OPT 2

PP 804-1

2014

Page 105: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROAD 6mm MIN.GAP

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

STO POREN PLASTER

SYSTEM/STO uPVC PANEL

END CAP & STO 6mm

FINISHING EDGE

50mm MIN.

50mm MIN.

COVER COVER

WALL UNDERLAY CONTINUOUS

SELECTED HORIZONTAL TIMBER

WEATHERBOARDS OVER 20mm DRAINED

CAVITY, SCRIBER TO SUIT PROFILE

E2/AS1 COMPLIANT BACK

FLASHING 50mm MIN.COVER TO

CLADDING

6

H3.2 REBATED TIMBER DIVIDING

POST

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT - WEATHERBOARD/STO POREN - OPT 3

PP 804-2

2014

Page 106: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

35m

m M

IN

.

5

35m

m M

IN

.

BEVEL-BACK TIMBER

WEATHERBOARDS TO NZS 3617

OVER 20mm DRAINED CAVITY

FLASHING TAPE LAPPED OVER

HEAD FLASHING

E2/AS1 COMPLIANT FLASHING

MIN. 5mm GAP

REQUIRED

CO

VE

RC

OV

ER

CAVITY CLOSER POSITIONED

TO GIVE 15mm MIN.DRIP

EDGE TO CLADDING

MS SEALANT OR STO JOINT

SEAL TAPE AS REQUIRED TO

PLASTER/FLASHING

POREN PANEL

STOPOREN PLASTER SYSTEM WITH 6mm

PRE MESHED FINISHING EDGE. SEAL

PANEL END WITH S PROTECT WS 205

20mm DRAINED CAVITY

TIMBER FILLET TO SUIT

1. IN EXTRA HIGH WIND ZONES

INCREASE FLASHING COVER TO 60mm

MIN.AND USE A RIGID UNDERLAY

1. IN EXTRA HIGH WIND ZONES

INCREASE FLASHING COVER TO 60mm

MIN.AND USE A RIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZONTAL JUNCTION WEATHERBOARD/STO POREN

PP 805

2014

Page 107: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

35m

m M

IN.

CO

VE

R35

mm

MIN

.C

OV

ER

POREN PANEL

STO POREN PLASTERSYSTEM WITH STO 6mmPREMESHED FINISHINGEDGE. SEAL END PANELWITH S PROTECT WS 205

20mm DRAINED CAVITY

POREN FIXING

BEVEL-BACKTIMBERWEATHERBOARDSOVER 20mmDRAINED CAVITY

FLASHING TAPELAPPED OVER HEADFLASHING

CAVITY CLOSERPOSITIONED TO GIVE15mm MIN.DRIP EDGETO CLADDING

RIGID AIR BARRIERTO GABLE END

H3.1 CONTINUOUSHORIZONTALTAPERED PACKERBEHIND CAVITYCLOSER TORESTRICT AIRFLOW

ALU.INTER-STOREYFLASHING,STOPEND, 15° SLOPE& 35mm MIN.COVERMS SEALANT TOPLASTER/FLASHING

1. IN EXTRA HIGH WINDZONES INCREASEFLASHING COVER TO60mm MIN.AND USE ARIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

GABLE END - WEATHERBOARD/STO POREN

PP 806

2014

Page 108: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

6mm WIDE MS

SEALANT JOINT OVER

STO JOINT SEAL TAPE

OR PEF ROD

SELECTED 70 SERIES

CLAY BRICK VENEER

40mm MIN.CAVITY

10

STO 6mm

PREMESHED

FINISHING EDGE. STO

uPVC END CAP TO

PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXTERNAL CORNER BRICK VENEER/STO POREN

PP 810

2014

Page 109: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

SELECTED 70 SERIES CLAY BRICK

VENEER 40mm MIN.CAVITY

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

STO POREN PANEL

STOPOREN PLASTER SYSTEM WITH STO

6mm PREMESHED FINING EDGE & STO

uPVC END CAP TO PANEL

STO THERM 20mm VH

CAVITY BATTEN

TIMBER FRAMING

TO NZS 3604

E2/AS1 COMPLIANT FLASHING, HEM TO

BOTH ENDS

50m

m M

IN

.

CO

VE

RC

OV

ER

50m

m M

IN

.

6mm WIDE MS SEALANT OVER STO

JOINT SEAL OR PEF ROD

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CNR BRICK VENEER/STO POREN - OPT 1

PP 811

2014

Page 110: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

6mm WIDE MS SEALANT OVER

STO JOINT SEAL TAPE

SELECTED 70 SERIES CLAY BRICK

VENEER 40mm MIN.CAVITY

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

STO THE5RM 20mm VH

CAVITY BATTEN

STO POREN PLASTER SYSTEM WITH

STO 6mm PREMESHED FINISHING EDGE

& S PROTECT WS 205 TO SEAL END OF

PANEL

POREN PANEL

TIMBER FRAMING

TO NZS 3604

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CNR BRICK VENEER/STO POREN - OPT 2

PP 812

2014

Page 111: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

SELECTED 70 SERIES CLAY BRICK

VENEER WITH 40mm MIN.CAVITY

50mm MIN. 51mm MIN.

COVER COVER

E2/AS1 COMPLIANT

BACK FLASHING

6mm WIDE MS SEALANT OVER

STO JOINT SEAL TAPE

STO THE5RM 20mm VH

CAVITY BATTEN

STO POREN PLASTER SYSTEM WITH STO

6mm PREMESHED FINISHING EDGE & STO

uPVC END CAP TO PANEL

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JUNCTION - BRICK VENEER/STO POREN

PP 813

2014

Page 112: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

20mm DRAINED CAVITY

STOPOREN PLASTERSYSTEM

SILL 15° SLOPE OVERHANG30-50mm. FINISH ENDS WITH

BRICK SILL OR SLIP

VENT EVERY THIRDPERPEND

BRICK TIES

20

10mm

GAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZ.JUNCTION - BRICK VENEER/STO POREN

PP 814

2014

Page 113: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CNR FC SHEET/STO POREN

PP 820

2014

Page 114: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

INSTALL FIBRE CEMENT SHEET AND SEAL BEFORE POREN PANEL CLADDING.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL.CORNER F C SHEET/STO POREN - OPT 1

PP 821

2014

Page 115: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO POREN PLASTER

SYSTEM

STO THERM 20mm VH

CAVITY BATTEN

STO uPVC PRE MESHED FINISHING

EDGE & STO uPVC BASE END

MS SEALANT OVER STO JOINT

SEAL TAPE or PEF ROD

STOARMAT PLASTER SYSTEM/FIBRE

CEMENT SHEET OVER 20mm DRAINED

CAVITY/STO uPVC FINISHING EDGE

WALL UNDERLAY CONTINUOUS

AROUND CORNER

ALLOW TO INSTALL 50x50mm

BACK FLASHING

STO POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL.CORNER F C SHEET/STO POREN - OPT 2

PP 822

2014

Page 116: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

TIMBER FRAMING

TO NZS 3604

INTERIOR LINING

FLOORING

DIRECT FIXED FIBRE

CEMENT SHEET

STOARMAT PLASTER SYSTEM

FRAMED SUBFLOOR

WALL/BASEMENT

NOTE: FRAMED SUBFLOOR WALL OR BASEMENT -

NOT SUITABLE AS A WALL CLADDING WHERE E2/AS1

RISK MATRIX IS ABOVE 6

50m

m

SCALE 1:5

STO uPVC VENTED

BASE CAP

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FC SHEET - FRAMED SUB FLOOR CLADDING

PP 823

2014

Page 117: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO POREN PANEL

STO POREN

PLASTER SYSTEM

20mm DRAINED

CAVITY

STOARMAT uPVC

CLIP ON FOOT

RIGID AIR BARRIER

TO GABLE END

SELECTED FIBRE

CEMENT SHEET TO

GABLE END -

STOARMAT

PLASTER SYSTEM

FLASHING TAPE

50mmMIN.ONTO

PANEL & UNDERLAY

H3.1 CONTINUOUS

HORIZONTAL

PACKER BEHIND

CAVITY CLOSER TO

RESTRICT AIRFLOW

25m

m

flash.

40m

m cover

cladding

35m

m

CO

VE

R

5mm MIN.GAP

STO uPVC 6mm

FINISHING EDGE

E2/AS1 COMPLIANT

METAL FLASHING

1. IN EXTRA HIGH WIND ZONES INCREASE

FLASHING COVER TO 60mm MIN.AND USE

A RIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENPLASTER SYSTEM

STO POREN PANEL CLADDING SYSTEM

FIBRE CEMENT SHEET GABLE END

PP 824

2014

Page 118: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

POREN PANEL

STO POREN

PLASTER SYSTEM

20mm DRAINED

CAVITY

50m

m M

IN

.

CO

VE

R

USE POLY PACKER

TO FORM GAP, STO

uPVC CONTROL JOINT

WITH MS SEALANT IN

STOARMAT CLASSIC

MESH

E2/AS1 COMPLIANT

BACK FLASHING

CHASED INTO

CONC.BLOCK

DPC

10

20

6

S PROTECT WS 205

TO SEAL END PANEL

STO THERM 20mm

VH CAVITY BATTEN

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CNR CONC.BLOCK/STO POREN

PP 830

2014

Page 119: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO S - PROTECT COATING SYSTEM FOR CLEAR FINISHED CONCRETE BLOCK

POREN PANEL

STO POREN PLASTER SYSTEM

WITH STO 6mm PREMESHED

FINISHING EDGE & STO uPVC END

CAP TO PANEL

20mm DRAINED CAVITY

STOARMAT MIRAL PLASTER

SYSTEM ON SELECTED

CONCRETE BLOCK

E2/AS1 COMPLIANT BACK

FLASHING CHASED INTO

CONC.BLOCK

MS SEALANT OVER STO JOINT

SEAL TAPE OR PEF ROD

DPC

20m

m50m

m M

IN

.

POREN FIXING

STO THERM 20mm VH CAVITY

BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL CORNER CONC.BLOCK/STO POREN

PP 831

2014

Page 120: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

COVER

POREN PANEL

STO POREN PLASTER

SYSTEM. SEL END PANEL

WITH S PROTECT WS 205

STOARMAT MIRAL PLASTER

SYSTEM ON SELECTED

CONCRETE BLOCK SERIES

E2/AS1 COMPLIANT BACK

FLASHING CHASED INTO

CONC.BLOCK

STO uPVC CONTROL JOINT

ALLOW 10mm GAP FILL WITH

MS SEALANT ON COMPLETION

10mm

DPC

50mm MIN. 20mm

POREN FIXING

STO THERM 20mm

VH CAVITY BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT CONC.BLOCK/STO POEREN

PP 832

2014

Page 121: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50m

m M

IN

.

6

m

m

G

A

P

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZONTAL JUNCTION CONC.BLOCK/STO POREN

PP 833

2014

Page 122: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

NOTE: FINISH STO POREN CLADDING SYSTEM

BEFORE INSTALLING STONE CLADDING

PROPRIETARY MANUF.STONE CLADDING

OVER ADHESIVE MORTAR ON 9mm

ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

STO THERM 20mm VH

CAVITY BATTEN

SEAL END PANEL WITH S

PROTECT WS 205

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER - MANUF.STONE/STO POREN - OPT 1

PP 840

2014

Page 123: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO PVC CORNER ANGLES

ON EXTERNAL CORNERS

MS SEALANT ON

PEF ROD

NOTE: FINISH STO POREN CLADDING SYSTEM

BEFORE INSTALLING STONE CLADDING

PROPRIETARY MANUF.STONE CLADDING

OVER ADHESIVE MORTAR ON 9mm

ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

STO THERM 20mm VH

CAVITY BATTEN

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER MANUF.STONE/STO POREN - OPT 2

PP 841

2014

Page 124: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER FRAMING

TO NZS 3604

MS SEALANT ON

PEF ROD

PROPRIETARY SCHIST OR STONE VENEER

CLADDING OVER ADHESIVE MORTAR ON

9mm ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

WALL UNDERLAY CONTINUOUS

AROUND CONERS,POLY

PROPYLENE FLASHING TAPE

APPLIED TO PROTECT WALL

UNDERLAY 75mm MIN.WIDE

NOTE: FINISH STO POREN CLADDING SYSTEM

BEFORE INSTALLING STONE CLADDING

POREN PANEL

20mm DRAINED

CAVITY

STO POREN

PLASTER SYSTEM

POREN FIXING

STO uPVC CORNER

ANGLE OVER FC

SHEET

STO THERM 20mm VH

CAVITY BATTEN

STOFLEXYL MORTAR

PANEL TO FC SHEET

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER - SCHIST or STONE VENEER/STO POREN

PP 842

2014

Page 125: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

POREN PANEL BONDED WITH POREN MINERAL PANEL ADHESIVE OR AAC 2HR CONSTRUCTION GLUE

POREN FIXING

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY

CONTINUOUS AROUND

CORNERS

E2/AS1 COMPLIANT

BACK FLASHING

PROPRIETARY

STONE VENEER

CLADDING OVER

ADHESIVE MORTAR

ON 9mm ETERPAN

FIXED ACCORDING

TO VENTCLAD

CONSTR.DETAILS

STO PREMESHED

PVC CNR.ANGLES

ON ALL EXT.CNRS

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

STO 6mm PREMESHED

FINISHING EDGE

SEAL END PANEL WITH S

PROTECT WS 205

MS SEALANT

OVER PEF ROD

STO PREMESHED

PVC CNR.ANGLES

ON ALL EXT.CNRS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

BOXED EXT.CORNER - STONE VENEER/STO POREN

PP 843

2014

Page 126: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER FRAMING

TO NZS 3604

POREN PANEL

STOPOREN PLASTER

SYSTEM

20mm DRAINED CAVITY

DOUBLE STUD REQUIRED

E2/AS1COMPLIANT

CORNER FLASHING

8mm GAP, MS SEALANT JOINT

NOTE: INSTALL FC SHEET AND FINISH STO POREN

CLADDING SYSTEM BEFORE INSTALLING STONE

8

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

MS SEALANT ON PEF ROD

PROPRIETARY MANUF.STONE CLADDING

OVER ADHESIVE MORTAR ON 9mm

ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

STO 6mm PREMESHED FINISHING

EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL CORNER - MANUF.STONE/STO POREN

PP 844

2014

Page 127: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER FRAMING

TO NZS 3604

POREN PANEL

STOPOREN PLASTER

SYSTEM

20mm DRAINED CAVITY

DOUBLE STUD REQUIRED

E2/AS1 COMPLIANT

CORNER FLASHING

8mm GAP, MS SEALANT JOINT

NOTE: INSTALL FC SHEET AND FINISH STO POREN

CLADDING SYSTEM BEFORE INSTALLING STONE

8

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

MS SEALANT ON PEF ROD

STO 6mm PREMESHED

FINISHING EDGE

PROPRIETARY SCHIST OR STONE VENEER

CLADDING OVER ADHESIVE MORTAR ON

9mm ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

STO THERM 20mm VH

CAVITY BATTEN

SEAL END PANEL WITH S

PROTECT WS 205

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CNR SCHIST or STONE VENEER/STO POREN

PP 845

2014

Page 128: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm MIN. 50mm MIN.

COVER COVER

MS SEALANT ON PEF ROD

E2/AS1 COMPLIANT

BACK FLASHING

PROPRIETARY MANUF.STONE CLADDING

OVER ADHESIVE MORTAR ON 9mm

ETERPAN FIXED ACCORDING TO

VENTCLAD CONSTR.DETAILS

POREN PANEL

STOPOREN PLASTER

SYSTEM

STO 6mm PREMESHED

FINISHING EDGE

STO THERM 20mm

VH CAVITY BATTEN

STO uPVC END CAP

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JUNCTION - MANUF.STONE/STO POREN

PP 846

2014

Page 129: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

MS SEALANT

E2/AS1 COMPLIANT BACK FLASHING

WITH 50mm MIN.CLADDING COVER

PROPRIETARY SCHIST OR STONE

VENEER CLADDING OVER ADHESIVE

MORTAR ON 9mm ETERPAN FIXED

ACCORDING TO VENTCLAD

CONSTR.DETAILS

MS SEALANT ON

PEF ROD

POREN PANEL

STOPOREN PLASTER

SYSTEM

STO 6mm PREMESHED

FINISHING EDGE

STO THERM 20mm

VH CAVITY BATTEN

STO uPVC END CAP

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERT.JUNCTION - SCHIST or STONE VENEER/STO POREN

PP 847

2014

Page 130: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZ.JUNCTION - MANUF.STONE/STO POREN

PP 848

2014

Page 131: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

PROPRIETARY SCHIST

OR STONE VENEER

CLADDING OVER

ADHESIVE MORTAR ON

9mm ETERPAN FIXED

ACCORDING TO

VENTCLAD

CONSTR.DETAILS

5

m

m

G

A

P

35

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZ.JUNCTION - SCHIST or STONE VENEER/STO POREN

PP 849

2014

Page 132: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

E2/AS1 COMPLIANTR

METAL FLASHING

10mm

100mm COVER

50m

m

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOTHERM 20mm VH

CAVITY BATTEN

POREN FIXING

HORIZONTAL PROFILED

METAL WALL CLADDING

PROFILED FOAM CLOSURE

STRIP UNDER CLADDING

STO uPVC END CAP/MS

SEALANT

STO uPVC 6mm

FINISHING EDGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER - HORIZ.PROFILED METAL/STO POREN

PP 850

2014

Page 133: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

FIXINGS IN ACCORDANCE WITH

E2/AS1

50m

m C

OV

ER

6m

m G

AP

10

PROFILED FOAM CLOSURE

STRIP UNDER CLADDING

DOUBLE STUD REQUIRED

HORIZONTAL PROFILED METAL WALL

CLADDING (SPECIFY TYPE, THICKNESS

& COATING)

E2/AS1 COMPLIANT FLASHING

REFER TO E2/AS1 FOR COMPLIANT PROFILES AND FLASHINGS

HORIZONTAL PROFILE METAL WALL CLADDING IS FIXED ON A DRAINED CAVITY

VERTICAL PROFILE METAL WALL CLADDING IS DIRECT FIXED OVER A ROOF UNDERLAY

STO POREN PLASTER

SYSTEM WITH 6mm STO

PREMESHED FINISHING EDGE

& STO uPVC END CAP

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROD 6mm MIN.GAP

POREN PANEL

STO THERM 20mm

VH CAVITY BATTEN

5

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CORNER - HORIZ.PROFILED METAL/STO POREN

PP 851

2014

Page 134: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

COVER

WALL UNDERLAY

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROAD 6mm MIN.GAP

POREN PANEL

STO POREN PLASTER SYSTEM

WITH 6mm FINISHING EDGE &

STO uPVC END CAP

COVER

50mm MIN. 50mm MIN.

A5

FIXINGS IN ACCORDANCE

WITH E2/AS1

PROFILED FOAM CLOSURE

STRIP UNDER CLADDING

HORIZONTAL PROFILED METAL

WALL CLADDING (SPECIFY TYPE,

THICKNESS & COATING)

E2/AS1 COMPLIANT FLASHING

10

REFER TO E2/AS1 FOR COMPLIANT PROFILES AND FLASHINGS

HORIZONTAL PROFILE METAL WALL CLADDING IS FIXED ON A DRAINED CAVITY

VERTICAL PROFILE METAL WALL CLADDING IS DIRECT FIXED OVER A ROOF UNDERLAY

NOTE:A = CHECK WITH SHEET METAL FOLDER A NARROW NECK

MAY REQUIRE A WELDED JOINT OR TOP HAT

STO THERM 20mm VH

CAVITY BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERT.JUNCTION - HORIZ.PROFILED METAL/STO POREN

PP 852

2014

Page 135: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

5

m

m

G

A

P

1. REFER TO E2/AS1 FOR COMPLIANT

PROFILES AND FLASHINGS

2. HORIZONTAL PROFILE METAL WALL

CLADDING IS FIXED ON A DRAINED CAVITY3. VERTICAL PROFILE METAL WALL

CLADDING IS DIRECT FIXED OVER A ROOF

UNDERLAY

4. IN EXTRA HIGH WIND ZONES INCREASE

FLASHING COVER TO 60mm MIN.AND USE

A RIGID UNDERLAY

15

35m

m M

IN

.

CO

VE

R

35m

m M

IN

.

CO

VE

R

FIXINGS IN ACCORDANCE

WITH E2/AS1

CONTINUOUS CAVITY DRAINAGE

CLOSURE STRIP

HORIZONTAL PROFILED METAL WALL

CLADDING (SPECIFY TYPE, THICKNESS &

COATING)

E2/AS1 COMPLIANT METAL

FLASHING

MS SEALANT

POREN PANEL

STOPOREN PLASTER

SYSTEM

SEAL END PANEL WITH S

PROTECT WS 205

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZ.JUNCTION - HORIZ.PROFILED METAL/STO POREN

PP 853

2014

Page 136: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

POREN PANEL

STOTHERM 20mm VH

CAVITY BATTEN

POREN FIXING

VERTICAL PROFILED METAL

WALL CLADDING (SPECIFYTYPE, THICKNESS &COATING)

STOPOREN

PLASTER SYSTEM

E2/AS1 COMPLIANT METAL

FLASHING

STO uPVC END CAP/MS

SEALANT

STO uPVC 6mm

FINISHING EDGE

FIXINGS IN ACCORDANCE

WITH E2/AS1

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXT.CORNER - VERTICAL PROFILED METAL/STO POREN

PP 854

2014

Page 137: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50m

m C

OV

ER

6m

m G

AP

REFER TO E2/AS1 FOR COMPLIANT PROFILES AND FLASHINGS

HORIZONTAL PROFILE METAL WALL CLADDING IS FIXED ON A DRAINED CAVITY

VERTICAL PROFILE METAL WALL CLADDING IS DIRECT FIXED OVER A ROOF UNDERLAY

FIXINGS IN ACCORDANCE

WITH E2/AS1

VERTICAL PROFILED METAL

WALL CLADDING (SPECIFY

TYPE, THICKNESS &

COATING)

E2/AS1 COMPLIANT FLASHING

(SPECIFY COATING)

DOUBLE STUD REQUIRED

STO POREN PLASTER

SYSTEM WITH 6mm STO

PREMESHED FINISHING

EDGE & STO uPVC END CAP

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROD 6mm MIN.GAP

POREN PANEL

STO THERM 20mm

VH CAVITY BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INT.CORNER - VERTICAL PROFILED METAL/STO POREN

PP 855

2014

Page 138: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

REFER TO E2/AS1 FOR COMPLIANT PROFILES AND FLASHINGS

HORIZONTAL PROFILE METAL WALL CLADDING IS FIXED ON A DRAINED CAVITY

VERTICAL PROFILE METAL WALL CLADDING IS DIRECT FIXED OVER A ROOF UNDERLAY.

FIXING IN ACCORDANCE WITH E2/AS1

50m

m M

IN

.

CO

VE

R

35m

m M

IN

.

CO

VE

R

3.5mm VENTILATION GAP, NON

VENTED CLOSER FLASHING

VERTICAL PROFILED METAL

WALL CLADDING (SPECIFY

TYPE, THICKNESS & COATING)

E2/AS1 COMPLIANT FLASHING

MS SEALANT

STO POREN PLASTER

SYSTEM

ROOF UNDERLAY TO LAP

OVER WALL UNDERLAY BY

75mm MIN.

FLASHING TAPE OVER

SEAL END OF PANEL

WITH S PROTECT WS205

POREN PANEL OVER 20mm

DRAINED CAVITY

POREN FIXING

1

0

m

m

G

A

P

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HORIZ.JUNCTION - VERT.PROFILED METAL/STO POREN

PP 856

2014

Page 139: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

WALL UNDERLAY

CONTINUOUS AROUND

CORNERS, FLASHING TAPE

APPLIED TO PROTECT WALL

UNDERLAY 75mm MIN.WIDE

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

STO POREN

PLASTER SYSTEM S

PROTECT WS 205

TO SEAL END PANEL

PORENFIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

EXTERNAL CORNER - STOTHERM/STO POREN

PP 860

2014

Page 140: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

6

MS SEALANT OVER STO JOINT

SEAL TAPE OR PEF ROD 6mm

MIN.GAP

50mm STOTHERM PANEL WITH

STOARMAT PLASTER SYSTEM

TO FINISH

STOTHERM FIXING

50m

m M

IN

.

50mm MIN.

STOTHERM uPVC END CAP

WALL UNDERLAY CONTINUOUS

AROUND CORNERS

STO THERM 20mm VH

CAVITY BATTEN

POREN PANEL

STOPOREN PLASTER SYSTEM WITH

6mm FINISHING EDGE. S PROTECT WS

205 TO SEAL END

E2/AS1 COMPLIANT

FLASHING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTERNAL CORNER - STOTHERM/STO POREN

PP 861

2014

Page 141: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm MIN. 50mm MIN.

WALL UNDERLAY

E2/AS1 COMPLIANT

HEMED METAL

FLASHING

50mm STOTHERM PANEL WITH

STOARMAT PLASTER SYSTEM TO

FINISH

STOTHERM FIXING

STOTHERM END CAP

STO POREN PLASTER SYSTEM S

PROTECT WS 205 TO SEAL END PANEL

USE A POLY PACKER TO FORM GAP

IN BASECOAT BEFORE INSTALLING

STO uPVC CONTROL JOINT

STO THERM 20mm

VH CAVITY BATTEN

POREN PANEL

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT - 50mm STOTHERM/STO POREN

PP 862

2014

Page 142: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm MIN. 50mm MIN.

WALL UNDERLAY

MS SEALANT ON STO JOINT SEAL

TAPE OR PEF ROAD 6mm MIN.GAP

E2/AS1 COMPLIANT

HEMED METAL FLASHING

POREN PANEL

NOTE: ADJUST FOR SELECTED STOTHERM PANEL SIZES - 60, 80 OR 100mm

(SHOWN - 50mm PANEL)

STO POREN PLASTER SYSTEM WITH

6mm PREMESHED FINISHING EDGE &

STO uPVC END CAP

STO THERM 20mm VH

CAVITY BATTEN

50mm STOTHERM PANEL WITH

STOARMAT PLASTER SYSTEM

TO FINISH

STOTHERM FIXING

STO uPVC 6mm

FINISHING EDGE

POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

VERTICAL JOINT - 80mm STOTHERM/STO POREN

PP 863

2014

Page 143: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm STOTHERM PANEL

WITH STOARMAT PLASTER

SYSTEM TO FINISH

STOTHERM uPVC

END CAP

20mm CAVITY

STO POREN PLASTER SYSTEM S

PROTECT WS 205 TO SEAL END PANEL

8-12m

m G

AP

POREN PANEL

20mm CAVITY

NOTE: UP TO A MAX. OF TWO STOREYS OR 7 METERS IN HEIGHT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

INTER-STOREY JUNCTION - STOTHERM/STO POREN

PP 864

2014

Page 144: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50mm STOTHERM PANELWITH STOARMAT PLASTERSYSTEM TO FINISH

STO uPVC BASEEND CAP

20mm CAVITY

STO POREN PLASTER SYSTEM SPROTECT WS 205 TO SEAL END PANEL

POREN PANEL

20mm CAVITY

1. DRAINED INTER-STOREY FLASHING REQUIRED TO LIMITCONTINUOUS CAVITY CONSTRUCTION TO TWO(2) STOREYS, GABLEEND OR 7 METERS

2. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO 60mmMIN.AND USE A RIGID UNDERLAY

3535

5

15° SLOPE TOINTER-STOREY FLASHING

CAVITY BASE CLOSERPOSTIONED TO GIVE 15mmMIN.DRIP EDGE TO CLADDING

ADDITIONAL WALL UNDERLAYDRESSED OVER FLASHING

ALLOW TO PLASTER BEHINDTHEN SEAL WITH MS SEALANTOR STO SEAL TAPE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

THIRD STOREY DRAINED INTER-STOREY JUNCTION

PP 865

2014

Page 145: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

AIRSEAL ON PEF RODGAP 7.5-8mm APPROX

TIMBER LINTEL ASPER NZS 3604

INTERNAL LINING

ARCHITRAVE ORSLIMLINE DETAIL

TIMBER WINDOW HEAD -PROFILE TO NZS 3610

FLEXIBLE FLASHING TAPEINSTALLED OVER WALL

UNDERLAY AT CORNERS

POREN PANEL

STO POREN PLASTERSYSTEM

20mm DRAINED &VENTED CAVITY -BATTENS AT 300 -600mm MAX.CTRS.

FLASHING TAPE ONTOWALL UNDERLAY andOVER ALU.HEADFLASHING

STO uPVC VENTEDBASE CAP WITHMIN 5mm GAP

E2/AS1 COMPLIANT HEADFLASHING, STOP ENDEDWITH 15° SLOPE AND10mm COVER

MIN. 5mm GAP REQUIRED10

5

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER WINDOW JOINERY - HEAD DETAIL

PP 870

2014

Page 146: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

CONTINUOUS

PACKING

MS SEALANT

20mm DRAINED & VENTED

CAVITY - BATTENS AT

300-400mm MAX CTRS.

WALL UNDERLAY

TURNED INTO

FRAMING REVEALS

AND TAPED AT

CORNERS

E2/AS1 COMPLIANT SILL

FLASHING WITH

STOP-END, LAPPED

UNDER JAMB FLASHING

TIMBER WINDOW SILL

TO NZS 3610

AIRSEAL ON PEF ROD

GAP 7.5-8mm APPROX

FLEXIBLE FLASHING

TAPE INSTALLED OVER

WALL UNDERLAY AT

CORNERS

10

STO POREN PLASTER

SYSTEM

STO POREN PANEL END

SEAL WITH S PROTECT

WS 205

STO uPVC 6mm

PREMESHED

FINISHING EDGE

25m

m M

IN

.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER WINDOW JOINERY - SILL DETAIL

PP 871

2014

Page 147: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STOPOREN PLASTER

SYSTEM

POREN PANEL

POREN FIXING

LINE OF HEAD

FLASHING

LINE OF SILL

FLASHING - LAPPED

UNDER JAMB PACKING

E2/AS1 COMPLIANT JAMB

FLASHING NOTCHED INTO TIMBER

WINDOW SILL JOINERY WITH STO

SEALANT OVER FIXINGS

TIMBER JAMB -

PROFILE TO NZS 3610

INTERNAL LINING

AIRSEAL GAP 7.5-8mm

APPROX

ARCHITRAVE OR

SLIMLINE DETAIL

JAMB PACKER TO

SUIT REBATE

WALL UNDERLAY TURNED

INTO FRAMING REVEALS

AND TAPED AT CORNERS

STO STICK ON JOINERY

CONNECTOR ON JAMB FLASHING

STO PREMESHED

CORNER ANGLE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER WINDOW JOINERY - JAMB DETAIL

PP 872

2014

Page 148: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

TIMBER DOOR SILL TO

NZS 3610

BOUNDARY JOISTS

20mm CAVITY BATTENS

@ 300-400mm MAX.

CTRS

50

AIR SEAL

WALL UNDERLAY

TURNED INTO

FRAMING REVEALS

E2/AS1 COMPLIANT

SILL FLASHING STOP

ENDED AND LAPPED

UNDER JAMB PACKERS

MS SEALANT

STO uPVC 6mm

PREMESHED

FINISHING EDGE

KEEP WALL

UNDERLAY &

BATTENS 20MM UP

FROM BOTTOM EDGE

OF CLADDING

STO POREN PLASTER

SYSTEM

STO uPVC VENTED

BASE CAP or FOOT

TRAY

DPC

STO POREN PANEL

FLASHING TAPE 100mm

MIN.UPSTAND TO

JAMBS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER DOOR JOINERY - TIMBER FLOOR THRESHOLD DETAIL

PP 873

2014

Page 149: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

UPSTAND TO SUIT

FLOOR FINISHES

NOTE: SILL TO BE SNUG

FIT AS AIR SEAL

PLASTER FURRING

CONCRETE SLAB

TIMBER SILL TO NZS

3610

DPC OVER PLASTER

FURRING

TIMBER TRIM UNDER

THRESHOLD

FLASHING TAPE 100mm

MIN.UPSTAND TO JAMBS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

TIMBER DOOR JOINERY - CONC.FLOOR THRESHOLD DETAIL

PP 874

2014

Page 150: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

50m

m

AIRSEAL OVER PEFROD GAP 7.5-8mm

APPROX

TIMBER LINTEL ASPER NZS 3604

INTERIOR LINING

WALL UNDERLAY

POREN PANEL

STO POREN PLASTERSYSTEM

20mm DRAINED CAVITY

35m

m M

IN.

FLASHING TAPE ONTO WALLUNDERLAY

STO uPVC VENTED BASECAP

ALUMINUM WINDOW HEADFLASHING MIN.15° SLOPEAND 10mm COVER ATWINDOW HEAD

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONESPROPRIETARY NK PVCuWINDOW SYSTEM

5

1. IN EXTRA HIGH WIND ZONESINCREASE FLASHING COVER TO 60mmAND USE A RIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

NK PVCu JOINERY - HEAD DETAIL

PP 875

2014

Page 151: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

JOINERY SUPPORT

BAR REQUIRE FOR

OPENINGS OVER

600mm

PROPRIETARY NK PVCu

WINDOW SYSTEM

MS SEALANT

STO uPVC SILL

FLASHING FOR NK

PVCu JOINERY

POREN PANEL

20mm DRAINED

CAVITY

FRAME BLOCK

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY

RETURNED INTO

OPENINGS & FLASHING

TAPE CONTINUOUS ALONG

SILL MIN 100mm UP JAMBS

& 50mm ONTO FACE OF

WALL UNDERLAY

AIRSEAL ON PEF ROD GAP

7.5-8mm APPROX.

INTERIOR LINING

STO POREN

PLASTER SYSTEM

STO PREMESHED

uPVC CNR

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

NK PVCu JOINERY - SILL DETAIL

PP 876

2014

Page 152: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO THERM 20mm VH

CAVITY BATTEN

FLASHING TAPE

(100mm UP JAMBS)

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

NK PVCu JOINERY - JAMB DETAIL

PP 877

2014

Page 153: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

PROPRIETARY TAPE OVER

HEAD FLASHING SUPPLIED

AND INSTALLED BY FLASHMAN

CONTRACTOR

FLASHMAN EXTRUDED ALUMINIUM

ONE PIECE CAVITY CLOSURE AND

HEAD FLASHING WITH STOP END

(SHOWN DASHED)

5

AIRSEAL OVER PEF

ROD GAP 7.5-8mm

APPROX

TIMBER LINTEL AS

PER NZS 3604

INTERIOR LINING

WALL UNDERLAY

POREN PANEL

STO POREN PLASTER

SYSTEM

20mm DRAINED CAVITY

STO POREN uPVC VENTED

BASE TRAY

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FOR

VERY HIGH AND EXTRA

HIGH WIND ZONES

ALUMINIUM WINDOW

JOINERY

25

25mm MIN. FROM OUTSIDE OF FRAMING

TO BACK OF WINDOW FLANGE

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FLASHMAN HEAD FLASHING

PP 878

2014

Page 154: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

FLASHMAN ALUMINIUM

MITRE SOAKER

SUPPLIED BY FLASHMAN

INSTALLED BY BUILDER

H3.1 PACKER SUPPLIED

AND INSTALLED BY

FLASHMAN

14 GAUGE HOT DIP

GALV.(316SS WHERE

REQ.) S.T.H.C SCREWS @

600mm CTRS. WITH 65mm

MIN. FRAME

PENETRATION. SUPPLIED

BY FLASHMAN

STO POREN PLASTER

SYSTEM

20mm DRAINED CAVITY

TIMBER FRAMING

TO NZS 3604

WALL UNDERLAY RETURNED

INTO OPENINGS & FLASHING

TAPE CONTINUOUS ALONG

SILL MIN 100mm UP JAMBS &

50mm ONTO FACE OF WALL

UNDERLAY

AIRSEAL ON PEF ROD

GAP 7.5-8mm APPROX.

FLASHMAN EXTRUDED

ALU.EURO SILL WITH END CAP

- SHOWN DASHED

25mm MIN. FROM OUTSIDE

FACE OF THE FRAMING LINE TO

THE BACK OF WINDOW FLANGE

25

STO STICK ON JOINERY

CONNECTOR 8mm MIN.

SUPPORT PACKER

8

FLASHMAN BACK PLATE -

SHOWN DASHED

ALT.METRO SILL -

SHOWN DASHED

STO POREN FIXING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FLASHMAN SILL FLASHING

PP 879

2014

Page 155: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

FLASHMAN EXTRUDED

ALUM.JAMB FLASHING

25mm MIN. FROM OUTSIDE

FACE OF FRAMING TO

BACK OF WINDOW FLANGE

25

SEAL PANEL END - S

PROTECT WS 205

LINE OF ALT.METRO SILL

BELOW - SHOWN

DASHED

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

FLASHMAN JAMB FLASHING

PP 880

2014

Page 156: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

AIRSEAL OVER PEFROD GAP 7.5-8mm

APPROX

TIMBER LINTEL ASPER NZS 3604

INTERIOR LINING

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONESPROPRIETARY HOMERITPVC WINDOW JOINERY

ALUMINIUM WINDOW HEADFLASHING MIN.15° SLOPE AND10mm COVER AT WINDOWHEAD

5

WALL UNDERLAYINSTALLED AS PERE2/AS1

POREN PANELSTO POREN PANELPLASTER SYSTEM

20mm DRAINEDCAVITY

FLASHING TAPE ONTOWALL UNDERLAYSTO uPVC VENTEDBASE CAP

STO CAVITY JAMBFLASHING STOPENDS

1. IN EXTRA HIGH WIND ZONESINCREASE FLASHING COVER TO60mm AND USE A RIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HOMERIT PVC JOINERY - HEAD DETAIL

PP 881

2014

Page 157: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

STO POREN

PLASTER SYSTEM

STO POREN FIXING

20mm DRAINED

CAVITYTIMBER FRAMING

TO NZS 3604

WALL UNDERLAY RETURNED

INTO OPENINGS & FLASHING

TAPE CONTINUOUS ALONG

SILL MIN 100mm UP JAMBS &

50mm ONTO FACE OF WALL

UNDERLAY AS PER E2/AS1

AIRSEAL ON PEF ROD

GAP 7.5-8mm APPROX.

INTERIOR LINING

JOINERY SUPPORT BAR

REQUIRE FOR

OPENINGS OVER 600mm

PROPRIETARY HOMERIT

PVC WINDOW JOINERY

MS SEALANT

STO uPVC

ADJUSTABLE CNR

STO POREN PANEL

5mm GAP BETWEEN

JOINERY & PLASTER

STO uPVC CAVITY

FACE FIXED SILL &

JAMB FLASHING

5

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HOMERIT PVC JOINERY - SILL DETAIL

PP 882

2014

Page 158: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

FLASHING TAPE AS

PER E2/AS1

H1.2 PACKER TO

SUPPORT JOINERY

AIRSEAL ON PEF ROD

GAP 7.5-8mm APPROX.

PROPRIETARY HOMERIT

PVC WINDOW JOINERY

MS SEALANT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING SYSTEM

HOMERIT PVC JOINERY - JAMB DETAIL

PP 883

2014

Page 159: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

STOPOREN PANEL PANEL (40mm cavity)SYSTEM

THE STOPOREN PANEL VENEER SYSTEM HAS BEEN APPRAISED AS AN EXTERNAL WALL CLADDING SYSTEM FORBUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER FRAMING COMPLYING WITH THE NZBC; AND,• WITH A RISK SCORE OF 0-20, CALCULATED IN ACCORDANCE WITH NZBC ACCEPTABLE SOLUTION E2/AS1, TABLE 2;

AND,• SITUATED IN NZS 3604 WIND ZONES UP TO, AND INCLUDING ‘EXTRA HIGH’.

THE STOPOREN PANEL VENEER SYSTEM HAS ALSO BEEN APPRAISED FOR WEATHERTIGHTNESS AND STRUCTURALWIND LOADING WHEN USED AS AN EXTERNAL WALL CLADDING SYSTEM FOR BUILDINGS WITHIN THE FOLLOWING SCOPE:• THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND,• CONSTRUCTED WITH TIMBER OR STEEL FRAMING COMPLYING WITH THE NZBC; AND,• SITUATED IN SPECIFIC DESIGN WIND PRESSURES UP TO A MAXIMUM DESIGN DIFFERENTIAL ULTIMATE LIMIT STATE

(ULS) OF 2.5 KPA.

NOTE: REFER TO STO POREN PANEL CLADDING SYSTEM FOR COMPREHENSIVE SET OF ACAD DETAILS

STOPOREN PLASTER SYSTEM

INCORPORATING:1. S-PROTECT WS 205 SEALER TO SEAL POREN PANELS2. STOPOREN PLASTER 25kg BAG3. STOPLEX W SEALER 10lt CONTAINER4. STOLIT K or MP COLOURED FINISHING RENDER 25kg PAIL5. STOCOLOR MAXICRYL FACADE PAINT 15lt PAIL

STOLASTIC COLOR FACADE PAINT 15lt PAILSTOLOTUSAN COLOR G 15lt PAIL

STOARMAT MIRAL PLASTER SYSTEMCAN ALSO BE USED FOR ADDITIONAL STRENGTH AND REINFORCEMENT

CAVITY SPACERS FIXING SYSTEM:

• 40mm x MINIMUM 200 LONG H3.1 TIMBER SPACERS FIXED WITH 75 x 3.06 GALVANIZED RING SHANK NAILS ANDSECURE PANEL WITH 75MM POREN FIXINGS COUNTERSUNK 10mm.

STO 40mm VH POLYSTYRENE CAVITY BATTENS:

• TEMPORARILY FIX CONTINUOUS STO 40mm CAVITY BATTENS TO FRAMING (OVER WALL UNDERLAY) AND SECUREPANEL WITH 120mm POREN FIXINGS COUNTERSUNK 5mm TO MAXIMUM 12MM.

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

INTRODUCTION

PP 1000

2014

Page 160: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

2200

2020

0mm

STE

EL

RE

INFO

RC

ING

CE

NTR

ES

25 55 SCALE NTS

600

5050

050

600

PANEL FIXING OVER40mm H3.1 TIMBER SPACERS

50

FIXINGS

FIXINGS

170 155165

200

200

200

200

200

160

200

200

200

200

200

STEEL REINFORCING

150

300

150

600

PANEL FIXING OVER40mm STO CAVITY BATTEN

50

FIXINGS

FIXINGS

POREN PANELAUTOCLAVED AERATEDCONCRETE DENSITY 600kg/m²THERMAL RESISTANCE RV 0.30 ONCAVITY CONSTRUCTION

POREN PANEL DIMENSIONS2200x600x50mmFREIGHT20 PANELS / DOUBLE PALLET1.3m² / PALLET + PALLETAREA: 1.32m² / PANELWEIGHT: 42kg / PANEL

POREN PANELON 40mm CAVITYTIMBER SPACERS to be MIN.200mmLONG X40mm x 40mmCAVITY BATTEN40mm STO VH POLY BATTEN40mm H3.1 TIMBER BATTEN

BEVELED EDGEOF PANEL FACESFRAMING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

INFORMATION

PP 1001

2014

Page 161: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

TIMBER FRAMING TO

NZS 3604

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- POREN PLASTER MESH PLASTER

- STOLIT K COLOURED

FINISHING RENDER

- STOCOLOR PAINT

H3.1 CAVITY SPACERS AT

MAX. 600mm CENTRES ON

FRAMING

50m

m m

in.

9

0

m

m

m

i

n

.

R

E

B

A

T

E

WALL UNDERLAY MEETING

REQUIREMENTS OF E2/AS1

NOTE: BUILDER REQUIRED TO

PROVIDE STRAPS AT MAX.

300mm CENTRES FOR STUDS

OVER 450mm CENTRES

NOTE:600mm FRAMING

TWO 75mm POREN FIXINGS EITHER SIDE OF PANEL JOINTS MIN

40mm FROM EDGE INTO CAVITY SPACER

SEE PP 1003 FOR NON REBATED DOUNDATION

CONCRETE FOUNDATION

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

CAVITY SPACER SETOUT (600ctrs)

PP 1002

2014

Page 162: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

TIMBER FRAMING

TO NZS 3604

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- STOPOREN MESH PLASTER

- STOLIT K COLOURED

FINISHING RENDER

- STOCOLOR PAINT

STO VH 40mm or H3.1 TIMBER

40mm CAVITY BATTEN AT 300mm

CENTRES ON 600mm FRAMING

50m

m m

in.

WALL UNDERLAY MEETING

REQUIREMENTS OF E2/AS1

NOTE:600mm FRAMING

120mm POREN FIXINGS AT 300mm CENTRES GENERALLY 150mm

FROM PANEL EDGE WITH ONE FIXING BETWEEN STUDS ON THE

BOTTOM PLATE

SEE PP 1002 FOR REBATED FOUNDATION

CONCRETE FOUNDATION

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm Cavity) SYSTEM

CAVITY BATTEN SETOUT (600ctrs)

PP 1003

2014

Page 163: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:20

TIMBER FRAMING

TO NZS 3604

STO VH 40mm or H3.1 TIMBER

CAVITY BATTENS

STOPOREN PLASTER SYSTEM

- S-PROTECT WS 205 SEALER

- POREN PLASTER

MESH COAT

- STOPLEX W SEALER

- STOLIT K COLOURED

FINISHING RENDER

- STOCOLOR PAINT

NOTE:400mm FRAMING

FIXINGS AT 300mm CENTRES GENERALLY 150mm FROM PANEL

EDGE

SEE PP 1002 FOR REBATED FOUNDATION

50m

m m

in.

POREN ADHESIVE

ON PANEL JOINTS

POREN PANEL

CONCRETE FOUNDATION

STO uPVC

ADJUSTABLE FOOT

TRAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

CAVITY BATTEN SETOUT (400ctrs)

PP 1004

2014

Page 164: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

DOOR WINDOW

FOUNDATION

FRAMING STUDS AT 600mm CENTRES

SCALE NTS

SOFFIT PLATE

40 40

200

22.5

°

33 40

200

H3.1 TIMBER CAVITYSPACERS FOR 40mmOR 33mm CAVITY

22.5

°

75 mm POREN FIXINGSJOINT TO FIX PANEL

50 mm PORENPANEL

FIX SPACERS WITH 275mm x 3.06GALVANIZED RINGSHANK NAILS

MINIMUM REBATE IN FOUNDATION 50mm OR HANGPANEL 50mm PAST FOUNDATION.FOR 40mm BATTENSYSTEM LAYOUT REFER - PP 1002, 1003 or 1004

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

CAVITY BATTEN SETOUT (400ctrs) - ELEVATION

PP 1005

2014

Page 165: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

TIMBER FRAMING

TO NZS 3604

DPC

INTERNAL LINING

DPM

FOR 1 OR 2 STOREYS

50

10

INSULATION TO EXTERIOR

WALLS

GL

*100

* DIM.FOR

UNPROTECTED

GROUND. REFER

NZS3604 FIG.7.11

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWNFOR CLARITY

STO PLASTER SYSTEM

INSULATION AS

PER NZBC H1/AS1

100m

m M

IN

.50m

m

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

REBATED SLAB-ON-GROUND - CAVITY SPACER

PP 1006

2014

Page 166: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

DPC

50

AS PER NZS 3604

DPM

6

CONCRETE SLAB/REINFORCING

AS PER NZS 3604 OR ENGINEER

SPECIFIC DESIGN - NOT SHOWNFOR CLARITY

INSULATION AS

NZBC H1/AS1

100m

m M

IN

.

plaster

50m

m

flexyl

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

FOUNDATION SLAB-ON-GROUND - CAVITY SPACER

PP 1007

2014

Page 167: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

POREN MINERAL PANEL

ADHESIVE OR AAC 2 HR

CONSTRUCTION GLUE ON ALL

PANEL JOINTS

WALL UNDERLAY

CONTINUOUS AROUND

CORNERS AS PER E2/AS1

STO PREMESHED

CORNER BEAD

STOPOREN PLASTER

SYSTEM

POREN PANEL

NOTE: USE 120mm POREN FIXINGS FOR

40mm STO VH CAVITY BATTENS or 75mm

POREN FIXINGS ON H3.1 TIMBER SPACERS

SELECTED H3.1 TIMBER

CAVITY SPACERS or STO

CAVITY BATTENS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

EXTERNAL CORNER

PP 1008

2014

Page 168: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

NOTE: USE 120mm POREN FIXINGS FOR

40mm STO CAVITY BATTENS or 75mm

POREN FIXING ON CAVITY SPACERS

POREN MINERAL PANEL

ADHESIVE OR AAC 2 HR

CONSTRUCTION GLUE ON ALL

PANEL JOINTS

WALL UNDERLAY

CONTINUOUS AROUND

CORNER AS PER E2/AS1

LAP STO MESH 75mm MIN.

BOTH WAYS

STO VH CAVITY 40mm

BATTENS or H3.1 TIMBER

SPACERS

STOPOREN PLASTER

SYSTEM

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

INTERNAL CORNER

PP 1009

2014

Page 169: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

10mm GAP IN PANELS

NOTE:ENSURE POREN PANELS ARE SUPPORTED BY A MAX.OF 2/STUDS. VERTICAL CONTROL

JOINTS ARE REQUIRED AT 8.0M MAX.CTRS. ADHERE STO CONTROL JOINT AND

REMOVE TAB CAREFULLY AS SOON AS THE JOINT IS SET TO AVOID CRACKS.

USE 120mm POREN FIXINGS FOR 40mm H3.1 TIMBER CAVITY BATTENS or 75mm POREN

FIXING FOR CAVITY SPACERS

STO uPVC CONTROL JOINT. FILL WITH

MS SEALANT or SEAL JOINS, PAINT

AND LEAVE AS A NEGATIVE DETAIL

300mm MAX.CTRS

STOPOREN PLASTER

SYSTEM

40mm H3.1 TIMBER

CAVITY SPACER or

40mm STO VH CAVITY

BATTEN

POREN PANEL

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

VERTICAL CONTROL JOINT

PP 1010

2014

Page 170: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

A

WALL UNDERLAY - ENSURE

UNDERLAY RUNS

CONTINUOUS OVER JOINT

POREN PANEL

H3.1 TIMBER CAVITY

SPACER or 40mm STO VH

CAVITY BATTEN

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOPOREN PLASTER

SYSTEM

STOPOREN PLASTER

SYSTEM

H3.1 TIMBER CAVITY

SPACER or 40mm STO VH

CAVITY BATTEN

NOTE:POREN PANEL 75mm FIXING

ON CAVITY SPACERS or

120mm FIXINGS ON 40mm

STO VH CAVITY BATTENS. A

STO PVC 12mm CONTROL

JOINT IS REQUIRED ON

UNSEASONED JOISTS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

HORIZONTAL INTER-STOREY JOINT

PP 1011

2014

Page 171: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE: 1:2

A

WALL UNDERLAY - ENSURE

UNDERLAY RUNS

CONTINUOUS OVER JOINT

POREN PANEL 75mm FIXING

ON CAVITY SPACERS or

120mm FIXINGS ON 40mm

CAVITY BATTENS

H3.1 TIMBER CAVITY

SPACER or 40mm STO VH

CAVITY BATTEN

STOPOREN PLASTER

SYSTEM

POREN PANEL

STOPOREN PLASTER

SYSTEM

H3.1 TIMBER CAVITY

SPACER or 40mm STO VH

CAVITY BATTEN

INSTALL STO uPVC 12mm

CONTROL JOINT WITH MS

SEALANT or FORM

NEGATIVE DETAIL

15

12m

m

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

HORIZONTAL INTER-STOREY CONTROL JOINT

PP 1012

2014

Page 172: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

40mm H3.1 CAVITY

SPACER or 40mm STO VH

CAVITY BATTEN

FLASHING TAPE OVER

STO uPVC VENTED

BASE CAP with

EXTENSION INSERT

ALLOW TO PLASTER

BEHIND THEN SEAL

WITH MS SEALANT OR

STO SEAL TAPE

AS REQUIRED TO LIMIT

CONTINUOUS CAVITY

CONSTRUCTION TO

TWO STOREYS

FLASHING BACK AND

FRONT COVER TO BE A

MINIMUM 35mm

EXCLUDING DRIP

EDGES

SCALE: 1:2

MIN

.C

OV

ER

MIN

.C

OV

ER

35

35

STO PLASTER SYSTEM

POREN PANEL

WALL UNDERLAY -

ENSURE UNDERLAY

RUNS CONTINUOUS

OVER JOINT

WALL UNDERLAY - ENSURE

UNDERLAY RUNS

CONTINUOUS OVER JOINT

5

1. IN EXTRA HIGH WIND

ZONES INCREASE

FLASHING COVER TO

60mm MIN.AND USE A

RIGID UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

DRAINED JOINT AT THIRD STOREY

PP 1013

2014

Page 173: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

40mm H3.1 TIMBERSPACER or STO VH

CAVITY BATTEN

FLASHING TAPE SEALED 50mmTOMETERBOX AND 100mm TO WALLUNDERLAY

8mm AIRSEAL ON PEFROD BY BUILDER

NOTE: USE 120mm POREN FIXINGSFOR 40mm CAVITY BATTENS or75mm POREN FIXINGS WITH CAVITYSPACERS

STO POREN PANEL SEAL ENDWITH S PROTECT WS 205

MS SEALANT OVER STO JOINTSEAL TO PERIMETER OF

METERBOXSTO uPVC FINISHING EDGE

STOPORENPLASTER SYSTEM

40mm CAVITY BATTEN SLOPED MIN.5° EXTENDING PAST SERVICE BOX

WITH FLASHING TAPE OVERBATTEN & 50mm MIN.ONTO

UNDERLAY

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

SERVICE BOX DETAIL

PP 1014

2014

Page 174: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE:FLASHING TAPE SYSTEM TO BE INSTALLEDAROUND JOINERY OPENINGS AS PER E2/AS1USE 120mm POREN FIXINGS FOR 40mm CAVITYBATTENS or 75mm POREN FIXINGS ON CAVITYSPACERS

SCALE 1:2

TIMBER LINTEL ASPER NZS 3604

STO POREN PLASTERSYSTEM

FLASHING TAPE ONTOWALL UNDERLAY

STO POREN PANEL

ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD

MIN. 5mm GAP REQUIRED

SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES

35m

m M

IN.

50m

m

ALUMINIUM WINDOWJOINERY

INTERIOR LINING

AIRSEAL ON PEFROD GAP 7.5-mm STO uPVC VENTED

BASE CAP withEXTENSION INSERT

HEAD FLASHING WITH10mm STOPENDSPOSITIONED 10mmPAST WINDOW JAMBS

STO uPVC STICK ONFLASHING TO FINISH ATHEAD FLASHING WITHPUNCHED PLASTERLEG CONTINUING 30mmABOVE

5

H3.1 CAVITY SPACERor 40mm CAVITYBATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

ALUMINIUM WINDOW JOINERY - HEAD DETAIL

PP 1015

2014

Page 175: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:2

NOTE: OPENINGS OVER 600mm REQUIRE JOINERY SUPPORT BAR USE 120mm POREN FIXINGS FOR 40mm CAVITY BATTENS and 75mm FIXINGS FOR CAVITY SPACERS

JOINERY SUPPORT MUST BE CUT 15mm SHORT OF JOINERY JAMBS TO ALLOW FOR STO uPVC FLASHINGS1. SEALANT IS APPLIED TO THE SILL AND JAMB FLASHINGS2. WINDOW HEADS ARE LEFT OPEN3. FLEXIBLE FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1

WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.

JOINERY SUPPORT BARREQUIRE FOROPENINGS OVER 600mm

PROPRIETARYALUM.WINDOWJOINERY

MS SEALANT

STOPOREN PLASTERSYSTEM

STO POREN PANEL

FRAME BLOCK

AIRSEAL ON PEF ROD GAP7.5mm APPROX.

STOPOREN FIXING

STO CAVITY SPACERFIXED 2/75mm x 3.06GALV.RING SHANK NAILS

STO uPVC STICK ONFLASHING, ADHESIVE FIXTO PANEL AT 15° SLOPE

STO PRE-MESHEDANGLE

WALL UNDERLAY RETURNED INTOOPENINGS & FLASHING TAPE

CONTINUOUS ALONG SILL MIN 100mm UPJAMBS & 50mm ONTO FACE OF WALL

UNDERLAY

APPLY S PROTECT WS 205SEALER BEFORE PLASTERING

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

ALUMINIUM WINDOW JOINERY - SILL DETAIL

PP 1016

2014

Page 176: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE:NSTALL STOPOREN JOINERY FLASHING DURING POREN

PANEL CONSTRUCTION USE 120mm POREN FIXING FOR 40mm

CAVITY BATTENS and 75mm FIXINGS FOR CAVITY SPACERS

SCALE 1:2

10mm6

H1.2 PACKER TO

SUPPORT JOINERY

WALL UNDERLAY RETURNED INTO RECESS

WITH FLASHING TAPE SYSTEM. FLASHING

TAPE RETURNED min 100mm UP JAMBS

STOPOREN PLASTER

SYSTEM

STO POREN PANEL

STOPOREN 75mm

FIXING

H3.1 CAVITY SPACER or

40mm CAVITY BATTEN

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL CLADDING (40mm cavity) SYSTEM

ALUMINIUM WINDOW JOINERY - JAMB DETAIL

PP 1017

2014

Page 177: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

Z

Z

35

150

CARRY MESH/PLASTERUP TO TOP EDGE

WALL UNDERLAY CONTINUOUSOVER TOP OF WALL FRAME

POREN PANEL

STO POREN PLASTERSYSTEM

REFER TABLE 7- E2/AS1

POREN FIXING

PROVIDE SEPARATION (ROOFUNDERLAY) UNDER METAL

CAPPING AND 15mm H3 PLY -PACKED TO A FALL

PRE FINISHED METAL CAPPINGTO PARAPET WITH 5° MIN.FALL

40mm DRAINEDCAVITY

H3.1 CAVITY SPACER or 40mmCAVITY BATTEN

STO uPVC VENTEDBASE CAP WITHEXTENSION INSERT

NOTE:H3.1 CAVITY SPACERS DETAILED ALTERNATIVELY -USE 120mm POREN FIXINGS or 40mm CAVITYBATTENS @ 300mm CTRS

BALUSTRADE 1000MMIN.HEIGHT FROM DECK

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

PARAPET/BALUSTRADE DETAIL - METAL CAP

PP 1018

2014

Page 178: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

35

150

POREN PANEL

STO POREN PLASTERSYSTEMSTO uPVC VENTEDBASE CAP WITHEXTENSION INSERT

75

75

10°POREN CAP AT 10°

OVERSEATS WALLS,GLUE TO POREN WALL

CLADDING

H3.1 PACKER CUT TO10° SLOPE WITH 15mm

PLYWOOD WITHFLASHING TAPE OR

ROOFING UNDERLAYWALL UNDERLAY CONTINUOUSOVER TOP OF WALL FRAME

POREN PANELSTO POREN PLASTERSYSTEM

40mm DRAINEDCAVITY

POREN FIXING

OVERLAY OF STO FLEXYL MEMBRANEUNDER MESH COAT TO TOP & SIDES,75mm MIN.DOWNTURN OVER BASECOAT

STO PREMESHED uPVC ADJUSTABLECORNERS

H3.1 CAVITY SPACER or 40mmCAVITY BATTEN

BALUSTRADE 1000M MIN.HEIGHT FROM DECK

NOTE:H3.1 CAVITY SPACERS DETAILEDALTERNATIVELY - USE 120mm POREN FIXINGSor 40mm CAVITY BATTENS @ 300mm CTRS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

PARAPET/BALUSTRADE DETAIL - PLASTERED FINISH

PP 1019

2014

Page 179: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

140 140

370

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

PARAPET and/or ENCL.BALUSTRADE TO WALL - PLAN

PP 1020

2014

Page 180: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:5

10° MIN.FALL TO TOP OFPARAPET

10°15mm H3 PLYWOOD OVER

H3.1 TIMBER PACKER WITHFLASHING TAPE or ROOFING

UNDERLAY

POREN PANELSTO POREN PLASTER

SYSTEM

WALL UNDERLAYCONTINUOUS

OVER TOP OF WALL FRAME

H3.1 CAVITY SPACERS or40mm CAVITY BATTENS

NOTE:HANDRAIL REQUIRED WHERE BALUSTRADE IS UNDER 1000M.ADHERE PANEL JOINTS WITH POREN MINERAL PANELADHESIVE or AAC 2hr CONSTRUCTION GLUE. HANDRAIL &FIXINGS TO HAVE 50x3mm EPDM WASHERS AROUND FIXINGS.USE 120mm POREN FIXINGS FOR 40mm CAVITY BATTENS or75mm FIXINGS FOR H3.1 CAVITY SPACERS

STO PREMESHED PVCADJUSTABLE CORNER ANGLESAT EXTERNAL CORNERS

OVERLAY OF STO FLEXYLMEMBRANE UNDER MESHCOAT TO TOP & SIDES, 75mmMIN.DOWNTURN OVER BASECOAT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO POREN SYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

BALUSTRADE/ENCLOSED DECK DETAIL

PP 1021

2014

Page 181: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

140

140

WALL UNDERLAY

NOTE:POREN PANEL CAP BUTTS INTO FRAMING AND ISSEALED & TAPED TO UNDERLAY WITH 50x50mmFLASHING TAPE. FLASHING TAPE ONTO THE SEALEDPOREN PANEL MUST BE 50mm MIN.

INSTALL 150mm FLASHINGTAPE 75x75mm EACH WAY

OVER UNDERLAY TOINTERNAL CORNERS

STO CAVITY BATTENS

POREN CAP BUTTS AGAINSTFRAME, PRIOR TO INSTALLINGCAVITY BATTENSPOREN CAP EXTENDS OVERTOP OF SIDE PANELSH3.1 TIMBER PACKER WITH15mm PLYWOOD OVERTIMBER PACKER FLASHINGTAPE or ROOFING UNDERLAY

POREN SIDE PANELS

CAVITY BATTENS or H3.1TIMBER SPACERS

FLASHING TAPE PORENCAP TO UNDERLAY

PARAPET FRAMING

10°WALL UNDERLAYCONTINUOUSOVER TOP OF WALL FRAME

POREN PANELSTO POREN PLASTERSYSTEM

POREN FIXING

OVERLAY OF STO FLEXYLMEMBRANE UNDER MESHCOAT TO TOP & SIDES,75mm MIN.DOWNTURNOVER BASE COAT

STO PREMESHED uPVCADJUSTABLE CORNERS

H3.1 CAVITY SPACER or40mm CAVITY BATTEN

STOFLEXYL MESHED SADDLEMEMBRANE

75POREN CAP AT

10° OVERSEATSWALLS, GLUE TO

POREN WALLCLADDING

H3.1 PACKERCUT TO 10°

SLOPE WITH15mm PLYWOODWITH FLASHING

TAPE ORROOFING

UNDERLAY

75

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

FLEXIBLE FLASHING INSTALL

PP 1022

2014

Page 182: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE: SADDLE FLASHING INSTALLED AFTER CAVITY

SYSTEM. 50x50mm INTERNAL CNR FLASHING FROM

BEHIND SADDLE EXTENDED TO BOTTOM OF WALL

PANELS ON EACH BUILDING FACE

STO 20mm VH CAVITY

BATTENS

PLACE CAP FLASHING OVER

SADDLE FLASHING - REFER TO

E2/AS1 FIGURE 12 FOR CAP FIXING

DETAILS.

H3.1 CAPPING PLATE CUT TO A

FALL WITH FLASHING TAPE OR

ROOFING UNDERLAY

WALL UNDERLAY

2 LINES OF

SEALANT

1

0

0

m

m

M

I

N

.

5

0

m

m

M

I

N

.

50m

m M

IN

.

A. SADDLE FLASHING B. PARAPET CAP

METAL PARAPET CAP

FLASHING

RIVET THROUGH TOP OF CAP TO

SADDLE FLASHING. MS SEALANT

TO RIVETS

EXTENT OF SADDLE FLASHING

8mm EXPANSION GAP BETWEEN

PARAPET CAP AND SADDLE

FLASHING - USE MS SEALANT

The information contained in this detail is based on our experience and testing and represents the latest information available at the date of

issue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to be

used in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is the

responsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

METAL SADDLE FLASHING

PP 1023

2014

Page 183: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

SCALE 1:10

WALL UNDERLAY

POREN PANEL

STO FLEXYL MESHEDWATERPROOFING MIN 75mm OVERADJACENT WALLS.

POREN BALUSTRADECAP AT 10° SLOPE

STO POREN MESHEDBASECOAT PLASTER

NOTE: APPLY STOFLEXYL MESHED WATERPROOFING OVERSTOPOREN MESHED BASECOAT PLASTER.

STO FLEXYL MESHED WATERPROOFING HAS BEEN TESTED BY BRANZ TO MEET AS/NZS4858 FOR A WATERPROOFING MEMBRANE AS REQUIRED BY E2/AS1

75mm MIN.DOWNTURN

H3.1 TIMBER PACKER CUTTO 10° SLOPE

POREN BALUSTRADE CAPLAPS OVER POREN AT SIDES

POREN PANEL AT SIDES

STO CAVITY BATTENOR TIMBER SPACERS

95

95

A. NZBC - E2/AS1 REQUIRES BALCONY & PARAPET WALLS TO BEOFFSET FROM THE MAIN WALL PLANE TO ALLOW FOR SADDLEFLASHINGS

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

STOFLEXYL MESHED SADDLE FLASHING

PP 1024

2014

Page 184: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

PRE-FINISHED METAL ROOFINGOVER ROOF UNDERLAY

PREFABRICATED TRUSS TOPCHORD OVERHANG

H3.1 PRE PRIMED &PAINTED FASCIABOARD

SCALE 1:10

SOFFIT LINING TOCLOSE OFF CAVITY MS SEALANT 6-8mm

(before plastering)

WALL UNDERLAYPOREN PANEL

STO POREN PLASTERSYSTEM

H3.1 CAVITY SPACER or 40mmCAVITY BATTEN

NOTE:REFER TO E2/AS1 TABLE 1 FOR DEFINITIONS of RISK LEVELS.EAVE FLASHINGS ARE REQUIRED WHEN FASCIA IS 100mm orLESS FROM EXTERIOR WALL CLADDING & ROOF SLOPES ARE10° or LESS & VERY HIGH/EXTRA HIGH WIND ZONES.USE 120mm POREN FIXINGS FOR 40mm CAVITY BATTENS and75mm FIXINGS FOR H3.1 CAVITY SPACERS

Varies

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

RAKING SOFFIT/WALL JUNCTION

PP 1025

2014

Page 185: STO POREN PANEL CLADDING SYSTEM DRAWING · PDF fileStoPoren Panel Cladding System Inter-storey Roof Stop End Flashing - Plan View PP 704 ... StoPoren Panel Cladding System Ext.Cnr

NOTE:REFER TO E2/AS1 TABLE 1 FOR DEFINITIONS of RISK LEVELS.EAVE FLASHINGS ARE REQUIRED WHEN FASCIA IS 100mm orLESS FROM EXTERIOR WALL CLADDING & ROOF SLOPES ARE10° or LESS & VERY HIGH/EXTRA HIGH WIND ZONES.USE 120mm POREN FIXINGS FOR 40mm CAVITY BATTENS and75mm FIXINGS FOR H3.1 CAVITY SPACERS

SCALE 1:10

Varies

6mm

The information contained in this detail is based on our experience and testing and represents the latest information available at the date ofissue. This detail is intended for use by the design professional and users of Sto products to assist in developing specific project details to beused in conjunction with a Sto Specification. We reserve the right to alter or update information at any time without prior notice & it is theresponsibility of the specifier and/or the project manager to insure that they have the current Sto details and specifications.

STO PORENSYSTEM

STO POREN PANEL (40mm cavity) SYSTEM

FLAT SOFFIT/WALL JUNCTION

PP 1026

2014