static switching modules unit
DESCRIPTION
1. The static switching modules of the JK3PSZT series are the basic building block for the construction of static capacitor banks for power factor correction purposes. These capacitor banks use thyristors instead of the classic contactors for the connection of each large group of capacitors and they are ideal in installations where the leakage current suffers quick and large fluctuations (load changes in intervals that can range from split seconds to 8 or 10 seconds). 2. The static switching units of the JK3PSZT Series have been designed to connect and disconnect capacitors in milliseconds. They can be used to build capacitors with various steps, or for the individual compensation of a load that must be compensated instantly due to connection / disconnection deficiencies, for example, in welding units, cranes, lifts, etc.TRANSCRIPT
Automatic capacitor banks with static system.
JAKIJK
Power factor correctionStatic switching units (Three phase).
Automatic capacitor banks with static system.
1JKwww.jaki.com.tw
Introduction
Selection table
2
3
JK3PSZTStatic switching units (three-phase)
4
JK3PSZT-XXXXX
Dimensions 5~7
2011 JAKI Co., All Rights Reserved.
Automatic capacitor banks with static system.
2 JKwww.jaki.com.tw
Automatic capacitor banks with static system
Automatic capacitor banks with staticsystem. JK3PSZT-XXXXX
The all series capacitor banks with staticsystem have been designed for Powerfactor correction purposes innetworks with fluctuating loads.
The variations in power are relativelyfast (in milliseconds) so that the switchingoperations are carried out by thyristors,which are connected to a voltage controlboard, so that the connection anddisconnection of the capacitor is carriedout with a zero voltage difference.
Transients are prevented between theconnection and disconnection of steps,obtaining the immediate response to theload fluctuations.
Functions and advantages of capacitorbanks with a static system
The functions or advantages of thiscompensation system are as follows:
Immediate response to the compensationrequest. The response time of the Powerfactor correction can be of a single networkfrequency cycle, thus achieving an almostinstantaneous compensation.
Elimination of start-up transients produc-ed by the capacitor's connection. The conn-ection takes place when the voltage networkmatches that of the capacitor when it is par-tially or totally loaded.
The lack of transients in the connection allo-ws us to eliminate gaps, flicker and any otheralteration generated by the connection's tran-sient.
Limited switching operations
Lower wear of capacitors and switching elem-ents, due to the elimination of transients andthe total absence of mobile mechanical parts.This is how we can greatly increase the work-ing life of the unit, as compared to conventio-nal electromechanical contactor units.
Connection of a static capacitor bankStatic capacitor banks are usually connectedto the general switchboard or secondary swit-chboards in the case of large-scale installatio-ns.
Reg
ula
tio
n m
od
e
Time(s)Fig.1
STATIC REGULATION
CONVENTIONAL REGULATION
20ms 8s
2011 JAKI Co., All Rights Reserved.
Automatic capacitor banks with static system.
3JKwww.jaki.com.tw
Product selection table
Equipment
10KVAR/240VAC20KVAR/440VAC24KVAR/480VAC22KVAR/525VAC29KVAR/600VAC
ScopeType
JK3PSZT-22050,22060,22080,22100JK3PSZT-48050,48060,48080,48100JK3PSZT-60050,60060,60080,60100
JK3PSZT-22125,22160JK3PSZT-48125,48160JK3PSZT-60125,48160
JK3PSZT-22180JK3PSZT-48180JK3PSZT-60180
JK3PSZT-22225,22250,22300JK3PSZT-48225,48250,48300JK3PSZT-60225,60250,60300
JK3PSZT-22350,22400JK3PSZT-48350,48400JK3PSZT-60350,60400
JK3PSZT-22035JK3PSZT-48035JK3PSZT-60035
15 to 30KVAR/240VAC29 to 58KVAR/440VAC35 to 70KVAR/480VAC31 to 63KVAR/525VAC41 to 83KVAR/600VAC
37 to 48KVAR/240VAC73 to 93KVAR/440VAC87 to 112KVAR/480VAC79 to 101KVAR/525VAC104 to 133KVAR/600VAC
54KVAR/240VAC105KVAR/440VAC126KVAR/480VAC114KVAR/525VAC150KVAR/600VAC
68 to 90KVAR/240VAC131 to 175KVAR/440VAC157 to 210KVAR/480VAC142 to 190KVAR/525VAC188 to 251KVAR/600VAC
105 to 120KVAR/240VAC204 to 234KVAR/440VAC245 to 280KVAR/480VAC222 to 253KVAR/525VAC292 to 334KVAR/600VAC
Photo
3.3kg
2
3
4
5
6
Weight
1
3.6kg
5kg
5.6kg
225A 16kg250A 17kg300A 18kg
18kg
2011 JAKI Co., All Rights Reserved.
4 JKwww.jaki.com.tw
Automatic capacitor banks with static system.
4 JKwww.jaki.com.tw
JK3PSZT-XXXXXStatic switching units (three-phase)
Description
The static switching modules of theJK3PSZT series are the basic buildingblock for the construction of staticcap-acitor banks for power factor correctionpurposes.
These capacitor banks use thyristorsinstead of the classic contactors for theconnection of each large group of capa-citors and they are ideal in installationswhere the leakage current suffers quickand large fluctuations (load changes inintervals that can range from splitseconds to 8 or 10 seconds).
Application
The static switching units of theJK3PSZT Series have been designedto connect and disconnect capacitorsin milliseconds.
They can be used to build capacitorswith various steps, or for the individ-ual compensation of a load that mustbe compensated instantly due to con-nection / disconnection deficiencies,for example, in welding units, cranes,lifts, etc.
Features
Features
Protections
Ambient conditions
Construction features
Standards
Standard voltages
Frequency
Auxiliary voltage
Overload capacity
208~240, 380~480, 500~600VAC 10%±
47~63 Hz
220VAC 15%±
1.5 n during 1 minI
Bussmann or Hinoda
90℃
Fuses
du / dt
Thermostat
di / dt RC protection at 1000 V/ sμ
100 A/ s (L=12 H, not included, it must beμ μinstalled in series with the capacitor)
Maximum ambient temperature
Maximum temperature of thedissipator
50℃
80℃
Degree of protection
IEC6015-2, EN61000-6-4, EN61000-6-2
Automatic fan Heat sink 55 start, 45 stop℃ ℃
Input control signal AC control, 220VAC 15%. Contact control.±DC control, 12-24VDC.
IP00
2011 JAKI Co., All Rights Reserved.
Automatic capacitor banks with static system.
5JKwww.jaki.com.tw
Dimensions
30mm
15
4m
m
142mm
5mm
22
0m
m
R S T
U V W
135mm
15
0m
m
142mm
P.1
30mm
FAN FAN
R S T
U V W
15
4m
m
142mm
5mm
24
3m
m
135mm
15
0m
m
142mm
P.2
2011 JAKI Co., All Rights Reserved.
4 JKwww.jaki.com.tw
Automatic capacitor banks with static system.
6 JKwww.jaki.com.tw
Dimensions
40mm
141mm
30
5m
m
FAN
R S T
U V W
133mm
19
0m
m
17
2m
m
141mm
5mm
P.3
141 mm
20
0 m
m
40mm
141mm
36
5
mm
FAN
R S T
U V W
135mm
24
0m
m
P.4
2011 JAKI Co., All Rights Reserved.
Automatic capacitor banks with static system.
7JKwww.jaki.com.tw
Dimensions
31
mm
21
0m
m
263mm
R S T
U V W
16
8m
m1
68
mm
INPUT
LOAD
242mm
6mm
40
0m
m
263mm
P.5
P.6
62 m
m2
44
mm
306mm
R S T
U V W
20
0m
m2
00
mm
INPUT
LOAD
288mm
6mm
52
7m
m
306mm
2011 JAKI Co., All Rights Reserved.
4 JKwww.jaki.com.tw
Automatic capacitor banks with static system.
8 JKwww.jaki.com.tw
Functional block Diagram
R S T
U V W
Zero point inputcontroller.
Power supply.
Error signalindicates.
Power input
Load (capacitor)
2011 JAKI Co., All Rights Reserved.
Fuse Fuse Fuse
Fuse opencheck circuit.
55°C fan wor-king circuitand overtemperaturecheck.
On the heatsink temper-ature sensor.
Automatic capacitor banks with static system.
9JKwww.jaki.com.tw
JAKI Enterprise Co., Ltd.No.11, Lane2 Rencih St.,Dali City, Taichung City41282 TaiwanTEL: +886-4-24915501FAX: +886-4-24954240www.jaki.com.tw