FAN DUTY : 1.269 m³/s Item Description Size / Quantity Unit App. Pressure Drop (Pascal) Total App. Pressure Drop (Pascal) 1 Fume Hood Total Pressure Drop 1 No. 500 500 2 Phoenix Flow Control Valve 1 No: 250 250 3 Manual/ Motorised Volume Control Dampers 1 No. 30 30 4 Back draft damper 1 No. 35 35 5 Sound Attenuator 1 No. 80 80 6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3 7 Approximate Ducting Length, 1.93 Pascal per Metre 14.2 m 1.93 Pascal per Metre 27.5 8 Approximate Ducting Length, 2.51 Pascal per Metre ( horizontal 87+35+31.5 ) 153.5 m 2.51 Pascal per Metre 385.3 9 Approximate Ducting Length, 2.51 Pascal per Metre ( vertical riser ) 48 m 2.51 Pascal per Metre 120 10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8 11 Duct & Fittings safety factor 10 % safety factor 153.60 1689.50 Static Pressure Calculations H-M2-45-24-HDE-20 Exhaust of Contaminated Lab fume air to outside. Total ESP For the fan

Upload: suchitk

Post on 01-May-2017

281 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Static Pressure

FAN DUTY : 1.269 m³/s

Item Description Size / QuantityUnit App. Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1 Fume Hood Total Pressure Drop 1 No. 500 500

2 Phoenix Flow Control Valve 1 No: 250 250

3 Manual/ Motorised Volume Control Dampers 1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3

7Approximate Ducting Length, 1.93 Pascal per

Metre14.2 m 1.93 Pascal per Metre 27.5

8Approximate Ducting Length, 2.51 Pascal per

Metre ( horizontal 87+35+31.5 )153.5 m 2.51 Pascal per Metre 385.3

9Approximate Ducting Length, 2.51 Pascal per

Metre ( vertical riser )48 m 2.51 Pascal per Metre 120

10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8

11 Duct & Fittings safety factor 10 % safety factor 153.60

1689.50

Static Pressure Calculations

H-M2-45-24-HDE-20

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 2: Static Pressure

FAN DUTY : 0.741 m³/s

Item Description Size / QuantityUnit App. Pressure Drop

(Pascal)

Total App. Pressure Drop

(Pascal)

1 Fume Hood Total Pressure Drop 1 No. 500 500

3 Phoenix Flow Control Valve 1 No: 250 250

3Manual/ Motorised Volume Control

Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6Approximate Ducting Length,0.54

Pascal per Metre (horizontal)25.2 m. 0.54 Pascal per Metre 13.6

7Approximate Ducting Length, 0.19

Pascal per Metre (horizontal )8.5 m 0.19 Pascal per Metre 1.6

8Approximate Ducting Length, 0.49

Pascal per Metre ( horizontal )4.5 m 0.49 Pascal per Metre 2.2

9Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )60 m 0.91 Pascal per Metre 54.6

10Approximate Ducting Length, 0.91

Pascal per Metre ( vertical )25 m 0.91 Pascal per Metre 22.8

11Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )67 m 0.91 Pascal per Metre 61

Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )13 m 0.91 Pascal per Metre 11.8

12 Approximate Duct Fittings 20 % of Duct pressure drop 36.2

13 Duct & Fittings safety factor 10 % safety factor 109.80

1208.6

H-M2-45-24-HDE-15

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 3: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

58 m.2.69 Pascal per

Metre156

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

20 m2.69 Pascal per

Metre53.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.4

11Duct & Fittings safety

factor10 % safety factor 122.70

1350.2

H-M2-45-24-HDE-01

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 4: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

62 m.2.69 Pascal per

Metre166.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

22 m2.69 Pascal per

Metre59.2

9 Approximate Duct Fittings20 % of Duct

pressure drop58.7

10Duct & Fittings safety

factor10 % safety factor 124.70

1371.7

H-M2-45-24-HDE-02

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 5: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

20 m.2.69 Pascal per

Metre53.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

38 m2.69 Pascal per

Metre102.2

9 Approximate Duct Fittings20 % of Duct

pressure drop44.7

10Duct & Fittings safety

factor10 % safety factor 116.30

1279.3

H-M2-45-24-HDE-04

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 6: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1353.1

H-M2-45-24-HDE-05

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 7: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 123.10

1353.8

H-M2-45-24-HDE-06

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 8: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 123.10

1353.8

H-M2-45-24-HDE-07

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 9: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop54.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1347.1

H-M2-45-24-HDE-08

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 10: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop54.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1347.1

H-M2-45-24-HDE-09

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 11: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

34 m.2.69 Pascal per

Metre91.5

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

36 m2.69 Pascal per

Metre96.8

9 Approximate Duct Fittings20 % of Duct

pressure drop50.1

10Duct & Fittings safety

factor10 % safety factor 119.60

1315.3

H-M2-45-24-HDE-10

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 12: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

36 m2.69 Pascal per

Metre96.8

9 Approximate Duct Fittings20 % of Duct

pressure drop48

10Duct & Fittings safety

factor10 % safety factor 118.30

1301.1

H-M2-45-24-HDE-11

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 13: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

18 m.2.69 Pascal per

Metre48.4

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

53 m2.69 Pascal per

Metre142.6

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

32 m2.69 Pascal per

Metre86.1

9

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

75 m2.69 Pascal per

Metre201.8

10 Approximate Duct Fittings20 % of Duct

pressure drop95.7

11Duct & Fittings safety

factor10 % safety factor 146.90

1616.5

H-M2-45-24-HDE-14

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 14: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

50 m.2.69 Pascal per

Metre134.5

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

6.5 m2.69 Pascal per

Metre17.5

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

75 m2.69 Pascal per

Metre201.8

9 Approximate Duct Fittings20 % of Duct

pressure drop70.8

10Duct & Fittings safety

factor10 % safety factor 132.00

1451.6

H-M2-45-24-HDE-13

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 15: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

20 m.2.69 Pascal per

Metre53.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

4.5 m2.69 Pascal per

Metre12.1

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

12 m2.69 Pascal per

Metre32.3

9 Approximate Duct Fittings20 % of Duct

pressure drop19.6

10Duct & Fittings safety

factor10 % safety factor 101.30

1114.1

H-M2-45-24-HDE-03

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 16: Static Pressure

FAN DUTY : 0.575 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.37 Pascal per

Metre (horizontal)

90 m.2.37 Pascal per

Metre213.3

7

Approximate Ducting

Length, 2.37 Pascal per

Metre (vertical )

50 m2.37 Pascal per

Metre118.5

8

Approximate Ducting

Length, 2.37 Pascal per

Metre ( horizontal )

42 m2.37 Pascal per

Metre99.5

9

Approximate Ducting

Length, 2.37 Pascal per

Metre ( horizontal )

35 m2.37 Pascal per

Metre82.9

10 Approximate Duct Fittings20 % of Duct

pressure drop102.8

11Duct & Fittings safety

factor10 % safety factor 151.20

1663.2

H-M2-45-24-HDE-12

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 17: Static Pressure

FAN DUTY : 0.844 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

28 m.0.91 Pascal per

Metre25.5

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

23 m0.91 Pascal per

Metre20.9

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

25 m0.91 Pascal per

Metre22.8

9

Approximate Ducting

Length, 1.17 Pascal per

Metre ( horizontal )

15 m1.17 Pascal per

Metre17.6

10 Approximate Duct Fittings20 % of Duct

pressure drop17.4

11Duct & Fittings safety

factor10 % safety factor 99.90

1099.1

H-M2-45-24-HDE-21

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 18: Static Pressure

FAN DUTY : 0.634 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

25 m.0.91 Pascal per

Metre22.8

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

64 m0.91 Pascal per

Metre58.2

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

14 m0.91 Pascal per

Metre12.7

9

Approximate Ducting

Length, 1.31 Pascal per

Metre ( horizontal )

13 m1.31 Pascal per

Metre17

10 Approximate Duct Fittings20 % of Duct

pressure drop22.14

11Duct & Fittings safety

factor10 % safety factor 102.78

1130.6

H-M2-45-24-HDE-23

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 19: Static Pressure

FAN DUTY : 0.634 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

17.5 m.0.91 Pascal per

Metre15.9

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

65 m0.91 Pascal per

Metre59.2

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

14 m0.91 Pascal per

Metre12.7

9

Approximate Ducting

Length, 1.31 Pascal per

Metre ( horizontal )

13 m1.31 Pascal per

Metre17

10 Approximate Duct Fittings20 % of Duct

pressure drop20.96

11Duct & Fittings safety

factor10 % safety factor 102.08

1122.8

H-M2-45-24-HDE-22

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 20: Static Pressure

FAN DUTY : 0.844 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

19 m.0.91 Pascal per

Metre17.3

7

Approximate Ducting

Length, 0.18 Pascal per

Metre (horizontal)

3 m0.18 Pascal per

Metre0.5

8

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizonta )

81 m0.65 Pascal per

Metre52.7

9

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizontal )

66 m0.65 Pascal per

Metre42.9

10

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizontal )

13 m0.65 Pascal per

Metre8.5

11

Approximate Ducting

Length, 0.65 Pascal per

Metre (vertical )

33 m0.65 Pascal per

Metre21.5

12 Approximate Duct Fittings20 % of Duct

pressure drop28.7

13Duct & Fittings safety

factor10 % safety factor 106.71

1173.8

H-M2-45-24-HDE-16

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 21: Static Pressure

FAN DUTY : 0.951 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

27 m.0.91 Pascal per

Metre24.6

7

Approximate Ducting

Length, 0.95 Pascal per

Metre (horizontal)

52 m0.95 Pascal per

Metre49.4

8

Approximate Ducting

Length, 0.95 Pascal per

Metre ( horizonta )

25 m0.95 Pascal per

Metre23.8

9

Approximate Ducting

Length, 0.95 Pascal per

Metre ( horizontal )

37 m0.95 Pascal per

Metre35.2

10

Approximate Ducting

Length, 0.95 Pascal per

Metre ( vertical )

50 m0.95 Pascal per

Metre47.5

11

Approximate Ducting

Length, 0.81 Pascal per

Metre (horizontal )

13 m0.81 Pascal per

Metre10.5

12 Approximate Duct Fittings20 % of Duct

pressure drop38.2

13Duct & Fittings safety

factor10 % safety factor 112.42

1236.6

H-M2-45-24-HDE-19

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 22: Static Pressure

FAN DUTY : 0.899 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 1.93 Pascal per

Metre (horizontal)

10.5 m.1.93 Pascal per

Metre20.3

7

Approximate Ducting

Length, 1.93 Pascal per

Metre (vertical)

23 m1.93 Pascal per

Metre44.4

8

Approximate Ducting

Length, 1.93 Pascal per

Metre ( horizontal )

35 m1.93 Pascal per

Metre67.6

9

Approximate Ducting

Length, 1.93 Pascal per

Metre ( horizontal )

30 m1.93 Pascal per

Metre57.9

10

Approximate Ducting

Length, 1.93 Pascal per

Metre ( vertical )

27 m1.93 Pascal per

Metre52.1

11

Approximate Ducting

Length, 1.31 Pascal per

Metre (horizontal )

13 m1.31 Pascal per

Metre17

12 Approximate Duct Fittings20 % of Duct

pressure drop51.8

13Duct & Fittings safety

factor10 % safety factor 120.61

1326.7

H-M2-45-24-HDE-18

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 23: Static Pressure

FAN DUTY : 1.864 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

1 Grille (450x600) 1 No. 50

2350x200 Ducting, 0.32

Pa/m6 m

0.32 Pascal per

Metre

3Phoenix Flow Control

Valve1 No: 250 Pascal

4 Sound Attenuator 1 No. 80

5200x150 Ducting, 0.95

Pa/m4.5 m

0.95 Pascal per

Metre

5300x250 Ducting, 0.47

Pa/m1.6 m

0.47 Pascal per

Metre

6 300x250 Ducting, 0.8 Pa/m 95 m0.8 Pascal per

Metre

7Motorised Fire Dampers/

Fire damper4 No. 30 Pascal

8300x250 Ducting, 0.93

Pa/m4 m

0.93 Pascal per

Metre

8 300x250 Ducting, 1.5 Pa/m 5 m1.5 Pascal per

Metre

7 Motorised Fire Dampers 1 No. 30 Pascal

8 300x250 Ducting, 2.2 Pa/m 2.5 m2.2 Pascal per

Metre

8 300x250 Ducting, 2.9 Pa/m 11 m2.9 Pascal per

Metre

8400x300 Ducting, 1.87

Pa/m4 m

1.87 Pascal per

Metre

8 400x300 Ducting, 2.3 Pa/m 2 m2.3 Pascal per

Metre

8 400x300 Ducting, 3.2 Pa/m 20 m3.2 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (vertical)14 m

2.88 Pascal per

Metre

H-PL-45-21-HDE-03A / 03B

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Page 24: Static Pressure

8500x300 Ducting, 2.88

Pa/m (horizontal diversion)25 m

2.88 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (vertical)32.5 m

2.88 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (horizontal)13 m

2.88 Pascal per

Metre

8400x400 Ducting, 2.88

Pa/m (horizontal)7 m

2.88 Pascal per

Metre

NRD 1 No: 35 Pascal

12 Approximate Duct Fittings20 % of Duct

pressure drop

13Duct & Fittings safety

factor10 % safety factor

Total ESP For the fan

Page 25: Static Pressure

Total App. Pressure

Drop (Pascal)

50

1.9

250

80

4.3

0.8

76

30

3.7

7.5

30

5.8

31.9

7.4

4.6

64

40.32

H-PL-45-21-HDE-03A / 03B

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Page 26: Static Pressure

72

93.6

37.5

20.2

35

94.3

104.08

1144.9

Page 27: Static Pressure

Sn Fan Ref. Location Flow Rate (m³/s)

1 H-M2-45-24-HDE-01 Roof 0.382

2 H-M2-45-24-HDE-02 Roof 0.382

3 H-M2-45-24-HDE-03 Roof 0.382

4 H-M2-45-24-HDE-04 Roof 0.382

5 H-M2-45-24-HDE-05 Roof 0.382

6 H-M2-45-24-HDE-06 Roof 0.382

7 H-M2-45-24-HDE-07 Roof 0.382

8 H-M2-45-24-HDE-08 Roof 0.382

9 H-M2-45-24-HDE-09 Roof 0.382

10 H-M2-45-24-HDE-10 Roof 0.382

11 H-M2-45-24-HDE-11 Roof 0.382

12 H-M2-45-24-HDE-12 Roof 0.575

13 H-M2-45-24-HDE-13 Roof 0.382

14 H-M2-45-24-HDE-14 Roof 0.382

15 H-M2-45-24-HDE-15 Roof 0.741

16 H-M2-45-24-HDE-16 Roof 0.846

17 H-M2-45-24-HDE-17 Roof 0.951

18 H-M2-45-24-HDE-18 Roof 0.899

19 H-M2-45-24-HDE-19 Roof 0.951

20 H-M2-45-24-HDE-20 Roof 1.269

21 H-M2-45-24-HDE-21 Roof 0.846

22 H-M2-45-24-HDE-22 Roof 0.634

23 H-M2-45-24-HDE-23 Roof 0.634