standby generators
TRANSCRIPT
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-1
c o n t e n t sGenerator Features 18-2 – 18-3Industry Leading System Controls 18-4Catalog Logic — Easy Order Selection Guide 18-5NEW—Optimus Series Air Cooled Generators 18-6Air Cooled Standby Generators 18-7Liquid Cooled Standby Generators 18-8 – 18-12Single-Phase Transfer Switches 18-13 – 18-14Three-Phase Transfer Switches 18-15Portable Generators 18-16Generator Ready Load Center 18-17 – 18-18Manual Transfer Interlock Kits 18-19 – 18-20Standby Generator Ratings / Maintenance Kits / Accessories 18-21Cellular Remote Monitoring 18-22Diesel Generator Introduction 18-23Protector™ Series Automatic Standby Diesel Generators 18-24 – 18-25SM & SL Type Transfer Switches 18-26Accessories for Diesel Generators 18-27Pre-order checklist 18-28Easy Order Selection Guide 18-29Additional Information 18-30
Scan to connect online to the most up-to-date version of this Section of SPEEDFAX.
Liquid cooled generator
Standard air cooled generator
Transfer switch
Standby Generators SPEEDFAXTM 2017 Section
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-2
Standby Power SystemsAir Cooled Generator Features
Generator Features
Generator back view
Fuel line connection
A section of UL or AGA approved flexible fuel line is required to protect the rigid fuel line connections against generator vibration. 1' flexible fuel line connector is included.
New Base Pad
Air cooled units will now be rated for direct-to-dirt mounting.
Wind resistant housing
150 MPH wind resistant design on both steel and aluminum units, ASCE 7 Standards. Electrostatically applied texturedepoxy paint for added durability.
Exhaust enclosure
Verify spacing with local code and inspector, prior to installation. Typically, the generator must be placed awayfrom any opening in the house due to exhaust regulationsfrom NFPA guidelines.
Oil dipstick, low oil switch, high temperature switch,oil filter, oil drain hose
Break in periods are not required on Siemens standby gen-erators to initiate the warranty, but are recommended.
Natural gas/liquid propane fuel setup
The 9-22kW units ship from the factory ready for use with natural gas. The conver-sion to propane is as simple as turning a knob. No tools required!
Substructure
Galvannealed substructure for excellent rust protection.
Snap-in cover plate
Easy access for remote wireless monitor. Refer to page 12 for monitor offering.
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-3
Standby Power SystemsAir Cooled Generator Features
Larger battery compartment
Batteries are not included and must be purchased separately.The recommended battery is a 26 frame battery capable of 525-550cca.
Air filter
Prolong the life of your enginethrough routine maintenance and ensure warranty requirements are met.
Maintenance is recommended annually or every 200 hours.
Refer to page 12 for mainte-nance kit offerings.
Electrical connections
All connections available in one single location internally that allows for easy visibility and connection.
Removable side panel
Giving technicians easier access to electrical connections, fuel, and battery installation. Saves consumers time and money.
LED indicator lightsincluded on 8-22 kW• Green = Generator OK• Yellow = Maintenance needed (not on 8-14kW)• Red = Contact dealer
New featuresNew Brighter LED indicator lights
Door improvement with lip to prevent water from leaking in.
Control panelEvolution controller functions include monitoring utility power, triggering the automatic transfer switch, starting and stopping the generator, exercising the generator, and monitoring the generator for any system faults. Combines the voltage regulator, engine control board and battery charger into one single item. Brings more functionality to the generator control for a smarter power solution
Product Activation is required on all Evolution Controlled Models to engage automatic transfer mode. Generator will operate in manual mode until activation code is entered. Easy, one-time activation process can be completed in shop or on-site.
Data label is located inside the generator. Serial number is required for generator activation.
New Optimus Series units will have the following features:n Upgraded battery charger from 3.5
to 5 amp, paired with an updated algorithm to work with an AGM or lead acid battery
n Quiet Test standard on 9-22kW air cooled unitsn 16-22kW units will have lower RPM exercise (1950 RPM) to
facilitate quieter exercisingn LEDs will blink during utility loss
n Will include consumer instructions on screen to reset fault prior to contacting dealer to reduce nuisance service calls
n Improved common alarm connection and usage information
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-4
Industry Leading System Controls
Evolution controller for air cooled generators
Standby Power SystemsAir Cooled Generator Controller
Air Cooled Evolution Controller for Optimus Units Orange text indicates a new or changed feature from previous version of Evolution controller
Display Alarms Dealer service features/menus Key miscellaneous
üLCD Display üLED Backlit Membrane Keypad üTime & Date üAlarm Log üRun Log üMaintenance Log & Reminders üSet Exercise via Display üRun Hour Display üBattery Condition üQuad-lingual Display (Portuguese) üQuiet Test Selection üFuel Selection üElimination of "Inspect" prompt üCapture of Dismissal of Maintenance Reminder Prompt üVariable Start Up Delay between 2-1500 seconds üLEDs will blink during utility loss
üGenerator Over Voltage üGenerator Under Voltage üUnderspeed/Fail to Xfer üLow Battery Voltage üHigh Engine Temperature üLow Oil Pressure üOvercrank üOverspeed üRPM Sensor Loss üInternal Fault üLow Fuel Pressure (QT only) üWiring Error üExternal common fault alarm üOverload Warning/Cooldown üLow Battery/Battery Problem üCharger Warning üCharger Missing AC üStepper Over Current üFuse Problem üRadio Signal Indication üImproved common alarm connection and usage information
üImproved smart battery charger, upgraded from 3.5 to 5 amps üBattery Voltage üUSB Port üGenerator Output Voltage üOutput Frequency & RPM üUtility Input Voltage üSoftware & Hardware Version üBoot Loader Version üCommand Status üVoltage Calibration üParameter Group üVotage Code üMaintenance Hard Reset üEdit Run Hours (controller replacement) üMaintenance Schedule üService/Monitoring Port üSerial Number üDebug üUpdateable Firmware Prompts üBrown Out Voltage üWill include consumer instructions on screen to reset fault prior to contacting dealer
üCompatible with Cellular Monitoring üProduct Activation üVoltage Regulator üExercise not set error ü16-22kW will have lower RPM exercise (1950rpm)
•Certain faults will also have an associated E-code after the general message to specifically call out what the exact problem for more exact/quick diagnosis.
Type "E" Evolution Digital LCD ControllerFunctions include monitoring utility power, triggering the automatic transfer switch, starting and stopping the generator, exercising the generator, and monitoring the generator for any system faults.
High Voltage Shutdown Shuts down the generator at >130%
rated voltage for 200 milliseconds or >110% for 5 seconds to better protect home owner appliances or connected items.
n Low Voltage ShutdownShuts down the generator at <60% voltage for 5 seconds to better protect home owners appliances or connected items.
n Internal Fault ShutdownShuts down the generator when a failure is detected within the Evolution Controller for more protection and easier diagnostics.
n Battery Sentinel Monitors the battery and charging system
to indicate that the battery is trending towards failure or that it has failed.
n Event Log All generators 8-22 kW feature a full
event log capable of recording 50 events.
n Smart Battery Charger Only delivers a charge to the battery
when needed. Battery charge depends on ambient air temperature. Upgraded charger from 3.5 to 5 amp; updated algorithm to work with an AGM or lead acid battery.
n Voltage Regulation With the combination into the
Evolution Controller, the voltage regulation delivers an industry leading voltage regulation +/- 1%.
n Product Activation Requires each generator to be
activated via website or phone before automatic function is enabled - Allows a warranty activation start point for every generator sold.
n External Common Fault Alarm The Evolution Controller has a
provision to connect to a set of contacts that will allow for a common alarm when any of the generator shut downs occur- This will allow individuals to connect into security systems, home automation systems or simply drive a different alarm within a home or business.
n Adjustable generator start time When utility fails, the control is factory
set to delay 10 seconds prior to starting the engine. There is also the capability to change the delay time between 2-1500 seconds.
n Incorrect Wiring Error Eliminates the potential of damaging
the Evolution Controller if it is not connected properly, a warning message is displayed that must be corrected before the controller is allowed to be fully operational.
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-5
Air Cooled and Liquid Cooled Generators
Standby Power Generators kW ratingsab
Voltage R = 120/240V, 1Ø C = 208/120V, 3Ø J = 240/120V, 3Ø I = 480/277V, 3Ø
Fuel G = Natural Gas P = Liquid Propane Vapor B = Accepts Both
Enclosure A = Aluminum
Speed Left Blank = 3600rpm L = 1800rpm
Emissions Compliant Optioncd E = Catalyst
Air
Co
ole
d
ASGM
9 R B A11 R B A16 R B A20 R B A22 R B A
Liq
uid
Co
ole
d SGE
22 R, C, J B A L25 R, C, J B A27 R, C, J B A L30 R, C, J B A32 R, C, J, I B A L36 R, C, J, I B A38 R, C, J, I B A L45 R, C, J, I B A E48 R, C, J, I B A L E60 R, C, J, I G, P A
SGN*
70 R, C, J, I G, P A L E80 R, C, J, I G, P A
100 R, C, J, I G, P A L E130 R, C, J, I G, P A E150 R, C, J, I G, P A E
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
Transfer Switches
Transfer SwitchesST = Indoor Branch CircuitSL = Outdoor Load Shedding SM = Load Management** Amp
VoltageR = 120/240V, 1ØC = 208/120V, 3ØJ = 240/120V, 3ØI = 480/277V, 3Ø
Service DisconnectBlank = NoD = Yes
Branch Circuits
ST 50 R 10C, 12C
100 R 16C
SL 100 C, J, I
200 C, J, I
400 C, J, I
600 C, J, I
800 C, J, I
SM 100 R Blank, D
150 R D
200 R Blank, D
300 R D
400 R D
600** R
800** R
** Will have Outdoor Load Shedding and Load Management Capabilities
Catalog Logic
a Battery not included for units 60kW and below.b Catalyst option available on 45, 48, and 70kW units,
catalyst factory standard on 100-150kW units.
c All units 30kW and below do not fall under CA/MA emis-sions standards, therefore are not required to have a catalyst.
d All units 32kW and above must contain emissions catalyst in order to be installed in California/Massachusettes (part number ending with “E”).
Standby Power SystemsAir Cooled and Liquid Cooled Generator Catalog Logic
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-6
NEW Siemens Optimus Series Air Cooled GeneratorsSiemens is happy to introduce the new Optimus line of air cooled generators, launching in October 2016. This launch introduces an entire new line of air cooled products with several changes that highlight ease of installation, and end-user functionality. A synopsis of these changes can be found below.
Standby Power SystemsAir Cooled Generator Controller
Door Alignment
Updated door alignment making access to the interior of the unit with ease.
Moved pins from side panels to the door, which eliminates the need to lift up and out, vertical removal and reinstallation only
New kW Range
9, 11, 16, 20 and 22kW
Base Changes
Allows for quicker installation, saving our consumers time and money.
Eliminates sinking and allows unit to be placed directly on ground (increased surface area by 9X).
Removable Side Panel
Giving our technicians easier access to all electrical connections, fuel and battery installation. Saving our consumers time and money.
Controller
Includes consumer introductions on screen to reset fault prior to contacting dealer to reduce nuisance service calls.
New design eliminates the external connection box and GFCI. The main breaker is moved inside by the control panel.
Enclosure Changes
Aluminum enclosures to give consumers a clean, rust-free enclosure for the life of their generator.
Fuel System Changes
Integrated Sediment Trap that eliminates the need to build and install it in the field which saves time and money.
Locking System
Improved locking system to prevent interference and less pressure to open. Lock covers to prevent debris and ice intrusion
Electrical Connections
All connections available in one single location for easy visibility and connection.
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-7
9, 11, 16, 20, and 22kW Air Cooled Generator, 120/240V, Single phase
Typical load requirementsc
Description kW Description kW
Electric Heat per 1,000 ft.b 12.0 General Receptacles per 1,000 ft.b 1.0
Heat Pump Elements per 1,000 ft.b 7.0 Dishwasher 1.5
Dryer 5.5 Blow Dryer 1.3
Hot Tub 5.0 AC (per ton) 1.0
Range Oven 5.0 Microwave 1.0
Hot Water Heater 4.5 Toasters 1.0
Stove Top Burner 1.5 Lighting per 1,000 ft.b 0.8
Current Catalog Numbers
Catalog Numbera kW Ratingc Enclosure Type
Engine Size Weight (lbs.) Dimensions (in.)
Maintenance Kits
ASGM009RBA 9 Aluminum 410CC 360
48 x 25 x 29
GENMKIT19
ASGM011RBA 11 Aluminum 530CC 428 GENMKIT20
ASGM016RBA 16 Aluminum 992CC 448 GENMKIT21
ASGM020RBA 20 Aluminum 999CC 516 GENMKIT22
ASGM022RBA 22 Aluminum 999CC 526 GENMKIT22
a All units ship ready for use with natural gas, minor adjustments required for liquid propane vapor use.
b Check local code requirements.
c Battery not included with air cooled models 8-22kw. Refer to page 12 for 26R battery.
Standard featuresn UL 2200 Listed
n Four-cycle industrial engines provide durable,reliable, long life
n Operate on either natural gas or propane vapora
n Composite mounting pad approved to eliminateneed to pour concrete padb
n Automatic high temperature, low oil pressure,over speed, and over crank shut down
n Low battery voltage indicator
n Standard safety fuse
n Provided with Type “E” Evolution controller
n Provided with the upgraded Optimus version of the Evolution controller
Standby Power SystemsAir Cooled Generators
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-8
1800, 2300, and 3600 RPM Liquid Cooled Generators, Single Phase and 3 Phase
Standard featuresn UL 2200 Listed
n Meets EPA Emission Regulations (units 45kW and above must have emissions catalyst to be used in CA/MA)
n Operate on either natural gas or propane vapor
n Automatic high temperature, low coolant, low oil pressure, and over speed shutdown
n Automatic voltage regulator with over voltage protection
n Isochronous Electronic Governor
n Safety fuse included
n Smart Battery Charger
n Quiet run weekly self test
n Provided with type "E" evolution controller (8-60kW units) or type "N" Nexus controller (70-150kW)
n Compatible with "SE", "SL", and "SM" type automatic transfer switches
Catalog Numbers
Standby Power Generators kW ratingscd
VoltageR =120/240v, 1 phaseC = 208/120v, 3 phaseJ = 240/120v, 3 phaseI = 480/277v, 3 phase
FuelG = Natural GasP = Liquid Propane VaporB = Accepts Both
EnclosureS = SteelA = Aluminum
SpeedBlank = 3600rpm L = 1800rpm
Emissions CompliantOptionab
E = Catalyst
Air
Co
ole
d
ASGM
8 R B A
11 R B A
16 R B A
20 R B A
22 R B A
Liq
uid
Co
ole
d SGE
22 R, C, J B A L
25 R, C, J B S
27 R, C, J B A L
30 R, C, J B A
32 R, C, J, I B A L
36 R, C, J, I B A
38 R, C, J, I B A L
45 R, C, J, I B A E
48 R, C, J, I B A L E
60 R, C, J, I G, P A
SGN*
70 R, C, J, I G, P A L E
80 R, C, J, I G, P A
100 R, C, J, I G, P A L E
130 R, C, J, I G, P A E
150 R, C, J, I G, P A E
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
a All units 38kW and below do not fall under CA/MA emissions standards, therefore are not required to have a catalyst
b All units 45kW and above must contain emissions catalyst to be installed in California/Massachusettes (part no. ending with “E”)
c Battery not included for units 60kW and belowd Catalyst option available on 45, 48, and 70kW units,
catalyst factory standard on 100-150kW units
Denotes speed of 2300RPM
Standby Power SystemsLiquid Cooled Generators
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-9
120/240V Single-Phase Liquid Cooled Generators
Catalog Number kW Rating
Fuel Type Enclosure
Engine Size (Liters)
Speed (RPM)
Amp Output
Weight (lbs.) Dimensions (in.)
SGE022RBAL 22 Both Aluminum 2.4 1800 92 955 62.2 x 30.6 x 38.6
SGE025RBA 25 Both Aluminum 1.5 3600 104 835 62.2 x 30.6 x 38.6
SGE027RBAL 27 Both Aluminum 2.4 1800 113 955 62.2 x 30.6 x 38.6
SGE030RBA 30 Both Aluminum 1.5 3600 125 865 62.2 x 30.6 x 38.6
SGE032RBAL 32 Both Aluminum 2.4 1800 133 1271 76.8 x 35 x 46.1
SGE036RBA 36 Both Aluminum 2.4 3600 150 1202 76.8 x 35 x 46.1
SGE038RBAL 38 Both Aluminum 2.4 1800 158 1271 76.8 x 35 x 46.1
SGE045RBA 45 Both Aluminum 2.4 3600 188 1260 76.8 x 35 x 46.1
SGE045RBAE 45 Both Aluminum 2.4 3600 188 1260 76.8 x 35 x 46.1
SGE048RBAL 48 Both Aluminum 5.4 1800 200 1555 76.8 x 35 x 46.1
SGE048RBALE 48 Both Aluminum 5.4 1800 200 1555 76.8 x 35 x 46.1
SGE060RGA 60 Gas Aluminum 2.4 3600 250 1230 76.8 x 35 x 46.1
SGE060RPA 60 Liquid Propane Aluminum 2.4 3600 250 1230 76.8 x 35 x 46.1
SGN070RGAL 70 Gas Aluminum 6.8 1800 279 2040 97 x 37 x 47
SGN070RGALE 70 Gas Aluminum 6.8 1800 279 2040 97 x 37 x 47
SGN070RPAL 70 Liquid Propane Aluminum 6.8 1800 279 2040 97 x 37 x 47
SGN070RPALE 70 Liquid Propane Aluminum 6.8 1800 279 2040 97 x 37 x 47
SGN080RGA 80 Gas Aluminum 5.4 3600 320 2075 116 x 37 x 55
SGN080RPA 80 Liquid Propane Aluminum 5.4 3600 320 2075 117 x 37 x 55
SGN100RGALE 100 Gas Aluminum 6.8 2300 417 2075 118 x 37 x 55
SGN100RPALE 100 Liquid Propane Aluminum 6.8 2300 417 2075 119 x 37 x 55
SGN130RGAE 130 Gas Aluminum 6.8 3600 542 2699 120 x 37 x 55
SGN130RPAE 130 Liquid Propane Aluminum 6.8 3600 542 2699 121 x 37 x 55
SGN150RGAE 150 Gas Aluminum 6.8 3600 600 2492 122 x 37 x 55
SGN150RPAE 150 Liquid Propane Aluminum 6.8 3600 600 2492 123 x 37 x 55
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
Compatible Transfer SwitchCatalog Number
SM100R
SM100RD
SM150RD
SM200R
SM200RD
SM300RD
SM400R
SM400RD
SM600R
SM800R
Liquid Cooled Generator Specifications/Compatible Transfer Switches
Standby Power SystemsLiquid Cooled Generators, 120/208V 3-Phase
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-10
120/208V 3-Phase Liquid Cooled Generators
Catalog Number kW Rating
Fuel Type Enclosure
Engine Size (Liters)
Speed (RPM)
Amp Output
Weight (lbs.) Dimensions (in.)
SGE022CBAL 22 Both Aluminum 2.4 1800 76 955 62.2 x 30.6 x 38.6
SGE025CBA 25 Both Aluminum 1.5 3600 87 835 62.2 x 30.6 x 38.6
SGE027CBAL 27 Both Aluminum 2.4 1800 94 955 62.2 x 30.6 x 38.6
SGE030CBA 30 Both Aluminum 1.5 3600 104 865 62.2 x 30.6 x 38.6
SGE032CBAL 32 Both Aluminum 2.4 1800 111 1271 76.8 x 35 x 46.1
SGE036CBA 36 Both Aluminum 2.4 3600 125 1202 76.8 x 35 x 46.1
SGE038CBAL 38 Both Aluminum 2.4 1800 132 1271 76.8 x 35 x 46.1
SGE045CBA 45 Both Aluminum 2.4 3600 156 1260 76.8 x 35 x 46.1
SGE045CBAE 45 Both Aluminum 2.4 3600 156 1260 76.8 x 35 x 46.1
SGE048CBAL 48 Both Aluminum 5.4 1800 167 1555 76.8 x 35 x 46.1
SGE048CBALE 48 Both Aluminum 5.4 1800 167 1555 76.8 x 35 x 46.1
SGE060CGA 60 Gas Aluminum 2.4 3600 208 1230 76.8 x 35 x 46.1
SGE060CPA 60 Liquid Propane Aluminum 2.4 3600 208 1230 76.8 x 35 x 46.1
SGN070CGAL 70 Gas Aluminum 6.8 1800 243 2040 97 x 37 x 47
SGN070CPAL 70 Gas Aluminum 6.8 1800 243 2040 97 x 37 x 47
SGN070CGALE 70 Liquid Propane Aluminum 6.8 1800 243 2040 97 x 37 x 47
SGN070CPALE 70 Liquid Propane Aluminum 6.8 1800 243 2040 97 x 37 x 47
SGN080CGA 80 Gas Aluminum 5.4 3600 278 2075 116 x 37 x 55
SGN080CPA 80 Liquid Propane Aluminum 5.4 3600 278 2075 117 x 37 x 55
SGN100CGALE 100 Gas Aluminum 6.8 2300 347 2075 118 x 37 x 55
SGN100CPALE 100 Liquid Propane Aluminum 6.8 2300 347 2075 119 x 37 x 55
SGN130CGAE 130 Gas Aluminum 6.8 3600 451 2699 120 x 37 x 55
SGN130CPAE 130 Liquid Propane Aluminum 6.8 3600 451 2699 121 x 37 x 55
SGN150CGAE 150 Gas Aluminum 6.8 3600 520 2492 122 x 37 x 55
SGN150CPAE 150 Liquid Propane Aluminum 6.8 3600 520 2492 123 x 37 x 55
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
Compatible Transfer SwitchCatalog Number
SL100C
SL200C
SL400C
SL600C
SL800C
Liquid Cooled Generator Specifications/Compatible Transfer Switches
Standby Power SystemsLiquid Cooled Generators, 120/208V 3-Phase
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-11
120/240V 3-Phase Liquid Cooled Generators
Catalog Number kW Rating
Fuel Type Enclosure
Engine Size (Liters)
Speed (RPM)
Amp Output
Weight (lbs.) Dimensions (in.)
SGE022JBAL 22 Both Aluminum 2.4 1800 66 955 62.2 x 30.6 x 38.6
SGE025JBA 25 Both Aluminum 1.5 3600 75 835 62.2 x 30.6 x 38.6
SGE027JBAL 27 Both Aluminum 2.4 1800 81 955 62.2 x 30.6 x 38.6
SGE030JBA 30 Both Aluminum 1.5 3600 90 865 62.2 x 30.6 x 38.6
SGE032JBAL 32 Both Aluminum 2.4 1800 96 1271 76.8 x 35 x 46.1
SGE036JBA 36 Both Aluminum 2.4 3600 108 1202 76.8 x 35 x 46.1
SGE038JBAL 38 Both Aluminum 2.4 1800 114 1271 76.8 x 35 x 46.1
SGE045JBA 45 Both Aluminum 2.4 3600 135 1260 76.8 x 35 x 46.1
SGE045JBAE 45 Both Aluminum 2.4 3600 135 1260 76.8 x 35 x 46.1
SGE048JBAL 48 Both Aluminum 5.4 1800 144 1555 76.8 x 35 x 46.1
SGE048JBALE 48 Both Aluminum 5.4 1800 144 1555 76.8 x 35 x 46.1
SGE060JGA 60 Gas Aluminum 2.4 3600 180 1230 76.8 x 35 x 46.1
SGE060JPA 60 Liquid Propane Aluminum 2.4 3600 180 1230 76.8 x 35 x 46.1
SGN070JGAL 70 Gas Aluminum 6.8 1800 210 2040 97 x 37 x 47
SGN070JPAL 70 Gas Aluminum 6.8 1800 210 2040 97 x 37 x 47
SGN070JGALE 70 Liquid Propane Aluminum 6.8 1800 210 2040 97 x 37 x 47
SGN070JPALE 70 Liquid Propane Aluminum 6.8 1800 210 2040 97 x 37 x 47
SGN080JGA 80 Gas Aluminum 5.4 3600 249 2075 116 x 37 x 55
SGN080JPA 80 Liquid Propane Aluminum 5.4 3600 249 2075 117 x 37 x 55
SGN100JGALE 100 Gas Aluminum 6.8 2300 301 2075 118 x 37 x 55
SGN100JPALE 100 Liquid Propane Aluminum 6.8 2300 301 2075 119 x 37 x 55
SGN130JGAE 130 Gas Aluminum 6.8 3600 391 2699 120 x 37 x 55
SGN130JPAE 130 Liquid Propane Aluminum 6.8 3600 391 2699 121 x 37 x 55
SGN150JGAE 150 Gas Aluminum 6.8 3600 451 2492 122 x 37 x 55
SGN150JPAE 150 Liquid Propane Aluminum 6.8 3600 451 2492 123 x 37 x 55
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
Compatible Transfer SwitchCatalog Number
SL100J
SL200J
SL400J
SL600J
SL800J
Liquid Cooled Generator Specifications/Compatible Transfer Switches
Standby Power SystemsLiquid Cooled Generators, 120/240V 3-Phase
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-12
277/480V 3-Phase Liquid Cooled Generators
Catalog Number kW Rating
Fuel Type Enclosure
Engine Size (Liters)
Speed (RPM)
Amp Output
Weight (lbs.) Dimensions (in.)
SGE032IBAL 32 Both Aluminum 2.4 1800 48 1271 76.8 x 35 x 46.1
SGE036IBA 36 Both Aluminum 2.4 3600 54 1202 76.8 x 35 x 46.1
SGE038IBAL 38 Both Aluminum 2.4 1800 57 1271 76.8 x 35 x 46.1
SGE045IBA 45 Both Aluminum 2.4 3600 68 1260 76.8 x 35 x 46.1
SGE045IBAE 45 Both Aluminum 2.4 3600 68 1260 76.8 x 35 x 46.1
SGE048IBAL 48 Both Aluminum 5.4 1800 72 1555 76.8 x 35 x 46.1
SGE048IBALE 48 Both Aluminum 5.4 1800 72 1555 76.8 x 35 x 46.1
SGE060IGA 60 Gas Aluminum 2.4 3600 90 1230 76.8 x 35 x 46.1
SGE060IPA 60 Liquid Propane Aluminum 2.4 3600 90 1230 76.8 x 35 x 46.1
SGN070IGAL 70 Gas Aluminum 6.8 1800 105 2040 97 x 37 x 47
SGN070IPAL 70 Gas Aluminum 6.8 1800 105 2040 97 x 37 x 47
SGN070IGALE 70 Liquid Propane Aluminum 6.8 1800 105 2040 97 x 37 x 47
SGN070IPALE 70 Liquid Propane Aluminum 6.8 1800 105 2040 97 x 37 x 47
SGN080IGA 80 Gas Aluminum 5.4 3600 120 2075 116 x 37 x 55
SGN080IPA 80 Liquid Propane Aluminum 5.4 3600 120 2075 117 x 37 x 55
SGN100IGALE 100 Gas Aluminum 6.8 2300 150 2075 118 x 37 x 55
SGN100IPALE 100 Liquid Propane Aluminum 6.8 2300 150 2075 119 x 37 x 55
SGN130IGAE 130 Gas Aluminum 6.8 3600 195 2699 120 x 37 x 55
SGN130IPAE 130 Liquid Propane Aluminum 6.8 3600 195 2699 121 x 37 x 55
SGN150IGAE 150 Gas Aluminum 6.8 3600 225 2492 122 x 37 x 55
SGN150IPAE 150 Liquid Propane Aluminum 6.8 3600 225 2492 123 x 37 x 55
*Prefix will be changing to “SGE” on 70-150kW liquid cooled units to reflect moving to the evolution controller. Expected to launch late 2017/early 2018
Compatible Transfer SwitchCatalog Number
SL100I
SL200I
SL400I
SL600I
SL800I
Liquid Cooled Generator Specifications/Compatible Transfer Switches
Standby Power SystemsLiquid Cooled Generators, 277/480V 3-Phase
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-13
SM Type transfer switches
SM Type Transfer Switches
Catalog Number Amp
Branch Circuits
KA Rating (in Amps)
Weight (lbs.) Dimensions (in.) Enclosure Type
SM100R100
10,000
20 20 x 14.6 x 7.09 Aluminum
SM100RD 23 21 x 14.6 x 7.09 Aluminum
SM150RD 150 39 30 x 13.5 x 6.3 Aluminum
SM200R200
20 20 x 14.6 x 7.09 Aluminum
SM200RD 39 30 x 13.5 x 6.3 Aluminum
SM300RD 300
22,000
140 48 x 21.82 x 10.06 Aluminum
SM400R400
133 36 x 24 x 10.6 Aluminum
SM400RD 140 48 x 21.82 x 10.06 Aluminum
* kW rating is from 8 to 20kW on each switch listed/NEMA 3 rating for each.
Features and ratingsn 100-400A
n Open transition
n Cover more circuits with a smaller generator
n Cover every circuit when paired with a higher kW generator
n Outdoor NEMA 3R aluminum enclosure
n Service rated and non-service rated
n Compatible with Evolution and NEXUS controllers
n Add additional PMM modules (6186) and manage up to four more large loads on single phase SE type transfer switches
Transfer switches provide the mechanism for transferring power between utility and generator service. Engineered with Digital Power Management (DPM) technology. 100-400A single phase SM Type transfer switches have the ability to cycle on and off two air conditioners without adding additional components, allowing for a smaller generator to cover more circuits than when paired with a standard transfer switch.
Transfer SwitchesSM Type Single-Phase
SM modelsSMD models
(service rated)
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-14
*Disconnect included
ST Type Transfer Switches
Catalog Number Amp
kW rating
Branch circuits
KA rating (Amp)
Weight (lbs.) Dimensions (in.)
NEMA rating Enclosure
ST050R10C 50
8 10
10,000
5722.5 x 15.4 x 3.8
1 ST
ST050R12C 11 12 61 1 ST
ST100R16C 100 16 16 68 29.25 x 12.5 x 7 1 ST
ST Type transfer switchesST type transfer switches are compatible with the Evolution and NEXUS controllers. The controller senses power outages and initiates the transfer of power to the generator via the automatic transfer switch.
Features and ratingsn 30 ft. pre-wired conduit for connecting
the transfer switch to the external connection box
n 2 ft. pre-wired conduit for moving circuits from the main panel to the transfer switch
n Pre-wired external connection box with a weatherproof conduit for generator connections
n Compatible with Evolution and NEXUS controllers
n Electrically operated, mechanically contacts for fast, positive connections
n Rated for all classes of load,100%
equipment rated, both inductive and resistive
n 160 millisecond transfer time
n 50 amps = 10 & 12 circuit, single coil design, flush mountable
n 100 amps = 14 & 16 circuit, dual coil design
n Main contacts are silver plated or silver alloy to resist welding and sticking
n Suitable for use only on air cooled products (8–17 kW)
n Open transition
n Express install kit included
Transfer SwitchesST Type Single-Phase
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-15
Features and ratingsn 100–800A
n Outdoor NEMA 3R aluminum enclosure
n Open transition
n Compatible with Nexus controllers
n Cover more circuits with a smaller generator
n Service rated and non-service rated
n Add additional individual DLM modules (5937) and manage up to four more large loads on single phase SL type transfer switches. See page 18-19
n Cover every circuit when paired with a higher kW generator
SL Type Transfer Switches
Catalog number Amp Phase
Withstand rating (Amps)
Weight (lb.) Dimensions (in.)
SL100C
100
120/208V, 3Ø 10,000 20 24.1 x 20.2 x 7.1
SL100J 120/240V, 3Ø 14,000 53 24.1 x 20.2 x 7.1
SL100I 277/480V, 3Ø 14,000 105 36.1 x 24 x 10
SL200C
200
120/208V, 3Ø 10,000 20 24.1 x 20.2 x 7.1
SL200J 120/240V, 3Ø 25,000 53 24.1 x 20.2 x 7.1
SL200I 277/480V, 3Ø 25,000 105 48.1 x 30.1 x 13.1
SL400C
400
120/208V, 3Ø 18,000 133 36.1 x 24 x 10
SL400J 120/240V, 3Ø 18,000 133 36.1 x 24 x 10
SL400I 277/480V, 3Ø 18,000 133 36.1 x 24 x 10
SL600C
600
120/208V, 3Ø 42,000 439 66 x 36 x 21
SL600J 120/240V, 3Ø 42,000 439 66 x 36 x 21
SL600I 277/480V, 3Ø 42,000 439 66 x 36 x 21
SL800C
800
120/208V, 3Ø 65,000 469 66 x 36 x 21
SL800J 120/240V, 3Ø 65,000 469 66 x 36 x 21
SL800I 277/480V, 3Ø 65,000 469 66 x 36 x 21
SL Type transfer switchesTransfer switches provide themechanism for transferring powerbetween utility and generator service.Engineered with Digital LoadManagement (DLM) technology, 100-400A single phase SL Type transferswitches have the ability to cycle onand off two air conditioners withoutadding additional components, allowingfor a smaller generator to covermore circuits than when paired witha standard transfer switch.
Three-Phase Transfer Switches
Three phase transfer switch
Catalog Number Amp Phase
Withstand rating (Amps)
Weight (lb.) Dimensions
RTSW100G3 100 120/208V 3Ø 14,000 49 24 x 20 x 7.3
RTSW100J3 100 120/240V 3Ø 14,000 49 24 x 20 x 7.3
RTSW100K3 100 277/480V 3Ø 14,000 49 24 x 20 x 7.3
RTSW200G3 200 120/208V 3Ø 18,000 49 24 x 20 x 7.3
RTSW200J3 200 120/240V 3Ø 18,000 49 24 x 20 x 7.3
RTSW200K3 200 277/480V 3Ø 18,000 49 24 x 20 x 7.3
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-16
Portable Generators: 5.5, 6.5, 7.5, 8, 15, 17.5 kWFeatures and ratingsn Ideal for residential emergency and
job-site power
n Gasoline powered, OHV engine
n Include handles and wheels for easy movement
n Hour meter included
n Large variety of outlets
n Low noise muffler
n 2 year residential warranty
n Easily integrated into home electrical systems with Siemens breaker interlock kits (pictured below)
Portable Accessories: 5715 - Lifting Beam Kit; 6.5 kW & 8.0 kW
Refer to page 12 for Portable Maintenance Kits
Portable Generator Catalog Numbers
PG0055 PG0065 PG0075Ea PG0080Ea PG015a PG017a
Rated Power 5.5 kW 6.5 kW 7.5 kW 8 kW 15 kW 17.5 kW
Surge 6.875 kW 8 kW 9.37 kW 10 kW 22.5 kW 26.2 kW
Rated Amps @ 60Hz 120/240, 1Ø, 1.0 pf 22.9 27.1 31.2 33.3 62.5 73
Engine RPM 3600 3600 3600 3600 3600 3600
Fuel Capacity (gallons) 6.6 6.6 8 8 16 16
Dimensions (inches) 34 x 26.5 x 27.5 34 x 27 x 28 28.75 x 26.75 x 26 34 x 27 x 28 39 x 31 x 49 39 x 31 x 49
Weight (lbs) 180 172 201 192 450 475
�a Manual Electric Starter
Standby Power SystemsPortable Generators
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-17
Features:n NEMA 3R / Indoor Type 1
n 225A max rated
n Flush or surface mounting
n Fits between standard stud centers
n Tin plated copper bus bars
n 22 kAIC rated
n 120/240V, 1 Phase
n Main lug – convertible to main breaker with addition of MBK150A, MBK200A, or MBK225A
n Installation of transfer mechanism can be performed at time of generator installation
A
B
D
E
F
C
S
A
BD
EF
CSS
Traditional Installation Generator Ready Load Center with Portable Generator installation
Generator Ready Load Center with Automatic Standby generator installation
The Siemens Generator Ready Load Center can save thousands of dollars in future generator installation expenses while keeping initial expenses to a minimum. Works with an automatic standby generator or a portable generator.
Catalog No.ECSBPK01 (mechanical interlock for manual or portable generation installation)
GENTFRSWTCH (auto transfer switch for automatic standby generation installation)
Automatic Transfer Switch features:n UL Listed
n Operates automatically when connected to generator
n Transfers load from utility to generator and back to utility
n Includes: Q215 and Q2125S needed for installation
NOTE:GENTFRSWTCH is sold separately from Gen ready panel!
Generator Ready Load Center
Standby Power SystemsGenerator Ready Load Center
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-18
Generator Ready Load Centers
Amp Rating
No. of Spaces
No. of Circuits Catalog No.
Dimensions (inches)
Height Width Depth
Indoor Enclosure – NEMA Type 1
200 30 42 G3042B1200GEN 42.00 14.25 4.00
225 30 42 G3042L1225GEN 42.00 14.25 4.00
200 42 54 G4254B1200GEN 44.0 14.25 4.00
225 42 54 G4254L1225GEN 44.0 14.25 4.00
Outdoor Enclosure – NEMA Type 3R200 30 42 W3042B1200GEN 42.00 14.63 4.00
225 30 42 W3042L1225GEN 42.00 14.63 4.00
G3042L1225GEN
Install ECSBPK01for portablegenerators
Install GENTFRSWTCH for automatic standby generators
Standby Power SystemsGenerator Ready Load Center
NOTE:GENTFRSWTCH is sold separately from Gen ready panel!
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-19
Panels in which the bussing or wire forms from the meter socket land on main lugs are not acceptable for use in standby systems because turning the main breaker to “OFF” does not prevent feedback to the utility power lines. Examples of such panels include catalog numbers that start with the following letters.
MC0606L1200*MM0406L1*MC1212L1200*
Standard featuresn UL listed for use in most Siemens
load centers and meter combinations
n Suitable for use with optional standby systems in accordance with article 702 of the National Electric Code
n Corrosion resistant finish
n Easy assembly requiring no modifications to the load center or meter combination
n Remains attached to the main breakers when load center cover
Wire formsor bussing
Acceptable usage of Interlock Kits by load center/meter combination catalog numbers
Siemens Meter CombinationsMC0816B1150RTH 5 7 MC2040B1200 5 7
MC0816B1150T 5 7 MC2040B1200R 5 7
MC0816B1150TH 5 7 MC2442B1200FEC 2
MC0816B1200FCTM 2 MC2442B1200SEC 2
MC0816B1200RT 5 7 MC3040B1200SECW 5 7
MC0816B1200RTB 5 7 MC3042B1200FED 3
MC0816B1200RTH 5 7 MC3042B1200SED 3
MC0816B1200SCTM 2 MC3042B1225FED 3
MC0816B1200T 7 MC3042B1225SED 3
MC0816B1200TH 5 7 MC4040B1200SECW 5 7
MC0816B1350RLTM 5 7 MC0816B1200RJBT 8
MC0816B1400RLTM 5 7 MC0816B1150RJBT 8
MC1224B1100FEC 2 MC0816B1200RCT 8
MC1224B1100SEC 2 MC0816B1150RCT 8
MC1224B1125 1 2 MC0816B1200CT 8
MC1224B1125FEC 2 MC0816B1150CT 8
MC1224B1125SEC 2 MC2040B1150RCT 9
MC1632B1100SEC 2 MC2040B1150CT 9
MC1632B1125FEC 2 MC2040B1200RCT 9
MC2040B1150 5 7 MC2040B1200CT 9
Numbers 1 through 9 in these tables represent the last digit in each interlock kit catalog number. Example: 1 = ECSBPK01
When used in horizontal positions as typical in most load centers, ECSBPK07 is recommended for use only with QNR type circuit breakers.
Standby power interlock kits are not intended for use with AFCI, GFCI, 3-pole or 1/2” frame circuit breakers and 4 space, 125 amp load centers.
Siemens type EQ load centers using a “4-pole” main breaker do not have a kit available to interlock this main to branch circuits. Branch circuit positions can be interlocked.
Convert load centers or meter combinations into standby power panels
ES Series Load Centers can utilize interlock kits: 1, 2, 5, 6, 7. Kits 3 and 4 can also be used on main breaker panels.
PL Series Load Centers can utilize interlock kits: 1, 2, 3, 4, 5, 6, 7.
To activate standby power the utility main breaker must be in the “OFF” position to prevent dangerous feedback between the power sources.
Utility main breaker
Standby power main breaker
Standby Power SystemsManual Transfer Interlock Kits
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-20
Standby Power SystemsManual Transfer Interlock Kits
Prevents dangerous feedback between two sources of power
a Manual breaker interlock kits are attached to the break-ers not the trim of the load center.
b These kits take up 2 spaces adjacent to the 2 pole breaker being interlocked. Those spaces cannot accommodate filler plates.
Manual Transfer Interlock Kitsa
Catalognumber
UsageInformation
Utility mainbreaker types
Standby mainbreaker types
InterlockNumber
ECSBPK01 For use on load centers or meter combinations that will accept 2-pole circuit breakers oppositeone another as shown.
QP, QPH, HQPH QP, QPH, HQPH 1
ECSBPK02 For use on load centers or meter combinations that will accept 2- or 4-pole next to a 2-pole circuit breaker side by side as shown.
QP, QPH, HQPH QP, QPH, HQPH 2
ECSBPK03b For use on UltimateTM and RockSolid load centers, 150 amp andhigher, to connect the main breakerto a 2-pole circuit breaker.
MBK150A,MBK200A, OR MBK225A
QP, QPH, HQPH 3
ECSBPK04b For use on Ultimate and Rock Solidload centers, 125 amp and lower,to connect the main breaker to a 2-pole circuit breaker.
MBK100A orMBK125A
QP, QPH, HQPH 4
ECSBPK05 For use on load centers or meter meter combinations that will accept a QNR (MD-TR) frame circuit breaker next to a 2-pole circuit breaker as shown.
QNR, QNRH, HQNR QP, QPH, HQPH 5
ECSBPK06b For use on load centers or meter combinations that will accept a QN (MD-T) frame circuit breaker next to a 2-pole circuit breaker as shown.
QN, QNH, HQN QP, QPH, HQPH 6
ECSBPK07 For use on load centers or meter combinations that will accept two QNR (MD--TR) circuit breakers side by side as shown OR will accept two QN (MD--T) circuit breakers side by side as shown.
QNR, QNRH, HQNR, QN, QNH, HQN
QNR, QNRH, HQNR QN,QNH, HQN
7
ECSBPK08b For use on 8 space, over/under,OH/UG feed meter combinations as shown. Limited application to specific catalog numbers.
QPP, QPPH QP, QPH, HQPH 8
ECSBPK09b For use on 20 space, over/under, OH/UG feed meter combinations as shown. Limited application to specific catalog numbers.
QPP, QPPH QP, QPH, HQPH 9
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-21
Generator Ratings
kW Rating(LP/NG) Rated Amps
Engine RPM at full load
Natural gas fuelconsumption(ft^3/hr)
Liquid propane vapor consumptionN(gal/hr)
Propane vaporconsumptionft^3/ft
Sound level atnormal load
Sound levelat exercise
8/7 35 3600 118.9 1.47 51.4 62 N/A
11/10 50 3600 160.3 2.08 72.7 63 N/A
16/16 65 3600 312 3.57 130 66 60
20/18 90 3600 303.4 3.99 139.5 66 60
22/19.5 100 3600 281 3.68 127 67 58
for Btu content, multiply ft^3/hr x 2520 (LP) or ft^3/hr x 1000
AccessoriesCatalog No. Usage
5621 Auxiliary Transfer Switch Contact
GENPAINT Gray Touch Up Paint for 2007 units
GENPAINT2 Generator Spray Paint Gray Textured
GENSHELL2 Display Shell, gray color
7101 Battery Pad Warmer
7102 Oil Warmer
7103 Breather Box Warmer
68730Smart Management Module - load management system that operates autonomously
6424 Brown Out Kit
5928 Standard Wireless Remote in Home Monitor
GENCART
The Generator Transport Cart is designed to allow a single individual to move and position any of the air-cooled generators without the need for additional people or equipment. By attaching the cart to the generator through the lifting holes, the generator is lifted from the pallet by leverage and is easily wheeled to the appropriate location for final setting
5666
The pad skirt snaps together around the bottom of the new 20kW generators. This offers a sleek, contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base. Available in grey, the pad skirt fits 20kW generators manufactured after 4/2008.
6510E-stop allows for immediate fuel shutoff and generator shutdown in the event of an emergency.
Maintenance KitsJust like an engine in an automobile, generator engines require routine main-tenance. Service kits, which include oil and air filters, are available and are selected based on engine size. Touch up paint is also provided to help cover minor scratches.
Oil and Air Filter KitsASGE ASGN
Catalog No. Usage Catalog No. Usage
GENMKIT19 8 kW 410cc GENMKIT10 8 kW 410cc
GENMKIT20 11 kW 530cc GENMKIT2 10 kW 530cc
GENMKIT21 14,16 kW 992cc GENMKIT3 14, 17 kW 990cc
GENMKIT22 20, 22 kW 999cc GENMKIT11 20 kW 990cc
PORTMKIT1 Portable 15, 17.5 kW
PORTMKIT2 Portable 5, 6.5 kW
PORTMKIT3 Portable 8 kW
Cold Weather Kits
Generator Size (kW)
Cold Weather Kit Part no.
Extreme Cold Weather Kit Part No.
9 7101, 7102, 7103 n/a11 7101, 7102, 7103 n/a16 7101, 7102, 7103 n/a20 7101, 7102, 7103 n/a22 (Air Cooled) 7101, 7102, 7103 n/a22 (Liquid Cooled) 5630 561625 6175 617427 5630 561630 6175 617432 5630 561636 5630 561638 5630 561645 5630 561648 5632 620460 5630 561670 5632 562080 5632 7088
100 5633 5620130 5633 5620150 5632 5667
Extreme cold weather kit
Standby Power SystemsRatings / Maintenance Kits / Accessories / Cold Weather Kits
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-22
6463 – Mobile Link6478 – Liquid-Cooled Extension CableNote: this cable is required with Mobile Link for all liquid-cooled units.
Compatibility:Mobile Link is designed for use with a generator equipped with an LCD display. Mobile Link is compatible with most 2008-and-newer air-cooled standby generators and 2010-and-newer liquid-cooled standby generators.Note: Please ensure you have cellular service in your area before purchasing.
Email or Text Notifications:StandbyStatus.com provides over 40 different notifications, including successful exercise, maintenance reminders, change in status, low battery, fault alert and more:
n When maintenance is required or fault conditions occur, StanbyStatus.com automatically sends out alerts
n Dealer gets accurate data and can respond quickly and efficiently to problems
n Customers designate up to 4 different accounts to receive email and text notifications, including their dealer, so that they can discuss options with the customer to address the generator’s issues.
n Notifications drive regular, timely communication with the customer
StandbyStatus.com:StandbyStatus.com features a user-friendly dashboard that allows the customer to check their generator’s status anytime, anywhere:n View current generator status and upcoming maintenance needs
n Remotely set exercise schedule
n Review run and maintenance history
n Get local weather updates
n Change messaging settings
Mobile Link: Cellular remote monitoring system for your generator
How does it work?
Standby Power SystemsCellular Monitor
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-23
All the conveniences of modern living—heat, central air, refrigeration, communication—are nothing without power. When the power supply is disrupted, our lives and businesses can come to a sudden halt. An automatic standby generator protects you from power failures, restoring power within seconds of an outage, so you can have peace of mind and the power you need.
Siemens’ new Protector™ Series diesel generators raise the bar for residential and light commercial diesel generators. Building and zoning codes can vary wildly from one region to another. In the past, the only answer was to order expensive, custom-configured solutions.
Protector™ Series Automatic Standby Diesel Generator
Until now.
Siemens’ diesel-powered Protector Series features Code Ready, a set of popular preconfigured options and a range of code-driven accessories, so you can feel confident that your generator will be able to conform to the required local codes. The Protector Series is versatile, adaptable, meets UL requirements, and is an affordable optional standby diesel generator for your backup power needs.
Standby Power SystemsDiesel Generators
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-24
Diesel Generator Specifications
15 kW 20 kW 30 kW 48 / 50 kWCatalog Number RD015 RD020 RD030 RD048* / RD050
Engine/Alternator RPM 1800/1800
Engine In-line 4-cylinder
Fuel Type Diesel
Output Voltage 120/240 V, 1Ø, 1.0 pf 62 83 125 200
Output Voltage 120/208 V, 3Ø, 0.8 pf 52 69 104 173
Output Voltage 120/240 V, 3Ø, 0.8 pf 45 60 90 150
Output Voltage 277/480 V, 3Ø, 0.8 pf n/a n/a 45 75
Fuel Consumption @ 1/2 load - gal/hr (L/hr) 0.79 (2.99) 1.05 (3.97) 1.45 (5.5) 2.3 (8.71)
Fuel Consumption @ full load - gal/hr (L/hr) 1.48 (5.58) 1.98 (7.48) 2.74 (10.4) 4.3 (16.36)
Quiet-Test Mode Yes
db(A) at exercise 65
db(A) at normal operating load 70
Enclosure Steel
Enclosure Color Gray
Warranty 5-year limited
Dimensions (L” x W” x H”) 49.4 x 80.8 x 30.55 55.4 x 95.4 x 35
Weight (lbs.) 1474 1574 1755 2114
EPA Emission Regulations Yes
*1Ø only
Diesel Generators:Siemens diesel generators are fully configured and tested. A fully configured diesel generator means you receive the generator and the fuel tank together. Our generators are prototyped tested, system torsional tested, NEMA MG1-22 evaluation, and motor starting ability tested. The prototype testing includes total commitment to component testing, reli-ability testing, environmental testing, destruction and life test-ing, plus testing to applicable CSA, NEMA, EGSA, and other standers. All models also come standard with a state of the art power maximizing regulation system. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque matching the surge loads to the engine and digital regulated
the voltage at +-1%. All this allows you to choose a Siemens diesel generator with confidence that these systems will pro-vide superior performance.
If you need assistance in ordering your diesel system please see our preorder check list and easy order selection guide on pages 7 and 8.
If you have any further questions please reference page 9 to contact our Siemens Tech Support line/email box that is dedi-cated for generators.
Standby Power SystemsProtector™ Series Automatic Standby Diesel Generators 15 - 50 kW
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-25
Diesel Generator Catalog Logic
Catalog No.
Catalog logic Generator information
Diesel
kW Size015 = 15kW020 = 20kW030 = 30kW048 = 48kW050 = 50kW
Engine Size in Liters23 = 2.3L24 = 2.4L34 = 3.4L
Voltage & PhaseADAE = 120/240V, 1ØGDAE = 120/208V, 3ØJDAE = 120/240V, 3ØKDAE = 277/480V, 3Ø Enclosure Speed
Weight (lbs.) Dimensions (in.)
db(A) at exercise / full load
RD01523ADAE RD 015 23L ADAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70
RD01523GDAE RD 015 23L GDAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70
RD01523JDAE RD 015 23L JDAE Aluminum 1800 RPM 1,474 49.4 x 80.8 x 30.55 65 / 70
RD02023ADAE RD 020 23L ADAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70
RD02023GDAE RD 020 23L GDAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70
RD02023JDAE RD 020 23L JDAE Aluminum 1800 RPM 1,574 49.4 x 80.8 x 30.55 65 / 70
RD03024ADAE RD 030 24L ADAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70
RD03024GDAE RD 030 24L GDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70
RD03024JDAE RD 030 24L JDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70
RD03024KDAE RD 030 24L KDAE Aluminum 1800 RPM 1,755 55.4 x 95.4 x 35 65 / 70
RD04834ADAE RD 048 34L ADAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70
RD05034GDAE RD 050 34L GDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70
RD05034JDAE RD 050 34L JDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70
RD05034KDAE RD 050 34L KDAE Aluminum 1800 RPM 2,114 55.4 x 95.4 x 35 65 / 70
Featuresn Two line LCD multilingual digital Evolution
Controller (English, Spanish, French, Portuguese) with external viewing window for easy indication of generator status and breaker position.
n Isochronous Electronic Governor
n Sound Attenuated Enclosure
n Smart Battery Charger
n UV/Ozone Resistant Hoses
n +-1 % Voltage Regulation
n Integrated Base Tank provides 24 hour run time minimum at ½ load
n UL/CUL2200/UL 142 Listed
n Meets code requirements for External Vent and Fill
Please read all additional information located in the following pages before purchasing a diesel generator.
Standby Power SystemsProtector™ Series Automatic Standby Diesel Generators 15 - 50 kW
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-26
SM & SL Type Transfer SwitchesTransfer switches provide the mechanism for transferring power between utility and generator service. Engineered with Digital Power Management (DPM) technology. 100-400A single phase SM & SL type transfer switches have the ability to cycle on and off 2 air conditioners without adding additional components, allowing for a smaller generator to cover more circuits than when paired with a standard transfer switch. Diesel units are compatible with the same transfer switches as natural gas/propane units.
SM and SL Transfer Switches
Catalog Number Amp
KA rating (Amp) Weight (lbs.) Dimensions (in.)
Disconnect included
Single PhaseSM100R 100 10,000 20 20 x 14.6 x 7.09 NoSM100RD 100 10,000 23 20 x 14.6 x 7.09 YesSM150RD 150 10,000 39 30 x 13.5 x 6.3 YesSM200R 200 10,000 20 20 x 14.6 x 7.09 NoSM200RD 200 10,000 39 30 x 13.5 x 6.3 YesSM300RD 300 22,000 145 48 x 21.82 x 10.06 YesSM400R 400 22,000 141 36 x 24 x 10.6 NoSM400RD 400 22,000 145 48 x 21.82 x 10.06 Yes
Three PhaseSL100C 100 10,000 65 24.1 x 20.2 x 7.1 NoSL100J 100 14,000 57 24.1 x 20.2 x 7.1 NoSL100I 100 14,000 135 36.1 x 24 x 10 NoSL200C 200 10,000 48 24.1 x 20.2 x 7.0 NoSL200J 200 25,000 65 24.1 x 20.2 x 7.0 NoSL200I 200 25,000 105 48.1 x 30.1 x 13.1 NoSL400C 400 18,000 160 36.1 x 24 x 10 NoSL400J 400 18,000 133 36.1 x 24 x 10 NoSL400I 400 18,000 133 48.1 x 30.1 x 13.1 NoSL600R 600 42,000 439 66 x 36 x 21 NoSL600C 600 42,000 439 66 x 36 x 21 NoSL600J 600 42,000 439 66 x 36 x 21 NoSL600I 600 42,000 439 66 x 36 x 21 NoSL800R 800 65,000 469 66 x 36 x 21 NoSL800C 800 65,000 469 66 x 36 x 21 NoSL800J 800 65,000 469 66 x 36 x 21 NoSL800I 800 65,000 469 66 x 36 x 21 No
Featuresn 100 – 800A
n Outdoor NEMA 3R AL enclosure
n Open transition
n Compatible with Evolution and Nexus controllers
n Cover more circuits with a smaller generator
n Service rated and non-service rated
n Add additional individual SMM Modules (68730) and manage up to 4 additional large loads on a single SM transfer switch
n Cover every circuit when paired with a higher kW generator
Transfer SwitchesSM Type Single Phase and SL Type Three-Phase
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-27
Diesel Generator Accessories
Model # Product Description
6502 Spill Box The 5-gallon spill box screws into the existing fuel fill port of the base tank. It captures and contains fuel if over fueling or spilling occurs during the fill process.
6504 90% Fuel Level Alarm The 90% fuel level alarm alerts the fuel fill operator when the tank reaches a 90% fill level by sounding an audible alarm and triggering an LED warning light.
6505 – 15 & 20 kW6506 – 30 & 50 kW Tank Risers Tank risers are required in some municipalities to help avoid potential base tank
corrosion caused by mounting on rough surfaces.
6507 Fuel Fill Drop Tube
A powder coat painted, steel fuel fill drop tube is required in some municipalities to prevent sparking due to static electricity buildup, which can be caused by the fuel dropping into the tank from the fill area. Using a drop tube also results in submerged filling, which increases the fuel delivery flow rate and reduces vapors, foam and potential tank evaporation.
6513 – 15 & 20 kW6517 – 30 kW6516 – 50 kW
Stainless Steel Fuel LinesSome municipalities require the use of stainless steel fuel lines instead of the standard hoses provided with the diesel generator products. These stainless steel lines are fire resistant for additional safety.
6510 E-Stop E-stop allows for immediate fuel shutoff and generator shutdown in the event of and emergency.
6511 Spill Box Drainback Kit The spill box drainback kit allows fuel that was captured in the 5-gallon spill box to be drained directly back into the fuel tank to avoid vapors.
6512 Lockable Fuel Cap The cast iron, lockable fuel cap provides the ability to lock the fuel system to prevent unwanted fuel tampering or fuel siphoning.
6572 – 15 & 20 kW6571 – 30 kW 6570 – 50 kW
Maintenance Kits The Protector Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac Protector generators.
6560 – 15 & 20 kW6559 – 30 kW6558 – 50 kW
Cold Weather KitsRecommended for generators installed in regions where the temperature regularly falls below 32 °F (0 °C). The Cold Weather Kits consist of a block heater with all necessary mounting hardware and a battery warmer with a thermostat built into the battery wrap.
6576 Fuel Maintenance Kit The Fuel Maintenance Kit contains everything needed to maintain and clean a diesel fuel system.
5704 Paint KitIf the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure.
5928 Basic Wireless Remote Completely wireless and battery powered, Generac’s wireless remote monitor provides you with instant status information without ever leaving the house.
5951 Advanced Wireless Remote Remotely control generator functions with the advanced model’s LCD display. In addition to remote testing of the generator, set the exercise cycle and maintenance interval reminders.
6199 PMM Starter Kit
The PMM Starter Kit consists of a 24 VAC, field installed transformer that enables the use of the 24 VAC Power Management Modules (PMMs) and one PMM. The standard controller (without starter kit) can control two HVAC loads with no additional hardware. Not compatible with pre-wired switches.
6186 Power Management Module (50 Amps)
Power Management Modules are used in conjunction with the Smart Switch to increase its power management capabilities. It gives the Smart Switch additional power management flexibility not found in any other transfer switch. Not compatible with pre-wired switches. Note: PMM Starter Kit required.
6588 Vent Extension Support Kit
The Vent extension support kit consists of 2 aluminum plates with the appropriate pipe cutouts to secure the bent extension pipes coming through the top of the generatorenclosure. It helps to minimize stress on the NPT fittings integrated on the tank and also helps protect against pests.
6463 Mobile Link Mobile Link is designed for use with a generator equipped with an LCD display. Mobile Link sends status updates to StandbyStatus.com.
6478 Extension Cable An extension cable to connect Mobile Link to the Diesel Generators.
Standby Power SystemsAccessories for 15, 20, 30, 48, 50 kW Diesel Generators
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-28
Pre-order checklist
Item Description Catalog no. Required
Emergency Stop Switch 6510 Yes No
90% Fuel Level Alarm 6504 Yes No
Five Gallon Spill Box 6502 Yes No
Spill Box Drain Back 6511 Yes No
Anti-Static Fuel Fill Tube 6507 Yes No
Fuel Tank Support Risers6505 (15 & 20 kW)6506 (30 & 50 kW)
Yes No
Stainless Steel Fuel Lines6513 (15 & 20 kW)6517 (30 kW)6516 (50 kW)
Yes No
The local fire marshal has confirmed that the generator must be located a minimum of ________ feet from a house or other structure.
NOTE: A minimum clearance of five feet is recommended.
The local AHJ has advised me regarding the requirements for electrical and/or building permits, as well as those regulations relating to emissions and fuel storage.
I have been advised of the local requirements for construction of a concrete base pad, and whether anchoring requirements are needed for installation on a flood plain.
I have confirmed with the appropriate authorities that the generator must be located a minimum of ________ feet from a property line.
I have been advised whether the local fire marshal (or other third party) is required to be present at start up.
I have confirmed that the installation site is applicable to optional standby only and does not require an NFPA 110 capable generator.
The local fire marshal has confirmed that I am required to extend the fuel tank vents ________ feet above the surrounding grade.
The local fire marshal has confirmed that local codes require installation of the diesel product safety accessories designated below.
Standby Power SystemsDiesel Generators
18
STAN
DB
Y G
ENERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 18-29
Easy Order Selection Guide
To determine the correct product codes for a diesel generator and transfer switch follow the steps below. A product code is required to order. To place an order, e-mail or fax the product
Transfer Switches Selection GuideStep 1 Step 2 Step 3 Step 4
Selection Criteria Transfer Switch used with Generator ControllerSL = 3 PhaseSM = 1 Phase
Amp Ratinge.g. (200 Amp = 200)
VoltageR = 120/208V, 1 ØC = 120/208V, 3 ØJ = 120/240V, 3 ØI = 277/480V, 3 Ø
Service Disconnect Rated*Blank = NoD = Yes
For Standby Generators 8 - 150 kW
SL 100, 150, 200, 300, 400, 600, 800
R, C, J, I D
Product Number (Enter on Order Form)
NOTE: There are no returns, changes or cancellations on Siemens DIESEL orders.This equipment is built -to-order once payment is received.
* Service rated switches only available for single phase units, with the exception of 100 and 200 amp options that will remain Generac branded - these can be found in the table on page 18-15.
Diesel Generator Selection GuideStep 1 Step 2 Step 3 Step 4 Step 5 Step 6
All diesel product codes begin with RD
kW Ratings e.g. (15 kW = 015)
Engine e.g. (2.3L = 23)
VoltageA = 120/240 1ØG = 120/208 3ØJ = 120/240 3ØK = 277/480 3Ø
Fuel D = Diesel
Enclosure A = Aluminum
Tank E = Extended Tank
015020030048*050*
2.3L @1800 RPM2.3L @ 1800 RPM2.4L @ 1800 RPM3.4L @ 1800 RPM3.4L @ 1800 RPM
A, G, JA, G, J
A, G, J, KA*, G, J, KA, G, J, K
DDDDD
AAAAA
EEEEE
Product Number (Enter on Order Form)* = 48kW in single phase configuration only. 50kW in three phase configuation only.
codes to your inside sales representative or place your order online. If you have questions, call 1-888-Generac. Freight is FOB factory. Charges will be determined at the time of order.
Standby Power SystemsDiesel Product - U.S. and Canada
R D 0 3 0 2 4 G D S E
R D
S M 2 0 0 R DSample
Sample
18
STA
ND
BY
GEN
ERA
TORS
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog18-30
Additional Information
n These units are not available with ALL enclosures.
n MUST USE A CERTIFIED GENERAC WARRANTY DEALER TO DO ANY AND ALL WARRANTY WORK ON THESE UNITS. A technician will be required to go through certification training prior to being able to file a warranty claim for diesel product.
n This product is currently NOT compatible with Mobile Link™.
n Extended warranties are currently NOT available for these units.
n These units will not ship with a battery. Battery requirements are Group 27F, 700 CCA for 15kW – 50kW.
n If you must connect your diesel generator to a day tank it is possible. THIS WILL VOID YOUR WARRANTY and Generac will not support the connection to a day tank.
n These are standby only, and will not have a limited prime rating.
n These units are NOT LIFE SAFETY RATED.
n These units CANNOT run on heating oil.
n MUST GET LOCAL FIRE MARSHAL’S APPROVAL BEFORE INSTALLATION. Fire Marshal is required for Diesel generator installations with tanks. Diesel cannot be added to the tank without approval and or witness by the fire marshal. It is also important to check with all other local, regional, and/or state codes that are required for installation. If diesel is added to the tank without the proper authority’s approval, the unit can be flagged for hazardous material. This will result in an expensive removal process that the customer will be responsible for.
n NON RETURNABLE.
n Compatible with single and three phase SL and SM series automatic transfer switches.
n Cold weather kits are necessary when the temp regularly falls below 32°F.
Standby Power SystemsDiesel Generators