    Appendix A

    Standard Penetration Test (SPT)

  • 7/25/2019 Standard Penetration Test.pdf

    2/13

    ii

    Standard Penetration Test (SPT)

    "SPT" is an abbreviation for the Standard Penetration Test, which is the most widely used

    in-situ soil characterization test in the world. Colonel Charles Gow of the Raymond Pile

    Company 02 first introduced this testing procedure in 1902.The purpose of this test is to

    obtain an indication of the relative density of sands and gravels. However it can also used

    to obtain an indication of the character of silts, clays and weak rock. The testing

    procedure was later modified to include the estimation of soil strength parameters and

    soil compressibility parameters.The popularity of the Standard Penetration Test can be

    attributed to both the ease of the test as well as the inexpensive cost. The continued

    popularity of the SPT is due to the many design correlations associated with the SPT - N

    value. Engineering applications of SPT results include: determination of settlement of

    granular soils, estimation of liquefaction potential, compaction control and bearing

    capacity of piles.

    The SPT equipment (ASTM D1586, Eurocode 7) comprises a split tube (sampler) with a

    driving head to recover disturbed soil samples. A split spoon sampler with two halves

    opened is shown in Figure A1.

    Figure A1. Split spoon sampler.

  • 7/25/2019 Standard Penetration Test.pdf

    3/13

    iii

    The head of the tube is threaded for connection (via a series of drive rods) to a hammer.

    The device is driven into the ground at the base of the borehole with a free falling 63.5 kg

    hammer dropping a distance of 760 mm. The standard is much less specific about the

    required design of the SPT hammer, stating only that the hammer must have a mass of

    140 lbs (63.5 kg) and must drop vertically as freely as possible through 30" (0.76 m)

    before hitting the anvil. As a result, different hammer designs have evolved and they vary

    considerably. The most commonly used hammer types in North America are the donut,

    safety and automatic hammers, as shown in the Figure A2.

    Figure A2. Different SPT hammer configurations

    The SPT test involves driving the split spoon sampler into the bottom of a borehole. The

    total blows required from a hammer, over the interval 150 to 450 mm (6 to 18 inches) aresummed to give the blow count N. A typical components of a SPT set up is shown in the

    Figure A3.

  • 7/25/2019 Standard Penetration Test.pdf

    4/13

    iv

    Figure A3. Typical SPT set up

    Correction of the Field SPT N

    The quality of test results depends on several factors, such as actual energy delivered to

    the head of the drill rod, the dynamic properties (impedance) of the drill rod, the method

    of drilling and borehole stabilisation. The actually delivered energy can vary between 50

    - 80% of the theoretical free-fall energy. The SPT can be difficult to perform in loose

    sands and silts below the ground water level (typical for land reclamation projects), as the

    borehole can collapse and disturb the soil to be tested. The following factors can affect

    the test results: nature of the drilling fluid in the borehole, diameter of the borehole, the

    configuration of the sampling spoon and the frequency of delivery of the hammer blows.

    Therefore, it should be noted that drilling and stabilization of the borehole must be

    carried out with care. The measured N-value (blows/0.3 m) is the so-called standard

    penetration resistance of the soil. The penetration resistance is influenced by the stress

    conditions at the depth of the test. Peck et al. (1974) proposed, based on settlement

  • 7/25/2019 Standard Penetration Test.pdf

    5/13

    v

    observations of footings, the following relationship for correction of confinement

    pressure. The measured N-value is to be multiplied by a correction factor CNto obtain a

    reference value, NCorrected, corresponding to an effective overburden stress of 1 t/ft2

    (approximately 107 kPa),

    NCorrected= NField.CN

    where CNis a stress correction factor and p' is the effective vertical overburden pressure

    at the test level.

    CN= 0.77.log10(20/p')

    A chart to obtain the correction factor CNis given in Figure A4.

    There is a correlation developed, as shown in Figure A5, to obtain strength parameters

    from the SPT value after application of the Peck correction for sandy soils.

    Figure A4. Chart to obtain the overburden correction factor as suggested by Peck et al.(1974)

  • 7/25/2019 Standard Penetration Test.pdf

    6/13

    vi

    Figure A5

    Chart to obtain angle of internal friction from the corrected SPT N value for

    sandy soils.

    Uncertainty In The Performance Of The Spt

    There is a large number of uncertainties involved in the performance of SPT

    Unfortunately most ofthese sources have not been sufficiently quantified. Table 1

    summarizes a total of 27 sources of uncertainty and bias,classified in five categories.This

    classification aims to assist the practicing personal in taking the necessary measures to

    minimize the uncertainties in the performance of the test:

    Category A includes sources that depend on the type of soil, with emphasis in sources

    related to granular materials since the use of the SPT is generally not recommended for

    cohesive soils.

    For example: Vertical stress, Mineralogy, Coarse gravel and cobbles in soil, horizontal

    stress and geologically aged deposits.

    Category Blists sources of uncertainty due to the presence of water.

    For example Pore pressure generation, and moisture sensitive behavior of geologically

    aged sand.

    Category Cincludes reducible sources related to the equipment and its maintenance.

  • 7/25/2019 Standard Penetration Test.pdf

    7/13

    vii

    For example hammer efficiency, borhole diameter, rod length, sampler, Lack of hammer

    free fall because of ungreased sheaves, new stiff rope for lifting weight, Use of bent drill

    rods etc.

    Category D includes sources that are reducible if the test procedure is performed

    carefully.

    For example Inadequate cleaning of hole, Inadequate head of water in the borehole,

    Careless measurement of hammer drop, Sampler driven above bottom of casing, More

    than two turns on cathead, Hammer strikes drill rod collar eccentrically, Incomplete

    release of rope in each drop, and Careless blow count.

    Category Elists irreducible sources in the inves-tigation procedure.

    For example Human factor, and Weather and site conditions.

    Energy Correction method for SPT N value

    Different researchers tried to correct the field SPT N values due to the errors due to

    reducible sources related to the equipment and its maintenance. In this method of the SPT

    correction, following corrections are applied.

    Overburden correction

    Overburden correction factor, CN, is obtained by the following expression.

    /

    76.95

    o

    Np

    C

    Where Po/is the effective overburden pressure in kPa.

    Energy correction factor (1)

    Several investigators have measured the hammer energy in various SPT systems and

    found considerable variability. Some investigations showed experimentally that the

    measured blow count was inversely proportional to the energy delivered to the drill rods

    for blow counts less than 50. Because of the variable energy input from different SPT

    hammer/rod systems, it was suggested that measured blow counts (N-value) be corrected

  • 7/25/2019 Standard Penetration Test.pdf

    8/13

    viii

    to reference value of 70% of the potential energy of the SPT hammer. The 70% reference

    energy was adopted because energy measurements carried out on different hammer

    configurations have indicated an average of about 70% of the theoretical potential energy

    of the SPT

    If the energy ratio of the SPT set up used is Erthen,

    701

    rE

    Similarly, other correction factors due to the rod length, sampler, and borehole diameter

    2, 2, and 3respectively can be obtained from Figure A6.

    Figure A6. SPT correction factors

  • 7/25/2019 Standard Penetration Test.pdf

    9/13

    ix

    The corrected SPT N value is referred to as N70/since the energy ratio is converted to that

    corresponding to 70%.

    4321

    /

    70 NCN

    N70/can be used to obtain the strength parameters from Figures A7

    Figure A7Strength parameters from the N70/from the SPT.

  • 7/25/2019 Standard Penetration Test.pdf

    10/13

    x

    Example A.1Five boreholes are driven in a proposed building site to investigate the subsurface

    condition for a 20-storey building. The subsurface at the site consists of loose silty sand,stiff clay, completely weathered rock, and fractured rock. A typical subsurface condition

    in a borehole together with the SPT blow counts and rock properties are given in the

    following Figure.If the SPT setup used has an energy ratio of 60% and the borehole diameter is 75 mm,estimate the soil strength parameters upto the weathered rock layer. (Assume weathered

    rock layer consists of coarse grained soil and noliner is used in the SPT sampler).

    Loose silty sand

    Stiff clay

    Completely weathered rock

    (Coarse sand)

    Fractured rock

    0.00

    5.00

    12.00

    17.00

    Depth (m) SPT

    1.0

    6.0

    2.0

    3.0

    5.0

    4.0

    7.0

    8.0

    9.0

    10.0

    11.0

    12.0

    3

    13.0

    14.0

    15.0

    16.0

    17.0

    4

    12

    4

    16

    14

    5

    12

    14

    17

    15

    40

    42

    40

    > 50

    > 50

    > 50

    1.00W. T

  • 7/25/2019 Standard Penetration Test.pdf

    11/13

    xi

    Answer

    Depth

    (m)

    P/o(kPa) CN 1 2 3 4 N/70 c

    (kPa)

    1 16.0 2.4 0.79 0.75 1 1 6 30

    2 22.2 2.1 0.79 0.75 1 1 5 303 28.4 1.8 0.79 0.85 1 1 5 30

    4 34.6 1.7 0.79 0.95 1 1 6 30

    5 41.8 1.5 0.79 0.95 1 1 14 83

    6 49.0 1.4 0.79 0.95 1 1 13 75

    7 56.1 1.3 0.79 0.95 1 1 14 83

    8 63.3 1.2 0.79 0.95 1 1 15 92

    9 70.5 1.2 0.79 1 1 1 14 83

    10 77.7 1.1 0.79 1 1 1 15 92

    11 84.9 1.1 0.79 1 1 1 12 67

    12 93.1 1.0 0.79 1 1 1 32 43

    13 101.3 1.0 0.79 1 1 1 32 4314 109.5 0.9 0.79 1 1 1 29 42

    15 117.7 0.9 0.79 1 1 1

    16 125.9 0.9 0.79 1 1 1

    17 134.0 0.8 0.79 1 1 1

    Example A2

    The subsurface condition at a building site consists of a 3m thick fine sand layer

    underlain by a 5m thick normally consolidated clay layer followed by a hard weatheredrock layer. The subsurface condition and the SPT blow counts obtained from the site

    investigation program are given in Figure A2. Water table is located at 2.0m below the

    ground surface.

    Estimate the soil strength parameters of the subsurface using the energy method.

    (Assume an energy ratio of 55%, borehole diameter of 90mm and noliner)

    /

    76.95

    oN P

    C

    WherePo

    / = Effective overburden pressure in kPa.

  • 7/25/2019 Standard Penetration Test.pdf

    12/13

    xii

    Figure A2

    Answer

    Depth (m) SPT (N) P/o(kPa) N2 N/70 / C (kPa)

    1 4 15.5 0.75 6 30

    2 3 31 0.75 3 283 5 37.7 0.85 5 29

    4 3 43.9 0.85 3 12.5

    5 4 50.1 0.95 4 18

    6 3 52.3 0.95 3 12.5

    7 3 62.5 0.95 3 12.5

    8 20 68.6 0.95 17 36

    9 22 75.3 1 19 37

    10 24 80 1 20 38

    12 28 95.4 1 22 39

    13 25 102.1 1 19 37

    14 50 108.8 1 36 45

    De th SPT1

    2

    3

    6

    Fine sand layer with wet= 15.5 kN/m3

    4

    5

    14

    13

    7

    8

    9

    10

    12

    3

    5

    3

    4

    4

    sat= 16.5 kN/m

    3

    3

    3

    20

    50